Georgia World Congress Center _ Bldg A _ Semi.pdf
PDF 292 KB Posted
- Attached to
- Fire Alarm Removal and Replacement
- Solicitation number
- PE-92200-RFP-2026-000000061
- Issued by
- Fulton County, Georgia
About this file
This is a Semiannual Sprinkler Report for Georgia World Congress Center - Building A, located at 285 Andrew Young International Boulevard, Atlanta, Georgia, inspected and tested per NFPA 25 standards on June 9, 2025, by Century Fire Protection. The inspection was conducted by licensed inspector Shawn Bennington (License #IL 000310) and covers the comprehensive testing of water-based and dry sprinkler systems throughout the facility. The report documents the inspection and flow testing of 19 wet system modules and 4 dry system modules, along with supervisory switches, waterflow alarms, tampers, main drains, and sectional valves. All devices tested were left in operational condition upon completion of the inspection.
The inspection summary reveals that of the devices tested, four supervisory switches passed, 21 of 22 waterflow alarms passed with one failure, all 37 tampers passed, all 23 main drains passed, 17 of 19 wet systems passed with two failures, and two of four dry systems passed with two failures. Specific deficiencies were identified in the A1 Auditorium Standpipe (module 332) and A1 Point Lobby (module 333) wet systems, both requiring alarm system repairs, and in the A3 Lower North Exit (module 341/350) and A2 Lower South Exit (module 342/355) dry systems, with notation that data placards are missing from the lower exit dry systems. Static pressure readings consistently measured 165 PSI across all tested systems with residual pressures of 155 PSI, indicating normal water supply conditions. All gauges on both wet and dry pipe systems were found to be in good condition with normal water supply pressure confirmed.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2450 Satellite Boulevard Duluth, GA 30096 Office: (770) 506-2388 centuryfp.com
Semiannual Sprinkler Report Inspected and tested per NFPA 25
Inspected Site Georgia World Congress Center - Bldg A
285 Andrew Young Intern. Blvd Atlanta, GA 30313
Date/Time 06/09/2025 08:02 Inspection Reference # 39599378
Conducted by: Shawn Bennington License # IL 000310
Backflow License #
Prepared For Georgia World Congress Center 285 Andrew Young International
Atlanta, GA 30313
Inspection and Testing Summary
Device Description Total Devices Number Inspected/Tested Number Passed Number Failed
Supervisory Switch 4 4 4 0
Waterflow Alarms 22 22 21 1
Tampers 37 37 37 0
Main Drains 23 23 23 0
Wet System 19 19 17 2
Dry System 4 4 2 2
Sectional Valve 15 15 15 0
Report of Inspection / Test Water Based System Inspection
Date: 06/09/2025 08:02
Inspection Site
Georgia World Congress Center - Bldg A 285 Andrew Young Intern. Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599378
1 of 19 Wet System - Semiannual | A3 South (module 306/337)
Control Valve & Flow Test on Wet System- Semiannual | A3 South (module 306/337)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
A3 South (module 306/337) Main Drain 2 165 165 155 Green Yes
Type OS&Y Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .26/4200
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
2 of 19 Wet System - Semiannual | A3 North (module 308/337)
Control Valve & Flow Test on Wet System- Semiannual | A3 North (module 308/337)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
A3 North (module 308/337) Main Drain 2 165 165 155 Green Yes
Type OS&Y Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .26/4200
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
3 of 19 Wet System - Semiannual | A3 Center (module 307/337)
Control Valve & Flow Test on Wet System- Semiannual | A3 Center (module 307/337)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
A3 Center (module 307/337) Main Drain 2 165 165 155 Green Yes
Date: 06/09/2025 08:02
Inspection Site
Georgia World Congress Center - Bldg A 285 Andrew Young Intern. Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599378
Type OS&Y Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .26/4200
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
4 of 19 Wet System - Semiannual | A1 South Hall (module 301/332)
Control Valve & Flow Test on Wet System- Semiannual | A1 South Hall (module 301/332)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
A1 South Hall (module 301/332)
Main Drain 2 165 165 155 Green Yes
Type Butterfly Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .26/4200
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
5 of 19 Wet System - Semiannual | A1 Auditorium Standpipe (module 332)
