N4008521B2504AsbestosSurveyReport.pdf
PDF 42 MB Posted
- Attached to
- Infrastructure Reset Demo Buildings - Package B Federal contract opportunity
- Solicitation number
- N4008521B2504
About this file
This document provides details on a federal solicitation and related asbestos survey report. The solicitation number is N4008521B2504 and concerns the demolition of various buildings at Naval Facilities Engineering Command according to provided plans and specifications. The Navy is seeking demolition services as described in the Infrastructure Reset Demo Buildings - Package B opportunity. The related asbestos survey report, with file name N4008521B2504AsbestosSurveyReport.pdf, contains information on any asbestos found in the buildings to be demolished. The response deadline and award date are not specified.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| N4008521B2504 Amendment08.pdf | ||
| N4008521B2505 Amendment08.pdf | ||
| N4008521B2504 Amendment07.pdf | ||
| EMD Decision Memorandum.pdf | ||
| N4008521B2504 Amendment06.pdf | ||
| Building 40 Asbestos Survey.pdf | ||
| Building 40 Lead Survey.pdf | ||
| Building 40 Demo Plans.pdf | ||
| Amended Section 02 82 16 Removal of Asbestos Materials.pdf | ||
| N4008521B2504 Amendment05.pdf | ||
| N4008521B2504 Amendment04.pdf | ||
| N4008521B2504 Amendment03.pdf | ||
| Contractor_Environmental_Guide.pdf | ||
| N4008521B2504 Amendment02.pdf | ||
| N4008521B2504 Amendment01.pdf | ||
| N4008521B2504Dwgs.pdf | ||
| N4008521B2504LeadSurveyReport.pdf | ||
| N4008521B2504Solicitation.pdf | ||
| N4008521B2504Specs.pdf |
Show all 19
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Asbestos Survey FY20 Infrastructure Reset Demo Buildings
Marine Corps Base Camp Lejeune Project # 20-0001
Package B
Report Prepared By:
Christopher B. Walker The Walker Group Architecture, Inc
September 21st, 2020 WGA Project No. – 2001.IR20
Project Information
The Walker Group Architecture, Inc. was contracted by Camp Lejeune to conduct an asbestos sampling survey for Buildings/Structures: 3, 3B, 39, 113, 116, 117, 117A, 126, 214, 229, 300A, 307, 339, 425, 435, 436, 438, 524, 731, 738, 762, 812, 812A, 911, 1010, 1203, 1307, 1315, 1409, 1410, 1728, 1742, 1804, 1808, 2043, H48, PT6, SH13, SH22, SH39, SHE22 . Building 300 was also contracted for demolition and has previously been inspected for Lead and asbestos by WGA consultant Precision environmental. (See appendix B for survey). The specified buildings or structures are slated for demolition on board Marine Corps Base Camp Lejeune. An asbestos survey has been requested prior to disturbance of any potential asbestos containing materials
(ACM).
Scope of Services
A. The survey was performed on 01/24/18, 03/01/18, 03/06/18, 03/11/18, 04/19/18, 04/24/19, 05/02/19, 04/28/20, 05/13/20, 05/14/20, 05/20/20, 09/15/20 by Christopher B. Walker (NC Accredited Inspector #12878, expires January 31, 2021). The sampling was conducted in general accordance with the U.S. Environmental Protection Agency (EPA) requirements as defined in the asbestos Hazards Emergency Response Act (40 CFR Part 763) guidelines (AHERA) and in general accordance with the North Carolina Health Hazards Control Unit (NCHHCU).
B. The survey was conducted to identify the presence of asbestos containing materials (ACM) prior to repairs to the building.
C. The building was assessed to determine homogenous areas (groups of materials appearing to have been installed in the same general time period and uniform in color and texture).
D. As per AHERA, sufficient samples were collected from random locations of each homogenous area, with the number of samples based on the following criteria:
a. Thermal Insulation Materials (piping, breeching, boiler insulation, etc.) – A minimum of (3) samples are required. Patch areas (less than 6 square or liner feet) may have (2) sample collected.
b. Surfacing Materials (plaster, fireproofing, etc.) – A minimum of (7) samples are to be taken for areas greater than 5,000 square feet, five (5) samples for areas greater than 1,000 square feet, but less than 5,000 square feet, three
(3) samples for areas less than 1,000 square feet, two (2) samples for patching materials.
c. Miscellaneous Materials (flooring, adhesives, roofing, wallboard, etc.) – A minimum of (2) samples are required.
If any one sample of a material from a homogenous area is found to be positive, then that material is considered positive, regardless of results of other samples of that material, within that area.
Samples
A. The Walker Group Architecture collected suspect samples and shipped them to EMSL Analytical, Inc. (NVLAP Accredited Laboratory 102104-0) for PLM (polarized Light Microscopy) analysis. In an effort to reduce cost, the Walker Group instructed the laboratory to Stop Analysis at the first positive sample for each suspect material HGA and not to analyze the remaining samples from the same HGA.
Building 3
Findings
A. Building Description and Findings (Inspected 04-24-19)
Building 3 is an abandoned office building. The building exterior is brick and cmu.
Interior partitions are cmu and wood framed with gypsum board, and the roof is wood framed with asphalt shingles.
B. Laboratory Results
Material Material Type
Location Friability Laboratory Result Approx.Quantity
Window Caulk Misc Exterior NF Non-Detected N/A
Beige VCT (Floor tile) Misc Interior NF Non-Detected N/A Beige VCT (Mastic) Misc Interior NF Non-Detected N/A Beige VCT (Leveler) Misc Interior NF Non-Detected N/A
Rubber Base/ Mastic Misc Interior NF Non-Detected N/A 2X2 ACT Misc Interior Ceiling F Non-Detected N/A
Exterior Door Caulk Misc Exterior Doors NF Non-Detected N/A
Gypsum Board/Joint Compound Misc Interior Walls NF Non-Detected N/A
Asphalt Shingles/ Felt Misc Roof NF Non-Detected N/A
Carpet Mastic Misc Interior NF Non-Detected N/A
Residual Mastic at 2nd Floor Windows
Misc Exterior NF Non-Detected N/A
Plaster Ceiling Surf. Ceiling F Non-Detected N/A
Exterior Concrete Expansion Joint at Building Perimeter
Misc Exterior NF 5% Chrysotile 1250SF
Exterior Residual Caulk at Old Awning Location
Misc Exterior NF 8% Chrysotile 350SF
Based on the sample analysis, the following materials were found to be Asbestos Containing Materials.
Exterior Concrete Expansion Joint at Building Perimeter Exterior Residual Caulk at Old Awning Location
Materials found to contain asbestos in current inspection report and government provided inspection report should all be considered for the purpose of any demolition/renovation activities and disturbance.
ACM Materials found in previous government report in area of work:
-Pipe Insulation at 1st floor above ceilings – approx. 850LF -Mudded fittings at pipe insulation – approx. 100EA -Residual exterior caulking at new windows and doors – approx. 550LF -Exterior Caulking at doorways - approx. 50LF -Floor tile debris at 2nd floor sill plate – approx.2SF -Interior caulking at first floor center closet – approx. 24LF -Carpet adhesive – approx. 9500SF purpose of any demolition/renovation activities and disturbance.
Building 3B
A. Building Description and Findings (Inspected 05-14-19)
Building 3B is an abandoned office building. The building exterior is brick and cmu.
Interior partitions are cmu and wood framed with gypsum board, and the roof is wood
Material Materi al Type
Location Friability Laboratory Result Approx.Quantity
Asphalt Shingles/ Felt Misc Roof NF Non-Detected N/A
Exterior Door/ Window Caulk Misc Exterior NF Non-Detected N/A 12X12 Cream VCT (mastic) (Mechanical room only)
Misc Interior NF Non-Detected N/A
12X12 Cream VCT (Floor tile) Misc Interior NF Non-Detected N/A
12X12 Beige VCT (Floor tile) (Mechanical room only)
Misc Interior NF Non-Detected N/A
12X12 Beige VCT Mastic (Mechanical room only)
Misc Interior NF Non-Detected N/A
Gypsum Board/Joint Compound Misc Interior NF Non-Detected N/A
2X2 ACT Misc Interior NF Non-Detected N/A
Rubber Base/ Mastic Misc Interior NF Non-Detected N/A
Based on the sample analysis, none of the materials were found to be Asbestos Containing Materials.
