24-0017 Asbestos and Lead Paint Survey.pdf
PDF 6 MB Posted
- Attached to
- Repair BEQ M445
- Solicitation number
- N4008525R2687
About this file
This document is an Asbestos and Lead-Paint Survey report for Repair BEQ M445 at Marine Corps Base Camp Lejeune in Jacksonville, North Carolina. The survey was conducted by ECS Southeast, LLC on August 28, 2024, for MBF Architects PA. The building, constructed in 1986, comprises approximately 48,396 square feet and is currently vacant, slated for interior and exterior renovations.
The survey's key findings include: No asbestos-containing materials (ACMs) were detected in the 42 bulk samples analyzed from 16 homogeneous areas. However, lead-containing paint (LCP) was identified on several building components, including a brown metal roof hatch, grey metal door frames, white metal doors, white metal door frames, brown CMU walls, white window frames and panels, and brown metal doors. The report recommends that any suspect materials discovered during construction be presumed to contain asbestos and handled accordingly, and that contractors follow OSHA regulations when disturbing lead-containing paint.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amend 0009.pdf | ||
| Amend 0008.pdf | ||
| Amend 0007.pdf | ||
| Amend 0006.pdf | ||
| 240017 Pricing Sheet Awarding All Options.pdf | ||
| Amend 0005.pdf | ||
| Amend 0004.pdf | ||
| Amend 0003.pdf | ||
| Amend 0002.pdf | ||
| Amend 0001.pdf | ||
| N4008524B0017 Dwgs.pdf | ||
| 24-0017 NEPA.pdf | ||
| 24-0017 REIR-DM.pdf | ||
| 24-0017 Appendix-D.pdf | ||
| 240017 RFP.pdf | ||
| N4008524B0017 Specs.pdf |
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ASBESTOS AND LEAD-PAINT SURVEY
REPAIR BEQ M445
M445, MARINE CORPS BASE CAMP LEJ
JACKSONVILLE, NORTH CAROLINA 28547
ECS PROJECT NO. 49:23910
FOR: MBF ARCHITECTS PA
SEPTEMBER 23, 2024
September 23, 2024
Mr. Bill Faulkenberry MBF Architects PA 317-C Pollock Street New Bern, North Carolina 28560 faulkenberry@mbfarchitects.com
ECS Project No. 49:23910
Reference: Asbestos and Lead-Paint Survey, Repair BEQ M445, M445, Marine Corps Base Camp Lej, Jacksonville, North Carolina
Dear Mr. Faulkenberry:
ECS Southeast, LLC (ECS) is pleased to provide MBF Architects PA with the results of the above referenced Asbestos and Lead-Paint Survey performed at BEQ M445 located at Marine Corps Base Camp Lejeune in Jacksonville, North Carolina. This report summarizes our observations, analytical results, findings, and recommendations related to the work performed. The work described in this report was performed by ECS in general accordance with the Scope of Services described in ECS Proposal Number 49:45162P and the terms and conditions of the agreement authorizing those services.
ECS appreciates this opportunity to provide MBF Architects PA with our services. If we can be of further assistance to you, please do not hesitate to contact us.
Sincerely, ECS Southeast, LLC
Matt Guthrie, CIE Lindsey Thompson, REM Environmental Project Manager Environmental Principal mguthrie@ecslimited.com lthompson@ecslimited.com 864-665-3010 864-987-1810
6714 Netherlands Drive, Wilmington, North Carolina 28405 • T:910-686-9114 NC Engineering No. F-1519 NC Geology No. C-553 SC Engineering No. 3239
ECS Florida, LLC • ECS Mid-Atlantic LLC • ECS Midwest, LLC • ECS Pacific, Inc. • ECS Southeast, LLC • ECS Southwest, LLP
ECS New York Engineering, PLLC - An Associate of ECS Group of Companies • ecslimited.com
"ONE FIRM. ONE MISSION."
EXECUTIVE SUMMARY
The property is developed with Bachelor's Enlisted Quarters (BEQ) building M445 located at Marine Corps Base (MCB) Camp Lejeune in Jacksonville, Onslow County, North Carolina. Based on the information available, BEQ M445 comprises approximately 48,396 square feet of space and was constructed in 1986. The subject building is vacant and is slated for interior and exterior renovations.
ECS was requested to conduct an asbestos and lead paint survey prior to the proposed renovations.
The purpose of the survey was to determine whether asbestos-containing materials (ACMs) and lead-containing paint (LCP), are present on the subject property. The survey was performed within interior and exterior areas of the subject building as well as the roof.
Asbestos Survey
On August 28, 2024, Mr. Braxton B. Dawson, a North Carolina state-certified inspector, performed the asbestos assessment. Bulk samples were submitted to Scientific Analytical Institute, Inc. (SAI) in Greensboro, North Carolina for analysis via Polarized Light Microscopy (PLM) in accordance with the current EPA-600 methodology.
A total of 42 bulk samples from 16 homogeneous areas were submitted to the laboratory, of which 52 layers were analyzed. Based on the laboratory analysis of the bulk samples collected during the survey, none of the materials were reported to contain asbestos.
Due to inaccessibility or the destructive means that asbestos sampling requires, unseen ACMs may remain within the building hidden behind inaccessible areas, which include, but are not limited to, sub-grade walls, structural members, topping slabs, sub-grade sealants, flooring located below underlayments, areas behind exterior walls, pipe trenches, and subsurface utilities.
If suspect materials are discovered during construction activities, they should be presumed to contain asbestos and be treated as ACMs or be sampled immediately upon discovery and prior to disturbance for asbestos content by an accredited or certified asbestos inspector in accordance with 29 Code of Federal Regulations (CFR) 1926.1101.
Lead Paint Survey
The lead paint assessment was conducted by collection of paint chip samples from suspect lead paint materials. The paint chip samples were submitted to a laboratory that participates in the American Industrial Hygiene Association (AIHA) Environmental Lead Proficiency Analytical Testing (ELPAT) Programs for analysis of lead concentration (percent by weight) using Flame Atomic Absorption Spectroscopy.
