Georgia World Congress Center _ Bldg B _Semi .pdf
PDF 384 KB Posted
- Attached to
- Fire Alarm Removal and Replacement
- Solicitation number
- PE-92200-RFP-2026-000000061
- Issued by
- Fulton County, Georgia
About this file
This is a semiannual sprinkler inspection report for the Georgia World Congress Center - Building B, conducted by Century Fire Protection on June 9, 2025. The inspection, referenced under Inspection Reference #39599665 and conducted by licensed inspector Shawn Bennington, evaluated 359 total devices across wet systems, dry systems, deluge systems, sectional valves, waterflow alarms, tampers, and supervisory switches at the facility located at 285 Andrew Young International Boulevard, Atlanta, Georgia. The report documents the testing and inspection of numerous control valves and flow tests performed per NFPA 25 standards across multiple zones and systems throughout the building, including mezzanine zones, boiler rooms, engineering areas, conference centers, stairwells, and specialized areas such as ballrooms and elevator systems.
The inspection results identified multiple deficiencies requiring attention. Of the devices tested, significant failures were documented across wet systems (31 passed of 42 tested), dry systems (7 passed of 11 tested), and all deluge systems (0 passed of 8 tested). Specific deficiencies included missing data placards on multiple systems, yellow-tagged control valves indicating non-compliance, alarm sight glass leaks, OS&Y valve leaks, out-of-date pressure gauges on deluge systems (requiring replacement), and a tamper switch on a butterfly sectional valve that failed to report to the fire alarm panel. The inspection also identified concerns with waterflow alarms (59 of 61 passed) and tampers (108 of 109 passed). These findings directly correlate with the related fire alarm removal and replacement contract opportunity, indicating the facility requires comprehensive upgrades to its fire protection systems to restore full compliance with applicable standards.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2450 Satellite Boulevard Duluth, GA 30096 Office: (770) 506-2388 centuryfp.com
Semiannual Sprinkler Report Inspected and tested per NFPA 25
Inspected Site Georgia World Congress Center - Bldg B
285 Andrew Young International Bvld Atlanta, GA 30313
Date/Time 06/09/2025 12:52 Inspection Reference # 39599665
Conducted by: Shawn Bennington License # IL 000310
Backflow License #
Prepared For Georgia World Congress Center 285 Andrew Young International
Atlanta, GA 30313
Inspection and Testing Summary
Device Description Total Devices Number Inspected/Tested Number Passed Number Failed
Supervisory Switch 19 19 19 0
Waterflow Alarms 61 61 59 2
Tampers 109 109 108 1
Main Drains 61 61 61 0
Wet System 42 42 31 11
Dry System 11 11 7 4
Deluge System 8 8 0 8
Sectional Valve 48 48 47 1
Report of Inspection / Test Water Based System Inspection
Date: 06/09/2025 12:52
Inspection Site
Georgia World Congress Center - Bldg B 285 Andrew Young International Bvld Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599665
1 of 42 Wet System - Semiannual | Mezzanine Zone 7 (module 124/123)
Control Valve & Flow Test on Wet System- Semiannual | Mezzanine Zone 7 (module 124/123)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Mezzanine Zone 7 (module 124/123)
Main Drain 2 170 170 160 Green Yes
Type Butterfly Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .20/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
2 of 42 Wet System - Semiannual | Mezzanine Zone 8 (module 122/123)
Control Valve & Flow Test on Wet System- Semiannual | Mezzanine Zone 8 (module 122/123)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Mezzanine Zone 8 (module 122/123)
Main Drain 2 170 170 160 Green Yes
Type Butterfly Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .19/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
3 of 42 Wet System - Semiannual | Phase 3 Boiler Room (module 476/477)
Control Valve & Flow Test on Wet System- Semiannual | Phase 3 Boiler Room (module 476/477)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Phase 3 Boiler Room (module 476/477)
Main Drain 2 170 170 160 Yellow Yes
Date: 06/09/2025 12:52
Inspection Site
Georgia World Congress Center - Bldg B 285 Andrew Young International Bvld Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599665
Type OS&Y Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density Data placard is missing
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
4 of 42 Wet System - Semiannual | B3 South (module 1049/1048)
Control Valve & Flow Test on Wet System- Semiannual | B3 South (module 1049/1048)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
B3 South (module 1049/1048) Main Drain 2 170 170 160 Green Yes
Type OS&Y Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .25/3000
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
5 of 42 Wet System - Semiannual | B3 Center (module 1050/1048)
Control Valve & Flow Test on Wet System- Semiannual | B3 Center (module 1050/1048)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
B3 Center (module 1050/1048) Main Drain 2 170 170 160 Green Yes
Type OS&Y Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .25/3000
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in YES Alarm devices free from YES
Date: 06/09/2025 12:52
Inspection Site
Georgia World Congress Center - Bldg B 285 Andrew Young International Bvld Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599665 good condition and showing normal water supply pressure physical damage?
