J01d Drawing and Specifications Addendum 2.pdf

PDF 981 KB Posted

Attached to
Pharmacy renovation at Wagner IHS Healthcare Facility located in Wagner, South Dakota
Solicitation number
75H70124R00025
Issued by

About this file

This document is an addendum to a set of drawings and specifications for the renovation of the pharmacy at the Wagner IHS Healthcare Facility to meet USP compounding standards. The addendum revises several items in the gypsum board assemblies section, including changes to wall types, ceiling details, and references to security barrier mesh. It also provides clarification on the installation of the gypsum board ceiling system. The renovated pharmacy will include new high-density shelving, transaction counter, and cabinetry. Key features are the addition of security barrier mesh in select wall assemblies and bullet-resistant panels. The overall project aims to upgrade the existing outpatient pharmacy to comply with the latest USP standards.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

P:\2023 Projects\023016.00 IHS Clinics Pharmacy USP Compliance Design\D - Bidding\4-Addenda\Wagner\Addendum 2\add 2.docx

2 West 1st Street, Suite 201, Duluth, Minnesota 55802 tel (218) 727-2626 fax (218) 722-7467

ADDENDUM 2

project Wagner Pharmacy USP Compliance project # 023016.01 date 03/22/24 from DSGW Architects to All planholders for above project

The following addendum shall become part of the construction documents for the construction of the above referenced project.

This addendum supersedes and supplements all previous reference to similar items.

I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am duly a Licensed Architect under the laws of the State of Minnesota.

Signature

Registration # 14817 Date 03/22/24 general clarifications 1. None specifications SECTION DESCRIPTION

09 21 16

1. Revise section 09 21 16 Gypsum Board Assemblies per attached reissued section

09 21 16 drawings SECTION DESCRIPTION

A2.1 Floor Plans

1. Revise Wall Type 5C per attached reissued sheet A2.1

A2.2 Floor Plans

1. Revise Wall Type 5C per attached reissued sheet A2.2

A3.1 Reflected Ceiling Plans

1. Revise Gyp. Bd. Ceiling Detail 3/A3.1 per attached reissued sheet A3.1 mechanical / electrical consultant

None enclosures J Spec section 09 21 16, Sheets A2.1, A2.2, and A3.1

This addendum shall become part of this bid. The bidder shall insert the addendum number in the space were indicated on the proposal form. Failure to comply may result in the bid being rejected.

END OF ADDENDUM 2

23016.10 – Wagner Pharmacy USP Compliance 09 21 16 - 1 GYPSUM BOARD ASSEMBLIES

ADDENDA

SECTION 09 21 16

GYPSUM BOARD ASSEMBLIES

PART 1 GENERAL

1.01 SECTION INCLUDES

A. Performance criteria for gypsum board assemblies.

B. Metal stud wall framing.

C. Metal channel ceiling framing.

D. Acoustic insulation.

E. Gypsum wallboard.

F. Glass mat faced gypsum board.

G. Joint treatment and accessories.

1.02 RELATED REQUIREMENTS

A. Section 06 10 00 – Rough Carpentry: Related.

B. Section 08 80 00 – Glazing: Transaction window area(s).

1.03 REFERENCE STANDARDS

A. AISI SG02-1 - North American Specification for the Design of Cold-Formed Steel Structural Members; American Iron and Steel Institute; 2001 with 2004 supplement. (replaced SG-971)

B. ANSI A108.11 - American National Standard for Interior Installation of Cementitious Backer Units; 2012.1.

C. ANSI A118.9 - American National Standard Specifications for Test Methods and Specifications for Cementitious Backer Units; 2012.1.

D. ASTM A653/A653M - Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc- Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process; 2011.

E. ASTM C475/C475M - Standard Specification for Joint Compound and Joint Tape for Finishing Gypsum Board; 2002 (Reapproved 2007).

F. ASTM C 645-07 - Standard Specification for Nonstructural Steel Framing Members; 2011a.

G. ASTM C665 - Standard Specification for Mineral-Fiber Blanket Thermal Insulation for Light Frame Construction and Manufactured Housing; 2012.

H. ASTM C754 - Standard Specification for Installation of Steel Framing Members to Receive Screw-Attached Gypsum Panel Products; 2011.

I. ASTM C840 - Standard Specification for Application and Finishing of Gypsum Board; 2011.

J. ASTM C954 - Standard Specification for Steel Drill Screws for the Application of Gypsum Panel Products or Metal Plaster Bases to Steel Studs From 0.033 in. (0.84 mm) to 0.112 in. (2.84

mm) in Thickness; 2011.

K. ASTM C1002 - Standard Specification for Steel Self-Piercing Tapping Screws for the Application of Gypsum Panel Products or Metal Plaster Bases to Wood Studs or Steel Studs;

2007.

L. ASTM C1278/C1278M - Standard Specification for Fiber-Reinforced Gypsum Panel; 2007a (Reapproved 2011).

M. ASTM C1288 - Standard Specification for Discrete Non-Asbestos Fiber-Cement Interior Substrate Sheets; 1999 (Reapproved 2010).

N. ASTM C1325 - Standard Specification for Non-Asbestos Fiber-Mat Reinforced Cement Substrate Sheets; 2008b.

O. ASTM C1396/C1396M - Standard Specification for Gypsum Board; 2011.

Compliance 09 21 16 - 2 GYPSUM BOARD ASSEMBLIES

ADDENDA

P. ASTM C1629/C1629 - Standard Classification for Abuse-Resistant Non-decorated Interior Gypsum Panel Products and Fiber-Reinforced Cement Panels; 2006.

Q. ASTM C1658/C1658M - Standard Specification for Glass Mat Gypsum Panels; 2012.

R. ASTM D3273 - Standard Test Method for Resistance to Growth of Mold on the Surface of Interior Coatings in an Environmental Chamber; 2012.