Based on the laboratory analysis of the paint chips collected during the survey, the following building components were reported as lead-containing paint:
• Brown metal roof hatch
• Grey metal door frames
• White metal doors ii
• White metal door frames
• Brown CMU walls
• White window frames and panels
• Brown metal doors
• Brown door/window frames
• Brown metal door frames
Paint and surface coatings that contain detectable concentrations of lead are considered “lead-containing paints.” Since OSHA has no specific action level for lead in paint, all paint on the site found to have a measurable concentration of lead should be assumed to be lead-containing. Work performed that may disturb lead-containing paint is regulated under OSHA, as referenced under 29
CFR 1926.62.
Recommendations regarding the removal and disposal of the LCP identified by ECS can be found in Section 5.0 of this report.
The executive summary is an integral portion of this report. However, ECS recommends the report be read in its entirety.
iii
PAGETABLE OF CONTENTS
1.0 SITE DESCRIPTION
2.0 PURPOSE
3.0 METHODOLOGY
3.1 Asbestos-Containing Materials
3.2 Lead in Paint and Surface Coatings
4.0 RESULTS
4.1 Asbestos Sampling
4.2 Suspect or Assumed Asbestos-Containing Materials
4.3 Lead in Paint and Surface Coatings
5.0 RECOMMENDATIONS AND REGULATORY REQUIREMENTS
5.1 Asbestos-Containing Materials
5.2 Lead in Paint and Surface Coatings
6.0 LIMITATIONS
iv
TABLE OF APPENDICES
Appendix I: Figures
Appendix II: Site Photographs
Appendix III: Asbestos Bulk Sample Results
Appendix IV: Lead Laboratory Analytical Results
Appendix V: Certifications/Licenses v
1.0 SITE DESCRIPTION
The property is developed with Bachelor's Enlisted Quarters (BEQ) building M445 located at Marine Corps Base (MCB) Camp Lejeune in Jacksonville, Onslow County, North Carolina. Based on the information available, BEQ M445 comprises approximately 48,396 square feet of space and was constructed in 1986. The subject building is vacant and is slated for interior and exterior renovations.
ECS was requested to conduct an asbestos and lead paint survey prior to the proposed renovations.
The exterior is constructed with a brick façade and a built-up roof. Interior finishes consist of suspended acoustic ceiling tiles, concrete masonry unit (CMU) block and drywall walls, and various vinyl composite tile (VCT) floors.
2.0 PURPOSE
The purpose of the Asbestos and Lead-Paint Survey was to identify asbestos-containing materials (ACM) and lead-containing paint (LCP), which require special handling and/or disposal if disturbed during construction activities. The identification of ACMs require trained labor, regulated work practices, and special disposal. The identification of LCP or other lead hazards requires disclosure to contractors and monitoring of lead exposure.
3.0 METHODOLOGY
ECS performed the authorized Scope of Services in general accordance with our proposal, standard industry practice(s) and methods specified by regulation(s) for the identification of ACMs and LBPs.
3.1 Asbestos-Containing Materials
The non-invasive asbestos survey was performed by Mr. Braxton Dawson (NC Asbestos Inspector No.
12830) on August 28, 2024. The survey consisted of observing the accessible areas of the building for the presence of suspect materials that may contain asbestos. The survey involved detecting both friable materials (materials that can be pulverized or reduced to a powder by hand pressure when dry) and non-friable materials (materials that pose a hazard when sawn, sanded, drilled, or pulverized). Homogeneous materials (based on material type, color, texture, etc.) were identified during the survey.
The EPA National Emissions Standard for Hazardous Air Pollutants (NESHAP) requires a survey for asbestos before renovation or demolition. Demolition is defined under NESHAP as the removal of a load-bearing structural member, and renovation is an action that disturbs building materials. Based on requirements under NESHAP and North Carolina Asbestos Hazard Management Program (AHMP), administered by the Health Hazards Control Unit (HHCU) for renovation or demolition activities, ECS conducted a limited survey for potential ACM. The ACM survey was limited in that we did not conduct demolition, such as jack/sledgehammering, to expose potentially concealed materials. Samples were collected in general accordance with Environmental Protection Agency (EPA) Standard 40 CFR 763 Subpart E, Asbestos Hazard Emergency Response Act (AHERA), and Occupational Safety and Health Administration (OSHA) Standard 29 CFR 1926.1101 Inspection Protocol.
September 23, 2024
ECS Project # 49:23910
Representative bulk samples were collected, placed in sealed packages, and submitted to SAI for analysis using the Environmental Protection Agency (EPA) recommended method of Polarized Light Microscopy (PLM) coupled with dispersion staining (Method No. EPA 600/R-93/116). SAI participates in the National Voluntary Laboratory Accreditation Program (NVLAP). Their NVLAP accreditation number is #200644-0. Several of the samples were layered and analyzed as multiple samples. EPA regulations require collecting multiple samples of each homogeneous area for laboratory analysis. The material type, sample location, and analytical results of each bulk sample are also summarized in the attached Asbestos Bulk Analysis report in Appendices.
Samples were analyzed using the “Positive Stop” methodology. If one sample of a homogeneous material is reported to contain asbestos, the remaining samples are not analyzed. If one sample of a material from a homogeneous area is reported to contain greater than 1% asbestos, then by EPA definition, it is characterized as an ACM regardless of additional analysis.
During the survey, ECS attempted to identify suspect ACMs in readily accessible areas. However, due to the destructive means required to identify some materials, certain areas were deemed inaccessible (i.e. behind walls or sub-grade materials) and were not surveyed for suspect ACMs.
