1363603Amendment0006_Specs.pdf
PDF 606 KB Posted
- Attached to
- P475 Aircraft Maintenance Hangar
- Solicitation number
- N4008526R0148
About this file
This is a technical specification section (Section 13 31 33.00 22) for pre-engineered framed fabric structures, specifically for the P-475 Aircraft Maintenance Hangar at MCAS Beaufort, South Carolina, under Amendment 0004. The specification establishes design, material, fabrication, and installation requirements for a fabric aircraft shelter measuring 60 feet wide by 60 feet long with 30 feet 6 inches exterior center height, providing 56 feet interior width and 26 feet interior clear center height with an 18-foot minimum vertical clearance at the sidewall. The structure must include four aluminum blast shields (4 feet 8 inches by 4 feet 8 inches by 3/16 inch thick), anchored tubular steel chord truss frame with tensioned laminated fabric cover and polyester scrim, designed to resist wind and seismic loads per ICC IBC and ASCE 7 standards.
Material and quality requirements specify tubular steel trusses fabricated from ASTM A500/A500M Grade B steel, hot-dip galvanized per ASTM A123/A123M, with structural bolts conforming to ASTM A325 and hardware galvanized per ASTM A153/A153M. The fabric cover must be 28 ounces per square yard, 100-percent waterproofed, PVC-coated polyester with polyester 18 x 13 denier scrim, flame-retardant per NFPA 701, matching existing airfield sunshade colors. The manufacturer must demonstrate minimum 20 years' experience in design, fabrication, erection, and service, with warranty coverage of 30 years on the frame and 20 years on the fabric canopy. Installation requirements include certification by a Professional Structural Engineer with minimum 10 years' experience, welding by certified welders with minimum 5 years' experience per AWS D1.1/D1.1M, trusses spaced 10 feet on center, and fabric tensioning at four corners using ratchet and cable systems. Additional systems required include lightning protection per Section 26 41 00 with air terminals, copper bonding conductors, and ground rods at each corner and middle of each side, and interior LED lighting per Section 26 51 00 providing 25 footcandles at 3 feet above floor at 5100 CCR color temperature.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P-475 AIRCRAFT MAINTENANCE HANGAR ({AMENDMENT 0004) 1363603
MCAS BEAUFORT, SC
SECTION 13 31 33.00 22
PRE-ENGINEERED FRAMED FABRIC STRUCTURES
09/16
AMENDMENT 00004
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this section to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN CONCRETE INSTITUTE (ACI)
ACI 318 (2014; Errata 1-2 2014; Errata 3-5 2015;
Errata 6 2016; Errata 7-9 2017) Building Code Requirements for Structural Concrete (ACI 318-14) and Commentary (ACI 318R-14)
AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE)
ASCE 7 (2017; Errata 2018; Supp 1 2018) Minimum Design Loads and Associated Criteria for Buildings and Other Structures
AMERICAN WELDING SOCIETY (AWS)
AWS D1.1/D1.1M (2020) Structural Welding Code - Steel
ASTM INTERNATIONAL (ASTM)
ASTM A123/A123M (2017) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products
ASTM A153/A153M (2016a) Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware
ASTM A325 (2014) Standard Specification for Structural Bolts, Steel, Heat Treated, 120/105 ksi Minimum Tensile Strength
ASTM A500/A500M (2020) Standard Specification for Cold-Formed Welded and Seamless Carbon Steel Structural Tubing in Rounds and Shapes
ASTM A615/A615M (2020) Standard Specification for Deformed and Plain Carbon-Steel Bars for Concrete Reinforcement
ASTM A780/A780M (2020) Standard Practice for Repair of Damaged and Uncoated Areas of Hot-Dip Galvanized Coatings
SECTION 13 31 33.00 22 Page 1 01/29/26
INTERNATIONAL CODE COUNCIL (ICC)
ICC IBC (2018) International Building Code
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 701 (2019) Standard Methods of Fire Tests for Flame Propagation of Textiles and Films
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00
SUBMITTAL PROCEDURES:
SD-01 Preconstruction Submittals
Manufacturer's Qualifications ; G
SD-02 Shop Drawings
Pre-Engineered Framed Fabric Structure ; G
Lightning Protection System ; G
Lighting System ; G
Submit shop drawings signed and sealed by a Professional Structural Engineer.
SD-03 Product Data
Pre-Engineered Framed Fabric Structure ; G
Lightning Protection System ; G
LED luminaires ; G
SD-04 Samples
Fabric Cover ; G
Submit fabric samples for color selection and/or approval.
