NFPA72 _ GWCC Node 9 _ Q4 ANNUAL FIRE INSPECT.pdf

PDF 978 KB Posted

Attached to
Fire Alarm Removal and Replacement
Solicitation number
PE-92200-RFP-2026-000000061
Issued by
Fulton County, Georgia

About this file

This is an NFPA 72 fire alarm and signaling system inspection and testing certificate for the Georgia World Congress Center (GWCC) Node 9 facility located at 285 Andrew Young International Blvd NW in Atlanta, Georgia. The inspection was conducted by Basesix Systems, with technician Christopher Kirkbride (NICET Certification #148593) performing the testing on January 20, 2025, and accepted by Kevin Rutledge of GWCC on November 15, 2024. The facility's fire alarm and signaling system comprises 108 total pieces of equipment, including 22 emergency control equipment items, 1 fire control panel, 64 initiating devices, and 21 power supplies. All equipment underwent visual and functional inspections in compliance with NFPA 72 standards, with 100 percent of all tested equipment passing inspection.

The system utilizes sealed lead-acid battery backups with both 12V7AH and 12V26AH configurations strategically located throughout the facility in rooms B115, BC119, BC120, and BC129, providing 24 hours of standby power and 15 minutes of alarm runtime. The fire control panel is a Notifier IFC2-3030 model installed on January 18, 2021, supported by six Wheelock Powerpath FCPS (Fire Control Panel Supply) units. The facility employs multiple categories of detection and notification equipment, including smoke detectors (general and duct-mounted), heat detectors, manual fire boxes, sprinkler risers, and notification appliances distributed throughout the B-C Hall, penthouse, and various mechanical spaces. Battery replacements were conducted on February 15, 2022, ensuring current system reliability. No deficiencies were identified during the inspection, and the system is approved for continued operation.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Inspection and Testing Certificate Presented To

Georgia World Congress Center

For

GWCC Node 9

285 Andrew Young International Blvd NW

Atlanta, Georgia 30313

United States

This site has been inspected and tested in compliance with applicable standards.

Completed Friday, November 15, 2024

Test Session :Q4 ANNUAL FIRE INSPECTION 2024

ACCEPTED BY TESTED BY

Kevin Rutledge

Georgia World Congress Center

285 Andrew Young International Blvd NW Atlanta, Georgia 30313 United States

Christopher Kirkbride

Basesix Systems

2053 Franklin Way Marietta, GA 30067 United States

INSPECTION STATUS

Acceptable

Everything Looks Okay

Basesix Systems

Inspection Summary

Building Information

PROPERTY GWCC Node 9 CONTACT Kevin Rutledge

ADDRESS 285 Andrew Young International Blvd NW

PHONE

CITY/STATE/ZIP Atlanta, Georgia 30313 MOBILE +1 404-392-7027

COUNTRY United States EMAIL krutledge@gwcc.com

Inspector Information

COMPANY Basesix Systems CONTACT Christopher Kirkbride

ADDRESS

2053 Franklin Way Marietta, GA 30067

LICENSE NUMBER Nicet Certification # 148593

PHONE +1 470-590-2691

COUNTRY United States EMAIL ckirkbride@basesix.com

Testing Summary

EQUIPMENT TYPE TOTAL TESTED PASSED FAILED

22 22(100%) 22(100%) 0(0%)

1 1(100%) 1(100%) 0(0%)

64 64(100%) 64(100%) 0(0%)

21 21(100%) 21(100%) 0(0%)

Certification The equipment specified herein was inspected and tested according to the NFPA 72 standard for fire alarm and signaling systems, with the inspection completed on Friday, November 15, 2024

ACCEPTED BY 11/15/2024 TESTED BY 11/15/2024

Kevin Rutledge Christopher Kirkbride

Building Representative Technician

Emergency Control Equipment

Fire Control Panel

Initiating Device

Power Supplies

Page 2 of 21Page 2 of 21Basesix Systems

System Details

Control Units

DESCRIPTION GEORGIA WORLD CONGRESS

CENTER NODE 9

ADDRESS / SCAN ADDRESS N9

S/W VERSIONMANUFACTURER

LAST UPDATEMODEL

S/W LOCATIONSERIAL NUMBER

INSTALL DATE 01/17/2021

Secondary Power TYPE Battery - Sealed Lead-acid DESCRIPTION In room bc119 idf battery 1

