Mt Home Chapel B13 - Bid Documents_Part3.pdf
PDF 20 MB Posted
- Attached to
- Z2DZ--36C249-21-AP-3989 - Project 621-20-101 Correct FCA Deficiencies w Historical Chapel Building 13
- Solicitation number
- 36C24921B0017
About this file
This notice solicits bids for correcting deficiencies at the Historical Chapel Building 13 at the James H. Quillen VA Medical Center in Mountain Home, Tennessee. Work includes selective demolition, abatement of environmental hazards including mold and asbestos, roof and exterior wall restoration, modification of interior and exterior features, and upgrades to mechanical, electrical, plumbing and communications systems. The estimated value is between $2,000,000 to $5,000,000.
The solicitation will be issued on October 15, 2021, with bids due by November 16, 2021. This is a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses. The NAICS code is 236220 for Commercial and Institutional Building Construction. All offerors must be listed in the CVE database and have an active SAM registration. Questions must be submitted in writing to the specified contracting officer by the specified date.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FIRST FLOOR
0' - 0"
ALUMINUM HANDRAIL AT
36" A.F.F.; ANODIZED
BRONZE, TYP.
5" 4"
FULLY GROUTED
BRICK VENEER
METAL SLEEVE EMBEDDED
IN CONCRETE WALL
CONCRETE PAD
4" GRANULAR FILL
6" 3'
2" 2'
2"
4" 2"
ALUMINUM GUARDRAIL AT
42" A.F.F.; ANODIZED
BRONZE, TYP.
8" 5"
4"
1"
FIRST FLOOR
0' - 0"
CONCRETE SIDEWALK
CONCRETE LANDING
AND STEPS. REFER
TO STRUCTURAL
DRAWINGS
4" GRANULAR
FILL. REFER TO
STRUCTURAL
DRAWINGS
LIMESTONE COPING
ALUMINUM HANDRAIL AT 36"
ABOVE STAIR NOSING; ANODIZED
BRONZE, TYP.
1" TYP.
1/2" EXPANSION JOINT
MATERIAL
C
LE
A R6"
4" C
LR
G U
A R
D R
A
IL
3'
4" C
LR
1'
1/ 2"
4" CLR MAX
ALUMINUM GUARDRAIL AT 42"
ABOVE STAIR NOSING; ANODIZED
BRONZE, TYP.
1' - 0"
3/
4"
/8
3/
4"
1 3/4"
11 5/8"
1 3/4"
5/
8"
5/
8"LINE OF LIMESTONE
CAP ABOVE
ALUMINUM GUARDRAIL; ANODIZED BRONZE
ALUMINUM HANDRAIL; ANODIZED BRONZE
1' - 3"
1'
"2
AS501
BRICK
GROUTED
SOLID
#4 REBAR
10"
1'
1' - 2"
LIMESTONE CAP
AS501
ALUMINUM GUARDRAIL; ANODIZED BRONZE
ALUMINUM HANDRAIL; ANODIZED BRONZE
FIRST FLOOR
0' - 0"
BRICK VENEER
RAMP FOUNDATION WALL.
REFER TO STRUCTURAL
DRAWINGS
RAMP FOOTING. REFER TO
STRUCTURAL DRAWINGS
CONCRETE SLAB
RAILING POST SET INTO
RAMP AND FOUNDATION
WALL 1'-0" MINIMUM
AS501
C
GRANULAR
FILL
1/2" EXPANSION JOINT MATERIAL
AIR GAP
5" 4"
GRANULAR FILL
CELLULOSE WEEPS AT 24" O.C., TYP.
FLEXIBLE FLASHING AND DRIP
AT BASE
8"
1' - 1"
3/
8"
3/8"
1/4"
DRIP
EDGE
7 1/2" 7 1/2"
1/
2"
1/ 4"
3/4" CHAMFERED EDGE
DRIP EDGE
STANDARD FACE BRICK
CONCRETE
FOUNDATION
5"
METAL RAILING ENGAGED IN
CONCRETE RAMP
2" 10"
M
IN
1'
3 1/2"
RECESSED SLEEVE TO
RECEIVE RAILING POST.
1/
2"
HSS 1.66" x .125" HANDRAIL
(PROVIDE 1'-0" EXTENSIONS
TOP & BOTTOM) (STAINLESS
STEEL FINISH)
5/8" DIA. SS HANDRAIL
SUPPORT
2 1/2" DIA x 1/8" STAINLESS STEEL
PLATE C/W 2 BOLTS AND CINCH
ANCHORS PER PLATE FASTENED
TO WALL, MAX 3'-0" O.C. TYPICAL
FACE OF WALL
2 1/2"
*NOTE - PAVER PATTERN IS FOR
VISUAL REFERENCE. CONFIRM
EXISTING PATTERN BEFORE
REMOVAL AND REINSTALLATION OF
PAVERS.
BRICK PAVER REINSTALLATION
STARTING POINT
1/2" EXPANSION JOINT
WITH CONTINUOUS SEALANT
AT PERIMETER
PAVERS SHALL BE PLACE TIGHTLY
AS501
FIRST FLOOR
0' - 0"
BASEMENT
-9' - 6 11/16"
GRADE
-3' - 9"
M
IN
2'
AS501
CONCRETE FOOTING.
REFER TO STRUCTURAL
DRAWINGS
CONCRETE FOUNDATION.
REFER TO STRUCTURAL
DRAWINGS
BRICK VENEER
GUARDRAIL
GRADE
CONCRETE RAMP
FIRST FLOOR
0' - 0"
AS501
BRICK
CAST STONE
CAP
HANDRAIL
GUARDRAIL
CONCRETE
FOUNDATION
WALL
CONCRETE
PAD
4" GRANULAR
FILL
1/
4" 1'
/4
1'
1" AIR GAP
DRIP
EDGE
1' - 1"
WALL BELOWDRILLED HOLE FOR
RAILING, WHERE
APPLICABLE
6 1/2" 2" 6 1/2"
1/
2"
3/
8"
FIRST FLOOR
0' - 0"
COMPACTED SUBGRADE
4" COMPACTED
AGGREGATE SUBBASE
MIN 1" DIA.
WEEP @ 24" O.C.
EXISTING PAVERS
TIGHTLY REINSTALLED
4" CONCRETE SLAB
8" CONCRETE
TURN DOWN SLAB
1/2" EXPANSION JOINT
WITH SEALANT
SLOPE 1/8" PER FOOT
3/4" COMPACTED
BITUMINOUS SETTING BED
NEW CONCRETE RAMP
#4 CONT.
6x6-W2.9xW2.9 WWF
FIRST FLOOR
0' - 0"
BASEMENT
-9' - 6 11/16"
ANGLE CLIPS AND 3/8" HILTI
HAS THREADED ROD (OR
EQUAL) W/ 3-3/4" EMBED.
9' LADDER
LADDER SAFETY POST
SEE STRUCTURAL
DRAWINGS
METAL ACCESS GRATE
ANGLE BAND HINGE
4' - 0"
3'
ANGLE BAND HINGE
WELDED STEEL FRAME
GALVINIZED STEEL
GRATE - 1 1/4" x 3/16"
EQ EQ EQ
POSTS O.C.
5' - 0" MAX
4" CLR MAX.
4" C
LR
M
A X
4"
C
LR
M A
X
3'
T Y
P
IC
A L
3'
/8
4"
11 5/8"
LIMESTONE CAP
BRICK POST
ALUMINUM HANDRAIL
ALUMINUM GUARDRAIL
3'
2" 2"
2"
CONCRETE
PLATFORM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EXP. 12/31/2021C
U s e rs
\d u n n t\ D o c u m e n ts \F
F E
M t H o m e
C h a p e l_
B tj .d u n n
.r v t
/3
/2
:0
:4
P
M
AS501
EXTERIOR DETAILS
Owner
07/30/2021 GA TD
CORRECT FCA DEFICIENCIES
HISTORICAL CHAPEL BLDG. 13
621-20-101
MT HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER
1 1/2" = 1'-0"
TYP. HANDRAIL AT EXT. STAIR
1" = 1'-0"
SECTION AT SOUTH TRANSEPT STAIRS
1 1/2" = 1'-0" E
PLAN DETAIL - BRICK POST
1 1/2" = 1'-0" D
PLAN DETAIL - LIMESTONE POST CAP
1" = 1'-0"
RAMP SECTION AT FOUNDATION
3" = 1'-0"
TYP. CAST STONE CAP
1 1/2" = 1'-0" C
CONCRETE RAMP / PAD - EDGE DETAIL
3" = 1'-0" B
SECTION AT WALL MOUNTED HANDRAIL
1/2" = 1'-0" A
EXTERIOR BRICK PAVER PATTERN
1/2" = 1'-0"
EAST TRANSEPT - TRANS. SECTION
1" = 1'-0"
SOUTH TRANSEPT STAIRS - TRANS. SECTIOn
3" = 1'-0"
TYP. CAST STONE CAP AT STAIRS
1/2" = 1'-0"
EXTERIOR PAVER SECTION
1/2" = 1'-0"
AREAWAY LADDER - SECTION
1/2" = 1'-0"
AREAWAY ACCESS GRATE
1" = 1'-0"
TYP. EXTERIOR RAILING ELEVATION
No. Revisions: Date:
/8
/8
/8
/4
/4
/4
/4
1 3/8" 3/4"
3/4" 1 5/8"
1/2"
1 3/8"
*NOTE: VERIFY DIMENSIONS, PROFILE, AND
CONSTRUCTION TO MATCH EXISTING WALL BASE.
1"
7/8"
/8
7/8" 3/4"
/4
*NOTE: VERIFY DIMENSIONS, PROFILE, AND
CONSTRUCTION TO MATCH EXISTING WALL BASE.
EXISTING WOOD TRUSS
EXISTING WOOD PIN
GLUE LAMINATED WOOD
/8
/4
/4
/8
/2
/4
1' - 0 1/2" 9 5/8" 3 7/8" 1 1/4"1 1/4"
/2
3/4"
4"
2' - 4 1/2"
1" 10" 1"
3/4" 1"
*NOTE: VERIFY DIMENSIONS, PROFILE, AND CONSTRUCTION TO MATCH EXISTING WOOD BRACKET.
EXISTING WOOD TRUSS
EXISTING WOOD PIN
GLUE LAMINATED WOOD
1" 3/4"
EXISTING WOOD PULPIT TO BE
SALVAGED, SANDED, AND
RE-STAINED FOR
REINSTALLATION IN NEW
WORK.
NEW INTERIOR GYPSUM
FURRING. SEE FLOOR PLAN
FOR MAKE-UP OF NEW
CONSTRUCTION.
EXISTING MASONRY CONSTRUCTION.
VERIFY LOCATION IN FIELD.
NEW INTERIOR GYPSUM
FURRING. SEE FLOOR PLAN
FOR MAKE-UP OF NEW
CONSTRUCTION.
REFER TO AE601 FOR
OPENING JAMB DETAILS.
NEW INTERIOR GYPSUM
FURRING. SEE FLOOR PLAN
FOR MAKE-UP OF NEW
CONSTRUCTION.
NEW INTERIOR GYPSUM
FURRING. SEE FLOOR PLAN
FOR MAKE-UP OF NEW
CONSTRUCTION.