S. ASTM E90 - Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements; 2009.

T. ASTM E413 - Classification for Rating Sound Insulation; 2010.

U. GA-216 - Application and Finishing of Gypsum Board; Gypsum Association; 2010.

1.04 SUBMITTALS

A. See Section 01 30 00 - Administrative Requirements, for submittal procedures.

B. Product Data: Provide data on metal framing, gypsum board, accessories, and joint finishing system.

C. Product Data: Provide manufacturer's data on partition head to structure connectors, showing compliance with requirements.

D. Test Reports: For all stud framing products that do not comply with ASTM C 645-07 or C 754, provide independent laboratory reports showing maximum stud heights at required spacings and deflections.

E. Header opening design information as provided by the header manufacturer.

1.05 QUALITY ASSURANCE

A. Perform in accordance with ASTM C 840. Comply with requirements of GA-600 for fire-rated assemblies. Assembly ratings are noted on the wall types as shown on the drawings.

1.06 REGULATORY REQUIREMENTS

A. Conform to applicable code for fire rated assemblies as follows:

1. Fire Rated Partitions: Listed assembly by UL, No. U465; 1 hour rating.

2. Fire Rated Partitions: Listed assembly by UL, No. U419; 2 hour rating.

PART 2 PRODUCTS

2.01 GYPSUM BOARD ASSEMBLIES

A. Provide completed assemblies complying with ASTM C840 and GA-216.

1. See PART 3 for finishing requirements.

B. Interior Partitions: Provide completed assemblies with the following characteristics:

1. Acoustic Attenuation: STC of 45-49 calculated in accordance with ASTM E413, based on tests conducted in accordance with ASTM E90.

2.02 METAL FRAMING MATERIALS

A. Manufacturers - Metal Framing, Connectors, and Accessories:

1. Clarkwestern Dietrich Building Systems LLC: www.clarkdietrich.com.

2. Dietrich Metal Framing: www.dietrichindustries.com.

3. Marino: www.marinoware.com.

4. Custom Stud, Inc.: www.customstud.com

5. Substitutions: See Section 01 60 00 - Product Requirements.

B. Metal Framing: Drywall and Plaster Ceilings:

1. Chicago Metallic Corporation - System 640 and fire Front 650.

2. USG - Drywall Suspension System Flat for Ceilings, rated and non-rated one hour.

C. Metal Framing Connectors and Accessories:

1. Dietrich Metal Framing: www.dietrichindustries.com.

2. The Steel Network Inc: www.SteelNetwork.com.

3. Substitutions: See Section 01 60 00 - Product Requirements.

Compliance 09 21 16 - 3 GYPSUM BOARD ASSEMBLIES

D. Non-Load Bearing Framing System Components: ASTM C 645-07; galvanized sheet steel, of size and properties necessary to comply with ASTM C 754 for the spacing indicated, with maximum deflection of wall framing of L/240 at 5 psf (240 Pa). Studs shall be a minimum of 20 gauge.

1. Exception: The minimum metal thickness and section properties requirements of ASTM C 645-07 are waived provided steel of 40 ksi (275 MPa) minimum yield strength is used, the metal is continuously dimpled, the effective thickness is at least twice the base metal thickness, and maximum stud heights are determined by testing in accordance with ASTM E 72 using assemblies specified by ASTM C 754.

a. Acceptable Products:

1) Clark Western Building Systems; UltraSteel (tm): www.clarkwestern.com.

2. Studs: "C" shaped with flat or formed webs with knurled faces.

3. Runners: U shaped, sized to match studs.

4. Ceiling Channels: Deep leg track at roof deck.

5. Furring: Not applicable.

6. Security Walls: use 16 gauge at walls with security barrier mesh

E. Shaft Wall Studs and Accessories: Not applicable.

F. Drywall Ceiling and Soffit Framing System shall consist of the following components:

1. All furring runners and furring tees shall be 1-1/2" high, double web, .020 electro-galvanized steel, with a 1-3/8" wide capped knurled face.

2. All cross tees shall be 1-1/2" high, double web, .020 electro-galvanized steel, with a 15/16" wide capped flange face.

3. Wall track shall be 1-1/2" or 1-5/8" inside diameter, .020 electro-galvanized steel, with 15/16" or 1" wide top and bottom faces.

4. Hanger wire to be 12 gauge galvanized soft annealed steel wire.

G. Ceiling Hangers: Type and size as specified in ASTM C754 for spacing required.

H. Sheet Metal Backing: 0.036 inch thick, galvanized.

I. Treated Wood Blocking: Danback as manufactured by Dietrich Metal Framing. Dricon fire retardant treated plywood 5-1/8 inches wide attached to sheet metal strapping, made in 48 inch lengths to fit over and attach to metal framing system.

J. Opening Headers: ProX Header System as manufactured by Brady Brand, phone 888-475- 7875. Submit design information for each specific opening size and header configuration and gauge required.

K. Partition Head to Structure Connections: Provide track fastened to structure with legs of sufficient length to accommodate deflection, for friction fit of studs cut short and screwed to secondary deflection channel set inside but unattached to top track.

1. Subject to compliance with requirements, provide: Dietrich Metal Framing SLP-TRK Slotted Deflection Track by Brady Innovations or equivalent.

L. Partition Head to Structure Connections: Provide mechanical anchorage devices that accommodate deflection using slotted holes, screws and anti-friction bushings, preventing rotation of studs while maintaining structural performance of partition.

1. Structural Performance: Maintain lateral load resistance and vertical movement capacity required by applicable code, when evaluated in accordance with AISI North American Specification for the Design of Cold-Formed Steel Structural Members.

2. Material: ASTM A1003/1003M steel sheet, SS Grade 50/340, with G60/Z180 galvanized coating or equivalent corrosion resistance.

3. Provide components UL-listed for use in UL-listed fire-rated head of partition joint systems of fire rating and movement required.

Compliance 09 21 16 - 4 GYPSUM BOARD ASSEMBLIES

4. Deflection and Firestop Track:

a. Provide mechanical anchorage devices as described above that accommodate deflection while maintaining the fire-rating of the wall assembly.

5. Acceptable Products: VertiClip(r) or VertiTrack(tm) manufactured by The Steel Network Inc. or Dietrich Metal Framing SLP-TRK Slotted Deflection Track by Brady Innovations or equivalent.

