Med Gas Annual Inspection Report.pdf
PDF 3 MB Posted
- Solicitation number
- 36C24426R0119
About this file
This is an Annual Medical Gas Inspection Report for VA Medical Center Erie documenting the July 29, 2025 inspection of piped medical gas and vacuum systems performed by Medpipe Maintenance Corp. (Project #624943).
The inspection tested 269 outlets across seven gas types (oxygen, medical air, vacuum, nitrous oxide, nitrogen, WAGD/evacuation, and carbon dioxide) along with 20 zone valve boxes, 11 area alarm panels, 2 master alarms, and associated source equipment including one bulk liquid oxygen system, one medical vacuum pump system, and one medical air compressor system. Testing confirmed compliance with NFPA 99, The Joint Commission (TJC), CGA, and ASSE standards for pressure, flow, concentration, labeling, and gas purity. The report identified deficiencies requiring correction: three manifold systems (CO2, N2, N2O) have cylinder leads/pigtails from 2020 exceeding the manufacturer's five-year service recommendation (deficiency code S30); the medical air compressor's carbon monoxide monitor display is blank despite functional local and master alarms (code S20); the vacuum pump system lacks a master alarm signal for lag pump running (code S18); one oxygen zone shutoff valve gauge is defective (code V4); and eight gas outlet locations exhibit leakage or connector issues (codes O2 and O3). All area alarm panels and gas/piping purity tests passed without deficiencies. The facility is required to address these findings to maintain full compliance with applicable standards.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Annual Medical Gas Inspection Report
VA Medical Center Erie 135 East 38th Street
Erie, PA 16504
Contact: Ken Watkins
Inspection Performed On: July 29, 2025
Medpipe Project #: 624943 On-Site Medpipe Representative(s): Austin Conroy, Josh Jones
Performed by: Medpipe Maintenance Corp.
P.O. Box 541 Lawrence, PA 15055 Phone: (724) 745-1854 Fax: (724) 745-2184
Medpipe Maintenance Corp. P.O. Box 541 Lawrence, PA 15055 724-745 1854 Fax: 724-745-2184
Acknowledgment, Terms of Verification, and Limitation of Liability
The verification provided applies only to the equipment and systems listed on the attached log as of the actual date of the inspection and shall not apply in the event of any modification of any element of the equipment or system subsequent to the date of inspection. MEDPIPE MAINTENANCE CORP. shall not be liable for claims, demands, liabilities, costs, attorney fees or damages resulting from incorrect or incomplete information supplied to MEDPIPE MAINTENANCE CORP., pertaining to the new or existing equipment and systems upon which verification is requested. By accepting the verification offered at the completion of the inspection, the purchaser/customer acknowledges the foregoing statement of the scope and limitations of the verification and agrees to hold harmless, indemnify and defend MEDPIPE MAINTENANCE CORP. as well as those engaged by MEDPIPE MAINTENANCE CORP. in the performance of the inspection/work, and any successors, assigns, subsidiaries of each, from any and all claims, demands, liabilities, costs attorneys fees or legal actions of any kind brought by third parties, regardless of the basis upon which such claim, demand, alleged liability or legal action is asserted, including the alleged negligence of MEDPIPE MAINTENANCE
CORP.
Further, by accepting the verification offered herein, the purchaser/customer, agrees that UNDER NO
CIRCUMSTANCES SHALL MEDPIPE MAINTENANCE CORP., ITS AGENTS, SUBCONTRACTORS,
SUPPLIERS AND THE EMPLOYEES OF EACH BE LIABLE FOR ANY SPECIAL, INCIDENTAL,
INDIRECT, OR CONSEQUENTIAL DAMAGES, (OR EQUIVALENTS THEREOF NO MATTER HOW
CLAIMED, COMPUTED OR CHARACTERIZED) ARISING OUT OF OR IN CONNECTION WITH THIS
VERIFICATION, ITS PERFORMANCE OR ALLEGED BREACH OF PERFORMANCE BY MEDPIPE
MAINTENANCE CORP. REGARDLESS OF WHETHER ANY SUCH LIABILITY SHALL BE CLAIMED IN
CONTRACT, EQUITY, TORT (INCLUDING NEGLIGENCE) OR OTHERWISE.
By way of example of the foregoing limitation of liability, but without limiting in any manner its scope or application, MEDPIPE MAINTENANCE CORP. shall not be liable for all or any part of the following no matter how claimed, computed, or characterized; loss of profit or revenue, loss of return on investment, cost of capital, loss of operating time or production, loss or reduction of use or value of any facilities (including existing facilities) or any portions of facilities, expense of replacement products or power, or increased costs of operations or maintenance. The limitation of liability contained in this Article shall be effective without regard to MEDPIPE MAINTENANCE CORP.’s performance, or failure or delay of performance or under any other term or condition of this verification and shall not be affected by any alleged oral agreement or other writing, including those contained in any Warranty or alleged warranty.
VA Medical Center Erie 2025 Annual Medical Gas & Vacuum System Inspection
Medpipe Maintenance Corp. P.O. Box 541 Lawrence, PA 15055 724-745 1854 Fax: 724-745-2184
Executive Summary Survey and testing of the piped medical gas and vacuum systems was conducted as part of the facility preventive maintenance program and to verify compliance with applicable regulations. This inspection is in conformity with NFPA 99, sections 5.1.14 & 5.1.15 and TJC Standard EC.02.05.09, which states:
“…the organization inspects, tests, and maintains critical components of piped medical gas systems, including master signal panels, area alarms, automatic pressure switches, shutoff valves, flexible connectors, and outlets.”
Tested systems and components are in compliance with NFPA, TJC, CGA, ASSE and other applicable agencies unless they are listed in the Deficiency Tables. Compliance is based primarily on the National Fire Protection Association document NFPA 99, Health Care Facilities Code, with specific reference to Chapter 5, Gas and Vacuum Systems. Complete Master Alarm testing results are presented in the table on page 7.
This report contains several sections. The first section contains the Executive Summary and Deficiency Summary Tables; the remaining sections contain complete listings of assets with test results, separated according to type.
Thank you for the opportunity to provide medical gas inspection services to your facility. Please contact us at your convenience with questions, comments or to order parts/service.
Larry Hall General Manager
Medpipe Maintenance Corp. P.O. Box 541 Lawrence, PA 15055 724-745 1854 Fax: 724-745-2184
Executive Summary (cont.)
Description of the testing program for this facility:
All area alarm panels, zone shutoff valves, accessible gas outlets/vacuum inlets, master alarms and central supply systems are tested each year.
Equipment tested/evaluated this visit:
Source Systems
Oxygen ✓ Vacuum ✓ Medical Air ✓ Nitrous Oxide ✓ Nitrogen ✓ WAGD (Evacuation) Carbon Dioxide ✓ HeliOx
Components Total
Bulk Liquid *Oxygen 1
Medical Vacuum System 1 Medical Air Compressor 1 Gas Manifold
*Carbon Dioxide 1 *Nitrogen 1 *Nitrous Oxide 1
Master Alarm 2 Area Alarm 11 Zone Valve Box 20 Outlet 269
*Carbon Dioxide 4 *Medical Air 31 *Medical Vacuum 114 *Nitrogen 2 *Nitrous Oxide 4 *Oxygen 110
*WAGD 4
Medpipe Maintenance Corp. P.O. Box 541 Lawrence, PA 15055 724-745 1854 Fax: 724-745-2184
Executive Summary (cont.)
Brief Summary of Test Procedures
Master Alarms-- Presence of required signals, location, labeling, function* Area Alarms-- Presence of required signals, location, labeling, function, set points, accuracy
Zone Shutoff Valves-- Presence of required valves, location, labeling, leakage, gauge accuracy Gas Outlets/Vacuum Inlets-- Pressure, flow, leakage, labeling, general condition
Gas/Piping Purity-- Particulates, moisture, contaminant gases Central Supply Systems-- NFPA 99 compliance
*The source equipment alarms (e.g. pressure switches, monitors) are triggered to verify function.