3.2 Lead in Paint and Surface Coatings
ECS completed a lead paint screening within the building as part of our assessment activities. The collection of representative paint chip samples was performed throughout the building. Samples collected were containerized, labeled, and transported to SAI. Each of the paint chip sampleswase subsequently analyzed for the presence of lead reported in percent lead by weight via EPA Method SW 846, 7000B (Flame AAS). The chain-of-custody, which includes sample numbers and sample locations, is included in an Appendix of this report.
4.0 RESULTS
The following is a summary of laboratory results, findings and observations.
4.1 Asbestos Sampling
In total, 42 bulk samples from 16 homogeneous areas were submitted to the laboratory, of which 52 layers were analyzed.
An ACM is defined as any material containing more than one percent (>1%) asbestos as determined using the method specified in Appendix E, Subpart E, 40 CFR Part 763, Section 1, PLM. Materials are categorized by the U.S. EPA in the following categories:
• Friable ACMs are defined as any ACM that, when dry, can be crumbled, pulverized, or reduced to powder by hand pressure. Non-friable ACMs are defined as any ACM that, when dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure.
• Category I non-friable ACMs include packings, gaskets, resilient floor coverings, and asphalt roofing products containing more than one percent (>1%) asbestos.
• Category II non-friable ACM are listed as any material, excluding Category I non-friable ACM, containing more than one percent (>1%) asbestos.
September 23, 2024
Regulated Asbestos Containing Materials (RACM) are friable ACM or non-friable ACM that will be or has been subjected to sanding, grinding, cutting, or abrading or has crumbled, been pulverized, or reduced to powder in the course of renovation and/or demolition operations.
SAI submitted a signed final laboratory report to ECS on September 6, 2024. None isof the bulk samples submitted for analysis were reported to contain asbestos in detectable concentrations. A complete list of the sampled materials submitted for analysis and material locations are included below. Photographs of representative building materials are located in Appendix II of this report.
Asbestos Bulk Sample Locations and Analysis Results
Sample ID Material Location
Material Description
Analytical Results
Category
1-1, 2 Roof Roof Tar Mats None Detected Not Applicable
2-1, 2 Roof Silver Seam Sealant
None Detected Not Applicable
3-1, 2 Roof Built-Up Roofing
None Detected Not Applicable
4-1, 2 Perimeter Parapets
Flashing Material
None Detected Not Applicable
5-1, 2 Lounges and Hallways
2' x 2' Fissured Ceiling Tiles
None Detected Not Applicable
6-1, 2 Common Areas Beige 12" VCT and Black Mastic
None Detected Not Applicable
7-1, 2 Mechanical Chases
Gray HVAC Duct Sealant
None Detected Not Applicable
8-1, 2 Rooms Beige 12" VCT and Black Mastic
None Detected Not Applicable
9-1, 2, 3, 4, 5, 6, Rooms and Common Areas
CMU Surfacing Material
None Detected Not Applicable
10-1, 2, 3, 4, 5, 6, 7
Rooms Ceiling Texture None Detected Not Applicable
11-1,2 Room Corners CMU Wall Caulk None Detected Not Applicable
12-1,2 Rooms Exterior Door Caulk
None Detected Not Applicable
September 23, 2024
Sample ID Material Location
Material Description
Analytical Results
Category
13-1,2 Rooms Drywall and Joint Compound
None Detected Not Applicable
14-1,2 Mechanical Rooms
Fiberglass TSI Sealant
None Detected Not Applicable
15-1,2 1st Floor Lounge
Black 12" VCT and Mastic
None Detected Not Applicable
16-1,2 1st Floor Lounge
White with Blue 12" VCT and Mastic
None Detected Not Applicable
4.2 Suspect or Assumed Asbestos-Containing Materials
Due to the inaccessibility or the destructive means that asbestos sampling requires, additional suspect ACMs may remain within the building hidden behind inaccessible areas that include, but are not limited to, sub-grade walls, structural members, topping slabs, sub-grade sealants, flooring located below underlayments, areas behind exterior walls, pipe trenches, and subsurface utilities, etc.
These areas were deemed inaccessible and were not assessed.
If these materials are discovered during construction activities, they should be presumed to contain asbestos and be treated as ACMs or be sampled immediately upon discovery and prior to disturbance for asbestos content by a certified asbestos inspector in accordance with 29 CFR 1926.1101.
The following materials were not sampled due to the destructive methods required and are assumed to be asbestos-containing (if encountered):
• HVAC Vibration Dampeners
• Mirror Mastic
4.3 Lead in Paint and Surface Coatings
Paint and surface coatings which contain detectable concentrations of lead considered “lead-containing paints” (LCP). Since OSHA has no specific action level for lead in paint, all paint on the site found to have a measurable concentration of lead should be assumed to be lead containing.
Work performed which may disturb lead-containing paint is regulated under OSHA as referenced under 29 CFR 1926.62.
Summary Paint Chip Sampling Results
Sample ID Location Substrate Component Color Result
PC-1 Roof Metal Roof Hatch Brown 0.024%
September 23, 2024
Sample ID Location Substrate Component Color Result
PC-2 Common Areas
Metal Doors Grey <0.0047%
PC-3 Common Areas
Metal Door Frames
Grey 0.027%
PC-4 Lounges CMU Walls White <0.0039%
P-5 Laundry and Common Areas
CMU Walls White <0.0043%
PC-6 Mechanical Chases
Metal Doors White 0.15%
PC-7 Mechanical Chases
Metal Door Frames
White 0.22%
PC-8 Rooms CMU Walls Brown 0.0025%
PC-9 Bathrooms in Rooms
Metal Door Frames
White 0.019%
PC-10 Bathrooms in Rooms
Wood Doors White <0.0068%
PC-11 Interior Rooms
Metal Window Frames and Panels
White 0.028%
PC-12 Entrance to Rooms
Metal Doors Brown 0.0042%
PC-13 Exterior Rooms
Metal Door/ Window Frames
Brown 0.020%
PC-14 Mechanical Building 445A
Metal Double Door Frames
Grey <0.0023%
PC-15 Mechanical Building 445A
Metal Double Doors
Grey <0.0029%
PC-16 Exterior Common Areas
Metal Door Frames
Brown 0.012%
September 23, 2024
5.0 RECOMMENDATIONS AND REGULATORY REQUIREMENTS
Based on our understanding of the purpose of the Asbestos and Lead-Paint Survey, the results of laboratory analysis, and our findings and observations, ECS presents the following recommendations.
