This document describes a federal contract opportunity for correcting facility condition assessment deficiencies at the Historical Chapel building at the James H. Quillen VA Medical Center in Mountain Home, Tennessee. Work includes selective demolition, abatement of environmental hazards including mold, lead-based paint, and asbestos-containing materials, as well as modification, restoration, and new construction of interior and exterior features such as the roof, walls, stairs, sidewalks, lighting, signage, walls, floors, ceilings, doors, mechanical and electrical systems, plumbing, and communications. The solicitation is expected to be issued on October 15, 2021, with responses due by November 16, 2021. This is a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses. The estimated value is between $2 million and $5 million.
View the file
Other files
Show all 31
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Asbestos and Lead-Based Paint Survey Report
VAMC MOUNTAIN HOME – BUILDING 13 CHAPEL
LAMONT STREET AND VETERANS WAY
JOHNSON CITY, TENNESSEE
February 25, 2021 Terracon Project No. 86207201
Prepared for:
FFE, Inc.
Cincinnati, Ohio
Prepared by:
Terracon Consultants, Inc.
Greenville, South Carolina
Inspector:
Stephen N. Ellis
TDEC License No. A-I-59148-59469 Inspected on January 12 and 13, 2021
TABLE OF CONTENTS
EXECUTIVE SUMMARY……………………………………………………………………………...i
1.0 INTRODUCTION
2.0 BUILDING DESCRIPTION
3.0 ASBESTOS SURVEY
3.1 Regulatory Overview
3.2 Previous Reports Review
3.3 Visual Assessment
3.4 Physical Assessment
3.5 Sample Collection
3.6 Sample Analysis
3.6 Findings
4.0 LEAD-BASED PAINT SURVEY
4.1 Regulatory Overview
4.2 Sampling and Analytical Protocol
4.3 Findings
5.0 RECOMMENDATIONS
6.0 GENERAL COMMENTS
LIST OF APPENDICES
APPENDIX A - FIGURE
Figure 1 – General Layout/ Sample Locations
APPENDIX B - TABLES
Table 1 - Asbestos Survey Sample Summary Table 2 – Lead-in-Paint Sample Summary (Paint Chip)
APPENDIX C – LABORATORY REPORTS
APPENDIX D – PHOTODOCUMENTATION
APPENDIX E – INSPECTOR’S CREDENTIAL
APPENDIX F – PRIOR SURVEY REPORTS
ACM and LBP Survey Report VAMC Mountain Home – Building 13 Chapel ■ Johnson City, Tennessee February 25, 2021 ■ Terracon Project No. 86207201
Responsive ■ Resourceful ■ Reliable i
EXECUTIVE SUMMARY
Terracon Consultants, Inc. (Terracon) conducted an asbestos and lead-based paint survey at VAMC Mountain Home – Building 13 Chapel at Lamont Street and Veterans Way in Johnson City, Tennessee. Our survey was conducted on January 12 and 13, 2021 in support of proposed renovations and repairs and in general accordance with the terms of our Proposal No. P86207201 dated September 23, 2020. This Executive Summary is intended as an overview for the convenience of the reader. The complete report must be reviewed in its entirety prior to making decisions regarding this site.
The asbestos-containing material (ACM) survey was performed by a Tennessee Department of Environment & Conservation (TDEC) licensed asbestos building inspector in general accordance with the sampling protocols established in Environmental Protection Agency (EPA) 40 Code of Federal Regulations (CFR) 763 (Asbestos Hazard Emergency Response Act, AHERA).
Asbestos-Containing Materials
A total of sixty-four (64) bulk samples were collected from the interior and exterior of the building.
A general layout with sample locations is included as Figure 1 in Appendix A. Sample descriptions, locations, analytical results, classification and estimated quantities are summarized in Table 1 in Appendix B. The asbestos laboratory analytical report is included in Appendix C and photographs are provided in Appendix D.
Asbestos was detected in concentrations of greater than one percent (1%) in the following materials:
§ TSI contaminated debris (40% chrysotile) in the closet under the basement stairs;
§ Silver duct mastic (2% chrysotile) on the intake duct work in the bell tower;
§ Caulking (3% chrysotile) on the exterior doors;
§ Gray mortar joint caulking (2% chrysotile) on the exterior concrete sill blocks;
§ Black mastic (6% chrysotile) on downspout connections;
§ Residual flashing mastic (5% chrysotile) on the roof; and, § Brown/gold stair tread mastic (2% chrysotile) on the stairwells to the organ loft.
Lead-Based Paint
Nineteen (19) paint-chip samples were collected from various components and submitted for laboratory analysis. The results of this analysis are summarized in Table 2 in Appendix B. A copy of the laboratory data report and chain of custody form is included in Appendix C. Lead was detected in eighteen (18) of the samples collected. Nine of the eighteen samples were analyzed to be above 0.5% by weight; therefore, these paints are considered to be lead-based paint by the EPA definition.
February 25, 2021 ■ Terracon Project No. 86207201
Responsive ■ Resourceful ■ Reliable ii
Paints exceeding 0.5% by weight are summarized below.
§ White paint on metal roof caps in the bell tower;
§ White paint on wooden windowsills in the Protestant Chapel;
§ Teal paint on brick walls in the basement;
§ White paint on wooden door to the crawlspace;
§ White paint on wooden door frame to the crawlspace;
§ White paint on the wooden exterior handrails;
§ White paint on wooden roof framing;
§ White paint on wooden window frames on the bell tower; and § White paint on wooden roof framing.
In addition to the above listed painted components, lead paint was identified and reported in the report titled Project 621-05-115 conducted by E. Roberts Alley and Associates, Inc. and dated January 27, 2006. These additional paints are identified as being on all interior wooden door and window components as well any exterior wooden components.