ADDRESS / SCAN ADDRESS NODE 9 panel NOMINAL VOLTAGE

LOAD VOLTAGE AMP HOURS 26

STANDBY HOURS 24 ALARM MINUTES 15

BATTERY LOCATION External can CHARGER VOLTAGE

TYPE Battery - Sealed Lead-acid DESCRIPTION In room bc119 idf battery 2

ADDRESS / SCAN ADDRESS NODE 9 panel NOMINAL VOLTAGE

LOAD VOLTAGE AMP HOURS 26

STANDBY HOURS 24 ALARM MINUTES 15

BATTERY LOCATION External can CHARGER VOLTAGE

TYPE Battery - Sealed Lead-acid DESCRIPTION In room b115 battery 2

ADDRESS / SCAN ADDRESS L1M01 NOMINAL VOLTAGE

LOAD VOLTAGE AMP HOURS 7

STANDBY HOURS 24 ALARM MINUTES 15

BATTERY LOCATION In panel CHARGER VOLTAGE

TYPE Battery - Sealed Lead-acid DESCRIPTION In room bc119 idf battery 2

ADDRESS / SCAN ADDRESS L1M08 NOMINAL VOLTAGE

LOAD VOLTAGE AMP HOURS 7

STANDBY HOURS 24 ALARM MINUTES 15

BATTERY LOCATION In panel CHARGER VOLTAGE

TYPE Battery - Sealed Lead-acid DESCRIPTION In room bc120 idf battery 2

ADDRESS / SCAN ADDRESS L1M17 NOMINAL VOLTAGE

LOAD VOLTAGE AMP HOURS 7

STANDBY HOURS 24 ALARM MINUTES 15

BATTERY LOCATION In panel CHARGER VOLTAGE

TYPE Battery - Sealed Lead-acid DESCRIPTION In room bc129 idf battery 2

ADDRESS / SCAN ADDRESS L1M34 NOMINAL VOLTAGE

LOAD VOLTAGE AMP HOURS 7

STANDBY HOURS 24 ALARM MINUTES 15

BATTERY LOCATION In panel CHARGER VOLTAGE

TYPE Battery - Sealed Lead-acid DESCRIPTION In room bc120 idf battery 2

ADDRESS / SCAN ADDRESS L1M36 NOMINAL VOLTAGE

LOAD VOLTAGE AMP HOURS 7

Page 3 of 21Page 3 of 21Basesix Systems

STANDBY HOURS 24 ALARM MINUTES 15

BATTERY LOCATION In panel CHARGER VOLTAGE

TYPE Battery - Sealed Lead-acid DESCRIPTION In room bc120 idf battery 2

ADDRESS / SCAN ADDRESS L1M61 NOMINAL VOLTAGE

LOAD VOLTAGE AMP HOURS 7

STANDBY HOURS 24 ALARM MINUTES 15

BATTERY LOCATION In panel CHARGER VOLTAGE

TYPE Battery - Sealed Lead-acid DESCRIPTION In room b115 battery 1

ADDRESS / SCAN ADDRESS L1M01 NOMINAL VOLTAGE

LOAD VOLTAGE AMP HOURS 7

STANDBY HOURS 24 ALARM MINUTES 15

BATTERY LOCATION In panel CHARGER VOLTAGE

TYPE Battery - Sealed Lead-acid DESCRIPTION In room bc119 idf battery 1

ADDRESS / SCAN ADDRESS L1M08 NOMINAL VOLTAGE

LOAD VOLTAGE AMP HOURS 7

STANDBY HOURS 24 ALARM MINUTES 15

BATTERY LOCATION In panel CHARGER VOLTAGE

TYPE Battery - Sealed Lead-acid DESCRIPTION In room bc120 idf battery 1

ADDRESS / SCAN ADDRESS L1M17 NOMINAL VOLTAGE

LOAD VOLTAGE AMP HOURS 7

STANDBY HOURS 24 ALARM MINUTES 15

BATTERY LOCATION In panel CHARGER VOLTAGE

TYPE Battery - Sealed Lead-acid DESCRIPTION In room bc129 idf battery 1

ADDRESS / SCAN ADDRESS L1M34 NOMINAL VOLTAGE

LOAD VOLTAGE AMP HOURS 7

STANDBY HOURS 24 ALARM MINUTES 15

BATTERY LOCATION In panel CHARGER VOLTAGE

TYPE Battery - Sealed Lead-acid DESCRIPTION In room bc120 idf battery 1

ADDRESS / SCAN ADDRESS L1M36 NOMINAL VOLTAGE

LOAD VOLTAGE AMP HOURS 7

STANDBY HOURS 24 ALARM MINUTES 15

BATTERY LOCATION In panel CHARGER VOLTAGE

TYPE Battery - Sealed Lead-acid DESCRIPTION In room bc120 idf battery 1

ADDRESS / SCAN ADDRESS L1M61 NOMINAL VOLTAGE

LOAD VOLTAGE AMP HOURS 7

STANDBY HOURS 24 ALARM MINUTES 15

BATTERY LOCATION In panel CHARGER VOLTAGE

Page 4 of 21Page 4 of 21Basesix Systems

Page 5 of 21Page 5 of 21Basesix Systems

Testing Details

Emergency Control Equipment

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