Building 3C
C. Building Description and Findings (Inspected 05-14-19)
Building 3C is a mechanical building serving Building 3. The building exterior is brick and cmu. The roof construction is metal trusses, wood decking, and asphalt shingles.
D. Laboratory Results
Material Materi al Type
Location Friability Laboratory Result Approx.Quantity
Asphalt Shingles/ felt Misc Exterior NF Non-Detected N/A
Door Caulk Misc Interior NF Non-Detected N/A
Building 39
A. Building Description and Findings (Inspected 03-11-18)
Building 39 is a martial arts facility. The building exterior is vinyl siding and brick with a wood framed, asphalt shingle roof. The interior walls are gypsum board with a gypsum board ceiling.
Location Friability Laboratory Result Approx.Quantity
Asphalt Shingles/Felt Misc Roof NF Non-Detected N/A
Roof Mastic at Exhaust Misc Roof NF 8% Chrysotile 2SF Cream 12x12 VCT/mastic Misc Floors NF <1% Chrysotile 487SF Beige 12x12 VCT Misc Floors NF Non-Detected N/A 12x12 VCT /mastic under stairs Misc Stairwell/Floor NF 5% Chrysotile 16SF Residual mastic from VCT Misc Floor NF 5% Chrysotile 660SF Gypsum/Joint Compound Misc Interior Walls F Non-Detected N/A Rubber Base/Mastic Misc Interior Wall NF Non-Detected N/A Fiberboard Misc Wall F Non-Detected N/A Textured ceilings in locker room Surface Ceiling F Non-Detected N/A
Roof Mastic at Exhaust Cream 12x12 VCT 12x12 VCT under stairs Residual mastic from VCT
Building 113
A. Building Description and Findings (Inspected 03-01-18)
Building 113 is a storage facility. The building exterior is brick masonry. The roof is wood framed with asphalt shingles. The interior walls are brick, covered in areas by gypsum board with a gypsum board ceiling.
Location Friability Laboratory Result Approx.Quantity
4” pipe insulation in attic TSI Attic F 5% Amosite 10% Chrysotile
360LF
Mudded fittings at 4” pipe Misc Attic F 30% Chrysotile 19EA
Asphalt shingles Misc Roof NF Non-Detected N/A Gypsum/Joint Compound Misc Walls F Non-Detected N/A Exterior window caulk Misc Exterior NF 2% Chrysotile 238LF
4” pipe insulation in attic Mudded fittings at 4” pipe
Exterior window caulk
Building 116
Building 116 is a storage facility. The building exterior is brick masonry. The roof is wood framed with asphalt shingles. The interior walls are brick covered in areas by gypsum board with a gypsum board ceiling.
Location Friability Laboratory Result Approx.Quantity
Gypsum/Joint compound Misc Walls F Non-Detected N/A
Rubber Base/Mastic Misc Floor/Wall NF Non-Detected N/A Exterior door/window caulk Misc Exterior Wall NF Non-Detected N/A Asphalt Shingles Misc Roof NF Non-Detected N/A
Based on the sample analysis, none of the materials were found to be Asbestos
Building 117
Building 117 is a storage facility. The building exterior is brick masonry. The roof is wood framed with asphalt shingles. The interior walls are wood stud and gypsum board with a gypsum board ceiling.
Location Friability Laboratory Result Approx.Quantity
Exterior caulk at reglet flashing Misc Exterior NF 8% Chrysotile 30LF
12x12 beige VCT Misc Floor NF Non-Detected N/A Gypsum/joint compound Misc Interior Wall/Ceiling F Non-Detected N/A Surface material on interior CMU at perimeter walls
Surface Walls F Non-Detected N/A
Water base/mastic Misc Floors NF Non-Detected N/A
Exterior caulk at reglet flashing
Building 117A
Building 117A is a storage facility. The building exterior is brick masonry. The roof is wood framed with asphalt shingles. A physical/ visual inspection revealed the following: No mechanical systems are in place.
Location Friability Laboratory Result Approx.Quantity
Asphalt Shingles Misc Roof NF Non-Detected N/A Exterior door caulk Misc Exterior NF Non-Detected N/A
Caulk at mechanical penetration on wall Misc Wall NF Non-Detected N/A
Building 126
A. Building Description and Findings (Inspected 05-02-19)
Building 126 is an abandoned ammunitions building. The building exterior is brick.
Interior partitions are cmu and wood framed with gypsum board and the roof is wood
Location Friability Laboratory Result Approx.Quantity
Asphalt Shingles Misc. Exterior NF Non-Detected N/A
Exterior Door/Window Caulk Misc Exterior NF Non-Detected N/A Gypsum Board/Joint Compound Misc Interior NF Non-Detected N/A purpose of any demolition/renovation activities and disturbance.
ACM Materials found in previous government report in area of work:
- Roof Sealant at Southwest vent piping – approx. 4SF
Buiding 214
A. Building Description and Findings (Inspected 05-20-20)
Building 214 is an abandoned office building. The building exterior is brick with a wood framed/asphalt shingle roof system. Interior partitions are wood framed with gypsum board.
Location Friability Laboratory Result Approx.Quantity
Asphalt Shingles/Felt Misc Roof NF Non-Detected N/A
Exterior Door/Window Caulk Misc Exterior NF Non-Detected N/A Gypsum Board/Joint Compound Misc Interior Walls NF Non-Detected N/A 12x12 Cream VCT/Mastic Misc Interior Floor NF Non-Detected N/A
12x12 White VCT/Mastic Misc Interior Floor NF Non-Detected N/A Plaster Walls Surf. Interior Ceiling F Non-Detected N/A 2x2 ACT Misc Interior Ceiling F Non-Detected N/A
Building 229
Building 229 is an operational storage facility. The building exterior is brick masonry.
The roof is wood framed with asphalt shingles. The interior walls are painted brick with a gypsum board ceiling.
Location Friability Laboratory Result Approx.Quantity
Asphalt Shingles Misc Roof NF Non-Detected N/A
Exterior Window Caulk Misc Exterior NF Non-Detected N/A Concrete Expansion Joint Misc Exterior NF Non-Detected N/A Residual Mastic around Columns Misc Interior NF Non-Detected N/A Gypsum/Joint Compound Misc Interior Walls F Non-Detected N/A Exterior Texture on Concrete Base Surface Exterior F 3% Chrysotile 316SF
Based on the sample analysis, the following materials were found to be Asbestos
Exterior Texture on Concrete Base
Building 300A
A. Building Description and Findings (Inspected 05-13-20)
Building 300A is a mechanical building serving Building 300. The Exterior is brick and cmu walls with a wood framed roof with asphalt shingles.
Location Friability Laboratory Result Approx.Quantity
Asphalt Shingles/Felt Misc Roof NF Non-Detected N/A
Door Caulk Misc Door NF Non-Detected N/A
Materials
Building 307
C. Building Description and Findings (Inspected 09-15-20)
Building 307 is an abandoned storage/office building that was damaged during the previous hurricane. The building exterior is brick and the roof consist of wood framing and asphalt shingles. The interior walls wood stud and gypsum board/plaster with plaster and acoustical ceilings.