Responsive ■ Resourceful ■ Reliable 1
ASBESTOS AND LEAD-BASED PAINT SURVEY REPORT
VAMC MOUNTAIN HOME – BUILDING 13 CHAPEL
LAMONT STREET AND VETERANS WAY
JOHNSON CITY, TENNESSEE
Project No. 86207201
1.0 INTRODUCTION
Terracon conducted an asbestos survey at VAMC Mountain Home – Building 13 Chapel at Lamont Street and Veterans Way in Johnson City, Tennessee. The survey was conducted on January 12 and 13, 2021 in general accordance with the terms of our Proposal No. P86207201 dated September 23, 2020. It is Terracon’s understanding that this survey was requested due to the proposed renovations and repairs scheduled for the structure. EPA regulation 40 CFR 61, Subpart M, National Emission Standards for Hazardous Air Pollutants (NESHAP), prohibits the release of asbestos fibers to the atmosphere during renovation/demolition activities. NESHAP requires that potentially regulated asbestos-containing materials (ACM) be identified, classified and quantified prior to planned disturbances or demolition activities.
Suspect ACM was sampled in general accordance with the sampling protocols outlined in EPA Regulation 40 CFR 763 Subpart E763.86 (Asbestos Hazard Emergency Response Act, AHERA).
Building components were surveyed and homogeneous areas of suspect ACM were visually identified and documented. Although reasonable effort was made to survey accessible suspect materials, additional suspect but un-sampled materials could be located in walls, in voids or in other concealed areas. Samples were delivered to an accredited laboratory for analysis by Polarized Light Microscopy (PLM).
Terracon also collected paint chip samples of selected components. Results from the paint chip analyses may be utilized when evaluating potential worker exposure scenarios for Occupational Safety and Health Administration (OSHA) compliance (29 CFR 1926.62).
Prior to mobilizing to the site, Terracon was provided with asbestos survey reports prepared by E.
Roberts Alley & Associates, Inc. (January 2006) and EFI Global (January 2010). Those reports were reviewed and the findings incorporated into our survey. Copies of these survey reports are provided in Appendix F.
February 25, 2021 ■ Terracon Project No. 86207201
Responsive ■ Resourceful ■ Reliable 2
2.0 BUILDING DESCRIPTION
The chapel (Building 13) is a two-story building covering approximately 6,875 square feet, with a basement. The building is constructed with a heavy brick veneer with interior wood framing atop a brick foundation. The building is split into two separate chapel areas (Protestant and Catholic), with organ lofts and a bell tower over a basement/crawlspace. Interior flooring is finished with predominantly hardwood, floor tile and mastic, stair treads and mastic, and residual carpet mastic.
Interior walls are mainly plaster over wooden lathe with limited gypsum board walls in the rear of the Catholic chapel. Ceilings are open to the rafters in the chapels with a few areas of plaster ceiling or drop-in cellulose ceiling tiles. Piping where observed was insulated with either fiberglass with mastic or foam rubber. A limited area of suspect thermal system insulation was noted on piping and the floor of a closet under the basement stairs. Several commercial heating, ventilation, and air conditioning (HVAC) units were observed in the crawlspaces. HVAC ductwork was metal or flexible plastic with fiberglass wrapped over it and suspect mastic on the seams.
Suspect caulking was observed in the interior and exterior of the building on windows, doors, and mortar lines. Roofing on the building was mainly slate over felt paper, with a small area of a rubberized membrane over plywood adjacent to the bell tower.
The crawlspace area underneath the Protestant chapel was not assessed as this space was labeled as a confined space and, therefore, Terracon did not attempt to access this area as part of our survey. Based upon limited cursory observations from the crawl space door the interior of the crawlspace appeared similar to the remaining crawlspace areas.
3.0 ASBESTOS SURVEY
The asbestos survey was conducted by Mr. Stephen N. Ellis a trained and TDEC-accredited asbestos building inspector (License No. A-I-59148-59469). A copy of Mr. Ellis’ accreditation is provided in Appendix E. The survey was conducted in general accordance with the protocols established by EPA regulation 40 CFR 763, the Asbestos Hazard Emergency Response Act (AHERA). A summary of the field activities is described below.
3.1 Regulatory Overview
The asbestos NESHAP (40 CFR Part 61, Subpart M) regulates asbestos fiber emissions and asbestos waste disposal practices. It also requires the identification and classification of existing building materials prior to demolition or renovation activity. Under NESHAP, asbestos-containing building materials are classified as either friable, Category I non-friable or Category II non-friable ACM. Friable materials are those that, when dry, may be crumbled, pulverized or reduced to powder by hand pressure. Category I non-friable ACM includes packing materials, gaskets, resilient floor coverings and asphalt roofing products containing more than 1 percent (%) asbestos.
Category II non-friable ACM are non-friable materials other than Category I materials that contain more than 1% asbestos.
February 25, 2021 ■ Terracon Project No. 86207201
Responsive ■ Resourceful ■ Reliable 3
Regulated Asbestos-Containing Materials are (a) friable asbestos material, (b) Category I non-friable ACM that has become friable, (c) Category I non-friable ACM that will be or has been subjected to sanding, grinding, cutting or abrading, or (d) Category II non-friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder by the forces expected to act on the material during demolition or renovation operations. RACM must be removed prior to renovation or demolition activities.
The Occupational Safety and Health Administration (OSHA) Asbestos Standard for Construction Industry (29 CFR 1926.1101) regulates workplace exposure to asbestos. The OSHA standard requires that employee exposure to airborne asbestos fibers be maintained below 0.1 asbestos fibers per cubic centimeter of air (0.1 f/cc). The OSHA standard classifies construction and maintenance activities, which could disturb ACM, and specifies work practices and precautions which employers must follow when engaging in each class of regulated work. A full copy of the OSHA asbestos standard for general industry may be found at OSHA’s website (www.osha.gov) and should be referenced for specific information.
3.2 Previous Reports Review
Terracon additionally reviewed previous reports conducted by E. Roberts Alley & Associates, Inc.
(January 2006) and EFI Global (January 2010). Upon review of these reports brown floor tile, gray/green floor tile, stair tread mastic, and roofing (assumed) were reported as being asbestos-containing materials.
During our assessment of the building it appeared that the brown and grey/green floor tile materials had been abated from their substrate. The stair tread materials appear to still be place and in good condition. Roofing felt was found during our assessment and was sampled, with results showing that these materials did not contain asbestos.
