This document contains a federal contract solicitation and related correspondence regarding replacing an air handling unit. The solicitation seeks to replace Air Handling Unit #3 located on the roof of Building 3030 at Naval Station Oceana. The scope of work includes securing all electrical power utilizing lockout/tagout procedures, disconnecting and removing wiring and components from the existing unit, demolishing insulation and piping, removing the existing unit, providing and installing a new unit that meets specifications, installing new outside air dampers and actuators, and ensuring controls compatibility with the direct digital controls system. The correspondence provides additional details regarding power and control wiring routing and requests information on the electrical panel and circuit breaker feeding an outlet on the unit. Only contractors holding the Utility Mechanical Construction for HR MACC contract N4008523KD0043-0048 are eligible to bid. The cut-off date for proposals is July 21, 2023. The Navy Facilities Engineering Command is the contracting agency.
View the file
Other files
Show all 37
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Page Section Para. Dwg #
1 Etolin Strait Associates 11/17/23
The power feeders and control wiring for
AHU-2, AHU-3, and the 120V convenience outlet circuit all come up thru the bottom of AHU-3 curb thru control cabinet.
In order to secure and deenergize all electrical wiring for safe removal of AHU-
3, AHU-2 will be deenergized, disconnected and off for duration of replacement task.
Does government require keeping AHU-2 running during the replacement of AHU-3 and have other plans to do so?
The Contractor will have to cordinate with the
Activity POC to schedule an outage.
2 Etolin Strait Associates 11/17/23
The power feeders and control wiring for
AHU-2, AHU-3, and the 120V convenience outlet circuit all come up thru the bottom of AHU-3 curb thru control cabinet.
In order to secure and deenergize all electrical wiring for safe removal of AHU-
3, AHU-2 will be
Contractor shall let Activity POC know of this issue.
3 Etolin Strait Associates 11/17/23
Please provide the panel location and circuit breaker that feeds the existing convenience outlet on AHU-3. This will require LO/TO to secure for removal and reinstallation.
No as-builds were found for this panel location. Contractor shall talk with Activity
POC for location.
Project Title: REPLACE AHU#3 ABOVE ROOM 39, BLDG 3030, NAS
OCEANA
Solicitation / RFP#: N4008523R2780 - PPI Cut Off Date: July 21, 2023
Amend No.
GOVERNMENT RESPONSE
PPI No.
Offeror
Date
Submitted
REFERENCE
A