NEW INTERIOR GYPSUM
FURRING. SEE FLOOR PLAN
FOR MAKE-UP OF NEW
CONSTRUCTION.
VIF
1' - 4" +/-
1/4" TYP.
EXISTING WOOD JOIST
TERRAZZO TILE
MORTAR BED. ADJUST TO BRING
FINISHED FLOOR LEVEL WITH
ADJACENT EXISTING FLOOR FINISHES
1/2" PLYWOOD SUBFLOOR
1/2" CEMENT BOARD SUBFLOOR
1' - 4" VIF
EXISTING WOOD JOIST
TERRAZZO TILE
MORTAR BED. ADJUST TO BRING
FINISHED FLOOR LEVEL WITH
ADJACENT EXISTING FLOOR FINISHES
1/2" PLYWOOD SUBFLOOR
1/2" CEMENT BOARD SUBFLOOR
TILE EDGE PIECE
VIF
1' - 4" +/-
VIF
1' - 4" +/-
EXISTING WOOD JOIST
1/2" PLYWOOD SUBFLOOR
FINISH FLOOR VARIES
R-21 BATT INSULATION
SUBFLOOR INSULATION NETTING
OR SIMILAR SUPPORT
BALCONY
10' - 1 5/8"
COORDINATE BALCONY TRIM WOOD WORK
WITH DEMOLITION SCOPE. WOOD SHALL BE
REFINISHED AND STAINED TO MATCH
ADJACENT TRIM.
6" X 8" WOOD BEAM
1/4" X 3-1/2" STAINLESS
STEEL WOOD SCREW
ORNAMENTAL JOIST
HANGER
5 1/2"
/2 "7
2 1/2"
EXISTING WOOD TRUSS
E Q
E Q
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EXP. 12/31/2021C
U s e rs
\d u n n t\ D o c u m e n ts \F
F E
M t H o m e
C h a p e l_
B tj .d u n n
.r v t
/3
/2
:0
:1
P
M
AE502
INTERIOR DETAILS
Owner
07/30/2021 GL TD
CORRECT FCA DEFICIENCIES
HISTORICAL CHAPEL BLDG. 13
621-20-101
MT HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER
3" = 1'-0"
EXISTING BASE TRIM - LARGE
3" = 1'-0"
EXISTING BASE TRIM - SMALL
1 1/2" = 1'-0"
TRUSS BRACKET DETAIL
3/4" = 1'-0"
PLAN DETAIL
3/4" = 1'-0"
PLAN DETAIL
1 1/2" = 1'-0"
TERRAZZO FLOOR SYSTEM
1 1/2" = 1'-0"
TERRAZZO FLOOR TO WOOD FLOOR
1 1/2" = 1'-0"
SUBFLOOR INSULATION AT TRANSEPTS
1/2" = 1'-0"
BALCONY RAILING DETAIL
3" = 1'-0"
JOIST HANGER AT TRUSS
3 1/4"1/2" SEE PLANSEE PLAN
RE-INSTALL VARNISHED WOOD
VARNISHED WOOD STOP
RE-INSTALL EXISTING WOOD TRIM
NEW 5/8" GYPSUM WALLBOARD
ON 2 1/2" METAL STUD
EXISTING PLASTER TO BE REMOVED
EXISTING WOOD TRIM. REMOVE,
CLEAN, AND VARNISH BEFORE
REINSTALLATION IN COORDINATION
WITH NEW WORK.
EXISTING WOOD STOP
DEMOLISHED NEW CONSTRUCTION
3 1/4" 1/2" SEE PLAN 2 3/4"SEE PLAN
1/2" VARNISHED WOOD
VARNISH WOOD STOP
REPLACE EXISTING
WOOD TRIM
NEW 5/8" GYPSUM WALLBOARD
ON 2 1/2" METAL STUD
EXISTING PLASTER TO BE REMOVED
EXISTING WOOD TRIM. REMOVE,
CLEAN, AND VARNISH BEFORE
REINSTALLATION IN COORDINATION
WITH NEW WORK.
EXISTING WOOD ACCENT PANEL
EXISTING TRIM TO REMAIN.
STRIP PAINT AND VARNISH
IN COORDINATION WITH
NEW WORK.
DEMOLISHED NEW CONSTRUCTION
3 1/4" 1/2" SEE PLAN 1/2" 3 1/4"SEE PLAN
1/2" VARNISHED WOOD
VARNISHED WOOD STOP
RE-INSTALL EXISTING WOOD TRIM
NEW 5/8" GYPSUM WALLBOARD
ON 2 1/2" METAL STUD
EXISTING PLASTER AND
LATHE TO BE REMOVED
EXISTING WOOD TRIM. REMOVE,
CLEAN, AND VARNISH BEFORE
REINSTALLATION IN COORDINATION
WITH NEW WORK.
EXISTING WOOD PANEL
EXISTING WOOD ACCENT PANEL
DEMOLISHED NEW CONSTRUCTION
3 1/4" 1/2" SEE PLAN 1/2" 3 1/4"SEE PLAN
1/2" VARNISHED WOOD
VARNISHED WOOD STOP
RE-INSTALL EXISTING
WOOD TRIM
NEW 5/8" GYPSUM
WALLBOARD ON 2 1/2"
METAL STUD
EXISTING PLASTER AND
LATHE TO BE REMOVED
EXISTING WOOD TRIM. REMOVE,
CLEAN, AND VARNISH BEFORE
REINSTALLATION IN COORDINATION
WITH NEW WORK.
EXISTING WOOD PANEL
EXISTING WOOD ACCENT PANEL
DEMOLISHED NEW CONSTRUCTION
1 15/16" VARIES VARIES
5/8" GYPSUM BOARD
DOUBLE STUDS
BACK TO BACK
CAULK ALL AROUND
BOTH SIDES
STANDARD FRAME FOR
GYPSUM BOARD
JAMB ANCHORS
/4
4 7/8"
FIRST FLOOR
0' - 0"
GRIND CONCRETE SILL BETWEEN
WOOD TRIM OPENING TO BE FLUSH
WITH ADJACENT FLOOR.
GRIND CONCRETE SILL BETWEEN
BRICK OPENING TO BE FLUSH WITH
ADJACENT FLOOR.
EXISTING BRICK
WALL BEYOND
EXISTING BRICK TRANSOM
TO BE SALVAGED AND
PALLETIZED FOR RE-USE.
WOOD DOOR FRAME TO BE REMOVED
EXISTING STEEL LINTEL TO BE
CUT AT BRICK JAMB EXTENT
EXISTING HINGE TO BE SALVAGED AND
RE-INSTALLED IN NEW WORK SCOPE.
EXTERIOR
DEMOLISHED
EXISTING BRICK
WALL BEYOND
GLAZING AS SCHEDULED
EXISTING HINGE TO BE
RE-INSTALLED.
NEW DOOR FRAME INSET
INTO WOOD GLAZING SYSTEM
WOOD FRAMING ASSOCIATED
WITH WOOD GLAZING SYSTEM
EXTERIOR
NEW 3/8" STEEL LINTEL EMBEDDED
6" IN JAMB MASONRY
A B C
E - EXTERIOR E - INTERIOR F G
SEE PLAN
CMU BLOCK WALL
STANDARD HOLLOW METAL FRAME
FOR CMU GROUTED SOLID
CAULK AROUND FRAME
ON ALL SIDES
REMOVE BASE
AND RETURN FOR
RE-INSTALLATION
IN NEW WORK
REMOVE BASE
AND RETURN FOR
RE-INSTALLATION
IN NEW WORK
REMOVE BASE
AND RETURN FOR
RE-INSTALLATION
IN NEW WORK
OPENING HEAD TRIM
AND FACING SHALL
BE EXTENDED AS
NECESSARY FOR
CONTINUOUS
PROFILE.
OPENING HEAD TRIM
AND FACING SHALL
BE EXTENDED AS
NECESSARY FOR
CONTINUOUS
PROFILE.
OPENING HEAD TRIM
AND FACING SHALL
BE EXTENDED AS
NECESSARY FOR
CONTINUOUS
PROFILE.
OPENING HEAD TRIM
AND FACING SHALL
BE EXTENDED AS
NECESSARY FOR
CONTINUOUS
PROFILE.
SEE PLAN
EXISTING PLASTER AND LATHE TO BE
REPLACED WITH GYPSUM BOARD. SEE
PLAN FOR EXTENT OF PLASTER REMOVAL.
WOOD TRIM. REMOVE, CLEAN, AND
VARNISH BEFORE REINSTALLATION
IN COORDINATION WITH NEW WORK.
WHERE NEW OPENING WIDTH VARIES
FROM EXISTING CONDITION, NEW
TRIM SHALL BE FABRICATED TO
MATCH EXISTING PROFILES.
EXISTING WOOD STOP
SEE PLAN
EXISTING PLASTER AND LATHE TO BE
REPLACED WITH GYPSUM BOARD. SEE
PLAN FOR EXTENT OF PLASTER REMOVAL.
WOOD TRIM. REMOVE, CLEAN, AND VARNISH
BEFORE REINSTALLATION IN COORDINATION
WITH NEW WORK. WHERE NEW OPENING
WIDTH VARIES FROM EXISTING CONDITION,
NEW TRIM SHALL BE FABRICATED TO MATCH
EXISTING PROFILES.
WOOD PANEL STAINED TO
MATCH ADJACENT TRIM
WOOD ACCENT PANEL STAINED
TO MATCH ADJACENT TRIM
TYPICAL EXTERIOR CONDITION
TYPICAL INTERIOR CONDITION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EXP. 12/31/2021C
U s e rs
\d u n n t\ D o c u m e n ts \F
F E
M t H o m e
C h a p e l_
B tj .d u n n
.r v t
/3
/2
:0
:2
P
M
AE601
DOOR SCHEDULE AND DETAILS
Owner
07/30/2021 GL TD
CORRECT FCA DEFICIENCIES
HISTORICAL CHAPEL BLDG. 13
621-20-101
MT HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER
DOOR SCHEDULE
MARK
DOOR PANEL DOOR FRAME
Hardware Set
SCHEDULE
NOTESPANEL TYPE HEIGHT* WIDTH* FRAME TYPE
FRAME
MATERIAL JAMB
003A -- 7' - 5" 2' - 8" ETR ETR -- 6.0 2
007A D 6' - 2" 3' - 0" 1 HM 4.0
010A G 6' - 8" 3' - 0" 1 HM 4.0
101A E 7' - 8" 5' - 10" * WD 1.0 1
102A B 7' - 5" 4' - 10" * WD 14/AE601 6.0 1
104A A 7' - 5" 2' - 8" * WD 13/AE601 7.0 1
104B A 7' - 5" 2' - 8" * WD 12/AE601 8.0 1
104C A* 7' - 5" 2' - 8" * WD 12/AE601 6.0 1
106A -- 7' - 11 1/2" 2' - 8" * WD 3/AE601 5.0 3
106B A* 7' - 5" 2' - 8" * WD 12/AE601 6.0 1
107 F 7' - 0" 3' - 0" 2 WD 2.0
108 F 7' - 0" 2' - 8" 2 WD 2.0
109A A 7' - 5" 2' - 8" ETR ETR* -- 6.0 2
109B A 7' - 5" 2' - 8" ETR ETR* -- 6.0 2
110A E 7' - 8" 5' - 10" ETR ETR* -- 6.0 2
111A B 7' - 5" 4' - 10" * WD 14/AE601 6.0 1
112A -- 7' - 11 1/2" 2' - 8" * WD 12/AE601 5.0 3
112B A* 7' - 5" 2' - 8" * WD 12/AE601 6.0 1
113 F 7' - 0" 2' - 8" 2 WD 2.0
114 F 7' - 0" 3' - 0" 2 WD 2.0
116A A 7' - 5" 2' - 8" * WD 13/AE601 7.0 2
116B A 7' - 11 1/2" 2' - 8" * WD 12/AE601 8.0
116C A* 7' - 5" 2' - 8" * WD 12/AE601 6.0 1
116D F 7' - 0" 2' - 0" WD 3.0
201 C 7' - 5" 2' - 8" ETR ETR -- 6.0 1
203 C 7' - 5" 2' - 8" ETR ETR -- 6.0 1
DOOR SCHEDULE NOTES:
1. REMOVE, CLEAN, STAIN, AND VARNISH EXISTING DOOR PANEL. HINGES SHALL BE SALVAGED AND CLEANED. ADJUST JAMB AND
RE-INSTALL DOOR ACCORDING TO SCHEDULED DETAIL.