Location Friability Laboratory Result Approx.Quantity
12x12 Cream VCT/Mastic Misc Floors NF Non-Detected N/A
2x2 ACT Misc Ceiling F Non-Detected N/A Gypsum Board/Joint Compound Misc Walls NF Non-Detected N/A Plaster Ceilings/Walls Surf. Walls/Ceiling F Non-Detected N/A Textured Ceiling Surf. Ceiling in Storage F Non-Detected N/A Asphalt Shingles/Felt Misc Main roof NF Non-Detected N/A Exterior Door/Window Caulk Misc Windows NF Non-Detected N/A Built Up Roof Misc Flat Roofs NF Non-Detected N/A Mastic at roof penetrations Misc Roof Penetrations NF Non-Detected N/A
Containing Materials
Building 339
A. Building Description and Findings (Inspected 09-15-20)
Building 339 is a storage building. The building exterior is stucco with metal windows/doors and an asphalt shingle roof. Interior partitions are wood with gypsum board. Flooring consists of VCT and sealed concrete.
Location Friability Laboratory Result Approx.Quantity
Exterior Stucco Surf Exterior Walls NF Non-Detected N/A
Asphalt Shingles/Felt Misc Roof NF Non-Detected N/A Exterior Door/Window Caulk Misc. Exterior
Doors/Windows NF 5% Chrysotile 168LF
9x9 Black VCT (Tile Only) Misc Floor Tile NF 2% Chrysotile 75SF
9x9 Black VCT (Mastic Only) Misc. Floors NF Non-Detected N/A Gypsum Board/Joint Compound Misc Walls NF Non-Detected N/A
Exterior Door/Window Caulk 9x9 Black VCT (Tile Only)
Additional items were found to be asbestos containing materials on previous government provided reports. See attached Appendix A for further information.
ACM Materials found in previous government report in area of work:
- 9x9 Black Floor Tile Mastic. 75SF
- 12x12 Black Floor Tile/Mastic- 575SF
- Adhesive at Board Back- 48SF
- White Heat Shield in attic – 8SF
Building 425
C. Building Description and Findings (Inspected 04/28/20)
Building 425 is an abandoned event building. The building exterior is brick masonry with aluminum windows/doors and an asphalt shingle roof. Interior partitions are wood and metal stud with plaster and gypsum board. Flooring consists of VCT, carpet, tile and sealed concrete.
Location Friability Laboratory Result Approx.Quantity
Asphalt Shingles Misc. Pitched Roof NF Non-Detected N/A
Exterior Door/Window Caulk Misc Exterior Windows/Doors
NF Non-Detected N/A
Gypsum Board/Joint Compound Misc. Interior Walls NF Non-Detected N/A 2x2 ACT Misc Interior Ceilings NF Non-Detected N/A 12x12 VCT with gray Specks Misc Small Bathrooms NF Non-Detected N/A
Plaster Walls/Ceilings Misc Interior perimeter Walls/Ceilings
NF Non-Detected N/A
Gray Rubber Base/Mastic Misc Interior Walls NF Non-Detected N/A
Built Up Roof Misc Flat Roof NF Non-Detected N/A
Roof Flashing at Reglet Misc Flat Roof NF Non-Detected N/A
Textured Ceiling Surf. Bar Textured Ceiling
F Non-Detected N/A
Roof Flashing at Roof Vents Misc Flat roof NF Non-Detected N/A
16x16 Vinyl Tile/Mastic Misc Flooring in atrium NF Non-Detected N/A
Residual Ceiling Tile Mastic Misc Ceilings throughout.
Residual round spots from previously removed ceilings
NF 3% Chrysotile 12,934SF
Joint Compound Misc Mechanical Room NF Non-Detected N/A
Residual Ceiling Tile Mastic
ACM Materials found in previous government report in area of work:
- Textured Ceiling Material approx. 1,500SF
- 12” Gray Floor Tile & Adhesive- 1,250SF
- Drywall/Joint Compound- 5,250SF
- Exterior Caulking- 25LF
- Transite Panel- 1SF
Building 435
Building 435 is a general storage facility. The building exterior is stucco type system with brick framed windows/doors. The roof consists of wood framing and asphalt shingles. The interior walls are painted cmu block with gypsum board ceilings.
Location Friability Laboratory Result Approx.Quantity
Asphalt Shingles/Felt Misc Roof NF Non-Detected N/A
Exterior Stucco Surface Exterior F Non-Detected N/A Exterior Door Caulk Misc Exterior NF Non-Detected N/A Exterior Window Caulk Misc Exterior NF 3% Chrysotile 672LF Gypsum/Joint Compound Misc Interior Wall F Non-Detected N/A Chalk Board / Fiberboard Misc Floor NF 5% Chrysotile 100SF Caulk at Chalk/Fiberboard Misc Wall NF 3% Chrysotile 100SF
Exterior Window Caulk Chalk Board / Fiberboard Caulk at Chalk/Fiberboard
Building 436
Building 436 is a general storage facility. The building exterior is stucco with brick framed windows/doors. The roof consists of wood framing and asphalt shingles. The interior walls are painted cmu block with gypsum board ceilings.
Location Friability Laboratory Result Approx.Quantity
Asphalt Shingles/Felt Misc Roof NF Non-Detected N/A
Exterior Stucco Surface Exterior F Non-Detected N/A Exterior Door Caulk Misc Exterior NF 3% Chrysotile 50LF Exterior Window Caulk Misc Exterior NF 3% Chrysotile 320LF Gypsum/Joint Compound Misc Interior Wall F Non-Detected Gray 12x12 VCT Mastic Misc Wall F Non-Detected Rubber Base/Mastic Misc Wall NF Non-Detected
Exterior Door Caulk Exterior Window Caulk
Building 438
A. Building Description and Findings (Inspected 05-20-20)
Building 438 is an abandoned storage/office building that was damaged during the previous hurricane. The building exterior is brick and the roof consist of wood framing and asphalt shingles.
Location Friability Laboratory Result Approx.Quantity
Asphalt shingles/felt Misc Floors NF Non-Detected N/A
Gypsum Board/Joint Compound Misc Ceiling NF Non-Detected N/A Gray Rubber Base/Mastic Misc Walls NF Non-Detected N/A
Building 524
A. Building Description and Findings (Inspected 05-21-20)
Building 524 is an abandoned office/event building. The building exterior is brick masonry with aluminum windows/doors and an asphalt shingle roof. Interior partitions are wood and metal stud with plaster and gypsum board. Flooring consists of VCT, carpet, tile and sealed concrete.
Location Friability Laboratory Result Approx.Quantity
Asphalt Shingles Misc. Pitched Roof NF Non-Detected N/A
Gypsum Board/Joint Compound Misc Exterior Windows/Doors
NF Non-Detected N/A
Wall Vapor Barrier Misc. Exterior Walls NF Non-Detected N/A 2x2 ACT Misc Interior Ceilings F Non-Detected N/A Plaster Ceiling Misc Interior Ceiling F Non-Detected N/A Door/Window Caulk Misc Door/Window
Caulk NF Non-Detected N/A
Caulk at Brick Step Flashing Misc Exterior Reglet NF Non-Detected N/A
Flashing at Roof Vent Misc Exterior Roof NF Non-Detected N/A
Built Up Roof Misc Flat Roof NF Non-Detected N/A
Expansion Joint Misc Expansion Joint at Exterior Walls
NF 2% Chrysotile 180LF
Residual Mastic at Exterior Wall
Misc Residual Caulk at 2nd floor exterior walls near flat
NF 8% Chrysotile 10LF roof 12x12 Cream VCT/Mastic Misc Flooring NF Non-Detected N/A
Rubber Base/ Mastic Misc Wall Base NF Non-Detected N/A
Expansion Joint Residual Mastic at Exterior Wall
ACM Materials found in previous government report in area of work:
- Fibrous Debris approx. 250SF
- Cloth Lagging Material- 20SF
- Gray Roof Sealant- 100SF
- Ceiling Tile Adhesive- 2800SF
- Black Roof Sealant- 1200SF
Building 731
A. Building Description and Findings (Inspected 05-14-20)
Building 731 is an abandoned restroom building that was damaged during the previous hurricane. The building exterior is cmu and the roof consist of wood framing and asphalt shingles.