M. Deflection Clips: Dietrich Metal Framing: Fast Strut / Fast Top Clips / FastClip Slide Clips / QuickClip / Slide Clip (SD) (866-638-1908).

N. Channel Bridging and Bracing: U-Channel Assembly: ASTM C645-07; Base metal thickness of.0538 inch (1.37 mm) and minimum 1/2 inch wide flanges.

1. Subject to compliance with requirements, provide one of the following:

a. Dietrich Metal Framing: Spazzer 9200 Bridging and Bracing Bar.

b. U-Channel Assembly: 3/4 inch, 1-1/2 inch, 2 inches: Dietrich Metal Framing; EasyClip U-Series Clip Angle or equivalent.

2.03 BOARD MATERIALS

A. Manufacturers - Gypsum-Based Board:

1. CertainTeed Corporation: www.certainteed.com.

2. Georgia-Pacific Gypsum: www.gpgypsum.com.

3. Lafarge North America Inc.: www.lafargenorthamerica.com.

4. National Gypsum Company: www.nationalgypsum.com.

5. USG Corporation: www.usg.com.

6. Substitutions: See Section 01 60 00 - Product Requirements.

B. Gypsum Wallboard: Paper-faced gypsum panels as defined in ASTM C1396/C1396M; sizes to minimize joints in place; ends square cut.

1. Application: Use for vertical surfaces and ceilings, unless otherwise indicated.

2. Thickness:

a. Vertical Surfaces: 5/8 inch (16 mm).

b. Ceilings: 5/8 inch (16 mm).

c. Multi-Layer Assemblies: Thicknesses as indicated on drawings.

3. Paper-Faced Products:

a. CertainTeed Corporation; ProRoc Brand Gypsum Board.

b. CertainTeed Corporation; ProRoc Brand Abuse Resistant Gypsum Board.

c. Georgia-Pacific Gypsum; ToughRock, ToughRock Fireguard, and ToughRock FireGuard C Gypsum Wallboard.

d. Lafarge North America Inc.; Regular Drywall and Firecheck Type X and Type C.

e. National Gypsum Company; Gold Bond Brand Gypsum Wallboard.

f. USG Corporation; Sheetrock Brand Gypsum Panels.

g. Substitutions: See Section 01 60 00 - Product Requirements.

4. Mold-Resistant Paper-Faced Products:

a. CertainTeed Corporation; ProRoc Brand Moisture & Mold Resistant Gypsum Board.

b. Lafarge North America Inc.; Mold Defense Drywall.

c. Lafarge North America Inc.; Protecta AR 100 Type X with Mold Defense.

d. National Gypsum Company; Gold Bond Brand XP Gypsum Board.

e. National Gypsum Company; Gold Bond Hi-Abuse Brand XP Wallboard.

f. USG Corporation; Sheetrock Brand Mold Tough Gypsum Panels.

g. USG Corporation; Sheetrock Brand Mold Tough Gypsum Panels AR.

h. Substitutions: See Section 01 60 00 - Product Requirements.

5. Glass-Mat-Faced Products:

a. Georgia-Pacific Gypsum; DensArmor Plus.

b. Georgia-Pacific Gypsum LLC; DensArmor Plus Abuse Guard.

c. National Gypsum Company; Gold Bond eXP Interior Extreme.

d. Substitutions: See Section 01 60 00 - Product Requirements.

Compliance 09 21 16 - 5 GYPSUM BOARD ASSEMBLIES

6. Unfaced Products:

a. USG Corporation; Fiberock Aqua-Tough Interior Panels.

b. USG Corporation; Fiberock Brand Panels--Abuse-Resistant.

C. Security Board/Mesh:

1. Gyp. Bd. Assemblies, Bullet Resistant Panels:

a. Manufacturer: QUICKSERV

b. Model: QS Protection 300

c. Thickness: 1/2"

d. Protection Level: UL Level 3

2. Security Barrier Mesh:

a. Manufacturer: CLARK DIETRICH

b. Model: BM50 BM15

c. GAUGE: 18 9

d. Material: Type II, Class 1 – Carbon Steel - Mesh, Complying to ASTM F1267 and

A1011

e. Installation: Install per manufactures instructions with Barrier Mesh clips ,

1. Install Barrier Mesh clips 6" on center.

2.04 ACCESSORIES

A. Acoustic Insulation:

1. Owens Corning - Noise Barrier Batts

2. Manville - Sound Control Batts

3. Certainteed - Sound Control Batts

4. Guardian Fiberglass, Inc. - Sound Control Batts

B. Acoustic Sealant: Non-hardening, non-skinning, for use in conjunction with gypsum board.

Acoustical sealant shall be as manufactured by one of the following or approved equal:

1. Ohio Sealants Inc. - Sound Sealant Rubber Base

2. Pecora - Acoustical Sealant

3. Tremco -Acoustical Sealant

C. Corner Beads: Galvanized steel, Dietrich 103 Delux Bead.

D. Edge Trim: J-Trim, type requiring an applied finished edge, Dietrich Metal Trims M20A.

E. Resilient Furring Channels: 1/2 inch deep Galvanized steel, Dietrich RC Deluxe.

F. Control Joint - Control joint shall be a vinyl extrusion conforming to ASTM C1047 or roll formed zinc. Control joint shall be as manufactured by one of the following or approved equal:

1. Dietrich Control Joint No. 093.

G. Joint Materials: ASTM C475 and as recommended by gypsum board manufacturer for project conditions.

1. Tape: 2 inch (50 mm) wide, coated glass fiber tape for joints and corners, except as otherwise indicated, for use in mold resistant systems.

2. Tape: 2 inch (50 mm) wide, creased paper tape for joints and corners, except as otherwise indicated.

3. Ready-mixed vinyl-based joint compound.

4. Chemical hardening type compound, for use in mold resistant systems.

H. Screws for Attachment to Steel Members Less Than 0.03 inch (0.7 mm) In Thickness, to Wood Members, and to Gypsum Board: ASTM C1002; self-piercing tapping type; cadmium-plated for exterior locations.