Valve supervisory switches indicate movement? YES Five Year Internal Year
6 of 42 Wet System - Semiannual | B3 North (module 1051/1048)
Control Valve & Flow Test on Wet System- Semiannual | B3 North (module 1051/1048)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
B3 North (module 1051/1048) Main Drain 2 170 170 160 Green Yes
Type OS&Y Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .25/3000
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
7 of 42 Wet System - Semiannual | Level 2 North (module 1053/1052)
Control Valve & Flow Test on Wet System- Semiannual | Level 2 North (module 1053/1052)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Level 2 North (module 1053/1052)
Main Drain 1 160 160 150 Yellow Yes
Type OS&Y Seal # 0 Size 2.5 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm FAIL Time for Alarm Density N/A
Verification Seal Color
Green Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
Date: 06/09/2025 12:52
Inspection Site
Georgia World Congress Center - Bldg B 285 Andrew Young International Bvld Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599665
8 of 42 Wet System - Semiannual | Level 3 North (module 1055/1054)
Control Valve & Flow Test on Wet System- Semiannual | Level 3 North (module 1055/1054)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Level 3 North (module 1055/1054)
Main Drain 1 150 150 140 Green Yes
Type OS&Y Seal # 0 Size 2.5 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density N/A
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
9 of 42 Wet System - Semiannual | Level 4 North (module 1057/1056)
Control Valve & Flow Test on Wet System- Semiannual | Level 4 North (module 1057/1056)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Level 4 North (module 1057/1056)
Main Drain 1 140 140 130 Yellow Yes
Type OS&Y Seal # 0 Size 2.5 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density N/A
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
10 of 42 Wet System - Semiannual | B2 Center (module 1035/1030)
Control Valve & Flow Test on Wet System- Semiannual | B2 Center (module 1035/1030)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
B2 Center (module 1035/1030) Main Drain 2 170 170 160 Green Yes
Date: 06/09/2025 12:52
Inspection Site
Georgia World Congress Center - Bldg B 285 Andrew Young International Bvld Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599665
Type OS&Y Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .30/2500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
11 of 42 Wet System - Semiannual | B1 Center (module1034/1030)
Control Valve & Flow Test on Wet System- Semiannual | B1 Center (module1034/1030)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
B1 Center (module1034/1030) Main Drain 2 170 170 160 Green Yes
Type OS&Y Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .25/3000
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
12 of 42 Wet System - Semiannual | B1 North (module 1033/1030)
Control Valve & Flow Test on Wet System- Semiannual | B1 North (module 1033/1030)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
B1 North (module 1033/1030) Main Drain 2 170 170 160 Green Yes
Type OS&Y Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .25/3000
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing YES Alarm devices free from physical damage? YES
Date: 06/09/2025 12:52
Inspection Site
Georgia World Congress Center - Bldg B 285 Andrew Young International Bvld Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599665 normal water supply pressure
Valve supervisory switches indicate movement? YES Five Year Internal Year
13 of 42 Wet System - Semiannual | B1 South (module 1032/1030)
Control Valve & Flow Test on Wet System- Semiannual | B1 South (module 1032/1030)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
B1 South (module 1032/1030) Main Drain 2 170 170 160 Green Yes
Type OS&Y Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .25/3000
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
14 of 42 Wet System - Semiannual | Level 2 Center (module 1039/1038)
Control Valve & Flow Test on Wet System- Semiannual | Level 2 Center (module 1039/1038)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Level 2 Center (module 1039/1038)
Main Drain 1 160 160 150 Green Yes
Type OS&Y Seal # 0 Size 3 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density N/A
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Date: 06/09/2025 12:52
Inspection Site
Georgia World Congress Center - Bldg B 285 Andrew Young International Bvld Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599665