Location Friability Laboratory Result Approx.Quantity
Asphalt shingles/felt Misc Roof NF Non-Detected N/A
Gypsum Board/Joint Compound Misc Ceiling NF Non-Detected N/A Door/Window Caulk Misc Windows NF Non-Detected N/A
Building 738
Building 738 is a grounds equipment shed. The building is a pre-engineered metal structure with exterior metal panels at the walls and roof. The interior walls are gypsum board and ceilings are drop down acoustical ceiling tiles.
Location Friability Laboratory Result Approx.Quantity
Black 12x12 VCT Misc Floor NF Non-Detected N/A
Gasket material on heat exchanger Misc NF Non-Detected N/A Transite panel material bathroom walls
Misc Walls F 20% Chrysotile 400SF
2x2 ACT Misc Ceiling F Non-Detected N/A Exterior Window Caulk Misc Exterior NF Non-Detected N/A Window Glaze Misc Exterior F Non-Detected N/A Gypsum/Joint Compound Misc Interior Wall F Non-Detected N/A Green VCT 12x12 under black on 1st Floor
Misc Floor NF Non-Detected N/A
Cream 12x12 VCT Misc Floor NF Non-Detected N/A
Transite panel material bathroom walls
Building 762
Building 762 is an abandoned office building. The building exterior is brick masonry with aluminum windows/doors and an asphalt shingle roof. Interior partitions are wood and metal stud with plaster and gypsum board. Flooring consists of VCT, carpet, tile and sealed concrete.
Asphalt Shingles Misc. Pitched Roof NF Non-Detected N/A
Plaster Walls/Ceiling Misc Interior Walls/Ceiling
NF Non-Detected N/A
12x12 Cream VCT/Mastic Misc. Floors under Carpet
NF Non-Detected N/A
2x2 ACT Misc Interior Ceilings F Non-Detected N/A Exterior Door/Window Caulk Misc Exterior
Doors/Windows NF Non-Detected N/A
Sealant at Brick Chimney Misc Roof Sealant at Chimney
NF 8% Chrysotile 6LF
Sealant at Brick Chimney
ACM Materials found in previous government report in area of work:
- Pipe Insulation approx. 32LF
- Cloth Expansion Joint material- 4SF
- Residual mastic- 15SF
Building 812
C. Building Description and Findings (Inspected 01-24-18 and 04-19-18)
Building 812 is a visitor/guard building. The building exterior is brick and the roof consists of wood framing and asphalt shingles. The interior walls wood stud and gypsum board with gypsum board ceilings.
Location Friability Laboratory Result Approx.Quantity
Asphalt shingles Misc Roof NF Non-Detected N/A
Storefront caulk Misc Doors NF Non-Detected N/A Window caulk Misc Windows NF Non-Detected N/A Asphalt shingles Misc Roof NF Non-Detected N/A Window Caulk Misc Windows NF Non-Detected N/A Gypsum Board/Joint Compound Misc Walls/Ceiling F Non-Detected N/A
Building 812A
A. Building Description and Findings (Inspected 01-24-18)
Building 812A is contractor vetting office. The building consists of a pre-fabricated metal building structure with exterior metal panels at the walls and pvc membrane roof.
Interior walls are gypsum board and the ceilings are drop down acoustical tile and gypsum board.
Location Friability Laboratory Result Approx.Quantity
Roof Membrane Misc. Roof NF Non-Detected N/A
Door Caulk Misc. Door NF Non-Detected N/A Gypsum Walls Misc. Walls F Non-Detected N/A Gypsum Ceiling Misc. Ceiling F Non-Detected N/A VCT/mastic Misc. Floor NF Non-Detected N/A
Based on the sample analysis none of the materials were found to be Asbestos
Building 911
Building 911 is a storage building. The building exterior is CMU block walls with a wood framed and asphalt shingle roof.
Asphalt shingles Misc Roof NF Non-Detected N/A
Building 1010
Building 1010 is a storage facility. The building is a pre-engineered metal structure with exterior metal panels at walls and roof. There is an additional room extension made of wood framing and wood sheathing. The interior walls are wood paneling with a gypsum board and drop in acoustical tile ceiling.
Location Friability Laboratory Result Approx.Quantity
Exterior roof sealant/silver Misc Exterior NF 3% Chrysotile 1250SF Dark Brown 9x9 VCT Misc Floors NF 5% Chrysotile 1000SF
12x12 Cream VCT Misc Floor NF <1% Chrysotile 48SF 12x12 Dark Blue VCT Misc Floor NF Non-Detected N/A 12x12 Black VCT Misc Floor NF Non-Detected N/A 12x12 Gray VCT Misc Floor NF 2% Chrysotile 50SF 12x12 Light Blue VCT Misc Floor NF Non-Detected N/A 12x12 Dark Beige VCT Misc Floor NF 5% Chrysotile 50SF 12x12 ACT I Misc Floor NF Non-Detected N/A 12x12 ACT II Misc Floor NF Non-Detected N/A Fiberboard Misc Walls F Non-Detected N/A Gypsum/Joint Ceiling Misc Exterior NF Non-Detected N/A Flat Roof Coating TSI Exterior NF Non-Detected N/A
Exterior roof sealant/silver Dark Brown 9x9 VCT
12x12 Cream VCT 12x12 Gray VCT 12x12 Dark Beige VCT
Building 1203
C. Building Description and Findings (Inspected 04/20/20)
Building 1203 is an abandoned workshop. The building exterior is cmu masonry with an asphalt shingle roof. Interior partitions are cmu masonry as well as wood framed with gypsum board. Flooring is VCT and sealed concrete.
Location Friability Laboratory Result Approx.Quantity
12x12 Black VCT & Mastic Misc. Interior Floor NF 5% Chrysotile 320SF
Window Glazing Misc Exterior Windows
NF Non-Detected N/A
Gypsum Board/Joint Compound Misc Interior Walls NF Non-Detected N/A
Exterior Door/Window Caulk Misc Exterior Doors NF 1% Chrysotile 350SF
12x12 Black VCT & Mastic Exterior Door/Window Caulk
ACM Materials found in previous government report in area of work:
- Window Glazing Material– approx. 576 LF
- White Heat Shield – approx. 2 SF
- 9” Black Floor Tile & Mastic- 224SF
- Gray Roofing Sealant- 2SF
Building 1307
Building 1307 is a wood framed storage building with vinyl siding and an asphalt shingle roof.
Asphalt shingles/felt Misc Roof NF Non-Detected N/A
Building 1315
A. Building Description and Findings (Inspected 05/14//20)
Building 1315 is a wood framed storage building with vinyl siding and an asphalt shingle roof.
Location Friability Laboratory Result Approx.Quantity
Plaster Walls Surf. Interior Wall NF <1% Chrysotile 400SF
Asphalt Shingles Misc Roof NF Non-Detected N/A Transite Panel Debris Misc Interior NF 15% Chrysotile 5SF Built Up Roof Misc Roof NF 3% Chrysotile 192SF Roof Debris Misc Exterior Debris NF 5% Chrysotile 5SF Window Glaze Misc Exterior Mech
Room window NF Non-Detected N/A
Exterior Door Caulk Misc Exterior mech.
Door
NF Non-Detected N/A
Plaster Walls Transite Panel Debris Built Up Roof Roof Debris
Additional items were found to be asbestos containing materials on previous government provided reports. See attached Appendix A for further information.
ACM Materials found in previous government report in area of work:
- Pipe Insulation– approx. 9 LF
- Transite Panel material – approx.1024 SF
- exterior Caulking- 17 LF
- Gray Roof Sealant- 160 SF
- HVAC Duct Insulation- 544 SF
Building 1409
Building 1409 is an operational training building. The building exterior is masonry with a textured finish. Interior partitions are wood framed with gypsum board and the roof is wood framed with asphalt shingles.