3.3 Visual Assessment
Our survey activities began with visual observation of the interior and exterior of the building to identify apparent homogeneous areas of suspect ACM. A homogeneous area consists of building materials, which appear similar throughout in terms of color, texture and date of application.
Building materials which were not identified as concrete, glass, wood, masonry, metal or rubber were considered suspect ACM.
Terracon lifted floor coverings, where possible, and did not observe additional flooring layers unless specifically mentioned herein; however, as Terracon could not assess beneath all floor coverings in all areas, there may be isolated areas of additional suspect material present beneath existing flooring.
http://www.osha.gov/
February 25, 2021 ■ Terracon Project No. 86207201
Responsive ■ Resourceful ■ Reliable 4
3.4 Physical Assessment
A physical assessment of each homogeneous area of suspect ACM was conducted to assess the friability and condition of the materials. A friable material is defined by the EPA as a material, which can be crumbled, pulverized or reduced to powder by hand pressure when dry. Friability was assessed by physically touching suspect materials.
3.5 Sample Collection
Based on the results of the visual assessment, bulk samples of suspect ACM were collected in general accordance with AHERA sample collection protocols. Random samples of suspect materials were collected in each homogeneous area. Bulk samples were collected using wet methods as applicable to reduce the potential for fiber release. Samples were placed in sealable containers and labeled with unique sample numbers using an indelible marker. The selection of sample locations and frequency of sampling was based on Terracon’s observations and the assumption that like materials in the same area are homogeneous in content. Sample locations are depicted on Figure 1 in Appendix A. A summary of the suspect ACM samples collected during the survey is presented in Table 1 in Appendix B.
3.6 Sample Analysis
Bulk samples were submitted using chain-of-custody procedures to Scientific Analytical Institute, Inc. (SAI) of Greensboro, North Carolina. SAI is accredited under the National Voluntary Laboratory Accreditation Program NVLAP (No. 200664).
Asbestos analysis was performed by PLM with dispersion staining techniques per EPA EPA/600/R- 93/116. The percentage of asbestos, where applicable, was determined by microscopical visual estimation.
3.7 Findings
A total of sixty-four (64) bulk samples were collected from the interior and exterior of the building.
A general layout with sample locations is included as Figure 1 in Appendix A. Sample descriptions, locations, analytical results, classification and estimated quantities are summarized in Table 1 in Appendix B. Asbestos laboratory analytical reports are included in Appendix C and photographs are provided in Appendix E.
Asbestos was detected in concentrations of greater than one percent (1%) in the following materials:
§ TSI contaminated debris (40% chrysotile) in the closet under the basement stairs;
§ Silver duct mastic (2% chrysotile) on the intake duct work in the bell tower;
§ Door caulking (3% chrysotile) on the exterior doors;
February 25, 2021 ■ Terracon Project No. 86207201
Responsive ■ Resourceful ■ Reliable 5
§ Gray mortar joint caulking (2% chrysotile) on the exterior concrete sill blocks;
§ Black mastic (6% chrysotile) on downspout connections;
§ Residual flashing mastic (5% chrysotile) on the roof; and, § Brown/gold stair tread mastic (2% chrysotile) on the stairwells to the organ loft.
4.0 LEAD-BASED PAINT SURVEY
4.1 Regulatory Overview
For the purpose of the OSHA lead standard, lead includes metallic lead, inorganic lead compounds, and organic lead soaps. A synopsis of the OSHA regulations (29 CFR 1926.62) and the applicability are described below.
The OSHA Lead Standard for Construction (29 CFR 1926.62) applies to construction work where an employee may be occupationally exposed to lead. Work related to construction, alteration, or repair (including painting and decorating) is included. The lead-in-construction standard applies to any detectable concentration of lead in paint, as even small concentrations of lead can result in unacceptable employee exposures depending upon on the method of removal and other workplace conditions. Under this standard construction includes, but is not limited to, the following:
§ Demolition or salvage of structures where lead or materials containing lead are present;
§ Removal or encapsulation of materials containing lead;
§ New construction, alteration, repair, or renovation of structures, substrates, or portions containing lead, or materials containing lead;
§ Installation of products containing lead;
§ Lead contamination/emergency clean-up;
§ Transportation, disposal, storage, or containment of lead or materials containing lead on the site or location at which construction activities are performed; and, § Maintenance operations associated with construction activities described above.
4.2 Sampling and Analytical Protocol
The LBP sampling was conducted by collecting random paint chip samples to supplement findings to assist the demolition/abatement contractor with determining potential engineering controls or other means to insure OSHA compliance during demolition efforts.
The paint samples were collected down to the surface substrate so as to include underlying paint (if present) in the analysis. The random paint chip samples were selected based on current paint schemes and may not be inclusive of old paint systems covered with paneling, or existing painted systems. The paint chip samples were submitted to an ELLAP approved laboratory (SAI) for analysis of lead by flame atomic absorption spectroscopy EPA Method No. SW-846 3050B/7000B. Results are reported in percent (%) by weight.
February 25, 2021 ■ Terracon Project No. 86207201
Responsive ■ Resourceful ■ Reliable 6
4.3 Findings
Nineteen (19) paint-chip samples were collected from various components and submitted for laboratory analysis. The results of this analysis are summarized in Table 2 in Appendix B. A copy of the laboratory data report and chain of custody form is included in Appendix C. Lead was detected in eighteen (18) of the samples collected. Nine of the eighteen samples were analyzed to be above 0.5% by weight; therefore, these paints are considered to be lead-based paint by the EPA definition.
Paints exceeding 0.5% by weight are summarized below:
§ White paint on metal roof caps in the bell tower;
§ White paint on wooden windowsills in the Protestant Chapel;
§ Teal paint on brick walls in the basement;
§ White paint on wooden door to the crawlspace;
§ White paint on wooden door frame to the crawlspace;
§ White paint on the wooden exterior handrails;
§ White paint on wooden roof framing;
§ White paint on wooden window frames on the bell tower; and § White paint on wooden roof framing.
