NFPA72 _ Silver Deck _ ANNUAL FIRE INSPECTION.pdf
PDF 549 KB Posted
- Attached to
- Fire Alarm Removal and Replacement
- Solicitation number
- PE-92200-RFP-2026-000000061
- Issued by
- Fulton County, Georgia
About this file
This is an NFPA 72 annual fire inspection and testing certificate for the Georgia World Congress Center's Silver Deck facility located at 285 Andrew Young International Boulevard NW in Atlanta, Georgia. The inspection was conducted on December 12, 2024, by Basesix Systems, with technician Christopher Kirkbride (NICET Certification #148593) performing the testing and Kevin Rutledge of the Georgia World Congress Center accepting the results. The facility's fire alarm and signaling system underwent comprehensive testing in accordance with NFPA 72 standards, with all equipment passing inspection. The system includes multiple initiating devices, emergency control equipment, emergency lighting and power systems, fire control panels, and secondary power supplies distributed throughout the facility's six floors.
The inspection results demonstrate full system compliance, with 38 total pieces of equipment tested across five categories: three emergency control equipment items (skipped), one emergency lighting and power item (skipped), one fire control panel (passed), 24 initiating devices including smoke detectors, heat detectors, and pull stations (23 passed, one skipped), and nine power supplies including six sealed lead-acid batteries and three FCPS units (all passed). Secondary power consists of sealed lead-acid batteries rated at 12 volts, 7 amp hours, with 24-hour standby capability and 15-minute alarm runtime, strategically located in the main electrical room serving the FACP and two FCPS systems. No deficiencies were identified during testing, and the system was marked as acceptable with an "Everything Looks Okay" status.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Inspection and Testing Certificate Presented To
Georgia World Congress Center
For
Silver Deck
285 Andrew Young International Blvd NW
Atlanta, Georgia 30313
United States
This site has been inspected and tested in compliance with applicable standards.
Completed Thursday, December 12, 2024
Test Session :ANNUAL FIRE INSPECTION 2024
ACCEPTED BY TESTED BY
Kevin Rutledge
Georgia World Congress Center
285 Andrew Young International Blvd NW Atlanta, Georgia 30313 United States
Christopher Kirkbride
Basesix Systems
2053 Franklin Way Marietta, GA 30067 United States
INSPECTION STATUS
Acceptable
Everything Looks Okay
Basesix Systems
Inspection Summary
Building Information
PROPERTY Silver Deck CONTACT Kevin Rutledge
ADDRESS 285 Andrew Young International Blvd NW
PHONE
CITY/STATE/ZIP Atlanta, Georgia 30313 MOBILE +1 404-392-7027
COUNTRY United States EMAIL krutledge@gwcc.com
Inspector Information
COMPANY Basesix Systems CONTACT Christopher Kirkbride
ADDRESS
2053 Franklin Way Marietta, GA 30067
LICENSE NUMBER Nicet Certification # 148593
PHONE +1 470-590-2691
COUNTRY United States EMAIL ckirkbride@basesix.com
Testing Summary
EQUIPMENT TYPE TOTAL TESTED PASSED FAILED
3 0(0%) 0(0%) 0(0%)
1 0(0%) 0(0%) 0(0%)
1 1(100%) 1(100%) 0(0%)
24 23(96%) 23(96%) 0(0%)
9 9(100%) 9(100%) 0(0%)
Certification The equipment specified herein was inspected and tested according to the NFPA 72 standard for fire alarm and signaling systems, with the inspection completed on Thursday, December 12, 2024
ACCEPTED BY 12/12/2024 TESTED BY 12/12/2024
Kevin Rutledge Christopher Kirkbride
Building Representative Technician
Emergency Control Equipment
Emergency Lighting and Power
Fire Control Panel
Initiating Device
Power Supplies
Page 2 of 11Page 2 of 11Basesix Systems
System Details
Secondary Power TYPE Battery - Sealed Lead-acid DESCRIPTION Fcps 1 in main electrical room battery 2
