These are transmittal forms documenting equipment submittals for contract N6660420P8218, the B47 Dust Collection project at NUWC Newport for the Naval Sea Systems Command (NAVSEA). The contractor, BESA Equipment LLC, submitted shop drawings and equipment specifications for government approval.
Transmittal #005 (dated 09/13/2020) covered ductwork shop drawings (Drawing 60089, Revision 2) for a 4000 CFM dust collection system with multiple inlet points (4", 5", 7", 8", 9", 10", and 12" diameter ductwork), floor sweeps, a concrete pad-mounted dust collector with external exhaust, and a control panel. The drawing notation states the design was "approved for sizes and ductwork path" with the understanding that "exact layout may vary based on field conditions." This submittal received approval code "B" on 09/14/2020, indicating approval except as noted on drawings with no resubmission required.
Transmittal #013 (dated 10/08/2020) was a resubmittal containing three items: the AGET dust collector unit (Model FT64S201-2HD4), the dust collector control panel drawing, and filtration specifications. The dust collector specifications detail an AGET FT64S201-2HD4-SP afterfilter attenuator with a 15 HP fan motor and 1/2 HP shaker motor, handling 4000 CFM at 14 inches of water gauge static pressure. The control panel uses a UL-listed steel enclosure with a Cincinnati Fan HDBI-160 backward-inclined wheel fan. Filter media consists of napped cotton sateen with 99.99% efficiency at 3-5 microns. This submittal received approval code "B" on 10/16/2020.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Enclosure (40)
TRANSMITTAL OF SUBMITTALS, SHOP DRAWINGS, EQUIPMENT DATA, MATERIAL
SAMPLES, OR MANUFACTURER'S CERTIFICATES OF COMPLIANCE
Date: 09/13/2020 Transmittal #: 005
SECTION 1 - REQUEST FOR APPROVAL OF THE FOLLOWING ITEMS (This section will be initiated by the contractor)
TO:
Travis Germano, Code 1022 Infrastructure Support
1176 Howell Street, Newport, RI 02841
From:
BESA EQUIPMENT LLC
1082 SPUR RD
SOUDERTON PA 18964-1042
Contract Number:
N6660420P8218
Check One:
( X) This is a new transmittal
( ) This is a resubmittal of transmittal
SPECIFICATION SECTION NUMBER:
(cover only one section with each transmittal)
PROJECT TITLE: B47 Dust Collection
Control
Number a.
Description of Item Submitted
(type, size, model number/etc.)
b.
Mfg or Ktr c.
# of
Copies d.
Contract Reference
Document
Contractor
Use Code g.
Variation
Request
(Y/N) h.
i. Spec.Para.
e.
Dwg
Sht f.
1 Ductwork Shop Drawing – Rev2 60089 1
REMARKS:
I hereby certify that the above item(s) shown and marked in this submittal and proposed to be incorporated with this contract, is in strict compliance with the contract drawings and specifications (except as otherwise stated), can be installed in the allocated spaces, and:
( ) is approved for use.
( x) is submitted for Government Approval
Contractor QC Representative's : _______________
Name and Signature: QC Manager
Action Codes: (Note: Approval of items does not relieve the contractor from complying with all the requirements of the plans and specifications)
A-Approved as Submitted
B-Approved, except as noted on drawings.
Resubmission not required
C-Approved, except as noted on drawings.
Refer to attached sheet. Resubmission required.
D-Will be returned by separate correspondence
E-Disapproved. See attached sheet.
SECTION II - APPROVAL ACTION (refer to ROICC Use Code)
Enclosures Returned
Name, Title and Signature of Approving Authority
Date
ENG FORM 4025, CS rev Jan 2002 Sheet 1 of 1 craig.guenette Typewritten Text B craig.guenette
09/14/2020
A A
B B
DRAWN
CHECKED
TITLE
NUWC Newport Dust Collection System
SIZE
B
SCALE
DWG NO
60089
REV
SHEET 1 OF 2
1/110
12" Ø
5"Ø Floor Sweep
5"Ø
5"Ø
5"Ø
5"Ø
5"Ø Floor Sweep
4"Ø
No Return Valve
Valve and Stand Submitted Separately
Dust Collector Mounted on
Concrete Pad
4000CFM Dust Collector
Exhaust Outside of Building
Dust Collector Control Panel
10"Ø
9"Ø
8"Ø
7"Ø
Concrete Pad Submitted Separately
AS NOTED
APPROVED FOR SIZES AND DUCTWORK
PATH, EXACT LAYOUT MAY VARY BASED
ON FIELD CONDITIONS.