5.1 Asbestos-Containing Materials
None of the bulk samples submitted to Scientific Analytical Institute, Inc. were reported to contain detectable concentrations of asbestos. If additional suspect asbestos-containing materials are uncovered which were not accessible during this sampling event, it is recommended that these materials be sampled or tested immediately upon discovery for asbestos content by an asbestos inspector in accordance with 29 CFR 1926.1101.
5.2 Lead in Paint and Surface Coatings
Based on the findings of the lead survey, detectable concentrations of lead were identified on some paints and surface coatings.
The presence of lead is a concern primarily when conditions exist where it may be inhaled or ingested.
Regardless of the analytical results of a material, all painted and/or glazed surfaces may still contain concentrations of lead in the paint, which when disturbed, may generate lead dust greater than the Permissible Exposure Limit (PEL) of 50 micrograms per cubic meter (ug/m3) as an 8-hour Time Weighted Average (TWA) established by the OSHA “Lead Exposure in Construction Rule (29 CFR 1926.62).”
The OSHA standard gives no guidance on acceptable levels of lead in paint at which no exposure to airborne lead (above the action level) would be expected. Rather, OSHA defines airborne concentrations, and references specific types of work practices and operations from which a lead hazard may be generated (reference 29 CFR 1926.62, section d). Environmental and personnel monitoring should be conducted during any removal/demolition process (as appropriate) to verify that actual personal exposures are below the Permissible Exposure Limit (PEL) of 50 micrograms per cubic meter (µg/m3) as an 8-hour Time Weighted Average (TWA). Under OSHA requirements, the contractor performing renovation work will be required to conduct this monitoring and follow applicable requirements under 29 CFR 1926.62 if disturbing lead-containing paint.
6.0 LIMITATIONS
The conclusions and recommendations presented within this report are based upon a reasonable level of assessment within normal bounds and standards of professional practice for a site in this particular geographic setting. ECS is not responsible or liable for the discovery and elimination of hazards that may potentially cause damage, accidents, or injuries.
The observations, conclusions, and recommendations pertaining to environmental conditions at the subject site are necessarily limited to conditions observed, and/or materials reviewed at the time this study was undertaken. No warranty, expressed or implied, is made with regard to the conclusions and recommendations presented within this report. This report is provided for the exclusive use of the client. This report is not intended to be used or relied upon in connection with other projects or by other unidentified third parties without the written consent of ECS and the client.
September 23, 2024
Our recommendations are in part based on federal, state, and local regulations and guidelines. ECS does not assume the responsibility of the person(s) in charge of the site, or otherwise undertake responsibility for reporting to any local, state, or federal public agencies, any conditions at the site that may present a potential danger to public health, safety, or the environment. Under this scope of services, ECS assumes no responsibility regarding any response actions initiated as a result of these findings. General compliance with regulations and response actions are the sole responsibility of the Client and should be conducted in accordance with local, state, and/or federal requirements.
September 23, 2024
Appendix I: Figures
Not to Scale
SUBJECT PROPERTY
Figure 1
Site Location Map
BEQ M445
Camp Johnson, Jacksonville, North Carolina
ECS Project No. 49-23910
XX-XX
LEGEND
Sample Location
Lead Containing Paint
No Lead or Asbestos Detected
NOTES:
Not to scale
Samples color coded
Figure 2
Sample Locations
BEQ M445
Camp Johnson, Jacksonville, North Carolina
ECS Project No. 49-23910
1F
2F
3F
HA5-2
HA6-1
HA6-2
HA7-1
HA7-2
HA8-1
HA8-2
HA5-1
HA9-2
HA9-3
HA9-4
HA9-6
HA9-5
HA9-1
HA10-7
HA10-6
HA13-1
HA10-5HA10-4
HA13-2
HA10-3
HA10-2
HA10-1
HA11-2
HA11-1
HA16-1,2
HA15-1,2
HA14-2
HA14-1
HA12-2
HA12-1
PC-8
PC-6,7
PC-5
PC-4
PC-3
PC-2
HA9-7
PC-9
PC-10
PC-11 PC-12
PC-13
PC-16
XX-XX
LEGEND
Sample Location
Lead Containing Paint
No Lead or Asbestos Detected
NOTES:
Not to scale
Samples color coded
Figure 3
Roof/M445A Sample Locations
BEQ M445
Camp Johnson, Jacksonville, North Carolina
ECS Project No. 49-23910
HA3-1HA2-1
HA1-2
HA1-1
HA3-2
PC-1
HA4-1
HA4-2
HA2-2
M445A
PC-14
PC-15
Appendix II: Site Photographs
1 - Building M445
2 - Laundry room
ECS Project No. 49:23910
3 - Hallway
4 - Common room
5 - Mechanical chase
6 - Bathroom showing white LCP on metal door frame
7 - Common room
8 - Room showing brown LCP on CMU walls
9 - Exterior walkway
10 - Mechanical room
11 - Roof
12 - Brown LCP on metal roof hatch
13 - White LCP on metal doors and door frames
14 - Gray LCP on metal door frames
15 - Mechanical building M445A
16 - Mechanical building M445A interior
17 - View of VCT in the 1st floor lounge.