Control Valve & Flow Test on Wet System- Semiannual | A1 Auditorium Standpipe (module 332)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
A1 Auditorium Standpipe (module 332)
Main Drain 2 165 165 155 Yellow Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm FAIL Time for Alarm Density .19/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Date: 06/09/2025 08:02
Inspection Site
Georgia World Congress Center - Bldg A 285 Andrew Young Intern. Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599378
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
6 of 19 Wet System - Semiannual | A1 Bellsouth (module 313)
Control Valve & Flow Test on Wet System- Semiannual | A1 Bellsouth (module 313)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
A1 Bellsouth (module 313) Main Drain 1 165 165 155 Green Yes
Type OS&Y Seal # 0 Size 2 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density N/A
Verification Seal Color
N/A Secured Type Chain & Lock
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? N/A Five Year Internal Year
7 of 19 Wet System - Semiannual | A1 Point Lobby (module 333)
Control Valve & Flow Test on Wet System- Semiannual | A1 Point Lobby (module 333)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
A1 Point Lobby (module 333) Main Drain 2 165 165 155 Yellow Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm FAIL Time for Alarm Density .10/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
Date: 06/09/2025 08:02
Inspection Site
Georgia World Congress Center - Bldg A 285 Andrew Young Intern. Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599378
8 of 19 Wet System - Semiannual | A1 Restrooms (module 309/333)
Control Valve & Flow Test on Wet System- Semiannual | A1 Restrooms (module 309/333)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
A1 Restrooms (module 309/333)
Main Drain 1 165 165 155 Green Yes
Type OS&Y Seal # 0 Size 3 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .10/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
9 of 19 Wet System - Semiannual | A1 North (module 303/334)
Control Valve & Flow Test on Wet System- Semiannual | A1 North (module 303/334)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
A1 North (module 303/334) Main Drain 2 165 165 155 Green Yes
Type Butterfly Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .26/4200
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
10 of 19 Wet System - Semiannual | A1 Center (module 302/334)
Control Valve & Flow Test on Wet System- Semiannual | A1 Center (module 302/334)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to
A1 Center (module 302/334) Main Drain 2 165 165 155 Green Yes
Date: 06/09/2025 08:02
Inspection Site
Georgia World Congress Center - Bldg A 285 Andrew Young Intern. Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599378
Type Butterfly Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .26/4200
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
11 of 19 Wet System - Semiannual | A2 Hall South (module 304/335)
Control Valve & Flow Test on Wet System- Semiannual | A2 Hall South (module 304/335)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
A2 Hall South (module 304/335)
Main Drain 2 165 165 155 Green Yes
Type Butterfly Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .26/4200
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
12 of 19 Wet System - Semiannual | A2 Level 4 North (module 318/336)
Control Valve & Flow Test on Wet System- Semiannual | A2 Level 4 North (module 318/336)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
A2 Level 4 North (module 318/336)
Main Drain 1 165 165 155 Green Yes
Type OS&Y Seal # 0 Size 3 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .10/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Date: 06/09/2025 08:02
Inspection Site
Georgia World Congress Center - Bldg A 285 Andrew Young Intern. Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599378
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
13 of 19 Wet System - Semiannual | A2 Level 3 North (module 315/336)
Control Valve & Flow Test on Wet System- Semiannual | A2 Level 3 North (module 315/336)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
A2 Level 3 North (module 315/336)
Main Drain 1 165 165 155 Green Yes
Type OS&Y Seal # 0 Size 3 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .10/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
14 of 19 Wet System - Semiannual | A2 Catering (module 310/336)
Control Valve & Flow Test on Wet System- Semiannual | A2 Catering (module 310/336)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
A2 Catering (module 310/336) Main Drain 1 165 165 155 Green Yes
