NFPA72 _ Orange Deck _ ANNUAL FIRE INSPECTION.pdf
PDF 444 KB Posted
- Attached to
- Fire Alarm Removal and Replacement
- Solicitation number
- PE-92200-RFP-2026-000000061
- Issued by
- Fulton County, Georgia
About this file
This is an NFPA 72 Annual Fire Inspection and Testing Certificate for the Georgia World Congress Center's Orange Deck facility located at 285 Andrew Young International Blvd NW, Atlanta, Georgia. The inspection and testing was conducted in compliance with NFPA 72 standards for fire alarm and signaling systems and was completed on December 12, 2024. The inspection was performed by Basesix Systems, with Christopher Kirkbride (NICET Certification #148593) serving as the testing technician, and accepted by Kevin Rutledge, the building representative at Georgia World Congress Center. The testing summary demonstrates comprehensive coverage with 16 emergency control equipment units, 1 fire control panel, 33 initiating devices (29 of which passed, representing 88% pass rate), and 9 power supply units (100% pass rate). The overall inspection status is marked as "Acceptable" with everything functioning properly.
The tested equipment includes multiple sealed lead-acid battery backup systems with 24-hour standby and 15-minute alarm capability, distributed across the main electrical room on the first floor and the electrical room on the fourth floor. System components include two Potter power supply units (PSN-106 models), a Notifier NFS 320 fire alarm control panel, 13 smoke detectors, 11 heat detectors, 9 manual fire boxes, and 16 elevator-related emergency control devices. One open corrective action remains unresolved regarding Network A&B trouble on the main fire alarm control panel identified on August 26, 2024, with the manufacturer (Notifier) noted as responsible for the proposed solution. Four previously identified corrective actions related to battery replacements in the fourth floor electrical room were resolved prior to the inspection, with batteries replaced using Power Patrol 12V 7AH units on February 23, 2025.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Inspection and Testing Certificate Presented To
Georgia World Congress Center
For
Orange Deck
285 Andrew Young International Blvd NW
Atlanta, Georgia 30313
United States
This site has been inspected and tested in compliance with applicable standards.
Completed Thursday, December 12, 2024
Test Session :ANNUAL FIRE INSPECTION 2024
ACCEPTED BY TESTED BY
Kevin Rutledge
Georgia World Congress Center
285 Andrew Young International Blvd NW Atlanta, Georgia 30313 United States
Christopher Kirkbride
Basesix Systems
2053 Franklin Way Marietta, GA 30067 United States
INSPECTION STATUS
Acceptable
Everything Looks Okay
Basesix Systems
Inspection Summary
Building Information
PROPERTY Orange Deck CONTACT Kevin Rutledge
ADDRESS 285 Andrew Young International Blvd NW
PHONE
CITY/STATE/ZIP Atlanta, Georgia 30313 MOBILE +1 404-392-7027
COUNTRY United States EMAIL krutledge@gwcc.com
Inspector Information
COMPANY Basesix Systems CONTACT Christopher Kirkbride
ADDRESS
2053 Franklin Way Marietta, GA 30067
LICENSE NUMBER Nicet Certification # 148593
PHONE +1 470-590-2691
COUNTRY United States EMAIL ckirkbride@basesix.com
Testing Summary
EQUIPMENT TYPE TOTAL TESTED PASSED FAILED
16 0(0%) 0(0%) 0(0%)
1 1(100%) 1(100%) 0(0%)
33 29(88%) 29(88%) 0(0%)
9 9(100%) 9(100%) 0(0%)
Certification The equipment specified herein was inspected and tested according to the NFPA 72 standard for fire alarm and signaling systems, with the inspection completed on Thursday, December 12, 2024
ACCEPTED BY 12/12/2024 TESTED BY 12/12/2024
Kevin Rutledge Christopher Kirkbride
Building Representative Technician