2. REMOVE, CLEAN, STAIN, AND VARNISH EXISTING DOOR PANEL FOR INSTALLATION IN NEW WORK PLANS.
3. REMOVE AND RESTORE DOOR AND EXISTING HARDWARE AND STORE IN COORDINATION WITH C.O.R. ADJUST JAMB ACCORDING
TO SCHEDULED DETAIL.
*PANEL TYPE - SEAL DOOR SHUT AFTER INSTALLATION OF NEW FURRING AND RE-INSTALLATION OF DOOR.
1 1/2" = 1'-0"
EXTERIOR JAMB REBUILD
1 1/2" = 1'-0"
INTERIOR JAMB - FURRING ONE SIDE
1 1/2" = 1'-0"
INTERIOR JAMB - ONE PANEL
1 1/2" = 1'-0"
INTERIOR JAMB - TWO PANEL
3" = 1'-0"
TYP. HOLLOW METAL HEAD DETAIL
1 1/2" = 1'-0"
SILL REPAIR AT TOWER ENTRY
1 1/2" = 1'-0"
ENTRY DOOR HEAD DETAIL
3" = 1'-0"
TYP HOLLOW METAL HEAD DETAIL IN CMU WALL
1 1/2" = 1'-0"
TYPICAL HEAD DETAIL
CA D E
H
B
GF I
W I N D O W T Y P E S
1/ 4"
4' - 0" 7' - 0"
8'
/4
6'
/8
2' - 4" 1' - 8"
6'
/8
5'
/8
1' - 3 3/4"
4'
/8
1' - 10" 1' - 10"
3'
/8
6' - 0" 2' - 0"
1'
/8
3'
1'
1"
8'
/8
2'
/2
2'
/4
/2 " 6
1/ 2"
2'
/4
2'
/2
NEW ALUMINUM WINDOW.
REFER TO SCHEDULE FOR
SIZE AND GLAZING TYPE.
EXISTING
MASONRY
WALL
5/8" TYPE "X"
GYPSUM BOARD
2 1/2" COLD FORMED
METAL FRAMING
GC TO VERIFY
EXISTING WINDOW
DEPTH IN MASONRY
OPENING
SELF-ADHERING
RUBBERIZED
FLASHING TO
WRAP JAMB, HEAD,
AND SILL
2" 2"
4 5/8"
1 5/8" 3"
4" 3"
2 5/8" 1 5/8"
FRT WOOD SHIM
EASED EDGE
SEALANT AND
BACKER ROD
SEALANT AND
BACKER ROD
EXISTING WOOD
TRIM SHALL BE
REINSTALLED AT
NEW WINDOW
EXISTING
MASONRY WALL
2" 2"
4 5/8" 1 5/8" NEW ALUMINUM WINDOW.
REFER TO SCHEDULE FOR
SIZE AND GLAZING TYPE.
GC TO VERIFY
EXISTING WINDOW
DEPTH IN MASONRY
OPENING
SEALANT AND
BACKER ROD
SEALANT AND
BACKER ROD
SELF-ADHERING
RUBBERIZED FLASHING
TO WRAP JAMB, HEAD,
AND SILL
FRT WOOD SHIM
EXISTING WOOD TRIM SHALL
BE REINSTALLED AT NEW
WINDOW. PREPARE WOOD
TRIM FOR NEW FINISHES
EXISTING
STONE SILL
TO REMAIN
NEW ALUMINUM WINDOW.
REFER TO SCHEDULE FOR
SIZE AND GLAZING TYPE.
5/8" TYPE "X"
GYPSUM BOARD
2 1/2" COLD FORMED
METAL FRAMING
PRE-FINISHED ALUMINUM
FLASHING OVER SLOPED FRT
SILL
SLOPED TREATED
WOOD BLOCKING
NOTE: CONTRACTOR TO VERIFY
EXISTING FLASHING.
CONDITIONS. COORDINATE
WITH COR.
EXISTING INTERIOR
WOOD SILL TO BE
REINSTALLED AT NEW
WINDOW.
4" 2"
ALUMINUM SILL TO HAVE
INTEGRAL RAINSCREEN
DRAINAGE
SEALANT AND
BACKER ROD
SEALANT AND BACKER ROD
INTEGRAL ALUMINUM SILL
FLASHING PAN
2 5/8" 1 5/8"
SEALANT AND BACKER ROD
SELF-ADHERING
RUBBERIZED FLASHING TO
WRAP JAMB, HEAD, AND SILL
FRT WOOD SHIM
EXISTING
STONE SILL
TO REMAIN
NEW ALUMINUM WINDOW.
REFER TO SCHEDULE FOR
SIZE AND GLAZING TYPE.
GC TO VERIFY EXISTING
WINDOW DEPTH IN MASONRY
OPENING
5/8" TYPE "X"
GYPSUM BOARD
2 1/2" COLD FORMED
METAL FRAMING
2" 2"
WOOD BLOCKING
AT BUILT UP SILL
BRAKE METAL
SILL
2 5/8" 1 5/8"
FRT BLOCKING AT SILL
NOTE: CONTRACTOR TO VERIFY
EXISTING FLASHING.
CONDITIONS. COORDINATE
WITH COR.
INTEGRAL ALUMINUM SILL
FLASHING PAN
EXISTING WOOD TRIM SHALL
BE REINSTALLED AT NEW
WINDOW. PREPARE WOOD
TRIM FOR NEW FINISHES
SEALANT AND BACKER ROD
SELF-ADHERING
RUBBERIZED FLASHING TO
WRAP JAMB, HEAD, AND SILL
ALUMINUM SILL TO HAVE
INTEGRAL RAINSCREEN
DRAINAGE
EXISTING
MASONRY
WALL
FRT WOOD SHIM
EXISTING WOOD TRIM SHALL
BE REINSTALLED AT NEW
WINDOW. PREPARE WOOD
TRIM FOR NEW FINISHES
NEW ALUMINUM WINDOW.
REFER TO SCHEDULE FOR
SIZE AND GLAZING TYPE.
EXISTING
STONE SILL
TO REMAIN
WOOD BLOCKING
AT BUILT UP SILL
BRAKE METAL
SILL
EXISTING MASONRY
WALL
EXISTING INTERIOR BRICK
SILL TO REMAIN
2" 2"
2 5/8" 1 5/8"
NOTE: CONTRACTOR TO VERIFY
EXISTING FLASHING.
CONDITIONS. COORDINATE
WITH COR.
SEALANT AND
BACKER ROD
SELF-ADHERING
RUBBERIZED FLASHING TO
WRAP JAMB, HEAD, AND SILL
INTEGRAL ALUMINUM SILL
FLASHING PAN
ALUMINUM SILL TO HAVE
INTEGRAL RAINSCREEN
DRAINAGE
FRT WOOD SHIM
SEALANT AND
BACKER ROD
EXISTING WOOD TRIM
SHALL BE REINSTALLED AT
NEW WINDOW. PREPARE
WOOD TRIM FOR NEW
FINISHES
EXISTING
MASONRY
WALL
NEW ALUMINUM WINDOW.
REFER TO SCHEDULE
FOR SIZE AND GLAZING
TYPE.
5/8" TYPE "X"
GYPSUM BOARD
2 1/2" COLD FORMED
STEEL FRAMING
EXISTING
STONE SILL
GC TO VERIFY
EXISTING WINDOW
DEPTH IN MASONRY
OPENING
2" 2"
4 5/8" 1 5/8"
SELF-ADHERING
RUBBERIZED
FLASHING TO WRAP
JAMB, HEAD, AND SILL
EASED EDGE
SEALANT AND
BACKER ROD
SEALANT AND
BACKER ROD
NEW ALUMINUM WINDOW.
REFER TO SCHEDULE FOR
SIZE AND GLAZING TYPE.
EXISTING
MASONRY
WALL
NEW ALUMINUM WINDOW.
REFER TO SCHEDULE FOR
SIZE AND GLAZING TYPE.
2" 2"
3" 4"
3"
2 5/8" 1 5/8"
4 5/8"
1 5/8"
5/8" TYPE "X"
GYPSUM BOARD
2 1/2" COLD FORMED
METAL FRAMING
EASED EDGE
SEALANT AND
BACKER ROD
SELF-ADHERING
RUBBERIZED FLASHING
TO WRAP JAMB, HEAD,
AND SILL
SEALANT AND
BACKER ROD
NEW ALUMINUM WINDOW.
REFER TO SCHEDULE FOR
SIZE AND GLAZING TYPE.
EXISTING STONE
SILL TO REMAIN
2" 2"
4 5/8" 1 5/8"
5/8" TYPE "X"
GYPSUM BOARD
2 1/2" COLD FORMED
METAL FRAMING
FRT BLOCKING AT SILL
1/2"
GC TO VERIFY
EXISTING WINDOW
DEPTH IN MASONRY
OPENING
SEALANT AND
BACKER ROD
SEALANT AND
BACKER ROD
FRT WOOD SHIM
SELF-ADHERING
RUBBERIZED
FLASHING TO
WRAP JAMB,
HEAD, AND SILL
EXISTING MASONRY
WALL
EXISTING WOOD TRIM SHALL BE
REINSTALLED AT NEW WINDOW.
PREPARE WOOD TRIM FOR NEW
FINISHES
NEW ALUMINUM WINDOW.
REFER TO SCHEDULE
FOR SIZE AND GLAZING
TYPE.
EXISTING STONE SILL
TO REMAIN
EXISTING
MASONRY
WALL
2" 2"
4 5/8" 1 5/8"
GC TO VERIFY
EXISTING WINDOW
DEPTH IN MASONRY
OPENING
SEALANT AND BACKER
ROD
SEALANT AND BACKER ROD
SELF-ADHERING
RUBBERIZED FLASHING
TO WRAP JAMB, HEAD,
AND SILL
FRT WOOD SHIM
REPAIR DAMAGED LEADING AND REPLACE BROKEN GLASS TO MATCH COLOR AS INDICATED.
