NFPA72 _ Orange Deck _ ANNUAL FIRE INSPECTION.pdf

PDF 444 KB Posted

Attached to
Fire Alarm Removal and Replacement
Solicitation number
PE-92200-RFP-2026-000000061
Issued by
Fulton County, Georgia

About this file

This is an NFPA 72 Annual Fire Inspection and Testing Certificate for the Georgia World Congress Center's Orange Deck facility located at 285 Andrew Young International Blvd NW, Atlanta, Georgia. The inspection and testing was conducted in compliance with NFPA 72 standards for fire alarm and signaling systems and was completed on December 12, 2024. The inspection was performed by Basesix Systems, with Christopher Kirkbride (NICET Certification #148593) serving as the testing technician, and accepted by Kevin Rutledge, the building representative at Georgia World Congress Center. The testing summary demonstrates comprehensive coverage with 16 emergency control equipment units, 1 fire control panel, 33 initiating devices (29 of which passed, representing 88% pass rate), and 9 power supply units (100% pass rate). The overall inspection status is marked as "Acceptable" with everything functioning properly.

The tested equipment includes multiple sealed lead-acid battery backup systems with 24-hour standby and 15-minute alarm capability, distributed across the main electrical room on the first floor and the electrical room on the fourth floor. System components include two Potter power supply units (PSN-106 models), a Notifier NFS 320 fire alarm control panel, 13 smoke detectors, 11 heat detectors, 9 manual fire boxes, and 16 elevator-related emergency control devices. One open corrective action remains unresolved regarding Network A&B trouble on the main fire alarm control panel identified on August 26, 2024, with the manufacturer (Notifier) noted as responsible for the proposed solution. Four previously identified corrective actions related to battery replacements in the fourth floor electrical room were resolved prior to the inspection, with batteries replaced using Power Patrol 12V 7AH units on February 23, 2025.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Inspection and Testing Certificate Presented To

Georgia World Congress Center

For

Orange Deck

285 Andrew Young International Blvd NW

Atlanta, Georgia 30313

United States

This site has been inspected and tested in compliance with applicable standards.

Completed Thursday, December 12, 2024

Test Session :ANNUAL FIRE INSPECTION 2024

ACCEPTED BY TESTED BY

Kevin Rutledge

Georgia World Congress Center

285 Andrew Young International Blvd NW Atlanta, Georgia 30313 United States

Christopher Kirkbride

Basesix Systems

2053 Franklin Way Marietta, GA 30067 United States

INSPECTION STATUS

Acceptable

Everything Looks Okay

Basesix Systems

Inspection Summary

Building Information

PROPERTY Orange Deck CONTACT Kevin Rutledge

ADDRESS 285 Andrew Young International Blvd NW

PHONE

CITY/STATE/ZIP Atlanta, Georgia 30313 MOBILE +1 404-392-7027

COUNTRY United States EMAIL krutledge@gwcc.com

Inspector Information

COMPANY Basesix Systems CONTACT Christopher Kirkbride

ADDRESS

2053 Franklin Way Marietta, GA 30067

LICENSE NUMBER Nicet Certification # 148593

PHONE +1 470-590-2691

COUNTRY United States EMAIL ckirkbride@basesix.com

Testing Summary

EQUIPMENT TYPE TOTAL TESTED PASSED FAILED

16 0(0%) 0(0%) 0(0%)

1 1(100%) 1(100%) 0(0%)

33 29(88%) 29(88%) 0(0%)

9 9(100%) 9(100%) 0(0%)

Certification The equipment specified herein was inspected and tested according to the NFPA 72 standard for fire alarm and signaling systems, with the inspection completed on Thursday, December 12, 2024

ACCEPTED BY 12/12/2024 TESTED BY 12/12/2024

Kevin Rutledge Christopher Kirkbride

Building Representative Technician

Emergency Control Equipment

Fire Control Panel

Initiating Device

Power Supplies

Page 2 of 13Page 2 of 13Basesix Systems

System Details

Control Units

DESCRIPTION PANELADDRESS / SCAN ADDRESS N0

S/W VERSIONMANUFACTURER

LAST UPDATEMODEL

S/W LOCATIONSERIAL NUMBER

INSTALL DATE 08/16/2023

Secondary Power TYPE Battery - Sealed Lead-acid DESCRIPTION In main electrical room 1st floor battery

ADDRESS / SCAN ADDRESS Main facp NOMINAL VOLTAGE

LOAD VOLTAGE AMP HOURS 12

STANDBY HOURS 24 ALARM MINUTES 15

BATTERY LOCATION In panel CHARGER VOLTAGE

TYPE Battery - Sealed Lead-acid DESCRIPTION Electrical room 401 4th floor battery 2