Location Friability Laboratory Result Approx.Quantity
Gypsum Board/ Joint Compound Misc Interior NF Non-Detected N/A
Exterior Window Caulk Misc Exterior NF Non-Detected N/A
Textured Masonry Wall Surf. Exterior NF Non-Detected N/A
Shingles/ Felt Misc Roof NF Non-Detected N/A
Window Glazing Misc Exterior NF Non-Detected N/A
Concrete Expansion Joint Misc Interior Floor NF Non-Detected N/A
Caulk at Roof Vents Misc Roof NF Non-Detected N/A purpose of any demolition/renovation activities and disturbance.
ACM Materials found in previous government report in area of work:
-Concrete expansion joint (perimeter and center joints) – approx. 484LF -Exterior window glazing – approx. 1584LF -Gray roofing sealant at box ridge vents – 160LF
Building 1410
Building 1410 is an operational office building. The building exterior is masonry with a textured finish. Interior partitions are wood framed with gypsum board and the roof is wood framed with asphalt shingles.
Location Friability Laboratory Result Approx.Quantity
Textured Wall Surf. Exterior NF Non-Detected N/A
Cream VCT (Floor tile) Misc Interior NF Non-Detected N/A
Cream VCT (Mastic) Surf. Interior NF Non-Detected N/A
Exterior Door/ Window Caulk Misc Exterior NF Non-Detected N/A
Rubber Base/ Mastic Misc Interior NF Non-Detected N/A
Gypsum Board/ Joint Compound Misc Interior NF Non-Detected N/A
2X2 ACT Misc Ceilings NF Non-Detected N/A
Caulk at Roof Vent Misc Roof NF Non-Detected N/A
Building 1728
A. Building Description and Findings (Inspected 03-16-18)
Building 1728 is a recreation pavilion snack stand. The building exterior cmu block walls with a built up roof.
Built up roof Misc Roof NF Non-Detected N/A
Building 1742
Building 1742 is an indoor handball court. The building exterior is brick with a wood framed, asphalt shingle roof. The interior walls and ceiling are high impact gypsum board.
Location Friability Laboratory Result Approx.Quantity
Fiberboard interior walls Misc Interior Walls F Non-Detected N/A
Flooring material, yellow Misc Interior Floor NF Non-Detected N/A Exterior mastic on duct insulation Misc Exterior NF Non-Detected N/A
Building 1804
Building 1804 is vehicle storage building. The building is a pre-engineered structure with metal wall and roof panels. There are no interior partitions.
Exterior Caulk Misc Exterior NF Non-Detected N/A
Building 1808
Building 1808 is vehicle storage building. The building is a pre-engineered structure with metal wall and roof panels. There are no interior partitions.
Exterior Caulk Misc Exterior NF Non-Detected N/A
Building 2043
Building 2043 is a golf course snack stand. The building exterior is wood siding with a wood framed, asphalt shingle roof. The interior walls and ceiling are FRP.
Location Friability Laboratory Result Approx.Quantity
Vinyl Floor/mastic Misc Interior Floor NF Non-Detected N/A
Building H48
Building H48 is a general storage shed. The building exterior is brick masonry. The roof is wood framed with asphalt shingles. The interior walls are brick with a transite panel ceiling.
Location Friability Laboratory Result Approx.Quantity
Ceiling transite board Misc Ceiling NF 15% Chrysotile 150SF
Ceiling transite board
Building PT6
Building PT6 is an abandoned office building. The building exterior is brick with stucco finish and a wood framed, asphalt shingle roof. The interior walls are gypsum board and painted brick with a gypsum board ceiling
Location Friability Laboratory Result Approx.Quantity
Exterior Stucco Surface Exterior Walls F <1% Chrysotile 2,250SF
Exterior Window Glaze Misc Exterior F Non-Detected Gypsum Board, Joint Compound Misc Interior F Non-Detected 12x12 Gray VCT 1st Floor Misc Interior Floor NF <1% Chrysotile 200SF Black VCT 2nd Floor Misc Interior Floor NF Non-Detected Tan VCT under black 2nd floor Misc Interior Floor NF 3% Chrysotile 300SF Fiberboard Misc Interior F Non-Detected Exterior Window/Door caulk Misc Exterior NF Non-Detected Asphalt Shingles Misc Roof NF Non-Detected Concrete expansion joint, perimeter floor floor
Misc Exterior NF 5% Chrysotile 160LF
Dark gray VCT, 1st floor bathroom
Misc Interior Floor NF <1% Chrysotile 200SF
Concrete expansion joint 1st floor middle of floor, square
Misc Interior NF 8% Chrysotile 15LF
Based on the sample analysis, the following materials were found to be Asbestos Containing
Exterior Stucco 12x12 Gray VCT 1st Floor Tan VCT under black 2nd floor Dark gray VCT, 1st floor bathroom Concrete expansion joint, perimeter floor floor Concrete expansion joint 1st floor middle of floor, square
Building SH13
Building SH13 is an abandoned metal guard house with acoustical ceiling.
2x2 Acoustical Ceiling Misc Ceiling F Non-Detected N/A
Building SH22
Building SH22 is an abandoned masonry guard house with gypsum board ceiling and asphalt shingle roof.
Location Friability Laboratory Result Approx.Quantity
Exterior Door Caulk Misc Exterior Door N Non-Detected N/A
Gypsum Board/Joint Compound Misc Interior Ceiling F Non-Detected N/A
Building SH39
A. Building Description and Findings (Inspected 04-28-20)
Building SH39 is a head facility and maintenance building. The building is constructed with cmu and wood framing and metal wall/roof panels. Interior walls consist of cmu and wood framing with gypsum board, and the floors are sealed concrete.
Location Friability Laboratory Result Approx.Quantity
Gypsum Board/Joint Compound Misc. Interior Walls NF Non-Detected N/A
Rubber Base/Mastic Misc. Interior Walls NF Non-Detected N/A
Exterior Door Caulk Misc. Exterior Doors NF Non-Detected N/A
Building SHE22
Building SHE22 is a metal restroom building with gypsum board ceiling and metal roof.
Location Friability Laboratory Result Approx.Quantity
Gypsum Board/Joint Compound Misc Interior Walls/Ceilings
NF Non-Detected N/A
See attached for Accreditations, Asbestos Lab Results and Chain of Custody. If further information is required, please contact me at 1-252-636-8778
Report Prepared by:
Christopher B. Walker North Carolina Asbestos Inspector Accreditation# 12878 The Walker Group Architecture, Inc., PO Box 541, New Bern, NC 28560
DRAWING NO.DATE
DRAWN BY
SCALE
PROJECT NO
ASBESTOS LOCATION PLAN
BUILDING 3
MCB CAMP LEJEUNE
1"=30'-0"
5-27-19
CBW
20-0001
G:\Projects\2020\2001.IR20\Drawings\100%\Package B\3\3-1.dwg
GROUP
ARCHITECTURE
WALKER
th e
N
AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP
AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.
AutoCAD SHX Text 252-636-8992(fax)
AutoCAD SHX Text
PO BOX 541, NEW BERN, NC 28563
AutoCAD SHX Text c
AutoCAD SHX Text 252-636-8778
AutoCAD SHX Text
EXTERIOR CONCRETE EXPANSION JOINT AT BUILDING PERIMETER - 1250SF
AutoCAD SHX Text
AutoCAD SHX Text
EXTERIOR RESIDUAL CAULK AT REMOVED AWNING - 350SF
AutoCAD SHX Text
FIRST FLOOR
AutoCAD SHX Text
2ND FLOOR
AutoCAD SHX Text
REMOVED AWNING LOCATION
AutoCAD SHX Text
SCALE
PROJECT NO
ASBESTOS LOCATION PLAN
MCB CAMP LEJEUNE
1/16"=1'-0"
CBW
20-0001
G:\Projects\2020\2001.IR20\Drawings\100%\Package B\39\39-1.dwg
GROUP
ARCHITECTURE
WALKER
th e
BUILDING 39
3-24-18
AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP
AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.