[Other] N009 L01M008 B-C HALL FCPS-2 Manual 1/20/2025 8:45:19 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L01M036 B-C HALL FCPS-5 Manual 1/20/2025 8:45:23 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L01M002 B-C HALL FCPS-1 Manual 1/20/2025 8:45:24 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L02M016 B-C HALL SEF-BC-2 Manual 1/20/2025 8:45:33 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L01M035 B-C HALL FCPS-4 Manual 1/20/2025 8:45:39 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L02M030 B-C HALL SEF-BC-6 Manual 1/20/2025 8:45:49 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L02M025 B-C HALL SEF-BC-5 Manual 1/20/2025 8:46:01 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L02M022 B-C HALL SEF-BC-3 Manual 1/20/2025 8:46:09 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L02M019 B-C HALL SEF-BC-1 Manual 1/20/2025 8:46:13 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L02M013 B-C HALL SEF-BC-4 Manual 1/20/2025 8:46:18 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L01M061 B-C HALL SYNC FCPS Manual 1/20/2025 8:46:21 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L01M010 C-4 SPRINKLER RISER Manual 1/20/2025 8:46:34 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L01M028 C-3 SPRINKLER RISER Manual 1/20/2025 8:46:36 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L01M003 B-4 SPRINKLER RISER Manual 1/20/2025 8:46:44 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L01M033 B-5 SPRINKLER RISER Manual 1/20/2025 8:46:46 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L01M017 B-C HALL FCPS-3 Manual 1/20/2025 8:46:58 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Page 6 of 21Page 6 of 21Basesix Systems

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

[Other] N009 L01M031 BC NORTH HANGER DOOR Manual 1/20/2025 8:47:07 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L01M005 BC SOUTH HANGER DOOR Manual 1/20/2025 8:47:11 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L02M003 B-C HALL RTU-BC-1 Manual 1/20/2025 8:47:18 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L02M004 B-C HALL RTU-BC-2 Manual 1/20/2025 8:47:20 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L02M005 B-C HALL RTU-BC-3 Manual 1/20/2025 8:47:21 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L02M006 B-C HALL RTU-BC-4 Manual 1/20/2025 8:47:23 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Fire Control Panel

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

Fire Alarm Panel N009 N009 GEORGIA WORLD CONGRESS

CENTER NODE 9

Manual 1/20/2025 8:46:23 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Initiating Device

Passed

EQUIPMENT TYPE ADDRESS DESCRIPTION METHOD DATE/TIME

[Other] N009 L01M029 BC NORTH HANGER DOOR Event 1/20/2025 8:41:59 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L01M009 B-C HALL FCPS-2 Manual 1/20/2025 8:45:21 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L01M037 B-C HALL FCPS-5 Manual 1/20/2025 8:45:26 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L01M034 B-C HALL FCPS-4 Manual 1/20/2025 8:45:27 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L01M001 B-C HALL FCPS-1 Manual 1/20/2025 8:45:29 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L01M062 B-C HALL SYNC FCPS Manual 1/20/2025 8:45:30 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L02M014 B-C HALL SEF-BC-4 Manual 1/20/2025 8:45:32 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L02M018 B-C HALL SEF-BC-2 Manual 1/20/2025 8:45:36 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L02M002 B-C HALL SEF-BC-1 Manual 1/20/2025 8:45:41 AM