SD-05 Design Data
Pre-Engineered Framed Fabric Structure ; G
Submit design calculations signed and sealed by the Professional Structural Engineer of Record.
Lightning Protection System ; G
Lighting System ; G
SD-10 Operation and Maintenance Data
Pre-Engineered Framed Fabric Structure ; G
SECTION 13 31 33.00 22 Page 2 01/29/26
SD-11 Closeout Submittals
Record Drawings ; G
1.3 QUALITY ASSURANCE
1.3.1 Products
The pre-engineered framed fabric structure is to be the product of a manufacturer who has had at least twenty (20) years experience in design, fabrication, erection, and service, and who is regularly engaged in the manufacture of the type of structures specified herein. Only manufacturers who can submit evidence of actual installations of comparable design and construction, and that the products have proven practical, durable, and require a minimum of maintenance, will be qualified under this specification. Submit manufacturer's qualifications and experience.
1.3.2 Installers
Installation of the pre-engineered framed fabric structure is to be by an authorized representative of the structure manufacturer and in accordance with approved design calculations and shop drawings. Provide mechanics skilled and experienced in the erection of structures of the type specified herein.
1.4 DELIVERY, STORAGE, AND HANDLING
The pre-engineered framed fabric structure manufacturer must provide shipment of all materials required for installation in protective packaging. Protect structure materials, fabric and accessories from damage during delivery, storage, and handling. Mark all packaging clearly with manufacturer's brand name and job site location. Store in dry location with adequate ventilation, free from dust and water. Storage must permit easy access for inspection and handling. Remove damaged items that cannot be restored to like new condition and replace with new items.
1.5 WARRANTY
Provide a warranty from the pre-engineered framed fabric structure manufacturer for all materials and workmanship for a period of thirty (30) years on the frame and twenty (20) years on the fabric canopy beginning from the date of final acceptance. Include in the warranty for fabric, failure due to deterioration, breakdown, mildew, heat, cold, fading or discoloration.
1.6 MAINTENANCE
Provide maintenance and cleaning instructions for fabric canopy. Provide instructions for periodic re-tensioning (if required).
PART 2 PRODUCTS
2.1 SYSTEM DESCRIPTION
Pre-engineered framed fabric aircraft-type structures in size (each) as follows:
SECTION 13 31 33.00 22 Page 3 01/29/26
a. Overall exterior dimensions are as follows: 60 feet wide x 60 feet long with 30 feet - 6 inches exterior center height. Minimum interior clear dimensions are as follows: 56 feet wide with 26 feet interior clear center height. Minimum interior vertical clearance at the sidewall: 18 feet. Include with each structure four aluminum blast shields, 4 feet - 8 inches by 4 feet - 8 inches by 3/16 inch thick, fastened to the underside of the structure.
Structures include anchored tubular steel chord truss frame with a tensioned laminated fabric cover with a polyester scrim.
Any proposed deviations from the size indicated above are required to meet all airfield and airfraft clearance requirements.
2.1.1 Design Requirements
Design canopy structure(s) to resist wind load and seismic criteria as indicated on Structural drawings in accordance with ICC IBC and ASCE 7 requirements for Components and Cladding.
Provide pre-engineered framed fabric structures designed by a Professional Structural Engineer with a minimum of ten (10) years in the design and construction of framed fabric structures of the type specified herein.
2.2 STEEL STRUCTURES AND FRAMEWORK
2.2.1 Anchor System
Use Epoxy Adhesive anchors for existing concrete foundations (if occurring). New concrete foundations (where required) to be reinforced concrete designed to resist uplift forces. Provide 60,000 psi reinforcing steel per ASTM A615/A615M , Grade 60, and placed in accordance with ACI Detailing Manuals. Provide 3,000 psi minimum concrete mix in compliance with ACI 318 .
The intent is to anchor structures to concrete apron pavement, provide details of anchorages and how joints in apron will be accommodated. Also provide calculations demonstrating adequacy of concrete pavement to support loads.
2.2.2 Tubular Steel Trusses and Connections
Use tubular steel trusses for main framing. Fabricate tubing from ASTM A500/A500M , Grade B steel and hot-dip galvanized conforming to
ASTM A123/A123M .
Provide structural bolts that conform to ASTM A325. Provide all bolts with lock washers or locking nuts. Hot-dip galvanize all hardware conforming to ASTM A153/A153M .
Support trusses with rows of lateral x-bracing that connect at each truss with welded tabs.