AutoCAD SHX Text 252-636-8992(fax)
AutoCAD SHX Text
PO BOX 541, NEW BERN, NC 28563
AutoCAD SHX Text c
AutoCAD SHX Text 252-636-8778
AutoCAD SHX Text ASBESTOS IDENTIFIED IN ROOF MASTIC AT EXHUAST FLUE IN THIS LOCATION, APPROX. 2SF.
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN ROOF MASTIC AT MECHANICAL EXHUAST , APPROX. 16LF.
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN 12X12 BLACK VCT/MASTIC UNDER STAIRS, APPROX. 16SF.
AutoCAD SHX Text ASBESTOS IDENTIFIED IN RESIDUAL MASTIC FROM PREVIOUSLY REMOVED VCT, APPROX. 660SF.
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN 12X12 CREAM VCT/MASTIC APPROX. 487SF.
SCALE
PROJECT NO
ASBESTOS LOCATION PLAN
MCB CAMP LEJEUNE
1/16"=1'-0"
CBW
20-0001
G:\Projects\2020\2001.IR20\Drawings\100%\Package B\113\113.dwg
GROUP
ARCHITECTURE
WALKER
th e
BUILDING 113
3-24-18
AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP
AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.
AutoCAD SHX Text 252-636-8992(fax)
AutoCAD SHX Text
PO BOX 541, NEW BERN, NC 28563
AutoCAD SHX Text c
AutoCAD SHX Text 252-636-8778
AutoCAD SHX Text ASBESTOS IDENTIFIED IN THERMAL SYSTEMS INSULATION AS INDICATED BY LINE TYPE IN ATTIC SPACE. ALL MUDDED FITTINGS AT INSULATION WERE FOUND TO CONTAIN ASBESTOS.
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN EXTERIOR WINDOW CAULK. APPROX. 238LF
ASBESTOS IDENTIFIED IN EXTERIOR WINDOW CAULK TYP. AT EXT. WINDOWS
SCALE
PROJECT NO
ASBESTOS LOCATION PLAN
MCB CAMP LEJEUNE
1/16"=1'-0"
CBW
20-0001
G:\Projects\2020\2001.IR20\Drawings\100%\Package B\117\117.dwg
GROUP
ARCHITECTURE
WALKER
th e
BUILDING 117
3-24-18
AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP
AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.
AutoCAD SHX Text 252-636-8992(fax)
AutoCAD SHX Text
PO BOX 541, NEW BERN, NC 28563
AutoCAD SHX Text c
AutoCAD SHX Text 252-636-8778
AutoCAD SHX Text ASBESTOS IDENTIFIED IN EXTERIOR CAULK AT REGLET FLASHING AT CANOPY AND BRICK FLASHING. TYPICAL AT CANOPIES.
AutoCAD SHX Text ASBESTOS IDENTIFIED IN EXTERIOR CAULK AT REGLET FLASHING ON CANOPYS. APPROX. 30LF.
SCALE
PROJECT NO
ASBESTOS LOCATION PLAN
MCB CAMP LEJEUNE
1/16"=1'-0"
CBW
20-0001
G:\Projects\2020\2001.IR20\Drawings\100%\Package B\229\229.dwg
GROUP
ARCHITECTURE
WALKER
th e
BUILDING 229
3-24-18
AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP
AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.
AutoCAD SHX Text 252-636-8992(fax)
AutoCAD SHX Text
PO BOX 541, NEW BERN, NC 28563
AutoCAD SHX Text c
AutoCAD SHX Text 252-636-8778
AutoCAD SHX Text ASBESTOS IDENTIFIED IN EXTERIOR CONCRETE BASE SURFACE TEXTURE. TYPICAL AT BUILDING PERIMETER.
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN EXTERIOR CONCRETE BASE SURFACE TEXTURE, APPROX. 316SF.
SCALE
PROJECT NO
ASBESTOS LOCATION PLAN
BUILDING 339
MCB CAMP LEJEUNE
1/16"=1'-0"
09-17-20
CBW
20-0001
G:\Projects\2020\2001.IR20\Drawings\100%\Package B\339\339.dwg
GROUP
ARCHITECTURE
WALKER
th e
N
AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP
AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.
AutoCAD SHX Text 252-636-8992(fax)
AutoCAD SHX Text
PO BOX 541, NEW BERN, NC 28563
AutoCAD SHX Text c
AutoCAD SHX Text 252-636-8778
AutoCAD SHX Text
9X9 BLACK VCT (VCT ONLY) - APPROX. 75SF
ASBESTOS LOCATED AT EXTERIOR DOOR/WINDOW CAULK, TYP.
SCALE
PROJECT NO
ASBESTOS LOCATION PLAN
BUILDING 425
MCB CAMP LEJEUNE
1/16"=1'-0"
05-18-20
CBW
20-0001
G:\Projects\2020\2001.IR20\Drawings\100%\Package B\425\425-1.dwg
GROUP
ARCHITECTURE
WALKER
th e
N
AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP
AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.
AutoCAD SHX Text 252-636-8992(fax)
AutoCAD SHX Text
PO BOX 541, NEW BERN, NC 28563
AutoCAD SHX Text c
AutoCAD SHX Text 252-636-8778
AutoCAD SHX Text
RESIDUAL CEILING TILE MASTIC - APPROX. 12,934SF
AutoCAD SHX Text *SEE GOV'T ASBESTOS REPORT AND PLAN FOR ADDITIONAL ASBESTOS CONTAINING MATERIAL LOCATIONS
AutoCAD SHX Text
1ST FLOOR
2ND FLOOR
SCALE
PROJECT NO
ASBESTOS LOCATION PLAN
MCB CAMP LEJEUNE
1/16"=1'-0"
CBW
20-0001
G:\Projects\2020\2001.IR20\Drawings\100%\Package B\435\435.dwg
GROUP
ARCHITECTURE
WALKER
th e
BUILDING 435
3-24-18
AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP
AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.
AutoCAD SHX Text 252-636-8992(fax)
AutoCAD SHX Text
PO BOX 541, NEW BERN, NC 28563
AutoCAD SHX Text c
AutoCAD SHX Text 252-636-8778
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN EXTERIOR WINDOW CAULK, APPROX. 672LF
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN CHALK BOARD/FIBERBOARD, APPROX. 100SF.
AutoCAD SHX Text
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN CAULK AT CHALK BOARD/FIBERBOARD, APPROX. 100SF.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN EXTERIOR WINDOW CAULK, TYPICAL AT EXTERIOR WINDOWS.
ASBESTOS IDENTIFIED IN CHALK BOARD AND CHALK BOARD CAULKING/SEALANT
SCALE
PROJECT NO
ASBESTOS LOCATION PLAN
MCB CAMP LEJEUNE
1/16"=1'-0"
CBW
20-0001
G:\Projects\2020\2001.IR20\Drawings\100%\Package B\436\436.dwg
GROUP
ARCHITECTURE
WALKER
th e
BUILDING 436
3-24-18
AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP
AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.
AutoCAD SHX Text 252-636-8992(fax)
AutoCAD SHX Text
PO BOX 541, NEW BERN, NC 28563
AutoCAD SHX Text c
AutoCAD SHX Text 252-636-8778
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN EXTERIOR DOOR CAULK, APPROX. 50LF.
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN EXTERIOR WINDOW CAULK, APPROX. 320LF.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN EXTERIOR WINDOW CAULK. TYPICAL FOR (20) WINDOWS.
ASBESTOS IDENTIFIED IN EXTERIOR DOOR CAULK. TYPICAL FOR (3) DOORS.