Page 7 of 21Page 7 of 21Basesix Systems

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L02M009 B-C HALL SEF-BC-6 Manual 1/20/2025 8:45:43 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L02M007 B-C HALL SEF-BC-3 Manual 1/20/2025 8:45:45 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L02M032 B-C HALL SEF-BC-6 Manual 1/20/2025 8:45:47 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L02M031 B-C HALL SEF-BC-6 Manual 1/20/2025 8:45:50 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L02M027 B-C HALL SEF-BC-5 Manual 1/20/2025 8:45:52 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L02M026 B-C HALL SEF-BC-5 Manual 1/20/2025 8:45:53 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L02M001 B-C HALL SEF-BC-4 Manual 1/20/2025 8:45:58 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L02M024 B-C HALL SEF-BC-3 Manual 1/20/2025 8:46:00 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L02M023 B-C HALL SEF-BC-3 Manual 1/20/2025 8:46:07 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L02M021 B-C HALL SEF-BC-1 Manual 1/20/2025 8:46:10 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L02M020 B-C HALL SEF-BC-1 Manual 1/20/2025 8:46:11 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L02M017 B-C HALL SEF-BC-2 Manual 1/20/2025 8:46:15 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L02M015 B-C HALL SEF-BC-4 Manual 1/20/2025 8:46:17 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L02M010 B-C HALL SEF-BC-5 Manual 1/20/2025 8:46:20 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L01M030 BC NORTH HANGER DOOR Manual 1/20/2025 8:46:25 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L01M154 CHARGER FAIL Manual 1/20/2025 8:46:26 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L01M153 EARTH FAULT Manual 1/20/2025 8:46:28 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L01M152 BATTERY Manual 1/20/2025 8:46:29 AM

Page 8 of 21Page 8 of 21Basesix Systems

Functional Inspection Passed

[Other] N009 L01M151 AC FAIL Manual 1/20/2025 8:46:31 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L01M150 GENERAL TROUBLE Manual 1/20/2025 8:46:33 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L01M063 SPRINKLER BELL Manual 1/20/2025 8:46:48 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L01M064 SPRINKLER BELL Manual 1/20/2025 8:46:49 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L01M065 SPRINKLER BELL Manual 1/20/2025 8:46:51 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L01M066 SPRINKLER BELL Manual 1/20/2025 8:46:52 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L01M006 BC SOUTH HANGER DOOR Manual 1/20/2025 8:46:57 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L01M018 B-C HALL FCPS-3 Manual 1/20/2025 8:47:00 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

[Other] N009 L01M007 BC SOUTH HANGER DOOR Manual 1/20/2025 8:47:02 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Manual Fire Box N009 L01M060 B-C HALL RISER ROOM Manual 1/20/2025 8:47:13 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Heat Detector - Restorable Spot

N009 L02D010 B-C HALL PENTHOUSE Manual 1/20/2025 8:47:14 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Sensitivity Fixed

Drift Compensation 30%

Heat Detector - Restorable Spot

N009 L02D014 B-C HALL PENTHOUSE Manual 1/20/2025 8:47:16 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Sensitivity Fixed

Drift Compensation 0%

Manual Fire Box N009 L01M004 B-C HALL Manual 1/20/2025 8:47:24 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Manual Fire Box N009 L01M032 B-C HALL Manual 1/20/2025 8:47:25 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General N009 L01D004 B-C HALL IDF Manual 1/20/2025 8:47:27 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Sensitivity 2.12%

Drift Compensation 35%

Smoke Detector - General N009 L01D003 B-C HALL IDF Manual 1/20/2025 8:47:28 AM

Page 9 of 21Page 9 of 21Basesix Systems

Functional Inspection Passed

Alarm Sensitivity 2.12%

Drift Compensation 35%

Smoke Detector - General N009 L01D002 B-C HALL IDF Manual 1/20/2025 8:47:30 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Sensitivity 2.12%

Drift Compensation 35%

Smoke Detector - General N009 L01D001 B-C HALL IDF Manual 1/20/2025 8:47:31 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Sensitivity 2.12%