Emergency Control Equipment
Fire Control Panel
Initiating Device
Power Supplies
Page 2 of 13Page 2 of 13Basesix Systems
System Details
Control Units
DESCRIPTION PANELADDRESS / SCAN ADDRESS N0
S/W VERSIONMANUFACTURER
LAST UPDATEMODEL
S/W LOCATIONSERIAL NUMBER
INSTALL DATE 08/16/2023
Secondary Power TYPE Battery - Sealed Lead-acid DESCRIPTION In main electrical room 1st floor battery
ADDRESS / SCAN ADDRESS Main facp NOMINAL VOLTAGE
LOAD VOLTAGE AMP HOURS 12
STANDBY HOURS 24 ALARM MINUTES 15
BATTERY LOCATION In panel CHARGER VOLTAGE
TYPE Battery - Sealed Lead-acid DESCRIPTION Electrical room 401 4th floor battery 2
ADDRESS / SCAN ADDRESS NOMINAL VOLTAGE
LOAD VOLTAGE 12 AMP HOURS 7
STANDBY HOURS 24 ALARM MINUTES 15
BATTERY LOCATION In panel CHARGER VOLTAGE 27.2
TYPE Battery - Sealed Lead-acid DESCRIPTION In main electrical room 1st floor battery
ADDRESS / SCAN ADDRESS Main fcps NOMINAL VOLTAGE
LOAD VOLTAGE AMP HOURS 7
STANDBY HOURS 24 ALARM MINUTES 15
BATTERY LOCATION In panel CHARGER VOLTAGE
TYPE Battery - Sealed Lead-acid DESCRIPTION Electrical room 401 4th floor battery 1
ADDRESS / SCAN ADDRESS NOMINAL VOLTAGE 12
LOAD VOLTAGE 12 AMP HOURS 7
STANDBY HOURS 24 ALARM MINUTES 15
BATTERY LOCATION In panel CHARGER VOLTAGE 27.2
TYPE Battery - Sealed Lead-acid DESCRIPTION In main electrical room 1st floor battery
ADDRESS / SCAN ADDRESS Main facp NOMINAL VOLTAGE
LOAD VOLTAGE AMP HOURS 12
STANDBY HOURS 24 ALARM MINUTES 15
BATTERY LOCATION In panel CHARGER VOLTAGE
TYPE Battery - Sealed Lead-acid DESCRIPTION In main electrical room 1st floor battery
ADDRESS / SCAN ADDRESS Main fcps NOMINAL VOLTAGE
LOAD VOLTAGE AMP HOURS 7
STANDBY HOURS 24 ALARM MINUTES 15
BATTERY LOCATION In panel CHARGER VOLTAGE
Page 3 of 13Page 3 of 13Basesix Systems
Page 4 of 13Page 4 of 13Basesix Systems
Open Corrective Action & Solution Summary The following 1 corrective action(s) remain open following the system inspection, testing or maintenance activities
EQUIPMENT TYPE ADDRESS DESCRIPTION
FACP Main facp In main electrical room 1st floor
Created By: Kanen Watson
Creation Date: 08/26/2024
Corrective Action: Network A&B trouble on panel when we arrived
Proposed Solution:
Manufacturer: Notifier
Model: NFS 320
Page 5 of 13Page 5 of 13Basesix Systems
Resolved Corrective Action & Solution Summary The following 4 corrective action(s) were resolved during the system inspection, testing or maintenance activities
EQUIPMENT TYPE ADDRESS DESCRIPTION
Battery - Sealed Lead-acid Electrical room 401 4th floor battery 1
Created By: Christopher Kirkbride
Creation Date: 12/04/2023
Corrective Action: Battery has exceeded its service life
12v7ah
Resolution: Battery was replaced prior to inspection
Resolved By: Christopher Kirkbride
Resolved On: 02/23/2025
Manufacturer: Power patrol
Model: 12V 7AH
Created By: Kanen Watson
Creation Date: 08/26/2024
Corrective Action: Batteries are out of date
Resolution: Duplicate
Resolved By: Christopher Kirkbride
Resolved On: 02/23/2025
Manufacturer: Power patrol
Model: 12V 7AH
Battery - Sealed Lead-acid Electrical room 401 4th floor battery 2
Created By: Christopher Kirkbride
Creation Date: 12/04/2023
Corrective Action: Battery has exceeded service life
12v7ah
Resolution: Batteries were replaced prior to inspection
Resolved By: Christopher Kirkbride
Resolved On: 02/23/2025
Manufacturer: Power patrol
Model: 12V 7AH
Created By: Kanen Watson
Creation Date: 08/26/2024
Corrective Action: Batteries are out of date
Resolution: Duplicate
Resolved By: Christopher Kirkbride
Resolved On: 02/06/2025
Manufacturer: Power patrol
Model: 12V 7AH
Page 6 of 13Page 6 of 13Basesix Systems
Testing Details
Emergency Control Equipment
Skipped