I. Screws for Attachment to Steel Members From 0.033 to 0.112 inch (0.8 to 2.8 mm) in Thickness: ASTM C954; steel drill screws for application of gypsum board to loadbearing steel studs.

J. Screws: ASTM C 1002; self-piercing tapping type.

Compliance 09 21 16 - 6 GYPSUM BOARD ASSEMBLIES

PART 3 EXECUTION

3.01 EXAMINATION

A. Verify that project conditions are appropriate for work of this section to commence.

3.02 SHAFT WALL INSTALLATION

A. N/A.

3.03 FRAMING INSTALLATION

A. Metal Framing: Install in accordance with ASTM C754 and manufacturer's instructions.

1. Align and secure top and bottom runners at 24 inches on center.

2. Fit runners under and above openings; secure intermediate studs to same spacing as wall studs.

3. Install studs vertically at 16 inches on center.

4. Align stud web openings horizontally.

5. Secure studs to tracks using fastener method. Do not weld.

6. Stud splicing is permissible; splice studs with 8 inch nested lap, secure each stud flange with flush head screw.

7. Fabricate corners using a minimum of three studs.

8. Double stud at wall openings, door and window jambs, not more than 2 inches from each side of openings.

9. Brace stud framing system rigid.

10. Coordinate erection of studs with requirements of door frames, and borrowed lites; install supports and attachments.

11. Coordinate installation of bucks, anchors, and blocking with electrical and mechanical work to be placed within or behind stud framing.

12. Partitions Extending Through the Ceiling to the Structure Above: Maintain clearance under structural building members to avoid deflection transfer to studs

B. Suspended Ceilings and Soffits: Space framing and furring members as indicated.

1. Level ceiling system to a tolerance of 1/360.

2. Main runners shall be installed 48" on center, and be directly suspended by not less than 12 gage galvanized steel wire spaced 48" on center along the furring runners. Hanger wires shall be wrapped tightly with at least 3 full turns.

3. Furring main runners shall be interconnected by furring cross tees 48" long spaced 16" on center and also 8" from the ends of each gypsum drywall panel. Cross tees shall also be installed adjacent to all recessed light fixtures on each side not supported by a furring runner. Pay special attention to the type of lay-in light fixture and direction in which they are installed.

4. Wall track shall be installed wherever suspension components meet vertical surfaces, and the suspension component ends shall be butt cut to fit into the wall track.

C. Studs: Space studs at 16 inches (400 mm) on center.

1. Extend stud framing through ceiling to structure above. Maintain clearance under structural building members to avoid deflection transfer to studs. Provide extended leg ceiling runners.

2. Partitions Terminating at Structure: Attach top runner to structure, maintain clearance between top of studs and structure, and connect studs to track using specified mechanical devices in accordance with manufacturer's instructions; verify free movement of top of stud connections; do not leave studs unattached to track.

D. Openings: Reinforce openings as required for weight of doors or operable panels, using not less than double studs at jambs.

E. Blocking: Install blocking for support of plumbing fixtures, wall cabinets, toilet accessories, and hardware. Bolt or screw steel channels to studs.

F. Blocking: If wood blocking is used it shall be Fire Resistive Treated.

Compliance 09 21 16 - 7 GYPSUM BOARD ASSEMBLIES

3.04 ACOUSTIC ACCESSORIES INSTALLATION

A. Acoustic Insulation: Place tightly within spaces, around cut openings, behind and around electrical and mechanical items within partitions, and tight to items passing through partitions.

Compliance 09 21 16 - 8 GYPSUM BOARD ASSEMBLIES

B. Acoustic Sealant: Install in accordance with manufacturer's instructions.

1. Place continuous bead at perimeter of each layer of gypsum board.

2. In non-fire-rated construction, seal around all penetrations by conduit, pipe, ducts, and rough-in boxes.

3. Bottom of Partitions: Apply a round bead of sealant at each side stud track before setting gypsum board. Set gypsum board into sealant to form complete contact with adjacent materials.

4. Top and Sides of Partitions Abutting Existing Construction or Non-acoustical New Construction - After gypsum board is installed apply acoustical sealant to provide full contact with adjacent existing surfaces at each side of the partition.

5. Cut Outs - Backs of electrical boxes, pipes, ducts, and other equipment penetrating the wall surface shall be buttered with sealant and perimeter edges of all items sealed with sealant.

3.05 BOARD INSTALLATION

A. Comply with ASTM C 840 and manufacturer's instructions. Install to minimize butt end joints, especially in highly visible locations.

B. Single-Layer Fire-Rated: Install gypsum board vertically, with edges and ends occurring over firm bearing.

C. Cementitious Backing Board: Install over steel framing members where indicated, in accordance with ANSI A108.11 and manufacturer's instructions.

D. Installation on Metal Framing: Use screws for attachment of all gypsum board.

E. Installation of security materials: Manufacturers directions.

3.06 GYPSUM BOARD INSTALLATION - CEILINGS

A. Gypsum drywall panels shall be screw attached to the suspension system, main runners and furring tees, with conventional drywall screws.

B. Attach the long dimension of the gypsum panel parallel to the main runner and perpendicular to the furring cross tee. All gypsum panels should be staggered.

C. The gypsum panels should be located such that the long dimension side joints are backed by the main runners and the short dimension butt joints fall under a furring tee.

D. Gypsum panels shall be fastened to each cross tee with five (5) drywall screws with one (1) screw located at the midspan of the cross tee, one (1) screw located 12" from and on each side of the cross tee midspan and one (1) screw located 1-1/2" from each gypsum panel side joint.

Except at gypsum panel end joints, drywall screws shall be located on alternating sides of the cross tee. At gypsum panel end joints, drywall screws shall be located 2" from the joint.

Gypsum board fastened to main runners with drywall screws, 2" from side joints, midway between intersections with cross tees.

E. Gypsum panels should be screw attached to the wall track at perimeter. Screw placement should be 12" on center.

F. Pay particular attention to the number and placement of hanger wires around light fixtures as shown on the drawings. Hanger wires shall be wrapped tightly with at least 3 full turns.

