Georgia World Congress Center _ Bldg C _ Semi.pdf
PDF 333 KB Posted
- Attached to
- Fire Alarm Removal and Replacement
- Solicitation number
- PE-92200-RFP-2026-000000061
- Issued by
- Fulton County, Georgia
About this file
This is a Semiannual Sprinkler Report documenting fire protection system inspection and testing conducted at Georgia World Congress Center - Building C in Atlanta, Georgia on June 11, 2025. The inspection was performed by Century Fire Protection (based in Duluth, Georgia) and conducted by licensed inspector Shawn Bennington under inspection reference number 39600290. The report details comprehensive testing of fire suppression systems across the facility, including 40 wet systems, 8 dry systems, 8 supervisory switches, 48 waterflow alarms, 120 tampers, 48 main drains, and 72 sectional valves. All devices were inspected and tested per NFPA 25 standards. The inspection summary indicates that 39 of 40 wet systems passed testing, with one wet system (Stair 41 System 10) failing due to a missing data placard on the control valve, which was marked with a yellow tag.
The inspection revealed that all sprinkler systems, control valves, alarms, and supervisory switches were in proper working condition with adequate water supply pressure and functioning alarm devices. Static pressure readings ranged from 150 to 170 PSI across various systems, with residual pressures between 140 and 160 PSI. Dry pipe systems demonstrated air pressure restoration times ranging from 22 to 48 seconds. All tested components including butterfly and OS&Y valves, tampers, and alarm mechanisms passed their respective functional tests. The one deficiency identified was the missing data placard on the Stair 41 System 10 sectional valve, which requires correction. The facility's fire protection infrastructure remained substantially operational and compliant with inspection standards as of the inspection date.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2450 Satellite Boulevard Duluth, GA 30096 Office: (770) 506-2388 centuryfp.com
Semiannual Sprinkler Report Inspected and tested per NFPA 25
Inspected Site Georgia World Congress Center - Bldg C 285 Andrew Young International Blvd
Atlanta, GA 30313 Date/Time 06/11/2025 08:01
Inspection Reference # 39600290 Conducted by: Shawn Bennington
License # IL 000310 Backflow License #
Prepared For Georgia World Congress Center 285 Andrew Young International
Atlanta, GA 30313
Inspection and Testing Summary
Device Description Total Devices Number Inspected/Tested Number Passed Number Failed
Supervisory Switch 8 8 8 0
Waterflow Alarms 48 48 48 0
Tampers 120 120 120 0
Main Drains 48 48 48 0
Wet System 40 40 39 1
Dry System 8 8 8 0
Sectional Valve 72 72 72 0
Report of Inspection / Test Water Based System Inspection
Date: 06/11/2025 08:01
Inspection Site
Georgia World Congress Center - Bldg C 285 Andrew Young International Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39600290
1 of 40 Wet System - Semiannual | Node 2 System 24 (module 164/163)
Control Valve & Flow Test on Wet System- Semiannual | Node 2 System 24 (module 164/163)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Node 2 System 24 (module 164/163)
Main Drain 2 170 170 160 Green Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
2 of 40 Wet System - Semiannual | C1 Wall Pocket System 39 (module (321/313)
Control Valve & Flow Test on Wet System- Semiannual | C1 Wall Pocket System 39 (module (321/313)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
C1 Wall Pocket System 39 (module (321/313)
Main Drain 2 170 170 160 Green Yes
Type Butterfly Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .30/4000
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
3 of 40 Wet System - Semiannual | C1 Wall Pocket System 40 (module 320/313)
Control Valve & Flow Test on Wet System- Semiannual | C1 Wall Pocket System 40 (module 320/313)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
C1 Wall Pocket System 40 (module 320/313)
Main Drain 2 170 170 160 Green Yes
Date: 06/11/2025 08:01
Inspection Site
Georgia World Congress Center - Bldg C 285 Andrew Young International Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39600290
Type Butterfly Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .30/4000
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
4 of 40 Wet System - Semiannual | C1 Wall Pocket System 41 (module 319/312)
Control Valve & Flow Test on Wet System- Semiannual | C1 Wall Pocket System 41 (module 319/312)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
C1 Wall Pocket System 41 (module 319/312)
Main Drain 2 170 170 160 Green Yes
Type Butterfly Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .30/4000
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
5 of 40 Wet System - Semiannual | C1 Wall Pocket System 42 (module 318/312)
Control Valve & Flow Test on Wet System- Semiannual | C1 Wall Pocket System 42 (module 318/312)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
C1 Wall Pocket System 42 (module 318/312)
Main Drain 2 170 170 160 Green Yes