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Elevator Shunt Trip N010 L01M053 ELEV 3 SHUNT Manual 2/23/2025 8:16:16 PM
Egress Elevator Status Indicator
N010 L01M054 ELEV 3 HAT Manual 2/23/2025 8:16:21 PM
Elevator Recall - Alternate N010 L01M055 ELEV 3 ALT Manual 2/23/2025 8:16:24 PM
Elevator Recall - Primary N010 L01M056 ELEV 3 PRI Manual 2/23/2025 8:16:31 PM
Elevator Shunt Trip N010 L01M057 ELEV 1 SHUNT Manual 2/23/2025 8:16:37 PM
Egress Elevator Status Indicator
N010 L01M058 ELEV 1 HAT Manual 2/23/2025 8:16:42 PM
Elevator Recall - Alternate N010 L01M059 ELEV 1 ALT Manual 2/23/2025 8:16:45 PM
Elevator Recall - Primary N010 L01M060 ELEV 1 PRI Manual 2/23/2025 8:16:48 PM
Elevator Recall - Primary N010 L01M061 ELEV 2 PRI Manual 2/23/2025 8:16:51 PM
Elevator Recall - Alternate N010 L01M062 ELEV 2 ALT Manual 2/23/2025 8:16:56 PM
Egress Elevator Status Indicator
N010 L01M063 ELEV 2 HAT Manual 2/23/2025 8:16:59 PM
Elevator Shunt Trip N010 L01M064 ELEV 2 SHUNT Manual 2/23/2025 8:17:02 PM
Elevator Recall - Primary N010 L01M065 ELEV 4 PRI Manual 2/23/2025 8:17:07 PM
Elevator Recall - Alternate N010 L01M066 ELEV 4 ALT Manual 2/23/2025 8:17:10 PM
Egress Elevator Status Indicator
N010 L01M067 ELEV 4 HAT Manual 2/23/2025 8:17:17 PM
Elevator Shunt Trip N010 L01M068 ELEV 4 SHUNT Manual 2/23/2025 8:17:20 PM
Fire Control Panel
Passed
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Fire Alarm Panel N000 N000 PANEL Manual 1/20/2025 8:52:47 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Initiating Device
Passed
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Smoke Detector - General N010 L01D012 ELEV 3/4 MACH RM Manual 1/20/2025 8:52:15 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Smoke Detector - General N010 L01D011 ELEV 1/2 MACH RM Manual 1/20/2025 8:52:17 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Manual Fire Box N010 L01M047 NORTH STAIR Manual 1/20/2025 8:52:19 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Manual Fire Box N010 L01M038 NORTH STAIR Manual 1/20/2025 8:52:21 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Smoke Detector - General N010 L01D003 SECTION A Manual 2/3/2025 9:46:10 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Page 7 of 13Page 7 of 13Basesix Systems
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Smoke Detector - General N010 L01D005 SECTION B Manual 2/3/2025 9:46:17 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Smoke Detector - General N010 L01D006 ELEC RM. 401 Manual 2/3/2025 9:46:18 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Smoke Detector - General N010 L01D004 SECTION A Manual 2/3/2025 9:46:21 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Smoke Detector - General N010 L01D001 ABOVE FACP MAIN ELEC Manual 2/23/2025 8:15:04 PM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Smoke Detector - General N010 L01D013 IDF ROOM 3rd FL Manual 2/23/2025 8:15:12 PM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Smoke Detector - General N010 L01D002 SECTION B Manual 2/23/2025 8:15:14 PM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Manual Fire Box N010 L01M017 NORTH STAIR Manual 2/23/2025 8:15:45 PM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Manual Fire Box N010 L01M022 SOUTH STAIR Manual 2/23/2025 8:15:47 PM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Manual Fire Box N010 L01M027 NORTH STAIR Manual 2/23/2025 8:15:51 PM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Manual Fire Box N010 L01M033 PULL STATION SOUTH Manual 2/23/2025 8:16:03 PM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Manual Fire Box N010 L01M043 SOUTH STAIR Manual 2/23/2025 8:16:05 PM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Manual Fire Box N010 L01M050 OUTSIDE NORTH STAIR Manual 2/23/2025 8:16:13 PM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Manual Fire Box N010 L01M070 SOUTH STAIR Manual 2/23/2025 8:17:27 PM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Heat Detector N010 L01M007 ELEV 3/4 LOBBY HEAT Manual 2/23/2025 8:17:40 PM
