NFPA72 _ Silver Deck _ ANNUAL FIRE INSPECTION.pdf

PDF 549 KB Posted

Attached to
Fire Alarm Removal and Replacement
Solicitation number
PE-92200-RFP-2026-000000061
Issued by
Fulton County, Georgia

About this file

This is an NFPA 72 annual fire inspection and testing certificate for the Georgia World Congress Center's Silver Deck facility located at 285 Andrew Young International Boulevard NW in Atlanta, Georgia. The inspection was conducted on December 12, 2024, by Basesix Systems, with technician Christopher Kirkbride (NICET Certification #148593) performing the testing and Kevin Rutledge of the Georgia World Congress Center accepting the results. The facility's fire alarm and signaling system underwent comprehensive testing in accordance with NFPA 72 standards, with all equipment passing inspection. The system includes multiple initiating devices, emergency control equipment, emergency lighting and power systems, fire control panels, and secondary power supplies distributed throughout the facility's six floors.

The inspection results demonstrate full system compliance, with 38 total pieces of equipment tested across five categories: three emergency control equipment items (skipped), one emergency lighting and power item (skipped), one fire control panel (passed), 24 initiating devices including smoke detectors, heat detectors, and pull stations (23 passed, one skipped), and nine power supplies including six sealed lead-acid batteries and three FCPS units (all passed). Secondary power consists of sealed lead-acid batteries rated at 12 volts, 7 amp hours, with 24-hour standby capability and 15-minute alarm runtime, strategically located in the main electrical room serving the FACP and two FCPS systems. No deficiencies were identified during testing, and the system was marked as acceptable with an "Everything Looks Okay" status.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Inspection and Testing Certificate Presented To

Georgia World Congress Center

For

Silver Deck

285 Andrew Young International Blvd NW

Atlanta, Georgia 30313

United States

This site has been inspected and tested in compliance with applicable standards.

Completed Thursday, December 12, 2024

Test Session :ANNUAL FIRE INSPECTION 2024

ACCEPTED BY TESTED BY

Kevin Rutledge

Georgia World Congress Center

285 Andrew Young International Blvd NW Atlanta, Georgia 30313 United States

Christopher Kirkbride

Basesix Systems

2053 Franklin Way Marietta, GA 30067 United States

INSPECTION STATUS

Acceptable

Everything Looks Okay

Basesix Systems

Inspection Summary

Building Information

PROPERTY Silver Deck CONTACT Kevin Rutledge

ADDRESS 285 Andrew Young International Blvd NW

PHONE

CITY/STATE/ZIP Atlanta, Georgia 30313 MOBILE +1 404-392-7027

COUNTRY United States EMAIL krutledge@gwcc.com

Inspector Information

COMPANY Basesix Systems CONTACT Christopher Kirkbride

ADDRESS

2053 Franklin Way Marietta, GA 30067

LICENSE NUMBER Nicet Certification # 148593

PHONE +1 470-590-2691

COUNTRY United States EMAIL ckirkbride@basesix.com

Testing Summary

EQUIPMENT TYPE TOTAL TESTED PASSED FAILED

3 0(0%) 0(0%) 0(0%)

1 0(0%) 0(0%) 0(0%)

1 1(100%) 1(100%) 0(0%)

24 23(96%) 23(96%) 0(0%)

9 9(100%) 9(100%) 0(0%)

Certification The equipment specified herein was inspected and tested according to the NFPA 72 standard for fire alarm and signaling systems, with the inspection completed on Thursday, December 12, 2024

ACCEPTED BY 12/12/2024 TESTED BY 12/12/2024

Kevin Rutledge Christopher Kirkbride

Building Representative Technician

Emergency Control Equipment

Emergency Lighting and Power

Fire Control Panel

Initiating Device

Power Supplies

Page 2 of 11Page 2 of 11Basesix Systems

System Details

Secondary Power TYPE Battery - Sealed Lead-acid DESCRIPTION Fcps 1 in main electrical room battery 2

ADDRESS / SCAN ADDRESS FCPS 1 NOMINAL VOLTAGE

LOAD VOLTAGE 12 AMP HOURS 7

STANDBY HOURS 24 ALARM MINUTES 15

BATTERY LOCATION In panel CHARGER VOLTAGE 27.2

TYPE Battery - Sealed Lead-acid DESCRIPTION Fcps 2 in main electrical room battery 1