15 of 42 Wet System - Semiannual | Level 3 Center (module 1041/1040)
Control Valve & Flow Test on Wet System- Semiannual | Level 3 Center (module 1041/1040)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Level 3 Center (module 1041/1040)
Main Drain 1 150 150 140 Green Yes
Type OS&Y Seal # 0 Size 3 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density N/A
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
16 of 42 Wet System - Semiannual | Level 4 Center (module 1043/1042)
Control Valve & Flow Test on Wet System- Semiannual | Level 4 Center (module 1043/1042)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Level 4 Center (module 1043/1042)
Main Drain 1 140 140 130 Green Yes
Type OS&Y Seal # 0 Size 2.5 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density N/A
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
17 of 42 Wet System - Semiannual | System 20 (module 544/543)
Control Valve & Flow Test on Wet System- Semiannual | System 20 (module 544/543)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to
System 20 (module 544/543) Main Drain 2 170 170 160 Yellow Yes
Date: 06/09/2025 12:52
Inspection Site
Georgia World Congress Center - Bldg B 285 Andrew Young International Bvld Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599665
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density Data placard is missing
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
18 of 42 Wet System - Semiannual | Terrace Level 5-Womens Restroom (module 915/914)
Control Valve & Flow Test on Wet System- Semiannual | Terrace Level 5-Womens Restroom (module 915/914)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Terrace Level 5-Womens Restroom (module 915/914)
Main Drain 1 Green N/A
Type OS&Y Seal # 0 Size 3 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density N/A
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
19 of 42 Wet System - Semiannual | Lobby Level Ceiling-Mechanical Room (module 437/438)
Control Valve & Flow Test on Wet System- Semiannual | Lobby Level Ceiling-Mechanical Room (module 437/438)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Lobby Level Ceiling-Mechanical Room (module 437/438)
Main Drain 1 140 140 135 Green Yes
Type OS&Y Seal # 0 Size 1 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density N/A
Verification Seal Color
Green Secured Type Electric Tamper
Date: 06/09/2025 12:52
Inspection Site
Georgia World Congress Center - Bldg B 285 Andrew Young International Bvld Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599665
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
20 of 42 Wet System - Semiannual | Murphy Ballroom (module 908/909)
Control Valve & Flow Test on Wet System- Semiannual | Murphy Ballroom (module 908/909)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Murphy Ballroom (module 908/909)
Main Drain 1 130 135 125 Green Yes
Type OS&Y Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .18/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
21 of 42 Wet System - Semiannual | Murphy Ballroom Stage (module 906/905)
Control Valve & Flow Test on Wet System- Semiannual | Murphy Ballroom Stage (module 906/905)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Murphy Ballroom Stage (module 906/905)
Main Drain 1 130 130 125 Yellow Yes
Type OS&Y Seal # 0 Size 3 Secured PASS
Open FAIL Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density N/A
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Date: 06/09/2025 12:52
Inspection Site
Georgia World Congress Center - Bldg B 285 Andrew Young International Bvld Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599665
22 of 42 Wet System - Semiannual | Engineering 2nd Floor (module 707/706)
Control Valve & Flow Test on Wet System- Semiannual | Engineering 2nd Floor (module 707/706)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Engineering 2nd Floor (module 707/706)
Main Drain 1 150 150 140 Green Yes
Type OS&Y Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density N/A
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
23 of 42 Wet System - Semiannual | Conference Center 3rd Floor (module 781/780)
Control Valve & Flow Test on Wet System- Semiannual | Conference Center 3rd Floor (module 781/780)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Conference Center 3rd Floor (module 781/780)
Main Drain 1 150 150 140 Green Yes
Type OS&Y Seal # 0 Size 3 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density N/A
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
24 of 42 Wet System - Semiannual | Stair 5 Level 3 (module 1029/1028)
