J01c Drawing and Specifications Addendum 1.pdf
PDF 4 MB Posted
- Solicitation number
- 75H70124R00025
About this file
This document is an Addendum to the construction documents for the renovation of the Wagner Pharmacy to meet USP compliance. It contains changes to the mechanical, electrical, and plumbing specifications and drawings, including revisions to plumbing fixtures, HVAC controls, and electrical equipment. The addendum provides updates to specific sections of the project manual and revisions to various drawing sheets. It indicates that a mechanical/electrical addendum dated 12/21/23 is to be included with this addendum.
The related federal contract opportunity is for the renovation of the existing outpatient pharmacy at the Wagner IHS Healthcare Facility to meet the latest United States Pharmacopeia (USP) compounding standards. The solicitation is being issued by the Department of Health and Human Services Indian Health Service.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P:\2023 Projects\023016.00 IHS Clinics Pharmacy USP Compliance Design\D - Bidding\4-Addenda\Wagner\Addendum 1\add 1.docx
2 West 1st Street, Suite 201, Duluth, Minnesota 55802 tel (218) 727-2626 fax (218) 722-7467
ADDENDUM 1
project Wagner Pharmacy USP Compliance project # 023016.01 date 01/02/24 from DSGW Architects to All planholders for above project
The following addendum shall become part of the construction documents for the construction of the above referenced project.
This addendum supersedes and supplements all previous reference to similar items.
I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am duly a Licensed Architect under the laws of the State of Minnesota.
Signature
Registration # 14817 Date 01/02/24 general clarifications 1. None specifications SECTION DESCRIPTION
None
1.
drawings SECTION DESCRIPTION
None -
1.
mechanical / electrical consultant
Mechanical/Electrical Addendum 1, dated 12/21/23, is to be included with this addendum as attached (29 Pages) enclosures J Mechanical/Electrical Addendum One
This addendum shall become part of this bid. The bidder shall insert the addendum number in the space where indicated on the proposal form. Failure to comply may result in the bid being rejected.
END OF ADDENDUM 1
21 December 2023 EDI-Dolejs, Inc. # 23-035
23016.10 – Wagner Pharmacy ADDENDUM ONE- 1 USP Compliance
MECHANICAL/ELECTRICAL ADDENDUM ONE
DIVISION 21 – FIRE PROTECTION
CHANGES TO THE PROJECT MANUAL:
None.
CHANGES TO THE MECHANICAL DRAWINGS:
None.
DIVISION 22 – PLUMBING
Section 22 4000 – PLUMBING FIXTURES
1. Replace section in its entirety.
Drawing M2.0 – Partial Underfloor Plan – Phase 2 – Plumbing
1. Refer to revised sheet for revisions and additional information.
Drawing M2.1 – Partial Floor Plan – Phase 2 – Plumbing
1. Refer to revised sheet for revisions and additional information.
Drawing M2.2 – Plumbing Riser Diagrams
1. Refer to revised sheet for revisions and additional information.
DIVISION 23 – HEATING, VENTILATION, AND AIR CONDITIONING
Section 23 0993 – SEQUENCE OF OPERATION FOR HVAC CONTROLS
1. Add to section 1.7 Exhaust Fans, C point list, item 3 “Room pressure sensor for exhaust fan VFD control.”
Drawing M3.2 – Partial Floor Plan – Phase 2 - Piping: (Reissued)
DIVISION 26 – ELECTRICAL
Table of Contents: (Reissued)
21 December 2023 EDI-Dolejs, Inc. # 23-035
23016.10 – Wagner Pharmacy ADDENDUM ONE- 2 USP Compliance
1. Add “26 2923 – VARIABLE FREQUENCY MOTOR CONTROLLERS” to the Table of Contents.
Section 26 2923 – VARIABLE FREQUENCY MOTOR CONTROLLERS: (Issued)
1. Add this Section in its entirety.
CHANGES TO THE ELECTRICAL DRAWINGS:
Drawing E6.1 – Schedules - Electrical: (Reissued)
END OF MECHANICAL/ELECTRICAL ADDENDUM ONE
23016.10 – Wagner Pharmacy 22 40 00 - 1 PLUMBING FIXTURES
SECTION 22 40 00
PLUMBING FIXTURES
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes the following:
1. Protective shielding guards.
2. Fixture supports.
3. Faucets.
4. Sinks.
B. Related Sections include the following:
1. Division 22 Section "Emergency Plumbing Fixtures."
1.3 DEFINITIONS
A. Retain abbreviations and terms that remain after this Section has been edited.
B. ABS: Acrylonitrile-butadiene-styrene plastic.
C. Accessible Fixture: Plumbing fixture that can be approached, entered, and used by people with disabilities.
D. FRP: Fiberglass-reinforced plastic.
E. PMMA: Polymethyl methacrylate (acrylic) plastic.
F. PVC: Polyvinyl chloride plastic.
G. Solid Surface: Nonporous, homogeneous, cast-polymer-plastic material with heat-, impact-, scratch-, and stain-resistance qualities.
1.4 SUBMITTALS
A. Product Data: For each type of product indicated.
B. Shop Drawings: Diagram power, signal, and control wiring.
C. Operation and maintenance data.
23016.10 – Wagner Pharmacy 22 40 00 - 2 PLUMBING FIXTURES
1.5 QUALITY ASSURANCE
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.
B. Retain option in first paragraph below if required by authorities having jurisdiction.
C. Regulatory Requirements: Comply with requirements in ICC A117.1, "Accessible and Usable Buildings and Facilities"; Public Law 90-480, "Architectural Barriers Act"; and Public Law 101- 336, "Americans with Disabilities Act"; for plumbing fixtures for people with disabilities.
D. Regulatory Requirements: Comply with requirements in Public Law 102-486, "Energy Policy Act," about water flow and consumption rates for plumbing fixtures.
E. NSF Standard: Comply with NSF 61, "Drinking Water System Components--Health Effects," for fixture materials that will be in contact with potable water.
