The RFP is for the construction of training facilities to support III Marine Expeditionary Forces 9th Engineer Support Battalion, including a medium-heavy equipment training area, a water supply training area, and a bulk fuel training area. Key details addressed in the Q&A include: over-excavation requirements for footings and trenches, grout thickness, storm drain materials, resinous flooring specifications, contractor certifications, proposal due date extension, meter box locations, and details related to the monorail hoist system. The proposal due date has been extended to May 07, 2024. Several drawings and specification sections will be revised and provided in an upcoming amendment.
View the file
Other files
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DEPARTMENT OF THE NAVY
NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND PACIFIC
258 MAKALAPA DR STE 100
PEARL HARBOR HI 96860-3134
RFP N62742-24-R-1313
Notice No. 4
Notice No. 4
23 April 2024
PRE-PROPOSAL QUESTIONS & ANSWERS
WON 1737354, FY24 MCON P-870, 9TH ENGINEERING SUPPORT BATTALION (ESB)
TRAINING COMPLEX, US NAVSUPPACT, MARINE CORPS BASE, GUAM
NOTE: The following questions and answers are provided for INFORMATION ONLY. The
RFP remains unchanged unless it is amended in writing on a Standard Form 30.
Revised Answer to Question 43:
43. Section 31 23 00.00 20, paragraph 3.3
Specification section 31 23 00.00 20 paragraph 3.3 requires to over excavate the footings for the Bleachers and Head at least 24 inches below the bottom of footing and 12 inches horizontally. Perform additional over excavation to remove any pockets of softy, loose and unsatisfactory material.
Please clarify the specification section 21 23 00.00 20 requirement of 12 inches (first paragraph of page 14) or 24 inches (second paragraph of page 14) horizontal distance from edge of foundation for over excavation.
REVISED ANSWER: Over excavation for 24-inches will be revised in section 31 23 00.00 20 and will be provided in an upcoming Amendment. **The sentence "Over excavate at least 24 inches below the bottom of wall footing, and 24 inches horizontally beyond the wall footing limits" will be removed.**
45. Grout
Provide thickness of Grout Rubble Pavement.
ANSWER: Minimum thickness is 15”. Section 31 23 00.00 20, Excavation and Fill will be revised in an upcoming amendment.
46. Drawing: CU503
Drawing sheet CU503 shows two (2) types of meter boxes. Please provide locations of meter box per type. Type X and Type III.
ANSWER: See notes respective to each water meter box. The contractor should be able to determine the location of each box based on the type of the meter box.
Notice No. 3
47. Section 33 40 00 paragraph 2.1
Spec section 33 40 00 paragraph 2.1 provided reinforced concrete pipe and corrugated steel pipe. Please clarify which type of material is required for storm drain?
a. Drain Line A
b. Drain Line B
c. Drain Line C
d. Drain Line D
e. Drain Line E
f. Drain Line F
ANSWER: Either is acceptable for all the referenced drain lines.
48. Sections 09 67 23.14 and 09 67 23.15, and Drawing A-601
The specifications provided for resinous flooring include 09 67 23.14 Chemical Resistant
Resinous Flooring and 09 67 23.15 Fuel Resistive Resinous Flooring, 3-coat System.
On Drawing A-601 the description for F1 finish is "Exposed Concrete w/ Slip Resistant
Epoxy Coating Membrane." Please confirm what specification between the two should be used for this.
ANSWER: See section 09 67 23.14 Chemical Resistant Resinous Flooring for Bleachers and
Public Toilet (Head) for A-601 List of Materials description F1.
49. Sections 09 67 23.14 and 09 67 23.15, and Drawings A-601, A-101, and A-102
The specifications provided for resinous flooring include 09 67 23.14 Chemical Resistant
Resinous Flooring and 09 67 23.15 Fuel Resistive Resinous Flooring, 3-coat System.
Could you please also provide the specific areas or locations within the project where these flooring finish specifications should be applied?
ANSWER: See section 09 67 23.14 for the Bleachers and Public Toilet (Head) noted in A-601 as F1 in Room Finish Schedule, and A-101/A-102 as concrete sidewalk. See section
09 67 23.15 for the Bulk Fuel bermed concrete pad.
50. Sections 09 67 23.15
Specs 09 67 23.15 Fuel Resistive Resinous Flooring, 3-Coat System, paragraph 1.3.4.3 stated that "All Contractors that perform surface preparation or coating application must be certified to SSPC QP 8 and should be SSPC QS 1 certified prior to Contract award and must remain certified while accomplishing any surface preparation or coating application..."
To our knowledge, no contractors in Guam currently hold both SSPC QP8 and SSPC QS 1
Certifications. Considering the project's flooring area is relatively small. Will the government consider, waiving this requirement?
ANSWER: The first and second subparagraphs of Specification Section 09 67 23.15 paragraph
1.3.4.3 will be removed in an upcoming amendment. The installation contractor requirements will only be the remaining paragraph: “Minimum requirements for the installation contractor are as follows: Completed three or more jobs within the past two years, applying the specified materials to concrete surfaces, and the total area exceeds 200,000 square feet. Submit documentation listing location of work, point of contact at job site, total square footage of applied materials, listing of both materials and equipment used, and validation from coating manufacturer documenting quality of materials purchased per job for work totaling 200,000 square feet within the past two years."
51. Proposal due date
We respectfully request a two (2) week extension of the bid submission deadline. The additional time is necessary to give vendors ample time to provide their quotations.