Line pressure switches are tested by pressure increase/decrease with a hand pump.
Acceptance Criteria for Medical Gas & Vacuum System Testing
Oxygen Medical Air Vacuum Nitrous Oxide Nitrogen WAGD Carbon Dioxide
Outlet/Inlet Testing
Pressure 50-55 psi 50-55 psi >12" Hg 50-55 psi 160-185 psi >12" Hg 50-55 psi Flow >3.5 scfm1 >3.5 scfm1 >3.0 scfm >3.5 scfm >5.0 scfm >3.0 scfm >3.5 scfm Concentration >99% 19.5-23.5% O2 n/a >99% >99% (<1% O2) n/a >99%
Alarm Testing
Alarm Setpoints +/- 20% +/- 20% 12" Hg +/- 20% +/- 20% 12" Hg +/- 20% of normal line of normal line of normal line of normal line of normal line pressure pressure pressure pressure pressure
Zone Valve Testing
Gauge Readings +/- 5% +/- 5% +/- 10% +/- 5% +/- 5% +/- 10% +/- 5% of normal line of normal line of normal line of normal line of normal line of normal line of normal line pressure pressure vacuum pressure pressure vacuum pressure
Labeling (colors)
Label/Text Green/white Yellow/black White/black Blue/white Black/white Purple/white Grey/white
Source Gas Contaminants/Purity
Particulates <1 mg <1 mg n/a <1 mg <1 mg n/a <1 mg Hydrocarbons n/a <25 ppm n/a n/a n/a n/a n/a Halocarbons n/a <2 ppm n/a <1 ppm n/a n/a n/a Carbon Monoxide <10 ppm <10 ppm n/a <10 ppm <10 ppm n/a <10 ppm Carbon Dioxide <300 ppm <500 ppm n/a <300 ppm n/a n/a n/a Dew Point n/a <2°C (35°F) n/a n/a n/a n/a n/a Visible Moisture None None n/a None None n/a None Odor None None n/a None None n/a None Oil None None n/a None None n/a None
1Transient flow of 6 scfm for 3 seconds in Critical Care Areas References: NFPA 99 (2024), USP, NF, CGA, ASSE, TJC
Medpipe Maintenance Corp. P.O. Box 541 Lawrence, PA 15055 724-745 1854 Fax: 724-745-2184
Executive Summary (cont.)
Deficiency Summary:
Master Alarms Deficiencies Identified. Refer to page 7 for complete master alarm testing results.
Area Alarms No Deficiencies Identified.
Zone Shutoff Valves Deficiencies Identified. Refer to the table on page 13.
Outlets/Inlets Deficiencies Identified. Refer to the table on page 14.
Gas/Piping Purity No Deficiencies Identified.
Central Supply Systems
Deficiencies identified for the Medical Air Compressor. Refer to the table on page 9.
Deficiencies identified for the Medical Vacuum Pump System. Refer to the table on page 10.
Deficiencies identified for the Manifold Systems. Refer to the table on page 11.
Medpipe Maintenance Corp. P.O. Box 541 Lawrence, PA 15055 724-745 1854 Fax: 724-745-2184
Master Alarms
Reference NFPA 99 2024 sections 5.1.9.1, 5.1.9.2
Codes:
P Pass
NP1 Signal Not Present, but the equipment local alarm/relay necessary to send the signal to the master alarms is present NP2 Signal Not Present, the equipment local alarm/relay necessary to send the signal to the master alarms is not present NT1 Signal Not Tested- possible risk of service interruption NT2 Signal Not Tested- sending device could not be triggered NT3 Signal Not Tested- sending device could not be located/accessed NT4 Signal Not Tested- system is not in service at this time NT5 Signal Not Tested – system is tested by Supplier
Comments:
Required Alarm Signals Panel Location Boiler Room Switchboard
Carbon Dioxide Gas Manifold (Manifold Room) Main Line Pressure High P P Main Line Pressure Low P P Changeover to Secondary P P Medical Air Compressor System (Mech Room BW035) Main Line Pressure High P P Main Line Pressure Low P P Lag Compressor Running P P Dew Point High P P Carbon Monoxide High P P Nitrogen Manifold (G) (Manifold Room) Main Line Pressure High P P Main Line Pressure Low P P Changeover to Secondary P P Nitrous Oxide Manifold (G) (Manifold Room) Main Line Pressure High P P Main Line Pressure Low P P Changeover to Secondary P P Oxygen Bulk Liquid System (Outdoor Bulk Pad) Main Liquid Level Low NT5 NT5 Reserve In Use NT5 NT5 Reserve Pressure Low NT5 NT5 Main Line Pressure High P P Main Line Pressure Low P P Vacuum Pump System (Mech Room PH) Lag Pump Running NP1 NP1 Vacuum Low P P
Medpipe Maintenance Corp. P.O. Box 541 Lawrence, PA 15055 724-745 1854 Fax: 724-745-2184
Deficiency Summary
Central Supply Systems – Bulk Liquid
Comments/Further Explanations:
System Type Codes O- Oxygen N2O- Nitrous Oxide N2- Nitrogen CO2- Carbon Dioxide
Deficiency Codes S1 Site not compliant (2 exits, bollards, lighting, signage) S12 Main line pressure gauge not present/accurate, location S2 Site condition issue (pad, fence, debris, foliage, icing) S13 Emergency O2 connection not present/correctly configured S3 Reserve supply not present/correctly configured S14 Alarms/switches not connected to master alarm panels S4 Piping not compliant (materials, protection, painted) S15 System main line pressure not within NFPA required range S5 System does not have all required alarms/sending devices S16 Leakage detected (see Comments section below for location) S6 Line pressure regulation not duplexed or bypass-able S17 Labeling not present/compliant S7 Pressure relief valves not present/functional, location, type S18 Demand check valves for pressure switch/gauge not present S8 Source shutoff valve not present, location, type S19 Cylinder lead (pigtails) not compliant (materials/expired) S9 Check valves not present/functional, location, type S20 See Comments section below S10 Main line valve not present, location, type S21 Emergency O2 connection box not locked/secured S11 Main line pressure switch not present/functional, location S22 Vessels/cylinders not properly secured/chained
Reference NFPA 99 2024 section 5.1.3.10
System Deficiency Codes Corrections Location Type Action Taken Date
No Deficiencies Identified.