COLOR SHALL MATCH EXISTING STAINED GLASS. REUSE EXISTING STAINED GLASS WHERE
POSSIBLE. CONTRACTOR SHALL PRESERVE THE HISTORICAL ACCURACY OF THE WINDOW.
*DRAWING IS REPRESENTATION OF EXISTING WINDOW AND MAY HAVE INACCURACIES.
NORTH WINDOW:
APPROXIMATELY 90% OF THE GLASS IS INTACT. GLASS AND LEADING LOOKS TO HAVE BEEN
REPAIRED OR REPLACED IN THE PAST. USE THIS WINDOW AS A REFERENCE FOR THE WEST
WINDOW.
WEST WINDOW:
APPROXIMATELY 80% OF THE WINDOW IS COVERED AND THE CONDITION IS UNKNOWN.
REPLICATE WINDOW PATTERN TO MATCH THE NORTH WINDOW.
COLOR LEGEND:
P = PURPLE STAINED GLASS
Y = YELLOW STAINED GLASS
G = GREEN STAINED GLASS
P
P
P
P
P
P
P
P P
P
P
P
P
P
P
P
Y
Y
Y
Y
P
P
P
P
P
P
P
PP
P
P
P
P
P
P
P
Y
Y
Y
Y
P
P PP
P
P
P
P
P P
P
P P
P
P
P
P
P
PP P
P
P
P
P
P P
P
P P
P
P
P
P
P Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y Y
Y
Y
Y
Y
Y
Y
Y
Y
YYYYYY
Y
G G
G
G G
Y Y
Y YY Y
G G
P P
P
P
P P P P
P
PPP
P P
P P P P P P P P
P P P P
P P
PP
P P
P P P P
P P
P
PP
PPP
G G G GG
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G G
Y Y
P P
Y Y
G
G
G
G G
G
G
G
G
G G
G G
G
G
G
G
G G
G
GG
G
G G
G
G G
G
G G
GGG
G G G
G
G
G G
G
G
G
GG
G
G G
S T A I N E D G L A S S W I N D O W S
SCALE: 1" = 1' - 0"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EXP. 12/31/2021C
U s e rs
\d u n n t\ D o c u m e n ts \F
F E
M t H o m e
C h a p e l_
B tj .d u n n
.r v t
/3
/2
:0
:3
P
M
AE602
WINDOW SCHEDULE AND DETAILS
Owner
07/30/2021 GL TD
CORRECT FCA DEFICIENCIES
HISTORICAL CHAPEL BLDG. 13
621-20-101
MT HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER
Window Schedule
TYPE MARK DESCRIPTION HEIGHT* WIDTH*
HEAD
DETAIL SILL DETAIL
JAMB
DETAIL
GLAZING
TYPE
SCHEDULE
NOTES
A ARCHED - FIXED 10' - 10" 4' - 0" 7/AE601 8/AE601 9/AE601 G1
B ARCHED - STAINED GLASS 8' - 0" 7' - 0" ETR ETR ETR G2 1
C ARCHED - FIXED 6' - 6" 2' - 4" 10/AE601 11/AE601 12/AE601 G1
D ARCHED - FIXED 6' - 1" 1' - 8" 13/AE601 14/AE601 15/AE601 G1
E ARCHED - FIXED 5' - 7" 1' -4" 13/AE601 14/AE601 15/AE601 G1
F ARCHED - HUNG 4' - 3" 1' - 10" 13/AE601 14/AE601 15/AE601 G1
G HUNG 3' - 8" 1' - 10" 13/AE601 14/AE601 15/AE601 G1
H ARCHED - FIXED 3' - 8" 6' - 0" 7/AE601 8/AE601 --- G1
I BASEMENT 1' - 8" 2' - 0" 13/AE601 14/AE601 15/AE601 G1
L
* CONTRACTOR TO VERIFY EXISTING WINDOW SIZES
WINDOW SCHEDULE NOTES:
1. REMOVE EXISTING BRICK INFILL AND CLEAN EXISTING JAMB, SILL, AND HEAD FOR NEW STAINED GLASS INSTALLATION. SEE STAINED
GLASS DETAIL ON SHEET AE602.
GLAZING TYPES:
G-1 EAST- AND WEST-FACING EXTERIOR WINDOWS: 1" INSULATED LOW-E LAMINATED ULTRA-CLEAR GLAZING.
G-2 NORTH- AND SOUTH-FACING EXTERIOR WINDOWS: 1" INSULATED LAMINATED ULTRA-CLEAR GLAZING.
G-3 ALTERNATE #2 (IN LIEU OF G-1) - EAST- AND WEST-FACING EXTERIOR WINDOWS - 1" INSULATED LOW-E STANDARD ULTRA-CLEAR
GLAZING.
G-4 ALTERNATE #2 (IN LIEU OF G-2) - NORTH- AND SOUTH-FACING EXTERIOR WINDOWS - 1" INSULATED STANDARD ULTRA-CLEAR GLAZING.
G-5 STAINED GLASS - CONTRACTOR SHALL RESTORE NEW AND MISSING PIECES TO LIKE NEW CONDITION. BASIS OF DESIGN: EXISTING
GLAZING.
1 1/2" = 1'-0"
WINDOW DETAIL - HEAD A
1 1/2" = 1'-0"
WINDOW DETAIL - HEAD E
1 1/2" = 1'-0"
WINDOW DETAIL - SILL A
1 1/2" = 1'-0"
WINDOW DETAIL - SILL C
1 1/2" = 1'-0"
WINDOW DETAIL - SILL E
1 1/2" = 1'-0"
WINDOW DETAIL - JAMB A
1 1/2" = 1'-0"
WINDOW DETAIL - HEAD C
1 1/2" = 1'-0"
WINDOW DETAIL - JAMB C
1 1/2" = 1'-0"
WINDOW DETAIL - JAMB E
RESTROOM
9"
9"
RESTROOM
10##
4 1/2"
/2
EMERGENCY EVACUATION
14"
ROOM NAME
9"
AUTHORIZED
PERSONNEL ONLY
1' - 2"
E Q
E Q
ROOM NUMBER
2"
SIGN
FRAME
GENERAL NOTE: EXISTING ROOM NUMBER SIGNS SHALL BE
REUSED AND MOUNTED AT THE TOP CENTER OF THE FRAME.
WEST CHAPEL
TOWER STAIR
ENTRANCE
ACCESSIBLE RESTROOM
STAGE
SOUTH TRANSEPT
STAIR
ENTRANCE
NORTH CHAPEL
RESTROOM
VESTIBULE
ACCESSIBLE RESTROOM
VESTIBULE
EAST TRANSEPT
HAC
116A
STAGE
116D
7 21
RESTROOM
9"
FIRE EXTINGUISHER
9"
MAXIMUM OCCUPANCY
14"
ABLE-BODIED
ONLY ACCESS
9"
IT
EAST TRANSEPT - C.S.
WEST TRANSEPT - C.S.
NORTH CRAWL SPACE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EXP. 12/31/2021C
U s e rs
\d u n n t\ D o c u m e n ts \F
F E
M t H o m e
C h a p e l_
B tj .d u n n
.r v t
/3
/2
:0
:4
P
M
AE611
SIGNAGE PLAN AND SCHEDULE
Owner
07/30/2021 GL TD
CORRECT FCA DEFICIENCIES
HISTORICAL CHAPEL BLDG. 13
621-20-101
MT HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER
S I G N A G E S C H E D U L E
MARK SIGN TYPE MESSAGE
1 EVACUATION ROUTE "EMERGENCY EVACUATION"
2 EVACUATION ROUTE "EMERGENCY EVACUATION"
3 ROOM NUMBER SIGN "107"
4 ROOM NUMBER SIGN "106"
5 ROOM NUMBER SIGN "107B"
6 ROOM NUMBER SIGN "107A"
7 ROOM NUMBER SIGN "103"
8 ROOM NUMBER SIGN "105"
9 ROOM NUMBER SIGN "105A"
10 ROOM NUMBER SIGN "104"
11 ROOM NUMBER SIGN "110"
12 ROOM NUMBER SIGN "111"
13 ROOM NUMBER SIGN "111A"
14 ROOM NUMBER SIGN "110A"
15 ROOM NUMBER SIGN "110B"
RESTROOM
IDENTIFCATION SIGN -
ACCESSIBLE
"RESTROOM"
RESTROOM
IDENTIFCATION SIGN
"RESTROOM"
RESTROOM
IDENTIFCATION SIGN
"RESTROOM"
RESTROOM
IDENTIFCATION SIGN
"RESTROOM"
AUTHORIZED
PERSONNEL SIGN
"AUTHORIZED PERSONNEL ONLY"
21 OCCUPANT LOAD "MAXIMUM OCCUPANCY 130"
22 OCCUPANT LOAD "MAXIMUM OCCUPANCY 130"
23 ROOM NAME SIGN "IT ROOM"
24 ABLE-BODIED ONLY "ABLE-BODIED ONLY"
25 FIRE EXTINGUISHER "FIRE EXTINGUISHER"
26 FIRE EXTINGUISHER "FIRE EXTINGUISHER"
1 1/2" = 1'-0"
RESTROOM SIGN
1 1/2" = 1'-0"
RESTROOM SIGN - ACCESSIBLE
1 1/2" = 1'-0"
EXISTING ROOM NUMBER SIGN
1 1/2" = 1'-0"
EVACUATION ROUTE SIGN
1 1/2" = 1'-0"
TYP. ROOM NAME SIGN
1 1/2" = 1'-0"
AUTHORIZED PERSONNEL ONLY SIGN
1/2" = 1'-0"
TYP. SIGNAGE ELEVATIONS
1. ALL FINAL NAMES AND NUMBERS TO BE CHOSEN BY THE VA DURING CONSTRUCTION
S I G N A G E N O T E S
1/8" = 1'-0"
SIGNAGE PLAN - FIRST FLOOR
1 1/2" = 1'-0"
RESTROOM SIGN - RIGHT ANGLE
1 1/2" = 1'-0"
FIRE EXTINGUISHER - RIGHT ANGLE
1 1/2" = 1'-0"
OCCUPANT LOAD SIGN
1 1/2" = 1'-0"
ABLE-BODIED ONLY ACCESS
1/8" = 1'-0"
SIGNAGE PLAN - BASEMENT
4'
3" 3'
3"
4"
CTW-2
CTB-1
CTW-3
CTW-3
CTW-1
BULLNOSE
P-2
64 SF
STAIR
ST-2
P-2
ST-1
P-3
P-3
P-3
P-3
P-3
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EXP. 12/31/2021C
U s e rs
\d u n n t\ D o c u m e n ts \F
F E
M t H o m e
C h a p e l_
B tj .d u n n
.r v t
/3
/2
:0
:5
P
M
AF801