Type OS&Y Seal # 0 Size 3 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .10/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES indicate movement? YES Five Year Internal Year
Date: 06/09/2025 08:02
Inspection Site
Georgia World Congress Center - Bldg A 285 Andrew Young Intern. Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599378
15 of 19 Wet System - Semiannual | A2 North (module 305/336)
Control Valve & Flow Test on Wet System- Semiannual | A2 North (module 305/336)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
A2 North (module 305/336) Main Drain 2 165 165 155 Green Yes
Type Butterfly Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density 0.26/4200
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
16 of 19 Wet System - Semiannual | A4 Center (module 317/339)
Control Valve & Flow Test on Wet System- Semiannual | A4 Center (module 317/339)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
A4 Center (module 317/339) Main Drain 0.5 Green N/A
Type OS&Y Seal # 0 Size 3 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density N/A
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
17 of 19 Wet System - Semiannual | A3 Center (module 314/339)
Control Valve & Flow Test on Wet System- Semiannual | A3 Center (module 314/339)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to
A3 Center (module 314/339) Main Drain 1 Green N/A
Date: 06/09/2025 08:02
Inspection Site
Georgia World Congress Center - Bldg A 285 Andrew Young Intern. Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599378
Type OS&Y Seal # 0 Size 3 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density N/A
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
18 of 19 Wet System - Semiannual | Level 2 South (module 316/340)
Control Valve & Flow Test on Wet System- Semiannual | Level 2 South (module 316/340)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Level 2 South (module 316/340) Main Drain 0.5 Green N/A
Type OS&Y Seal # 0 Size 3 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density N/A
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
19 of 19 Wet System - Semiannual | Auditorium (module 319/340)
Control Valve & Flow Test on Wet System- Semiannual | Auditorium (module 319/340)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Auditorium (module 319/340) Main Drain 0.5 Green N/A
Type OS&Y Seal # 0 Size 3 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density N/A
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing YES Alarm devices free from physical damage? YES
Date: 06/09/2025 08:02
Inspection Site
Georgia World Congress Center - Bldg A 285 Andrew Young Intern. Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599378 normal water supply pressure
Valve supervisory switches indicate movement? YES Five Year Internal Year
1 of 4 Dry System - Semiannual | A3 Lower North Exit (module 341/350)
Control Valve & Flow Test on Dry System- Semiannual | A3 Lower North Exit (module 341/350)
System ID Connection
Flowed Outlet Size Static PSI Residual PSI
Static PSI After Test
Time to Restore Air Pressure Tag Color Results comparable to prior year?
A3 Lower North Exit (module 341/350)
Main Drain 2 in 165 155 165 42 Yellow Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density Data placard is missing
Verification Seal Color
N/A Secured Type Electric Tamper
General
Comment
Dry Pipe Sprinkler System Inspection
Gauges on dry pipe system in good condition and showing normal water supply pressure YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year Last Full Trip Test Year
2 of 4 Dry System - Semiannual | A2 Lower South Exit (module 342/355)
Control Valve & Flow Test on Dry System- Semiannual | A2 Lower South Exit (module 342/355)
System ID Connection
Flowed Outlet Size Static PSI Residual PSI
Static PSI After Test
Time to Restore Air Pressure Tag Color Results comparable to prior year?
A2 Lower South Exit (module 342/355)
Main Drain 2 in 165 155 165 58 Yellow Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density Data placard is missing
Verification Seal Color
N/A Secured Type Electric Tamper
General
Comment
Date: 06/09/2025 08:02
Inspection Site
Georgia World Congress Center - Bldg A 285 Andrew Young Intern. Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599378
Dry Pipe Sprinkler System Inspection
Gauges on dry pipe system in good condition and showing normal water supply pressure YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year Last Full Trip Test Year
3 of 4 Dry System - Semiannual | South Dock (module 311/333)
Control Valve & Flow Test on Dry System- Semiannual | South Dock (module 311/333)
System ID Connection
Flowed Outlet Size Static PSI Residual PSI
Static PSI After Test
Time to Restore Air Pressure Tag Color Results comparable to prior year?