Medpipe Maintenance Corp. P.O. Box 541 Lawrence, PA 15055 724-745 1854 Fax: 724-745-2184
Deficiency Summary
Central Supply Systems – Medical Air Compressors
Comments/Further Explanations:
Deficiency Codes S1 System not dedicated to human respiration S19 Dew Point monitor not present/functional, location S2 Intake location/configuration incorrect S20 CO monitor not present/functional, location S3 System not oil free S21 Source supply shutoff valve not present, location S4 Compressors not duplexed S22 Main line pressure switch not present/functional, location S5 Isolation, check or relief valves not present S23 Main line pressure gauge not present/functional, location S6 Flexible connectors not present S24 Lead/Lag pressure settings incorrect S7 Compressor alternation is not automatic S25 Lead or lag compressor operation incorrect S8 System not connected to emergency power circuits S26 System main line pressure incorrect S9 Local receiver flooded alarm not present/functional S27 Dew Point above 35F (2C) S10 Local separator(s) flooded alarm not present/functional S28 Alarms/sensors not connected to master alarm panels S11 Local lag compressor alarm not present/functional S29 Leakage detected S12 Local high air temperature alarm not present/functional S30 Labeling incorrect S13 Receiver – no relief valve, auto drain, sight glass, or gauge S31 Demand check valves for pressure switch/gauge not present S14 Receiver three-valve bypass, manual drain not present S32 Dryer auto-drain not present S15 Dryers, filters, or aftercoolers not present/functional S33 Sample port not present, location S16 Dryers, filters, or aftercoolers not duplexed/bypassable S34 Other, see worksheets for further detail S17 Line pressure regulation not duplexed/bypassable S35 See Comments section below S18 Line pressure relief valve not present/incorrect location, type
Reference NFPA 99 2024 section 5.1.3.6
System Deficiency Codes Corrections Location Action Taken Date
Mech Room BW035 S20
Mech Room BW035 S20- Carbon Monoxide monitor display is blank. (Note: Local and Master CO High alarms rang when tested)
Medpipe Maintenance Corp. P.O. Box 541 Lawrence, PA 15055 724-745 1854 Fax: 724-745-2184
Deficiency Summary
Central Supply Systems – Vacuum Pumps
Comments/Further Explanations:
System Type Codes MV- Medical Vacuum WAGD – Waste Anesthetic Gas Disposal
Deficiency Codes S1 Discharge location/configuration incorrect S13 Lead or lag pump operation incorrect S2 Pumps not duplexed S14 Lab Vacuum – no separate line, valve and/or trap S3 Isolation or check valves not present S15 System main line Vacuum level incorrect S4 Flexible couplings not present S16 Leakage detected S5 Pump alternation not automatic S17 Labeling incorrect S6 System not connected to emergency power circuits S18 Alarms/switches not connected to master alarm panels S7 Receiver bypass and/or drain not present S19 Demand check valves for vacuum switch/gauge not present S8 Local lag pump running alarm not present/functional S20 Other, see worksheets for further detail S9 Source supply shutoff valve not present, location S21 See Comments section below S10 Main line vacuum switch not present/functional, location S22 System location not compliant S11 Main line vacuum gauge not present/functional, location S23 Incorrect piping/valve materials S12 Lead/Lag pressure settings incorrect
Reference NFPA 99 2024 section 5.1.3.7
System Deficiency Codes Corrections Location Action Taken Date
Mech Room PH (MV) S18
Mech Room PH (MV) S18 - Lag Pump Running (Master).
Medpipe Maintenance Corp. P.O. Box 541 Lawrence, PA 15055 724-745 1854 Fax: 724-745-2184
Deficiency Summary
Central Supply Systems – Manifolds
Comments/Further Explanations:
System Type Codes O- Oxygen MA- Medical Air N2O- Nitrous Oxide N2- Nitrogen CO2- Carbon Dioxide H- HeliOx
Deficiency Codes S1 Storage configuration not compliant S17 Pressure relief not vented outside of building S2 Automatic changeover not present/functional S18 Alarms/switches not connected to master alarm panels S3 Normal/Changeover lights not present/burned out S19 System not connected to emergency power circuits S4 Minimum number of cylinders not present S20 System main line pressure incorrect S5 Cylinder lead check valves not present S21 Leakage detected S6 Header valves not present/functional S22 Labeling incorrect S7 Line pressure regulation not duplexed or bypassable S23 In use/reserve cylinders not secured by safety chains, brackets S8 Pressure relief valve(s) not present/incorrect location, type S24 Demand check valves for pressure switch/gauge not present S9 Source supply shutoff valve not present/incorrect location S25 Room ventilation not compliant S10 Main line pressure switch not present/functional, location S26 Electrical devices not >5 feet AFF or protected S11 Main line pressure gauge not present/functional, location S27 Other, see worksheets for further detail S12 Liquid system does not have a reserve supply S28 See Comments section below S13 Reserve supply incorrect size or type S29 Cylinder lead (pigtail) material not compliant S14 Emergency Reserve In Use pressure switch not present S30 Cylinder lead (pigtail) time in service > 5 year mfr recomm S15 Emergency Reserve Low pressure switch not present S31 Check valve on reserve header not present/location S16 Emergency O2 connection not present/incorrect configuration S32 Manifold line pressure reading inaccurate
Reference NFPA 99 2024 sections 5.1.3.5.(9,10,11)
System Deficiency Codes Corrections Location Type Action Taken Date
Manifold Room CO2 S30
Manifold Room N2 S30 Manifold Room N2O S30
CO2 (Manifold Room) S30- Pigtails 2020 (3x3).
N2 (Manifold Room) S30- Pigtails 2020 (2x2).
N2O (Manifold Room) S30- Pigtails 2020 (3x3).
Medpipe Maintenance Corp. P.O. Box 541 Lawrence, PA 15055 724-745 1854 Fax: 724-745-2184
Deficiency Summary
Alarm Panels
Comments/Further Explanations:
System Type Codes O- Oxygen MA- Medical Air MV- Medical Vacuum N2O- Nitrous Oxide N2- Nitrogen W- WAGD (Evacuation) CO2- Carbon Dioxide VW – Combined Vac/WAGD H - HeliOx
Deficiency Codes A1 Area monitored labeling not present, incorrect or unclear A10 Digital or analog pressure displays not accurate A2 Gas/Signal labeling not present, incorrect or incomplete A11 Panel/module malfunctioning A3 Audible indicator malfunctioning A12 Panel/module physically damaged A4 Normal (Green) indicator malfunctioning A13 Panel location non-compliant/undesirable A5 Abnormal (Red or Yellow) indicator malfunctioning A14 Panel not on emergency power circuits A6 Alarm did not activate when triggered A15 Required signals or panel not present A7 Alarm did not return to normal after cleared A16 Sensors in non-compliant location for area type A8 Test button sequence malfunctioning A17 No electrical power to panel A9 Set points incorrect A18 See Comments section below
Reference NFPA 99 2024 section 5.1.9.1 & 5.1.9.4
System Deficiency Codes Corrections
No Deficiencies Identified.
Medpipe Maintenance Corp. P.O. Box 541 Lawrence, PA 15055 724-745 1854 Fax: 724-745-2184
Deficiency Summary
Shutoff Valves
Comments/Further Explanations:
System Type Codes O- Oxygen MA- Medical Air MV- Medical Vacuum N2O- Nitrous Oxide N2- Nitrogen W- WAGD (Evacuation) CO2- Carbon Dioxide VW – Combined Vac/WAGD H - HeliOx
Deficiency Codes V1 Area controlled labeling not present, incorrect or unclear V8 Cover/frame damaged or missing V2 Gas labeling not present or incorrect V9 Valve location non-compliant/undesirable V3 Leakage detected V10 Valve configuration non-compliant V4 Gauge(s) defective V11 Valve type non-compliant V5 No gauge(s) present - port available V12 Valve not locked, latched, or in secure area as required V6 No gauge(s) present - no port available V13 No valve(s) present as required V7 Handle difficult to move V14 See Comments section below
Reference NFPA 99 2024 section 5.1.4
System Deficiency Codes Corrections
Floor 1-In Sterile Process Room O V4
Medpipe Maintenance Corp. P.O. Box 541 Lawrence, PA 15055 724-745 1854 Fax: 724-745-2184
Deficiency Summary
Outlets/Inlets
Reference NFPA 99 2024 section 5.1.5
System Type Codes O- Oxygen MA- Medical Air MV- Medical Vacuum N2O- Nitrous Oxide N2- Nitrogen W- WAGD (Evacuation) CO2- Carbon Dioxide H - HeliOx
Mounting Codes CE-Ceiling CB-Ceiling Boom CO - Console FC-Fixed Column FP-Floor Pedestal W-Wall
Legend 1 Difficult to insert / extract connector 6 Defective / missing parts 11 Incorrect labeling / color-coding 2 Leak with connector in 7 Patient using outlet / inlet 12 Visible water detected 3 Leak with connector out 8 Unable to test at this time 13 Latch cover missing / broken 4 Reduced flow / no flow 9 Facility’s connector broken 14 Ceiling outlets without hoses (#) 5 Abnormal pressure 10 Hoses need replacement 15 Contamination detected
Location Type Code Comments Corrections Floor:1-Bio Med MV 3 W#4 Floor:1-ER 2 O 2 CO#1 Floor:6-625J O 2 CO#2 Floor:5-519 O 2 W#2 Floor:5-520 O 2 W#2 Floor:5-521 O 2,3 W#1 Floor:5-522 O 2 W#1 Floor:5-531 O 2 W#1
Medpipe Maintenance Corp. P.O. Box 541 Lawrence, PA 15055 724-745 1854 Fax: 724-745-2184
Deficiency Summary
Gas/Piping Purity
Particulates
Outlets at random representative locations were tested to check particulate content.