Drift Compensation 35%

Manual Fire Box N009 L02M011 B-C HALL PENTHOUSE Manual 1/20/2025 8:47:32 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Manual Fire Box N009 L02M012 B-C HALL PENTHOUSE Manual 1/20/2025 8:47:34 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General N009 L02D011 B-C HALL PENTHOUSE Manual 1/20/2025 8:47:36 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Sensitivity 2.12%

Drift Compensation 35%

Smoke Detector - General N009 L02D013 B-C HALL PENTHOUSE Manual 1/20/2025 8:47:38 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Sensitivity 2.12%

Drift Compensation 35%

Smoke Detector - General N009 L02D012 B-C HALL PENTHOUSE Manual 1/20/2025 8:47:40 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Sensitivity 2.12%

Drift Compensation 35%

Manual Fire Box N009 L02M028 B-C HALL PENTHOUSE Manual 1/20/2025 8:47:42 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General N009 L02D015 B-C HALL PENTHOUSE Manual 1/20/2025 8:47:43 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Sensitivity 2.12%

Drift Compensation 39%

Manual Fire Box N009 L02M029 B-C HALL PENTHOUSE Manual 1/20/2025 8:47:44 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - General N009 L02D017 B-C HALL PENTHOUSE Manual 1/20/2025 8:47:46 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Sensitivity 2.12%

Drift Compensation 37%

Smoke Detector - General N009 L02D016 B-C HALL PENTHOUSE Manual 1/20/2025 8:47:47 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Sensitivity 2.12%

Drift Compensation 36%

Smoke Detector - Duct N009 L02D003 B-C HALL RTU-BC-1 Manual 1/20/2025 8:47:49 AM

Page 10 of 21Page 10 of 21Basesix Systems

Functional Inspection Passed

Alarm Sensitivity 2.12%

Drift Compensation 35%

Smoke Detector - Duct N009 L02D002 B-C HALL RTU-BC-1 Manual 1/20/2025 8:47:50 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Sensitivity 2.12%

Drift Compensation 35%

Smoke Detector - Duct N009 L02D006 B-C HALL RTU-BC-3 Manual 1/20/2025 8:47:52 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Sensitivity 2.12%

Drift Compensation 35%

Smoke Detector - Duct N009 L02D005 B-C HALL RTU-BC-2 Manual 1/20/2025 8:47:53 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Sensitivity 2.12%

Drift Compensation 35%

Smoke Detector - Duct N009 L02D007 B-C HALL RTU-BC-3 Manual 1/20/2025 8:47:55 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Sensitivity 2.12%

Drift Compensation 35%

Smoke Detector - Duct N009 L02D008 B-C HALL RTU-BC-4 Manual 1/20/2025 8:47:56 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Sensitivity 2.12%

Drift Compensation 35%

Smoke Detector - Duct N009 L02D009 B-C HALL RTU-BC-4 Manual 1/20/2025 8:47:58 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Sensitivity 2.12%

Drift Compensation 35%

[Other] N009 L02M008 B-C HALL SEF-BC-2 Manual 1/20/2025 8:48:00 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Smoke Detector - Duct N009 L02D004 B-C HALL RTU-BC-2 Manual 1/20/2025 8:48:01 AM

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Sensitivity 2.12%

Drift Compensation 35%

Power Supplies

Passed

Page 11 of 21Page 11 of 21Basesix Systems

Battery - Sealed Lead-acid L1M34 In room bc129 idf battery 1 Manual 1/20/2025 8:44:22 AM

Model 12V7AH

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Minutes 15

Amp Hours 7

Battery Location In panel

Stand By Hours 24

FCPS L1M34 In room bc129 idf Manual 1/20/2025 8:44:25 AM

Manufacturer Wheelock

Model Powerpath

Visual Inspection Passed (Manual)

Functional Inspection Passed

Battery - Sealed Lead-acid L1M34 In room bc129 idf battery 2 Manual 1/20/2025 8:44:28 AM

Model 12V7AH

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Minutes 15

Amp Hours 7

Battery Location In panel

Stand By Hours 24

Page 12 of 21Page 12 of 21Basesix Systems

Battery - Sealed Lead-acid L1M17 In room bc120 idf battery 2 Manual 1/20/2025 8:44:29 AM