In addition to the above listed painted components, lead paint was identified and reported in the report titled Project 621-05-115 conducted by E. Roberts Alley and Associates, Inc. and dated January 27, 2006. These additional paints are identified as being on all interior wooden door and window components as well as exterior wooden components.
5.0 RECOMMENDATIONS
Asbestos A Tennessee-accredited asbestos abatement firm should be contracted to perform the asbestos-containing material removal prior to the renovation process. The following steps should be taken for the removal of the identified ACMs prior to renovations:
1. Notify (written) TDEC-DAPC officials of the impending abatement project at the following address:
State of Tennessee Department of Environment and Conservation Division of Air Pollution Control William R. Snodgrass Tennessee Tower 312 Rosa L. Parks Avenue, 15th Floor Nashville, Tennessee 37243-1531
February 25, 2021 ■ Terracon Project No. 86207201
Responsive ■ Resourceful ■ Reliable 7
2. Remove the materials from the building before any activity begins that would break up, dislodge, or similarly disturb the material. The ACMs must be manifested and disposed at a classified landfill (Tennessee) or a landfill that is certified to accept RACM and non-RACM materials (if disposed in other states).
It should be noted that suspect materials, other than those identified during the January 12 and 13, 2021, survey may exist within the structure. Should suspect materials other than those which were identified during this survey be uncovered prior to or during the upcoming project, those materials should be assumed to be asbestos-containing until sampling and analysis demonstrates otherwise. Federal, state and local regulations should be referred to in order to verify compliance before any actions are initiated on an ACM.
Lead Containing Paint Regulatory agencies, such as the US EPA and the Consumer Products Safety Commission (CPSC) have designated levels of lead in paint, below which they consider the paint to be non-lead containing. The missions of these agencies differ from OSHA's, and for that reason, OSHA cannot recognize these levels as safe under workplace situations. The OSHA lead-in-construction standard was intended to apply to detectable concentrations of lead in paint, as even small concentrations of lead can result in unacceptable employee exposures depending upon on the method of removal and other workplace conditions.
OSHA does not consider methods that rely solely on the analysis of bulk materials or surface content of lead (or other toxic material) to be acceptable for safely predicting employee exposure to airborne contaminants. Without air monitoring results or without the benefit of historical or objective data (including air sampling which clearly demonstrates that the employee cannot be exposed above the action level during any process, operation, or activity) the analysis of bulk or surface samples cannot be used to determine employee airborne exposure. A full copy of the OSHA lead standard for construction industry may be found at OSHA’s website (www.osha.gov) and should be referenced for specific information.
Building materials, equipment, and components identified in this report as being coated with lead-containing paint/primer should be properly evaluated to determine if the paint system should be abated by qualified and properly equipped personnel under the OSHA Lead Construction Standard, found at 29 CFR 1926.62. The condition of the paint systems and the demolition activities intended for them will dictate the proper course of action, in terms of whether abatement is necessary. Waste generated from any abatement activities, as well as other materials contaminated from the abatement activities, must also be evaluated in terms of the hazardous waste Toxicity Characteristic. It is not required to fully abate the lead paint from the substrate for disposal or recycling efforts; however, the deteriorated paint and disturbance of paint must be addressed in accordance with 29 CFR 1926.62 and disposed of properly, as discussed above.
http://www.osha.gov/
February 25, 2021 ■ Terracon Project No. 86207201
Responsive ■ Resourceful ■ Reliable 8
6.0 GENERAL COMMENTS
This survey was conducted in a manner consistent with the level of care and skill ordinarily exercised by members of the profession currently practicing under similar conditions in the same locale. The results, findings, conclusions and recommendations expressed in this report are based on conditions observed during our survey of the building. The information contained in this report is relevant to the date on which this survey was performed and may not be relied upon to represent conditions at a later date.
This report has been prepared on behalf of and exclusively for use by FFE, Inc. for specific application to their project as discussed. Terracon does not warrant the work of regulatory agencies, laboratories or other third parties supplying information, which may have been used in the preparation of this report (including information provided in historical survey reports provided for our review). No warranty, express or implied is made.
This report is not a bidding document. Contractors or consultants reviewing this report must draw their own conclusions regarding further investigation or remediation deemed necessary.
APPENDIX A
FIGURE
Figure
GKF 86207201
Drawn By: Scale:
VAMC Mountain Home
Building 13 - Chapel Lamont Street and Veterans Way
Johnson City, Tennessee
72 Pointe Circle Greenville, SC 29615
1/14/2021 PH. (864) 292-2901 FAX. (864) 292-6361
SNE N.T.S.
Checked By:
Building layout and sample locations are approximated. Base drawing provided by FFE, Inc.
Project Manager: Project No.