Control Valve & Flow Test on Wet System- Semiannual | Stair 5 Level 3 (module 1029/1028)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Stair 5 Level 3 (module 1029/1028)
Main Drain 1 150 150 140 Green Yes
Date: 06/09/2025 12:52
Inspection Site
Georgia World Congress Center - Bldg B 285 Andrew Young International Bvld Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599665
Type OS&Y Seal # 0 Size 2 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density N/A
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
25 of 42 Wet System - Semiannual | Stair 5 Level 2 (module 1027/1026)
Control Valve & Flow Test on Wet System- Semiannual | Stair 5 Level 2 (module 1027/1026)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Stair 5 Level 2 (module 1027/1026)
Main Drain 1 155 155 145 Green Yes
Type OS&Y Seal # 0 Size 2.5 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density N/A
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
26 of 42 Wet System - Semiannual | West Engineering (module 542/541)
Control Valve & Flow Test on Wet System- Semiannual | West Engineering (module 542/541)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
West Engineering (module 542/541)
Main Drain 1 Yellow N/A
Type OS&Y Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density Data placard is missing.
Verification Seal
N/A Secured Type Electric Tamper
Date: 06/09/2025 12:52
Inspection Site
Georgia World Congress Center - Bldg B 285 Andrew Young International Bvld Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599665
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
27 of 42 Wet System - Semiannual | B4 Zone 6 (module 118/121)
Control Valve & Flow Test on Wet System- Semiannual | B4 Zone 6 (module 118/121)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
B4 Zone 6 (module 118/121) Main Drain 2 170 170 160 Green Yes
Type Butterfly Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .37/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
28 of 42 Wet System - Semiannual | B4 Zone 5 (module 117/120)
Control Valve & Flow Test on Wet System- Semiannual | B4 Zone 5 (module 117/120)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
B4 Zone 5 (module 117/120) Main Drain 2 170 170 160 Green Yes
Type Butterfly Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .19/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Date: 06/09/2025 12:52
Inspection Site
Georgia World Congress Center - Bldg B 285 Andrew Young International Bvld Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599665
29 of 42 Wet System - Semiannual | B4 B/C Connector (module 150/151)
Control Valve & Flow Test on Wet System- Semiannual | B4 B/C Connector (module 150/151)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
B4 B/C Connector (module 150/151)
Main Drain 2 170 170 160 Green Yes
Type Butterfly Seal # 0 Size 8 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .30/3049
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
30 of 42 Wet System - Semiannual | B4 B/C Connector Fire Hose Station (module 152/153)
Control Valve & Flow Test on Wet System- Semiannual | B4 B/C Connector Fire Hose Station (module 152/153)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
B4 B/C Connector Fire Hose Station (module 152/153)
Main Drain 2 170 170 160 Green Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm FAIL Time for Alarm Density 750gpm/100psi
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
31 of 42 Wet System - Semiannual | B5 Zone 4 (module 116/112)
Control Valve & Flow Test on Wet System- Semiannual | B5 Zone 4 (module 116/112)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to
B5 Zone 4 (module 116/112) Main Drain 2 170 170 160 Yellow Yes
Date: 06/09/2025 12:52
Inspection Site
Georgia World Congress Center - Bldg B 285 Andrew Young International Bvld Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599665
Type Butterfly Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density Data placard is missing
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
32 of 42 Wet System - Semiannual | B5 Zone 1 (module 108/113)
Control Valve & Flow Test on Wet System- Semiannual | B5 Zone 1 (module 108/113)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
B5 Zone 1 (module 108/113) Main Drain 2 170 170 160 Yellow Yes
Type Butterfly Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density Data placard is missing
Verification Seal Color
Green Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
33 of 42 Wet System - Semiannual | B5 Zone 2 (module 107/114)
Control Valve & Flow Test on Wet System- Semiannual | B5 Zone 2 (module 107/114)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
