Med Air System - Dental duplex Reciprocating.pdf

PDF 162 KB Posted

Attached to
Z1DA--Upgrade Medical Gas & Communication System Design Build
Solicitation number
36C24426R0119
Issued by

About this file

This is a preventive maintenance service report for a dental air compressor system at the VA Medical Center in Erie, Pennsylvania. The document records the inspection and testing of a RAMVAC dental air duplex system (Model OSP25, Serial #4773030) performed on December 11, 2024, by technician RG/TP. The system, manufactured on July 1, 2019, is located in the dental mechanical room and operates two Gast OF1202 compressor units (Item #004822 each).

The inspection findings indicate that all major components evaluated—including discharge check valves, unloaders and solenoids, inlet filters, after cooler drain valves, rider and piston rings, and starter contacts—were rated as "Acceptable" across both pump units. Motor testing recorded voltage readings of 208V across all three phase combinations and amperage readings ranging from 9.30 to 9.70 AMPS across Motor #1 and Motor #2, with the system operating at 1,650 RPM. The CO monitor showed no manufacturer/model information available, and the dew point monitor similarly had no data recorded. The lead pressure switch was set to 80-100 psi with local lag alarm capability (audible and visual indicators). The report notes that the customer has installed an additional compressor system and is currently servicing dental units due to patient backlog. No parts were used during this service visit, and no specific deficiencies or recommendations were documented in the respective sections.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Facility Job # 622374

Address SO # 622374

Trip # 1

Contact Year 2024

Email Date 12/11/24

Phone Tech RG/TP

A A

A A

A A

A A

A A

A A

80-100 psi psi Audible psi Visual psi

RPM 1,650

Manuf/Model/SN: Manuf/Model/SN:

Gas Conc.= 20 PPM

Fail

Unit On Line (as found)

Unit On Line (as left)

Dryers

Pre Filters

Selector Switch

Lamps

Suction Pressure

Blow Down Valve

Auto Blow Down

Float Drain

Purge Select

Line Regulator

After Filters

Discharge Check Valve

Mufflers

Solenoids

Davvid Dombkowski

Gast Item#004822

Discharge Temperature

77°FRoom Temperature

OF1202

Gast Item#004822

Job Information

Pump # #1 #2 #3 #4

Customer System #

RAMVAC dental air duplex

OSP25

4773030

07/01/19

Dental Mechanical room

System Description

System Model #

System Serial # david.dombkowski@va.org

Manufacture Date

System Location

System Information

VA Medical Center Erie

Customer Information

135 East 38th Street

Erie,PA 16504

Lag 1 Pressure Switch

LEGEND

A = Acceptable

U = Unacceptable

R = Repaired

NR = Needs Replaced

High Temp Shutdown

Crankcase Filter

Rider and Piston Rings

Starter Contacts

814-860-2924

Discharge Check Valves

Unloaders and Solenoids

Inlet Filters

After Cooler Drain Valves

Model #

Serial #

Run Hours

OF1202

Lag 2 Pressure Switch

A

A

Thermal Overload Settings

Transformer Condition

Panel Lamps

Panel Relays

Lead Pressure Switch

Relief Valves

Horse Power

Volts L2 to L3

Volts L1 to L3

Motor #1 Motor # 2 Motor # 3 Motor #4

9.50 AMPS

9.40 AMPS

9.40 AMPS

9.30 AMPS

9.50 AMPS

9.70 AMPS

Reading after Cal

Dew Point Monitor

D.P. Reading (as found)

Measured D.P. (Medpipe)

Sensor Replaced ?

Test Gas Reading

Cal Performed ?

Sensor Replaced ?

CO Monitor

D.P. Reading (as left)

NA = Not Applicable

Local Lag Alarm

None None

A

Motor Information Section

Volts L1 to L2

Frame Size Voltage Full Load Amps

Lag 3 Pressure Switch

Efficiency Service Factor

Quantity

Parts Used

Deficiencies

Customer installed additional compressor system customer servicing units for dental due to patient backlog

Recommendations

Comments

Part Number Part Description