Model 12v7ah

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Minutes 15

Amp Hours 7

Battery Location In panel

Stand By Hours 24

Battery - Sealed Lead-acid L1M17 In room bc120 idf battery 1 Manual 1/20/2025 8:44:31 AM

Model 12v7ah

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Minutes 15

Amp Hours 7

Battery Location In panel

Stand By Hours 24

Battery - Sealed Lead-acid L1M36 In room bc120 idf battery 2 Manual 1/20/2025 8:44:32 AM

Model 12V7AH

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Minutes 15

Amp Hours 7

Battery Location In panel

Page 13 of 21Page 13 of 21Basesix Systems

FCPS L1M17 In room bc120 idf Manual 1/20/2025 8:44:35 AM

Manufacturer Wheelock

Model Powerpath

Visual Inspection Passed (Manual)

Functional Inspection Passed

FCPS L1M61 In room bc120 idf Manual 1/20/2025 8:44:37 AM

Manufacturer Wheelock

Model Powerpath

Visual Inspection Passed (Manual)

Functional Inspection Passed

FCPS L1M36 In room bc120 idf Manual 1/20/2025 8:44:38 AM

Manufacturer Wheelock

Model Powerpath

Visual Inspection Passed (Manual)

Page 14 of 21Page 14 of 21Basesix Systems

Battery - Sealed Lead-acid L1M61 In room bc120 idf battery 2 Manual 1/20/2025 8:44:40 AM

Model 12v7ah

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Minutes 15

Amp Hours 7

Battery Location In panel

Stand By Hours 24

Battery - Sealed Lead-acid L1M61 In room bc120 idf battery 1 Manual 1/20/2025 8:44:41 AM

Model 12v7ah

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Minutes 15

Amp Hours 7

Battery Location In panel

Stand By Hours 24

Battery - Sealed Lead-acid L1M36 In room bc120 idf battery 1 Manual 1/20/2025 8:44:43 AM

Model 12V7AH

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Minutes 15

Amp Hours 7

Battery Location In panel

Page 15 of 21Page 15 of 21Basesix Systems

FCPS L1M08 In room bc119 idf Manual 1/20/2025 8:44:45 AM

Manufacturer Wheelock

Model Powerpath

Visual Inspection Passed (Manual)

Functional Inspection Passed

Battery - Sealed Lead-acid L1M08 In room bc119 idf battery 2 Manual 1/20/2025 8:44:46 AM

Model 12V7AH

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Minutes 15

Amp Hours 7

Battery Location In panel

Stand By Hours 24

Battery - Sealed Lead-acid L1M08 In room bc119 idf battery 1 Manual 1/20/2025 8:44:48 AM

Model 12V7AH

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Minutes 15

Amp Hours 7

Battery Location In panel

Page 16 of 21Page 16 of 21Basesix Systems

Battery - Sealed Lead-acid NODE 9 panel In room bc119 idf battery 1 Manual 1/20/2025 8:44:49 AM

Model 12V26ah

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Minutes 15

Amp Hours 26

Battery Location External can

Stand By Hours 24

Battery - Sealed Lead-acid NODE 9 panel In room bc119 idf battery 2 Manual 1/20/2025 8:44:51 AM

Model 12V26ah

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Minutes 15

Amp Hours 26

Battery Location External can

Stand By Hours 24

FACP Node 9 panel In room bc119 idf Manual 1/20/2025 8:44:52 AM

Manufacturer Notifier

Model Ifc2-3030

Visual Inspection Passed (Manual)

Page 17 of 21Page 17 of 21Basesix Systems

Battery - Sealed Lead-acid L1M01 In room b115 battery 2 Manual 1/20/2025 8:44:54 AM

Model 12V 7AH

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Minutes 15

Amp Hours 7

Battery Location In panel

Stand By Hours 24

Battery - Sealed Lead-acid L1M01 In room b115 battery 1 Manual 1/20/2025 8:44:55 AM

Model 12V 7AH

Visual Inspection Passed (Manual)

Functional Inspection Passed

Alarm Minutes 15

Amp Hours 7

Battery Location In panel

Stand By Hours 24

FCPS L1M01 In room b115 Manual 1/20/2025 8:44:58 AM

Manufacturer Wheelock

Model Powerpath

Visual Inspection Passed (Manual)