B5 Zone 2 (module 107/114) Main Drain 2 170 170 160 Yellow Yes
Type Butterfly Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density Data placard is missing
Verification Seal
Date: 06/09/2025 12:52
Inspection Site
Georgia World Congress Center - Bldg B 285 Andrew Young International Bvld Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599665
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
34 of 42 Wet System - Semiannual | B5 Zone 3 (module 106/115)
Control Valve & Flow Test on Wet System- Semiannual | B5 Zone 3 (module 106/115)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
B5 Zone 3 (module 106/115) Main Drain 2 170 170 160 Yellow Yes
Type Butterfly Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density Data placard is missing
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
35 of 42 Wet System - Semiannual | B5 B/C Connector North (module 142/143)
Control Valve & Flow Test on Wet System- Semiannual | B5 B/C Connector North (module 142/143)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
B5 B/C Connector North (module 142/143)
Main Drain 2 170 170 160 Green Yes
Type Butterfly Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .30/3040
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Date: 06/09/2025 12:52
Inspection Site
Georgia World Congress Center - Bldg B 285 Andrew Young International Bvld Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599665
36 of 42 Wet System - Semiannual | Service Street (module 540/539)
Control Valve & Flow Test on Wet System- Semiannual | Service Street (module 540/539)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Service Street (module 540/539)
Main Drain 1 165 165 160 Green Yes
Type OS&Y Seal # 0 Size 2.5 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density N/A
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
37 of 42 Wet System - Semiannual | Service Street (module 1037/1036)
Control Valve & Flow Test on Wet System- Semiannual | Service Street (module 1037/1036)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Service Street (module 1037/1036)
Main Drain 1 Green N/A
Type OS&Y Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density N/A
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
38 of 42 Wet System - Semiannual | Service Street North (module 418/417)
Control Valve & Flow Test on Wet System- Semiannual | Service Street North (module 418/417)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Service Street North (module 418/417)
Main Drain 1 Green Yes
Date: 06/09/2025 12:52
Inspection Site
Georgia World Congress Center - Bldg B 285 Andrew Young International Bvld Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599665
Type OS&Y Seal # 0 Size 3 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density N/A
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
39 of 42 Wet System - Semiannual | Stair 7 System 66 5th Floor (module 979/978)
Control Valve & Flow Test on Wet System- Semiannual | Stair 7 System 66 5th Floor (module 979/978)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Stair 7 System 66 5th Floor (module 979/978)
Main Drain 2 130 130 120 Green Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
40 of 42 Wet System - Semiannual | Stair 7 System 63 4th Floor (module 904/903)
Control Valve & Flow Test on Wet System- Semiannual | Stair 7 System 63 4th Floor (module 904/903)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Stair 7 System 63 4th Floor (module 904/903)
Main Drain 2 135 135 125 Green Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .10/1500
Verification Seal
Date: 06/09/2025 12:52
Inspection Site
Georgia World Congress Center - Bldg B 285 Andrew Young International Bvld Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599665
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
41 of 42 Wet System - Semiannual | Stair 7 System 57 3rd Floor (module 717/716)
Control Valve & Flow Test on Wet System- Semiannual | Stair 7 System 57 3rd Floor (module 717/716)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Stair 7 System 57 3rd Floor (module 717/716)
Main Drain 2 145 145 135 Green Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .19/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year
42 of 42 Wet System - Semiannual | Stair 7 System 48 2nd Floor (module 709/708)
Control Valve & Flow Test on Wet System- Semiannual | Stair 7 System 48 2nd Floor (module 709/708)
System ID Connection Flowed Outlet Size Static PSI Static PSI After Test Time to Restore Residual PSI Tag Color Results comparable to prior year?