General Layout / Sample Locations
File Name:
GKF
Approved By: Date:
APPENDIX B
TABLES
A1 PLM
A2 PLM
A3 PLM
B1 PLM
B2 PLM
B3 PLM
C1 PLM
C2 PLM
C3 PLM
D1 PLM
D2 PLM
D3 PLM
E1 PLM
E2 PLM
E3 PLM
E4 PLM
E5 PLM
E6 PLM
E7 PLM
13 03A
## PLM
F1 PLM
F2 PLM
F3 PLM
G1 PLM
G2 PLM
G3 PLM
H1 PLM
H2 PLM
H3 PLM
I1 PLM
I2 NA
I3 NA
SF40% Chrysotile Closet Under Basement Stairs TSI Contaminated Debris I TSI Friable Significantly
Damaged
PSD 30
SF
NAD Vestibule Ceiling Tile, 2' X 4'
Birdwing and Dot Pattern H Miscellaneous Friable Good LPD 100 SF
NAD
Restrooms Behind Catholic
Chapel
Ceiling Tile, 2' X 4'
Birdwing and Dot Pattern G Miscellaneous Friable Damaged PD 300
SF
NAD Pipe Organs Fabric on the Pipe Organ
Bellows F Miscellaneous Friable Good LPD 20 SF
Base - NAD
Finish - NAD
Limited Surfacing - NAD
Throughout Interior Plaster E Surfacing Friable Damaged PD 6,000
SF
Drywall - NAD
Joint Compound - NAD
Restrooms behind Catholic
Chapel and Front Walls of the
Chapel
Drywall and Joint Compound D Miscellaneous /
Surfacing Friable Good LPD 850 SF
Floor Tile - NAD
Leveler/Mastic - NAD
Restrooms behind Catholic
Chapel
12" White Streaked Floor Tile and Gray Floor Leveler C Miscellaneous Non-Friable Good LPD 320
SF
NAD Protestant Chapel and Entry Way Yellow Carpet Mastic B Miscellaneous Non-Friable Good LPD 820 SF
NAD Chaplain and Vestry Area Residual Felt Paper A Miscellaneous Friable Damaged PD 90
TABLE 1
ASBESTOS RESULTS SAMPLE SUMMARY
LAMONT STREET AND VETERANS WAY
JOHNSON CITY, TENNESSEE
Sample
Number
Analysis
Method
Estimated
Quantity Sample Location
TERRACON PROJECT NO. 86207201
Sample Description Homogeneous
Area Classification
Current
Condition
Potential for
Disturbance
Friable /
Non-Friable Analytical Results
VAMC MOUNTAIN HOME - BUILDING 13 CHAPEL
TABLE 1
ASBESTOS RESULTS SAMPLE SUMMARY
LAMONT STREET AND VETERANS WAY
JOHNSON CITY, TENNESSEE
Sample
Number
Analysis
Method
Estimated
Quantity Sample Location
TERRACON PROJECT NO. 86207201
Sample Description Homogeneous
Area Classification
Current
Condition
Potential for
Disturbance
Friable /
Non-Friable Analytical Results
VAMC MOUNTAIN HOME - BUILDING 13 CHAPEL
J1 PLM
J2 PLM
J3 PLM
K1 PLM
K2 PLM
K3 PLM
L1 PLM
L2 PLM
L3 PLM
M1 PLM
M2 PLM
M3 PLM
N1 PLM
N2 NA
N3 NA
O1 PLM
O2 PLM
O3 PLM
P1 PLM
P2 NA
P3 NA
Q1 PLM
Q2 PLM
Q3 PLM
R1 PLM
R2 PLM
R3 PLM
S1 PLM
S2 PLM
S3 PLM
SF
3% Chrysotile Exterior Doors Caulking P Miscellaneous Friable Damaged PD 4 SF
Roof Flashing at Brick and
Copper Interface Residual Flashing Mastic S Miscellaneous
Category I
Non-Friable Good LPD 200 LF
NAD
NAD
NAD
NAD
2% Chrysotile
NAD
5% Chrysotile
Basement and Crawlspace
Basement
Intake Duct Work in
Bell Tower
Chapel Windows
2% Chrysotile Exterior Concrete Sill Blocks
6% Chrysotile Downspout Connections
SF
Gray Mortar Joint Caulking Q Miscellaneous Category II
Non-Friable Good LPD 50 SF
Black Mastic R Miscellaneous Category II
Non-Friable Good LPD 12
Silver Duct Mastic N Miscellaneous Friable Significantly
Damaged
PSD 20
Light Brown Duct Mastic O Miscellaneous Non-Friable Good LPD 150
SF
M Miscellaneous Non-Friable Good LPD 150 SFFelt Paper under Subflooring
Gray Interior Window Caulking L Miscellaneous Non-Friable Good LPD 20 SF
SFCloset under Basement Stairs Black Fabric Duct Elbow J Miscellaneous Friable
Basement and Crawlspace White Mastic on Pipe Ends K Miscellaneous Non-Friable Good LPD 100 SF
Good LPD 3
TABLE 1
ASBESTOS RESULTS SAMPLE SUMMARY
LAMONT STREET AND VETERANS WAY
JOHNSON CITY, TENNESSEE
Sample
Number
Analysis
Method
Estimated
Quantity Sample Location
TERRACON PROJECT NO. 86207201
Sample Description Homogeneous
Area Classification
Current
Condition
Potential for
Disturbance
Friable /
Non-Friable Analytical Results
VAMC MOUNTAIN HOME - BUILDING 13 CHAPEL
T1 PLM
T2 PLM
T3 PLM
Notes:
N/A N/A Brown/Gold Stair Tread Mastic 13A-12** Miscellaneous Category II
Non-Friable Good LPD 60 SF
Felt Paper under Slate T Miscellaneous Non-Friable Good LPD 6,875 SF
2% Chrysotile Stairwells to Organ Loft
NAD Slate Roof
NA - Not Analyzed
NAD - No Asbestos Detected
PLM - Polarized Light Microscopy
TEM - Transmission Electron Microscopy
PACM - Presumed Asbestos Containing Material
1) Quantities listed above are estimates to be used for inspection purposes only and should be field-verified for all other uses.
2) A general overview of the site is depicted on Figure 1.
** - Previously sampled and identified in the report Project 621-05-115 conducted by E. Roberts Alley & Associates, Inc. dated January 27, 2006
## - Sample 13 03A was collected as part of the survey in report Comprehensive Asbestos-Containing Materials Inspection conducted EFI Global dated January 2010.
LPD - Low potential for disturbance
PD - Potential for disturbance
PSD - Potential of significant disturbance
SF - square feet
LF - linear feet
CF - cubic feet
Sample ID
No.
Area Substrate Component Color
Lead
Concentration
PC-1 BellTower Metal Roof Cap White 17.0
PC-2 Chaplain's Office Plaster Wall White 0.160
PC-3 Chaplain's Office Plaster Ceiling White 0.150
PC-4 Protestant Chapel Wood Door Frame Tan <0.0075
PC-5 Protestant Chapel Plaster Wall White 0.130
PC-6 Catholic Chapel Wood Door White 0.170
PC-7 Catholic Chapel Wood Door Frame White 0.230
PC-8 Entryway Wood Door Tan 0.110
PC-9 Vestibule Wood Newel Post Tan 0.077
PC-10 Vestibule Wood Stair Tread Gray 0.240
PC-11 Proestant Chapel Wood Windowsill White 0.86
PC-12 Basement Brick Wall Teal 2.2
PC-13 Basement Wood Floor Joist Teal 0.150
PC-14 Crawlspace Wood Door White 19
PC-15 Crawlspace Wood Door Frame White 1.4
PC-16 Exterior Wood Handrail White 27
PC-17 Exterior Wood Roof Framing White 19
PC-18 Exterior Bell Tower Wood Window Frame White 32
PC-19 Exterior Wood Roof Framing White 4.9
Notes:
1) Values above the analytical method detection limit are indicated in bold type.
