PPI Set 3 Etolin Strait OC3030.xlsx.pdf

PDF 9 KB Posted

Attached to
REPLACE AHU#3 ABOVE ROOM 39, BLDG 3030, NAS OCEANA
Solicitation number
N4008523R2780
Issued by

About this file

This document contains a project information package (PIP) regarding the replacement of air handling unit 3 above room 39 in building 3030 at Naval Station Oceana. The PIP includes six sections requesting information from offerors. Section one requests as-built electrical drawings, as none are available. Section two requests the location, manufacturer, and specifications of the electrical panel and breakers feeding the relevant air handling units. Section three notes the current electrical configuration and requests plans for shutting down related systems during work. Section four notes another component is also fed through the same configuration. Section five requests new equipment specifications and electrical requirements. The related federal contract opportunity is solicitation number N4008523R2780 from the Department of the Navy Naval Facilities Engineering Command to replace the air handling unit. The PIP cutoff date for responses is July 21, 2023.

View the file

Other files

File Type Posted
23R2780 AMENDMENT 0015.pdf PDF
23R2780 AMENDMENT 0014.pdf PDF
AMENDMENT 0013.pdf PDF
SOW AMENDED (1) (W)21304022 REPLACE AHU 3 ABOVE ROOM 39 - OC-3030.pdf PDF
PPI Set 5 Etolin Strait OC-3030.xlsx.pdf PDF
CSAA - AHU-3 - Consolidated Customer Package.pdf PDF
PPI Set 6 Etolin Strait OC-3030.xlsx.pdf PDF
AMENDMENT 0012.pdf PDF
AMENDMENT 0011.pdf PDF
AMENDMENT 0010.pdf PDF
AMENDMENT 0009.docx DOCX document
PPI Set 1 Etolin Strait OC3030.xlsx.pdf PDF
PPI Set 2 Etolin Strait OC3030.xlsx.pdf PDF
AMENDMENT 0008.pdf PDF
PPI MIG GOV OC3030 Replace AHU 3 Above room 39.xlsx.pdf PDF
PPI Goshawk OC3030 AHU 3.xlsx.pdf PDF
PPI Set 4 Etolin Strait OC3030.xlsx.pdf PDF
CSAA - Oceana-3030 AHU-3 Equipment Specifications - TRANE.pdf PDF
Amendment 0007.pdf PDF
AMENDMENT 0006.pdf PDF
AMENDMENT 0005.pdf PDF
AMENDMENT 0004.pdf PDF
Oceana IDIQ Front End SPECS.pdf PDF
Site Visit AHU.pdf PDF
AMENDMENT 0003.pdf PDF
AMENDMENT 0002.pdf PDF
IMG-5778.jpg JPG image
IMG-5777.jpg JPG image
IMG-5779.jpg JPG image
AMENDMENT 0001.pdf PDF
PROVISION 52.204-24.pdf PDF
va167 (1).txt TXT text file
SECNAV 5512.pdf PDF
GENERAL REQUIREMENTS BLDG 3030.pdf PDF
PPI Spreadsheet.xlsx XLSX spreadsheet
BASE ACCESS INSTRUCTION.pdf PDF
SOW (W)21304022 AHU 3 ABOVE ROOM 39 IS DOWN THIS IS NEEDED FOR COMMS EQUIP OC3030.pdf PDF
Show all 37

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Page Section Para. Dwg #

1 Etolin Strait Associates

Please provide as built electrical drawings. No As-builds for this area are available.

2 Etolin Strait Associates

The panel feeding AHU-3 & AHU-2 were not located during site visit. Please provide location of panel, manufacturer and breaker type and size feeding AHU-

Motor Control Panel MCP-R Room-34

AHU-2 CB11

AHU-3 CB12

3 Etolin Strait Associates

Currently AHU-2 is fed thru the pitch pocket thru AHU-3 to a junction box with conduit across roof to AHU-2 disconenct switch. AHU-2 will have to be shut down as well. Please address how to handle.

Contractor will have to coordinate with the

Building/Activity POC for this action.

4 Etolin Strait Associates

The convienience receptacle is also fed thru the pitch pocket thru AHU-3 to the junction box.

5 Etolin Strait Associates

Please provide new AHU basis of design specifications with electrical requirements.

New Equipment specifications will be provided.

Project Title: REPLACE AHU#3 ABOVE ROOM 39, BLDG

3030, NAS OCEANA

Solicitation / RFP#: N4008523R2780 - PPI Cut Off Date: July 21, 2023

Amend No.

GOVERNMENT RESPONSE

PPI No.

Offeror

Date

Submitted

REFERENCE

A

File details come from the government source that posted it. Updated .