G. Light fixtures are to be installed with long dimension perpendicular to the furring main runner.

H. Loading of any suspension component may not cause deflection of more than 1/360 of the span.

3.07 INSTALLATION OF TRIM AND ACCESSORIES

A. Control Joints: Place control joints consistent with lines of building spaces and as follows:

1. Not more than 30 feet (10 meters) apart on walls over 50 feet (16 meters) long.

2. At exterior soffits, not more than 30 feet (10 meters) apart in both directions.

3. Partition, furring or column fireproofing abuts a structural element (except floor) or dissimilar wall or ceiling.

Compliance 09 21 16 - 9 GYPSUM BOARD ASSEMBLIES

4. Ceiling or soffit abuts a structural element, dissimilar wall or partition or other vertical penetration.

5. Construction changes within the plane of partition or ceiling.

6. Ceiling dimensions exceed fifty feet in either direction with perimeter relief, thirty feet without relief.

7. Where wings of "L", "U" and "T" shaped ceiling areas are joined.

8. Where gypsum board systems abut dissimilar materials, gypsum board shall be isolated by installing a casing bead within a 1/4" of the dissimilar material and sealing the joint with either acoustical sealant as specified above for sound insulated partitions or caulking as specified under Section 07 90 05.

9. Ceiling height door frames may be used as control joints. Less than ceiling height frames shall have control joints extending to the ceiling from both corners. Window openings shall be treated similar to doors with joint extending to the floor as well as the ceiling. Control joints in gypsum board to gypsum board configurations shall be formed using expansion joint formers as specified above. Joints shall be caulked with sound sealant or caulking as specified in Section 07 90 05 as appropriate to the condition.

10. Control joints in fire rated construction shall be formed with double studs and expansion joint former and backed with safing insulation.

B. Corner Beads: Install at external corners, using longest practical lengths.

C. Edge Trim: Install at locations where gypsum board abuts dissimilar materials and as indicated.

3.08 JOINT TREATMENT

A. Glass Mat Faced Gypsum Board or mold resistant systems: Use fiberglass joint tape, bedded and finished with chemical hardening type joint compound.

B. Paper Faced Gypsum Board: Use paper joint tape, bedded with ready-mixed vinyl-based joint compound and finished with ready-mixed vinyl-based joint compound.

C. Finish gypsum board in accordance with levels defined in ASTM C840, as follows:

1. Level 4: Walls and ceilings to receive paint finish or wall coverings, unless otherwise indicated.

2. Level 1: Fire rated wall areas above finished ceilings, whether or not accessible in the completed construction.

D. Tape, fill, and sand exposed joints, edges, and corners to produce smooth surface ready to receive finishes.

1. Feather coats of joint compound so that camber is maximum 1/32 inch (0.8 mm).

END OF SECTION

Refrigerator

STERILE

DRUG INFO

EYE EXAM

SUPPLY

JANITOR

HSKP/CLEAN

LINEN

HZD WASTE

STORAGE

EYE SCREENING

VESTIBULE

TEMPORARY

PHARMACY

DISPENSING

4 5

8'-0"

133B

OFFICE5B

5B

H M

-W

HM-W1

TA

-W

133B

MEDICAL

RECORDS

106B

MAIN

CORRIDOR

2'-0"

WOMEN TOILET

VENI

SPECIMEN

TOILET

SUPPLY

TOILET

ULTRASOUND

CORRIDOR

SUPPLY

DARK ROOM

OFFICE

DRESSING

DRESSING

FILM READING

WORK AREA

NEW SHEET VINYL

TO MATCH EXISTING

EXISTING FLOOR

TO REMAIN

NEW PAINT AND

VINYL BASE TO MATCH

EXISTING,

EXISTING COVE BASE

MANUFACTUER: VPI

COLOR: LONDON GRAY

EXISTING SHEET VINYL FLOOR

MANUFACTUER: CONGOLEUM

STYLE AND COLOR: AIR STEP

ADVANTAGE REMINISCE

CATCHING FIREFLIES

Wall Types

5A

3 5/8" METAL STUD

@ 16" O.C.

5/8" GYP.BD. EA. SIDE

BATT INSULATION

METAL STUD WALL TO

STRUCTURE

5B

OMIT BATT INSULATION, GYP BD

TO EXTEND TO 6" ABOVE CEILING

3 5/8" METAL STUD

CHANNEL

3 5/8" METAL STUD

DEFLECTION TRACK

BASE - SEE

SCHEDULE

ROOF OR FLOOR

STRUCTURE

CLG WHERE APPLICABLE;

SEE RCP

1A

5/8" GYP.BD.

FURRING OVER

EXISTING WALL TO

STRUCTURE

BASE - SEE

SCHEDULE

ROOF OR FLOOR

STRUCTURE

CLG WHERE

APPLICABLE; SEE

RCP

3A

3 5/8" METAL STUD @

16" O.C.

5/8" GYP.BD.

FURRING OVER

EXISTING WALL TO

STRUCTURE

3 5/8" METAL STUD

CHANNEL

BASE - SEE SCHEDULE

ROOF OR FLOOR

STRUCTURE

CLG WHERE APPLICABLE;

SEE RCP

3 5/8" METAL STUD

DEFLECTION TRACK

ACOUSTIC SEALANT

EA. SIDE

ACOUSTIC SEALANT

NOTE: ALL WALLS SHALL BE BUILT TO STRUCTURE ABOVE UNLESS OTHERWISE NOTED

7/8" 4 3/8"

4 7/8"

SECTION

@ FLOOR

SECTION

@ HEAD

SECTION

@ FLOOR

PLAN

VIEW

SECTION

@ HEAD

SECTION

@ FLOOR

PLAN

VIEW

SECTION

@ HEAD

SECURITY BARRIER

MESH

SECURITY BARRIER

MESH

EXTEND EXISTING WALL

TO STR ABOVE: 3 5/8"

METAL STUD @ 16" O.C.

EXISTING WALL

1B

5/8" GYP.BD.