2) Values equal to or greater than 0.500 percent are bolded and shaded.
TABLE 2
LEAD IN PAINT SAMPLE SUMMARY (PAINT CHIP)
VAMC MOUNTAIN HOME - BUILDING 13 CHAPEL
JOHNSON CITY, TENNESSEE
TERRACON PROJECT NO. 86207201
LAMONT STREET AND VETERANS WAY
APPENDIX C
LABORATORY REPORTS
Bulk Asbestos Analysis By Polarized Light Microscopy
EPA Method: 600/R-93/116 and 40 CFR, Part 763, Subpart E, App.E
VAMC Bldg 13 Chapel 86207201Project:
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos Fibrous
Components Non-Fibrous Components
Attributes
Treatment
Stephen Ellis George Flores
Attn:Customer: Terracon 72 Pointe Circle Greenville, SC 29615
Analysis ID: 71958030_PLM
Date Reported: 1/21/2021
Date Received: 1/18/2021
Lab Order ID: 71958030
None Detected A1
Residual Felt Paper Black Fibrous Homogeneous
Teased, Dissolved71958030PLM_1
Cellulose Other 70% 30%
None Detected A2
Residual Felt Paper Black Fibrous Homogeneous
Teased, Dissolved71958030PLM_2
Cellulose Other 70% 30%
None Detected A3
Residual Felt Paper Black Fibrous Homogeneous
Teased, Dissolved71958030PLM_3
Cellulose Other 70% 30%
None Detected B1
Yellow Carpet Mastic mixed mastic
Brown, Yellow Non Fibrous Heterogeneous
Dissolved71958030PLM_4
Other 100%
None Detected B2
Yellow Carpet Mastic mixed mastic
Brown, Yellow Non Fibrous Heterogeneous
Dissolved71958030PLM_5
Other 100%
None Detected B3
Yellow Carpet Mastic mixed mastic
Brown, Yellow Non Fibrous Heterogeneous
Dissolved71958030PLM_6
Other 100%
None Detected C1 - A
White Floor Tile and Gray Leveler floor tile
White Non Fibrous Homogeneous
Dissolved71958030PLM_7
Other 100%
None Detected C1 - B
White Floor Tile and Gray Leveler mastic/leveling compound
Gray, Yellow Non Fibrous Heterogeneous
Dissolved71958030PLM_65
Other 100%
Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogeneous soil samples be conducted by TEM for confirmation of “None Detected” by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program. Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.
Approved SignatoryAnalyst
Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
Byron Stroble (76)
P-F-002 r15 1/16/2021
EPA Method: 600/R-93/116 and 40 CFR, Part 763, Subpart E, App.E
VAMC Bldg 13 Chapel 86207201Project:
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos Fibrous
Components Non-Fibrous Components
Attributes
Treatment
Stephen Ellis George Flores
Attn:Customer: Terracon 72 Pointe Circle Greenville, SC 29615
Analysis ID: 71958030_PLM
Date Reported: 1/21/2021
Date Received: 1/18/2021
Lab Order ID: 71958030
None Detected C2 - A
White Floor Tile and Gray Leveler floor tile
White Non Fibrous Homogeneous
Dissolved71958030PLM_8
Other 100%
None Detected C2 - B
White Floor Tile and Gray Leveler mastic/leveling compound
Gray, Yellow Non Fibrous Heterogeneous
Dissolved71958030PLM_66
Other 100%
None Detected C3 - A
White Floor Tile and Gray Leveler floor tile
White Non Fibrous Homogeneous
Dissolved71958030PLM_9
Other 100%
None Detected C3 - B
White Floor Tile and Gray Leveler mastic/leveling compound
Gray, Yellow Non Fibrous Heterogeneous
Dissolved71958030PLM_67
Other 100%
None Detected D1
Drywall and Joint Compound drywall: none detect; joint compnd: none detect
Brown, White Non Fibrous Heterogeneous
Teased71958030PLM_10
Cellulose Other 10% 90%
None Detected D2
Drywall and Joint Compound drywall: none detect; joint compnd: none detect
White, Brown Non Fibrous Heterogeneous
Teased71958030PLM_11
Cellulose Other 10% 90%
None Detected D3
Drywall and Joint Compound drywall: none detect; joint compnd: none detect
Brown, White Non Fibrous Heterogeneous
Teased71958030PLM_12
Cellulose Other 10% 90%
None Detected E1 - A
Plaster surfacing
White Non Fibrous Homogeneous
Teased71958030PLM_13
Other 100%
Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogeneous soil samples be conducted by TEM for confirmation of “None Detected” by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program. Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.
Approved SignatoryAnalyst
Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
EPA Method: 600/R-93/116 and 40 CFR, Part 763, Subpart E, App.E
VAMC Bldg 13 Chapel 86207201Project:
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos Fibrous
Components Non-Fibrous Components
Attributes
Treatment
Stephen Ellis George Flores
Attn:Customer: Terracon 72 Pointe Circle Greenville, SC 29615
Analysis ID: 71958030_PLM
Date Reported: 1/21/2021
Date Received: 1/18/2021
Lab Order ID: 71958030
None Detected E1 - B
Plaster finish
White Non Fibrous Homogeneous
Crushed71958030PLM_68
Other 100%
None Detected E1 - C
Plaster base
Gray Non Fibrous Homogeneous
Crushed71958030PLM_69
Other 100%
None Detected E2 - A
Plaster surfacing
White Non Fibrous Homogeneous
Teased71958030PLM_14
Other 100%
None Detected E2 - B
Plaster finish
White Non Fibrous Homogeneous
Teased71958030PLM_70
Other 100%
None Detected E2 - C
Plaster base
Gray Non Fibrous Homogeneous
Crushed71958030PLM_71
Other 100%
None Detected E3 - A
Plaster finish
White Non Fibrous Homogeneous
Teased71958030PLM_15
Other 100%
None Detected E3 - B
Plaster base
Gray Non Fibrous Homogeneous
Crushed71958030PLM_72
Other 100%
None Detected E4 - A
Plaster finish
White Non Fibrous Homogeneous
Teased71958030PLM_16
Other 100%
Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogeneous soil samples be conducted by TEM for confirmation of “None Detected” by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program. Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.