SCALE
PROJECT NO
ASBESTOS LOCATION PLAN
BUILDING 524
MCB CAMP LEJEUNE
1/16"=1'-0"
05-28-20
CBW
20-0001
G:\Projects\2020\2001.IR20\Drawings\100%\Package B\524\524-1.dwg
GROUP
ARCHITECTURE
WALKER
th e
N
AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP
AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.
AutoCAD SHX Text 252-636-8992(fax)
AutoCAD SHX Text
PO BOX 541, NEW BERN, NC 28563
AutoCAD SHX Text c
AutoCAD SHX Text 252-636-8778
AutoCAD SHX Text
EXTERIOR EXPANSION JOINT MATERIAL - APPROX. 180LF
AutoCAD SHX Text
EXTERIOR EXPANSION JOINT MATERIAL - APPROX. 180LF
AutoCAD SHX Text
EXTERIOR EXPANSION JOINT MATERIAL - APPROX. 180LF
AutoCAD SHX Text
EXTERIOR EXPANSION JOINT MATERIAL - APPROX. 180LF
AutoCAD SHX Text
RESIDUAL MASTIC AT WALL ABOVE FLAT ROOF - APPROX. 10LF
AutoCAD SHX Text
SEE 2017 CAMP LEJEUNE SURVEY FOR ADDITIONAL ASBESTOS CONTAINING MATERIALS
SCALE
PROJECT NO
ASBESTOS LOCATION PLAN
MCB CAMP LEJEUNE
1/16"=1'-0"
CBW
20-0001
G:\Projects\2020\2001.IR20\Drawings\100%\Package B\738\738-1.dwg
GROUP
ARCHITECTURE
WALKER
th e
BUILDING 738
3-24-18
AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP
AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.
AutoCAD SHX Text 252-636-8992(fax)
AutoCAD SHX Text
PO BOX 541, NEW BERN, NC 28563
AutoCAD SHX Text c
AutoCAD SHX Text 252-636-8778
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN TRANSITE PANEL IN 2ND FLOOR BATHROOMS, APPROX. 400SF
AutoCAD SHX Text
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN EXTERIOR WINDOW CAULK. TYPICAL FOR (20) WINDOWS.
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN TRANSITE PANELING LOCATED ON THE WALLS OF THE BATHROOM.
2ND FLOOR
SCALE
PROJECT NO
ASBESTOS LOCATION PLAN
BUILDING 762
MCB CAMP LEJEUNE
1/8"=1'-0"
5-27-20
CBW
20-0001
G:\Projects\2020\2001.IR20\Drawings\100%\Package B\762\762.dwg
GROUP
ARCHITECTURE
WALKER
th e
N
AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP
AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.
AutoCAD SHX Text 252-636-8992(fax)
AutoCAD SHX Text
PO BOX 541, NEW BERN, NC 28563
AutoCAD SHX Text c
AutoCAD SHX Text 252-636-8778
AutoCAD SHX Text
ROOF SEALANT AT BRICK CHIMNEY - APPROX. 6LF
*SEE GOV'T ASBESTOS REPORT AND PLAN FOR ADDITIONAL ASBESTOS CONTAINING MATERIAL LOCATIONS
SCALE
PROJECT NO
ASBESTOS LOCATION PLAN
MCB CAMP LEJEUNE
1/16"=1'-0"
CBW
20-0001
G:\Projects\2020\2001.IR20\Drawings\100%\Package B\1010\1010.dwg
GROUP
ARCHITECTURE
WALKER
th e
BUILDING 1010
3-24-18
AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP
AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.
AutoCAD SHX Text 252-636-8992(fax)
AutoCAD SHX Text
PO BOX 541, NEW BERN, NC 28563
AutoCAD SHX Text c
AutoCAD SHX Text 252-636-8778
AutoCAD SHX Text ASBESTOS IDENTIFIED IN EXTERIOR METAL ROOF/WALL PANEL SEALANT. TYPICAL OVER ENTIRE BUILDING.
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN EXTERIOR ROOF SEALANT, APPROX. 1250SF.
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN DARK BROWN 9X9 VCT/MASTIC, APPROX. 1000SF.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN CREAM 12X12 VCT/MASTIC, APPROX. 48SF.
AutoCAD SHX Text
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN GRAY 12X12 VCT/MASTIC, APPROX. 50SF.
AutoCAD SHX Text
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN DARK BEIGE 12X12 VCT/MASTIC, APPROX. 50SF.
AutoCAD SHX Text
AutoCAD SHX Text ASBESTOS IDENTIFIED IN DARK BROWN FLOOR TILE AND MASTIC THROUGHOUT BUILDING. IDENTIFIED BY HATCH.
ASBESTOS IDENTIFIED IN CREAM, GRAY, AND DARK BEIGE VCT AND MASTIC, 2ND LAYER OVER DARK BROWN VCT
SCALE
PROJECT NO
ASBESTOS LOCATION PLAN
BUILDING 1203
MCB CAMP LEJEUNE
1/16"=1'-0"
05-07-20
CBW
20-0001
G:\Projects\2020\2001.IR20\Drawings\100%\Package B\1203\1203.dwg
GROUP
ARCHITECTURE
WALKER
th e
N
AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP
AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.
AutoCAD SHX Text 252-636-8992(fax)
AutoCAD SHX Text
PO BOX 541, NEW BERN, NC 28563
AutoCAD SHX Text c
AutoCAD SHX Text 252-636-8778
AutoCAD SHX Text 12x12 BLACK VCT AND MASTIC - APPROX. 320SF
AutoCAD SHX Text
ASBESTOS LOCATED IN WHITE DOOR/WINDOW CAULKING. TYP.
SCALE
PROJECT NO
ASBESTOS LOCATION PLAN
BUILDING 1315
MCB CAMP LEJEUNE
1/16"=1'-0"
05-27-20
CBW
20-0001
G:\Projects\2020\2001.IR20\Drawings\100%\Package B\1315\1315-1.dwg
GROUP
ARCHITECTURE
WALKER
th e
N
AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP
AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.
AutoCAD SHX Text 252-636-8992(fax)
AutoCAD SHX Text
PO BOX 541, NEW BERN, NC 28563
AutoCAD SHX Text c
AutoCAD SHX Text 252-636-8778
AutoCAD SHX Text
INTERIOR PLASTER WALL - APPROX. 400SF
AutoCAD SHX Text
BUILT UP ROOF OVER MECHANICAL ROOM - APPROX. 192SF
AutoCAD SHX Text
ROOF DEBRIS - APPROX. 5SF
AutoCAD SHX Text
TRANSITE PANEL DEBRIS - APPROX. 5SF
SCALE
PROJECT NO
ASBESTOS LOCATION PLAN
MCB CAMP LEJEUNE
1/16"=1'-0"
CBW
20-0001
G:\Projects\2020\2001.IR20\Drawings\100%\Package B\H48\H48.dwg
GROUP
ARCHITECTURE
WALKER
th e
BUILDING H48
3-24-18
AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP
AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.
AutoCAD SHX Text 252-636-8992(fax)
AutoCAD SHX Text
PO BOX 541, NEW BERN, NC 28563
AutoCAD SHX Text c
AutoCAD SHX Text 252-636-8778
AutoCAD SHX Text ASBESTOS IDENTIFIED IN TRANSITE PANEL CEILING, APPROX. 150SF. TYPICAL THROUGHOUT BUILDING.
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN CEILING TRANSITE BOARD, APPROX. 150SF
SCALE
PROJECT NO
ASBESTOS LOCATION PLAN
MCB CAMP LEJEUNE
1/16"=1'-0"
CBW
20-0001
G:\Projects\2020\2001.IR20\Drawings\100%\Package B\PT6\PT6-1.dwg
GROUP
ARCHITECTURE
WALKER
th e
BUILDING PT6
3-24-18
AutoCAD SHX Text Copyright 2006 by THE WALKER GROUP
AutoCAD SHX Text ARCITECTURE,INC. All rights reserved.