F. Select combinations of fixtures and trim, faucets, fittings, and other components that are compatible.
G. Comply with the following applicable standards and other requirements specified for plumbing fixtures:
1. Enameled, Cast-Iron Fixtures: ASME A112.19.1M.
2. Plastic Laundry Trays: ANSI Z124.6.
3. Plastic Shower Enclosures: ANSI Z124.2.
4. Plastic Sinks: ANSI Z124.6.
5. Porcelain-Enameled, Formed-Steel Fixtures: ASME A112.19.4M.
6. Slip-Resistant Bathing Surfaces: ASTM F 462.
7. Solid-Surface-Material Lavatories and Sinks: ANSI/ICPA SS-1.
8. Stainless-Steel Residential Sinks: ASME A112.19.3.
9. Vitreous-China Fixtures: ASME A112.19.2M.
10. Water-Closet, Flush Valve, Tank Trim: ASME A112.19.5.
11. Water-Closet, Flushometer Tank Trim: ASSE 1037.
H. Comply with the following applicable standards and other requirements specified for lavatory and sink faucets:
1. Backflow Protection Devices for Faucets with Side Spray: ASME A112.18.3M.
2. Backflow Protection Devices for Faucets with Hose-Thread Outlet: ASME A112.18.3M.
3. Diverter Valves for Faucets with Hose Spray: ASSE 1025.
4. Faucets: ASME A112.18.1.
5. Hose-Connection Vacuum Breakers: ASSE 1011.
6. Hose-Coupling Threads: ASME B1.20.7.
7. Integral, Atmospheric Vacuum Breakers: ASSE 1001.
8. NSF Potable-Water Materials: NSF 61.
9. Pipe Threads: ASME B1.20.1.
10. Sensor-Actuated Faucets and Electrical Devices: UL 1951.
11. Supply Fittings: ASME A112.18.1.
12. Brass Waste Fittings: ASME A112.18.2.
I. Comply with the following applicable standards and other requirements specified for bathtub/shower and shower faucets:
23016.10 – Wagner Pharmacy 22 40 00 - 3 PLUMBING FIXTURES
1. Backflow Protection Devices for Hand-Held Showers: ASME A112.18.3M.
2. Combination, Pressure-Equalizing and Thermostatic-Control Antiscald Faucets:
ASSE 1016.
3. Faucets: ASME A112.18.1.
4. Hand-Held Showers: ASSE 1014.
5. High-Temperature-Limit Controls for Thermal-Shock-Preventing Devices: ASTM F 445.
6. Hose-Coupling Threads: ASME B1.20.7.
7. Manual-Control Antiscald Faucets: ASTM F 444.
8. Pipe Threads: ASME B1.20.1.
9. Pressure-Equalizing-Control Antiscald Faucets: ASTM F 444 and ASSE 1016.
10. Sensor-Actuated Faucets and Electrical Devices: UL 1951.
11. Thermostatic-Control Antiscald Faucets: ASTM F 444 and ASSE 1016.
J. Comply with the following applicable standards and other requirements specified for miscellaneous fittings:
1. Atmospheric Vacuum Breakers: ASSE 1001.
2. Brass and Copper Supplies: ASME A112.18.1.
3. Dishwasher Air-Gap Fittings: ASSE 1021.
4. Manual-Operation Flushometers: ASSE 1037.
5. Plastic Tubular Fittings: ASTM F 409.
6. Brass Waste Fittings: ASME A112.18.2.
7. Sensor-Operation Flushometers: ASSE 1037 and UL 1951.
K. Comply with the following applicable standards and other requirements specified for miscellaneous components:
1. Disposers: ASSE 1008 and UL 430.
2. Dishwasher Air-Gap Fittings: ASSE 1021.
3. Flexible Water Connectors: ASME A112.18.6.
4. Grab Bars: ASTM F 446.
5. Hose-Coupling Threads: ASME B1.20.7.
6. Hot-Water Dispensers: ASSE 1023 and UL 499.
7. Off-Floor Fixture Supports: ASME A112.6.1M.
8. Pipe Threads: ASME B1.20.1.
9. Plastic Toilet Seats: ANSI Z124.5.
10. Supply and Drain Protective Shielding Guards: ICC A117.1.
PART 2 - PRODUCTS
2.1 PROTECTIVE SHIELDING GUARDS
A. Protective Shielding Pipe Covers:
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Plumberex Specialty Products Inc.
b. TRUEBRO, Inc.
c. Zurn Plumbing Products Group; Tubular Brass Plumbing Products Operation.
23016.10 – Wagner Pharmacy 22 40 00 - 4 PLUMBING FIXTURES
2. Description: Manufactured plastic wraps for covering plumbing fixture hot- and cold-water supplies and trap and drain piping. Comply with Americans with Disabilities Act (ADA) requirements.
2.2 FIXTURE SUPPORTS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Josam Company.
2. MIFAB Manufacturing Inc.
3. Smith, Jay R. Mfg. Co.
4. Tyler Pipe; Wade Div.
5. Watts Drainage Products Inc.; a div. of Watts Industries, Inc.
6. Zurn Plumbing Products Group; Specification Drainage Operation.
B. Lavatory Supports:
1. Description: Type II, lavatory carrier with concealed arms and tie rod for wall-mounting, lavatory-type fixture. Include steel uprights with feet.
2. Accessible-Fixture Support: Include rectangular steel uprights.
2.3 FAUCETS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Chicago Faucets.
2. Symmons Industries, Inc.
3. Delta Faucet Company - Commercial.
4. Zurn Plumbing Products Group; Commercial Brass Operation/
2.4 SINKS
A. SK-1: Counter-mounting, single bowl, stainless-steel fixture.
1. Basis-of-Design Product: Subject to compliance with requirements, provide Elkay Model LRAD2022 or an approved equal by one of the following:
a. Eljer.
b. Kohler Co.
c. American Standard Companies, Inc.
d. Just Manufacturing Company.
e. Moen, Inc.
f. Franke
2. Description: ADA compliant, single-bowl, counter-mounting, self-rimming, stainless-steel sink.
a. Overall Dimensions: 19 1/2” x 22”. Depth 6-1/2”.
b. Inside Bowl Dimensions: 16” x 16”. Depth 6-1/2”.
c. Metal Thickness: 18 gauge stainless steel.
23016.10 – Wagner Pharmacy 22 40 00 - 5 PLUMBING FIXTURES
d. Bowl:
1) Drain: 3-1/2-inch.
a) Location: Centered in bowl.
e. Faucet Hole Punching: Compatible with faucet.
f. Faucet: Chicago Faucet Model 1100-GN8AE3-317AB, deck mounted faucet with
8-1/4-inch rigid/swing gooseneck spout and 4-inch hot and cold water metal vandal proof wristblade handles, vandal proof 2.2 gpm aerator, polished chrome plated brass construction.
g. Scald Protection: Provide thermostatic mixing valve TMV-1. Refer to specification section 22 1119 for requirements.
h. Supplies: NPS 1/2 chrome-plated copper with loose key stops.
i. Drain Piping: NPS 1-1/2 chrome-plated, cast-brass P-trap; 0.045-inch-thick tubular brass waste to wall; and wall escutcheon(s).
j. Protective Shielding Guard(s): Yes.