Provide side and roof cables to provide additional strength to the frame system. Provide side cables with high visibility protection sleeves with reflective tape.
SECTION 13 31 33.00 22 Page 4 01/29/26
2.3 FABRIC COVER
2.3.1 Fabric Material
Provide a heavy-duty, PVC coated polyester fabric membrane with a demonstrated minimum field performance consistent with this structure's use, environment, and required warranty. Fabricate the fabric cover into one continuous panel that will cover the entire structure's length and width to the sidewall height indicated. Multiple section fabric covers are not acceptable.
Fabric weight is to be 28 oz. per square yard, 100-percent waterproofed with no track or keder system and laminated with a polyester 18 x 13 denier scrim. Provide flame retardant fabric conforming to NFPA 701 .
Color of fabric will match existing sunshades on the airfield at MCAS Beaufort..
2.4 LIGHTNING PROTECTION SYSTEM
Provide Lightning Protection System in accordance with Specification Section 26 41 00 LIGHTNING PROTECTION SYSTEM, including air terminals, wiring, and ground rods in the each corner and middle of each side of each sunshade. Interconnect all ground rods with copper bonding conductors.
Interconnect all air terminals with copper bonding conductors and provide copper down conductors to connect to the ground rods. Do not depend on the structural steel to provide the electrical path. Design to facilitate replacement of canvas without affecting the lightning protection system.
2.5 LIGHTING
Provide Lighting inside the fabric structure in accordance with Specification Section 26 51 00 INTERIOR LIGHTING. Provide LED luminaires suitable for wet locations. Provide lighting color temp of 5100 CCR.
Lighting system must provide approximately even illumination of 25 footcandles at 3 feet above finished floor. Locate luminaires to avoid aircraft exhaust and blast shields.
PART 3 EXECUTION
3.1 INSTALLATION
Install and erect the canopy structure in strict accordance with approved shop drawings per manufacturer's instructions.
Conform to ground slope (if occurring) and site conditions, ensuring a uniform appearance throughout the installation.
Weld all metal to metal connections with certified welders with a minimum of five (5) years experience. Provide welds in accordance with
AWS D1.1/D1.1M .
Space trusses at 10-feet on center unless otherwise required for design loading.
Form truss connections with plasma burnt plate to plate junctions using structural bolts, nuts and locking washers.
Tension fabric at the four corners of each structure with a ratchet and
SECTION 13 31 33.00 22 Page 5 01/29/26 cable system and attach longitudinally with cover tensioning tubes attached to the frame with all thread to frame connection.
Coat all weld joints or areas of damaged galvanizing with zinc cold galvanizing compound for corrosion protection. The repair to conform to ASTM A780/A780M . Provide Cold galvanizing compound that contains a minimum of 95 percent zinc dust in the dried film.
Place reflective tape on the four corners of the shelter to improve night visibility.
3.2 RECORD DRAWINGS
Provide record drawings of the pre-engineered framed fabric structure using the NAVFAC standard drawing format.
3.3 CONSTRUCTION WASTE MANAGEMENT
Comply with requirements of the Waste Management Plan specified in Section
01 74 19 CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL.
-- End of Section --
SECTION 13 31 33.00 22 Page 6 01/29/26
| PROJECT TABLE OF CONTENTS |
| DIVISION 13 - SPECIAL CONSTRUCTION |
| 13 31 33.00 22 - PRE-ENGINEERED FRAMED FABRIC STRUCTURES |
| PART 1 GENERAL |
| 1.1 REFERENCES |
| 1.2 SUBMITTALS |
| 1.3 QUALITY ASSURANCE |
| 1.3.1 Products |
| 1.3.2 Installers |
| 1.4 DELIVERY, STORAGE, AND HANDLING |
| 1.5 WARRANTY |
| 1.6 MAINTENANCE |
| PART 2 PRODUCTS |
| 2.1 SYSTEM DESCRIPTION |
| 2.1.1 Design Requirements |
| 2.2 STEEL STRUCTURES AND FRAMEWORK |
| 2.2.1 Anchor System |
| 2.2.2 Tubular Steel Trusses and Connections |
| 2.3 FABRIC COVER |
| 2.3.1 Fabric Material |
| 2.4 LIGHTNING PROTECTION SYSTEM |
| 2.5 LIGHTING |
| PART 3 EXECUTION |
| 3.1 INSTALLATION |
| 3.2 RECORD DRAWINGS |
| 3.3 CONSTRUCTION WASTE MANAGEMENT |