Reference NFPA 99 2024 section 5.1.12.4.8
Contaminants
Tests were performed at the Source Equipment and at random outlet locations to check for contamination.
Reference NFPA 99 2024 section 5.1.12.4.8,12
Location Type Level Comments No Deficiencies Identified
Location Type Comments No Deficiencies Identified
Annual Medical Gas Inspection
COMPLETE MEDICAL GAS INSPECTION SERVICES
P.O. Box 541 Lawrence, PA 15055 Ph: (724) 745-1854 Fax: (724) 745-2184
Facility: VA Medical Center Erie
Project #: 624943
Manuf/Model: Amico Alert 2
Master Alarm - Boiler Room
Date Inspected: July 29, 2025
Labeling - P Test Button - P Green Light - P Red/Yellow Light - P Audible - P
Comments:Carbon Dioxide Gas Manifold (Manifold Room) - Main Line Pressure High Pass
Carbon Dioxide Gas Manifold (Manifold Room) - Main Line Pressure Low Pass
Carbon Dioxide Gas Manifold (Manifold Room) - Changeover to Secondary Pass
Medical Air Compressor System (Mech Room BW035) - Main Line Pressure High Pass
Medical Air Compressor System (Mech Room BW035) - Main Line Pressure Low Pass
Medical Air Compressor System (Mech Room BW035) - Lag Compressor Running Pass
Medical Air Compressor System (Mech Room BW035) - Dew Point High Pass
Medical Air Compressor System (Mech Room BW035) - Carbon Monoxide High Pass
Nitrogen Manifold (G) (Manifold Room) - Main Line Pressure High Pass
Nitrogen Manifold (G) (Manifold Room) - Main Line Pressure Low Pass
Nitrogen Manifold (G) (Manifold Room) - Changeover to Secondary Pass
Nitrous Oxide Manifold (G) (Manifold Room) - Main Line Pressure High Pass
Nitrous Oxide Manifold (G) (Manifold Room) - Main Line Pressure Low Pass
Nitrous Oxide Manifold (G) (Manifold Room) - Changeover to Secondary Pass
Oxygen Bulk Liquid System (Outdoor Bulk Pad) - Main Liquid Level Low NT5
Oxygen Bulk Liquid System (Outdoor Bulk Pad) - Reserve In Use NT5
Oxygen Bulk Liquid System (Outdoor Bulk Pad) - Reserve Pressure Low NT5
Oxygen Bulk Liquid System (Outdoor Bulk Pad) - Main Line Pressure High Pass
Oxygen Bulk Liquid System (Outdoor Bulk Pad) - Main Line Pressure Low Pass
Vacuum Pump System (Mech Room PH) - Lag Pump Running NP1
Vacuum Pump System (Mech Room PH) - Vacuum Low Pass
Codes
P - Pass NP1- Signal Not Present, but the equipment local alarm/relay necessary to send the signal to the master alarms is present
NP2 - Signal Not Present, the equipment local alarm/relay necessary to send the signal to the master alarms is not present
NT1 - Signal Not Tested- possible risk of service interruption
NT2 - Signal Not Tested- sending device could not be triggered
NT3 - Signal Not Tested- sending device could not be located/accessed
NT4 - Signal Not Tested- system is not in service at this time
NT5 - Signal Not Tested – system is tested by Supplier F - Fail
P.O. Box 541 Lawrence, PA 15055 Ph: (724) 745-1854 Fax: (724) 745-2184
Facility: VA Medical Center Erie
Project #: 624943
Manuf/Model: Amico Alert 2
Master Alarm - Switchboard
Date Inspected: July 29, 2025
Labeling - P Test Button - P Green Light - P Red/Yellow Light - P Audible - P
Comments:Carbon Dioxide Gas Manifold (Manifold Room) - Main Line Pressure High Pass
Carbon Dioxide Gas Manifold (Manifold Room) - Main Line Pressure Low Pass
Carbon Dioxide Gas Manifold (Manifold Room) - Changeover to Secondary Pass
Medical Air Compressor System (Mech Room BW035) - Main Line Pressure High Pass
Medical Air Compressor System (Mech Room BW035) - Main Line Pressure Low Pass
Medical Air Compressor System (Mech Room BW035) - Lag Compressor Running Pass
Medical Air Compressor System (Mech Room BW035) - Dew Point High Pass
Medical Air Compressor System (Mech Room BW035) - Carbon Monoxide High Pass
Nitrogen Manifold (G) (Manifold Room) - Main Line Pressure High Pass
Nitrogen Manifold (G) (Manifold Room) - Main Line Pressure Low Pass
Nitrogen Manifold (G) (Manifold Room) - Changeover to Secondary Pass
Nitrous Oxide Manifold (G) (Manifold Room) - Main Line Pressure High Pass
Nitrous Oxide Manifold (G) (Manifold Room) - Main Line Pressure Low Pass
Nitrous Oxide Manifold (G) (Manifold Room) - Changeover to Secondary Pass
Oxygen Bulk Liquid System (Outdoor Bulk Pad) - Main Liquid Level Low NT5
Oxygen Bulk Liquid System (Outdoor Bulk Pad) - Reserve In Use NT5
Oxygen Bulk Liquid System (Outdoor Bulk Pad) - Reserve Pressure Low NT5
Oxygen Bulk Liquid System (Outdoor Bulk Pad) - Main Line Pressure High Pass
Oxygen Bulk Liquid System (Outdoor Bulk Pad) - Main Line Pressure Low Pass
Vacuum Pump System (Mech Room PH) - Lag Pump Running NP1
Vacuum Pump System (Mech Room PH) - Vacuum Low Pass
Codes
P - Pass NP1- Signal Not Present, but the equipment local alarm/relay necessary to send the signal to the master alarms is present
NP2 - Signal Not Present, the equipment local alarm/relay necessary to send the signal to the master alarms is not present
NT1 - Signal Not Tested- possible risk of service interruption
NT2 - Signal Not Tested- sending device could not be triggered
NT3 - Signal Not Tested- sending device could not be located/accessed
NT4 - Signal Not Tested- system is not in service at this time
NT5 - Signal Not Tested – system is tested by Supplier F - Fail
P.O. Box 541 Lawrence, PA 15055 Ph: (724) 745-1854 Fax: (724) 745-2184
Facility: VA Medical Center Erie
Project #: 624943
Area Alarms
Date Inspected: July 29, 2025
Building: 1
Floor: 1
Location Outside Pulmonary
Area Monitored
Pulmonary/Secretary Primary Care
Manufacturer P-B
Model MEGA
Asset #: 1-AA-1-1 Result Pass
40 60
Def. Code(s)