B. SK-2: Wall-Hung, Single Bowl, Surgeon Scrub Sink, Stainless Steel.
1. Basis-of-Design Product: Subject to compliance with requirements, provide Elkay Model EWSF130261 or an approved equal by one of the following:
a. Eljer.
b. Kohler Co.
c. American Standard Companies, Inc.
d. Just Manufacturing Company.
e. Moen, Inc.
f. Franke
2. Description: Stainless steel scrub-up sink.
a. Overall Dimensions: 30” x 23”. Depth 26”.
b. Metal Thickness: 16 gauge stainless steel.
c. Bowl:
1) Drain: 3-1/2-inch.
a) Location: Rear center in bowl.
d. Faucet Hole Punching: Compatible with faucet.
e. Faucet: Elkay Model LKB721C, Commercial Electronic Sensor Scrub/Handwash
Battery Powered Deck Mount Faucet Chrome.
f. Supplies: Valve Connection is ½” NPT Female.
g. Drain Piping: NPS 1-1/2 chrome-plated, cast-brass P-trap; 0.045-inch-thick tubular brass waste to wall; and wall escutcheon(s).
h. Protective Shielding Guard(s): Yes.
C. SK-3: Accessible, wall-hanging, vitreous-china fixture.
1. Basis-of-Design Product: Subject to compliance with requirements, provide American Standard Companies Model “Lucerne” or an approved equal by one of the following:
a. Kohler Co.
23016.10 – Wagner Pharmacy 22 40 00 - 6 PLUMBING FIXTURES
2. Description: Accessible, wall-mounting, vitreous-china fixture.
a. Type: With back.
b. Size: 20 by 18 inches rectangular.
c. Color: White.
d. Faucet Hole Punching: Compatible with faucet.
e. Faucet: Sloan Faucet Model SF-2350-BAT-BDT-CP-0.5GPM-MLM-IR-FCT deck mounted, infrared battery operated sensor faucet with integral deck cover plate.
0.5 gpm pressure compensating vandal resistant, multi-laminar spray and below deck thermostatic mixer complying with ASSE 1070.
f. Supplies: NPSM 1/2” chrome-plated copper with stops.
g. Drain and piping: Grid strainer with 1-1/4” offset tailpiece, adjustable offset p-traps, 17 gauge tubing waste to wall, chrome escutcheon.
h. Protective Shielding Guard(s): Yes
i. Fixture Support: Yes.
D. SK-4: Counter-mounting, single bowl, stainless-steel fixture.
1. Basis-of-Design Product: Subject to compliance with requirements, provide Elkay Model LRAD1716 or an approved equal by one of the following:
a. Eljer.
b. Kohler Co.
c. American Standard Companies, Inc.
d. Just Manufacturing Company.
e. Moen, Inc.
f. Franke
2. Description: ADA compliant, single-bowl, counter-mounting, self-rimming, stainless-steel sink.
a. Overall Dimensions: 17” x 16”. Depth 5-1/2”.
b. Inside Bowl Dimensions: 14” x 10”. Depth 5-1/2”.
c. Metal Thickness: 18 gauge stainless steel.
d. Bowl:
1) Drain: 3-1/2-inch.
a) Location: Centered in bowl.
e. Faucet Hole Punching: Compatible with faucet.
f. Faucet: Chicago Faucet Model 116.213.AB.1, deck mounted faucet with 5-1/4-inch rigid/swing gooseneck spout with battery powered Dual Beam Infrared Sensor, vandal proof 0.5 gpm aerator, polished chrome plated brass construction.
g. Scald Protection: Provide thermostatic mixing valve TMV-1. Refer to specification section 22 1119 for requirements.
h. Supplies: NPS 1/2 chrome-plated copper with loose key stops.
i. Drain Piping: NPS 1-1/2 chrome-plated, cast-brass P-trap; 0.045-inch-thick tubular brass waste to wall; and wall escutcheon(s).
j. Protective Shielding Guard(s): Yes.
E. SK-5: Counter-mounting, double bowl, stainless-steel fixture.
1. Basis-of-Design Product: Subject to compliance with requirements, provide Elkay Model LRAD3321 or an approved equal by one of the following:
23016.10 – Wagner Pharmacy 22 40 00 - 7 PLUMBING FIXTURES
a. Eljer.
b. Kohler Co.
c. American Standard Companies, Inc.
d. Just Manufacturing Company.
e. Moen, Inc.
f. Franke
2. Description: ADA compliant, single-bowl, counter-mounting, self-rimming, stainless-steel sink.
a. Overall Dimensions: 33” x 21 1/4”. Depth 6-1/2”.
b. Inside Bowl Dimensions: 13 1/2” x 16”. Depth 6-1/2”.
c. Metal Thickness: 18 gauge stainless steel.
d. Bowl:
1) Drain: 3-1/2-inch.
a) Location: Off-centered in bowl.
e. Faucet Hole Punching: Compatible with faucet.
f. Faucet: Chicago Faucet Model 431-ABCP, deck mounted faucet with 8 inch swing spout manual sink faucet, vandal proof 1.5 gpm aerator, polished chrome plated brass construction.
g. Scald Protection: Provide thermostatic mixing valve TMV-1. Refer to specification section 22 1119 for requirements.
h. Supplies: NPS 1/2 chrome-plated copper with loose key stops.
i. Drain Piping: NPS 1-1/2 chrome-plated, cast-brass P-trap; 0.045-inch-thick tubular brass waste to wall; and wall escutcheon(s).
j. Protective Shielding Guard(s): Yes.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Assemble plumbing fixtures, trim, fittings, and other components according to manufacturers' written instructions.
B. Install off-floor supports, affixed to building substrate, for wall-mounting fixtures.
1. Use carrier supports with waste fitting and seal for back-outlet fixtures.
2. Use carrier supports without waste fitting for fixtures with tubular waste piping.
3. Use chair-type carrier supports with rectangular steel uprights for accessible fixtures.
C. Install wall-mounting fixtures with tubular waste piping attached to supports.
D. Install floor-mounting fixtures on closet flanges or other attachments to piping or building substrate.
E. Install counter-mounting fixtures in and attached to casework.
F. Install fixtures level and plumb according to roughing-in drawings.
23016.10 – Wagner Pharmacy 22 40 00 - 8 PLUMBING FIXTURES
G. Install water-supply piping with stop on each supply to each fixture to be connected to water distribution piping. Attach supplies to supports or substrate within pipe spaces behind fixtures.
Install stops in locations where they can be easily reached for operation.
H. Install trap and tubular waste piping on drain outlet of each fixture to be directly connected to sanitary drainage system.
I. Install tubular waste piping on drain outlet of each fixture to be indirectly connected to drainage system.
J. Install flushometer valves for accessible water closets and urinals with handle mounted on wide side of compartment. Install other actuators in locations that are easy for people with disabilities to reach.
K. Install toilet seats on water closets.
L. Install faucet-spout fittings with specified flow rates and patterns in faucet spouts if faucets are not available with required rates and patterns. Include adapters if required.