Type Butterfly Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .30/4000
Verification Seal Color
N/A Secured Type Electric Tamper
Date: 06/11/2025 08:01
Inspection Site
Georgia World Congress Center - Bldg C 285 Andrew Young International Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39600290
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
6 of 40 Wet System - Semiannual | C1 Wall Pocket System 43 (module 317/311)
Control Valve & Flow Test on Wet System- Semiannual | C1 Wall Pocket System 43 (module 317/311)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
C1 Wall Pocket System 43 (module 317/311)
Main Drain 2 170 170 160 Green Yes
Type Butterfly Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .30/4000
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
7 of 40 Wet System - Semiannual | C1 Wall Pocket System 44 (module 316/311)
Control Valve & Flow Test on Wet System- Semiannual | C1 Wall Pocket System 44 (module 316/311)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
C1 Wall Pocket System 44 (module 316/311)
Main Drain 2 170 170 160 Green Yes
Type Butterfly Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .30/4000
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
Date: 06/11/2025 08:01
Inspection Site
Georgia World Congress Center - Bldg C 285 Andrew Young International Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39600290
8 of 40 Wet System - Semiannual | C1 Wall Pocket System 8 (module 315/310)
Control Valve & Flow Test on Wet System- Semiannual | C1 Wall Pocket System 8 (module 315/310)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
C1 Wall Pocket System 8 (module 315/310)
Main Drain 2 170 170 160 Green Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
9 of 40 Wet System - Semiannual | C2 Wall Pocket System 7 (module 372/369)
Control Valve & Flow Test on Wet System- Semiannual | C2 Wall Pocket System 7 (module 372/369)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
C2 Wall Pocket System 7 (module 372/369)
Main Drain 2 170 170 160 Green Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
10 of 40 Wet System - Semiannual | C3 Exhibit Hall System 36 (module 423/422)
Control Valve & Flow Test on Wet System- Semiannual | C3 Exhibit Hall System 36 (module 423/422)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
C3 Exhibit Hall System 36 (module 423/422)
Date: 06/11/2025 08:01
Inspection Site
Georgia World Congress Center - Bldg C 285 Andrew Young International Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39600290
Type Butterfly Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .30/4000
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
11 of 40 Wet System - Semiannual | C3 Exhibit Hall System 37 (module 425/424)
Control Valve & Flow Test on Wet System- Semiannual | C3 Exhibit Hall System 37 (module 425/424)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
C3 Exhibit Hall System 37 (module 425/424)
Main Drain 2 170 170 160 Green Yes
Type Butterfly Seal # 0 Size 2 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .30/4000
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
12 of 40 Wet System - Semiannual | C3 Exhibit Hall System 38 (module 427/426)
Control Valve & Flow Test on Wet System- Semiannual | C3 Exhibit Hall System 38 (module 427/426)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
C3 Exhibit Hall System 38 (module 427/426)
Main Drain 2 170 170 160 Green Yes
Type Butterfly Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .20/1500
Verification Seal
Date: 06/11/2025 08:01
Inspection Site
Georgia World Congress Center - Bldg C 285 Andrew Young International Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39600290
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
13 of 40 Wet System - Semiannual | C4 Exhibit Hall Fire Hose Connection (module 445/437)
Control Valve & Flow Test on Wet System- Semiannual | C4 Exhibit Hall Fire Hose Connection (module 445/437)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
C4 Exhibit Hall Fire Hose Connection (module 445/437)
Main Drain 2 170 170 160 Green Yes
Type Butterfly Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .10/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
14 of 40 Wet System - Semiannual | C4 Exhibit Hall System 33 (module 444/434)
Control Valve & Flow Test on Wet System- Semiannual | C4 Exhibit Hall System 33 (module 444/434)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
C4 Exhibit Hall System 33 (module 444/434)
Main Drain 2 170 170 160 Green Yes
Type Butterfly Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Date: 06/11/2025 08:01
Inspection Site
Georgia World Congress Center - Bldg C 285 Andrew Young International Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39600290
15 of 40 Wet System - Semiannual | C4 Exhibit Hall System 35 (module 442/435)
Control Valve & Flow Test on Wet System- Semiannual | C4 Exhibit Hall System 35 (module 442/435)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
C4 Exhibit Hall System 35 (module 442/435)
Main Drain 2 170 170 160 Green Yes