ADDRESS / SCAN ADDRESS FCPS 2 NOMINAL VOLTAGE

LOAD VOLTAGE 12 AMP HOURS 7

STANDBY HOURS 24 ALARM MINUTES 15

BATTERY LOCATION In panel CHARGER VOLTAGE 27.2

TYPE Battery - Sealed Lead-acid DESCRIPTION Fcps 2 in main electrical room battery 2

ADDRESS / SCAN ADDRESS FCPS 2 NOMINAL VOLTAGE

LOAD VOLTAGE 12 AMP HOURS 7

STANDBY HOURS 24 ALARM MINUTES 15

BATTERY LOCATION In panel CHARGER VOLTAGE 27.2

TYPE Battery - Sealed Lead-acid DESCRIPTION Facp in main electrical room battery 2

ADDRESS / SCAN ADDRESS main facp NOMINAL VOLTAGE

LOAD VOLTAGE 12 AMP HOURS 7

STANDBY HOURS 24 ALARM MINUTES 15

BATTERY LOCATION In panel CHARGER VOLTAGE 27.2

TYPE Battery - Sealed Lead-acid DESCRIPTION Fcps 1 in main electrical room battery 1

ADDRESS / SCAN ADDRESS FCPS 1 NOMINAL VOLTAGE

LOAD VOLTAGE 12 AMP HOURS 7

STANDBY HOURS 24 ALARM MINUTES 15

BATTERY LOCATION In panel CHARGER VOLTAGE 27.2

TYPE Battery - Sealed Lead-acid DESCRIPTION Facp in main electrical room battery 1

ADDRESS / SCAN ADDRESS main facp NOMINAL VOLTAGE

LOAD VOLTAGE 12 AMP HOURS 7

STANDBY HOURS 24 ALARM MINUTES 15

BATTERY LOCATION In panel CHARGER VOLTAGE 27.2

Page 3 of 11Page 3 of 11Basesix Systems

Testing Details

Emergency Control Equipment

Skipped

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Elevator Shunt Trip Shunt trip Manual 2/23/2025 8:50:01 PM

Elevator Recall - Alternate Alternate recall Manual 2/23/2025 8:50:25 PM

Elevator Recall - Primary Primary recall Manual 2/23/2025 8:50:28 PM

Emergency Lighting and Power

Skipped

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Egress Elevator Status Indicator

Hat light Manual 2/23/2025 8:49:03 PM

Fire Control Panel

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Remote Annunciator 6th floor security office Manual 2/23/2025 8:44:33 PM

Manufacturer Est

Visual Inspection Passed (Manual)

Functional Inspection Passed

Initiating Device

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Smoke Detector - General D1 Above FACP Manual 2/23/2025 8:44:35 PM

Manufacturer Est

Model Siga-PS

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General D2 Security/communication room Manual 2/23/2025 8:45:04 PM

Manufacturer Est

Model Siga-PS

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General D19 6th floor security office Manual 2/23/2025 8:45:06 PM

Manufacturer Est

Model Siga-PS

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General D20 6th floor security office Manual 2/23/2025 8:45:07 PM

Manufacturer Est

Page 4 of 11Page 4 of 11Basesix Systems

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Model Siga-PS

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General D21 6th floor security office Manual 2/23/2025 8:45:10 PM

Manufacturer Est

Model Siga-PS

Visual Inspection Passed (Manual)

Functional Inspection Passed

Heat Detector - Non-restorable Spot

D7 3rd floor elevator lobby Manual 2/23/2025 8:45:13 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Pull Station M11 4th floor north stair Manual 2/23/2025 8:45:15 PM

Manufacturer Est

Model Siga-278

Visual Inspection Passed (Manual)

Functional Inspection Passed

Pull Station M12 5th floor south stair Manual 2/23/2025 8:45:17 PM

Manufacturer Est

Model Siga-278

Visual Inspection Passed (Manual)

Functional Inspection Passed

Pull Station M14 5th floor north stair Manual 2/23/2025 8:45:18 PM

Manufacturer Est

Model Siga-278

Visual Inspection Passed (Manual)