Appendix III: Asbestos Bulk Sample Results
Bulk Asbestos Analysis By Polarized Light Microscopy EPA Method: 600/R-93/116 and
40 CFR, Part 763, Subpart E, App.E
Lab Order ID:Attn: 10061415Customer: ECS Southeast, LLP 6714 Netherlands Dr Wilmington, NC 28405
Analysis:
Date Received:
Braxton Dawson
PLM
08/30/2024
Project: M445 - Camp Johnson ACM Date Reported: 09/06/2024
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos
Fibrous Components
Non-Fibrous Components Treatment
Attributes
HA1-1
10061415_0001
Roof Tar Mats
None Detected 10% 10%
Fiber Glass Cellulose
80% Other
Non-Fibrous
Dissolved
Black, Gray
Heterogeneous
HA1-2
10061415_0002
Roof Tar Mats
None Detected 10% 10%
Fiber Glass Cellulose
80% Other
Non-Fibrous
Dissolved
Black, Gray
Heterogeneous
HA2-1
10061415_0003
Silver Seam Sealant
None Detected 30% Cellulose 70% Other
Fibrous
Dissolved
Silver, Black
Heterogeneous
HA2-2
10061415_0004
Silver Seam Sealant
None Detected 30% Cellulose 70% Other
Fibrous
Dissolved
Black, Silver
Heterogeneous
HA3-1
10061415_0005
Built-up Roofing
None Detected 20% Fiber Glass 80% Other
Non-Fibrous
Dissolved
Black
Heterogeneous
HA3-2
10061415_0006
Built-up Roofing
None Detected 20% Fiber Glass 80% Other
Non-Fibrous
Dissolved
Black
Heterogeneous
HA4-1
10061415_0007
Flashing Material
None Detected 10% 10%
Fiber Glass Cellulose
80% Other
Non-Fibrous
Dissolved
Black
Heterogeneous
HA4-2
10061415_0008
Flashing Material
None Detected 10% 10%
Cellulose Fiber Glass
80% Other
Non-Fibrous
Dissolved
Black
Heterogeneous
Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogenous soil samples be conducted by TEM for confirmation of "None Detected" by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program.
Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.
Megan Javonovich (52)
Analyst Approved Signatory
Page 1 of 7P-F-002 r15 1/15/2028 Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
EPA Method: 600/R-93/116 and
40 CFR, Part 763, Subpart E, App.E
Lab Order ID:Attn: 10061415Customer: ECS Southeast, LLP 6714 Netherlands Dr Wilmington, NC 28405
Analysis:
Date Received:
Braxton Dawson
PLM
08/30/2024
Project: M445 - Camp Johnson ACM Date Reported: 09/06/2024
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos
Fibrous Components
Non-Fibrous Components Treatment
Attributes
HA5-1
10061415_0009
2x2 Fissured Ceiling Tiles
None Detected 40% 40%
Cellulose Fiber Glass
10% 10%
Other Perlite
Fibrous
Ashed
Gray
Homogeneous
HA5-2
10061415_0010
2x2 Fissured Ceiling Tiles
None Detected 40% 40%
Cellulose Fiber Glass
10% 10%
Perlite Other
Fibrous
Ashed
Gray
Homogeneous
HA6-1 - A
10061415_0011
Beige 12" VCT and Black Mastic
None Detected 100% Other
Non-Fibrous
Dissolved
Beige
Homogeneous tile
HA6-1 - B
10061415_0043
Beige 12" VCT and Black Mastic
None Detected 10% Cellulose 90% Other
Non-Fibrous
Dissolved
Black
Homogeneous mastic
HA6-2 - A
10061415_0012
Beige 12" VCT and Black Mastic
None Detected 100% Other
Non-Fibrous
Dissolved
Beige
Homogeneous tile
HA6-2 - B
10061415_0044
Beige 12" VCT and Black Mastic
None Detected 10% Cellulose 90% Other
Non-Fibrous
Dissolved
Black
Homogeneous mastic
HA7-1
10061415_0013
Grey HVAC Duct Sealant
None Detected 100% Other
Non-Fibrous
Ashed
Gray
Homogeneous
HA7-2
10061415_0014
Grey HVAC Duct Sealant
None Detected 100% Other
Non-Fibrous
Ashed
Gray
Homogeneous
Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogenous soil samples be conducted by TEM for confirmation of "None Detected" by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program.
Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.
Megan Javonovich (52)
Page 2 of 7P-F-002 r15 1/15/2028 Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
EPA Method: 600/R-93/116 and
40 CFR, Part 763, Subpart E, App.E
Lab Order ID:Attn: 10061415Customer: ECS Southeast, LLP 6714 Netherlands Dr Wilmington, NC 28405
Analysis:
Date Received:
Braxton Dawson
PLM
08/30/2024
Project: M445 - Camp Johnson ACM Date Reported: 09/06/2024
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos
Fibrous Components
Non-Fibrous Components Treatment
Attributes
HA8-1 - A
10061415_0015
Beige 12" VCT and Black Mastic
None Detected 100% Other
Non-Fibrous
Dissolved
Beige
Homogeneous tile
HA8-1 - B
10061415_0045
Beige 12" VCT and Black Mastic
None Detected 100% Other
Non-Fibrous
Dissolved
Black
Homogeneous mastic
HA8-2 - A
10061415_0016
Beige 12" VCT and Black Mastic
None Detected 100% Other
Non-Fibrous
Dissolved
Beige
Homogeneous tile
HA8-2 - B
10061415_0046
Beige 12" VCT and Black Mastic
None Detected 100% Other
Non-Fibrous
Dissolved
Black
Homogeneous mastic
HA9-1
10061415_0017
CMU Surfacing Material
None Detected 100% Other
Non-Fibrous
Dissolved
Beige, White
Heterogeneous
HA9-2
10061415_0018
CMU Surfacing Material
None Detected 100% Other
Non-Fibrous
Dissolved
Beige, White
Heterogeneous
HA9-3
10061415_0019
CMU Surfacing Material
None Detected 100% Other
Non-Fibrous
Dissolved
Beige, White
Heterogeneous
HA9-4
10061415_0020
CMU Surfacing Material
None Detected 100% Other
Non-Fibrous
Dissolved
Beige, White
Heterogeneous
Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogenous soil samples be conducted by TEM for confirmation of "None Detected" by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program.
Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.
Megan Javonovich (52)
Page 3 of 7P-F-002 r15 1/15/2028 Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
EPA Method: 600/R-93/116 and
40 CFR, Part 763, Subpart E, App.E
Lab Order ID:Attn: 10061415Customer: ECS Southeast, LLP 6714 Netherlands Dr Wilmington, NC 28405
Analysis:
Date Received:
Braxton Dawson
PLM
08/30/2024
Project: M445 - Camp Johnson ACM Date Reported: 09/06/2024
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos
Fibrous Components
Non-Fibrous Components Treatment
Attributes
HA9-5
10061415_0021
CMU Surfacing Material
None Detected 100% Other
Non-Fibrous
Dissolved
Beige, White
Heterogeneous
HA9-6
10061415_0022
CMU Surfacing Material
None Detected 100% Other
Non-Fibrous
Dissolved
Beige, White
Heterogeneous
HA9-7
10061415_0023
CMU Surfacing Material
None Detected 100% Other
Non-Fibrous
Dissolved
Beige, White
Heterogeneous
HA10-1
10061415_0024
Ceiling Texture
None Detected 100% Other
Non-Fibrous
Teased
White
Homogeneous
HA10-2
10061415_0025
Ceiling Texture
None Detected 100% Other
Non-Fibrous
Teased
White
Homogeneous
HA10-3
10061415_0026
Ceiling Texture
None Detected 100% Other
Non-Fibrous
Teased
White
Homogeneous
HA10-4
10061415_0027
Ceiling Texture
None Detected 100% Other
Non-Fibrous
Teased
White
Homogeneous
HA10-5
10061415_0028
Ceiling Texture
None Detected 100% Other
Non-Fibrous
Teased
White
Homogeneous
Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogenous soil samples be conducted by TEM for confirmation of "None Detected" by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program.
Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.
Megan Javonovich (52)
Page 4 of 7P-F-002 r15 1/15/2028 Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
EPA Method: 600/R-93/116 and
40 CFR, Part 763, Subpart E, App.E
Lab Order ID:Attn: 10061415Customer: ECS Southeast, LLP 6714 Netherlands Dr Wilmington, NC 28405
Analysis:
Date Received:
Braxton Dawson
PLM
08/30/2024
Project: M445 - Camp Johnson ACM Date Reported: 09/06/2024
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos
Fibrous Components
Non-Fibrous Components Treatment
Attributes
HA10-6
10061415_0029
Ceiling Texture
None Detected 100% Other
Non-Fibrous
Dissolved
White
Homogeneous
HA10-7
10061415_0030
Ceiling Texture
None Detected 100% Other
Non-Fibrous
Dissolved
White
Homogeneous
HA11-1
10061415_0031
CMU Wall Caulk
None Detected 100% Other
Non-Fibrous
Ashed
Gray
Homogeneous
HA11-2
10061415_0032
CMU Wall Caulk
None Detected 100% Other
Non-Fibrous
Ashed
Gray
Homogeneous
HA12-1
10061415_0033
Exterior Door Caulk
None Detected 100% Other
Non-Fibrous
Ashed
Gray
Homogeneous
HA12-2
10061415_0034
Exterior Door Caulk
None Detected 100% Other
Non-Fibrous
Ashed
Gray
Homogeneous
HA13-1 - A
10061415_0035
Drywall & Joint Compound
None Detected 100% Other
Non-Fibrous
Teased
White
Homogeneous texture, no joint compound
HA13-1 - B
10061415_0047
Drywall & Joint Compound
None Detected 10% Cellulose 90% Other
Non-Fibrous
Crushed
Gray
Homogeneous drywall
Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogenous soil samples be conducted by TEM for confirmation of "None Detected" by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program.
Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.
Megan Javonovich (52)
Page 5 of 7P-F-002 r15 1/15/2028 Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
EPA Method: 600/R-93/116 and
40 CFR, Part 763, Subpart E, App.E
Lab Order ID:Attn: 10061415Customer: ECS Southeast, LLP 6714 Netherlands Dr Wilmington, NC 28405
Analysis:
Date Received:
Braxton Dawson
PLM
08/30/2024
Project: M445 - Camp Johnson ACM Date Reported: 09/06/2024
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos
Fibrous Components
Non-Fibrous Components Treatment
Attributes
HA13-2 - A
10061415_0036
Drywall & Joint Compound
None Detected 100% Other
Non-Fibrous
Teased
White
Homogeneous texture, no joint compound
HA13-2 - B
10061415_0048
Drywall & Joint Compound
None Detected 10% Cellulose 90% Other
Non-Fibrous
Crushed
Gray
Homogeneous drywall
HA14-1
10061415_0037
Fiberglass TSI Sealant
None Detected 10% Wollastonite 90% Other
Non-Fibrous
Dissolved
White
Homogeneous
HA14-2
10061415_0038
Fiberglass TSI Sealant
None Detected 10% Wollastonite 90% Other
Non-Fibrous
Dissolved
White
Homogeneous
HA15-1 - A
10061415_0039
Black 12" VCT and Mastic
None Detected 100% Other
Non-Fibrous
Dissolved
Black
Homogeneous tile
HA15-1 - B
10061415_0049
Black 12" VCT and Mastic
None Detected 100% Other
Non-Fibrous
Dissolved
Yellow
Homogeneous mastic
HA15-2 - A
10061415_0040
Black 12" VCT and Mastic
None Detected 100% Other
Non-Fibrous
Dissolved
Black
Homogeneous tile
HA15-2 - B
10061415_0050
Black 12" VCT and Mastic
None Detected 100% Other
Non-Fibrous
Dissolved
Yellow
Homogeneous mastic
Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogenous soil samples be conducted by TEM for confirmation of "None Detected" by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program.
Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.