Type Butterfly Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .30/4000
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
16 of 40 Wet System - Semiannual | C4 Exhibit Hall System 34 (module 443/436)
Control Valve & Flow Test on Wet System- Semiannual | C4 Exhibit Hall System 34 (module 443/436)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
C4 Exhibit Hall System 34 (module 443/436)
Main Drain 2 170 170 160 Green Yes
Type Butterfly Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .10/1098
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
17 of 40 Wet System - Semiannual | C4 North Dock (module 440/439)
Control Valve & Flow Test on Wet System- Semiannual | C4 North Dock (module 440/439)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
C4 North Dock (module 440/439)
Date: 06/11/2025 08:01
Inspection Site
Georgia World Congress Center - Bldg C 285 Andrew Young International Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39600290
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .20/1567
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
18 of 40 Wet System - Semiannual | Level 3 System 56 (module 371/370)
Control Valve & Flow Test on Wet System- Semiannual | Level 3 System 56 (module 371/370)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Level 3 System 56 (module 371/370)
Main Drain 2 155 Green Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
19 of 40 Wet System - Semiannual | Level 3 System 55 (module 372/368)
Control Valve & Flow Test on Wet System- Semiannual | Level 3 System 55 (module 372/368)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Level 3 System 55 (module 372/368)
Main Drain 2 155 Green Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1500
Verification Seal
Date: 06/11/2025 08:01
Inspection Site
Georgia World Congress Center - Bldg C 285 Andrew Young International Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39600290
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
20 of 40 Wet System - Semiannual | Level 3 System 53 (module 369/368)
Control Valve & Flow Test on Wet System- Semiannual | Level 3 System 53 (module 369/368)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Level 3 System 53 (module 369/368)
Main Drain 2 155 Green Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
21 of 40 Wet System - Semiannual | Stair 14 System 65-4th Floor (module 1001/1002)
Control Valve & Flow Test on Wet System- Semiannual | Stair 14 System 65-4th Floor (module 1001/1002)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Stair 14 System 65-4th Floor (module 1001/1002)
Main Drain 2 150 150 140 Green Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Date: 06/11/2025 08:01
Inspection Site
Georgia World Congress Center - Bldg C 285 Andrew Young International Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39600290
22 of 40 Wet System - Semiannual | Stair 14 System 59-4th Floor (module 1003/1002)
Control Valve & Flow Test on Wet System- Semiannual | Stair 14 System 59-4th Floor (module 1003/1002)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Stair 14 System 59-4th Floor (module 1003/1002)
Main Drain 2 150 150 140 Green Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
23 of 40 Wet System - Semiannual | Stair 14 System 64-4th Floor (module 1061/1060)
Control Valve & Flow Test on Wet System- Semiannual | Stair 14 System 64-4th Floor (module 1061/1060)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Stair 14 System 64-4th Floor (module 1061/1060)
Main Drain 2 150 150 140 Green Yes
Type Butterfly Seal # 0 Size 2.5 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .10/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
24 of 40 Wet System - Semiannual | Stair 14 System 52-3rd Floor (module 719/720)
Control Valve & Flow Test on Wet System- Semiannual | Stair 14 System 52-3rd Floor (module 719/720)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Stair 14 System 52-3rd Floor (module 719/720)
Main Drain 2 155 155 145 Green Yes
Date: 06/11/2025 08:01
Inspection Site
Georgia World Congress Center - Bldg C 285 Andrew Young International Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39600290
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
25 of 40 Wet System - Semiannual | Stair 14 System 49-2nd Floor (module 602/601)
Control Valve & Flow Test on Wet System- Semiannual | Stair 14 System 49-2nd Floor (module 602/601)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Stair 14 System 49-2nd Floor (module 602/601)
Main Drain 2 165 165 155 Green Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
26 of 40 Wet System - Semiannual | Stair 14 System 22-1st Floor (module 386/385)
Control Valve & Flow Test on Wet System- Semiannual | Stair 14 System 22-1st Floor (module 386/385)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Stair 14 System 22-1st Floor (module 386/385)
Main Drain 2 170 170 160 Green Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1500
Verification Seal
Date: 06/11/2025 08:01
Inspection Site