Functional Inspection Passed

Pull Station M15 6th floor south stair Manual 2/23/2025 8:45:20 PM

Manufacturer Est

Model Siga-278

Visual Inspection Passed (Manual)

Functional Inspection Passed

Pull Station M17 6th floor north stair Manual 2/23/2025 8:45:21 PM

Manufacturer Est

Model Siga-278

Visual Inspection Passed (Manual)

Functional Inspection Passed

Pull Station M26 6th floor security office Manual 2/23/2025 8:45:22 PM

Manufacturer Est

Model Siga-278

Visual Inspection Passed (Manual)

Functional Inspection Passed

Pull Station M27 Ground floor north stair Manual 2/23/2025 8:45:24 PM

Manufacturer Est

Model Siga-278

Visual Inspection Passed (Manual)

Functional Inspection Passed

Pull Station M28 Ground floor south stair Manual 2/23/2025 8:45:25 PM

Manufacturer Est

Model Siga-278

Visual Inspection Passed (Manual)

Functional Inspection Passed

Pull Station M3 2nd floor south stair Manual 2/23/2025 8:45:27 PM

Manufacturer Est

Model Siga-278

Visual Inspection Passed (Manual)

Functional Inspection Passed

Pull Station M5 2nd floor north stair Manual 2/23/2025 8:45:28 PM

Page 5 of 11Page 5 of 11Basesix Systems

Manufacturer Est

Model Siga-278

Visual Inspection Passed (Manual)

Functional Inspection Passed

Pull Station M6 3rd floor south stair Manual 2/23/2025 8:45:29 PM

Manufacturer Est

Model Siga-278

Visual Inspection Passed (Manual)

Functional Inspection Passed

Pull Station M8 3rd floor north stair Manual 2/23/2025 8:45:31 PM

Manufacturer Est

Model Siga-278

Visual Inspection Passed (Manual)

Functional Inspection Passed

Heat Detector - Non-restorable Spot

D4 2nd floor elevator lobby Manual 2/23/2025 8:45:32 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Heat Detector - Non-restorable Spot

D16 6th floor elevator lobby Manual 2/23/2025 8:45:34 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Heat Detector - Non-restorable Spot

D13 5th floor elevator lobby Manual 2/23/2025 8:45:35 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Pull Station M9 4th floor south stair Manual 2/23/2025 8:45:37 PM

Manufacturer Est

Model Siga-278

Visual Inspection Passed (Manual)

Functional Inspection Passed

Heat Detector - Non-restorable Spot

D10 4th floor elevator lobby Manual 2/23/2025 8:45:38 PM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Skipped

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Smoke Detector - General D18 Top of elevator shaft Manual 2/23/2025 8:45:01 PM

Manufacturer Est

Model Siga-PS

Power Supplies

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Battery - Sealed Lead-acid main facp Facp in main electrical room battery 2 Manual 2/23/2025 8:43:54 PM

Manufacturer Power patrol

Model 12V12ah

Page 6 of 11Page 6 of 11Basesix Systems

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Minutes 15

Amp Hours 7

Battery Location In panel

Charger Voltage 27.2

Load Voltage 12

Stand By Hours 24

Battery - Sealed Lead-acid main facp Facp in main electrical room battery 1 Manual 2/23/2025 8:44:05 PM

Manufacturer Power patrol

Model 12V 7AH

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Minutes 15

Amp Hours 7

Battery Location In panel

Charger Voltage 27.2

Load Voltage 12

Stand By Hours 24

Battery - Sealed Lead-acid FCPS 2 Fcps 2 in main electrical room battery 1 Manual 2/23/2025 8:44:15 PM

Model 12V 7AH

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Minutes 15

Amp Hours 7

Battery Location In panel

Charger Voltage 27.2

Load Voltage 12

Stand By Hours 24

Page 7 of 11Page 7 of 11Basesix Systems

Battery - Sealed Lead-acid FCPS 1 Fcps 1 in main electrical room battery 1 Manual 2/23/2025 8:44:25 PM

Model 12V 7AH

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Minutes 15

Amp Hours 7

Battery Location In panel

Charger Voltage 27.2

Load Voltage 12

Stand By Hours 24

FCPS FCPS 1 Fcps 1 in main electrical room Manual 2/23/2025 8:44:28 PM

Manufacturer Est

Model Bps10a

Visual Inspection Passed (Manual)

