SECTION 15055 - PIPING AND EQUIPMENT IDENTIFICATION
PART 1 GENERAL
1.1
STANDARDS
A.
Piping, valves and equipment listed herein shall be identified as set forth in ANSI A13.1-1981 SCHEME FOR THE IDENTIFICATION OF PIPING SYSTEMS.
1.2
SUBMITTAL DATA
A.
See SECTION 15000 for general submittal requirements.
B.
Provide submittal data for any materials or equipment specified in this Section as listed on the Submittal Schedule (see SECTION 15000) and any special or additional data as requested by the Contracting Officer.
PART 2 PRODUCTS
2.1
MANUFACTURER
A.
Markers and tags shall be as manufactured by Seton Name Plate Corporation, or approved equal.
2.2
PIPING IDENTIFICATION
A.
Pipe markers to be Seton's "Setmark" semi-rigid plastic snap-on markers with nylon ties. Pressure-sensitive stick-on markers shall not be used. All markers shall have direction of flow arrows. Markers for pipe or pipe coverings up to 6" in diameter shall be the self-securing snap-on type. Markers on pipe or coverings 6" in diameter and over shall be secured with nylon ties.
B.
Identify the following systems:
Sanitary Sewer
Sanitary Sewer Vent
Industrial Cold Water
Steam Supply
Steam Relief
Condensate
PART 3 EXECUTION
3.1
INSTALLATION SCHEDULE
A.
Identification of pipe shall be done near the end of the project after finish work such as insulating and painting has been completed.
3.2
PIPING IDENTIFICATION
A.
Piping shall be identified at locations described herein and any other specific location as directed by the Contracting Officer. Markers shall be installed in accordance with manufacturer's instructions in all locations listed below.
1.
Adjacent to each isolation valve and drain valve, on all relief valve piping and adjacent to floor drains.
2.
At each connection to equipment.
END OF SECTION 15055
PACKAGE M OUTBUILDING RENOVATION NIH-NIAID RML HAMILTON, MT
PIPING AND EQUIPMENT IDENTIFICATION 15055-2
RML AUTOCLAVE REPLACEMENT ( NIH-NIAID RML ( HAMILTON, MT
PIPING AND EQUIPMENT IDENTIFICATION 15055-2