NFPA72 _ GWCC Node 9 _ Q4 ANNUAL FIRE INSPECT.pdf
PDF 978 KB Posted
- Attached to
- Fire Alarm Removal and Replacement
- Solicitation number
- PE-92200-RFP-2026-000000061
- Issued by
- Fulton County, Georgia
About this file
This is an NFPA 72 fire alarm and signaling system inspection and testing certificate for the Georgia World Congress Center (GWCC) Node 9 facility located at 285 Andrew Young International Blvd NW in Atlanta, Georgia. The inspection was conducted by Basesix Systems, with technician Christopher Kirkbride (NICET Certification #148593) performing the testing on January 20, 2025, and accepted by Kevin Rutledge of GWCC on November 15, 2024. The facility's fire alarm and signaling system comprises 108 total pieces of equipment, including 22 emergency control equipment items, 1 fire control panel, 64 initiating devices, and 21 power supplies. All equipment underwent visual and functional inspections in compliance with NFPA 72 standards, with 100 percent of all tested equipment passing inspection.
The system utilizes sealed lead-acid battery backups with both 12V7AH and 12V26AH configurations strategically located throughout the facility in rooms B115, BC119, BC120, and BC129, providing 24 hours of standby power and 15 minutes of alarm runtime. The fire control panel is a Notifier IFC2-3030 model installed on January 18, 2021, supported by six Wheelock Powerpath FCPS (Fire Control Panel Supply) units. The facility employs multiple categories of detection and notification equipment, including smoke detectors (general and duct-mounted), heat detectors, manual fire boxes, sprinkler risers, and notification appliances distributed throughout the B-C Hall, penthouse, and various mechanical spaces. Battery replacements were conducted on February 15, 2022, ensuring current system reliability. No deficiencies were identified during the inspection, and the system is approved for continued operation.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Inspection and Testing Certificate Presented To
Georgia World Congress Center
For
GWCC Node 9
285 Andrew Young International Blvd NW
Atlanta, Georgia 30313
United States
This site has been inspected and tested in compliance with applicable standards.
Completed Friday, November 15, 2024
Test Session :Q4 ANNUAL FIRE INSPECTION 2024
ACCEPTED BY TESTED BY
Kevin Rutledge
Georgia World Congress Center
285 Andrew Young International Blvd NW Atlanta, Georgia 30313 United States
Christopher Kirkbride
Basesix Systems
2053 Franklin Way Marietta, GA 30067 United States
INSPECTION STATUS
Acceptable
Everything Looks Okay
Basesix Systems
Inspection Summary
Building Information
PROPERTY GWCC Node 9 CONTACT Kevin Rutledge
ADDRESS 285 Andrew Young International Blvd NW
PHONE
CITY/STATE/ZIP Atlanta, Georgia 30313 MOBILE +1 404-392-7027
COUNTRY United States EMAIL krutledge@gwcc.com
Inspector Information
COMPANY Basesix Systems CONTACT Christopher Kirkbride
ADDRESS
2053 Franklin Way Marietta, GA 30067
LICENSE NUMBER Nicet Certification # 148593
PHONE +1 470-590-2691
COUNTRY United States EMAIL ckirkbride@basesix.com
Testing Summary
EQUIPMENT TYPE TOTAL TESTED PASSED FAILED
22 22(100%) 22(100%) 0(0%)
1 1(100%) 1(100%) 0(0%)
64 64(100%) 64(100%) 0(0%)
21 21(100%) 21(100%) 0(0%)
Certification The equipment specified herein was inspected and tested according to the NFPA 72 standard for fire alarm and signaling systems, with the inspection completed on Friday, November 15, 2024
ACCEPTED BY 11/15/2024 TESTED BY 11/15/2024