FURRING OVER

EXISTING WALL TO

STRUCTURE

BASE - SEE

SCHEDULE

ROOF OR FLOOR

STRUCTURE

CLG WHERE

APPLICABLE; SEE

RCP

7/8"

SECTION

@ FLOOR

SECTION

@ HEAD

SECURITY BARRIER

MESH

EXISTING WALL

5C

3 5/8" 16 GAUGE METAL

STUD @ 16" O.C.

5/8" GYP.BD. EA. SIDE

BATT INSULATION

METAL STUD WALL TO

STRUCTURE W/

SECURITY BARRIER

MESH

3 5/8" 16 GAUGE METAL

STUD CHANNEL

3 5/8" 16 GAUGE METAL

STUD DEFLECTION TRACK

BASE - SEE

SCHEDULE

ROOF OR FLOOR

STRUCTURE

CLG WHERE APPLICABLE;

SEE RCP

ACOUSTIC SEALANT

EA. SIDE

5 1/8"

SECTION

@ FLOOR

PLAN

VIEW

SECTION

@ HEAD

SECURITY BARRIER

MESH

5D

3 5/8" METAL STUD

@ 16" O.C.

5/8" GYP.BD. EA. SIDE

BATT INSULATION

METAL STUD WALL TO

STRUCTURE W/

BULLET RESISTANT

PANEL

3 5/8" METAL STUD

CHANNEL

3 5/8" METAL STUD

DEFLECTION TRACK

BASE - SEE

SCHEDULE

ROOF OR FLOOR

STRUCTURE

CLG WHERE APPLICABLE;

SEE RCP

ACOUSTIC SEALANT

EA. SIDE

5 3/8"

SECTION

@ FLOOR

PLAN

VIEW

SECTION

@ HEAD

BULLET RESISTANT

PANEL

Çê~ïå=ÄóW

ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW

Ç~íÉW éêçàÉÅí=@W

Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW

DULUTH I TWIN CITIES I VIRGINIA

www.dsgw.com

14817

3/21/2024 4:02:30 PM

023016.01

BC

RT

10/06/23

Wagner Pharmacy

USP

Compliance

A2.1

FLOOR PLANS

111 Washington Ave. NW Wagner, SD 57380

1/4" = 1'-0"

FLOOR PLAN - PHASE 1 - TEMPORARY

PHARMACY

Floor Plan Notes 1 EXISTING RELOCATED HIGH DENSITY MOBILE SHELVING UNIT FROM PHASE 1 DEMO - RADIOLOGY DEPT.

2 NEW PORTABLE HAND WASHING CART, SEE SECTION 10 28 00

3 EXISTING RELOCATED SCRIPTPRO, CONTRACTOR TO SUBCONTRACT WITH SCRIPTPRO FOR MOVING AND

CALIBRATING EQUIPMENT.

4 NEW 30"x60" SIT-STAND DESK (NIC)

5 NEW 30"x48" SIT-STAND DESK (NIC)

6 NEW 24"x60" SIT-STAND DESK (NIC)

7 EXISTING RELOCATED PYXIS SAFE

8 EXISTING RELOCATED UNDERCOUNTER REFRIGERATOR

9 EXISTING RELOCATED REFRIGERATOR

10 EXISTING RELOCATED WALL MOUNTED WILL CALL HANGING BRACKETS FROM PHASE 1 PHARMACY DEMO

11 EXISTING RELOCATED TALL OPEN SHELVING CABINET FROM PHASE 1 PHARMACY DEMO

12 RELOCATED CORROSIVE CABINET

13 STEEL PACKAGE RECIEVER

14 ELECTRICAL POWER POLE - SEE ELEC

15 UPPER CABINETS, SEE SECTION 12 00 50

16 NEW 4'-0" WIDE WALL MOUNTED WILL CALL HANGING BRACKETS, SEE SECTION 10 28 00

17 WIRE MESH PARTITION

18 CART (NIC)

19 3'-0" x 4'-0" TACKBOARD

20 LITERATURE RACK

21 (2) ROBE HOOKS, MOUNT 5'-0" A.F.F.

23 BOUFFANT CAP BOX HOLDER, MOUNT 5'-0" A.F.F. TO CENTERLINE, SEE SECTION 10 28 00

24 SHOE COVER BOX HOLDER, MOUNT 5'-0" A.F.F. TO CENTERLINE, SEE SECTION 10 28 00

25 EXISTING RELOCATED TV AND BRACKET, PROVIDE WALL BACKING

26 HIGH-DENSITY SHELVING UNIT, SEE SECTION 12 00 50

27 CONSULT DESK, SEE SECTION 12 00 50

1/4" = 1'-0"

FLOOR PLAN - PHASE 1 - RADIOLOGY

DEPT.

êÉîáëáçå=L áëëìÉ åçK Ç~íÉ

^ÇÇÉåÇìã O PLOOLOQ

A d d en d u m

U.C.

Refr.

Refrigerator

PHARMACY

CONSULT

ELECTRICAL

ALCOVE

CORRIDOR

CORRIDOR

OFFICE

115A

SCA

115B

BREAKROOM

RECEIVING/HZD

STORAGE

NARCOTICS

115C

A2.2

A2.2

A2.2

A2.2

A2.24

A2.2

A2.2

/8

/4

4A

5A

5A

5A

5B

5 3

1A

1A

1B

5C

5C

1B

1B

1B

1A

1B

1A

1A

1A

1B

1A 1A 1B

1B

5D 5D

5A

1B

1B

8'-0"

TA-W1

A

B

146A

146B

145B145A

114A

B

7'-6" 9'-1 1/2"

MEDICAL

RECORDS

3'-0" 4'-0"

OUTPATIENT/PHARMACY

WAITING

17 18

A2.2

A2.2 12

SD (OPCI)

PTH (OPCI)

VERIFY

3'-0"

1"1"

2'-3" 2'-0" 2'-0" 2'-0" 2'-7"

RELOCATED

REFR.

RELOCATED

U/C REFR.