ADDRESS / SCAN ADDRESS NOMINAL VOLTAGE

LOAD VOLTAGE 12 AMP HOURS 7

STANDBY HOURS 24 ALARM MINUTES 15

BATTERY LOCATION In panel CHARGER VOLTAGE 27.2

TYPE Battery - Sealed Lead-acid DESCRIPTION In main electrical room 1st floor battery

ADDRESS / SCAN ADDRESS Main fcps NOMINAL VOLTAGE

LOAD VOLTAGE AMP HOURS 7

STANDBY HOURS 24 ALARM MINUTES 15

BATTERY LOCATION In panel CHARGER VOLTAGE

TYPE Battery - Sealed Lead-acid DESCRIPTION Electrical room 401 4th floor battery 1

ADDRESS / SCAN ADDRESS NOMINAL VOLTAGE 12

LOAD VOLTAGE 12 AMP HOURS 7

STANDBY HOURS 24 ALARM MINUTES 15

BATTERY LOCATION In panel CHARGER VOLTAGE 27.2

TYPE Battery - Sealed Lead-acid DESCRIPTION In main electrical room 1st floor battery

ADDRESS / SCAN ADDRESS Main facp NOMINAL VOLTAGE

LOAD VOLTAGE AMP HOURS 12

STANDBY HOURS 24 ALARM MINUTES 15

BATTERY LOCATION In panel CHARGER VOLTAGE

TYPE Battery - Sealed Lead-acid DESCRIPTION In main electrical room 1st floor battery

ADDRESS / SCAN ADDRESS Main fcps NOMINAL VOLTAGE

LOAD VOLTAGE AMP HOURS 7

STANDBY HOURS 24 ALARM MINUTES 15

BATTERY LOCATION In panel CHARGER VOLTAGE

Page 3 of 13Page 3 of 13Basesix Systems

Page 4 of 13Page 4 of 13Basesix Systems

Open Corrective Action & Solution Summary The following 1 corrective action(s) remain open following the system inspection, testing or maintenance activities

EQUIPMENT TYPE ADDRESS DESCRIPTION

FACP Main facp In main electrical room 1st floor

Created By: Kanen Watson

Creation Date: 08/26/2024

Corrective Action: Network A&B trouble on panel when we arrived

Proposed Solution:

Manufacturer: Notifier

Model: NFS 320

Page 5 of 13Page 5 of 13Basesix Systems

Resolved Corrective Action & Solution Summary The following 4 corrective action(s) were resolved during the system inspection, testing or maintenance activities

EQUIPMENT TYPE ADDRESS DESCRIPTION

Battery - Sealed Lead-acid Electrical room 401 4th floor battery 1

Created By: Christopher Kirkbride

Creation Date: 12/04/2023

Corrective Action: Battery has exceeded its service life

12v7ah

Resolution: Battery was replaced prior to inspection

Resolved By: Christopher Kirkbride

Resolved On: 02/23/2025

Manufacturer: Power patrol

Model: 12V 7AH

Created By: Kanen Watson

Creation Date: 08/26/2024

Corrective Action: Batteries are out of date

Resolution: Duplicate

Resolved By: Christopher Kirkbride

Resolved On: 02/23/2025

Manufacturer: Power patrol

Model: 12V 7AH

Battery - Sealed Lead-acid Electrical room 401 4th floor battery 2

Created By: Christopher Kirkbride

Creation Date: 12/04/2023

Corrective Action: Battery has exceeded service life

12v7ah

Resolution: Batteries were replaced prior to inspection

Resolved By: Christopher Kirkbride

Resolved On: 02/23/2025

Manufacturer: Power patrol

Model: 12V 7AH

Created By: Kanen Watson

Creation Date: 08/26/2024

Corrective Action: Batteries are out of date

Resolution: Duplicate

Resolved By: Christopher Kirkbride

Resolved On: 02/06/2025

Manufacturer: Power patrol

Model: 12V 7AH

Page 6 of 13Page 6 of 13Basesix Systems

Testing Details

Emergency Control Equipment

Skipped

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Elevator Shunt Trip N010 L01M053 ELEV 3 SHUNT Manual 2/23/2025 8:16:16 PM