FINISH SCHEDULE, LEGEND, AND
GENERAL DETAILS
Owner
07/30/2021 GL TD
CORRECT FCA DEFICIENCIES
HISTORICAL CHAPEL BLDG. 13
621-20-101
MT HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER
R O O M F I N I S H S C H E D U L E
ROOM
NUMBER NAME FLOOR FINISH BASE FINISH
WALL FINISH CEILING
FINISH COMMENTSNORTH SOUTH EAST WEST
001 STAIR ETR, ST-2 / ETR ETR, ST-1 PL-1, P-2 EXP, P-3 EXP, P-3 PL-1, P-2 / EXP, P-3 PL-1, P-2 / EXP, P-3 1, SEE ENLARGED PLAN ON 1/AF801
002 MECHANICAL 1 ETR - EXP, P-3 EXP, P-3 EXP, P-3 EXP, P-3 EXP, P-3
003 MECHANICAL 2 ETR - EXP, P-3 EXP, P-3 EXP, P-3 EXP, P-3 EXP, P-3
004 WEST CRAWL SPACE - - EXP EXP EXP EXP EXP
005 SOUTH TRANSEPT - C.S. - - EXP EXP EXP EXP EXP
006 NORTH TRANSEPT - C.S. - - EXP EXP EXP EXP EXP
007 EAST TRANSEPT - C.S. - - EXP EXP EXP EXP EXP
008 NORTH CRAWL SPACE - - EXP EXP EXP EXP EXP
009 WEST TRANSEPT - C.S. - - EXP EXP EXP EXP EXP
010 IT SLC-1 - P-4 P-4 P-4 P-4 P-4
011 NORTH CRAWL SPACE SLC-1 - EXP EXP EXP EXP EXP
101 TOWER STAIR ETR, ST-2 / ETR ETR, ST-1 EXP EXP EXP EXP EXP, ST-1
102 ENTRANCE ST-2 ETR (PRB-1), ST-1 PL-1, P-2 PL-1, P-2 PL-1, P-2 PL-1, P-2 PL-1, P-2 1, 2
103 WEST CHAPEL ST-2 PRB-1, ST-1 GWB, P-2 GWB, P-2 GWB, P-2 GWB, P-2 EXP 1, 2
104 SOUTH TRANSEPT ST-2 PRB-2, ST-1 GWB, P-2 GWB, P-2 GWB, P-2 GWB, P-2 GWB, P-2 1, 2
105 STAGE ST-2 PRB-2, ST-1 GWB, P-2 GWB, P-2 GWB, P-2 GWB, P-2 GWB, P-2 1, 2
106 VESTIBULE ST-2 PRB-2, ST-1 GWB, P-2 GWB, P-2 GWB, P-2 GWB, P-2 GWB, P-2 1, 2
107 ACCESSIBLE RESTROOM TT-1 CTB-1 GWB, P-2, CTW-1, CTW-2, CTW-3 GWB, P-2 GWB, P-2, CTW-1, CTW-2, CTW-3 GWB, P-2, CTW-1, CTW-2, CTW-3 GWB, P-2
108 RESTROOM TT-1 CTB-1 GWB, P-2, CTW-1, CTW-2, CTW-3 GWB, P-2 GWB, P-2, CTW-1, CTW-2, CTW-3 GWB, P-2, CTW-1, CTW-2, CTW-3 GWB, P-2
109 STAIR ST-2 ETR (PRB-2), ST-1 PL-1, P-2 PL-1, P-2 PL-1, P-2 PL-1, P-2 PL-1, P-2 1, 2
110 ENTRANCE ST-2 ETR (PRB-1), ST-1 PL-1, P-2 PL-1, P-2 PL-1, P-2 PL-1, P-2 PL-1, P-2 1, 2
111 NORTH CHAPEL ST-2 PRB-2, ST-1 GWB, P-2 GWB, P-2 GWB, P-2 GWB, P-2 EXP 1, 2
112 VESTIBULE ST-2 PRB-2, ST-1 GWB, P-2 GWB, P-2 GWB, P-2 GWB, P-2 GWB, P-2 1, 2
113 RESTROOM TT-1 CTB-1 GWB, P-2, CTW-1, CTW-2, CTW-3 GWB, P-2, CTW-1, CTW-2, CTW-3 GWB, P-2 GWB, P-2, CTW-1, CTW-2, CTW-3 GWB, P-2
114 ACCESSIBLE RESTROOM TT-1 CTB-1 GWB, P-2, CTW-1, CTW-2, CTW-3 GWB, P-2, CTW-1, CTW-2, CTW-3 GWB, P-2 GWB, P-2, CTW-1, CTW-2, CTW-3 GWB, P-2
115 STAGE ST-2 PRB-2, ST-1 GWB, P-2 GWB, P-2 GWB, P-2 GWB, P-2 GWB, P-2 1,2
116 EAST TRANSEPT ST-2 PRB-2, ST-1 GWB, P-2 GWB, P-2 GWB, P-2 GWB, P-2 GWB, P-2 1, 2
116A HAC TT-1 CTB-1 GWB, P-2, CTW-1, CTW-2, CTW-3 GWB, P-2, CTW-1, CTW-2, CTW-3 GWB, P-2, CTW-1, CTW-2, CTW-3 GWB, P-2, CTW-1, CTW-2, CTW-3 GWB, P-2
201 TOWER STAIR ST-2 ETR, ST-1 EXP EXP EXP EXP EXP 1
202 WEST BALCONY ST-2 PRB-2, ST-1 GWB, P-2 GWB, P-2 GWB, P-2 GWB, P-2 GWB, P-2 1, 2
203 STAIR ST-2 ETR, ST-1 PL-1, P-2 PL-1, P-2 PL-1, P-2 PL-1, P-2 PL-1, P-2 1
204 NORTH BALCONY ST-2 PRB-2, ST-1 GWB, P-2 GWB, P-2 GWB, P-2 GWB, P-2 GWB, P-2 1, 2
301 TOWER LANDING ST-2 - EXP EXP EXP EXP EXP 1
401 BELL LANDING - ETR EXP EXP EXP EXP P-1
EXP EXPOSED STRUCTURE - - -
ETR EXISTING TO REMAIN - - SEE FINISH NOTE 1.
GYP GYPSUM BOARD USG TBD TBD
PL-1 PLASTER CONSTRUCTION TBD TBD TBD
P-1 PAINT - TYPE 1 SHERWIN WILLIAMS 7035 AESTHETIC WHITE EXTERIOR PAINT
P-2 PAINT - TYPE 2 SHERWIN WILLIAMS 7035 AESTHETIC WHITE GENERAL INTERIOR PAINT
P-3 PAINT - TYPE 3 SHERWIN WILLIAMS 7043 WORLDLY GREY HM DOOR FRAME/CMU WALLS
BASEMENT BRICK WALLS
P-4 PAINT - TYPE 4 SHERWIN WILLIAMS 7005 PURE WHITE PLYWOOD IN ELEC CLOSET
WDB-1 WOOD BASE EXISTING WOOD BASE 2'-1" X 0'-2" TALL PROFILE MATCH EXISTING WOOD BASE IN
PROFILE AND WOOD SPECIES.
SEE DETAIL 1/AE502.
WDB-2 WOOD BASE EXISTING WOOD BASE 0'-7" X 0'-2" SHORT PROFILE MATCH EXISTING WOOD BASE IN
PROFILE AND WOOD SPECIES.
SEE DETAIL 2/AE502.
CTB-1 CERAMIC TILE DALTILE BALANS, GLAZED CERAMIC, BASE TILE IN RESTROOMS -
3X12 FLOOR BULLNOSE / BULLNOSE AT NON-WET WALLS
COLOR TBD
CTW-1 CERAMIC TILE DALTILE BALANS, GLAZED CERAMIC, FIELD TILE USED AT
4X12 WALL TILE / RESTROOM WET WALLS
COLOR TBD
CTW-2 CERAMIC TILE DALTILE BALANS, GLAZED CERAMIC, USE AT TOP COURSE OF TILE
3X12 WALL BULLNOSE / AT WET WALL
COLOR TBD
CTW-3 CERAMIC TILE DALTILE BALANS, GLAZED CERAMIC, ACCENT TILE AT WET WALLS
4X12 WALL TILE /
COLOR TBD
SLC-1 SEALED CONCRETE TBD TBD REFER TO CIVIL SPECIFICATION.
ST-1 WOOD STAIN AND VARNISH TBD TBD INTERIOR WOOD TRIM
ST-2 WOOD STAIN AND VARNISH TBD TBD WOOD FLOORING
ST-3 WOOD STAIN AND VARNISH TBD MATCH EXISTING OPAQUE CEILING PLANKS, WHERE NOTED
TT-1 TERRAZZO FLOORING BOSTIK TBD RESTROOM FLOORING
F I N I S H L E G E N D
MARK DESCRIPTION BASIS OF DESIGN STYLE/COLOR COMMENTS
NOTES:
1. IF EXISTING WOOD BASE BECOMES DAMAGED DURING CONSTRUCTION, REPLACE DAMAGED BASE TO MATCH WITH PRB-1 OR PRB-2.
CONTRACTOR TO MINIMIZE DAMAGE DURING CONSTRUCTION.
2. NOTES: PRODUCTS, COLORS AND FINISHES AS USED IN THE LEGENDS ARE NOT REQUIRED FOR USE. COLOR, FINISHES AND MANUFACTURERS LISTED HERE ARE FOR AESTHETIC AND SPECIFICATION QUALITY STANDARD REFERENCE ONLY. CONTRACTOR MAY SUBMIT OTHER MANUFACTURES PRODUCTS THAT MEET THE CONTRACT DRAWINGS AND SPECIFICATIONS REQUIREMENTS. SUBMITTED
PRODUCTS SHALL COMPLY WITH FAR AND VAAR REQUIREMENTS INCLUDING BUY-AMERICAN ACT.
1. SAND AND REFINISH EXISTING WOOD FLOORING TO REMAIN. SEE NEW WORK PLAN FOR EXTENT OF NEW FLOORING
2. RE-INSTALL REFURBISHED WDB-1 OR WDB-2 PER SCHEDULE.
3. PAINT AT CEILINGS IS FOR GYPSUM BOARD OR PLASTER CEILINGS ONLY - SEE REFLECTED CEILING PLANS - NO PAINT AT EXISTING WOOD CEILINGS.
1 1/2" = 1'-0"
TYPICAL WET WALL ELEVATION
FINISH SCHEDULE NOTES:
1/2" = 1'-0"
ENLARGED BASEMENT STAIR - FINISH PLAN
STAIR
MECHANICAL 1
MECHANICAL 2
FIRE DEPARTMENT
CONNECTION
4" FPD
3" FPD
1 1/2" FPD
3" FPD
UG 4" FPD
AIR COMPRESSOR
DRY PIPE VALVE
A. THE ENTIRETY OF THE BUILDING IS CURRENTLY SPRINKLERED WITH A DRY PIPE FIRE
PROTECTION SYSTEM.
B. REMOVE ALL FIRE PROTECTION SYSTEM COMPONENTS IN BUILDING. A NEW DRY PIPE
FIRE PROTECTION SYSTEM WILL BE INSTALLED IN NEW WORK PHASE.
C. PATCH ALL PIPE PENETRATIONS THROUGH WALLS AND FLOORS TO MATCH EXISTING
AFTER REMOVAL OF FIRE PROTECTION SYSTEM.