Kevin Rutledge Christopher Kirkbride
Building Representative Technician
Emergency Control Equipment
Fire Control Panel
Initiating Device
Power Supplies
Page 2 of 21Page 2 of 21Basesix Systems
System Details
Control Units
DESCRIPTION GEORGIA WORLD CONGRESS
CENTER NODE 9
ADDRESS / SCAN ADDRESS N9
S/W VERSIONMANUFACTURER
LAST UPDATEMODEL
S/W LOCATIONSERIAL NUMBER
INSTALL DATE 01/17/2021
Secondary Power TYPE Battery - Sealed Lead-acid DESCRIPTION In room bc119 idf battery 1
ADDRESS / SCAN ADDRESS NODE 9 panel NOMINAL VOLTAGE
LOAD VOLTAGE AMP HOURS 26
STANDBY HOURS 24 ALARM MINUTES 15
BATTERY LOCATION External can CHARGER VOLTAGE
TYPE Battery - Sealed Lead-acid DESCRIPTION In room bc119 idf battery 2
ADDRESS / SCAN ADDRESS NODE 9 panel NOMINAL VOLTAGE
LOAD VOLTAGE AMP HOURS 26
STANDBY HOURS 24 ALARM MINUTES 15
BATTERY LOCATION External can CHARGER VOLTAGE
TYPE Battery - Sealed Lead-acid DESCRIPTION In room b115 battery 2
ADDRESS / SCAN ADDRESS L1M01 NOMINAL VOLTAGE
LOAD VOLTAGE AMP HOURS 7
STANDBY HOURS 24 ALARM MINUTES 15
BATTERY LOCATION In panel CHARGER VOLTAGE
TYPE Battery - Sealed Lead-acid DESCRIPTION In room bc119 idf battery 2
ADDRESS / SCAN ADDRESS L1M08 NOMINAL VOLTAGE
LOAD VOLTAGE AMP HOURS 7
STANDBY HOURS 24 ALARM MINUTES 15
BATTERY LOCATION In panel CHARGER VOLTAGE
TYPE Battery - Sealed Lead-acid DESCRIPTION In room bc120 idf battery 2
ADDRESS / SCAN ADDRESS L1M17 NOMINAL VOLTAGE
LOAD VOLTAGE AMP HOURS 7
STANDBY HOURS 24 ALARM MINUTES 15
BATTERY LOCATION In panel CHARGER VOLTAGE
TYPE Battery - Sealed Lead-acid DESCRIPTION In room bc129 idf battery 2
ADDRESS / SCAN ADDRESS L1M34 NOMINAL VOLTAGE
LOAD VOLTAGE AMP HOURS 7
STANDBY HOURS 24 ALARM MINUTES 15
BATTERY LOCATION In panel CHARGER VOLTAGE
TYPE Battery - Sealed Lead-acid DESCRIPTION In room bc120 idf battery 2
ADDRESS / SCAN ADDRESS L1M36 NOMINAL VOLTAGE
LOAD VOLTAGE AMP HOURS 7
Page 3 of 21Page 3 of 21Basesix Systems
STANDBY HOURS 24 ALARM MINUTES 15
BATTERY LOCATION In panel CHARGER VOLTAGE
TYPE Battery - Sealed Lead-acid DESCRIPTION In room bc120 idf battery 2
ADDRESS / SCAN ADDRESS L1M61 NOMINAL VOLTAGE
LOAD VOLTAGE AMP HOURS 7
STANDBY HOURS 24 ALARM MINUTES 15
BATTERY LOCATION In panel CHARGER VOLTAGE
TYPE Battery - Sealed Lead-acid DESCRIPTION In room b115 battery 1
ADDRESS / SCAN ADDRESS L1M01 NOMINAL VOLTAGE
LOAD VOLTAGE AMP HOURS 7
STANDBY HOURS 24 ALARM MINUTES 15
BATTERY LOCATION In panel CHARGER VOLTAGE
TYPE Battery - Sealed Lead-acid DESCRIPTION In room bc119 idf battery 1
ADDRESS / SCAN ADDRESS L1M08 NOMINAL VOLTAGE
LOAD VOLTAGE AMP HOURS 7
STANDBY HOURS 24 ALARM MINUTES 15
BATTERY LOCATION In panel CHARGER VOLTAGE
TYPE Battery - Sealed Lead-acid DESCRIPTION In room bc120 idf battery 1
ADDRESS / SCAN ADDRESS L1M17 NOMINAL VOLTAGE
LOAD VOLTAGE AMP HOURS 7
STANDBY HOURS 24 ALARM MINUTES 15
BATTERY LOCATION In panel CHARGER VOLTAGE
TYPE Battery - Sealed Lead-acid DESCRIPTION In room bc129 idf battery 1
ADDRESS / SCAN ADDRESS L1M34 NOMINAL VOLTAGE
LOAD VOLTAGE AMP HOURS 7
STANDBY HOURS 24 ALARM MINUTES 15
BATTERY LOCATION In panel CHARGER VOLTAGE
TYPE Battery - Sealed Lead-acid DESCRIPTION In room bc120 idf battery 1
ADDRESS / SCAN ADDRESS L1M36 NOMINAL VOLTAGE
LOAD VOLTAGE AMP HOURS 7
STANDBY HOURS 24 ALARM MINUTES 15
BATTERY LOCATION In panel CHARGER VOLTAGE
TYPE Battery - Sealed Lead-acid DESCRIPTION In room bc120 idf battery 1
ADDRESS / SCAN ADDRESS L1M61 NOMINAL VOLTAGE
LOAD VOLTAGE AMP HOURS 7
STANDBY HOURS 24 ALARM MINUTES 15
BATTERY LOCATION In panel CHARGER VOLTAGE