High Set
Low Set
MA1
Reading
Gas
O1
Comments
Building: 1
Floor: 1
Location Blue Clinic Nurses Desk
Area Monitored
(Blue Clinic) Exam A-F
Manufacturer Amico
Model Alert 3
Asset #: 1-AA-1-2 Result Pass
12 30
Def. Code(s)
High Set
Low Set
MV1
Reading
Gas
O1
Comments
Building: 1
Floor: 1
Location ED Nurses Desk
Area Monitored
Emergency Department
Manufacturer Allied
Model DA2
Asset #: 1-AA-1-3 Result Pass
Def. Code(s)
High Set
Low Set
11.9
O1
MA1
Reading
Gas
MV1
Comments
A1 - Area monitored labeling not present, incorrect
A5 - Abnormal (Red or Yellow) indicator malfunctioning
A9 - Set points incorrect
A13 - Panel Location non-compliant/undesirable
A17 - No electrical power to panel
A2 - Gas/Signal labeling not present, incorrect or incomplete
A6 - Alarm did not activate when triggered
A10 - Digital or analog pressure displays not accurate
A14 - Panel not on emergency power circuits
A18 - See Comments
A3 - Audible indicator malfunctioning
A7 - Alarm did not return to normal after cleared
A11 - Panel/module malfunctioning
A15 - Required signals or panel not present
A4 - Normal (Green) indicator malfunctioning
A8 - Test button sequence malfunctioning
A12 - Panel/module physically damaged
A16 - Sensors in non-compliant location for area type
Deficiency Codes NT (Not Tested), NA (Not Applicable), NP (Not Present)
Gas Codes: O - Oxygen MA - Medical Air MV - Medical Vacuum N2O - Nitrous Oxide N2 - Nitrogen W - WAGD (Evacuation) CO2 - Carbon Dioxide VW - Vac/WAGD H - HeliOx
P.O. Box 541 Lawrence, PA 15055 Ph: (724) 745-1854 Fax: (724) 745-2184
Facility: VA Medical Center Erie
Project #: 624943
Area Alarms
Date Inspected: July 29, 2025
Building: 1
Floor: 1
Location Hallway Outside 1W224
Area Monitored
Xray 1W221, Sonography 1W222 & 1W223, CT 1W224
Manufacturer Amico
Model Alert 2
Asset #: 1-AA-1-4 Result Pass
12 30
Def. Code(s)
High Set
Low Set
MV1
Reading
Gas
O1
Comments
Building: 1
Floor: 1
Location Outside 1W221
Area Monitored
RFI 1 & 2
Manufacturer Amico
Model Alert 3
Asset #: 1-AA-1-5 Result Pass
12 30
Def. Code(s)
High Set
Low Set
MV1
Reading
Gas
O1
Comments
Building: 1
Floor: 2
Location Across from Pre Post 4 (Endo)
Area Monitored
Endo Rooms
Manufacturer Amico
Model Alert 3
Asset #: 1-AA-2-1 Result Pass
Def. Code(s)
High Set
Low Set
N2O1
O1
VW1
Reading
Gas
MA1
Comments
A1 - Area monitored labeling not present, incorrect
A5 - Abnormal (Red or Yellow) indicator malfunctioning
A9 - Set points incorrect
A13 - Panel Location non-compliant/undesirable
A17 - No electrical power to panel
A2 - Gas/Signal labeling not present, incorrect or incomplete
A6 - Alarm did not activate when triggered
A10 - Digital or analog pressure displays not accurate
A14 - Panel not on emergency power circuits
A18 - See Comments
A3 - Audible indicator malfunctioning
A7 - Alarm did not return to normal after cleared
A11 - Panel/module malfunctioning
A15 - Required signals or panel not present
A4 - Normal (Green) indicator malfunctioning
A8 - Test button sequence malfunctioning
A12 - Panel/module physically damaged
A16 - Sensors in non-compliant location for area type
Gas Codes: O - Oxygen MA - Medical Air MV - Medical Vacuum N2O - Nitrous Oxide N2 - Nitrogen W - WAGD (Evacuation) CO2 - Carbon Dioxide VW - Vac/WAGD H - HeliOx
P.O. Box 541 Lawrence, PA 15055 Ph: (724) 745-1854 Fax: (724) 745-2184
Facility: VA Medical Center Erie
Project #: 624943
Area Alarms
Date Inspected: July 29, 2025
Building: 1
Floor: 2
Location Across from Pre Post 4 (OR)
Area Monitored
OR Rooms
Manufacturer Amico
Model Alert 3
Asset #: 1-AA-2-2 Result Pass
Def. Code(s)
High Set
Low Set
MA1
VW1
N2O1
CO21
N21
Reading
Gas
O1
Comments
Building: 1
Floor: 2
Location Right of Pre Post 4
Area Monitored
PACU Rooms 1-3, Pre OP 1-7, Air Only in PACU 1-3
Manufacturer Amico
Model Alert 3
Asset #: 1-AA-2-3 Result Pass
Def. Code(s)
High Set
Low Set
MA1
MV1
Reading
Gas
O1
Comments
Building: 1
Floor: 3
Location Infusion Nurses Station
Area Monitored
Infusion Bays 1-9, Private Exam (Bay10)
Manufacturer Amico
Model Alert 3
Asset #: 1-AA-3-1 Result Pass
Def. Code(s)
High Set
Low Set
Reading
Gas
O1
Comments
A1 - Area monitored labeling not present, incorrect
A5 - Abnormal (Red or Yellow) indicator malfunctioning
A9 - Set points incorrect
A13 - Panel Location non-compliant/undesirable
A17 - No electrical power to panel
A2 - Gas/Signal labeling not present, incorrect or incomplete
A6 - Alarm did not activate when triggered
A10 - Digital or analog pressure displays not accurate
A14 - Panel not on emergency power circuits
A18 - See Comments
A3 - Audible indicator malfunctioning
A7 - Alarm did not return to normal after cleared
A11 - Panel/module malfunctioning
A15 - Required signals or panel not present
A4 - Normal (Green) indicator malfunctioning
A8 - Test button sequence malfunctioning
A12 - Panel/module physically damaged
A16 - Sensors in non-compliant location for area type
Gas Codes: O - Oxygen MA - Medical Air MV - Medical Vacuum N2O - Nitrous Oxide N2 - Nitrogen W - WAGD (Evacuation) CO2 - Carbon Dioxide VW - Vac/WAGD H - HeliOx
P.O. Box 541 Lawrence, PA 15055 Ph: (724) 745-1854 Fax: (724) 745-2184
Facility: VA Medical Center Erie
Project #: 624943
Area Alarms
Date Inspected: July 29, 2025
Building: 1
Floor: 6
Location Right of 625J
Area Monitored
625G, 625H, 625J, 625M
Manufacturer Amico
Model Alert 3
Asset #: 1-AA-6-1 Result Pass
40 60
Def. Code(s)
High Set
Low Set
O1
Reading
Gas
MV1
Comments
Building: 1
Floor: 6
Location Nurse Station (617-619...)