Stair 7 System 48 2nd Floor (module 709/708)
Main Drain 2 155 155 145 Green Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .10/1500
Verification Seal Color
N/A Secured Type Electric Tamper
Water Based System Inspection
Gauges on wet pipe system in good condition and showing normal water supply pressure
YES Alarm devices free from physical damage? YES
Valve supervisory switches
1 of 11 Dry System - Semiannual | Service Street (module 401/402)
Date: 06/09/2025 12:52
Inspection Site
Georgia World Congress Center - Bldg B 285 Andrew Young International Bvld Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599665
Control Valve & Flow Test on Dry System- Semiannual | Service Street (module 401/402)
System ID Connection
Flowed Outlet Size Static PSI Residual PSI
Static PSI After Test
Time to Restore Air Pressure Tag Color Results comparable to prior year?
Service Street (module 401/402)
Main Drain 1.25 in 170 160 170 32 Green Yes
Type Butterfly Seal # 0 Size 2 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .30/35heads
Verification Seal Color
N/A Secured Type Electric Tamper
General
Comment
Dry Pipe Sprinkler System Inspection
Gauges on dry pipe system in good condition and showing normal water supply pressure YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year Last Full Trip Test Year
2 of 11 Dry System - Semiannual | Main Out of Tunnel (module 1074/1030)
Control Valve & Flow Test on Dry System- Semiannual | Main Out of Tunnel (module 1074/1030)
System ID Connection
Flowed Outlet Size Static PSI Residual PSI
Static PSI After Test
Time to Restore Air Pressure Tag Color Results comparable to prior year?
Main Out of Tunnel (module 1074/1030)
Main Drain 2 in 170 160 170 42 Green Yes
Type OS&Y Seal # 0 Size 6 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .30/40heads
Verification Seal Color
N/A Secured Type Electric Tamper
General
Comment
Dry Pipe Sprinkler System Inspection
Gauges on dry pipe system in good condition and showing normal water supply pressure YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year Last Full Trip Test Year
3 of 11 Dry System - Semiannual | B3 Dock (module 1064/1063)
Date: 06/09/2025 12:52
Inspection Site
Georgia World Congress Center - Bldg B 285 Andrew Young International Bvld Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599665
Control Valve & Flow Test on Dry System- Semiannual | B3 Dock (module 1064/1063)
System ID Connection
Flowed Outlet Size Static PSI Residual PSI
Static PSI After Test
Time to Restore Air Pressure Tag Color Results comparable to prior year?
B3 Dock (module 1064/1063) Main Drain 2 in 170 160 170 44 Green Yes
Type OS&Y Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .20/1958
Verification Seal Color
N/A Secured Type Electric Tamper
General
Comment
Dry Pipe Sprinkler System Inspection
Gauges on dry pipe system in good condition and showing normal water supply pressure YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year Last Full Trip Test Year
4 of 11 Dry System - Semiannual | System 21A (module 551/550)
Control Valve & Flow Test on Dry System- Semiannual | System 21A (module 551/550)
System ID Connection
Flowed Outlet Size Static PSI Residual PSI
Static PSI After Test
Time to Restore Air Pressure Tag Color Results comparable to prior year?
System 21A (module 551/550) Main Drain 2 in 170 160 170 17 Green Yes
Type OS&Y Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1950
Verification Seal Color
N/A Secured Type Electric Tamper
General
Comment
Dry Pipe Sprinkler System Inspection
Gauges on dry pipe system in good condition and showing normal water supply pressure YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year Last Full Trip Test Year
5 of 11 Dry System - Semiannual | System 21B (module 549/550)
Control Valve & Flow Test on Dry System- Semiannual | System 21B (module 549/550)
Date: 06/09/2025 12:52
Inspection Site
Georgia World Congress Center - Bldg B 285 Andrew Young International Bvld Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599665
System ID Connection
Flowed Outlet Size Static PSI Residual PSI
Static PSI After Test
Time to Restore Air Pressure Tag Color Results comparable to prior year?
System 21B (module 549/550) Main Drain 2 in 170 160 170 38 Green Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .21/1950
Verification Seal Color
N/A Secured Type Electric Tamper
General
Comment
Dry Pipe Sprinkler System Inspection
Gauges on dry pipe system in good condition and showing normal water supply pressure YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year Last Full Trip Test Year
6 of 11 Dry System - Semiannual | B5 B/C Connector North Entry (module 144/146)
Control Valve & Flow Test on Dry System- Semiannual | B5 B/C Connector North Entry (module 144/146)
System ID Connection
Flowed Outlet Size Static PSI Residual PSI
Static PSI After Test
Time to Restore Air Pressure Tag Color Results comparable to prior year?