Page 4 of 21Page 4 of 21Basesix Systems
Page 5 of 21Page 5 of 21Basesix Systems
Testing Details
Emergency Control Equipment
Passed
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
[Other] N009 L01M008 B-C HALL FCPS-2 Manual 1/20/2025 8:45:19 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L01M036 B-C HALL FCPS-5 Manual 1/20/2025 8:45:23 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L01M002 B-C HALL FCPS-1 Manual 1/20/2025 8:45:24 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L02M016 B-C HALL SEF-BC-2 Manual 1/20/2025 8:45:33 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L01M035 B-C HALL FCPS-4 Manual 1/20/2025 8:45:39 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L02M030 B-C HALL SEF-BC-6 Manual 1/20/2025 8:45:49 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L02M025 B-C HALL SEF-BC-5 Manual 1/20/2025 8:46:01 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L02M022 B-C HALL SEF-BC-3 Manual 1/20/2025 8:46:09 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L02M019 B-C HALL SEF-BC-1 Manual 1/20/2025 8:46:13 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L02M013 B-C HALL SEF-BC-4 Manual 1/20/2025 8:46:18 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L01M061 B-C HALL SYNC FCPS Manual 1/20/2025 8:46:21 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L01M010 C-4 SPRINKLER RISER Manual 1/20/2025 8:46:34 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L01M028 C-3 SPRINKLER RISER Manual 1/20/2025 8:46:36 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L01M003 B-4 SPRINKLER RISER Manual 1/20/2025 8:46:44 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L01M033 B-5 SPRINKLER RISER Manual 1/20/2025 8:46:46 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L01M017 B-C HALL FCPS-3 Manual 1/20/2025 8:46:58 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Page 6 of 21Page 6 of 21Basesix Systems
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
[Other] N009 L01M031 BC NORTH HANGER DOOR Manual 1/20/2025 8:47:07 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L01M005 BC SOUTH HANGER DOOR Manual 1/20/2025 8:47:11 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L02M003 B-C HALL RTU-BC-1 Manual 1/20/2025 8:47:18 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L02M004 B-C HALL RTU-BC-2 Manual 1/20/2025 8:47:20 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L02M005 B-C HALL RTU-BC-3 Manual 1/20/2025 8:47:21 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L02M006 B-C HALL RTU-BC-4 Manual 1/20/2025 8:47:23 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Fire Control Panel
Passed
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
Fire Alarm Panel N009 N009 GEORGIA WORLD CONGRESS
CENTER NODE 9
Manual 1/20/2025 8:46:23 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Initiating Device
Passed
EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME
[Other] N009 L01M029 BC NORTH HANGER DOOR Event 1/20/2025 8:41:59 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L01M009 B-C HALL FCPS-2 Manual 1/20/2025 8:45:21 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L01M037 B-C HALL FCPS-5 Manual 1/20/2025 8:45:26 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L01M034 B-C HALL FCPS-4 Manual 1/20/2025 8:45:27 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L01M001 B-C HALL FCPS-1 Manual 1/20/2025 8:45:29 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L01M062 B-C HALL SYNC FCPS Manual 1/20/2025 8:45:30 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L02M014 B-C HALL SEF-BC-4 Manual 1/20/2025 8:45:32 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L02M018 B-C HALL SEF-BC-2 Manual 1/20/2025 8:45:36 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L02M002 B-C HALL SEF-BC-1 Manual 1/20/2025 8:45:41 AM