ADDRESS / SCAN ADDRESS FCPS 1 NOMINAL VOLTAGE
LOAD VOLTAGE 12 AMP HOURS 7
STANDBY HOURS 24 ALARM MINUTES 15
BATTERY LOCATION In panel CHARGER VOLTAGE 27.2
TYPE Battery - Sealed Lead-acid DESCRIPTION Fcps 2 in main electrical room battery 1
ADDRESS / SCAN ADDRESS FCPS 2 NOMINAL VOLTAGE
LOAD VOLTAGE 12 AMP HOURS 7
STANDBY HOURS 24 ALARM MINUTES 15
BATTERY LOCATION In panel CHARGER VOLTAGE 27.2
TYPE Battery - Sealed Lead-acid DESCRIPTION Fcps 2 in main electrical room battery 2
ADDRESS / SCAN ADDRESS FCPS 2 NOMINAL VOLTAGE
LOAD VOLTAGE 12 AMP HOURS 7
STANDBY HOURS 24 ALARM MINUTES 15
BATTERY LOCATION In panel CHARGER VOLTAGE 27.2
TYPE Battery - Sealed Lead-acid DESCRIPTION Facp in main electrical room battery 2
ADDRESS / SCAN ADDRESS main facp NOMINAL VOLTAGE
LOAD VOLTAGE 12 AMP HOURS 7
STANDBY HOURS 24 ALARM MINUTES 15
BATTERY LOCATION In panel CHARGER VOLTAGE 27.2
TYPE Battery - Sealed Lead-acid DESCRIPTION Fcps 1 in main electrical room battery 1
ADDRESS / SCAN ADDRESS FCPS 1 NOMINAL VOLTAGE
LOAD VOLTAGE 12 AMP HOURS 7
STANDBY HOURS 24 ALARM MINUTES 15
BATTERY LOCATION In panel CHARGER VOLTAGE 27.2
TYPE Battery - Sealed Lead-acid DESCRIPTION Facp in main electrical room battery 1
ADDRESS / SCAN ADDRESS main facp NOMINAL VOLTAGE
LOAD VOLTAGE 12 AMP HOURS 7
STANDBY HOURS 24 ALARM MINUTES 15
BATTERY LOCATION In panel CHARGER VOLTAGE 27.2
Page 3 of 11Page 3 of 11Basesix Systems
Testing Details
Emergency Control Equipment
Skipped
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Elevator Shunt Trip Shunt trip Manual 2/23/2025 8:50:01 PM
Elevator Recall - Alternate Alternate recall Manual 2/23/2025 8:50:25 PM
Elevator Recall - Primary Primary recall Manual 2/23/2025 8:50:28 PM
Emergency Lighting and Power
Skipped
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Egress Elevator Status Indicator
Hat light Manual 2/23/2025 8:49:03 PM
Fire Control Panel
Passed
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Remote Annunciator 6th floor security office Manual 2/23/2025 8:44:33 PM
Manufacturer Est
Visual Inspection Passed (Manual)
Functional Inspection Passed
Initiating Device
Passed
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Smoke Detector - General D1 Above FACP Manual 2/23/2025 8:44:35 PM
Manufacturer Est
Model Siga-PS
Visual Inspection Passed (Manual)
Functional Inspection Passed
Smoke Detector - General D2 Security/communication room Manual 2/23/2025 8:45:04 PM
Manufacturer Est
Model Siga-PS
Visual Inspection Passed (Manual)
Functional Inspection Passed
Smoke Detector - General D19 6th floor security office Manual 2/23/2025 8:45:06 PM
Manufacturer Est
Model Siga-PS
Visual Inspection Passed (Manual)
Functional Inspection Passed
Smoke Detector - General D20 6th floor security office Manual 2/23/2025 8:45:07 PM
Manufacturer Est
Page 4 of 11Page 4 of 11Basesix Systems
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Model Siga-PS
Visual Inspection Passed (Manual)
Functional Inspection Passed
Smoke Detector - General D21 6th floor security office Manual 2/23/2025 8:45:10 PM
Manufacturer Est
Model Siga-PS
Visual Inspection Passed (Manual)
Functional Inspection Passed
Heat Detector - Non-restorable Spot
D7 3rd floor elevator lobby Manual 2/23/2025 8:45:13 PM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Pull Station M11 4th floor north stair Manual 2/23/2025 8:45:15 PM
Manufacturer Est
Model Siga-278
Visual Inspection Passed (Manual)
Functional Inspection Passed
Pull Station M12 5th floor south stair Manual 2/23/2025 8:45:17 PM
Manufacturer Est
Model Siga-278
Visual Inspection Passed (Manual)
Functional Inspection Passed
Pull Station M14 5th floor north stair Manual 2/23/2025 8:45:18 PM
Manufacturer Est
Model Siga-278
Visual Inspection Passed (Manual)