Approved SignatoryAnalyst
Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
EPA Method: 600/R-93/116 and 40 CFR, Part 763, Subpart E, App.E
VAMC Bldg 13 Chapel 86207201Project:
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos Fibrous
Components Non-Fibrous Components
Attributes
Treatment
Stephen Ellis George Flores
Attn:Customer: Terracon 72 Pointe Circle Greenville, SC 29615
Analysis ID: 71958030_PLM
Date Reported: 1/21/2021
Date Received: 1/18/2021
Lab Order ID: 71958030
None Detected E4 - B
Plaster base
Gray Non Fibrous Homogeneous
Crushed71958030PLM_73
Other 100%
None Detected E5 - A
Plaster finish
White Non Fibrous Homogeneous
Teased71958030PLM_17
Other 100%
None Detected E5 - B
Plaster base
Gray Non Fibrous Homogeneous
Crushed71958030PLM_74
Other 100%
None Detected E6 - A
Plaster surfacing
White Non Fibrous Homogeneous
Teased71958030PLM_18
Other 100%
None Detected E6 - B
Plaster single layer
Gray Non Fibrous Homogeneous
Crushed71958030PLM_75
Other 100%
None Detected E7 - A
Plaster finish
White Non Fibrous Homogeneous
Crushed71958030PLM_19
Other 100%
None Detected E7 - B
Plaster base
Gray Non Fibrous Homogeneous
Crushed71958030PLM_76
Other 100%
None Detected F1
Pipe Bellow Fabric Beige Non Fibrous Heterogeneous
Ashed71958030PLM_20
Cellulose Other 40% 60%
Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogeneous soil samples be conducted by TEM for confirmation of “None Detected” by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program. Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.
Approved SignatoryAnalyst
Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
EPA Method: 600/R-93/116 and 40 CFR, Part 763, Subpart E, App.E
VAMC Bldg 13 Chapel 86207201Project:
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos Fibrous
Components Non-Fibrous Components
Attributes
Treatment
Stephen Ellis George Flores
Attn:Customer: Terracon 72 Pointe Circle Greenville, SC 29615
Analysis ID: 71958030_PLM
Date Reported: 1/21/2021
Date Received: 1/18/2021
Lab Order ID: 71958030
None Detected F2
Pipe Bellow Fabric Green Non Fibrous Heterogeneous
Ashed71958030PLM_21
Synthetic Fibers Cellulose
Other 30% 10%
60%
None Detected F3
Pipe Bellow Fabric Beige Fibrous Heterogeneous
Ashed71958030PLM_22
Cellulose Synthetic Fibers
Other 30% 20%
50%
None Detected G1
Ceiling Tile, Birdwing and Dot Pattern
Gray Fibrous Homogeneous
Teased, Ashed71958030PLM_23
Cellulose Mineral Wool
Other 45% 45%
10%
None Detected G2
Ceiling Tile, Birdwing and Dot Pattern
Gray Fibrous Homogeneous
Teased, Ashed71958030PLM_24
Cellulose Mineral Wool
Other 45% 45%
10%
None Detected G3
Ceiling Tile, Birdwing and Dot Pattern
Gray Fibrous Homogeneous
Teased, Ashed71958030PLM_25
Cellulose Mineral Wool
Other 45% 45%
10%
None Detected H1
Ceiling Tile, Pinhole and Dot Pattern
Gray, Pink Fibrous Homogeneous
Teased, Ashed71958030PLM_26
Cellulose Mineral Wool
Other 45% 45%
10%
None Detected H2
Ceiling Tile, Pinhole and Dot Pattern
Gray, Pink Fibrous Homogeneous
Teased, Ashed71958030PLM_27
Cellulose Mineral Wool
Other 45% 45%
10%
None Detected H3
Ceiling Tile, Pinhole and Dot Pattern
Gray, Pink Fibrous Homogeneous
Teased, Ashed71958030PLM_28
Cellulose Mineral Wool
Other 45% 45%
10%
Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogeneous soil samples be conducted by TEM for confirmation of “None Detected” by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program. Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.
Approved SignatoryAnalyst
Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
EPA Method: 600/R-93/116 and 40 CFR, Part 763, Subpart E, App.E
VAMC Bldg 13 Chapel 86207201Project:
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos Fibrous
Components Non-Fibrous Components
Attributes
Treatment
Stephen Ellis George Flores
Attn:Customer: Terracon 72 Pointe Circle Greenville, SC 29615
Analysis ID: 71958030_PLM
Date Reported: 1/21/2021
Date Received: 1/18/2021
Lab Order ID: 71958030
40% Chrysotile
I1 TSI Debris
Gray Fibrous Homogeneous
Teased71958030PLM_29
Cellulose Other 20% 40%
Not Analyzed I2
TSI Debris
71958030PLM_30
Not Analyzed I3
TSI Debris
71958030PLM_31
None Detected J1
Fabric Duct Elbow Black, Beige Fibrous Heterogeneous
Teased, Dissolved71958030PLM_32
Cellulose Other 60% 40%
None Detected J2
Fabric Duct Elbow Black, Beige Fibrous Heterogeneous
Teased, Dissolved71958030PLM_33
Cellulose Other 60% 40%
None Detected J3
Fabric Duct Elbow Black, Beige Fibrous Heterogeneous
Teased, Dissolved71958030PLM_34
Cellulose Other 60% 40%
None Detected K1
White Mastic on Pipe Ends Beige Non Fibrous Homogeneous
Dissolved71958030PLM_35
Wollastonite Other 10% 90%
None Detected K2
White Mastic on Pipe Ends Beige Non Fibrous Homogeneous
Dissolved71958030PLM_36
Wollastonite Other 10% 90%
Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogeneous soil samples be conducted by TEM for confirmation of “None Detected” by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program. Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.