Megan Javonovich (52)
Page 6 of 7P-F-002 r15 1/15/2028 Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
EPA Method: 600/R-93/116 and
40 CFR, Part 763, Subpart E, App.E
Lab Order ID:Attn: 10061415Customer: ECS Southeast, LLP 6714 Netherlands Dr Wilmington, NC 28405
Analysis:
Date Received:
Braxton Dawson
PLM
08/30/2024
Project: M445 - Camp Johnson ACM Date Reported: 09/06/2024
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos
Fibrous Components
Non-Fibrous Components Treatment
Attributes
HA16-1 - A
10061415_0041
White w/ Blue 12" VCT and Mastic
None Detected 100% Other
Non-Fibrous
Dissolved
Beige
Homogeneous tile
HA16-1 - B
10061415_0051
White w/ Blue 12" VCT and Mastic
None Detected 100% Other
Non-Fibrous
Dissolved
Yellow
Homogeneous mastic
HA16-2 - A
10061415_0042
White w/ Blue 12" VCT and Mastic
None Detected 100% Other
Non-Fibrous
Dissolved
Beige
Homogeneous tile
HA16-2 - B
10061415_0052
White w/ Blue 12" VCT and Mastic
None Detected 100% Other
Non-Fibrous
Dissolved
Yellow
Homogeneous mastic
Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogenous soil samples be conducted by TEM for confirmation of "None Detected" by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program.
Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.
Megan Javonovich (52)
Page 7 of 7P-F-002 r15 1/15/2028 Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888 l 00 lo l 4 \ \ Client: ECS Southeast, LLC *Instructions:
Contact: Braxton Dawson Use Column •a• for your contact info Address: 6714 Netherlands Drive
Wilmington, NC 28405 Phone: 910-899-1289 To See an Example Click the
Fax: 910-686-9666 bottom Example Tab.
Email: bdawson@ecslimited .com cc: Enter samples between "<<"and">>"
Project: M445 - Camp Johnson ACM Begin Samples with a "<< "above the first sample
Scientific • and end with a ">>" below the last sample. Analytical !.AJ
Client Notes: Only Enter your data on the first sheet "Sheet1" Institute .,.
Date Sampled: 8/28/2024 12:00 P.O.#. 49-23910-2 Note: Data 1 and Data 2 are optional 4604 Dundas Drive Date Submitted: 8/29/2024 17:00 fields that do not show up on the official Greensboro, NC 27407 report, however they will be included Phone: 336.292.3888 Analysis: PLM Bulk w/ Positive Stop in the electronic data returned to you Fax: 336.292.3313 TurnAroundTime: 3-dav to facilitate vour reintearation of the report data. Email: lab@sailab.com
Sample Number !Notes ISample Description !Location
HA1-1 Roof Tar Mats Roof
HA1-2 Roof Tar Mats Roof
HA2-1 Silver Seam Sealant Roof
HA2-2 Silver Seam Sealant Roof
HA3-1 Built-up Roofina Roof
HA3-2 Built-UP Roofina Roof HA4-1 Flashina Material Perimeter Paraoets
HA4-2 Flashina Material Perimeter Parapets HAS-1 2x2 Fissured Ceilina Tiles Lounaes and Hallwavs HAS-2 2x2 Fissured Ceilina Tiles Lounaes and Hallways HA6-1 Beiae 12" VCT and Black Mastic Common Areas HA6-2 Beiae 12" VCT and Black Mastic Cammon Areas HA7-1 Grev HVAC Duct Sealant Mechanical Chases HA7-2 Grev HVAC Duct Sealant Mechanical Chases HA8-1 Beiae 12" VCT and Black Mastic Rooms HA8-2 Beiae 12" VCT and Black Mastic Rooms HA9-1 CMU Surfacina Material Rooms and Common Areas HA9-2 CMU Surfacina Material Rooms and Common Areas HA9-3 CMU Surfacina Material Rooms and Common Areas HA9-4 CMU Surfacina Material Rooms and Common Areas HA9-5 CMU Surfacina Material Rooms and Common Areas HA9-6 CMU Surfacina Material Rooms and Common Areas HA9-7 CMU Surfacina Material Rooms and Common Areas HA10-1 Ceilina Texture Rooms onlv HA10-2 Ceilina Texture Roomsonlv HA10-3 Ceilina Texture Rooms onlv HA10-4 Ceilina Texture Rooms onlv HA10-5 Ceilina Texture Roomsonlv HA10-6 Ceilina Texture Rooms onlv HA10-7 Ceilina Texture Rooms onlv HA11-1 CMU Wall Caulk Room Comers HA11-2 CMU Wall Caulk Room Comers HA12-1 Exterior Door Caulk Rooms HA12-2 Exterior Door Caulk Rooms HA13-1 Drvwall & Joint Comoound Rooms HA13-2 Drvwall & Joint Comoound Rooms HA14-1 Fiberalass TSI Sealant Mech. Rooms HA14-2 Fiberalass TSI Sealant Mech. Rooms HA15-1 Black 12" VCT and Mastic 1st Floor Lou nae HA15-2 Black 12" VCT and Mastic 1st Floor Lounae HA16-1 White w/ Blue 12" VCT and Mastic 1st Floor Lounae HA16-2 White w/ Blue 12" VCT and Mastic 1st Floor Lounae
Accepted ·EI
Appendix IV: Lead Laboratory Analytical Results
Analysis for Lead Concentration in Paint Chips by Flame Atomic Absorption Spectroscopy
EPA SW-846 3050B/6010C/7000B
Lab Order ID:Attn: 10061423Customer: ECS Southeast, LLP 6714 Netherlands Dr Wilmington, NC 28405
Analysis:
Date Received:
Braxton Dawson
PBP
08/30/2024
Project: M445 - Camp Johnson Date Reported: 09/06/2024
Sample ID
Lab Sample ID
Description
Lab Notes
Concentration (ppm)
Concentration (% by weight)
Mass (g)
PC-1
10061423_0001
Brown Metal Roof Hatch
2400.1016 0.024%
PC-2
10061423_0002
Grey Metal Doors <470.0853 <0.0047%
PC-3
10061423_0003
Grey Metal Door Frames
2700.1191 0.027%
PC-4
10061423_0004
White CMU Walls <390.1020 <0.0039%
PC-5
10061423_0005
White CMU Walls <430.0920 <0.0043%
PC-6
10061423_0006
White Metal Doors
15000.1531 0.15%
PC-7
10061423_0007
White Metal Door Frames
22000.0925 0.22%
PC-8
10061423_0008
Brown CMU Walls
250.1777 0.0025%
Disclaimer: Unless otherwise noted blank sample correction was not performed on analytical results. Scientific Analytical Institute participates in the AIHA ELPAT program. ELPAT Laboratory ID: 173190. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. Analytical uncertainty available upon request. The quality control samples run with the samples in this report have passed all EPA required specifications unless otherwise noted. RL: (Report Limit for an undiluted 50ml sample is 4µg Total Pb).