M. Install water-supply flow-control fittings with specified flow rates in fixture supplies at stop valves.
N. Install faucet flow-control fittings with specified flow rates and patterns in faucet spouts if faucets are not available with required rates and patterns. Include adapters if required.
O. Install traps on fixture outlets.
1. Exception: Omit trap on fixtures with integral traps.
2. Exception: Omit trap on indirect wastes, unless otherwise indicated.
P. Install escutcheons at piping wall and ceiling penetrations in exposed, finished locations and within cabinets and millwork. Use deep-pattern escutcheons if required to conceal protruding fittings. Escutcheons are specified in Division 22 Section "Common Work Results for Plumbing."
Q. Set service basins in leveling bed of cement grout. Grout is specified in Division 22 Section "Common Work Results for Plumbing."
R. Install ice maker boxes recessed in wall. Install 2-by-4-inch fire-retardant-treated-wood blocking wall reinforcement between studs. Fire-retardant-treated-wood blocking is specified in Division 06 Section "Miscellaneous Rough Carpentry."
S. Install dishwasher air-gap fitting at each sink indicated to have air-gap fitting. Install on countertop at sink. Connect inlet hose to dishwasher and outlet hose to a wye branch fitting on the tailpiece of the sink.
T. Seal joints between fixtures and walls, floors, and countertops using sanitary-type, one-part, mildew-resistant silicone sealant. Match sealant color to fixture color. Sealants are specified in Division 07 Section "Joint Sealants."
3.2 CONNECTIONS
A. Piping installation requirements are specified in other Division 22 Sections. Drawings indicate general arrangement of piping, fittings, and specialties.
23016.10 – Wagner Pharmacy 22 40 00 - 9 PLUMBING FIXTURES
B. Connect fixtures with water supplies, stops, and risers, and with traps, soil, waste, and vent piping. Use size fittings required to match fixtures.
C. Comply with water piping requirements specified in Section 221116 "Domestic Water Piping."
D. Comply with soil and waste piping requirements specified in Section 221316 "Sanitary Waste and Vent Piping."
E. Where installing piping adjacent to water closets, allow space for service and maintenance.
F. Install protective shielding pipe covers and enclosures on exposed supplies and waste piping of accessible lavatories and sinks.
3.3 ADJUSTING
A. Operate and adjust plumbing fixtures and controls. Replace damaged and malfunctioning fixtures, fittings, and controls.
B. Adjust water pressure at flushometer valves and faucets to produce proper flow.
3.4 FIELD QUALITY CONTROL
A. Verify that installed plumbing fixtures are categories and types specified for locations where installed.
B. Check that plumbing fixtures are complete with trim, faucets, fittings, and other specified components.
C. Inspect installed plumbing fixtures for damage. Replace damaged fixtures and components.
D. Test installed fixtures after water systems are pressurized for proper operation. Replace malfunctioning fixtures and components, then retest. Repeat procedure until units operate properly.
E. Clean fixtures, remove stains and labels prior to acceptance.
F. Install fresh batteries in sensor-operated mechanisms.
3.5 PROTECTION
A. Provide protective covering for installed fixtures and fittings.
B. Do not allow use of plumbing fixtures for temporary facilities unless approved in writing by Owner.
END OF SECTION
THIS PAGE LEFT BLANK INTENTIONALLY
23016.10 - Wagner Pharmacy 26 00 00 - 1 TABLE OF CONTENTS
Division ........ Section Title......................................................................................................................... Pages
DIVISION 26 - ELECTRICAL
260010 ......... GENERAL PROVISIONS FOR ELECTRICAL WORK
260090 ......... ELECTRICAL DEMOLITION
260100 ......... CONSTRUCTION POWER AND LIGHTING
260445 ......... ELECTRICAL CONNECTIONS TO EQUIPMENT
260500 ......... COMMON WORK RESULTS FOR ELECTRICAL
260519 ......... LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
260523 ......... CONTROL-VOLTAGE ELECTRICAL POWER CABLES
260529 ......... HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
260533 ......... RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS
260553 ......... IDENTIFICATION FOR ELECTRICAL SYSTEMS
260700 ......... COMMUNICATION RACEWAY
260923 ......... LIGHTING CONTROL DEVICES
262726 ......... WIRING DEVICES
262813 ......... FUSES
262816 ......... ENCLOSED SWITCHES AND CIRCUIT BREAKERS
262913.03 .... MANUAL AND MAGNETIC MOTOR CONTROLLERS
262923 ......... VARIABLE-FREQUENCY MOTOR CONTROLLERS
265119 .......... LED INTERIOR LIGHTING
265219 ......... EMERGENCY AND EXIT LIGHTING
267111 .......... DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
23016.10 - Wagner Pharmacy 26 2923 - 1 VARIABLE-FREQUENCY USP Compliance MOTOR CONTROLLERS
SECTION 26 29 23
VARIABLE-FREQUENCY MOTOR CONTROLLERS
PART 1 - GENERAL
1.1 SUMMARY
A. Section includes separately enclosed, preassembled, combination VFCs, rated 600 V and less, for speed control of three-phase, squirrel-cage induction motors.
1.2 DEFINITIONS
A. CPT: Control power transformer.
B. DDC: Direct digital control.
C. EMI: Electromagnetic interference.
D. OCPD: Overcurrent protective device.
E. PID: Control action, proportional plus integral plus derivative.
F. VFC: Variable-frequency motor controller.
1.3 ACTION SUBMITTALS
A. Product Data: For each type and rating of VFC indicated.
B. Shop Drawings: For each VFC indicated.
1. Include details of equipment assemblies. Indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection.
2. Include diagrams for power, signal, and control wiring.
1.4 CLOSEOUT SUBMITTALS
A. Operation and maintenance data.
1.5 QUALITY ASSURANCE
A. Testing Agency Qualifications: Member company of NETA or an NRTL.
23016.10 - Wagner Pharmacy 26 2923 - 2 VARIABLE-FREQUENCY
1.6 WARRANTY
A. Special Warranty: Manufacturer agrees to repair or replace VFCs that fail in materials or workmanship within specified warranty period.
1. Warranty Period: Five years from date of Substantial Completion.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. ABB (Electrification Products Division).
2. Eaton.
3. Schneider Electric USA, Inc.
4. Siemens Industry, Inc. (Building Technologies Division).
2.2 SYSTEM DESCRIPTION
A. General Requirements for VFCs:
1. VFCs and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
2. Comply with NEMA ICS 7, NEMA ICS 61800-2, UL 508A, and UL 508C.
B. Application:
1. Constant torque for loads such as positive-displacement pumps and reciprocating and screw compressors.
2. Variable torque for loads such as centrifugal blowers, compressors, fans, and pumps.
C. VFC Description: Variable-frequency motor controller, consisting of power converter that employs pulse-width-modulated inverter, factory built and tested in an enclosure, with integral disconnecting means and overcurrent and overload protection; listed and labeled by an NRTL as a complete unit; arranged to provide self-protection, protection, and variable-speed control of one or more three-phase induction motors by adjusting output voltage and frequency.