D. REFER TO SHEET P001 FOR LEGENDS, ABBREVIATIONS, AND GENERAL PROJECT NOTES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
C U s e rs \k y le g \D o c u m e n ts
\R e v it L o c a l F ile s \2
\F
F E
M t H o m e
C h a p e l_ B
M
E P k y le
.g u g g e n h e im .r v t
/3
/2
:1
:3
P
M
FD101
BASEMENT FIRE PROTECTION
DEMOLITION PLAN
07/30/2021 PP GP
CORRECT FCA DEFICIENCIES
HISTORICAL CHAPEL BLDG. 13
621-20-101
MT. HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER
1/8" = 1'-0"
BASEMENT FIRE SUPPRESSION DEMOLITION PLAN
G E N E R A L N O T E S :
D R A W I N G N O T E S :
1 REMOVE ALL FIRE PROTECTION PIPING AND ASSOCIATED SPRINKLERS, VALVES, HOSE REELS, AND EQUIPMENT IN ENTIRETY OF BUILDING. CONTRACTOR TO FIELD VERIFY EXTENT OF
EXISTING FIRE PROTECTION SYSTEM.
2 REMOVE DRY PIPE VALVE AND AIR COMPRESSOR.
3 REMOVE EXTERIOR FIRE DEPARTMENT CONNECTION AND ASSOCIATED PIPING. EXISTING
OPENINGS SHALL BE REUSED. SEE NEW WORK DRAWINGS.
4 REFER TO CIVIL SITE UTILITY PLAN FOR CONTINUATION OF PIPING.
07/30/2021
NORTH TRANSEPT - C.S.
WEST CRAWL SPACE
SOUTH TRANSEPT - C.S.
STAIR
MECHANICAL 1
MECHANICAL 2
NORTH CRAWL SPACE
WEST TRANSEPT - C.S.
FPD
FPD
FPD UP
FPD UP
FX101
FPD UP
FPD UP
FPD UP
FPD UP
AC-1
UG 4" FPD
IT
EAST TRANSEPT - C.S.
NORTH CRAWL SPACE
STAGE
ACCESSIBLE RESTROOM
SOUTH TRANSEPT
WEST CHAPEL
STAIR
ENTRANCE
ENTRANCE
TOWER STAIR
NORTH CHAPEL
RESTROOM
FPD UP & DN
FPD DN
FPD DN
FPD UP & DN
FPD DN
FPD DN
FPD UP & DN
FPD UP & DN
RESTROOM
VESTIBULE
FPD
ACCESSIBLE RESTROOM
VESTIBULE
HAC
116A
EAST TRANSEPT
FPD DN
STAGE
A. INSTALL COMPLETE AUTOMATIC DRY FIRE SPRINKLER SYSTEM IN ACCORDANCE WITH
NFPA 13 AND VA FIRE PROTECTION MANUAL.
B. INSTALL SPRINKLER SYSTEM OVER AND UNDER DUCTS, PIPING, AND PLATFORMS WHEN
SUCH EQUIPMENT CAN NEGATIVELY EFFECT OR DISRUPT THE SPRINKLER DISCHARGE
PATTERN AND COVERAGE.
C. FURNISH PIPING OFFSETS, FITTINGS, AND ANY OTHER ACCESSORIES AS REQUIRED TO
PROVIDE A COMPLETE INSTALLATION AND TO ELIMINATE INTERFERENCE WITH OTHER
CONSTRUCTION.
D. PROVIDE AUXILIARY DRAIN WHERE CHANGE IN PIPING DIRECTION PREVENTS DRAINAGE
OF SYSTEM PIPING THROUGH MAIN DRAIN VALVE.
E. PIPE SIZES SHALL BE DETERMINED BY HYDRAULIC CALCULATION COMPLETED BY
CONTRACTOR. CONTRACTOR TO SUBMIT SPRINKLER DESIGN.
F. COMPLETELY COORDINATE WITH STRUCTURAL, ARCHITECTURAL, AND ALL OTHER
TRADES. EQUIPMENT, SPRINKLERS, AND PIPING SHOWN ON THESE PLANS IS TO CONVEY
DESIGN INTENT AND DOES NOT DICTATE THE MEANS AND METHODS OF
IMPLEMENTATION. ADHERE TO ALL HAZARD CLASSIFICATIONS SHOWN.
G. REFER TO ARCHITECTURAL AND FIRE ALARM DRAWINGS FOR FIRE ALARM ZONES, SMOKE
PARTITIONS, AND FIRE EXTINGUISHER CABINETS.
H. CONTRACTOR TO CONDUCT FIRE WATER FLOW TEST AND SUBMIT RESULTS.
I. REFER TO SHEET P001 FOR LEGENDS, ABBREVIATIONS, AND GENERAL PROJECT NOTES.
FIRST FLOOR
0' - 0"
BASEMENT
-9' - 6 11/16"
AC-1
4" DRY
PIPE VALVE
4" FPD
4" FPD
4" DOUBLE CHECK
DETECTOR VALVE WITH
SUPERVISORY SWITCHES
(E) UG 4" FP
FROM SITE
FIRE DEPARTMENT
CONNECTION
4" CHECK
VALVE HOSE
CONNECTION
FIRE SPRINKLER HAZARD SCHEDULE
CLASSIFICATION CRITERIA HOSE DURATION SPRINKLER SPRINKLER DENSITY NOTES
LIGHT HAZARD 0.10 GPM/SF OVER
1500 SF
100 GPM 30 MIN QR; K = 5.6 OR K = 8.0 1 SPRINKLER PER
225 SF
BASE AREA
ORDINARY HAZARD
GROUP I
0.15 GPM/SF OVER
1500 SF
250 GPM 60 MIN QR; K = 5.6 OR K = 8.0 1 SPRINKLER PER
130 SF
BASE AREA
ORDINARY HAZARD
GROUP II
0.20 GPM/SF OVER
1500 SF
250 GPM 60 MIN QR; K = 5.6 OR K = 8.0 1 SPRINKLER PER
130 SF
BASE AREA
AIR COMPRESSOR SCHEDULE
MARK LOCATION
SYSTEM AND/OR
SERVICE
TYPE
INLET
AIRFLOW
DISCHARGE
PRESSURE
SYSTEM
CAPACITY
RECEIVER
SIZE
COMPRESSOR DIMENSIONS
L x W x H
ELECTRIC POWER [60 Hz] OPERATING
WEIGHT REMARKS
CFM [L/S] PSIG [kPa] GAL [L] GAL [L] IN [mm] # OF MOTORS HP [KW] PHASE VOLT LBS [KG]
AC-1 MECHANICAL 1 002
DRY PIPE FIRE
SUPPRESSION
TANK
MOUNTED
3.5 1.65 40 276 290 1098 10 38 33 x 13 x 28 838 x 330 x 711 1 1/2 0.37 1 120 115 52 1, 2
REMARKS:
1. PROVIDE WITH AIR MAINTENANCE DEVICE.
2. DESIGNED TO FILL DRY PIPE SYSTEM TO 40 PSI IN 30 MINUTES.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
C U s e rs \k y le g \D o c u m e n ts
\R e v it L o c a l F ile s \2
\F
F E
M t H o m e
C h a p e l_ B
M
E P k y le
.g u g g e n h e im .r v t
/3
/2
:1
:4
P
M
FX101
BASEMENT & FIRST FLOOR FIRE
SUPPRESSION PLANS
07/30/2021 PP GP
CORRECT FCA DEFICIENCIES
HISTORICAL CHAPEL BLDG. 13
621-20-101
MT. HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER
1/8" = 1'-0"
BASEMENT FIRE SUPPRESSION PLAN
1/8" = 1'-0"
FIRST FLOOR FIRE SUPPRESSION PLAN
G E N E R A L N O T E S :
F I R E H A Z A R D L E G E N D :
LIGHT HAZARD
ORDINARY HAZARD LEVEL 1
1/4" = 1'-0"
FIRE PROTECTION SECTION
D R A W I N G N O T E S :
1 INSTALL NEW FIRE DEPARTMENT CONNECTION IN PLACE OF EXISTING.
2 INSTALL 4" DRY PIPE VALVE.
3 INSTALL TANK MOUNTED AIR COMPRESSOR TO SERVE DRY PIPE VALVE. REFER TO AIR
COMPRESSOR SCHEDULE ON THIS SHEET.
4 REFER TO CIVIL SITE UTILITY PLAN FOR CONTINUATION OF PIPING.
ORDINARY HAZARD LEVEL 2
WEST BALCONY
STAIR
NORTH BALCONY
TOWER STAIR
FPD DN
FPD DN
FPD DN
FPD
FPD
FPD
FPD
FPD FPD
FPD
FPD DN
FPD UP
STAGE
WEST CHAPEL
NORTH CHAPEL
STAGE
FPD DN
BELL LANDING
A. INSTALL COMPLETE AUTOMATIC DRY FIRE SPRINKLER SYSTEM IN ACCORDANCE WITH
NFPA 13 AND VA FIRE PROTECTION MANUAL.
B. INSTALL SPRINKLER SYSTEM OVER AND UNDER DUCTS, PIPING, AND PLATFORMS WHEN
SUCH EQUIPMENT CAN NEGATIVELY EFFECT OR DISRUPT THE SPRINKLER DISCHARGE
PATTERN AND COVERAGE.
C. FURNISH PIPING OFFSETS, FITTINGS, AND ANY OTHER ACCESSORIES AS REQUIRED TO
PROVIDE A COMPLETE INSTALLATION AND TO ELIMINATE INTERFERENCE WITH OTHER
CONSTRUCTION.
D. PROVIDE AUXILIARY DRAIN WHERE CHANGE IN PIPING DIRECTION PREVENTS DRAINAGE
OF SYSTEM PIPING THROUGH MAIN DRAIN VALVE.
E. PIPE SIZES SHALL BE DETERMINED BY HYDRAULIC CALCULATION COMPLETED BY
CONTRACTOR. CONTRACTOR TO SUBMIT SPRINKLER DESIGN.
F. COMPLETELY COORDINATE WITH STRUCTURAL, ARCHITECTURAL, AND ALL OTHER
TRADES. EQUIPMENT, SPRINKLERS, AND PIPING SHOWN ON THESE PLANS IS TO CONVEY
DESIGN INTENT AND DOES NOT DICTATE THE MEANS AND METHODS OF
IMPLEMENTATION. ADHERE TO ALL HAZARD CLASSIFICATIONS SHOWN.
G. REFER TO ARCHITECTURAL AND FIRE ALARM DRAWINGS FOR FIRE ALARM ZONES, SMOKE
PARTITIONS, AND FIRE EXTINGUISHER CABINETS.