Egress Elevator Status Indicator

N010 L01M054 ELEV 3 HAT Manual 2/23/2025 8:16:21 PM

Elevator Recall - Alternate N010 L01M055 ELEV 3 ALT Manual 2/23/2025 8:16:24 PM

Elevator Recall - Primary N010 L01M056 ELEV 3 PRI Manual 2/23/2025 8:16:31 PM

Elevator Shunt Trip N010 L01M057 ELEV 1 SHUNT Manual 2/23/2025 8:16:37 PM

Egress Elevator Status Indicator

N010 L01M058 ELEV 1 HAT Manual 2/23/2025 8:16:42 PM

Elevator Recall - Alternate N010 L01M059 ELEV 1 ALT Manual 2/23/2025 8:16:45 PM

Elevator Recall - Primary N010 L01M060 ELEV 1 PRI Manual 2/23/2025 8:16:48 PM

Elevator Recall - Primary N010 L01M061 ELEV 2 PRI Manual 2/23/2025 8:16:51 PM

Elevator Recall - Alternate N010 L01M062 ELEV 2 ALT Manual 2/23/2025 8:16:56 PM

Egress Elevator Status Indicator

N010 L01M063 ELEV 2 HAT Manual 2/23/2025 8:16:59 PM

Elevator Shunt Trip N010 L01M064 ELEV 2 SHUNT Manual 2/23/2025 8:17:02 PM

Elevator Recall - Primary N010 L01M065 ELEV 4 PRI Manual 2/23/2025 8:17:07 PM

Elevator Recall - Alternate N010 L01M066 ELEV 4 ALT Manual 2/23/2025 8:17:10 PM

Egress Elevator Status Indicator

N010 L01M067 ELEV 4 HAT Manual 2/23/2025 8:17:17 PM

Elevator Shunt Trip N010 L01M068 ELEV 4 SHUNT Manual 2/23/2025 8:17:20 PM

Fire Control Panel

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Fire Alarm Panel N000 N000 PANEL Manual 1/20/2025 8:52:47 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Initiating Device

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Smoke Detector - General N010 L01D012 ELEV 3/4 MACH RM Manual 1/20/2025 8:52:15 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General N010 L01D011 ELEV 1/2 MACH RM Manual 1/20/2025 8:52:17 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Manual Fire Box N010 L01M047 NORTH STAIR Manual 1/20/2025 8:52:19 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Manual Fire Box N010 L01M038 NORTH STAIR Manual 1/20/2025 8:52:21 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General N010 L01D003 SECTION A Manual 2/3/2025 9:46:10 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Page 7 of 13Page 7 of 13Basesix Systems

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Smoke Detector - General N010 L01D005 SECTION B Manual 2/3/2025 9:46:17 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General N010 L01D006 ELEC RM. 401 Manual 2/3/2025 9:46:18 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General N010 L01D004 SECTION A Manual 2/3/2025 9:46:21 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General N010 L01D001 ABOVE FACP MAIN ELEC Manual 2/23/2025 8:15:04 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General N010 L01D013 IDF ROOM 3rd FL Manual 2/23/2025 8:15:12 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General N010 L01D002 SECTION B Manual 2/23/2025 8:15:14 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Manual Fire Box N010 L01M017 NORTH STAIR Manual 2/23/2025 8:15:45 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Manual Fire Box N010 L01M022 SOUTH STAIR Manual 2/23/2025 8:15:47 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Manual Fire Box N010 L01M027 NORTH STAIR Manual 2/23/2025 8:15:51 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Manual Fire Box N010 L01M033 PULL STATION SOUTH Manual 2/23/2025 8:16:03 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Manual Fire Box N010 L01M043 SOUTH STAIR Manual 2/23/2025 8:16:05 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Manual Fire Box N010 L01M050 OUTSIDE NORTH STAIR Manual 2/23/2025 8:16:13 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Manual Fire Box N010 L01M070 SOUTH STAIR Manual 2/23/2025 8:17:27 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Heat Detector N010 L01M007 ELEV 3/4 LOBBY HEAT Manual 2/23/2025 8:17:40 PM

Visual Inspection Passed (Manual)

Heat Detector N010 L01M069 ELEV 1/2 LOBBY HEAT Manual 2/23/2025 8:17:45 PM

Visual Inspection Passed (Manual)

Heat Detector N010 L01M049 ELEV 3/4 LOBBY HEAT Manual 2/23/2025 8:17:49 PM

Visual Inspection Passed (Manual)

Heat Detector N010 L01M048 ELEV 3/4 LOBBY HEAT Manual 2/23/2025 8:17:56 PM

Visual Inspection Passed (Manual)

Heat Detector N010 L01M037 ELEV 3/4 LOBBY HEAT Manual 2/23/2025 8:18:00 PM

Visual Inspection Passed (Manual)