1. Units suitable for operation of NEMA MG 1 motors.
2. Listed and labeled for integrated short-circuit current (withstand) rating by an NRTL acceptable to authorities having jurisdiction.
D. Design and Rating: Match load type, such as fans, blowers, and pumps; and type of connection used between motor and load such as direct or through a power-transmission connection.
E. Output Rating:
1. Constant Torque: Three phase; 10 to 66 Hz, with torque constant as speed changes;
maximum voltage equals input voltage.
2. Variable Torque: Three phase; 10 to 60 Hz, with voltage proportional to frequency throughout voltage range; maximum voltage equals input voltage.
F. Unit Operating Requirements:
http://www.specagent.com/Lookup?ulid=2177 http://www.specagent.com/Lookup?uid=123457177802 http://www.specagent.com/Lookup?uid=123457141441 http://www.specagent.com/Lookup?uid=123457141444 http://www.specagent.com/Lookup?uid=123457141450
23016.10 - Wagner Pharmacy 26 2923 - 3 VARIABLE-FREQUENCY
1. Input AC Voltage Tolerance: Plus 10 and minus 10 percent of VFC input voltage rating.
2. Input AC Voltage Unbalance: Not exceeding 3 percent.
3. Input Frequency Tolerance: Plus or minus 3 percent of VFC frequency rating.
4. Minimum Efficiency: 97 percent at 60 Hz, full load.
5. Minimum Displacement Primary-Side Power Factor: 98 percent under any load or speed condition.
6. Minimum Short-Circuit Current (Withstand) Rating: 22 kA.
7. Ambient Temperature Rating: Not less than 32 deg F and not exceeding 104 deg F.
8. Humidity Rating: Less than 95 percent (noncondensing).
9. Altitude Rating: Not exceeding 3300 feet.
10. Vibration Withstand: Comply with NEMA ICS 61800-2.
11. Overload Capability: 1.5 times the base load current for 60 seconds; minimum of 1.8 times the base load current for three seconds.
12. Starting Torque: Minimum 100 percent of rated torque from 3 to 60 Hz.
13. Speed Regulation: Plus or minus 5 percent.
14. Output Carrier Frequency: Selectable; 0.5 to 15 kHz.
15. Stop Modes: Programmable; includes fast, free-wheel, and dc injection braking.
G. Inverter Logic: Microprocessor based, 32 bit, isolated from all power circuits.
H. Isolated Control Interface: Allows VFCs to follow remote-control signal over a minimum 40:1 speed range.
1. Signal: Electrical.
I. Internal Adjustability Capabilities:
1. Minimum Speed: 5 to 25 percent of maximum rpm.
2. Maximum Speed: 80 to 100 percent of maximum rpm.
3. Acceleration: 0.1 to 999.9 seconds.
4. Deceleration: 0.1 to 999.9 seconds.
5. Current Limit: 30 to minimum of 150 percent of maximum rating.
J. Self-Protection and Reliability Features:
1. Surge Suppression: Factory installed as an integral part of the VFC, complying with UL 1449 SPD, Type 1 or Type 2.
2. Loss of Input Signal Protection: Selectable response strategy, including speed default to a percent of the most recent speed, a preset speed, or stop; with alarm.
3. Under- and overvoltage trips.
4. Inverter overcurrent trips.
5. VFC and Motor-Overload/Overtemperature Protection: Microprocessor-based thermal protection system for monitoring VFCs and motor thermal characteristics, and for providing VFC overtemperature and motor-overload alarm and trip; settings selectable via the keypad.
6. Critical frequency rejection, with three selectable, adjustable dead-bands.
7. Instantaneous line-to-line and line-to-ground overcurrent trips.
8. Loss-of-phase protection.
9. Reverse-phase protection.
10. Short-circuit protection.
11. Motor-overtemperature fault.
K. Automatic Reset/Restart: Attempt three restarts after drive fault or on return of power after an interruption and before shutting down for manual reset or fault correction; adjustable delay time between restart attempts.
23016.10 - Wagner Pharmacy 26 2923 - 4 VARIABLE-FREQUENCY
L. Power-Interruption Protection: To prevent motor from re-energizing after a power interruption until motor has stopped, unless "Bidirectional Auto-speed Search" feature is available and engaged.
M. Bidirectional Auto-speed Search: Capable of starting VFC into rotating loads spinning in either direction and returning motor to set speed in proper direction, without causing damage to drive, motor, or load.
N. Torque Boost: Automatically varies starting and continuous torque to at least 1.5 times the minimum torque to ensure high-starting torque and increased torque at slow speeds.
O. Motor Temperature Compensation at Slow Speeds: Adjustable current fall-back based on output frequency for temperature protection of self-cooled, fan-ventilated motors at slow speeds.
P. Integral Input Disconnecting Means and OCPD: NEMA KS 1, fusible switch with pad-lockable, door-mounted handle mechanism.
1. Disconnect Rating: Not less than 115 percent of VFC input current rating.
2. Auxiliary Contacts: NO or NC, arranged to activate before switch blades open.
3. Auxiliary contacts "a" and "b" arranged to activate with circuit-breaker handle.
4. NC, NO alarm contacts that operates only when circuit breaker has tripped.
2.3 CONTROLS AND INDICATION
A. Status Lights: Door-mounted LED indicators displaying the following conditions:
1. Power on.
2. Run.
3. Overvoltage.
4. Line fault.
5. Overcurrent.
6. External fault.
B. Panel-Mounted Operator Station: Manufacturer's standard front-accessible, sealed keypad and plain-English-language digital display; allows complete programming, program copying, operating, monitoring, and diagnostic capability.
1. Keypad: In addition to required programming and control keys, include keys for HAND, OFF, and AUTO modes.
2. Security Access: Provide electronic security access to controls through identification and password with at least one level of access: View only; view and operate; and view, operate, and service.
a. Control Authority: Supports at least four conditions: Off, local manual control at VFC, local automatic control at VFC, and automatic control through a remote source.
C. Historical Logging Information and Displays:
1. Real-time clock with current time and date.
2. Running log of total power versus time.
3. Total run time.
4. Fault log, maintaining last four faults with time and date stamp for each.
23016.10 - Wagner Pharmacy 26 2923 - 5 VARIABLE-FREQUENCY
D. Indicating Devices: Digital display mounted flush in VFC door and connected to display VFC parameters including, but not limited to:
1. Output frequency (Hz).
2. Motor speed (rpm).
3. Motor status (running, stop, fault).
4. Motor current (amperes).
5. Motor torque (percent).
6. Fault or alarming status (code).
7. PID feedback signal (percent).
8. DC-link voltage (V dc).
9. Set point frequency (Hz).
10. Motor output voltage (V ac).
E. Control Signal Interfaces:
1. Electric Input Signal Interface:
a. A minimum of two programmable analog inputs: Operator-selectable "x"- to "y"-mA dc.
b. A minimum of six multifunction programmable digital inputs.