Area Monitored
617-619, 628-631
Manufacturer P-B
Model MEGA
Asset #: 1-AA-6-2 Result Pass
40 60
Def. Code(s)
High Set
Low Set
O1
Reading
Gas
MV1
Comments
A1 - Area monitored labeling not present, incorrect
A5 - Abnormal (Red or Yellow) indicator malfunctioning
A9 - Set points incorrect
A13 - Panel Location non-compliant/undesirable
A17 - No electrical power to panel
A2 - Gas/Signal labeling not present, incorrect or incomplete
A6 - Alarm did not activate when triggered
A10 - Digital or analog pressure displays not accurate
A14 - Panel not on emergency power circuits
A18 - See Comments
A3 - Audible indicator malfunctioning
A7 - Alarm did not return to normal after cleared
A11 - Panel/module malfunctioning
A15 - Required signals or panel not present
A4 - Normal (Green) indicator malfunctioning
A8 - Test button sequence malfunctioning
A12 - Panel/module physically damaged
A16 - Sensors in non-compliant location for area type
Gas Codes: O - Oxygen MA - Medical Air MV - Medical Vacuum N2O - Nitrous Oxide N2 - Nitrogen W - WAGD (Evacuation) CO2 - Carbon Dioxide VW - Vac/WAGD H - HeliOx
P.O. Box 541 Lawrence, PA 15055 Ph: (724) 745-1854 Fax: (724) 745-2184
Facility: VA Medical Center Erie
MP Project # 624943
Zone Shutoff Valves
Date Inspected: July 29, 2025
Building: 1
Floor: 1
Location Outside Pulmonary
Area Controlled
Pulmonary Lab / Secretary Primary Care
Manufacturer P-B
Asset #: 1-ZVB-1-1 Result Pass
Def. Code(s)
Comments
Gas O
MA
Pressure Reading
Building: 1
Floor: 1
Location Outside Blue Clinic
Area Controlled
Blue Clinic A-F (342,344,346,352,354,356)
Manufacturer Allied
Asset #: 1-ZVB-1-2 Result Pass
Def. Code(s)
Comments
Gas O
MV
Pressure Reading
Building: 1
Floor: 1
Location Outside Rad Clinic
Area Controlled
Red Clinic Exams 1-5
Manufacturer Amico
Asset #: 1-ZVB-1-3 Result Pass
Def. Code(s)
Comments
Gas O
MV
Pressure Reading
V1 - Area controlled labeling not present, incorrect
V5 - No gauge(s) present - port available
V9 - Valve location non-compliant/undesirable
V13 - No valve(s) present as required
V2 - Gas labeling not present or incorrect
V6 - No gauge(s) present - no port available
V10 - Valve configuration non-compliant
V14 - See Comments Section
V3 - Leakage detected
V7 - Handle difficult to move
V11 - Valve type non-compliant
V4 - Gauge(s) defective
V8 - Cover/Frame damaged or missing
V12 - Valve not locked, latched or in secure area as required
Deficiency Codes
Gas Codes: O - Oxygen MA - Medical Air MV - Medical Vacuum N2O - Nitrous Oxide N2 - Nitrogen W - WAGD (Evacuation) CO2 - Carbon Dioxide VW - Vac/WAGD H - HeliOx
NT (Not Tested), NA (Not Applicable), NP (Not Present)
P.O. Box 541 Lawrence, PA 15055 Ph: (724) 745-1854 Fax: (724) 745-2184
Facility: VA Medical Center Erie
MP Project # 624943
Zone Shutoff Valves
Date Inspected: July 29, 2025
Building: 1
Floor: 1
Location Left of ED 8
Area Controlled
Emergency Department
Manufacturer Allied
Asset #: 1-ZVB-1-4 Result Pass
Def. Code(s)
Comments
Gas O
MA
MV
Pressure Reading
Building: 1
Floor: 1
Location Outside CT
Area Controlled
CT 64 Slice
Manufacturer Amico
Asset #: 1-ZVB-1-5 Result Pass
Def. Code(s)
Comments
Gas O
MV
Pressure Reading
Building: 1
Floor: 1
Location Outside Bone Density
Area Controlled
Bone Density / Dexascan
Manufacturer Amico
Asset #: 1-ZVB-1-6 Result Pass
Def. Code(s)
Comments
Gas O
MV
Pressure Reading
V1 - Area controlled labeling not present, incorrect
V5 - No gauge(s) present - port available
V9 - Valve location non-compliant/undesirable
V13 - No valve(s) present as required
V2 - Gas labeling not present or incorrect
V6 - No gauge(s) present - no port available
V10 - Valve configuration non-compliant
V14 - See Comments Section
V3 - Leakage detected
V7 - Handle difficult to move
V11 - Valve type non-compliant
V4 - Gauge(s) defective
V8 - Cover/Frame damaged or missing
V12 - Valve not locked, latched or in secure area as required
Deficiency Codes
Gas Codes: O - Oxygen MA - Medical Air MV - Medical Vacuum N2O - Nitrous Oxide N2 - Nitrogen W - WAGD (Evacuation) CO2 - Carbon Dioxide VW - Vac/WAGD H - HeliOx
P.O. Box 541 Lawrence, PA 15055 Ph: (724) 745-1854 Fax: (724) 745-2184
Facility: VA Medical Center Erie
MP Project # 624943
Zone Shutoff Valves
Date Inspected: July 29, 2025
Building: 1
Floor: 1
Location In Sterile Process Room
Area Controlled
Bio Med 15216
Manufacturer Amico
Asset #: 1-ZVB-1-7 Result FAIL
Def. Code(s) V4
Comments Medical Air is Not in Use/Not in Service V4 - O
Gas O
MA
MV
Pressure Reading
NA
Building: 1
Floor: 1
Location Outside 1W222
Area Controlled
Sonography 1W222 & 1W223, CT 1W224, X Ray 1W221
Manufacturer Amico
Asset #: 1-ZVB-1-8 Result Pass
Def. Code(s)
Comments
Gas O
MV
Pressure Reading
Building: 1
Floor: 1
Location Outside RF 2
Area Controlled
RF 1 & 2
Manufacturer Amico
Asset #: 1-ZVB-1-9 Result Pass
Def. Code(s)
Comments
Gas O
MV
Pressure Reading
V1 - Area controlled labeling not present, incorrect
V5 - No gauge(s) present - port available
V9 - Valve location non-compliant/undesirable
V13 - No valve(s) present as required
V2 - Gas labeling not present or incorrect
V6 - No gauge(s) present - no port available
V10 - Valve configuration non-compliant
V14 - See Comments Section
V3 - Leakage detected
V7 - Handle difficult to move
V11 - Valve type non-compliant
V4 - Gauge(s) defective
V8 - Cover/Frame damaged or missing
V12 - Valve not locked, latched or in secure area as required
Deficiency Codes
Gas Codes: O - Oxygen MA - Medical Air MV - Medical Vacuum N2O - Nitrous Oxide N2 - Nitrogen W - WAGD (Evacuation) CO2 - Carbon Dioxide VW - Vac/WAGD H - HeliOx
P.O. Box 541 Lawrence, PA 15055 Ph: (724) 745-1854 Fax: (724) 745-2184
Facility: VA Medical Center Erie
MP Project # 624943
Zone Shutoff Valves
Date Inspected: July 29, 2025
Building: 1
Floor: 2
Location Left of Endo 1
Area Controlled
Endo 1
Manufacturer Amico
Asset #: 1-ZVB-2-1 Result Pass
Def. Code(s)
Comments
Gas O
MA
MV
N2O
CO2
WAGD
Pressure Reading
Building: 1
Floor: 2
Location Right of Endo 2
Area Controlled
Endo 2
Manufacturer Amico
Asset #: 1-ZVB-2-2 Result Pass
Def. Code(s)
Comments
Gas O
MA
MV
N2O
CO2
WAGD
Pressure Reading
Building: 1
Floor: 2
Location Right of OR 1
Area Controlled
OR Room 1
Manufacturer Amico
Asset #: 1-ZVB-2-3 Result Pass
Def. Code(s)
Comments
Gas O
MA
MV
N2O
N2
CO2
Pressure Reading
WAGD 21
V1 - Area controlled labeling not present, incorrect