Page 7 of 21Page 7 of 21Basesix Systems
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L02M009 B-C HALL SEF-BC-6 Manual 1/20/2025 8:45:43 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L02M007 B-C HALL SEF-BC-3 Manual 1/20/2025 8:45:45 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L02M032 B-C HALL SEF-BC-6 Manual 1/20/2025 8:45:47 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L02M031 B-C HALL SEF-BC-6 Manual 1/20/2025 8:45:50 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L02M027 B-C HALL SEF-BC-5 Manual 1/20/2025 8:45:52 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L02M026 B-C HALL SEF-BC-5 Manual 1/20/2025 8:45:53 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L02M001 B-C HALL SEF-BC-4 Manual 1/20/2025 8:45:58 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L02M024 B-C HALL SEF-BC-3 Manual 1/20/2025 8:46:00 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L02M023 B-C HALL SEF-BC-3 Manual 1/20/2025 8:46:07 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L02M021 B-C HALL SEF-BC-1 Manual 1/20/2025 8:46:10 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L02M020 B-C HALL SEF-BC-1 Manual 1/20/2025 8:46:11 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L02M017 B-C HALL SEF-BC-2 Manual 1/20/2025 8:46:15 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L02M015 B-C HALL SEF-BC-4 Manual 1/20/2025 8:46:17 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L02M010 B-C HALL SEF-BC-5 Manual 1/20/2025 8:46:20 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L01M030 BC NORTH HANGER DOOR Manual 1/20/2025 8:46:25 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L01M154 CHARGER FAIL Manual 1/20/2025 8:46:26 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L01M153 EARTH FAULT Manual 1/20/2025 8:46:28 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L01M152 BATTERY Manual 1/20/2025 8:46:29 AM
Page 8 of 21Page 8 of 21Basesix Systems
Functional Inspection Passed
[Other] N009 L01M151 AC FAIL Manual 1/20/2025 8:46:31 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L01M150 GENERAL TROUBLE Manual 1/20/2025 8:46:33 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L01M063 SPRINKLER BELL Manual 1/20/2025 8:46:48 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L01M064 SPRINKLER BELL Manual 1/20/2025 8:46:49 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L01M065 SPRINKLER BELL Manual 1/20/2025 8:46:51 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L01M066 SPRINKLER BELL Manual 1/20/2025 8:46:52 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L01M006 BC SOUTH HANGER DOOR Manual 1/20/2025 8:46:57 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L01M018 B-C HALL FCPS-3 Manual 1/20/2025 8:47:00 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
[Other] N009 L01M007 BC SOUTH HANGER DOOR Manual 1/20/2025 8:47:02 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Manual Fire Box N009 L01M060 B-C HALL RISER ROOM Manual 1/20/2025 8:47:13 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Heat Detector - Restorable Spot
N009 L02D010 B-C HALL PENTHOUSE Manual 1/20/2025 8:47:14 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Sensitivity Fixed