Heat Detector N010 L01M026 ELEV 3/4 LOBBY HEAT Manual 2/23/2025 8:18:04 PM

Visual Inspection Passed (Manual)

Heat Detector N010 L01M025 ELEV 1/2 LOBBY HEAT Manual 2/23/2025 8:18:09 PM

Visual Inspection Passed (Manual)

Page 8 of 13Page 8 of 13Basesix Systems

Heat Detector N010 L01M016 ELEV 3/4 LOBBY HEAT Manual 2/23/2025 8:18:13 PM

Visual Inspection Passed (Manual)

Heat Detector N010 L01M012 ELEV 3 AND 4 HEAT Manual 2/23/2025 8:18:18 PM

Visual Inspection Passed (Manual)

Heat Detector N010 L01M036 ELEV 1/2 LOBBY HEAT Manual 2/23/2025 8:19:27 PM

Visual Inspection Passed (Manual)

Heat Detector N010 L01M046 ELEV 1/2 LOBBY HEAT Manual 2/23/2025 8:19:34 PM

Visual Inspection Passed (Manual)

Skipped

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Smoke Detector - General N010 L01D010 ELEV 2 TOP OF SHAFT Manual 2/23/2025 8:15:07 PM

Smoke Detector - General N010 L01D007 ELEV 3 TOP OF SHAFT Manual 2/23/2025 8:15:21 PM

Smoke Detector - General N010 L01D008 ELEV 4 TOP OF SHAFT Manual 2/23/2025 8:15:23 PM

Smoke Detector - General N010 L01D009 ELEV 1 TOP OF SHAFT Manual 2/23/2025 8:15:27 PM

Power Supplies

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Battery - Sealed Lead-acid Main facp In main electrical room 1st floor battery

Manual 1/20/2025 8:51:34 AM

Manufacturer Power patrol

Model 12V12ah

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Minutes 15

Amp Hours 12

Battery Location In panel

Stand By Hours 24

Battery - Sealed Lead-acid Main facp In main electrical room 1st floor battery

Manual 1/20/2025 8:51:36 AM

Manufacturer Power patrol

Model 12V12ah

Visual Inspection Passed (Manual)

Functional Inspection Passed

Page 9 of 13Page 9 of 13Basesix Systems

Alarm Minutes 15

Amp Hours 12

Battery Location In panel

Stand By Hours 24

Battery - Sealed Lead-acid Main fcps In main electrical room 1st floor battery

Manual 1/20/2025 8:51:38 AM

Manufacturer Power patrol

Model 12V 7AH

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Minutes 15

Amp Hours 7

Battery Location In panel

Stand By Hours 24

Battery - Sealed Lead-acid Main fcps In main electrical room 1st floor battery

Manual 1/20/2025 8:51:39 AM

Manufacturer Power patrol

Model 12V 7AH

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Minutes 15

Amp Hours 7

Battery Location In panel

Stand By Hours 24

FCPS Main fcps In main electrical room 1st floor Manual 1/20/2025 8:51:41 AM

Manufacturer Potter

Page 10 of 13Page 10 of 13Basesix Systems

Model Psn-106

Visual Inspection Passed (Manual)

Functional Inspection Passed

FCPS Electrical room 401 4th floor Manual 1/20/2025 8:53:05 AM

Manufacturer Potter

Model Psn 106

Visual Inspection Passed (Manual)

Functional Inspection Passed

FACP Main facp In main electrical room 1st floor Manual 2/6/2025 9:39:35 AM

Manufacturer Notifier

Model NFS 320

Visual Inspection Passed (Manual)

Functional Inspection Passed

Battery - Sealed Lead-acid Electrical room 401 4th floor battery 2 Manual 2/23/2025 8:23:29 PM

Manufacturer Power patrol

Model 12V 7AH

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Minutes 15

Amp Hours 7

Battery Location In panel

Charger Voltage 27.2

Load Voltage 12

Stand By Hours 24

Battery - Sealed Lead-acid Electrical room 401 4th floor battery 1 Manual 2/23/2025 8:23:51 PM