TA-W1

STEEL PACKAGE

RECIEVER

3'-1" 3'-0"

PULL OUT

PINTER

SHELF

WALL CABINET

SEE SECTION

12 00 50

BASE CABINETS

AND COUNTERTOP,

SEE SECTION

12 00 50

FILLMASTER

ON SIDE WALL

(OPCI)

PTH (OPCI)

SD (OPCI)

FILLMASTER

FILTRATION

SYSTEM MOUNTED

IN CABINET3

1"

3'-6"3'-0"

NEW WALL

MOUNTED

WILL CALL

BRACKETS

BASE CABINETS

AND COUNTERTOP,

SEE SECTION

12 00 50

TALL CABINET,

SEE SECTION

12 00 50

3'-0" 3'-0" 2'-6" 3'-0"

OPEN

1"2'-0"2'-0"2'-0"2'-0"2'-0"2'-0"2'-1"

BASE CABINETS

AND COUNTERTOP,

SEE SECTION

12 00 50

WALL CABINETS,

SEE SECTION

12 00 50

6'-0"

OPEN 3

PTH (OPCI)

SD (OPCI)

EYEWASH,

SEE MECH 3

3'-6"

EXHAUST

GRILLS, SEE

MECH

BASE CABINETS

AND COUNTERTOP,

SEE SECTION

12 00 50

WALL CABINETS,

SEE SECTION

12 00 50

(5) ROBE HOOKS

6 TIER METAL

LOCKERS, SEE

SECTION 12 00 50

3'-9"

4'-0" 3'-6"

QUICKSERVE

TRANSACTION

WINDOW W/

INTERCOM SYSTEM

STEEL PACKAGE

RECEIVER

RELOCATED TV AND

BRACKET PROVIDE

BLOCKING

COUNTERTOP,

SEE SECTION

12 00 50

SUPPORT

BRACKETS

5'-3"

COUNTERTOP,

SEE SECTION

12 00 50

1"1" 2'-0" 1'-6" 2'-0"

2'-6"3'-0"

PTH (OPCI) ON

SIDE WALL

SD (OPCI)

WAST BIN BEHIND

DOOR

MICROWAVE

(NIC)

COFFEE

(NIC)

U/C REFR

(NIC)

BASE CABINETS

AND COUNTERTOP,

SEE SECTION

12 00 50

WALL CABINETS,

SEE SECTION

12 00 50

Wall Types

5A

3 5/8" METAL STUD

@ 16" O.C.

5/8" GYP.BD. EA. SIDE

BATT INSULATION

METAL STUD WALL TO

STRUCTURE

5B

OMIT BATT INSULATION, GYP BD

TO EXTEND TO 6" ABOVE CEILING

3 5/8" METAL STUD

CHANNEL

3 5/8" METAL STUD

DEFLECTION TRACK

BASE - SEE

SCHEDULE

ROOF OR FLOOR

STRUCTURE

CLG WHERE APPLICABLE;

SEE RCP

1A

5/8" GYP.BD.

FURRING OVER

EXISTING WALL TO

STRUCTURE

BASE - SEE

SCHEDULE

ROOF OR FLOOR

STRUCTURE

CLG WHERE

APPLICABLE; SEE

RCP

3A

3 5/8" METAL STUD @

16" O.C.

5/8" GYP.BD.

FURRING OVER

EXISTING WALL TO

STRUCTURE

3 5/8" METAL STUD

CHANNEL

BASE - SEE SCHEDULE

ROOF OR FLOOR

STRUCTURE

CLG WHERE APPLICABLE;

SEE RCP

3 5/8" METAL STUD

DEFLECTION TRACK

ACOUSTIC SEALANT

EA. SIDE

ACOUSTIC SEALANT

NOTE: ALL WALLS SHALL BE BUILT TO STRUCTURE ABOVE UNLESS OTHERWISE NOTED

7/8" 4 3/8"

4 7/8"

SECTION

@ FLOOR

SECTION

@ HEAD

SECTION

@ FLOOR

PLAN

VIEW

SECTION

@ HEAD

SECTION

@ FLOOR

PLAN

VIEW

SECTION

@ HEAD

SECURITY BARRIER

MESH

SECURITY BARRIER

MESH

EXTEND EXISTING WALL

TO STR ABOVE: 3 5/8"

METAL STUD @ 16" O.C.

EXISTING WALL

1B

5/8" GYP.BD.

FURRING OVER

EXISTING WALL TO

STRUCTURE

BASE - SEE

SCHEDULE

ROOF OR FLOOR

STRUCTURE

CLG WHERE

APPLICABLE; SEE

RCP

7/8"

SECTION

@ FLOOR

SECTION

@ HEAD

SECURITY BARRIER

MESH

EXISTING WALL

5C

3 5/8" 16 GAUGE METAL

STUD @ 16" O.C.

5/8" GYP.BD. EA. SIDE

BATT INSULATION

METAL STUD WALL TO

STRUCTURE W/

SECURITY BARRIER

MESH

3 5/8" 16 GAUGE METAL

STUD CHANNEL

3 5/8" 16 GAUGE METAL

STUD DEFLECTION TRACK

BASE - SEE

SCHEDULE

ROOF OR FLOOR

STRUCTURE

CLG WHERE APPLICABLE;

SEE RCP

ACOUSTIC SEALANT

EA. SIDE

5 1/8"

SECTION

@ FLOOR

PLAN

VIEW

SECTION

@ HEAD

SECURITY BARRIER

MESH

5D

3 5/8" METAL STUD

@ 16" O.C.