2. Remote Signal Inputs: Capability to accept any of the following speed-setting input signals from the DDC system for HVAC or other control systems:
a. 0- to 10-V dc.
b. 4- to 20-mA dc.
c. Potentiometer using up/down digital inputs.
d. Fixed frequencies using digital inputs.
e. <Insert signal input>.
3. Output Signal Interface: A minimum of one programmable analog output signal(s) operator-selectable "x"- to "y"-mA dc, which can be configured for any of the following:
a. Output frequency (Hz).
b. Output current (load).
c. DC-link voltage (V dc).
d. Motor torque (percent).
e. Motor speed (rpm).
f. Set point frequency (Hz).
g. <Insert indication>.
F. PID Control Interface: Provides closed-loop set point, differential feedback control in response to dual feedback signals. Allows for closed-loop control of fans and pumps for pressure, flow, or temperature regulation.
1. Number of Loops: Two.
2.4 OPTIONAL FEATURES
A. Damper control circuit with end-of-travel feedback capability.
23016.10 - Wagner Pharmacy 26 2923 - 6 VARIABLE-FREQUENCY
B. Communication Port: RS-232 port, USB 2.0 port, or equivalent connection capable of connecting a printer and a notebook computer.
2.5 ENCLOSURES
A. VFC Enclosures: NEMA 250, to comply with environmental conditions at installed location.
1. Dry and Clean Indoor Locations: Type 1.
2. Outdoor Locations: Type 4X.
3. Kitchen/Wash-Down Areas: Type 4X, stainless steel.
4. Other Wet or Damp Indoor Locations: Type 4.
5. Indoor Locations Subject to Dust, Falling Dirt, and Dripping Noncorrosive Liquids:
Type 12.
B. Plenum Rating: UL 1995; NRTL certification label on enclosure, clearly identifying VFC as "Plenum Rated."
2.6 ACCESSORIES
A. General Requirements for Control-Circuit and Pilot Devices: NEMA ICS 5; factory installed in VFC enclosure cover unless otherwise indicated.
1. Push Buttons: Covered.
2. Pilot Lights: Push to test.
3. Selector Switches: Rotary type.
B. Control Relays: Auxiliary and adjustable solid-state time-delay relays.
C. Phase-Failure, Phase-Reversal, and Undervoltage and Overvoltage Relays: Solid-state sensing circuit with isolated output contacts for hard-wired connections. Provide adjustable undervoltage, overvoltage, and time-delay settings.
1. Current Transformers: Continuous current rating, basic impulse insulating level (BIL) rating, burden, and accuracy class suitable for connected circuitry. Comply with
IEEE C57.13.
D. Supplemental Digital Meters:
1. Elapsed-time meter.
2. Kilowatt meter.
3. Kilowatt-hour meter.
E. Breather and drain assemblies, to maintain interior pressure and release condensation in NEMA 250, Type 4X enclosures installed outdoors or in unconditioned interior spaces subject to humidity and temperature swings.
F. Space heaters, with NC auxiliary contacts, to mitigate condensation in NEMA 250, Type 4X enclosures installed outdoors or in unconditioned interior spaces subject to humidity and temperature swings.
23016.10 - Wagner Pharmacy 26 2923 - 7 VARIABLE-FREQUENCY
PART 3 - EXECUTION
3.1 INSTALLATION
A. Wall-Mounting Controllers: Install with tops at uniform height and with disconnect operating handles not higher than 79 inches above finished floor, unless otherwise indicated, and by bolting units to wall or mounting on lightweight structural-steel channels bolted to wall. For controllers not on walls, provide freestanding racks complying with Section 260529 "Hangers and Supports for Electrical Systems."
B. Roof-Mounting Controllers: Install VFC on roofs with tops at uniform height and with disconnect operating handles not higher than 79 inches above finished roof surface unless otherwise indicated, and by bolting units to curbs or mounting on freestanding, lightweight, structural-steel channels bolted to curbs. Seal roof penetrations after raceways are installed.
1. Curbs and roof penetrations are specified in Section 077200 "Roof Accessories."
2. Structural-steel channels are specified in Section 260529 "Hangers and Supports for
Electrical Systems."
C. Temporary Lifting Provisions: Remove temporary lifting eyes, channels, and brackets and temporary blocking of moving parts from enclosures and components.
D. Install fuses in each fusible-switch VFC.
E. Install fuses in control circuits if not factory installed. Comply with requirements in Section 262813 "Fuses."
F. Install heaters in thermal-overload relays. Select heaters based on actual nameplate full-load amperes after motors are installed.
G. Install, connect, and fuse thermal-protector monitoring relays furnished with motor-driven equipment.
H. Comply with NECA 1.
3.2 CONTROL WIRING INSTALLATION
A. All control wiring by division 23 contractor
3.3 IDENTIFICATION
A. Identify VFCs, components, and control wiring. Comply with requirements for identification specified in Section 260553 "Identification for Electrical Systems."
1. Identify field-installed conductors, interconnecting wiring, and components; provide warning signs.
2. Label each VFC with engraved nameplate.
3. Label each enclosure-mounted control and pilot device.
23016.10 - Wagner Pharmacy 26 2923 - 8 VARIABLE-FREQUENCY
3.4 FIELD QUALITY CONTROL
A. Perform tests and inspections with the assistance of a factory-authorized service representative.
B. Acceptance Testing Preparation:
1. Test insulation resistance for each VFC element, bus, component, connecting supply, feeder, and control circuit.
2. Test continuity of each circuit.
C. Tests and Inspections:
1. Inspect VFC, wiring, components, connections, and equipment installation. Test and adjust controllers, components, and equipment.
2. Test insulation resistance for each VFC element, component, connecting motor supply, feeder, and control circuits.
3. Test continuity of each circuit.
4. Verify that voltages at VFC locations are within 10 percent of motor nameplate rated voltages. If outside this range for any motor, notify Engineer before starting the motor(s).
5. Test each motor for proper phase rotation.
6. Perform tests according to the Inspection and Test Procedures for Adjustable Speed
Drives stated in NETA Acceptance Testing Specification. Certify compliance with test parameters.
7. Correct malfunctioning units on-site, where possible, and retest to demonstrate compliance; otherwise, replace with new units and retest.