Mark Doki (16)
Page 1 of 2L-F-021 r17 2/13/2027 Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
Analysis for Lead Concentration in Paint Chips by Flame Atomic Absorption Spectroscopy
EPA SW-846 3050B/6010C/7000B
Lab Order ID:Attn: 10061423Customer: ECS Southeast, LLP 6714 Netherlands Dr Wilmington, NC 28405
Analysis:
Date Received:
Braxton Dawson
PBP
08/30/2024
Project: M445 - Camp Johnson Date Reported: 09/06/2024
Sample ID
Lab Sample ID
Description
Lab Notes
Concentration (ppm)
Concentration (% by weight)
Mass (g)
PC-9
10061423_0009
White Metal Door Frames
1900.0916 0.019%
PC-10
10061423_0010
White Wood Doors <680.0590 <0.0068%
PC-11
10061423_0011
White Window Frames and Panels
2800.1109 0.028%
PC-12
10061423_0012
Brown Metal Doors
420.1483 0.0042%
PC-13
10061423_0013
Brown Door/Window Frames
2000.0961 0.020%
PC-14
10061423_0014
Grey Metal Double Door Frames <230.1728 <0.0023%
PC-15
10061423_0015
Grey Metal Double Doors <290.1369 <0.0029%
PC-16
10061423_0016
Brown Metal Door Frames
1200.0519 0.012%
Disclaimer: Unless otherwise noted blank sample correction was not performed on analytical results. Scientific Analytical Institute participates in the AIHA ELPAT program. ELPAT Laboratory ID: 173190. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. Analytical uncertainty available upon request. The quality control samples run with the samples in this report have passed all EPA required specifications unless otherwise noted. RL: (Report Limit for an undiluted 50ml sample is 4µg Total Pb).
Mark Doki (16)
Page 2 of 2L-F-021 r17 2/13/2027 Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
Mobile#:
Fax:
Email:
Project:
Clent NGIN:
O..Sampled:
P.0.1.
Dall Submltlad:
PC-1
PC-2
PC-3
PC-4
PC-5
PC-6
PC-7
PC-8
PC-9
PC-10
PC-11
PC-12
PC-13
PC-14
PC-15
PC-16
ECS utheast, LLC Braxton Dawson 6714 Netherlands Drive Wilmington, NC 28405 910-899-1289 910-686-9666 bdawson@ecslimited.com
M445 - Camp Johnson
49-23910-2 8/28/2024 12:00
8/29/2024 17:00
U• Column -s• for your contact Info
To See an Example CIiek Ille bottom Example Tab.
Enter..,,,,,,_.....,, "Cc• and'">>• ..,,,,,....,..wlllta"<<"MOW9.,_,.,.,....,.
and and ... ""»· ........... ..,,,,..
Only Enlw your data on the fnt .,,_, "ShNW
Nole: Data 1 and Dela 2 .. optional flelda thllt do not allow up on Ille ol'lfcla/ report, IICM9wr they wlll be Included In ,,,. eleclronlc data f8tumed to )'OIi
'° l'ac:ltlaf9 al,,, Brown Metal Roof Hatch Grev Metal Doors Grev Metal Door Frames White CMU Walls White CMU Walls White Metal Doors White Metal Door Frames Brown CMU Walls White Metal Door Frames White Wood Doors White Window Frames and Panels Brown Metal Doors Brown Door/Window Frames Grev Metal Double Door Frames Grey Metal Double Doors Brown Metal Door Frames -
Lead Paint Chips
Sdal1tlffc
""°" Dunda Orin
G~NC27407
Phone: u•.2112.~ Fu: "4.292.DU
*,,..#: labOullab.com
Roof Common Areas Common Areas Lounaes Laundrey and Common Areas Mechanical Chases Mechanical Chases Rooms Bathrooms in Rooms Bathrooms in Rooms Interior Rooms Entrance to Rooms Exterior Rooms Mechanical Bldg. 445A Mechanical Blda. 445A Exterior Common Areas
Accepted Er Reiecte~ D
~ [stJ (o : 2J) d±L Received By
Appendix V: Certifications/ Licenses
| Title Page |
| Cover Letter |
| Executive Summary |
| 1.0 Site Description |
| 2.0 Purpose |
| 3.0 Methodology |
| 3.1 Asbestos-Containing Materials |
| 3.2 Lead in Paint and Surface Coatings |
| 4.0 Results |
| 4.1 Asbestos Sampling |
| 4.2 Suspect or Assumed Asbestos-Containing Materials |
| 4.3 Lead in Paint and Surface Coatings |
| 5.0 Recommendations and Regulatory Requirements |
| 5.1 Asbestos-Containing Materials |
| 5.2 Lead in Paint and Surface Coatings |
| 6.0 Limitations |
| Figures |
| Site Photographs |
| Asbestos Bulk Sample Results |
| Lead Laboratory Analytical Results |
| Certifications/Licenses |
File details come from the government source that posted it. Updated .