Georgia World Congress Center - Bldg C 285 Andrew Young International Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39600290
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
27 of 40 Wet System - Semiannual | Stair 27 System 27 2nd Floor (module 254/253)
Control Valve & Flow Test on Wet System- Semiannual | Stair 27 System 27 2nd Floor (module 254/253)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Stair 27 System 27 2nd Floor (module 254/253)
Main Drain 2 160 160 150 Green Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
28 of 40 Wet System - Semiannual | Stair 28 System 60 4th Floor (module 803/802)
Control Valve & Flow Test on Wet System- Semiannual | Stair 28 System 60 4th Floor (module 803/802)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Stair 28 System 60 4th Floor (module 803/802)
Main Drain 2 155 155 145 Green Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Date: 06/11/2025 08:01
Inspection Site
Georgia World Congress Center - Bldg C 285 Andrew Young International Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39600290
29 of 40 Wet System - Semiannual | Stair 28 System 51 4th Floor (module 805/804)
Control Valve & Flow Test on Wet System- Semiannual | Stair 28 System 51 4th Floor (module 805/804)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Stair 28 System 51 4th Floor (module 805/804)
Main Drain 2 155 155 145 Green Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
30 of 40 Wet System - Semiannual | Stair 28 System 61 4th Floor (module 806/804)
Control Valve & Flow Test on Wet System- Semiannual | Stair 28 System 61 4th Floor (module 806/804)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Stair 28 System 61 4th Floor (module 806/804)
Main Drain 2 155 155 145 Green Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
31 of 40 Wet System - Semiannual | Stair 32 System 46 2nd Floor (module 271/270)
Control Valve & Flow Test on Wet System- Semiannual | Stair 32 System 46 2nd Floor (module 271/270)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Stair 32 System 46 2nd Floor (module 271/270)
Main Drain 2 155 155 145 Green Yes
Date: 06/11/2025 08:01
Inspection Site
Georgia World Congress Center - Bldg C 285 Andrew Young International Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39600290
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
32 of 40 Wet System - Semiannual | Stair 32 System 13 1st Floor (module 235/234)
Control Valve & Flow Test on Wet System- Semiannual | Stair 32 System 13 1st Floor (module 235/234)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Stair 32 System 13 1st Floor (module 235/234)
Main Drain 2 170 170 160 Green Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
33 of 40 Wet System - Semiannual | Stair 34 System 12 2nd Floor (module 131/146)
Control Valve & Flow Test on Wet System- Semiannual | Stair 34 System 12 2nd Floor (module 131/146)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Stair 34 System 12 2nd Floor (module 131/146)
Main Drain 2 160 160 150 Green Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1500
Verification Seal
Date: 06/11/2025 08:01
Inspection Site
Georgia World Congress Center - Bldg C 285 Andrew Young International Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39600290
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
34 of 40 Wet System - Semiannual | Stair 39 System 50 3rd Floor (module 304/303)
Control Valve & Flow Test on Wet System- Semiannual | Stair 39 System 50 3rd Floor (module 304/303)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Stair 39 System 50 3rd Floor (module 304/303)
Main Drain 2 155 155 145 Green Yes
Type Butterfly Seal # 0 Size 45 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
35 of 40 Wet System - Semiannual | Stair 39 System 45 2nd Floor (module 309/307)
Control Valve & Flow Test on Wet System- Semiannual | Stair 39 System 45 2nd Floor (module 309/307)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Stair 39 System 45 2nd Floor (module 309/307)
Main Drain 2 160 160 150 Green Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Date: 06/11/2025 08:01
Inspection Site
Georgia World Congress Center - Bldg C 285 Andrew Young International Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39600290
36 of 40 Wet System - Semiannual | Stair 39 System 14 2nd Floor (module 308/307)
Control Valve & Flow Test on Wet System- Semiannual | Stair 39 System 14 2nd Floor (module 308/307)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Stair 39 System 14 2nd Floor (module 308/307)
Main Drain 2 160 160 150 Green Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
37 of 40 Wet System - Semiannual | Stair 39 System 11 1st Floor (module 111/110)
Control Valve & Flow Test on Wet System- Semiannual | Stair 39 System 11 1st Floor (module 111/110)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Stair 39 System 11 1st Floor (module 111/110)
Main Drain 2 170 170 160 Green Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
38 of 40 Wet System - Semiannual | Stair 41 System 10 (module 104/103)