keith.boulds Approved
A A
B B
DRAWN
CHECKED
TITLE
NUWC Newport Dust Collection System
SIZE
B
SCALE
DWG NO
60089
REV
SHEET 2 OF 2
1 /110
Floor Sweep
Floor Sweep
5"Ø
4"Ø
Dust Collector Mounted on Concrete Pad
Concrete Pad Submitted Separately
12" Ø
10" Ø
9" Ø
8" Ø
7" Ø
Enclosure (40)
TRANSMITTAL OF SUBMITTALS, SHOP DRAWINGS, EQUIPMENT DATA, MATERIAL
SAMPLES, OR MANUFACTURER'S CERTIFICATES OF COMPLIANCE
Date: 10/08/2020 Transmittal #: 013
SECTION 1 - REQUEST FOR APPROVAL OF THE FOLLOWING ITEMS (This section will be initiated by the contractor)
TO:
Travis Germano, Code 1022 Infrastructure Support
1176 Howell Street, Newport, RI 02841
From:
BESA EQUIPMENT LLC
1082 SPUR RD
SOUDERTON PA 18964-1042
Contract Number:
N6660420P8218
Check One:
( ) This is a new transmittal
(X ) This is a resubmittal of transmittal
SPECIFICATION SECTION NUMBER:
(cover only one section with each transmittal)
PROJECT TITLE: B47 Dust Collection
Control a.
Description of Item Submitted
(type, size, model number/etc.)
b.
Mfg or Ktr c.
# of
Copies d.
Contract Reference
Document
Contractor g.
Variation
Request
(Y/N) h.
i. Spec.Para.
e.
Dwg
Sht f.
1 Dust Collector Drawing – FT64S201-2HD4 AGET - FT64S201-2HD4 1
1 Dust Collector Panel Drawing 1
1 Filtration Specifications 1
REMARKS:
I hereby certify that the above item(s) shown and marked in this submittal and proposed to be incorporated with this contract, is in strict compliance with the contract drawings and specifications (except as otherwise stated), can be installed in the allocated spaces, and:
( ) is approved for use.
( x) is submitted for Government Approval
Contractor QC Representative's : _______________
Name and Signature: QC Manager
Action Codes: (Note: Approval of items does not relieve the contractor from complying with all the requirements of the plans and specifications)
A-Approved as Submitted
B-Approved, except as noted on drawings.
Resubmission not required
C-Approved, except as noted on drawings.
Refer to attached sheet. Resubmission required.
D-Will be returned by separate correspondence
E-Disapproved. See attached sheet.
SECTION II - APPROVAL ACTION (refer to ROICC Use Code)
Enclosures Returned
Name, Title and Signature of Approving Authority
Date
ENG FORM 4025, CS rev Jan 2002 Sheet 1 of 1 craig.guenette
B craig.guenette
10/16/2020
SCALE
DRAWN BY:
APPROVED BY
DESC.
PRINT NO.
LET. CHANGE DATE
FRAC. TOL. ± 1/32
AGET MANUFACTURING COMPANY - ADRIAN, MICHIGAN
REV
SHEET
SIZE
DEC. TOL. ±.03125
COMMENTS:
UNLESS OTHERWISE SPECIFIED:
CHECKED BY:
- A
CUST.
ALL DIMENSIONS
IN INCHES
UNLESS
SPECIFIED---
FT64-091120
TK
9/14/2020
BESA
EQUIPMENT
CSL
9/11/2020
FT64S201-2HD4-SP
9/32" = 1'-0"
48"
88" 10'-111
4"
12"
16'-21 2"
18'-9"
16'-8"
2"
24 x 28
PRESSURE
RELIEF PANEL
2 REQ'D
(SPECIFY LOCATION)
14" I.D.
72" 68"
EVASE DISCHARGE
W/ BIRDSCREEN
ATTENUATORFT64S201-2HD4-SP AFTERFILTER
W/ PULL-THROUGH EXHAUSTER
- 15 HP FAN MOTOR
- 1/2 HP SHAKER MOTOR
- (4) 55 GALLON DRUMS
∅16" O.D.