Functional Inspection Passed

FCPS FCPS 2 Fcps 2 in main electrical room Manual 2/23/2025 8:44:29 PM

Manufacturer Est

Visual Inspection Passed (Manual)

Functional Inspection Passed

Page 8 of 11Page 8 of 11Basesix Systems

FACP main facp Facp in main electrical room Manual 2/23/2025 8:44:31 PM

Manufacturer Est

Model Est2

Visual Inspection Passed (Manual)

Functional Inspection Passed

Battery - Sealed Lead-acid FCPS 1 Fcps 1 in main electrical room battery 2 Manual 2/23/2025 8:44:46 PM

Model 12V 7AH

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Minutes 15

Amp Hours 7

Battery Location In panel

Charger Voltage 27.2

Load Voltage 12

Stand By Hours 24

Battery - Sealed Lead-acid FCPS 2 Fcps 2 in main electrical room battery 2 Manual 2/23/2025 8:44:57 PM

Model 12V 7AH

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Minutes 15

Amp Hours 7

Battery Location In panel

Charger Voltage 27.2

Load Voltage 12

Stand By Hours 24

Page 9 of 11Page 9 of 11Basesix Systems

Device/Equipment Details

Emergency Control Equipment

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Elevator Shunt Trip

Shunt trip 02/23/2025

Elevator Recall - Primary

Primary recall 02/23/2025

Elevator Recall - Alternate

Alternate recall 02/23/2025

Emergency Lighting and Power

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Egress Elevator Status Indicator

Hat light 02/23/2025

Fire Control Panel

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Remote Annunciator

6th floor security office Est 10/03/2022

Initiating Device

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Smoke Detector - General

D1 Above FACP Est Siga-PS 02/23/2025

D19 6th floor security office Est Siga-PS 02/23/2025

D20 6th floor security office Est Siga-PS 02/23/2025

D21 6th floor security office Est Siga-PS 02/23/2025

D2 Security/communication room Est Siga-PS 02/23/2025

D18 Top of elevator shaft Est Siga-PS 02/23/2025

Pull Station

M6 3rd floor south stair Est Siga-278 02/23/2025

M8 3rd floor north stair Est Siga-278 02/23/2025

M11 4th floor north stair Est Siga-278 02/23/2025

M17 6th floor north stair Est Siga-278 02/23/2025

M26 6th floor security office Est Siga-278 02/23/2025

M15 6th floor south stair Est Siga-278 02/23/2025

M12 5th floor south stair Est Siga-278 02/23/2025

M5 2nd floor north stair Est Siga-278 02/23/2025

M14 5th floor north stair Est Siga-278 02/23/2025

M9 4th floor south stair Est Siga-278 02/23/2025

M3 2nd floor south stair Est Siga-278 02/23/2025

M27 Ground floor north stair Est Siga-278 02/23/2025

M28 Ground floor south stair Est Siga-278 02/23/2025

Heat Detector - Non-restorable Spot

D4 2nd floor elevator lobby 02/23/2025

D7 3rd floor elevator lobby 02/23/2025

D16 6th floor elevator lobby 02/23/2025

D13 5th floor elevator lobby 02/23/2025

D10 4th floor elevator lobby 02/23/2025

Power Supplies

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

FACP

main facp Facp in main electrical room Est Est2

Page 10 of 11Page 10 of 11Basesix Systems

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Battery - Sealed Lead-acid main facp Facp in main electrical room battery 1

Power patrol 12V 7AH 02/18/2022 main facp Facp in main electrical room battery 2

Power patrol 12V12ah 09/01/2022

FCPS 1 Fcps 1 in main electrical room battery 1

12V 7AH 10/03/2021

FCPS 1 Fcps 1 in main electrical room battery 2

12V 7AH 10/03/2021

FCPS 2 Fcps 2 in main electrical room battery 2

12V 7AH 02/18/2022

FCPS 2 Fcps 2 in main electrical room battery 1

12V 7AH 02/18/2022

FCPS

FCPS 1 Fcps 1 in main electrical room Est Bps10a

FCPS 2 Fcps 2 in main electrical room Est

Page 11 of 11Page 11 of 11Basesix Systems