Med Vac System - Penthouse Oil Lubricated duplex vacuum.pdf

PDF 159 KB Posted

Attached to
Z1DA--Upgrade Medical Gas & Communication System Design Build
Solicitation number
36C24426R0119
Issued by

About this file

This is a preventive maintenance inspection report for a Rietschle Duplex Medical Vacuum System (Model CHBD-341-243) at VA Medical Center Erie, located at 135 East 38th Street, Erie, Pennsylvania 16504. The inspection was conducted on December 11, 2024 (Job #622374, SO #622374) by technician RG/TP, with contact information provided for David Dombkowski (david.dombkowski@va.org, 814-860-2924).

The system comprises two pumps with high operating hours (76,698 and 76,811 hours respectively) and includes four motors with specifications detailed in the Motor Information Section, including voltage ratings (203-205V L1-L3), amperage readings (31.90-32.90 AMPS), frame size 284TC, 230V supply, 40 full load amps, 15 horsepower, and 1,165 RPM. The inspection assessment indicates that all major components are acceptable (A), including exhaust filters, ballast filters, inlet filters, coupling, motor lubrication, starter contacts, transformer condition, and panel components. Oil and oil filters for both pumps were marked as repaired (R) on 12/11/24. Thermal overload settings measured 48.00 AMPS for both units. Vacuum switch readings included lead vac switch at 18-23 inHG and lag switches at 16-21 inHG, with local lag alarm audible and visual indicators functioning. No deficiencies were identified. The maintenance work performed included changing oil in both pumps, cleaning and blowing out coolers, and flushing oil from coolers and exhaust box sumps. The technician noted that pumps are well-maintained with acceptable oil levels and clarity despite high operating hours. The recommendation is to maintain preventive maintenance frequency. Five units of OEM Synthetic Oil (Part Number R590) from customer stock were used during the service.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Facility Job # 622374

Address SO # 622374

Trip # 1

Contact Year 2024

Email Date 12/11/24

Phone Tech RG/TP

A A

A A

A A

A A

R 12/11/24 R 12/11/24

A A

A A

A A

18-23 inHG

16-21 inHG Audible Yes inHG Visual Yes inHG

90.20% 1.15 15 RPM 1,165

284TC 230 40Frame Size Voltage Full Load Amps

Efficiency Service Factor Horse Power

Volts L2 to L3

Volts L1 to L3

Motor #1 Motor # 2 Motor # 3 Motor #4

32.90 AMPS

32.90 AMPS

32.70 AMPS

31.90 AMPS

32.10 AMPS

32.90 AMPS

Motor Information Section

Volts L1 to L2

48.00 AMPS

Lag 1 Vac Switch

Lag 2 Vac Switch

48.00 AMPS

A

A

A

Thermal Overload Settings

Transformer Condition

Panel Lamps

Panel Relays

Lead Vac Switch

Lag 3 Vac Switch

LEGEND

Customer Information

High Temp Shutdown

Coupling

Motor Greased

Starter Contacts

814-860-2924

Exhaust Filters

Ballast Filters

Inlet Filters

Oil and Oil Filters

Discharge Temperature

Exhaust Drip Leg

137°F

Model #

Serial #

Run Hours

CLFH/EH341(12)100923-1200

1742146 (96)

76,698

74°FRoom Temperature

Job Information

Pump # #1 #2 #3 #4

Customer System #

Rietschle Duplex Medical Vacuum

CHBD-341-243 SYSTEM

3000496097

None

Penthouse 8th floor (7th fl up stairs)

None

System Description

System Model #

System Serial #

Manufacture Date

System Location

System Information

VA Medical Center Erie

135 East 38th Street

Erie,PA 16504

David Dombkowski david.dombkowski@va.org

A = Acceptable

U = Unacceptable

R = Repaired

NR = Needs Replaced

NA = Not Applicable

Local Lag Alarm

141°F

CLFH/EH341(12)100923-1200

1735925 (96)

76,811

Quantity

Part Number Part Description

R590 OEM SYNTHETIC OIL CUSTOMER STOCK

Maintain PM Frequency

Recommendations

Comments

Parts Used

Deficiencies

None

Change oil both pumps, clean and blow out coolers, flush oil out of coolers and exhaust box sumps 1,2.

Foam Clean Coolers

Pumps have high hours-oil levels and clarity okay well maintained