Drift Compensation 30%
Heat Detector - Restorable Spot
N009 L02D014 B-C HALL PENTHOUSE Manual 1/20/2025 8:47:16 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Sensitivity Fixed
Drift Compensation 0%
Manual Fire Box N009 L01M004 B-C HALL Manual 1/20/2025 8:47:24 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Manual Fire Box N009 L01M032 B-C HALL Manual 1/20/2025 8:47:25 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Smoke Detector - General N009 L01D004 B-C HALL IDF Manual 1/20/2025 8:47:27 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Sensitivity 2.12%
Drift Compensation 35%
Smoke Detector - General N009 L01D003 B-C HALL IDF Manual 1/20/2025 8:47:28 AM
Page 9 of 21Page 9 of 21Basesix Systems
Functional Inspection Passed
Alarm Sensitivity 2.12%
Drift Compensation 35%
Smoke Detector - General N009 L01D002 B-C HALL IDF Manual 1/20/2025 8:47:30 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Sensitivity 2.12%
Drift Compensation 35%
Smoke Detector - General N009 L01D001 B-C HALL IDF Manual 1/20/2025 8:47:31 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Sensitivity 2.12%
Drift Compensation 35%
Manual Fire Box N009 L02M011 B-C HALL PENTHOUSE Manual 1/20/2025 8:47:32 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Manual Fire Box N009 L02M012 B-C HALL PENTHOUSE Manual 1/20/2025 8:47:34 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Smoke Detector - General N009 L02D011 B-C HALL PENTHOUSE Manual 1/20/2025 8:47:36 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Sensitivity 2.12%
Drift Compensation 35%
Smoke Detector - General N009 L02D013 B-C HALL PENTHOUSE Manual 1/20/2025 8:47:38 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Sensitivity 2.12%
Drift Compensation 35%
Smoke Detector - General N009 L02D012 B-C HALL PENTHOUSE Manual 1/20/2025 8:47:40 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Sensitivity 2.12%
Drift Compensation 35%
Manual Fire Box N009 L02M028 B-C HALL PENTHOUSE Manual 1/20/2025 8:47:42 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Smoke Detector - General N009 L02D015 B-C HALL PENTHOUSE Manual 1/20/2025 8:47:43 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Sensitivity 2.12%
Drift Compensation 39%
Manual Fire Box N009 L02M029 B-C HALL PENTHOUSE Manual 1/20/2025 8:47:44 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Smoke Detector - General N009 L02D017 B-C HALL PENTHOUSE Manual 1/20/2025 8:47:46 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Sensitivity 2.12%
Drift Compensation 37%
Smoke Detector - General N009 L02D016 B-C HALL PENTHOUSE Manual 1/20/2025 8:47:47 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Sensitivity 2.12%
Drift Compensation 36%
Smoke Detector - Duct N009 L02D003 B-C HALL RTU-BC-1 Manual 1/20/2025 8:47:49 AM
Page 10 of 21Page 10 of 21Basesix Systems
Functional Inspection Passed
Alarm Sensitivity 2.12%
Drift Compensation 35%
Smoke Detector - Duct N009 L02D002 B-C HALL RTU-BC-1 Manual 1/20/2025 8:47:50 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Sensitivity 2.12%
Drift Compensation 35%
Smoke Detector - Duct N009 L02D006 B-C HALL RTU-BC-3 Manual 1/20/2025 8:47:52 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Sensitivity 2.12%
Drift Compensation 35%
Smoke Detector - Duct N009 L02D005 B-C HALL RTU-BC-2 Manual 1/20/2025 8:47:53 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Sensitivity 2.12%
Drift Compensation 35%
Smoke Detector - Duct N009 L02D007 B-C HALL RTU-BC-3 Manual 1/20/2025 8:47:55 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Sensitivity 2.12%