B5 B/C Connector North Entry (module 144/146)
Main Drain 2 in 170 160 170 50 Green Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .30/3050
Verification Seal Color
N/A Secured Type Electric Tamper
General
Comment
Dry Pipe Sprinkler System Inspection
Gauges on dry pipe system in good condition and showing normal water supply pressure YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year Last Full Trip Test Year
7 of 11 Dry System - Semiannual | B5 Loading Dock (module 147/149)
Control Valve & Flow Test on Dry System- Semiannual | B5 Loading Dock (module 147/149)
Date: 06/09/2025 12:52
Inspection Site
Georgia World Congress Center - Bldg B 285 Andrew Young International Bvld Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599665
System ID Connection
Flowed Outlet Size Static PSI Residual PSI
Static PSI After Test
Time to Restore Air Pressure Tag Color Results comparable to prior year?
B5 Loading Dock (module 147/149)
Main Drain 2 in 170 160 170 50 Green Yes
Type Butterfly Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density .20/1567
Verification Seal Color
N/A Secured Type Electric Tamper
General
Comment
Dry Pipe Sprinkler System Inspection
Gauges on dry pipe system in good condition and showing normal water supply pressure YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year Last Full Trip Test Year
8 of 11 Dry System - Semiannual | Cart Shop (module 404/408)
Control Valve & Flow Test on Dry System- Semiannual | Cart Shop (module 404/408)
System ID Connection
Flowed Outlet Size Static PSI Residual PSI
Static PSI After Test
Time to Restore Air Pressure Tag Color Results comparable to prior year?
Cart Shop (module 404/408) Main Drain 0.75 in 170 160 170 52 Yellow Yes
Type Butterfly Seal # 0 Size 2 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density Data placard is missing.
Verification Seal Color
N/A Secured Type Electric Tamper
General
Comment
Dry Pipe Sprinkler System Inspection
Gauges on dry pipe system in good condition and showing normal water supply pressure YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year Last Full Trip Test Year
9 of 11 Dry System - Semiannual | B5 Break Room (module 217/218)
Control Valve & Flow Test on Dry System- Semiannual | B5 Break Room (module 217/218)
Date: 06/09/2025 12:52
Inspection Site
Georgia World Congress Center - Bldg B 285 Andrew Young International Bvld Atlanta, GA 30313
Customer
Georgia World Congress Center 285 Andrew Young International Atlanta, GA 30313
2450 Satellite Boulevard Duluth, GA null Office: null centuryfp.com
Conducted by: Shawn Bennington
Inspection Reference: 39599665
System ID Connection
Flowed Outlet Size Static PSI Residual PSI
Static PSI After Test
Time to Restore Air Pressure Tag Color Results comparable to prior year?
B5 Break Room (module 217/218)
Main Drain 2 in 170 160 170 40 Yellow Yes
Type OS&Y Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS
Tamper PASS Alarm PASS Time for Alarm Density Data placard is missing.
Verification Seal Color
N/A Secured Type Electric Tamper
General
Comment
Dry Pipe Sprinkler System Inspection
Gauges on dry pipe system in good condition and showing normal water supply pressure YES Alarm devices free from physical damage? YES
Valve supervisory switches indicate movement? YES Five Year Internal Year Last Full Trip Test Year
10 of 11 Dry System - Semiannual | Level 1 Pump Room (module 219/220)
Control Valve & Flow Test on Dry System- Semiannual | Level 1 Pump Room (module 219/220)
System ID Connection
Flowed Outlet Size Static PSI Residual PSI
Static PSI After Test
Time to Restore Air Pressure Tag Color Results comparable to prior year?
Level 1 Pump Room (module 219/220)
Main Drain 2 in 170 160 170 55 Yellow Yes
Type OS&Y Seal # 0 Size 4 Secured PASS
Open PASS Accessible PASS Signs PASS Excs PASS