5/8" GYP.BD. EA. SIDE

BATT INSULATION

METAL STUD WALL TO

STRUCTURE W/

BULLET RESISTANT

PANEL

3 5/8" METAL STUD

CHANNEL

3 5/8" METAL STUD

DEFLECTION TRACK

BASE - SEE

SCHEDULE

ROOF OR FLOOR

STRUCTURE

CLG WHERE APPLICABLE;

SEE RCP

ACOUSTIC SEALANT

EA. SIDE

5 3/8"

SECTION

@ FLOOR

PLAN

VIEW

SECTION

@ HEAD

BULLET RESISTANT

PANEL

3'-0"

TALL CABINET ,

SEE SECTION

12 00 50

1" 3'-0" 1'-11"

EXISTING

RELOCATED

PYXIS SAFE

3'-0"

WALL CABINET

SEE SECTION

12 00 50

BASE CABINET

AND COUNTERTOP

SEE SECTION

12 00 50

OPEN

Çê~ïå=ÄóW

ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW

Ç~íÉW éêçàÉÅí=@W

Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW

DULUTH I TWIN CITIES I VIRGINIA

www.dsgw.com

14817

3/21/2024 4:03:01 PM

023016.01

BC

RT

10/06/23

Wagner Pharmacy

USP

Compliance

A2.2

FLOOR PLANS

111 Washington Ave. NW Wagner, SD 57380

1/4" = 1'-0"

FLOOR PLAN - PHASE 2 - PHARMACY

1/4" = 1'-0"

ELEV AT SCA - SOUTH

1/4" = 1'-0"

ELEV AT PHARMACY - SOUTH

1/4" = 1'-0"

ELEV AT PHARMACY - WEST

1/4" = 1'-0"

ELEV AT PHARMACY - NORTH

1/4" = 1'-0"

ELEV AT RECEIVING / HZRD STOR

1/4" = 1'-0"

ELEV BREAK RM - NORTH

1/4" = 1'-0"

ELEV AT TRANSACTION COUNTER

Floor Plan Notes 1 EXISTING RELOCATED HIGH DENSITY MOBILE SHELVING UNIT FROM PHASE 1 DEMO - RADIOLOGY DEPT.

2 NEW PORTABLE HAND WASHING CART, SEE SECTION 10 28 00

3 EXISTING RELOCATED SCRIPTPRO, CONTRACTOR TO SUBCONTRACT WITH SCRIPTPRO FOR MOVING AND

CALIBRATING EQUIPMENT.

4 NEW 30"x60" SIT-STAND DESK (NIC)

5 NEW 30"x48" SIT-STAND DESK (NIC)

6 NEW 24"x60" SIT-STAND DESK (NIC)

7 EXISTING RELOCATED PYXIS SAFE

8 EXISTING RELOCATED UNDERCOUNTER REFRIGERATOR

9 EXISTING RELOCATED REFRIGERATOR

10 EXISTING RELOCATED WALL MOUNTED WILL CALL HANGING BRACKETS FROM PHASE 1 PHARMACY DEMO

11 EXISTING RELOCATED TALL OPEN SHELVING CABINET FROM PHASE 1 PHARMACY DEMO

12 RELOCATED CORROSIVE CABINET

13 STEEL PACKAGE RECIEVER

14 ELECTRICAL POWER POLE - SEE ELEC

15 UPPER CABINETS, SEE SECTION 12 00 50

16 NEW 4'-0" WIDE WALL MOUNTED WILL CALL HANGING BRACKETS, SEE SECTION 10 28 00

17 WIRE MESH PARTITION

18 CART (NIC)

19 3'-0" x 4'-0" TACKBOARD

20 LITERATURE RACK

21 (2) ROBE HOOKS, MOUNT 5'-0" A.F.F.

23 BOUFFANT CAP BOX HOLDER, MOUNT 5'-0" A.F.F. TO CENTERLINE, SEE SECTION 10 28 00

24 SHOE COVER BOX HOLDER, MOUNT 5'-0" A.F.F. TO CENTERLINE, SEE SECTION 10 28 00

25 EXISTING RELOCATED TV AND BRACKET, PROVIDE WALL BACKING

26 HIGH-DENSITY SHELVING UNIT, SEE SECTION 12 00 50

27 CONSULT DESK, SEE SECTION 12 00 50

1/4" = 1'-0"

ELEV BREAK RM - EAST

1/4" = 1'-0"

ELEV BREAK RM - SOUTH

êÉîáëáçå=L áëëìÉ åçK Ç~íÉ

^ÇÇÉåÇìã O PLOOLOQ

1/4" = 1'-0"

ELEV OFFICE - NORTH

1/4" = 1'-0"

ELEV AT NARCOTICS - WEST

A d d en d

TEMPORARY

PHARMACY

133B

OFFICE

9'-0"

MEDICAL

RECORDS

EXISTING CLG

TO REMAIN

9'-0"

NEW CEILING IN

PHASE 2

PHARMACY

CONSULT

EYE EXAM

ELECTRICAL

ALCOVE

EYE SCREENING

VISUAL FIELDS

STORAGE

OFFICE

115A SCA

115B

BREAKROOM

RECEIVING/HZD

STORAGE

NARCOTICS

115C

8'-0"

8'-0" 8'-5"

8'-0"

8'-0"

MEDICAL

RECORDS

8'-6"

9'-0"

9'-0"

GYP BD AND SECURITY BARRIER MESH CEILING

SEE DETAIL 3/A3.1

GYP BD CEILING

SEE DETAIL 4/A3.1

STRUCTURE/FRAMING ABOVE

3 5/8" 16 GAUGE METAL

STUD FRAMING

5/8" GYP. BD.

SECURITY BARRIER MESH

STRUCTURE/FRAMING ABOVE

DRYWALL SUSPENSION SYSTEM OR

3 5/8" METAL STUD FRAMING -

CONTRACTOR'S CHOICE

5/8" GYP. BD.

Çê~ïå=ÄóW

ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW

Ç~íÉW éêçàÉÅí=@W

Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW

DULUTH I TWIN CITIES I VIRGINIA

www.dsgw.com

14817

3/21/2024 3:02:56 PM

023016.01

BC

RT

10/06/23

Wagner

Pharmacy

USP

Compliance

A3.1

REFLECTED

CEILING PLANS

111 Washington Ave. NW

Wagner, SD 57380

1/8" = 1'-0"

REFLECTED CEILING PLAN - PHASE 1

1/4" = 1'-0"

REFLECTED CEILING PLAN - PHASE 2

êÉîáëáçå=L áëëìÉ åçK Ç~íÉ

^ÇÇÉåÇìã O PLOOLOQ

1" = 1'-0"

Gyp. Bd. Ceiling Detail

1" = 1'-0"

Gyp. Bd. Ceiling Detail1

A d d en d