Drift Compensation 35%
Smoke Detector - Duct N009 L02D008 B-C HALL RTU-BC-4 Manual 1/20/2025 8:47:56 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Sensitivity 2.12%
Drift Compensation 35%
Smoke Detector - Duct N009 L02D009 B-C HALL RTU-BC-4 Manual 1/20/2025 8:47:58 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Sensitivity 2.12%
Drift Compensation 35%
[Other] N009 L02M008 B-C HALL SEF-BC-2 Manual 1/20/2025 8:48:00 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Smoke Detector - Duct N009 L02D004 B-C HALL RTU-BC-2 Manual 1/20/2025 8:48:01 AM
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Sensitivity 2.12%
Drift Compensation 35%
Power Supplies
Passed
Page 11 of 21Page 11 of 21Basesix Systems
Battery - Sealed Lead-acid L1M34 In room bc129 idf battery 1 Manual 1/20/2025 8:44:22 AM
Model 12V7AH
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Minutes 15
Amp Hours 7
Battery Location In panel
Stand By Hours 24
FCPS L1M34 In room bc129 idf Manual 1/20/2025 8:44:25 AM
Manufacturer Wheelock
Model Powerpath
Visual Inspection Passed (Manual)
Functional Inspection Passed
Battery - Sealed Lead-acid L1M34 In room bc129 idf battery 2 Manual 1/20/2025 8:44:28 AM
Model 12V7AH
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Minutes 15
Amp Hours 7
Battery Location In panel
Stand By Hours 24
Page 12 of 21Page 12 of 21Basesix Systems
Battery - Sealed Lead-acid L1M17 In room bc120 idf battery 2 Manual 1/20/2025 8:44:29 AM
Model 12v7ah
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Minutes 15
Amp Hours 7
Battery Location In panel
Stand By Hours 24
Battery - Sealed Lead-acid L1M17 In room bc120 idf battery 1 Manual 1/20/2025 8:44:31 AM
Model 12v7ah
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Minutes 15
Amp Hours 7
Battery Location In panel
Stand By Hours 24
Battery - Sealed Lead-acid L1M36 In room bc120 idf battery 2 Manual 1/20/2025 8:44:32 AM
Model 12V7AH
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Minutes 15
Amp Hours 7
Battery Location In panel
Page 13 of 21Page 13 of 21Basesix Systems
FCPS L1M17 In room bc120 idf Manual 1/20/2025 8:44:35 AM
Manufacturer Wheelock
Model Powerpath
Visual Inspection Passed (Manual)
Functional Inspection Passed
FCPS L1M61 In room bc120 idf Manual 1/20/2025 8:44:37 AM
Manufacturer Wheelock
Model Powerpath
Visual Inspection Passed (Manual)
Functional Inspection Passed
FCPS L1M36 In room bc120 idf Manual 1/20/2025 8:44:38 AM
Manufacturer Wheelock
Model Powerpath
Visual Inspection Passed (Manual)
Page 14 of 21Page 14 of 21Basesix Systems
Battery - Sealed Lead-acid L1M61 In room bc120 idf battery 2 Manual 1/20/2025 8:44:40 AM
Model 12v7ah
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Minutes 15
Amp Hours 7
Battery Location In panel
Stand By Hours 24
Battery - Sealed Lead-acid L1M61 In room bc120 idf battery 1 Manual 1/20/2025 8:44:41 AM
Model 12v7ah
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Minutes 15
Amp Hours 7
Battery Location In panel
Stand By Hours 24
Battery - Sealed Lead-acid L1M36 In room bc120 idf battery 1 Manual 1/20/2025 8:44:43 AM
Model 12V7AH
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Minutes 15
Amp Hours 7
Battery Location In panel
Page 15 of 21Page 15 of 21Basesix Systems
FCPS L1M08 In room bc119 idf Manual 1/20/2025 8:44:45 AM
Manufacturer Wheelock
Model Powerpath
Visual Inspection Passed (Manual)
Functional Inspection Passed
Battery - Sealed Lead-acid L1M08 In room bc119 idf battery 2 Manual 1/20/2025 8:44:46 AM