Manufacturer Power patrol

Model 12V 7AH

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Minutes 15

Amp Hours 7

Battery Location In panel

Charger Voltage 27.2

Load Voltage 12

Nominal Voltage 12

Stand By Hours 24

Page 11 of 13Page 11 of 13Basesix Systems

Device/Equipment Details

Emergency Control Equipment

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Elevator Shunt Trip

N010 L01M053 ELEV 3 SHUNT 07/31/2024

N010 L01M054 ELEV 3 HAT 07/31/2024

N010 L01M055 ELEV 3 ALT 07/31/2024

N010 L01M056 ELEV 3 PRI 07/31/2024

N010 L01M057 ELEV 1 SHUNT 07/31/2024

N010 L01M058 ELEV 1 HAT 07/31/2024

N010 L01M059 ELEV 1 ALT 07/31/2024

N010 L01M060 ELEV 1 PRI 07/31/2024

N010 L01M061 ELEV 2 PRI 07/31/2024

N010 L01M062 ELEV 2 ALT 07/31/2024

N010 L01M063 ELEV 2 HAT 07/31/2024

N010 L01M064 ELEV 2 SHUNT 07/31/2024

N010 L01M065 ELEV 4 PRI 07/31/2024

N010 L01M066 ELEV 4 ALT 07/31/2024

N010 L01M067 ELEV 4 HAT 07/31/2024

N010 L01M068 ELEV 4 SHUNT 07/31/2024

Fire Control Panel

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Fire Alarm Panel

N000 N000 PANEL 08/17/2023

Initiating Device

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Smoke Detector - General

N010 L01D001 ABOVE FACP MAIN ELEC 07/31/2024

N010 L01D002 SECTION B 07/31/2024

N010 L01D003 SECTION A 07/31/2024

N010 L01D004 SECTION A 07/31/2024

N010 L01D005 SECTION B 07/31/2024

N010 L01D006 ELEC RM. 401 07/31/2024

N010 L01D007 ELEV 3 TOP OF SHAFT 07/31/2024

N010 L01D008 ELEV 4 TOP OF SHAFT 07/31/2024

N010 L01D009 ELEV 1 TOP OF SHAFT 07/31/2024

N010 L01D010 ELEV 2 TOP OF SHAFT 07/31/2024

N010 L01D011 ELEV 1/2 MACH RM 07/31/2024

N010 L01D012 ELEV 3/4 MACH RM 07/31/2024

N010 L01D013 IDF ROOM 3rd FL 07/31/2024

Heat Detector

N010 L01M007 ELEV 3/4 LOBBY HEAT 07/31/2024

N010 L01M012 ELEV 3 AND 4 HEAT 07/31/2024

N010 L01M016 ELEV 3/4 LOBBY HEAT 07/31/2024

N010 L01M025 ELEV 1/2 LOBBY HEAT 07/31/2024

N010 L01M026 ELEV 3/4 LOBBY HEAT 07/31/2024

N010 L01M036 ELEV 1/2 LOBBY HEAT 07/31/2024

N010 L01M037 ELEV 3/4 LOBBY HEAT 07/31/2024

N010 L01M046 ELEV 1/2 LOBBY HEAT 07/31/2024

N010 L01M048 ELEV 3/4 LOBBY HEAT 07/31/2024

N010 L01M049 ELEV 3/4 LOBBY HEAT 07/31/2024

Page 12 of 13Page 12 of 13Basesix Systems

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

N010 L01M069 ELEV 1/2 LOBBY HEAT 07/31/2024

Manual Fire Box

N010 L01M017 NORTH STAIR 07/31/2024

N010 L01M022 SOUTH STAIR 07/31/2024

N010 L01M027 NORTH STAIR 07/31/2024

N010 L01M033 PULL STATION SOUTH 07/31/2024

N010 L01M038 NORTH STAIR 07/31/2024

N010 L01M043 SOUTH STAIR 07/31/2024

N010 L01M047 NORTH STAIR 07/31/2024

N010 L01M050 OUTSIDE NORTH STAIR 07/31/2024

N010 L01M070 SOUTH STAIR 07/31/2024

Power Supplies

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

FCPS

Electrical room 401 4th floor Potter Psn 106

Main fcps In main electrical room 1st floor Potter Psn-106

Battery - Sealed Lead-acid

Electrical room 401 4th floor battery 1

Power patrol 12V 7AH 12/01/2023

Electrical room 401 4th floor battery 2

Power patrol 12V 7AH 12/01/2023

Main facp In main electrical room 1st floor battery 1

Power patrol 12V12ah 09/20/2023

Main facp In main electrical room 1st floor battery 2

Power patrol 12V12ah 09/20/2023

Main fcps In main electrical room 1st floor battery 1

Power patrol 12V 7AH 09/20/2023

Main fcps In main electrical room 1st floor battery 2

Power patrol 12V 7AH 02/20/2020

FACP

Main facp In main electrical room 1st floor Notifier NFS 320

Page 13 of 13Page 13 of 13Basesix Systems