ANSWER: The proposal due date will be changed to May 07, 2024, and it will be provided in an upcoming amendment.
52. Drawing: A3/CU503
Please clarify if the meter reading cover for type box X is the same with type box III (Cast
Iron) (Dwg. Ref CU503 Detail A3)
ANSWER: Type III box cover to be provided in an upcoming amendment.
53. Drawing: Detail C1/CU511
Drawing CU511 detail C1 Sewer Trench Detail (Option 1). Sub-bedding with a thickness of
12" is shown in the section with "see note 2". Note 2 says prepare subgrade per spec section
31 23 00.00 20. If cohesive material, unsatisfactory material, or unstable material is encountered or the bottom of trench is within 2 feet of water table, overexcavate and replace the overexcavated material with crushed rock wrapped in non-woven geotextile fabric.
a. Question 1: Is the 12" sub-bedding provided in the detail C1 should be included as the regular trench section?
b. Question 2: Is the 12" sub-bedding provided in the detail C1 supposed to be part of note 2 and should not be included in the pricing as it is considered to be unforeseen condition and shall be subject to change order?
ANSWERS:
a. Follow Note 2. The 12” sub-bedding is only required as described by Note 2 for
“cohesive material, unsatisfactory material, or unstable material” and is not part of the
“regular” trench section.
b. Follow Note 2. The 12” sub-bedding is only required as described by Note 2 for
“cohesive material, unsatisfactory material, or unstable material” and is part of SLIN
0001AC.
54. Drawing: CU511
Drawing CU511 detail C1 Sewer Trench Detail (Option 1). Sub-bedding with a thickness of
12" is shown in the section with "see note 2". Note 2 says prepare subgrade per spec section
31 23 00.00 20. If cohesive material, unsatisfactory material, or unstable material is encountered or the bottom of trench is within 2 feet of water table, overexcavate and replace the overexcavated material with crushed rock wrapped in non-woven geotextile fabric.
Question 3: Note 3 mentions Controlled Low Strength material (CLSM). Is CLSM acceptable as sub-bedding?
ANSWER: Yes, CLSM is acceptable as sub-bedding.
55. Oil and Water Separator
Please provide reinforcement details for oil and water separator.
ANSWER: For pricing purposes only, assume 12" thick concrete slab with #5 @ 12" OC EW
T&B. Per A1/M-503, plan dimensions and reinforcing of the pad are contingent upon OWS Manufacturer.
56. Section 32 12 13, Bituminous Prime and Tack Coats, para 2.1.2, 2.2.2, 2.1.1.4
Section 32 13 13.06, para. 2.1.1, states - to "Provide cementitious materials in concrete mix with 20 to 50 percent non-portland cement pozzolanic materials by weight”. Para 2.1.1.4, states - to “Use of one of the SCMs listed below is optional, unless the SCM is required to mitigate ASR.” Para. 2.1.1 states - to provide, but, para. 2.1.1.4 states, to provide “is optional” unless the SCM is required to mitigate ASR.
Note, that our aggregates are not alkali-silica reactive.
Question: Is “SCM” still required, per par. 2.1.1, if the aggregates are not alkali-silica reactive?
ANSWER: Follow paragraph 2.1.1.4.
57. Drawing: Details C1/CU501 and C1/CU521
Drawings CU501 detail C1 for Waterline trench and drawing sheet CU521 detail C1 Drain
Line Trench. Both trench section shows a 24" thick sub-bedding.
Please confirm the 24" thick sub-bedding to be used for waterline and storm drainage line as shown in the drawings.
ANSWER: Detail C1/CU501 will be revised and provided in an upcoming amendment.
58. Drawing: Details C1/CU501 and C1/CU521
Drawings CU501 detail C1 for Waterline trench and drawing sheet CU521 detail C1 Drain
Line Trench. Both trench section shows a 24" thick sub-bedding.
Please confirm the sub bedding for waterline and storm drainage line are to be included in
BASE ITEM 0001AA.
ANSWER: Details C1/CU501 and C1/CU521 will be revised and provided in an upcoming amendment. Sub-bedding is considered over excavation in accordance with SLIN
0001AC.
59. Section 31 23 00.00 20, para 3.3
Specification section 31 23 00.00 20 paragraph 3.3 requires to over excavate the footings for the Bleachers and Head at least 24 inches below the bottom of footing and 12 inches horizontally. Perform additional over excavation to remove any pockets of softy, loose and unsatisfactory material.
Is the 24 inches below and 12 inches horizontal over-excavation requirement under foundation of Bleacher and Head shall be included as Option Item 1 under bid item 0002?
Please clarify.
ANSWER: All work associated with bid option 1 is part of CLIN 0002.
60. Drawing: Detail A2/CG414
Drawing CG414 section detail A2 shows a 4-feet limit of MEC clearance from the bottom of the pit and Over excavation limit. Please clarify if this over-excavation requirement is to be included under bid item 0001AC OVER-EXCAVATION.
ANSWER: HE Dig Pit Over excavation is required in the base bid for a different purpose than the over excavation in the Options.
61. Section 41 22 23.19, Sheet S-511
Reference to specification 41 22 23.19 and drawing sheet S-511 regarding the required monorail hoist. Please provide details and sizing of steel columns and steel beams supporting monorail hoist system so we can source out separately from the hoist supplier. Multiple supplier of hoist already declined to provide pricing due to missing details.
ANSWER: For bidding purposes only, assume HSS columns & WF beams weighting 50 lb/ft.
Per RFI #27 response, Monorail system to be designed by others.