REPLACE AHU#3 ABOVE ROOM 39, BLDG 3030, NAS OCEANA
Solicitation number
N4008523R2780
Issued by

About this file

This document contains responses to pre-proposal inquiries (PPIs) regarding the replacement of Air Handling Unit (AHU) #3 above Room 39 in Building 3030 at Naval Station Oceana. The Naval Facilities Engineering Command issued solicitation number N4008523R2780 for this project with a PPI cut-off date of July 21, 2023. PPI #1 requests as-built drawings showing the location and specifications of the electrical panel feeding AHU #2 and AHU #3, as well as the circuit breaker sizes. It notes the power to both units comes through the same feed. PPI #2 advises both units will be out of service at the same time during replacement of AHU #3, and the contractor must coordinate the outage with the building activity point of contact.

View the file

Other files

File Type Posted
23R2780 AMENDMENT 0015.pdf PDF
23R2780 AMENDMENT 0014.pdf PDF
AMENDMENT 0013.pdf PDF
SOW AMENDED (1) (W)21304022 REPLACE AHU 3 ABOVE ROOM 39 - OC-3030.pdf PDF
PPI Set 5 Etolin Strait OC-3030.xlsx.pdf PDF
CSAA - AHU-3 - Consolidated Customer Package.pdf PDF
PPI Set 6 Etolin Strait OC-3030.xlsx.pdf PDF
AMENDMENT 0012.pdf PDF
AMENDMENT 0011.pdf PDF
AMENDMENT 0010.pdf PDF
AMENDMENT 0009.docx DOCX document
PPI Set 2 Etolin Strait OC3030.xlsx.pdf PDF
AMENDMENT 0008.pdf PDF
PPI MIG GOV OC3030 Replace AHU 3 Above room 39.xlsx.pdf PDF
PPI Goshawk OC3030 AHU 3.xlsx.pdf PDF
PPI Set 4 Etolin Strait OC3030.xlsx.pdf PDF
PPI Set 3 Etolin Strait OC3030.xlsx.pdf PDF
CSAA - Oceana-3030 AHU-3 Equipment Specifications - TRANE.pdf PDF
Amendment 0007.pdf PDF
AMENDMENT 0006.pdf PDF
AMENDMENT 0005.pdf PDF
AMENDMENT 0004.pdf PDF
Oceana IDIQ Front End SPECS.pdf PDF
Site Visit AHU.pdf PDF
AMENDMENT 0003.pdf PDF
AMENDMENT 0002.pdf PDF
IMG-5778.jpg JPG image
IMG-5777.jpg JPG image
IMG-5779.jpg JPG image
AMENDMENT 0001.pdf PDF
PROVISION 52.204-24.pdf PDF
va167 (1).txt TXT text file
SECNAV 5512.pdf PDF
GENERAL REQUIREMENTS BLDG 3030.pdf PDF
PPI Spreadsheet.xlsx XLSX spreadsheet
BASE ACCESS INSTRUCTION.pdf PDF
SOW (W)21304022 AHU 3 ABOVE ROOM 39 IS DOWN THIS IS NEEDED FOR COMMS EQUIP OC3030.pdf PDF
Show all 37

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Page Section Para. Dwg #

1 ETOLIN STRAIT ASSOCIATES 7.13.23

during the site visit we observed that the power feeding AHU 3 come thru a pitch pocket inside AHU 3 then feeds to a junction box which then connects to another junction box mounted on the outside of AHU 2 and feeds power to that unit. The B3030 user and the ET tried to locate the panel where the power feed is coming from for AHu's 2 and 3 but could not locate the panel. Please provide as-built drawings showing the location and mfg/capacity of the panel feeding these AHUs. We also need to know the breaker sizes for the circuit(s) feeding the AHUs.

As-builds drawings for this area are not available. Here is the info for the Power.

Motor Control Panel MCP-R Room – 34

AHU-2 CB11

AHU-3 CB12

2 ETOLIN STRAIT ASSOCIATES 7.13.23

The scope of work states to disconnect/reconnect the power from

AHU 3 so it can be removed and replaced. At the site visit it was observed that one feed is providing power to both as describe in PPI #1.

This is not a question but more of a notice that both units will be out of service at the same time for the same duration. Please advise if the govt has a different plan.

Contractor will have to coordinate with the

Building/Activity POC for this action.

Project Title: REPLACE AHU#3 ABOVE ROOM 39, BLDG

3030, NAS OCEANA

Solicitation / RFP#: N4008523R2780 - PPI Cut Off Date: July 21, 2023

Amend No.

GOVERNMENT RESPONSE

PPI No.

Offeror

Date

Submitted

REFERENCE

A

File details come from the government source that posted it. Updated .