H. CONTRACTOR TO CONDUCT FIRE WATER FLOW TEST AND SUBMIT RESULTS.
I. REFER TO SHEET P001 FOR LEGENDS, ABBREVIATIONS, AND GENERAL PROJECT NOTES.
FIRE SPRINKLER HAZARD SCHEDULE
CLASSIFICATION CRITERIA HOSE DURATION SPRINKLER SPRINKLER DENSITY NOTES
LIGHT HAZARD 0.10 GPM/SF OVER
1500 SF
100 GPM 30 MIN QR; K = 5.6 OR K = 8.0 1 SPRINKLER PER
225 SF
BASE AREA
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
C U s e rs \k y le g \D o c u m e n ts
\R e v it L o c a l F ile s \2
\F
F E
M t H o m e
C h a p e l_ B
M
E P k y le
.g u g g e n h e im .r v t
/3
/2
:1
:5
P
M
FX102
SECOND FLOOR & BELL TOWER
FIRE SUPPRESSION PLANS
07/30/2021 PP GP
CORRECT FCA DEFICIENCIES
HISTORICAL CHAPEL BLDG. 13
621-20-101
MT. HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER
1/8" = 1'-0"
SECOND FLOOR FIRE SUPPRESSION PLAN
1/8" = 1'-0"
BELL TOWER FIRE SUPPRESSION PLAN
G E N E R A L N O T E S : F I R E H A Z A R D L E G E N D :
LIGHT HAZARD
PLUMBING VALVE SYMBOLS
BALL VALVE
CHECK VALVE
BUTTERFLY VALVE
GATE VALVE
GENERAL PLUMBING SYMBOLS
LIMIT OF DEMOLITION
ANCHOR
REDUCER OR INCREASER
DIRECTION OF FLOW
SIDE CONNECTION
ECCENTRIC REDUCER
BOTTOM CONNECTION, 45° OR 90°
TOP CONNECTION, 45° OR 90°
DIRECTION OF PIPE PITCH (DOWN)
UNION
RISE OR DROP IN PIPE
CAPPED OUTLET
POINT OF CONNECTION BETWEEN NEW AND
EXISTING WORK
PRESSURE GAGE
THERMOMETER
STRAINER
PIPE UP
PIPE DOWN
CO CLEAN OUT
DRAWING SYMBOLS
PL101
A
26-P 3
DETAIL NUMBER
DRAWING NUMBER WHERE SHOWN
SECTION LETTER
TYPICAL UNIT NO.
BUILDING NO. WHERE EQUIPMENT IS LOCATED.
PUMP NO.3 IN BUILDING NO.26
EQUIPMENT ABBREVIATION (PUMP)
DRAWING NUMBER WHERE DRAWN
PL105
PIPING CONTINUATION
PLUMBING ABBREVIATIONS
REVISION NUMBER
PIPING SYMBOLS
DOMESTIC COLD WATER
DOMESTIC HOT WATER
DOMESTIC HOT WATER RETURN
VENT (SANITARY)
DCW
DHW
DHWR
SANITARY SEWER
SAN
STORM WATER
SW
V
PLUMBING GENERAL NOTES
A. THE FOLLOWING NOTES APPLY EQUALLY TO THE FULL SET OF PLUMBING DOCUMENTS.
B. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
C. REFER TO SCHEDULES, DETAILS, AND DIAGRAMS FOR PIPING, PIPE SIZES AND PIPELINE DEVICES NOT
INDICATED ON FLOOR PLAN.
D. LOCATIONS AND SIZES OF EXISTING PIPING SHOWN ON THIS DRAWING HAVE BEEN DETERMINED FROM A REVIEW OF EXISTING DRAWINGS AND/OR SITE INVESTIGATION WHERE POSSIBLE. CONTRACTOR TO FIELD VERIFY EXISTING CONDITIONS. ANY DISCREPANCIES BETWEEN EXISTING CONDITIONS AND THE WORK SHOWN ON THE CONTRACT DRAWINGS WHICH MAY IMPACT THE PROGRESS OF WORK SHALL BE BROUGHT
TO THE ATTENTION OF THE VA IN WRITING BEFORE PROCEEDING WITH THE WORK.
E. EACH CONTRACTOR SHALL COORDINATE THEIR WORK WITH THE WORK OF OTHERS.
F. ALL WORK SHALL BE IN COMPLIANCE WITH GOVERNING CODES AND VA STANDARDS.
G. PROVIDE ACCESS PANELS IN NON-ACCESSIBLE SUSPENDED CEILINGS FOR VALVES, CLEANOUTS, CONTROLS, ETC.
H. ALL PENETRATIONS THROUGH FIRE-RATED ASSEMBLIES SHALL BE PROTECTED AND/OR FIRESTOPPED AS REQUIRED TO MAINTAIN FIRE RATINGS. REFER TO ARCHITECTURAL PLANS FOR LOCATIONS OF FIRE-RATED
ASSEMBLIES.
I. CONTRACTOR TO IMMEDIATELY INFORM THE COR IN THE EVENT THAT MATERIALS OBSERVED ARE
SUSPECTED TO CONTAIN ASBESTOS.
J. PROVIDE OFFSETS AS NECESSARY TO COMPLETE SYSTEMS AND COORDINATE WORK WITH OTHER TRADES.
PIPING PENETRATION THROUGH FLOOR/ROOF
NEW PIPING
PIPING TO BE REMOVED
EXISTING PIPING
A/E ARCHITECT / ENGINEER
AC AIR COMPRESSOR
AD AREA DRAIN/ACCESS DOOR
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AG AIR GAP
AP ACCESS PANEL
AS AUTOMATIC SPRINKLER/AIR SEPARATOR
ASD ADJUSTABLE SPEED DRIVES/AUTOMATIC SPRINKLER DRAIN
ASHRAE AMERICAN SOCIETY OF HEATING REFRIGERATION AIR
CONDITIONING ENGINEERS
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS
ASPE AMERICAN SOCIETY OF PLUMBING ENGINEERS
ASR AUTOMATIC SPRINKLER RISER
BFP BACKFLOW PREVENTER
BHP BRAKE HORSEPOWER
BSP BLACK STEEL PIPE
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
C CENTIGRADE (CELSIUS)
CA COMPRESSED AIR
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CFT CUBIC FEET
CI CAST IRON
CM COUNTER MOUNTED/CUBIC METER
CO CLEAN OUT
COMP COMPARTMENT
CV CONSTANT VOLUME/CONTROL VALVE
D DRAIN
DCW DOMESTIC COLD WATER
DD-1 DESIGN DEVELOPMENT (SUBMISSION 1)
DD-2 DESIGN DEVELOPMENT (SUBMISSION 2)
DFU DRAINAGE FIXTURE UNITS
DHW DOMESTIC HOT WATER
DHWR DOMESTIC HOT WATER RETURN
DIA DIAMETER
DN DOWN
DOE DEPARTMENT OF ENERGY
DS DOWNSPOUT
DWG DRAWING
DWH DOMESTIC WATER HEATER
DWV DRAIN WASTE VENT
EL ELEVATION
EPA ENVIRONMENTAL PROTECTION AGENCY
ESC ESCUTCHEON
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
(E) EXISTING TO REMAIN
F FAHRENHEIT
FCO FLOOR CLEANOUT
FD FLOOR DRAIN
FDC FIRE DEPARTMENT (HOSE) CONNECTION
FF FINISHED FLOOR
FM FLOW METER/FLOOR MOUNTED
FPD FIRE PROTECTION - DRY PIPE
FPS FEET PER SECOND
FS FLOW SWITCH/FLOOR SINK
FT FEET
FT WC FEET OF WATER COLUMN
FT-LB FOOT-POUND
FU FIXTURE UNITS
GAL GALLON
GCO GRADE CLEANOUT
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GS GALVANIZED STEEL
H HEIGHT
H&CW HOT AND COLD WATER
HAC HOUSEKEEPING AID CLOSET
HB HOSE BIBB
HP HORSEPOWER
HS HAND SINK
HYD HYDRANT
ID INSIDE DIAMETER
IE INVERT ELEVATION
IN INCHES
INV INVERT
IPC INTERNATIONAL PLUMBING CODE
IW INDIRECT WASTE
IWH INSTANTANEOUS WATER HEATER
KG KILOGRAM
KW KILOWATT
KWH KILOWATT HOUR
L LITER/LENGTH
L/H LITERS PER HOUR (or LITERS/HOUR) L/M LITERS PER MINUTE (or LITERS/MINUTE) L/S LITERS PER SECOND (or LITERS/SECOND)
LAV LAVATORY
LBS/HR POUNDS PER HOUR
LF LINEAR FOOT (FEET)
LW LOW WATER
M METER
M/S METERS PER SECOND (OR METERS/SECOND)
MAV MANUAL AIR VENT
MAX MAXIMUM
MBH 1,000 BTUH
MH MANHOLE
MHP MOTOR HORSEPOWER
MIN MINIMUM
MOU MEMORANDUM OF UNDERSTANDING
MS MOP SINK
NA NOT APPLICABLE
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NOM NOMINAL
NPW NON POTABLE WATER
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OFD OVERFLOW DRAIN
PCF POUNDS PER CUBIC FOOT (FEET)
PD PRESSURE DROP
PDI PLUMBING AND DRAINAGE INSTITUTE
PG PRESSURE GAGE
PPM PARTS PER MILLION
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH – ABSOLUTE
PSIG POUNDS PER SQUARE INCH – GAGE
PW POTABLE WATER
QR QUICK RESPONSE
RD ROOF DRAIN
RDL ROOF DRAIN LEADER
RL ROOF LEADER
RPM REVOLUTIONS PER MINUTE
RTU ROOF TOP UNIT
SAN SANITARY SEWER
SD SMOKE DETECTOR
SDMH STORM DRAIN MANHOLE
SD-1 SCHEMATIC DESIGN (SUBMISSION1)
SD-2 SCHEMATIC DESIGN (SUBMISSION2)
SF SQUARE FOOT (FEET)
SMACNA SHEET METAL AND AIR CONDITIONING
CONTRACTORS NATIONAL ASSOCIATION
SMH SANITARY MANHOLE
SP SUMP PUMP/STATIC PRESSURE
SP GR SPECIFIC GRAVITY
SS STAINLESS STEEL
SSD SUBSOIL DRAINAGE
ST STORAGE TANK/STEAM TRAP
SW STORM WATER
TD TRENCH DRAIN/TEMPERATURE DIFFERENCE
TDH TOTAL DYNAMIC HEAD
TEMP TEMPERATURE
TMV THERMOSTATIC MIXING VALVE
TP TRAP PRIMER
TSP TOTAL STATIC PRESSURE
TYP TYPICAL
UG UNDERGROUND
V VENT
VB VACUUM BREAKER
VCO VACUUM CLEANER OUTLET
VHA VETERANS HEALTH ADMINISTRATION
VS VENT STACK
VTR VENT THROUGH ROOF
W WASTE/WATTS/WIDTH
WC WATER CLOSET
WCO WALL CLEANOUT
WG WATER GAGE
WH WALL HYDRANT/WATER HEATER
WHA WATER HAMMER ARRESTER
WL WATER LINE
WM WATER METER/WALL MOUNTED
WPD WATER PRESSURE DROP
WS WASTE STACK
WSFU WATER SUPPLY FIXTURE UNITS
YCO YARD CLEANOUT
YH YARD HYDRANT
FIRE PROTECTION (DRY PIPE SYSTEM)
FPD
NOTE: NOT ALL SYMBOLS AND ABBREVIATIONS ARE USED ON DRAWINGS
SUBSOIL DRAIN (FOUNDATION DRAINAGE)