Control Valve & Flow Test on Wet System- Semiannual | Stair 41 System 10 (module 104/103)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Stair 41 System 10 (module 104/103)
Main Drain 2 160 160 150 Yellow Yes
Date: 06/11/2025 08:01
Inspection Site
Georgia World Congress Center - Bldg C 285 Andrew Young International Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39600290
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density Data placard is missing
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
39 of 40 Wet System - Semiannual | Stair 44 System 31 (module 691/690)
Control Valve & Flow Test on Wet System- Semiannual | Stair 44 System 31 (module 691/690)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Stair 44 System 31 (module 691/690)
Main Drain 2 165 165 155 Green Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .10/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
40 of 40 Wet System - Semiannual | Stair 48 System 32 2nd Floor (module 621/620)
Control Valve & Flow Test on Wet System- Semiannual | Stair 48 System 32 2nd Floor (module 621/620)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Stair 48 System 32 2nd Floor (module 621/620)
Main Drain 2 165 165 155 Green Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .20/1500
Verification Seal
Date: 06/11/2025 08:01
Inspection Site
Georgia World Congress Center - Bldg C 285 Andrew Young International Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39600290
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
1 of 8 Dry System - Semiannual | Node 2 System 23 (module 172/167)
Control Valve & Flow Test on Dry System- Semiannual | Node 2 System 23 (module 172/167)
System ID Connection
Flowed Outlet Size Static PSI Residual PSI
Static PSI After Test
Time to Restore Air Pressure Tag Color Results comparable to prior year?
Node 2 System 23 (module 172/167)
Main Drain 2 in 170 160 170 28 Green Yes
Type OS&Y Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1950
Verification Seal Color
N/A Secured Type Electric Tamper
General
Comment
Dry Pipe Sprinkler System Inspection
Gauges on dry pipe system in good condition and showing normal water supply pressure YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year Last Full Trip Test Year
2 of 8 Dry System - Semiannual | Node 2 System 25 (module 168/165)
Control Valve & Flow Test on Dry System- Semiannual | Node 2 System 25 (module 168/165)
System ID Connection
Flowed Outlet Size Static PSI Residual PSI
Static PSI After Test
Time to Restore Air Pressure Tag Color Results comparable to prior year?
Node 2 System 25 (module 168/165)
Main Drain 2 in 170 160 170 30 Green Yes
Type OS&Y Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1950
Verification Seal Color
N/A Secured Type Electric Tamper
General
Comment
Date: 06/11/2025 08:01
Inspection Site
Georgia World Congress Center - Bldg C 285 Andrew Young International Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39600290
Dry Pipe Sprinkler System Inspection
Gauges on dry pipe system in good condition and showing normal water supply pressure YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year Last Full Trip Test Year
3 of 8 Dry System - Semiannual | Node 2 System 26 (module 169/165)
Control Valve & Flow Test on Dry System- Semiannual | Node 2 System 26 (module 169/165)
System ID Connection
Flowed Outlet Size Static PSI Residual PSI
Static PSI After Test
Time to Restore Air Pressure Tag Color Results comparable to prior year?
Node 2 System 26 (module 169/165)
Main Drain 2 in 170 160 170 30 Green Yes
Type OS&Y Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1950
Verification Seal Color
N/A Secured Type Electric Tamper
General
Comment
Dry Pipe Sprinkler System Inspection
Gauges on dry pipe system in good condition and showing normal water supply pressure YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year Last Full Trip Test Year
4 of 8 Dry System - Semiannual | Node 2 System 30 (module 170/166)
Control Valve & Flow Test on Dry System- Semiannual | Node 2 System 30 (module 170/166)
System ID Connection
Flowed Outlet Size Static PSI Residual PSI
Static PSI After Test
Time to Restore Air Pressure Tag Color Results comparable to prior year?
Node 2 System 30 (module 170/166)
Main Drain 2 in 170 160 170 28 Green Yes
Type OS&Y Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1950
Verification Seal Color
N/A Secured Type Electric Tamper
Date: 06/11/2025 08:01
Inspection Site
Georgia World Congress Center - Bldg C 285 Andrew Young International Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39600290
Dry Pipe Sprinkler System Inspection
Gauges on dry pipe system in good condition and showing normal water supply pressure YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year Last Full Trip Test Year
5 of 8 Dry System - Semiannual | Node 2 System 29 (module 171/166)
Control Valve & Flow Test on Dry System- Semiannual | Node 2 System 29 (module 171/166)
System ID Connection
Flowed Outlet Size Static PSI Residual PSI
Static PSI After Test
Time to Restore Air Pressure Tag Color Results comparable to prior year?