V5 - No gauge(s) present - port available
V9 - Valve location non-compliant/undesirable
V13 - No valve(s) present as required
V2 - Gas labeling not present or incorrect
V6 - No gauge(s) present - no port available
V10 - Valve configuration non-compliant
V14 - See Comments Section
V3 - Leakage detected
V7 - Handle difficult to move
V11 - Valve type non-compliant
V4 - Gauge(s) defective
V8 - Cover/Frame damaged or missing
V12 - Valve not locked, latched or in secure area as required
Deficiency Codes
Gas Codes: O - Oxygen MA - Medical Air MV - Medical Vacuum N2O - Nitrous Oxide N2 - Nitrogen W - WAGD (Evacuation) CO2 - Carbon Dioxide VW - Vac/WAGD H - HeliOx
P.O. Box 541 Lawrence, PA 15055 Ph: (724) 745-1854 Fax: (724) 745-2184
Facility: VA Medical Center Erie
MP Project # 624943
Zone Shutoff Valves
Date Inspected: July 29, 2025
Building: 1
Floor: 2
Location Left of OR 2
Area Controlled
OR Room 2
Manufacturer Amico
Asset #: 1-ZVB-2-4 Result Pass
Def. Code(s)
Comments
Gas O
MA
MV
N2O
N2
CO2
Pressure Reading
WAGD 22
Building: 1
Floor: 2
Location Hallway Outside of Pre/Post & PACU
Area Controlled
Pre/Post 1-7, PACU 1-3 (Air in PACU only)
Manufacturer Amico
Asset #: 1-ZVB-2-5 Result Pass
Def. Code(s)
Comments
Gas O
MA
MV
Pressure Reading
Building: 1
Floor: 3
Location Outside Small Procedure
Area Controlled
Small Procedures
Manufacturer Beacon
Asset #: 1-ZVB-3-2 Result Pass
Def. Code(s)
Comments
Gas O
MV
Pressure Reading
V1 - Area controlled labeling not present, incorrect
V5 - No gauge(s) present - port available
V9 - Valve location non-compliant/undesirable
V13 - No valve(s) present as required
V2 - Gas labeling not present or incorrect
V6 - No gauge(s) present - no port available
V10 - Valve configuration non-compliant
V14 - See Comments Section
V3 - Leakage detected
V7 - Handle difficult to move
V11 - Valve type non-compliant
V4 - Gauge(s) defective
V8 - Cover/Frame damaged or missing
V12 - Valve not locked, latched or in secure area as required
Deficiency Codes
Gas Codes: O - Oxygen MA - Medical Air MV - Medical Vacuum N2O - Nitrous Oxide N2 - Nitrogen W - WAGD (Evacuation) CO2 - Carbon Dioxide VW - Vac/WAGD H - HeliOx
P.O. Box 541 Lawrence, PA 15055 Ph: (724) 745-1854 Fax: (724) 745-2184
Facility: VA Medical Center Erie
MP Project # 624943
Zone Shutoff Valves
Date Inspected: July 29, 2025
Building: 1
Floor: 3
Location Outside of Infusion Suite
Area Controlled
Infusion Bays 1-9, Private Exam Bay
Manufacturer Beacon
Asset #: 1-ZVB-3-3 Result Pass
Def. Code(s)
Comments Medical Air and Vacuum are Futures, Valved Off and Handles Removed
Gas O
MA
MV
Pressure Reading
Building: 1
Floor: 5
Location Right of 518
Area Controlled
519-522, 529-533
Manufacturer P-B
Asset #: 1-ZVB-5-1 Result Pass
Def. Code(s)
Comments
Gas O
MV
Pressure Reading
Building: 1
Floor: 5
Location Right of 515
Area Controlled
504-508, 510-513
Manufacturer P-B
Asset #: 1-ZVB-5-2 Result Pass
Def. Code(s)
Comments
Gas O
MV
Pressure Reading
V1 - Area controlled labeling not present, incorrect
V5 - No gauge(s) present - port available
V9 - Valve location non-compliant/undesirable
V13 - No valve(s) present as required
V2 - Gas labeling not present or incorrect
V6 - No gauge(s) present - no port available
V10 - Valve configuration non-compliant
V14 - See Comments Section
V3 - Leakage detected
V7 - Handle difficult to move
V11 - Valve type non-compliant
V4 - Gauge(s) defective
V8 - Cover/Frame damaged or missing
V12 - Valve not locked, latched or in secure area as required
Deficiency Codes
Gas Codes: O - Oxygen MA - Medical Air MV - Medical Vacuum N2O - Nitrous Oxide N2 - Nitrogen W - WAGD (Evacuation) CO2 - Carbon Dioxide VW - Vac/WAGD H - HeliOx
P.O. Box 541 Lawrence, PA 15055 Ph: (724) 745-1854 Fax: (724) 745-2184
Facility: VA Medical Center Erie
MP Project # 624943
Zone Shutoff Valves
Date Inspected: July 29, 2025
Building: 1
Floor: 6
Location Left of 625M
Area Controlled
625G, 625H, 625J, 625M
Manufacturer Beacon
Asset #: 1-ZVB-6-1 Result Pass
Def. Code(s)
Comments Air Not in Service. Valved Off; Handle Removed
Gas O
MV
Pressure Reading
Building: 1
Floor: 6
Location Right of 616
Area Controlled
617-619, 628-631
Manufacturer Beacon
Asset #: 1-ZVB-6-2 Result Pass
Def. Code(s)
Comments Medical Air is Not in Service. Valved Off; Handle Removed.
Gas O
MA
MV
Pressure Reading
NA
V1 - Area controlled labeling not present, incorrect
V5 - No gauge(s) present - port available
V9 - Valve location non-compliant/undesirable
V13 - No valve(s) present as required
V2 - Gas labeling not present or incorrect
V6 - No gauge(s) present - no port available
V10 - Valve configuration non-compliant
V14 - See Comments Section
V3 - Leakage detected
V7 - Handle difficult to move
V11 - Valve type non-compliant
V4 - Gauge(s) defective
V8 - Cover/Frame damaged or missing
V12 - Valve not locked, latched or in secure area as required
Deficiency Codes
Gas Codes: O - Oxygen MA - Medical Air MV - Medical Vacuum N2O - Nitrous Oxide N2 - Nitrogen W - WAGD (Evacuation) CO2 - Carbon Dioxide VW - Vac/WAGD H - HeliOx
P.O. Box 541 Lawrence, PA 15055 Ph: (724) 745-1854 Fax: (724) 745-2184
Facility: VA Medical Center Erie
MP Project # 624943
GAS OUTLETS/SUCTION INLETS
Bldg Floor Area/Dept Room Gas # Result Def. Code(s)Pres Mfr Model
Date Inspected: July 29, 2025
Mounting Connector Adapter Comments
1 Bio Med1 Bio Med Not Tested O8 Beacon Series BMA 1 QCWall Puritan-BennettNot in Service
1 Bio Med1 Bio Med Not Tested O8 Beacon Series BMA 2 QCWall Puritan-BennettNot in Service
1 Bio Med1 Bio Med Not Tested O8 Beacon Series BMA 3 QCWall Puritan-BennettNot in Service
1 Bio Med1 Bio Med Not Tested O8 Beacon Series BMA 4 QCWall Puritan-BennettNot in Service
1 Bio Med1 Bio Med Not Tested O8 Beacon Series BMA 5 QCWall Puritan-BennettNot in Service
1 Bio Med1 Bio Med Pass Beacon Series BMV 1 27 QCWall Puritan-Bennett
1 Bio Med1 Bio Med Pass Beacon Series BMV 2 27 QCWall Puritan-Bennett
1 Bio Med1 Bio Med Pass Beacon Series BMV 3 27 QCWall Puritan-Bennett
1 Bio Med1 Bio Med Fail O3 Beacon Series BMV 4 27 QCWall Puritan-Bennett
1 Bio Med1 Bio Med Pass Beacon Series BMV 5 27 QCWall Puritan-Bennett
1 Bio Med1 Bio Med Pass Beacon Series BO 1 51 QCWall Puritan-Bennett
1 Bio Med1 Bio Med Pass Beacon Series BO 2 51 QCWall Puritan-Bennett
1 Bio Med1 Bio Med Pass Beacon Series BO 3 51 QCWall Puritan-Bennett