Approved SignatoryAnalyst
Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
EPA Method: 600/R-93/116 and 40 CFR, Part 763, Subpart E, App.E
VAMC Bldg 13 Chapel 86207201Project:
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos Fibrous
Components Non-Fibrous Components
Attributes
Treatment
Stephen Ellis George Flores
Attn:Customer: Terracon 72 Pointe Circle Greenville, SC 29615
Analysis ID: 71958030_PLM
Date Reported: 1/21/2021
Date Received: 1/18/2021
Lab Order ID: 71958030
None Detected K3
White Mastic on Pipe Ends Beige Non Fibrous Homogeneous
Dissolved71958030PLM_37
Wollastonite Other 10% 90%
None Detected L1
Gray Window Caulking Gray Non Fibrous Homogeneous
Ashed71958030PLM_38
Other 100%
None Detected L2
Gray Window Caulking Gray Non Fibrous Homogeneous
Ashed71958030PLM_39
Other 100%
None Detected L3
Gray Window Caulking Gray Non Fibrous Homogeneous
Ashed71958030PLM_40
Other 100%
None Detected M1
Felt Paper on Subflooring Black Fibrous Homogeneous
Teased, Dissolved71958030PLM_41
Cellulose Other 80% 20%
None Detected M2
Felt Paper on Subflooring Black Fibrous Homogeneous
Teased, Dissolved71958030PLM_42
Cellulose Other 80% 20%
None Detected M3
Felt Paper on Subflooring Black Fibrous Homogeneous
Teased, Dissolved71958030PLM_43
Cellulose Other 80% 20%
2% Chrysotile
N1 Silver Duct Mastic
Silver Non Fibrous Homogeneous
Dissolved71958030PLM_44
Other 98%
Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogeneous soil samples be conducted by TEM for confirmation of “None Detected” by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program. Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.
Approved SignatoryAnalyst
Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
EPA Method: 600/R-93/116 and 40 CFR, Part 763, Subpart E, App.E
VAMC Bldg 13 Chapel 86207201Project:
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos Fibrous
Components Non-Fibrous Components
Attributes
Treatment
Stephen Ellis George Flores
Attn:Customer: Terracon 72 Pointe Circle Greenville, SC 29615
Analysis ID: 71958030_PLM
Date Reported: 1/21/2021
Date Received: 1/18/2021
Lab Order ID: 71958030
Not Analyzed N2
Silver Duct Mastic
71958030PLM_45
Not Analyzed N3
Silver Duct Mastic
71958030PLM_46
None Detected O1
Lt Brown Duct Mastic Brown Non Fibrous Homogeneous
Dissolved71958030PLM_47
Other 100%
None Detected O2
Lt Brown Duct Mastic Brown Non Fibrous Homogeneous
Dissolved71958030PLM_48
Other 100%
None Detected O3
Lt Brown Duct Mastic Brown Non Fibrous Homogeneous
Dissolved71958030PLM_49
Other 100%
3% Chrysotile
P1 Exterior Door Caulking
Gray Non Fibrous Homogeneous
Ashed71958030PLM_50
Other 97%
Not Analyzed P2
Exterior Door Caulking
71958030PLM_51
Not Analyzed P3
Exterior Door Caulking
71958030PLM_52
Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogeneous soil samples be conducted by TEM for confirmation of “None Detected” by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program. Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.
Approved SignatoryAnalyst
Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
EPA Method: 600/R-93/116 and 40 CFR, Part 763, Subpart E, App.E
VAMC Bldg 13 Chapel 86207201Project:
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos Fibrous
Components Non-Fibrous Components
Attributes
Treatment
Stephen Ellis George Flores
Attn:Customer: Terracon 72 Pointe Circle Greenville, SC 29615
Analysis ID: 71958030_PLM
Date Reported: 1/21/2021
Date Received: 1/18/2021
Lab Order ID: 71958030
2% Chrysotile
Q1 Gray Mortar Joint Caulking
Gray Non Fibrous Homogeneous
Ashed71958030PLM_53
Other 98%
Not Analyzed Q2
Gray Mortar Joint Caulking
71958030PLM_54
Not Analyzed Q3
Gray Mortar Joint Caulking
71958030PLM_55
6% Chrysotile
R1 Downspout Mastic
Black Non Fibrous Homogeneous
Dissolved71958030PLM_56
Cellulose Other 14% 80%
Not Analyzed R2
Downspout Mastic
71958030PLM_57
Not Analyzed R3
Downspout Mastic
71958030PLM_58
5% Chrysotile
S1 Residual Flashing Mastic
Gray, Black Non Fibrous Homogeneous
Dissolved71958030PLM_59
Other 95%
Not Analyzed S2
Residual Flashing Mastic
71958030PLM_60
Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommend that analysis of floor tiles, vermiculite, and/or heterogeneous soil samples be conducted by TEM for confirmation of “None Detected” by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Analytical uncertainty available upon request. Scientific Analytical Institute participates in the NVLAP Proficiency Testing program. Unless otherwise noted blank sample correction was not performed. Estimated MDL is 0.1%.
Approved SignatoryAnalyst
Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
EPA Method: 600/R-93/116 and 40 CFR, Part 763, Subpart E, App.E
VAMC Bldg 13 Chapel 86207201Project:
Sample ID
Lab Sample ID
Description
Lab Notes Asbestos Fibrous
Components Non-Fibrous Components
Attributes
Treatment
Stephen Ellis George Flores
Attn:Customer: Terracon 72 Pointe Circle Greenville, SC 29615
Analysis ID: 71958030_PLM
Date Reported: 1/21/2021
Date Received: 1/18/2021
Lab Order ID: 71958030
Not Analyzed S3
Residual Flashing Mastic
71958030PLM_61
None Detected T1
Felt Paper under Slate…
This is the start of the file's text. The full file is on GovTribe.