Functional Inspection Passed
Pull Station M15 6th floor south stair Manual 2/23/2025 8:45:20 PM
Manufacturer Est
Model Siga-278
Visual Inspection Passed (Manual)
Functional Inspection Passed
Pull Station M17 6th floor north stair Manual 2/23/2025 8:45:21 PM
Manufacturer Est
Model Siga-278
Visual Inspection Passed (Manual)
Functional Inspection Passed
Pull Station M26 6th floor security office Manual 2/23/2025 8:45:22 PM
Manufacturer Est
Model Siga-278
Visual Inspection Passed (Manual)
Functional Inspection Passed
Pull Station M27 Ground floor north stair Manual 2/23/2025 8:45:24 PM
Manufacturer Est
Model Siga-278
Visual Inspection Passed (Manual)
Functional Inspection Passed
Pull Station M28 Ground floor south stair Manual 2/23/2025 8:45:25 PM
Manufacturer Est
Model Siga-278
Visual Inspection Passed (Manual)
Functional Inspection Passed
Pull Station M3 2nd floor south stair Manual 2/23/2025 8:45:27 PM
Manufacturer Est
Model Siga-278
Visual Inspection Passed (Manual)
Functional Inspection Passed
Pull Station M5 2nd floor north stair Manual 2/23/2025 8:45:28 PM
Page 5 of 11Page 5 of 11Basesix Systems
Manufacturer Est
Model Siga-278
Visual Inspection Passed (Manual)
Functional Inspection Passed
Pull Station M6 3rd floor south stair Manual 2/23/2025 8:45:29 PM
Manufacturer Est
Model Siga-278
Visual Inspection Passed (Manual)
Functional Inspection Passed
Pull Station M8 3rd floor north stair Manual 2/23/2025 8:45:31 PM
Manufacturer Est
Model Siga-278
Visual Inspection Passed (Manual)
Functional Inspection Passed
Heat Detector - Non-restorable Spot
D4 2nd floor elevator lobby Manual 2/23/2025 8:45:32 PM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Heat Detector - Non-restorable Spot
D16 6th floor elevator lobby Manual 2/23/2025 8:45:34 PM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Heat Detector - Non-restorable Spot
D13 5th floor elevator lobby Manual 2/23/2025 8:45:35 PM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Pull Station M9 4th floor south stair Manual 2/23/2025 8:45:37 PM
Manufacturer Est
Model Siga-278
Visual Inspection Passed (Manual)
Functional Inspection Passed
Heat Detector - Non-restorable Spot
D10 4th floor elevator lobby Manual 2/23/2025 8:45:38 PM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Skipped
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Smoke Detector - General D18 Top of elevator shaft Manual 2/23/2025 8:45:01 PM
Manufacturer Est
Model Siga-PS
Power Supplies
Passed
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Battery - Sealed Lead-acid main facp Facp in main electrical room battery 2 Manual 2/23/2025 8:43:54 PM
Manufacturer Power patrol
Model 12V12ah
Page 6 of 11Page 6 of 11Basesix Systems
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Minutes 15
Amp Hours 7
Battery Location In panel
Charger Voltage 27.2
Load Voltage 12
Stand By Hours 24
Battery - Sealed Lead-acid main facp Facp in main electrical room battery 1 Manual 2/23/2025 8:44:05 PM
Manufacturer Power patrol
Model 12V 7AH
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Minutes 15
Amp Hours 7
Battery Location In panel
Charger Voltage 27.2
Load Voltage 12
Stand By Hours 24
Battery - Sealed Lead-acid FCPS 2 Fcps 2 in main electrical room battery 1 Manual 2/23/2025 8:44:15 PM
Model 12V 7AH
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Minutes 15
Amp Hours 7
Battery Location In panel
Charger Voltage 27.2
Load Voltage 12
Stand By Hours 24
Page 7 of 11Page 7 of 11Basesix Systems
Battery - Sealed Lead-acid FCPS 1 Fcps 1 in main electrical room battery 1 Manual 2/23/2025 8:44:25 PM
Model 12V 7AH
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Minutes 15
Amp Hours 7
Battery Location In panel
Charger Voltage 27.2
Load Voltage 12
Stand By Hours 24