Visual Inspection Passed (Manual)
Heat Detector N010 L01M069 ELEV 1/2 LOBBY HEAT Manual 2/23/2025 8:17:45 PM
Visual Inspection Passed (Manual)
Heat Detector N010 L01M049 ELEV 3/4 LOBBY HEAT Manual 2/23/2025 8:17:49 PM
Visual Inspection Passed (Manual)
Heat Detector N010 L01M048 ELEV 3/4 LOBBY HEAT Manual 2/23/2025 8:17:56 PM
Visual Inspection Passed (Manual)
Heat Detector N010 L01M037 ELEV 3/4 LOBBY HEAT Manual 2/23/2025 8:18:00 PM
Visual Inspection Passed (Manual)
Heat Detector N010 L01M026 ELEV 3/4 LOBBY HEAT Manual 2/23/2025 8:18:04 PM
Visual Inspection Passed (Manual)
Heat Detector N010 L01M025 ELEV 1/2 LOBBY HEAT Manual 2/23/2025 8:18:09 PM
Visual Inspection Passed (Manual)
Page 8 of 13Page 8 of 13Basesix Systems
Heat Detector N010 L01M016 ELEV 3/4 LOBBY HEAT Manual 2/23/2025 8:18:13 PM
Visual Inspection Passed (Manual)
Heat Detector N010 L01M012 ELEV 3 AND 4 HEAT Manual 2/23/2025 8:18:18 PM
Visual Inspection Passed (Manual)
Heat Detector N010 L01M036 ELEV 1/2 LOBBY HEAT Manual 2/23/2025 8:19:27 PM
Visual Inspection Passed (Manual)
Heat Detector N010 L01M046 ELEV 1/2 LOBBY HEAT Manual 2/23/2025 8:19:34 PM
Visual Inspection Passed (Manual)
Skipped
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Smoke Detector - General N010 L01D010 ELEV 2 TOP OF SHAFT Manual 2/23/2025 8:15:07 PM
Smoke Detector - General N010 L01D007 ELEV 3 TOP OF SHAFT Manual 2/23/2025 8:15:21 PM
Smoke Detector - General N010 L01D008 ELEV 4 TOP OF SHAFT Manual 2/23/2025 8:15:23 PM
Smoke Detector - General N010 L01D009 ELEV 1 TOP OF SHAFT Manual 2/23/2025 8:15:27 PM
Power Supplies
Passed
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Battery - Sealed Lead-acid Main facp In main electrical room 1st floor battery
Manual 1/20/2025 8:51:34 AM
Manufacturer Power patrol
Model 12V12ah
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Minutes 15
Amp Hours 12
Battery Location In panel
Stand By Hours 24
Battery - Sealed Lead-acid Main facp In main electrical room 1st floor battery
Manual 1/20/2025 8:51:36 AM
Manufacturer Power patrol
Model 12V12ah
Visual Inspection Passed (Manual)
Functional Inspection Passed
Page 9 of 13Page 9 of 13Basesix Systems
Alarm Minutes 15
Amp Hours 12
Battery Location In panel
Stand By Hours 24
Battery - Sealed Lead-acid Main fcps In main electrical room 1st floor battery
Manual 1/20/2025 8:51:38 AM
Manufacturer Power patrol
Model 12V 7AH
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Minutes 15
Amp Hours 7
Battery Location In panel
Stand By Hours 24
Battery - Sealed Lead-acid Main fcps In main electrical room 1st floor battery
Manual 1/20/2025 8:51:39 AM
Manufacturer Power patrol
Model 12V 7AH
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Minutes 15
Amp Hours 7
Battery Location In panel
Stand By Hours 24
FCPS Main fcps In main electrical room 1st floor Manual 1/20/2025 8:51:41 AM
Manufacturer Potter
Page 10 of 13Page 10 of 13Basesix Systems
Model Psn-106
Visual Inspection Passed (Manual)
Functional Inspection Passed
FCPS Electrical room 401 4th floor Manual 1/20/2025 8:53:05 AM
Manufacturer Potter
Model Psn 106
Visual Inspection Passed (Manual)
Functional Inspection Passed
FACP Main facp In main electrical room 1st floor Manual 2/6/2025 9:39:35 AM
Manufacturer Notifier
Model NFS 320
Visual Inspection Passed (Manual)
Functional Inspection Passed
Battery - Sealed Lead-acid Electrical room 401 4th floor battery 2 Manual 2/23/2025 8:23:29 PM
Manufacturer Power patrol