SSD
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
C U s e rs \k y le g \D o c u m e n ts
\R e v it L o c a l F ile s \2
\F
F E
M t H o m e
C h a p e l_ B
M
E P k y le
.g u g g e n h e im .r v t
/3
/2
:1
:0
P
M
P001
PLUMBING LEGEND SHEET
07/30/2021 PP GP
CORRECT FCA DEFICIENCIES
HISTORICAL CHAPEL BLDG. 13
621-20-101
MT. HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER
P-503
2" DCW
1 1/2" DCW
4" SAN
UG 2" DCW
UG 6" SAN
UG 4" SAN
4" SAN
3/4" DCW UP
1 1/4" SAN UP
1/2" DHW UP
1 1/2" SAN UP
1/2" DCW UP
4" SAN UP
1/2" DCW UP
3/4" DHW
3/4" DCW
3/4" DCW
1/2" DCW UP
1 1/2" SAN UP
1/2" DHW UP
4" SAN UP
1/2" DCW UP
2" V UP
1/2" DCW UP
1 1/2" SAN UP
1/2" DHW UP
1/2" DCW UP
4" SAN UP
2" V UP
2" V UP
4 4
66 66 5
P-101 P-414
P-604
P-106
P-414 P-414
P-106
P-801
(E) 3" VTR
(E) 3" VTR
3 3
3 3
P-106
P-414
A. REFER TO SHEET P001 FOR LEGEND, ABBREVIATIONS, AND GENERAL PROJECT NOTES.
B. LOCATIONS OF EXISTING PIPING, PIPING ACCESSORIES, PLUMBING EQUIPMENT, AND
PLUMBING FIXTURES SHOWN ON THIS DRAWING HAVE BEEN DETERMINED BY EXISTING
DRAWINGS AND SITE INVESTIGATION. CONTRACTOR TO FIELD VERIFY LOCATIONS OF
UNSEEN PIPING AND REPORT DISCREPANCIES THAT WILL IMPACT THE PROGRESS OF
WORK TO THE VA COR.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
C U s e rs \k y le g \D o c u m e n ts
\R e v it L o c a l F ile s \2
\F
F E
M t H o m e
C h a p e l_ B
M
E P k y le
.g u g g e n h e im .r v t
/3
/2
:1
:1
P
M
PD101
BASEMENT & FIRST FLOOR
PLUMBING DEMOLITION PLANS
07/30/2021 PP GP
CORRECT FCA DEFICIENCIES
HISTORICAL CHAPEL BLDG. 13
621-20-101
MT. HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER
1/8" = 1'-0"
BASEMENT PLUMBING DEMOLITION PLAN
1/8" = 1'-0"
FIRST FLOOR PLUMBING DEMOLITION PLAN
G E N E R A L N O T E S :
PLUMBING FIXTURE SCHEDULE - FIXTURES TO BE REMOVED
MARK DESCRIPTION
P-101 WATER CLOSET, FLOOR MOUNTED
P-106 WATER CLOSET, TANK TYPE
P-414 LAVATORY, WALL MOUNTED
P-503 SERVICE SINK, WALL MOUNTED, FOOT PEDAL CONTROL
P-604 ELECTRIC WATER COOLER, WALL HUNG, SINGLE BOWL
P-801 WALL HYDRANT, EXTERIOR, NON-FREEZE
D R A W I N G N O T E S :
1 REMOVE ALL DOMESTIC WATER PIPING AND ASSOCIATED ACCESSORIES.
2 REMOVE ALL VENT PIPING BACK TO POINT JUST BELOW EXISTING VENTS THROUGH ROOF. EXISTING
VENTS THROUGH ROOF TO REMAIN AND BE RE-USED IN NEW WORK PHASE.
3 REMOVE PLUMBING FIXTURE AND ASSOCIATED PIPING.
4 REMOVE WATER HEATER AND ASSOCIATED PIPING.
5 PATCH FLOOR PENETRATION TO MATCH EXISTING AFTER REMOVAL OF PIPING.
6 PATCH WALL PENETRATION TO MATCH EXISTING AFTER REMOVAL OF PIPING.
7 REFER TO CIVIL SITE UTILITY PLAN FOR CONTINUATION OF PIPING.
8 REMOVE ALL ABOVE GROUND SANITARY PIPING INSIDE BUILDING. FILL UNDERGROUND SANITARY
PIPING WITH FLOWABLE GROUT AND LEAVE ABANDONED IN PLACE.
B F
P
NORTH TRANSEPT - C.S.
SOUTH TRANSEPT - C.S.
WEST CRAWL SPACE
STAIR
MECHANICAL 1
MECHANICAL 2
WEST TRANSEPT - C.S.
2" BFP
2" WATER METER
UG 4" SSD
UG 4" SSD
UG 4" SSD
4" CO
4" CO
4" GCO
4" GCO
UG 4" SSD
2" V UP
1 1/2" DCW UP
4" SAN UP
1 1/2" SAN UP
4" SAN UP
2" V UP1 1/2" SAN UP
1 1/2" DCW
1 1/2" SAN UP
4" SAN UP
2" V UP
1 1/2" DCW UP
1 1/2" SAN UP
2" V UP
4" SAN UP
4" SAN
UG 4" SAN
UG 4" SAN
4" FCO
4" FCO
4" FD-E
4" FD-E
UG 2" V
4" SAN
2" V UP
TP-1
UG 4" SAN
UG 2" DCW
2" DCW
2" DCW
1 1/2" DCW
2" DCW
1 1/2" DCW
NORTH CRAWL SPACE
IT
EAST TRANSEPT - C.S.
P-801
1/2" DCW
1/2" DCW
1 1/2" V
3" SAN UP
1/2" DCW UP
NORTH CRAWL SPACE
4" GCO
UG 4" SSD
UG 4" SSD
RESTROOM
NORTH CHAPEL
ACCESSIBLE RESTROOM
STAGE
SOUTH TRANSEPT
WEST CHAPEL
STAIR
ENTRANCE
ENTRANCE
TOWER STAIR
RESTROOM
VESTIBULE
ACCESSIBLE RESTROOM
VESTIBULE
PL101
PL101
2" V DN
2" V UP TO
3" VTR
EWH-3P-502
1/2" DCW DN
EAST TRANSEPT
HAC
116A
A. REFER TO SHEET P001 FOR LEGEND, ABBREVIATIONS, AND GENERAL PROJECT NOTES.
B. EXISTING CONDITIONS SHOWN ON THIS DRAWING HAVE BEEN DETERMINED BY EXISTING
DRAWINGS AND SITE INVESTIGATION. CONTRACTOR TO FIELD VERIFY EXISTING
CONDITIONS AND REPORT DISCREPANCIES THAT WILL IMPACT THE PROGRESS OF WORK
TO THE VA COR.
C. REFER TO CIVIL SITE UTILITY AND ARCHITECTURAL DRAWINGS FOR STORM
DOWNSPOUTS AND UNDERGROUND STORM DRAINAGE.
P-101
P-414
P-101
P-414
ACCESSIBLE RESTROOM
VESTIBULE
RESTROOM
(E) 3" VTR
EWH-1
21 1/2" DCW DN
P-801
P-101
P-414
P-414
P-101
(E) 3" VTR
ACCESSIBLE RESTROOM
VESTIBULE
RESTROOM
EWH-2
1 1/2" DCW DN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
C U s e rs \k y le g \D o c u m e n ts
\R e v it L o c a l F ile s \2
\F
F E
M t H o m e
C h a p e l_ B
M
E P k y le
.g u g g e n h e im .r v t
/3
/2
:1
:2
P
M
PL101
BASEMENT & FIRST FLOOR
PLUMBING NEW WORK PLANS
07/30/2021 PP GP
CORRECT FCA DEFICIENCIES
HISTORICAL CHAPEL BLDG. 13
621-20-101
MT. HOME, TENNESSEE
BID DOCUMENTS
JAMES H.
QUILLEN VA
MEDICAL
CENTER
1/8" = 1'-0"
BASEMENT PLUMBING NEW WORK PLAN
1/8" = 1'-0"
FIRST FLOOR PLUMBING NEW WORK PLAN
G E N E R A L N O T E S :
1/4" = 1'-0"
ENLARGED PLUMBING PLAN - NORTH TRANSEPT
1/4" = 1'-0"
ENLARGED PLUMBING PLAN - WEST TRANSEPT
D R A W I N G N O T E S :
1 CONNECT VENT PIPING TO EXISTING AT POINT SHOWN. RE-USE EXISTING VENT THROUGH
ROOF.
2 INSTALL INSTANTANEOUS ELECTRIC WATER HEATER ON WALL UNDER LAVATORY. REFER TO
WATER HEATER SCHEDULE ON SHEET PL501.
3 REFER TO CIVIL SITE UTILITY PLAN FOR CONTINUATION OF PIPING.
4 REFER TO DETAIL 1 ON SHEET AE311 FOR FOUNDATION DRAINAGE PIPING INSTALLATION.
5 INSTALL INSTANTANEOUS ELECTRIC WATER HEATER ON WALL ABOVE MOPSINK. REFER TO
WATER HEATER SCHEDULE ON SHEET PL501.
ELECTRIC WATER HEATER SCHEDULE
MARK LOCATION
AREA AND/OR
BLDG SERVED
SYSTEM
AND/OR
SERVICE
TYPE
TEMPERATURE RISE
AT 1.0 GPM
ELECTRICAL INPUT
REMARKS
oF o[C] kW PHASE VOLT
EWH-1 RESTROOM 108
NORTH
TRANSEPT
DOMESTIC HOT
WATER
INSTANTANEOUS
POINT OF USE
57 [ 32 ] 8.3 1 208 1, 3
EWH-3
HAC CLOSET
116A
EAST TRANSEPT
DOMESTIC HOT
WATER
INSTANTANEOUS
POINT OF USE
57 [ 32 ] 8.3 1 208 2, 3
REMARKS:
1. SERVES (2) LAVATORIES.
2. SERVES MOPSINK.
3. LIMIT HOT WATER TEMPERATURE OUTPUT TO 110 DEGREES F TO PREVENT SCALDING.
EWH-2 RESTROOM 113 WEST TRANSEPT
DOMESTIC HOT
WATER
INSTANTANEOUS
POINT OF USE
57 [ 32 ] 8.3 1 208 1, 3
[2100]
NOM. SIZE
PIPE
TUBING
IN.
[mm]
FT.
[mm]
FT.
[mm]
SIDE VIEW TRAPEZE HANGER FOR UP
TO 1000 LB. [453KG] UNIFORM LOAD
ADJUSTABLE CLEVIS
HANGER TYPE 1 - SEE
SPECIFICATIONS
PROVIDE INSULATION SHIELD &
INSERT FOR ALL PIPING (8"
[200mm] MIN.)
BAND
1-5/8" [43mm] 12 GAUGE CHANNEL OR 2"x2"x1/4" [50x50x6.4mm] ANGLE
1/2" [15mm] DIA. HANGER RODS WITH 36" [900mm] MAX. SPACING ON EACH
CHANNEL
WELD
SADDLE
INSULATION SHIELD AT
HANGER
PROVIDE HIGH COMPRESSIVE
STRENGTH INSULATION (9 PSF MIN.
DENSITY) UNDER INSULATION
SHI…