Page 18 of 21Page 18 of 21Basesix Systems

Device/Equipment Details

Emergency Control Equipment

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

[Other]

N009 L01M002 B-C HALL FCPS-1 01/18/2021

N009 L01M003 B-4 SPRINKLER RISER 01/18/2021

N009 L01M005 BC SOUTH HANGER DOOR 01/18/2021

N009 L01M008 B-C HALL FCPS-2 01/18/2021

N009 L01M010 C-4 SPRINKLER RISER 01/18/2021

N009 L01M017 B-C HALL FCPS-3 01/18/2021

N009 L01M028 C-3 SPRINKLER RISER 01/18/2021

N009 L01M031 BC NORTH HANGER DOOR 01/18/2021

N009 L01M033 B-5 SPRINKLER RISER 01/18/2021

N009 L01M035 B-C HALL FCPS-4 01/18/2021

N009 L01M036 B-C HALL FCPS-5 01/18/2021

N009 L01M061 B-C HALL SYNC FCPS 01/18/2021

N009 L02M003 B-C HALL RTU-BC-1 01/18/2021

N009 L02M004 B-C HALL RTU-BC-2 01/18/2021

N009 L02M005 B-C HALL RTU-BC-3 01/18/2021

N009 L02M006 B-C HALL RTU-BC-4 01/18/2021

N009 L02M013 B-C HALL SEF-BC-4 01/18/2021

N009 L02M016 B-C HALL SEF-BC-2 01/18/2021

N009 L02M019 B-C HALL SEF-BC-1 01/18/2021

N009 L02M022 B-C HALL SEF-BC-3 01/18/2021

N009 L02M025 B-C HALL SEF-BC-5 01/18/2021

N009 L02M030 B-C HALL SEF-BC-6 01/18/2021

Fire Control Panel

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Fire Alarm Panel

N009 N009 GEORGIA WORLD CONGRESS

CENTER NODE 9

01/18/2021

Initiating Device

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Smoke Detector - General

N009 L01D001 B-C HALL IDF 01/18/2021

N009 L01D002 B-C HALL IDF 01/18/2021

N009 L01D003 B-C HALL IDF 01/18/2021

N009 L01D004 B-C HALL IDF 01/18/2021

N009 L02D011 B-C HALL PENTHOUSE 01/18/2021

N009 L02D012 B-C HALL PENTHOUSE 01/18/2021

N009 L02D013 B-C HALL PENTHOUSE 01/18/2021

N009 L02D015 B-C HALL PENTHOUSE 01/18/2021

N009 L02D016 B-C HALL PENTHOUSE 01/18/2021

N009 L02D017 B-C HALL PENTHOUSE 01/18/2021

[Other]