South Dock (module 311/333) Main Drain 2 in 165 155 165 50 Green Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .19/1950
Verification Seal Color
N/A Secured Type Electric Tamper
General
Comment
Dry Pipe Sprinkler System Inspection
Gauges on dry pipe system in good condition and showing normal water supply pressure YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year Last Full Trip Test Year
4 of 4 Dry System - Semiannual | North Dock (module 312/338)
Control Valve & Flow Test on Dry System- Semiannual | North Dock (module 312/338)
System ID Connection
Flowed Outlet Size Static PSI Residual PSI
Static PSI After Test
Time to Restore Air Pressure Tag Color Results comparable to prior year?
North Dock (module 312/338) Main Drain 2 in 165 155 165 38 Green Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .19/1950
Verification Seal Color
N/A Secured Type Electric Tamper
General
Comment
Date: 06/09/2025 08:02
Inspection Site
Georgia World Congress Center - Bldg A 285 Andrew Young Intern. Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599378
Dry Pipe Sprinkler System Inspection
Gauges on dry pipe system in good condition and showing normal water supply pressure YES Alarm devices free from physical damage? YES indicate movement? YES Five Year Internal Year Last Full Trip Test Year
Date: 06/09/2025 08:02
Inspection Site
Georgia World Congress Center - Bldg A 285 Andrew Young Intern. Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599378
Wet Sprinklers
Location A1 Auditorium Standpipe (module 332)
System Type/Name Deficiency Comments
A1 Auditorium Standpipe (module 332)
Wet Sprinkler Results:
The System has failed
A1 Auditorium Standpipe (module 332) A1 Auditorium Standpipe (module 332)
Control Valves:
Alarm
Need to install a 4” flow switch and wire it to the electric bell that was installed to replace water motor gong.
A1 Auditorium Standpipe (module 332) A1 Auditorium Standpipe (module 332)
Control Valves:
Labeled Yellow Tag
Location A1 Point Lobby (module 333)
System Type/Name Deficiency Comments
A1 Point Lobby (module 333)
Wet Sprinkler Results:
The System has failed
A1 Point Lobby (module 333) A1 Point Lobby (module 333)
Control Valves:
Alarm
Water motor gong didn’t operate.
A1 Point Lobby (module 333) A1 Point Lobby (module 333)
Control Valves:
Labeled Yellow Tag
Dry Sprinklers
Location A3 Lower North Exit (module 341/350)
System Type/Name Deficiency Comments
A3 Lower North Exit (module 341/350) Dry 1
Dry Sprinkler Results:
The System has failed
A3 Lower North Exit (module 341/350) A3 Lower North Exit (module 341/350)
Control Valves:
Labeled Yellow Tag
Location A2 Lower South Exit (module 342/355)
System Type/Name Deficiency Comments
A2 Lower South Exit (module 342/355) Dry 2
Dry Sprinkler Results:
The System has failed
A2 Lower South Exit (module 342/355) A2 Lower South Exit (module 342/355)
Control Valves:
Labeled Yellow Tag
Sectional Valve
System Type/Name System Type/Name Comments
Date: 06/09/2025 08:02
Inspection Site
Georgia World Congress Center - Bldg A 285 Andrew Young Intern. Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599378
Owner's Section
Has the occupancy classification and hazard of contents remained the same since last inspection? N/A
Has the system remained in service without modification since the last inspection? N/A
Has an internal inspection been performed within the past 5 years? N/A
Are all the protection systems in service? Yes
Was the system free of actuation of devices and alarms since the last inspection? N/A
Statement
I state the information on this form is correct at the time and place of my inspection, and that all equipment tested at this time was left in operation condition upon completion of this inspection except as noted.
| A3 Lower North Exit (module 341/350) Dry 1 |
| A2 Lower South Exit (module 342/355) Dry 2 |