Model 12V 7AH
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Minutes 15
Amp Hours 7
Battery Location In panel
Charger Voltage 27.2
Load Voltage 12
Stand By Hours 24
Battery - Sealed Lead-acid Electrical room 401 4th floor battery 1 Manual 2/23/2025 8:23:51 PM
Manufacturer Power patrol
Model 12V 7AH
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Minutes 15
Amp Hours 7
Battery Location In panel
Charger Voltage 27.2
Load Voltage 12
Nominal Voltage 12
Stand By Hours 24
Page 11 of 13Page 11 of 13Basesix Systems
Device/Equipment Details
Emergency Control Equipment
ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE
Elevator Shunt Trip
N010 L01M053 ELEV 3 SHUNT 07/31/2024
N010 L01M054 ELEV 3 HAT 07/31/2024
N010 L01M055 ELEV 3 ALT 07/31/2024
N010 L01M056 ELEV 3 PRI 07/31/2024
N010 L01M057 ELEV 1 SHUNT 07/31/2024
N010 L01M058 ELEV 1 HAT 07/31/2024
N010 L01M059 ELEV 1 ALT 07/31/2024
N010 L01M060 ELEV 1 PRI 07/31/2024
N010 L01M061 ELEV 2 PRI 07/31/2024
N010 L01M062 ELEV 2 ALT 07/31/2024
N010 L01M063 ELEV 2 HAT 07/31/2024
N010 L01M064 ELEV 2 SHUNT 07/31/2024
N010 L01M065 ELEV 4 PRI 07/31/2024
N010 L01M066 ELEV 4 ALT 07/31/2024
N010 L01M067 ELEV 4 HAT 07/31/2024
N010 L01M068 ELEV 4 SHUNT 07/31/2024
Fire Control Panel
ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE
Fire Alarm Panel
N000 N000 PANEL 08/17/2023
Initiating Device
ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE
Smoke Detector - General
N010 L01D001 ABOVE FACP MAIN ELEC 07/31/2024
N010 L01D002 SECTION B 07/31/2024
N010 L01D003 SECTION A 07/31/2024
N010 L01D004 SECTION A 07/31/2024
N010 L01D005 SECTION B 07/31/2024
N010 L01D006 ELEC RM. 401 07/31/2024
N010 L01D007 ELEV 3 TOP OF SHAFT 07/31/2024
N010 L01D008 ELEV 4 TOP OF SHAFT 07/31/2024
N010 L01D009 ELEV 1 TOP OF SHAFT 07/31/2024
N010 L01D010 ELEV 2 TOP OF SHAFT 07/31/2024
N010 L01D011 ELEV 1/2 MACH RM 07/31/2024
N010 L01D012 ELEV 3/4 MACH RM 07/31/2024
N010 L01D013 IDF ROOM 3rd FL 07/31/2024
Heat Detector
N010 L01M007 ELEV 3/4 LOBBY HEAT 07/31/2024
N010 L01M012 ELEV 3 AND 4 HEAT 07/31/2024
N010 L01M016 ELEV 3/4 LOBBY HEAT 07/31/2024
N010 L01M025 ELEV 1/2 LOBBY HEAT 07/31/2024
N010 L01M026 ELEV 3/4 LOBBY HEAT 07/31/2024
N010 L01M036 ELEV 1/2 LOBBY HEAT 07/31/2024
N010 L01M037 ELEV 3/4 LOBBY HEAT 07/31/2024
N010 L01M046 ELEV 1/2 LOBBY HEAT 07/31/2024
N010 L01M048 ELEV 3/4 LOBBY HEAT 07/31/2024
N010 L01M049 ELEV 3/4 LOBBY HEAT 07/31/2024
Page 12 of 13Page 12 of 13Basesix Systems
ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE
N010 L01M069 ELEV 1/2 LOBBY HEAT 07/31/2024
Manual Fire Box
N010 L01M017 NORTH STAIR 07/31/2024
N010 L01M022 SOUTH STAIR 07/31/2024
N010 L01M027 NORTH STAIR 07/31/2024
N010 L01M033 PULL STATION SOUTH 07/31/2024
N010 L01M038 NORTH STAIR 07/31/2024
N010 L01M043 SOUTH STAIR 07/31/2024
N010 L01M047 NORTH STAIR 07/31/2024
N010 L01M050 OUTSIDE NORTH STAIR 07/31/2024
N010 L01M070 SOUTH STAIR 07/31/2024
Power Supplies
ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE
FCPS
Electrical room 401 4th floor Potter Psn 106
Main fcps In main electrical room 1st floor Potter Psn-106
Battery - Sealed Lead-acid
Electrical room 401 4th floor battery 1
Power patrol 12V 7AH 12/01/2023
Electrical room 401 4th floor battery 2
Power patrol 12V 7AH 12/01/2023
Main facp In main electrical room 1st floor battery 1
Power patrol 12V12ah 09/20/2023
Main facp In main electrical room 1st floor battery 2
Power patrol 12V12ah 09/20/2023
Main fcps In main electrical room 1st floor battery 1
Power patrol 12V 7AH 09/20/2023
Main fcps In main electrical room 1st floor battery 2
Power patrol 12V 7AH 02/20/2020
FACP
Main facp In main electrical room 1st floor Notifier NFS 320
Page 13 of 13Page 13 of 13Basesix Systems