Model 12V7AH
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Minutes 15
Amp Hours 7
Battery Location In panel
Stand By Hours 24
Battery - Sealed Lead-acid L1M08 In room bc119 idf battery 1 Manual 1/20/2025 8:44:48 AM
Model 12V7AH
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Minutes 15
Amp Hours 7
Battery Location In panel
Page 16 of 21Page 16 of 21Basesix Systems
Battery - Sealed Lead-acid NODE 9 panel In room bc119 idf battery 1 Manual 1/20/2025 8:44:49 AM
Model 12V26ah
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Minutes 15
Amp Hours 26
Battery Location External can
Stand By Hours 24
Battery - Sealed Lead-acid NODE 9 panel In room bc119 idf battery 2 Manual 1/20/2025 8:44:51 AM
Model 12V26ah
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Minutes 15
Amp Hours 26
Battery Location External can
Stand By Hours 24
FACP Node 9 panel In room bc119 idf Manual 1/20/2025 8:44:52 AM
Manufacturer Notifier
Model Ifc2-3030
Visual Inspection Passed (Manual)
Page 17 of 21Page 17 of 21Basesix Systems
Battery - Sealed Lead-acid L1M01 In room b115 battery 2 Manual 1/20/2025 8:44:54 AM
Model 12V 7AH
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Minutes 15
Amp Hours 7
Battery Location In panel
Stand By Hours 24
Battery - Sealed Lead-acid L1M01 In room b115 battery 1 Manual 1/20/2025 8:44:55 AM
Model 12V 7AH
Visual Inspection Passed (Manual)
Functional Inspection Passed
Alarm Minutes 15
Amp Hours 7
Battery Location In panel
Stand By Hours 24
FCPS L1M01 In room b115 Manual 1/20/2025 8:44:58 AM
Manufacturer Wheelock
Model Powerpath
Visual Inspection Passed (Manual)
Page 18 of 21Page 18 of 21Basesix Systems
Device/Equipment Details
Emergency Control Equipment
ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE
[Other]
N009 L01M002 B-C HALL FCPS-1 01/18/2021
N009 L01M003 B-4 SPRINKLER RISER 01/18/2021
N009 L01M005 BC SOUTH HANGER DOOR 01/18/2021
N009 L01M008 B-C HALL FCPS-2 01/18/2021
N009 L01M010 C-4 SPRINKLER RISER 01/18/2021
N009 L01M017 B-C HALL FCPS-3 01/18/2021
N009 L01M028 C-3 SPRINKLER RISER 01/18/2021
N009 L01M031 BC NORTH HANGER DOOR 01/18/2021
N009 L01M033 B-5 SPRINKLER RISER 01/18/2021
N009 L01M035 B-C HALL FCPS-4 01/18/2021
N009 L01M036 B-C HALL FCPS-5 01/18/2021
N009 L01M061 B-C HALL SYNC FCPS 01/18/2021
N009 L02M003 B-C HALL RTU-BC-1 01/18/2021
N009 L02M004 B-C HALL RTU-BC-2 01/18/2021
N009 L02M005 B-C HALL RTU-BC-3 01/18/2021
N009 L02M006 B-C HALL RTU-BC-4 01/18/2021
N009 L02M013 B-C HALL SEF-BC-4 01/18/2021
N009 L02M016 B-C HALL SEF-BC-2 01/18/2021
N009 L02M019 B-C HALL SEF-BC-1 01/18/2021
N009 L02M022 B-C HALL SEF-BC-3 01/18/2021
N009 L02M025 B-C HALL SEF-BC-5 01/18/2021
N009 L02M030 B-C HALL SEF-BC-6 01/18/2021
Fire Control Panel
ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE
Fire Alarm Panel
N009 N009 GEORGIA WORLD CONGRESS
CENTER NODE 9
01/18/2021
Initiating Device
ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE
Smoke Detector - General
N009 L01D001 B-C HALL IDF 01/18/2021
N009 L01D002 B-C HALL IDF 01/18/2021
N009 L01D003 B-C HALL IDF 01/18/2021
N009 L01D004 B-C HALL IDF 01/18/2021
N009 L02D011 B-C HALL PENTHOUSE 01/18/2021
N009 L02D012 B-C HALL PENTHOUSE 01/18/2021
N009 L02D013 B-C HALL PENTHOUSE 01/18/2021
N009 L02D015 B-C HALL PENTHOUSE 01/18/2021
N009 L02D016 B-C HALL PENTHOUSE 01/18/2021
N009 L02D017 B-C HALL PENTHOUSE 01/18/2021
[Other]
N009 L01M001 B-C HALL FCPS-1 01/18/2021
N009 L01M006 BC SOUTH HANGER DOOR 01/18/2021
N009 L01M007 BC SOUTH HANGER DOOR 01/18/2021