1 Bio Med1 Bio Med Pass Beacon Series BO 4 51 QCWall Puritan-Bennett
1 Blue Clinic1 Blue Clinic Exam A (1W342) Pass Amico Alert 1MV 1 27 QCWall Puritan-Bennett
1 Blue Clinic1 Blue Clinic Exam A (1W342) Pass Amico Alert 1O 1 51 QCWall Puritan-Bennett
1 Blue Clinic1 Blue Clinic Exam B (1W344) Pass Amico Alert 1MV 1 27 QCWall Puritan-Bennett
1 Blue Clinic1 Blue Clinic Exam B (1W344) Pass Amico Alert 1O 1 51 QCWall Puritan-Bennett
1 Blue Clinic1 Blue Clinic Exam C (1W346) Pass Amico Alert 1MV 1 27 QCWall Puritan-Bennett
1 Blue Clinic1 Blue Clinic Exam C (1W346) Pass Amico Alert 1O 1 51 QCWall Puritan-Bennett
1 Blue Clinic1 Blue Clinic Exam D (1W352) Pass Amico Alert 1MV 1 27 QCWall Puritan-Bennett
1 Blue Clinic1 Blue Clinic Exam D (1W352) Pass Amico Alert 1O 1 51 QCWall Puritan-Bennett
1 Blue Clinic1 Blue Clinic Exam E (1W354) Pass Amico Alert 1MV 1 27 QCWall Puritan-Bennett
1 Blue Clinic1 Blue Clinic Exam E (1W354) Pass Amico Alert 1O 1 51 QCWall Puritan-Bennett
1 Blue Clinic1 Blue Clinic Exam F (1W356) Pass Amico Alert 1MV 1 27 QCWall Puritan-Bennett
1 Blue Clinic1 Blue Clinic Exam F (1W356) Pass Amico Alert 1O 1 51 QCWall Puritan-Bennett
1 ED1 1W452 (Left) Pass Amico Alert 1MV 1 27 QCWall Puritan-Bennett
1 ED1 1W452 (Left) Pass Amico Alert 1O 1 51 QCWall Puritan-Bennett
1 ED1 ER 1 Pass Amico Alert 1MA 1 50 QCWall Puritan-Bennett
1 ED1 ER 1 Pass Amico Alert 1MV 1 27 QCWall Puritan-Bennett
1 ED1 ER 1 Pass Beacon Series BO 1 51 QCConsole Puritan-Bennett
1 ED1 ER 2 Pass Beacon Series BMA 1 50 QCConsole Puritan-Bennett
1 ED1 ER 2 Pass Beacon Series BMV 1 27 QCConsole Puritan-Bennett
Gas Codes: O - Oxygen MA - Medical Air MV - Medical Vacuum N2O - Nitrous Oxide N2 - Nitrogen W - WAGD (Evacuation) CO2 - Carbon Dioxide VW - Vac/WAGD H - HeliOx
Deficiency Codes
O12 - Visible water detected
O8 - Unable to test at this time
O4 - Reduced flow/no flow
O15 - Contamination detected
O11 - Incorrect labeling/color-coding
O7 - Patient using outlet/inlet
O3 - Leak with connector out
O14 - Ceiling outlets without hoses
O10 - Hoses need replacement
O6 - Defective/Missing Parts
O2 - Leak with connector in
O13 - Latch cover missing/broken
O9 - Facility's connector broken
O5 - Abnormal Pressure
O1 - Difficult to insert/extract connector
P.O. Box 541 Lawrence, PA 15055 Ph: (724) 745-1854 Fax: (724) 745-2184
Facility: VA Medical Center Erie
MP Project # 624943
GAS OUTLETS/SUCTION INLETS
Bldg Floor Area/Dept Room Gas # Result Def. Code(s)Pres Mfr Model
Date Inspected: July 29, 2025
Mounting Connector Adapter Comments
1 ED1 ER 2 Fail O2 Beacon Series BO 1 51 QCConsole Puritan-Bennett
1 ED1 ER 3 Pass Beacon Series BMA 1 50 QCConsole Puritan-Bennett
1 ED1 ER 3 Pass Beacon Series BMV 1 27 QCConsole Puritan-Bennett
1 ED1 ER 3 Pass Beacon Series BO 1 51 QCConsole Puritan-Bennett
1 ED1 ER 4 Pass Beacon Series BMA 1 50 QCConsole Puritan-Bennett
1 ED1 ER 4 Pass Beacon Series BMV 1 27 QCConsole Puritan-Bennett
1 ED1 ER 4 Pass Beacon Series BO 1 51 QCConsole Puritan-Bennett
1 ED1 ER 5 Pass Beacon Series BMA 1 50 QCConsole Puritan-Bennett
1 ED1 ER 5 Pass Beacon Series BMV 1 27 QCConsole Puritan-Bennett
1 ED1 ER 5 Pass Beacon Series BO 1 51 QCConsole Puritan-Bennett
1 ED1 ER 6 Pass Beacon Series BMA 1 50 QCConsole Puritan-Bennett
1 ED1 ER 6 Pass Beacon Series BMV 1 27 QCConsole Puritan-Bennett
1 ED1 ER 6 Pass Beacon Series BO 1 51 QCConsole Puritan-Bennett
1 ED1 ER 7 Pass Amico Alert 1MA 1 50 QCWall Puritan-Bennett
1 ED1 ER 7 Pass Amico Alert 1MV 1 27 QCWall Puritan-Bennett
1 ED1 ER 7 Pass Amico Alert 1O 1 51 QCWall Puritan-Bennett
1 ED1 ER 8 Pass Amico Alert 1MA 1 50 QCWall Puritan-Bennett
1 ED1 ER 8 Pass Amico Alert 1MV 1 27 QCWall Puritan-Bennett
1 ED1 ER 8 Pass Amico Alert 1O 1 51 QCWall Puritan-Bennett
1 ED1 ER 9 Pass Amico Alert 1MA 1 50 QCWall Puritan-Bennett
1 ED1 ER 9 Pass Amico Alert 1MV 1 27 QCWall Puritan-Bennett
1 ED1 ER 9 Pass Amico Alert 1O 1 51 QCWall Puritan-Bennett
1 Pulm/Cardiac1 Pulm Lab (1N1170) Not Tested O8 P-B Series BMA 1 QCWall Puritan-BennettOutlet Access Obstructed
1 Pulm/Cardiac1 Pulm Lab (1N1170) Not Tested O8 P-B Series BO 1 QCWall Puritan-BennettOutlet Access Obstructed
1 Pulm/Cardiac1 Secretary Primary Care 1N1169
Not Tested O8 Beacon Series BO 1 QCWall Puritan-BennettOutlet Access Obstructed
1 Radiology1 1W222 Sonography Not Tested O8 Amico Alert 1MV 1 QCWall Puritan-BennettOutlet Access Obstructed
1 Radiology1 1W222 Sonography Pass Amico Alert 1O 1 51 QCWall Puritan-Bennett
1 Radiology1 1W223 Sonography Pass Amico Alert 1MV 1 27 QCWall Puritan-Bennett
1 Radiology1 1W223 Sonography Pass Amico Alert 1O 1 51 QCWall Puritan-Bennett
1 Radiology1 Bone Density Dexascan Pass Amico Alert 1MV 1 27 QCWall Puritan-Bennett
1 Radiology1 Bone Density Dexascan Pass Amico Alert 1O 1 51 QCWall Puritan-Bennett
1 Radiology1 CT 1W224 Pass Amico Alert 1MV 1 27 QCWall Puritan-Bennett
Gas Codes: O - Oxygen MA - Medical Air MV - Medical Vacuum N2O - Nitrous Oxide N2 - Nitrogen W - WAGD (Evacuation) CO2 - Carbon Dioxide VW - Vac/WAGD H - HeliOx
Deficiency Codes
O12 - Visible water detected
O8 - Unable to test at this time
O4 - Reduced flow/no flow
O15 - Contamination detected
O11 - Incorrect labeling/color-coding
O7 - Patient using outlet/inlet
O3 - Leak with connector out
O14 - Ceiling outlets without hoses
O10 - Hoses need replacement
O6 - Defective/Missing Parts
O2 - Leak with connector in
O13 - Latch cover missing/broken
O9 - Facility's connector broken
P.O. Box 541 Lawrence, PA 15055 Ph: (724) 745-1854 Fax: (724) 745-2184
Facility: VA Medical Center Erie
MP Project # 624943
GAS OUTLETS/SUCTION INLETS
Bldg Floor Area/Dept Room Gas # Result Def. Code(s)Pres Mfr Model
Date Inspected: July 29, 2025
Mounting Connector Adapter Comments
1 Radiology1 CT 1W224 Pass Amico Alert 1O 1 51 QCWall Puritan-Bennett
1 Radiology1 CT 64 Slice 1W225A Pass Amico Alert 1MV 1 27 QCWall Puritan-Bennett
1 Radiology1 CT 64 Slice 1W225A Pass Amico Alert 1O 1 51 QCWall Puritan-Bennett
1 Radiology1 RF1 Pass Amico Alert 1MV 1 27 QCWall Puritan-Bennett
1 Radiology1 RF1 Pass Amico Alert 1O 1 51 QCWall Puritan-Bennett
1 Radiology1 RF2 Pass Amico Alert 1MV 1 27 QCWall Puritan-Bennett
1 Radiology1 RF2 Pass Amico Alert 1O 1 51 QCWall Puritan-Bennett
1 Radiology1 X Ray 1W221 Pass Amico Alert 1MV 1 27 QCWall Puritan-Bennett
1 Radiology1 X Ray…