AutoCAD SHX Text 252-636-8992(fax)
AutoCAD SHX Text
PO BOX 541, NEW BERN, NC 28563
AutoCAD SHX Text c
AutoCAD SHX Text 252-636-8778
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN TAN VCT UNDER BLACK
AutoCAD SHX Text
1ST FLOOR
AutoCAD SHX Text
2ND FLOOR
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN CLOTH EXPANSION JOINT MATERIAL AT CONC. PERIMETER.
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN CLOTH EXPANSION JOINT MATERIAL AT SQUARE FLOOR CUTOUT.
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN EXTERIOR STUCCO, TYPICAL FOR ENTIRE BUILDING.
AutoCAD SHX Text
ASBESTOS IDENTIFIED GRAY AND DARK GRAY VCT ON 1ST FLOOR.
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN TAN VCT UNDER BLACK 2ND FLOOR, APPROX. 300SF.
AutoCAD SHX Text
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN CONCRETE EXPANSION JOINT PERIMETER FLOOR, APPROX. 160LF.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text ASBESTOS IDENTIFIED IN CONCRETE EXPANSION JOINT 1ST FLOOR MIDDLE OF FLOOR, SQUARE, APPROX. 15LF.
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN EXTERIOR STUCCO, APPROX. 2,250SF.
AutoCAD SHX Text
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN 12X12 GRAY VCT/MASTIC AT 1ST FLOOR, APPROX. 200SF.
AutoCAD SHX Text
AutoCAD SHX Text
ASBESTOS IDENTIFIED IN 12X12 DARK GRAY VCT/MASTIC AT 1ST FLOOR, APPROX. 200SF.
EMSL Analytical, Inc.
706 Gralin Street Kernersville, NC 27284
Tel/Fax: (336) 992-1025 / (336) 992-4175 http://www.EMSL.com / greensborolab@emsl.com
021902963EMSL Order:
Customer ID: WALK85
Customer PO:
Project ID:
Attention: Phone:Chris Walker (252) 636-8778
Fax:The Walker Group Architecture (252) 636-8992
Received Date:PO Box 541 04/30/2019 11:30 AM
Analysis Date:New Bern, NC 28563 05/01/2019
Collected Date: 04/24/2019
Project: Bldg 3
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
021902963-0001
None DetectedCa Carbonate
Non-fibrous (Other)
5%
95%
Gray
Non-Fibrous
Homogeneous
Window Caulk
021902963-0002
None DetectedCa Carbonate
Non-fibrous (Other)
5%
95%
Gray
Non-Fibrous
Homogeneous
Window Caulk
03-Floor Tile
021902963-0003
None DetectedQuartz
Non-fibrous (Other)
25%
75%
White
Non-Fibrous
Homogeneous
Beige VCT/Mastic
03-Mastic
021902963-0003A
None DetectedNon-fibrous (Other)100%Tan
Non-Fibrous
Homogeneous
Beige VCT/Mastic
03-Leveler
021902963-0003B
None DetectedCa Carbonate
Non-fibrous (Other)
10%
90%
Cellulose<1%Tan
Non-Fibrous
Homogeneous
Beige VCT/Mastic
04-Floor Tile
021902963-0004
None DetectedQuartz
Non-fibrous (Other)
25%
75%
Gray/Beige
Non-Fibrous
Homogeneous
Beige VCT/Mastic
04-Mastic
021902963-0004A
None DetectedNon-fibrous (Other)100%Cellulose<1%Tan
Non-Fibrous
Homogeneous
Beige VCT/Mastic
04-Leveler
021902963-0004B
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
1%
10%
89%
Cellulose<1%Gray
Non-Fibrous
Homogeneous
Beige VCT/Mastic
021902963-0005
Not SubmittedRubber Base/Mastic
Sample bag empty
021902963-0006
None DetectedNon-fibrous (Other)100%Gray/Beige
Non-Fibrous
Homogeneous
Rubber Base/Mastic
Composite result
021902963-0007
None DetectedPerlite
Non-fibrous (Other)
10%
10%
Cellulose
Min. Wool
40%
40%
Tan/White
Fibrous
Homogeneous
2x2 ACT
021902963-0008
None DetectedPerlite
Non-fibrous (Other)
10%
10%
Cellulose
Min. Wool
35%
45%
Gray/White
Fibrous
Homogeneous
2x2 ACT
021902963-0009
None DetectedCa Carbonate
Non-fibrous (Other)
5%
95%
Beige
Non-Fibrous
Homogeneous
Exterior Door Caulk
021902963-0010
None DetectedCa Carbonate
Non-fibrous (Other)
10%
89%
Cellulose
Fibrous (Other)
<1%
1%
Beige
Non-Fibrous
Homogeneous
Exterior Door Caulk
021902963-0011
None DetectedCa Carbonate
Non-fibrous (Other)
5%
14%
Cellulose
Glass
80%
1%
Brown/Gray/White
Fibrous
Homogeneous
Gypsum Board/Joint
Compound
Composite result
Initial report from: 05/02/2019 08:51:49
Page 1 of 3ASB_PLM_0008_0001 - 1.78 Printed: 5/2/2019 8:51 AM
Tel/Fax: (336) 992-1025 / (336) 992-4175 http://www.EMSL.com / greensborolab@emsl.com
021902963EMSL Order:
Customer ID: WALK85
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
021902963-0012
None DetectedNon-fibrous (Other)84%Cellulose
Glass
15%
1%
Brown/Gray
Fibrous
Homogeneous
Gypsum Board/Joint
Compound
No joint compound present
021902963-0013
None DetectedNon-fibrous (Other)92%Glass8%Brown/Gray/Tan
Fibrous
Homogeneous
Asphalt Shingles/ Felt
021902963-0014
None DetectedNon-fibrous (Other)92%Glass8%Gray/Tan/Black
Fibrous
Heterogeneous
Asphalt Shingles/ Felt
021902963-0015
None DetectedNon-fibrous (Other)97%Synthetic3%Gray/Tan
Fibrous
Homogeneous
Carpet Mastic
021902963-0016
None DetectedNon-fibrous (Other)99%Cellulose
Synthetic
<1%
1%
Gray/Tan
Non-Fibrous
Homogeneous
Carpet Mastic
021902963-0017
None DetectedCa Carbonate
Non-fibrous (Other)
5%
95%
Gray
Non-Fibrous
Homogeneous
Residual Mastic at
2nd Floor Windows
021902963-0018
None DetectedCa Carbonate
Non-fibrous (Other)
5%
95%
Cellulose<1%Gray/White
Non-Fibrous
Homogeneous
Residual Mastic at
2nd Floor Windows
021902963-0019
None DetectedQuartz
Non-fibrous (Other)
30%
70%
Hair<1%Tan/Beige
Non-Fibrous
Homogeneous
Plaster Ceiling
021902963-0020
None DetectedQuartz
Non-fibrous (Other)
30%
70%
Hair<1%Tan
Non-Fibrous
Homogeneous
Plaster Ceiling
021902963-0021
None DetectedQuartz
Non-fibrous (Other)
30%
70%
Hair<1%Tan
Non-Fibrous
Homogeneous
Plaster Ceiling
021902963-0022
None DetectedQuartz
Non-fibrous (Other)
30%
70%
Hair<1%Tan/White
Non-Fibrous
Homogeneous
Plaster Ceiling
021902963-0023
None DetectedQuartz
Non-fibrous (Other)
30%
70%
Hair<1%Tan
Non-Fibrous
Homogeneous
Plaster Ceiling
021902963-0024
None DetectedQuartz
Non-fibrous (Other)
30%
70%
Hair<1%Tan
Non-Fibrous
Homogeneous
Plaster Ceiling
021902963-0025
None DetectedQuartz
Non-fibrous (Other)
30%
70%
Hair<1%Tan
Non-Fibrous
Homogeneous
Plaster Ceiling
021902963-0026
None DetectedQuartz
Non-fibrous (Other)
30%
70…