Node 2 System 29 (module 171/166)
Main Drain 2 in 170 160 170 30 Green Yes
Type OS&Y Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1950
Verification Seal Color
N/A Secured Type Electric Tamper
General
Comment
Dry Pipe Sprinkler System Inspection
Gauges on dry pipe system in good condition and showing normal water supply pressure YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year Last Full Trip Test Year
6 of 8 Dry System - Semiannual | C1 Wall Pocket System 4 (module 322/310)
Control Valve & Flow Test on Dry System- Semiannual | C1 Wall Pocket System 4 (module 322/310)
System ID Connection
Flowed Outlet Size Static PSI Residual PSI
Static PSI After Test
Time to Restore Air Pressure Tag Color Results comparable to prior year?
C1 Wall Pocket System 4 (module 322/310)
Main Drain 2 in 170 160 170 Green Yes
Type OS&Y Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1950
Verification Seal Color
N/A Secured Type Electric Tamper
Date: 06/11/2025 08:01
Inspection Site
Georgia World Congress Center - Bldg C 285 Andrew Young International Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39600290
Dry Pipe Sprinkler System Inspection
Gauges on dry pipe system in good condition and showing normal water supply pressure YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year Last Full Trip Test Year
7 of 8 Dry System - Semiannual | C2 Wall Pocket System 3 (module 371/369)
Control Valve & Flow Test on Dry System- Semiannual | C2 Wall Pocket System 3 (module 371/369)
System ID Connection
Flowed Outlet Size Static PSI Residual PSI
Static PSI After Test
Time to Restore Air Pressure Tag Color Results comparable to prior year?
C2 Wall Pocket System 3 (module 371/369)
Main Drain 2 in 170 160 170 22 Green Yes
Type OS&Y Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1950
Verification Seal Color
N/A Secured Type Electric Tamper
General
Comment
Dry Pipe Sprinkler System Inspection
Gauges on dry pipe system in good condition and showing normal water supply pressure YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year Last Full Trip Test Year
8 of 8 Dry System - Semiannual | C3 Exhibit Hall System 15 (module 430/428)
Control Valve & Flow Test on Dry System- Semiannual | C3 Exhibit Hall System 15 (module 430/428)
System ID Connection
Flowed Outlet Size Static PSI Residual PSI
Static PSI After Test
Time to Restore Air Pressure Tag Color Results comparable to prior year?
C3 Exhibit Hall System 15 (module 430/428)
Main Drain 2 in 170 160 170 48 Green Yes
Type Butterfly Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1950
Verification Seal Color
N/A Secured Type Electric Tamper
Date: 06/11/2025 08:01
Inspection Site
Georgia World Congress Center - Bldg C 285 Andrew Young International Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39600290
Dry Pipe Sprinkler System Inspection
Gauges on dry pipe system in good condition and showing normal water supply pressure YES Alarm devices free from physical damage? YES indicate movement? YES Five Year Internal Year Last Full Trip Test Year
Date: 06/11/2025 08:01
Inspection Site
Georgia World Congress Center - Bldg C 285 Andrew Young International Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39600290
Wet Sprinklers
Location Stair 41 System 10 (module 104/103)
System Type/Name Deficiency Comments
Stair 41 System 10 (module 104/103)
Wet Sprinkler Results:
The System has failed
Stair 41 System 10 (module 104/103) Stair 41 System 10 (module 104/103)
Control Valves:
Labeled Yellow Tag
Sectional Valve
System Type/Name System Type/Name Comments
Date: 06/11/2025 08:01
Inspection Site
Georgia World Congress Center - Bldg C 285 Andrew Young International Blvd Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39600290
Owner's Section
Has the occupancy classification and hazard of contents remained the same since last inspection? N/A
Has the system remained in service without modification since the last inspection? N/A
Has an internal inspection been performed within the past 5 years? N/A
Are all the protection systems in service? N/A
Was the system free of actuation of devices and alarms since the last inspection? N/A
Statement
I state the information on this form is correct at the time and place of my inspection, and that all equipment tested at this time was left in operation condition upon completion of this inspection except as noted.
File details come from the government source that posted it. Updated .