CSAA - AHU-3 - Consolidated Customer Package.pdf

PDF 773 KB Posted

Attached to
REPLACE AHU#3 ABOVE ROOM 39, BLDG 3030, NAS OCEANA
Solicitation number
N4008523R2780
Issued by

About this file

This document provides specifications for an air handling unit replacement project for Building 3030 at Naval Station Oceana. The scope of work includes disconnecting and removing the existing Air Handling Unit 3, associated controls, piping and wiring. The contractor shall supply and install a new air handler that meets or exceeds the specifications outlined, including dimensions, capacity, and electrical requirements. Additional requirements include installing new outside air dampers and actuators that are compatible with the existing Direct Digital Controls system. Only contractors holding the Utility Mechanical Construction Multiple Award Contract for the Naval Facilities Engineering Command can bid on this project.

View the file

Other files

File Type Posted
23R2780 AMENDMENT 0015.pdf PDF
23R2780 AMENDMENT 0014.pdf PDF
AMENDMENT 0013.pdf PDF
SOW AMENDED (1) (W)21304022 REPLACE AHU 3 ABOVE ROOM 39 - OC-3030.pdf PDF
PPI Set 5 Etolin Strait OC-3030.xlsx.pdf PDF
PPI Set 6 Etolin Strait OC-3030.xlsx.pdf PDF
AMENDMENT 0012.pdf PDF
AMENDMENT 0011.pdf PDF
AMENDMENT 0010.pdf PDF
AMENDMENT 0009.docx DOCX document
PPI Set 1 Etolin Strait OC3030.xlsx.pdf PDF
PPI Set 2 Etolin Strait OC3030.xlsx.pdf PDF
AMENDMENT 0008.pdf PDF
PPI MIG GOV OC3030 Replace AHU 3 Above room 39.xlsx.pdf PDF
PPI Goshawk OC3030 AHU 3.xlsx.pdf PDF
PPI Set 4 Etolin Strait OC3030.xlsx.pdf PDF
PPI Set 3 Etolin Strait OC3030.xlsx.pdf PDF
CSAA - Oceana-3030 AHU-3 Equipment Specifications - TRANE.pdf PDF
Amendment 0007.pdf PDF
AMENDMENT 0006.pdf PDF
AMENDMENT 0005.pdf PDF
AMENDMENT 0004.pdf PDF
Oceana IDIQ Front End SPECS.pdf PDF
Site Visit AHU.pdf PDF
AMENDMENT 0003.pdf PDF
AMENDMENT 0002.pdf PDF
IMG-5778.jpg JPG image
IMG-5777.jpg JPG image
IMG-5779.jpg JPG image
AMENDMENT 0001.pdf PDF
PROVISION 52.204-24.pdf PDF
va167 (1).txt TXT text file
SECNAV 5512.pdf PDF
GENERAL REQUIREMENTS BLDG 3030.pdf PDF
PPI Spreadsheet.xlsx XLSX spreadsheet
BASE ACCESS INSTRUCTION.pdf PDF
SOW (W)21304022 AHU 3 ABOVE ROOM 39 IS DOWN THIS IS NEEDED FOR COMMS EQUIP OC3030.pdf PDF
Show all 37

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Trane Performance Climate Changer Air Handler

Unit Overview - AHU-3

Application Unit Size External Dimensions Weight

Height Width Length Installed Rigging Outdoor unit CSAA010 43.6 in 61.5 in 133.0 in 2367 lb 2069 lb

Quantity of Shipping Sections Largest Ship Split

Heaviest Ship Split Elevation Height Width Length

1 piece(s) 43.6 in 61.5 in 132.9 in 2141 lb 0.00 ft Supply Fan

Airflow 5000 cfm Total Static Pressure 4.570 in H2O

Note: Height includes air handler sloped roof panel and standing seam.

Construction Features

Panel 2in. foam injected R-13 with thermal break

Panel Material

All unit inner panels -galvanized

Integral Base Frame 6in. integral base frame

Paint Slate gray

Short Circuit

Current Rating

5 kA

Agency Approval UL listed unit

Roof Curb Type Standard roof curb

Unit Electrical

Circuit Voltage/Phase/Frequency FLA MCA Max Fuse Size

Circuit number 1 Supply fan + controls-LL 200-208/3/60 29.50 A 36.50 60.00

Unit Controls Factory Controls Package Variable volume

Controller Type Symbio Controller mounting Unit mounted

Controller location Right Factory programmed Yes

Warranty Warranty section Extd. warranty

Labor - 1st year 1st year labor warranty

Air mixing section - Position: 1

Openings

Face Path Type Airflow Face Velocity Area Pressure

Drop Hood

Back Outside Parallel blade damper 5000 cfm 1202 ft/min 4.16 sq ft 0.321 in H2O Yes

Bottom Return Parallel blade damper 5000 cfm 1202 ft/min 4.16 sq ft 0.282 in H2O N/A

Filter

Type Frame MERV Rating Quantity Size Pleated media - MERV 8 2" MERV 8 4.00 20in.x25in.