8. Test and adjust controls, remote monitoring, and safeties. Replace damaged and malfunctioning controls and equipment.
D. VFCs will be considered defective if they do not pass tests and inspections.
3.5 ADJUSTING
A. Program microprocessors for required operational sequences, status indications, alarms, event recording, and display features. Clear events memory after final acceptance testing and prior to Substantial Completion.
B. Set field-adjustable switches, auxiliary relays, time-delay relays, timers, and overload-relay pickup and trip ranges.
C. Adjust the trip settings of instantaneous-only circuit breakers and thermal-magnetic circuit breakers with adjustable, instantaneous trip elements. Initially adjust to 6 times the motor nameplate full-load amperes and attempt to start motors several times, allowing for motor cool-down between starts. If tripping occurs on motor inrush, adjust settings in increments until motors start without tripping. Do not exceed 8 times the motor full-load amperes (or 11 times for NEMA Premium Efficient motors if required). Where these maximum settings do not allow starting of a motor, notify Engineer before increasing settings.
D. Set the taps on reduced-voltage autotransformer controllers.
E. Set field-adjustable circuit-breaker trip ranges.
F. Set field-adjustable pressure switches.
23016.10 - Wagner Pharmacy 26 2923 - 9 VARIABLE-FREQUENCY
3.6 DEMONSTRATION
A. Train Owner's maintenance personnel to adjust, operate, reprogram, and maintain VFCs.
END OF SECTION 262923
GENERAL NOTES
E
F
G
H
J
K
L
M
P
Q
121110987.175432
2" SS UP TO SK-1
2" SS UP TO FCO
2" SS
2" SS UP TO SK-2
2" SS
2" SS UP
TO FCO
2" SS UP TO SK-1
2" SS UP TO SK-3
2" SS
2" SS
EX. 8" SS
EX. 8" SS
(BELOW GRADE)
(BELOW GRADE)
(CRAWL SPACE)
(CRAWL SPACE)
(CRAWL SPACE)
(CRAWL SPACE)
CONNECT NEW 2" SS (CRAWL SPACE)
TO EXISTING 8" SS (BELOW GRADE).
FIELD VERIFY EXISTING SIZE,
LOCATION AND INVERT ELEVATION.
E
F
G
H
J
K
L
M
P
Q
121110987.175432
DISCONNECT AND REMOVE
EXISTING 2" SS, LOCATED IN
CRAWL SPACE, ASSOCIATED WITH
EXISTING SINK TO BE REMOVED.
REMOVE EXISTING 2" SS BRANCH
LINE BACK TO MAIN. REFER TO
SHEET 2/M2.0 FOR NEW WORK.EX. 8" SS
BELOW GRADE
TO REMAIN.
EX. 8" SS
BELOW GRADE
TO REMAIN.
A. FIELD VERIFY EXISTING CONDITIONS PRIOR TO COMMENCING
WORK. FIELD VERIFY LOCATIONS AND SIZES OF DUCTWORK AND
PIPING AND EQUIPMENT TO BE REMOVED.
B. NOTIFY ENGINEER OF ANY DISCREPANCIES.
C. CUT AND PATCH EXISTING SURFACES (WALLS, FLOORS, AND/OR
CEILINGS) AS REQUIRED TO PERFORM WORK. PATCHING SHALL
MATCH SURROUNDING SURFACES.
D. REFER TO WASTE AND VENT RISER DIAGRAMS AND DOMESTIC
WATER RISER DIAGRAMS FOR ADDITIONAL SIZES, PIPE ROUTING,
VALVES AND PLUMBING SPECIALTY DEVICES. REFER TO SHEET
M5.1 FOR PLUMBING ROUGH IN SCHEDULE, TYPICAL.
E. PROVIDE SLEEVES OR CORE DRILLING FOR ALL PIPING PASSING
THROUGH STRUCTURAL FOOTINGS AND FOUNDATION WALLS.
REFER TO SPECIFICATION SECTION 22 0500 AND DETAIL ON SHEET
M6.1 FOR ADDITIONAL INFORMATION. COORDINATE AND VERIFY
EXACT LOCATIONS AND ELEVATIONS WITH STRUCTURAL. TYPICAL.
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW íóéÉÇLéêáåíÉ Ç=å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW
1112 North 5th Street Minneapolis, MN 55411
(612) 343-5965
1624 North Riverfront Drive Mankato, MN 56001
(507) 625-7869 ëÜÉÉí= íáíäÉW ëÜÉÉí= åìãÄÉêW
DULUTH I TWIN CITIES I VIRGINIA
www.dsgw.com
023016.00
10/06/2023
10/06/2023
EDI-DOLEJS #23-035
14204
MIKE S. DOLEJS
Wagner
Pharmacy
USP
Compliance
111 WASHINGTON AVE. NW
WAGNER, SD 57380
AE, LS
MD
M2.0
Partial
Underfloor
Plan - Phase 2 -
Plumbing
8' 16'4'0 1/8" = 1'-0"M2.0
2 Partial Underfloor Plan - Phase 2 - Plumbing
NORTHNORTH
8' 16'4'0 1/8" = 1'-0"M2.0
1 Partial Underfloor Plan - Phase 2 - Plumbing Demolition êÉîáëáçå=L áëëìÉ åçK Ç~íÉ
^aa=@N N NOLONLOP
RefrigeratorRefrigerator
PLAN NOTES
GENERAL NOTES
MEDICAL
RECORDS
OFFICE
115A
SCA
115B
PHARMACY
CONSULT
NARCOTICS
115C
ELECTRICAL
RECEIVING/HZD
STORAGE
BREAKROOM
HSKP/CLEAN
LINEN
STORAGE
TEMPORARY
PHARMACY-1
107-1
JANITOR
EYE LAB
EYEGLASS
FITTING
VISUAL
FIELDS
EYE
SCREENING
EYE EXAM
SUPPLY
INTERVIEW
ROOM
HZD WASTE
STORAGE
EEW-1
ETMV-1
INSTALL THERMOSTATIC
MIXING VALVES BELOW
THE SINK
EX. 1" HW-R
EX. 1 1/2" HW
EX. 2 1/2" CW
EX. 2 1/2" CW
EX. 1 1/2" HW
EX. 1" HW-R
3/4" HW-R
1" HW
1" CW
SK-1
SK-2
2" V
3/4" HW-R
1" HW
1" CW
2" V
3/4" CW
3/4" HW
3/4" HW-R
2" V UP
TO 4" VTR
1 1/2" V
SK-1
3/4" HW
3/4" CW
SK-33/4" HW-R
THERMOSTATIC
RECIRCULATION
VALVE ASSEMBLY.
E
F
G
H
J
K
L
M
P
Q
121110987.175432
2" FCO
2" FCO
CONNECT NEW 1" CW, 1" HW AND 3/4"
HW-R TO EXISTING 2-1/2" CW, 1-1/2"
HW AND 1" HW-R. FIELD VERIFY
EXISTING SIZE AND LOCATION.