OUTLET
AS NOTED
INCLUDE ATTACHED FAN WITH UNIT
Matt Callout Located on the Exhaust Side - Facing away from building
Matt Callout Relief panels located this side
Matt Callout Attenuator fully supported from collector stand. Support drawings submitted separately.
AGET MANUFACTURING COMPANY
ADRIAN, MICHIGAN
DUSTKOP - MISTKOP
FILTER SPECIFICATIONS
FABRIC: NAPPED COTTON SATEEN
FILTER MEDIA:
Fiber: Cotton Thread Count (per sq. inch): 88 x 54 Weight (per sq. yard): 10 Ounce Permeability: 12 – 20 CFM/ Sq Ft Yarn Type: Spun Construction: Sateen weave Mullen Burst : Min. 300 PSI Finish: Raised nap on filtration side only (inside) Thickness: .025 prior to nap processing Max operating temp: 1800 F continuos, 2250 F surge
EFFICIENCY*:
99.99% 3 - 5 Microns** 99.97% 1 - 2 Microns 99.94% .5 - 1 Micron
Efficiencies from test studies conducted with standard Aget fabric samples by an independent testing laboratory, Inter-Basic Resources (IBR), Accredited Laboratory Cert. No. 1362-01. Testing at 3:1 ratio, with PTI Fine Test Dust (neutralized), using the Aerosol Retention Efficiency Method per TM E-217, using HIAC/ROYCO 1230 Sensor and 8000A Automatic Particle Counter.
(www.ibr-usa.com)
*Filtration efficiency is affected by many factors including particle size, shape, and weight, filter velocity (air-to-cloth ratio), dust loading, and the amount of residual dust, or "dust cake", remaining in or on the filter surface after reconditioning (i.e. bag shaking). A slight residual after reconditioning is desirable for optimum efficiency upon restarting the system. The above data was generated by an independent testing laboratory, and represents new fabric with a modest, stabilized surface residual, after reconditioning (shaking).
**One micron = One millionth of a meter; 0.0003937 Inch; Approx. 1/25,440 inch. The lower level of visibility to the naked eye is 40 microns.
Note: As with any "surface load" type filter media, filtration efficiency will improve as the collected dust cake builds, making longer intervals between filter shaking desirable, however an excessive dust cake will reduce fan capacity to some degree. Conversely, frequent reconditioning restores air volume, but adversely affects filtration efficiency as the dust cake is destroyed. Reconditioning is recommended only when air volume is reduced to a marginal or unacceptable level for its intended purpose. Experience will establish a desirable interval pattern, with one shake cycle per 8 hours being the normal starting point. When reconditioning no longer restores an acceptable air volume for an acceptable duration, the filters should be replaced.
www.agetmfg.com
Your Representative:
Douglas Roehl
Air Systems, Inc
2828 Kraft Road Suite 262
Grand Rapids MI 49512
616.608.1098 Phone
616.608.1099 Fax
Doug@airsystems-usa.com
FAN SELECTION
And
PERFORMANCE
AGET MANUFACTURING CO.
4000 CFM @ 14"
Job Name:
Reference:
Wednesday, October 14, 2020
Class IIIConstruction Class70 13.1Motor Frequency, Hz 60 69.6%Static Efficiency, %AMCA Arrangement No. 4HM 13.1
2,941Outlet Velocity, ft./min.
18.00Inlet Diameter, in.
Wheel Diameter, in. 17.81
70%Wheel Width, %70 SQ Backward InclinedWheel Description0.075
HDBI-160Model4,000
3,530Fan RPM14.0
Fan Selection and SpecificationsOperating Requirements
Volume, ACFM
Static Pressure, in. wg
Density, lb./ft.³
Operating Temperature, °F
Start-Up Temperature, °F Cold Start BHP
Fan BHP Suggested Motor HP: 15.0
Cincinnati Fan Selector - © 2017 by Cincinnati Fan and Ventilator Co. All Rights Reserved
CFSWin Version: 8.5.7404.17791 8.7.4Database Version:
| B47 Dust Submittal 001B Ductwork Shop Drawing - B |
| B47 Dust Submittal 002C - Dust Collector - B |
| 20201008 - Dust Collector Submittal 4A |
| Fan Curve 2A |