Pressure Drop Condition Face Velocity Airflow Area

0.595 Mid-life 360 ft/min 5000 cfm 13.89 sq ft

Section Options

Door Location Both

CSAA

Quantity: 1 Tags: AHU-3

Job Name: NAS Oceana - Bldg. 3030, AHU#3

2023/12/05 14:19:09 Page 1 of 3 Product Version: 1

Cooling coil section - Position: 2

Coil Construction

Model Chilled water - 1/2" Unit Optimized, General (UW)

Rows 8 Tube Diameter 1/2in. tube diameter (12.7 mm)

Coil Connection Standard Tube Matl/Wall Thickness .016" (0.406 mm) copper tubes

Fin Spacing 87 Per Foot Fin Material Aluminum fins

Fin Type Delta flo H (Hi efficient) Face Area 9.98 sq ft

Coil (top/single) H x L 28 in. (711 mm) X 50" (1270 mm) finned length

Casing Galvanized Coating CompleteCoat(TM) Epoxy E-coat

Turbulators Not Included Rigging Weight 188.3 lb

Installed Weight 259.9 lb

Coil Section Options

Extended Drain and Vent Holes only Drain Pan Stainless steel

Drain Pan Size Medium Drain Connection Left

Minimum Trap Height (L) 8.039 in H Trap Dimension 4.693 in J Trap Dimension 2.346 in

Door Location Right

Coil Performance

Capacity

Total 190.74 MBh Sensible 137.79 MBh

Air

Flow 5000 cfm Entering Dry Bulb 80.00 F Entering Wet Bulb 67.00 F Leaving Dry Bulb 55.00 F Leaving Wet Bulb 54.68 F

Pressure Drop 1.057 in H2O Face Velocity 501 ft/min

Fluid

Flow 25.34 gpm Entering 42.00 F Leaving 57.00 F

Pressure Drop 2.80 ft fluid Tube Velocity 1.98 ft/s

Reynolds Number 5730.35 Type Water

Concentration 100.00 % Fouling Factor 0.00000 hr-sq ft-deg F/Btu

Volume 8.56 gal

AHRI 410 Classification

AHRI 410 Classification NOT Certified by AHRI Data Generation Date 11/21/2023

Trane Select Assist update number 2770

Note: Coil is NOT certified by AHRI. Coil is within the scope of AHRI Standard 410.

Supply fan section - Position: 3

Fan Data

Wheel Diameter/Type/Class 18.25in. dd plenum, full width, M press

Fan Quantity 1 Discharge Location Bottom front

Motor Location Right side drive

Blades Higher eff.(some bands lower,more spike)

Drive Service Factor Direct drive Fan K-factor 1822.00

Fan Performance

Airflow 5000 cfm Total Static Pressure 4.570 in H2O

Total Brake Power 5.612 hp Operating Speed 2371 rpm

AMCA FEG FEG85

Bare fan peak total efficiency 72.20 %

Unit Static Efficiency 64.19 %

Motor Interface Options

Selection Type VFD Voltage 200-208/3

Mounting Location Internal mounting VFD Frequency 80.00 Hz

Motor Data

Power / Fan 7.5 hp Voltage 200-208/3

Speed 1800 Class NEMA premium compliant ODP

Efficiency 91.19 % Part Load Efficiency 85.73 %

Fan electrical power (FEP) 4.82 kW

FEI 1.31

AHRI VFD HP 7.500 hp Wire to air static efficiency 55.64 %

Note: VFD driven motor fan electrical power calculated in accordance with AHRI 430.

Note: Certified airflow performance per AHRI 430

Fan Section Options

Fan Wheel Balance Inverter balance with shaft grounding

Door Location Both Door Guard Yes

Fan Discharge Options

Face Type Airflow Face Velocity Area Pressure Drop Exhaust Hood Damper Torque

Requirement

Bottom Face Feature

Bottom rectangular discharge 5000 cfm 1502 ft/min 3.33 sq ft 0.282 in H2O N/A N/A

Note: Certified by the AHRI Central Station Air-Handling Unit (AHU) Certification Program, based on AHRI Standard 430/431. AHRI certified units are subject to rigorous and continuous testing, have performance ratings independently measured and are third party verified. Certified units may be found in the AHRI Directory at www.ahridirectory.org.

CSAA

Quantity: 1 Tags: AHU-3

Job Name: NAS Oceana - Bldg. 3030, AHU#3

2023/12/05 14:19:09 Page 2 of 3

Pressure Drop in (in w.g.)

Supply fan

Air mixing section 1.23

Coil section 1.06

Fan section 0.28

Internal Static Pressure 2.57

External Static Pressure 2.00

Total Static Pressure 4.57

Starter/VFD only section - Position: 4 Supply Fan Motor Interface Door Right

CSAA

Quantity: 1 Tags: AHU-3

Job Name: NAS Oceana - Bldg. 3030, AHU#3

2023/12/05 14:19:09 Page 3 of 3

File details come from the government source that posted it. Updated .