FCPS FCPS 1 Fcps 1 in main electrical room Manual 2/23/2025 8:44:28 PM
Manufacturer Est
Model Bps10a
Visual Inspection Passed (Manual)
Functional Inspection Passed
FCPS FCPS 2 Fcps 2 in main electrical room Manual 2/23/2025 8:44:29 PM
Manufacturer Est
Visual Inspection Passed (Manual)
Functional Inspection Passed
Page 8 of 11Page 8 of 11Basesix Systems
FACP main facp Facp in main electrical room Manual 2/23/2025 8:44:31 PM
Manufacturer Est
Model Est2
Visual Inspection Passed (Manual)
Functional Inspection Passed
Battery - Sealed Lead-acid FCPS 1 Fcps 1 in main electrical room battery 2 Manual 2/23/2025 8:44:46 PM
Model 12V 7AH
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Minutes 15
Amp Hours 7
Battery Location In panel
Charger Voltage 27.2
Load Voltage 12
Stand By Hours 24
Battery - Sealed Lead-acid FCPS 2 Fcps 2 in main electrical room battery 2 Manual 2/23/2025 8:44:57 PM
Model 12V 7AH
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Minutes 15
Amp Hours 7
Battery Location In panel
Charger Voltage 27.2
Load Voltage 12
Stand By Hours 24
Page 9 of 11Page 9 of 11Basesix Systems
Device/Equipment Details
Emergency Control Equipment
ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE
Elevator Shunt Trip
Shunt trip 02/23/2025
Elevator Recall - Primary
Primary recall 02/23/2025
Elevator Recall - Alternate
Alternate recall 02/23/2025
Emergency Lighting and Power
ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE
Egress Elevator Status Indicator
Hat light 02/23/2025
Fire Control Panel
ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE
Remote Annunciator
6th floor security office Est 10/03/2022
Initiating Device
ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE
Smoke Detector - General
D1 Above FACP Est Siga-PS 02/23/2025
D19 6th floor security office Est Siga-PS 02/23/2025
D20 6th floor security office Est Siga-PS 02/23/2025
D21 6th floor security office Est Siga-PS 02/23/2025
D2 Security/communication room Est Siga-PS 02/23/2025
D18 Top of elevator shaft Est Siga-PS 02/23/2025
Pull Station
M6 3rd floor south stair Est Siga-278 02/23/2025
M8 3rd floor north stair Est Siga-278 02/23/2025
M11 4th floor north stair Est Siga-278 02/23/2025
M17 6th floor north stair Est Siga-278 02/23/2025
M26 6th floor security office Est Siga-278 02/23/2025
M15 6th floor south stair Est Siga-278 02/23/2025
M12 5th floor south stair Est Siga-278 02/23/2025
M5 2nd floor north stair Est Siga-278 02/23/2025
M14 5th floor north stair Est Siga-278 02/23/2025
M9 4th floor south stair Est Siga-278 02/23/2025
M3 2nd floor south stair Est Siga-278 02/23/2025
M27 Ground floor north stair Est Siga-278 02/23/2025
M28 Ground floor south stair Est Siga-278 02/23/2025
Heat Detector - Non-restorable Spot
D4 2nd floor elevator lobby 02/23/2025
D7 3rd floor elevator lobby 02/23/2025
D16 6th floor elevator lobby 02/23/2025
D13 5th floor elevator lobby 02/23/2025
D10 4th floor elevator lobby 02/23/2025
Power Supplies
ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE
FACP
main facp Facp in main electrical room Est Est2
Page 10 of 11Page 10 of 11Basesix Systems
ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE
Battery - Sealed Lead-acid main facp Facp in main electrical room battery 1
Power patrol 12V 7AH 02/18/2022 main facp Facp in main electrical room battery 2
Power patrol 12V12ah 09/01/2022
FCPS 1 Fcps 1 in main electrical room battery 1
12V 7AH 10/03/2021
FCPS 1 Fcps 1 in main electrical room battery 2
12V 7AH 10/03/2021
FCPS 2 Fcps 2 in main electrical room battery 2
12V 7AH 02/18/2022
FCPS 2 Fcps 2 in main electrical room battery 1
12V 7AH 02/18/2022
FCPS
FCPS 1 Fcps 1 in main electrical room Est Bps10a
FCPS 2 Fcps 2 in main electrical room Est
Page 11 of 11Page 11 of 11Basesix Systems