N009 L01M001 B-C HALL FCPS-1 01/18/2021

N009 L01M006 BC SOUTH HANGER DOOR 01/18/2021

N009 L01M007 BC SOUTH HANGER DOOR 01/18/2021

N009 L01M009 B-C HALL FCPS-2 01/18/2021

N009 L01M018 B-C HALL FCPS-3 01/18/2021

N009 L01M029 BC NORTH HANGER DOOR 01/18/2021

N009 L01M030 BC NORTH HANGER DOOR 01/18/2021

Page 19 of 21Page 19 of 21Basesix Systems

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

N009 L01M034 B-C HALL FCPS-4 01/18/2021

N009 L01M037 B-C HALL FCPS-5 01/18/2021

N009 L01M062 B-C HALL SYNC FCPS 01/18/2021

N009 L01M063 SPRINKLER BELL 01/18/2021

N009 L01M064 SPRINKLER BELL 01/18/2021

N009 L01M065 SPRINKLER BELL 01/18/2021

N009 L01M066 SPRINKLER BELL 01/18/2021

N009 L01M150 GENERAL TROUBLE 01/18/2021

N009 L01M151 AC FAIL 01/18/2021

N009 L01M152 BATTERY 01/18/2021

N009 L01M153 EARTH FAULT 01/18/2021

N009 L01M154 CHARGER FAIL 01/18/2021

N009 L02M001 B-C HALL SEF-BC-4 01/18/2021

N009 L02M002 B-C HALL SEF-BC-1 01/18/2021

N009 L02M007 B-C HALL SEF-BC-3 01/18/2021

N009 L02M008 B-C HALL SEF-BC-2 01/18/2021

N009 L02M009 B-C HALL SEF-BC-6 01/18/2021

N009 L02M010 B-C HALL SEF-BC-5 01/18/2021

N009 L02M014 B-C HALL SEF-BC-4 01/18/2021

N009 L02M015 B-C HALL SEF-BC-4 01/18/2021

N009 L02M017 B-C HALL SEF-BC-2 01/18/2021

N009 L02M018 B-C HALL SEF-BC-2 01/18/2021

N009 L02M020 B-C HALL SEF-BC-1 01/18/2021

N009 L02M021 B-C HALL SEF-BC-1 01/18/2021

N009 L02M023 B-C HALL SEF-BC-3 01/18/2021

N009 L02M024 B-C HALL SEF-BC-3 01/18/2021

N009 L02M026 B-C HALL SEF-BC-5 01/18/2021

N009 L02M027 B-C HALL SEF-BC-5 01/18/2021

N009 L02M031 B-C HALL SEF-BC-6 01/18/2021

N009 L02M032 B-C HALL SEF-BC-6 01/18/2021

Manual Fire Box

N009 L01M004 B-C HALL 01/18/2021

N009 L01M032 B-C HALL 01/18/2021

N009 L01M060 B-C HALL RISER ROOM 01/18/2021

N009 L02M011 B-C HALL PENTHOUSE 01/18/2021

N009 L02M012 B-C HALL PENTHOUSE 01/18/2021

N009 L02M028 B-C HALL PENTHOUSE 01/18/2021

N009 L02M029 B-C HALL PENTHOUSE 01/18/2021

Smoke Detector - Duct

N009 L02D002 B-C HALL RTU-BC-1 01/18/2021

N009 L02D003 B-C HALL RTU-BC-1 01/18/2021

N009 L02D004 B-C HALL RTU-BC-2 01/18/2021

N009 L02D005 B-C HALL RTU-BC-2 01/18/2021

N009 L02D006 B-C HALL RTU-BC-3 01/18/2021

N009 L02D007 B-C HALL RTU-BC-3 01/18/2021

N009 L02D008 B-C HALL RTU-BC-4 01/18/2021

N009 L02D009 B-C HALL RTU-BC-4 01/18/2021

Heat Detector - Restorable Spot

N009 L02D010 B-C HALL PENTHOUSE 01/09/2024

N009 L02D014 B-C HALL PENTHOUSE 01/09/2024

Power Supplies

ADDRESS DESCRIPTION MANUFACTURER MODEL SERIAL INSTALL DATE

Page 20 of 21Page 20 of 21Basesix Systems

FCPS

L1M01 In room b115 Wheelock Powerpath

L1M08 In room bc119 idf Wheelock Powerpath

L1M34 In room bc129 idf Wheelock Powerpath

L1M36 In room bc120 idf Wheelock Powerpath

L1M17 In room bc120 idf Wheelock Powerpath

L1M61 In room bc120 idf Wheelock Powerpath

Battery - Sealed Lead-acid

L1M01 In room b115 battery 1 12V 7AH 02/15/2022

L1M01 In room b115 battery 2 12V 7AH 02/15/2022

L1M08 In room bc119 idf battery 1 12V7AH 02/15/2022

L1M08 In room bc119 idf battery 2 12V7AH 02/15/2022

NODE 9 panel In room bc119 idf battery 1 12V26ah 02/15/2022

NODE 9 panel In room bc119 idf battery 2 12V26ah 02/15/2022

L1M34 In room bc129 idf battery 1 12V7AH 02/15/2022

L1M34 In room bc129 idf battery 2 12V7AH 02/15/2022

L1M36 In room bc120 idf battery 1 12V7AH 02/15/2022

L1M36 In room bc120 idf battery 2 12V7AH 02/15/2022

L1M17 In room bc120 idf battery 1 12v7ah 02/15/2022

L1M17 In room bc120 idf battery 2 12v7ah 02/15/2022

L1M61 In room bc120 idf battery 1 12v7ah 02/15/2022

L1M61 In room bc120 idf battery 2 12v7ah 02/15/2022

FACP

Node 9 panel In room bc119 idf Notifier Ifc2-3030

Page 21 of 21Page 21 of 21Basesix Systems