N009 L01M009 B-C HALL FCPS-2 01/18/2021
N009 L01M018 B-C HALL FCPS-3 01/18/2021
N009 L01M029 BC NORTH HANGER DOOR 01/18/2021
N009 L01M030 BC NORTH HANGER DOOR 01/18/2021
Page 19 of 21Page 19 of 21Basesix Systems
ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE
N009 L01M034 B-C HALL FCPS-4 01/18/2021
N009 L01M037 B-C HALL FCPS-5 01/18/2021
N009 L01M062 B-C HALL SYNC FCPS 01/18/2021
N009 L01M063 SPRINKLER BELL 01/18/2021
N009 L01M064 SPRINKLER BELL 01/18/2021
N009 L01M065 SPRINKLER BELL 01/18/2021
N009 L01M066 SPRINKLER BELL 01/18/2021
N009 L01M150 GENERAL TROUBLE 01/18/2021
N009 L01M151 AC FAIL 01/18/2021
N009 L01M152 BATTERY 01/18/2021
N009 L01M153 EARTH FAULT 01/18/2021
N009 L01M154 CHARGER FAIL 01/18/2021
N009 L02M001 B-C HALL SEF-BC-4 01/18/2021
N009 L02M002 B-C HALL SEF-BC-1 01/18/2021
N009 L02M007 B-C HALL SEF-BC-3 01/18/2021
N009 L02M008 B-C HALL SEF-BC-2 01/18/2021
N009 L02M009 B-C HALL SEF-BC-6 01/18/2021
N009 L02M010 B-C HALL SEF-BC-5 01/18/2021
N009 L02M014 B-C HALL SEF-BC-4 01/18/2021
N009 L02M015 B-C HALL SEF-BC-4 01/18/2021
N009 L02M017 B-C HALL SEF-BC-2 01/18/2021
N009 L02M018 B-C HALL SEF-BC-2 01/18/2021
N009 L02M020 B-C HALL SEF-BC-1 01/18/2021
N009 L02M021 B-C HALL SEF-BC-1 01/18/2021
N009 L02M023 B-C HALL SEF-BC-3 01/18/2021
N009 L02M024 B-C HALL SEF-BC-3 01/18/2021
N009 L02M026 B-C HALL SEF-BC-5 01/18/2021
N009 L02M027 B-C HALL SEF-BC-5 01/18/2021
N009 L02M031 B-C HALL SEF-BC-6 01/18/2021
N009 L02M032 B-C HALL SEF-BC-6 01/18/2021
Manual Fire Box
N009 L01M004 B-C HALL 01/18/2021
N009 L01M032 B-C HALL 01/18/2021
N009 L01M060 B-C HALL RISER ROOM 01/18/2021
N009 L02M011 B-C HALL PENTHOUSE 01/18/2021
N009 L02M012 B-C HALL PENTHOUSE 01/18/2021
N009 L02M028 B-C HALL PENTHOUSE 01/18/2021
N009 L02M029 B-C HALL PENTHOUSE 01/18/2021
Smoke Detector - Duct
N009 L02D002 B-C HALL RTU-BC-1 01/18/2021
N009 L02D003 B-C HALL RTU-BC-1 01/18/2021
N009 L02D004 B-C HALL RTU-BC-2 01/18/2021
N009 L02D005 B-C HALL RTU-BC-2 01/18/2021
N009 L02D006 B-C HALL RTU-BC-3 01/18/2021
N009 L02D007 B-C HALL RTU-BC-3 01/18/2021
N009 L02D008 B-C HALL RTU-BC-4 01/18/2021
N009 L02D009 B-C HALL RTU-BC-4 01/18/2021
Heat Detector - Restorable Spot
N009 L02D010 B-C HALL PENTHOUSE 01/09/2024
N009 L02D014 B-C HALL PENTHOUSE 01/09/2024
Power Supplies
ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE
Page 20 of 21Page 20 of 21Basesix Systems
FCPS
L1M01 In room b115 Wheelock Powerpath
L1M08 In room bc119 idf Wheelock Powerpath
L1M34 In room bc129 idf Wheelock Powerpath
L1M36 In room bc120 idf Wheelock Powerpath
L1M17 In room bc120 idf Wheelock Powerpath
L1M61 In room bc120 idf Wheelock Powerpath
Battery - Sealed Lead-acid
L1M01 In room b115 battery 1 12V 7AH 02/15/2022
L1M01 In room b115 battery 2 12V 7AH 02/15/2022
L1M08 In room bc119 idf battery 1 12V7AH 02/15/2022
L1M08 In room bc119 idf battery 2 12V7AH 02/15/2022
NODE 9 panel In room bc119 idf battery 1 12V26ah 02/15/2022
NODE 9 panel In room bc119 idf battery 2 12V26ah 02/15/2022
L1M34 In room bc129 idf battery 1 12V7AH 02/15/2022
L1M34 In room bc129 idf battery 2 12V7AH 02/15/2022
L1M36 In room bc120 idf battery 1 12V7AH 02/15/2022
L1M36 In room bc120 idf battery 2 12V7AH 02/15/2022
L1M17 In room bc120 idf battery 1 12v7ah 02/15/2022
L1M17 In room bc120 idf battery 2 12v7ah 02/15/2022
L1M61 In room bc120 idf battery 1 12v7ah 02/15/2022
L1M61 In room bc120 idf battery 2 12v7ah 02/15/2022
FACP
Node 9 panel In room bc119 idf Notifier Ifc2-3030
Page 21 of 21Page 21 of 21Basesix Systems