DISCONNECT AND REMOVE EXISTING
PLUMBING FIXTURE AND ASSOCIATED CW,
HW, WASTE AND VENT BACK TO MAINS AND
CAP. REFER TO DETAIL 2/M2.1 FOR NEW
WORK
E
F
G
H
J
K
L
M
P
Q
121110987.175432
DISCONNECT AND REMOVE EXISTING
CLEANOUT AND ASSOCIATED PIPING BACK
TO MAINS AND CAP. REFER TO DETAIL
2/M2.1 FOR NEW WORK
A. PROVIDE A WALL OR FLOOR CLEANOUT AS REQUIRED TO SERVE
EACH PLUMBING FIXTURE, SPECIALITY DEVICE, ETC. THAT HAS A
NON-ACCESSIBLE TRAP, TYPICAL.
B. PROVIDE A WALL CLEANOUT AT THE VERTICAL DRAIN, TO SERVE
EACH SINK, IN ACCORDANCE WITH CODE REQUIREMENTS.
TYPICAL.
C. PROVIDE A WALL CLEANOUT AT THE VERTICAL DRAIN, ABOVE THE
WASTE CONNECTION TO EACH URINAL IN ACCORDANCE WITH
CODE REQUIREMENTS. TYPICAL.
D. REFER TO PIPE HANGER AND SUPPORT DETAIL ON SHEET M6.1
INDICATING INSTALLATION REQUIREMENTS, TYPICAL.
E. REFER TO PIPE PENETRATION DETAIL ON SHEET M6.1 FOR PIPE
PENETRATION INSTALLATION REQUIREMENTS, TYPICAL.
F. REFER TO WASTE AND VENT RISER DIAGRAMS AND DOMESTIC
WATER RISER DIAGRAMS FOR ADDITIONAL SIZES, PIPE ROUTING,
VALVES AND PLUMBING SPECIALITY DEVICES. REFER TO SHEET
M5.1 FOR PLUMBING ROUGH-IN SCHEDULE. TYPICAL.
1. INDICATES PLUMBING FIXTURE OR PLUMBIG SPECIALTY DEVICE
IDENTIFICATION. PROVIDE PLUMBING ROUGH-INS AND FINAL
CONNECTIONS. REFER TO SPECIFICATION DIVISION 22 FOR MODEL,
DESCRIPTION, ACCESSORIES, ETC. REFER TO PLUMBING ROUGH-IN
SCHEDULE FOR ROUGH-IN SIZES, TYPICAL.
2. SHUT-OFF VALVE, TYPICAL, UNLESS OTHERWISE NOTED.
3. THERMOSTATIC RECIRCULATION VALVE ASSEMBLY. REFER TO
DIVISION 22 SPECIFICATION AND DETAIL FOR ADDITIONAL
INFORMATION AND REQUIREMENTS.
4. REFER TO DETAIL ON SHEET M6.1 FOR ADDITIONAL INFORMATION
AND REQUIREMENTS.
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW íóéÉÇLéêáåíÉ Ç=å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW
1112 North 5th Street Minneapolis, MN 55411
(612) 343-5965
1624 North Riverfront Drive Mankato, MN 56001
(507) 625-7869 ëÜÉÉí= íáíäÉW ëÜÉÉí= åìãÄÉêW
DULUTH I TWIN CITIES I VIRGINIA
www.dsgw.com
023016.00
10/06/2023
10/06/2023
EDI-DOLEJS #23-035
14204
MIKE S. DOLEJS
Wagner
Pharmacy
USP
Compliance
111 WASHINGTON AVE. NW
WAGNER, SD 57380
AE, LS
MD
M2.1
Partial Floor
Plan - Phase 2 -
Plumbing
NORTH
8' 16'4'0 1/8" = 1'-0"M2.1
2 Partial Floor Plan - Phase 2 - Plumbing
NORTH
8' 16'4'0 1/8" = 1'-0"M2.1
1 Partial Floor Plan - Phase 2 - Plumbing Demolition êÉîáëáçå=L
GENERAL NOTES
SK-3
3/4" ETMVEEW-1
3/4" CW
3/4" HW
3/4" HW-R
SHUT OFF VALVE,
TYPICAL UNLESS
OTHERWISE NOTED.
THERMOSTATIC
RECIRCULATION
VALVE ASSEMBLY.
THERMOSTATIC
RECIRCULATION
VALVE ASSEMBLY.
SK-1
3/4" CW
3/4" HW
3/4" HW-R
SK-2
1" CW
1" HW
3/4" HW-R
1" CW
1" HW
3/4" HW-R
SK-1
SHUT OFF VALVE,
TYPICAL UNLESS
OTHERWISE NOTED.
EX. 2 1/2" CW
EX. 1 1/2" HW
EX. 1 1/2" HW
EX. 2 1/2" CW
EX. 1" HW-REX. 1" HW-R
EX. 8" SS
EX. 8" SS
8" SS
SK-1
SK-3
2" SS
2" FCO
2" SS
SK-2
SK-1
2" FCO
2" V
1 1/2" V
2" V
4" VTR
2" SS
A. PROVIDE A WALL OR FLOOR CLEANOUT AS REQUIRED TO SERVE
EACH PLUMBING FIXTURE. SPECIALTY DEVICE, ETC. THAT HAS A
NON-ACCESSIBLE TRAP, TYPICAL.
B. PROVIDE A CLEANOUT AT THE BASE OF EACH WASTE STACK,
TYPICAL.
C. REFER TO DIVISION 22 SPECIFICATIONS FOR ADDITIONAL
REQUIREMENTS, TYPICAL.
D. PROVIDE WATER HAMMER ARRESTORS ON HOT AND COLD WATER
PIPING SERVING SENSORED FAUCETS AND FLUSH VALVE ON QUICK
CLOSING DEVICES. REFER TO DIVISION 22 SPECIFICATIONS FOR
ADDITIONAL INFORMATION AND REQUIREMENTS, TYPICAL.
E. FIELD VERIFY EXISTING CONDITIONS FRIOR TO COMMENCING
WORK.
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW íóéÉÇLéêáåíÉ Ç=å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW
1112 North 5th Street Minneapolis, MN 55411
(612) 343-5965
1624 North Riverfront Drive Mankato, MN 56001
(507) 625-7869 ëÜÉÉí= íáíäÉW ëÜÉÉí= åìãÄÉêW
DULUTH I TWIN CITIES I VIRGINIA
www.dsgw.com
023016.00
10/06/2023
10/06/2023
EDI-DOLEJS #23-035
14204
MIKE S. DOLEJS
Wagner
Pharmacy
USP
Compliance
111 WASHINGTON AVE. NW
WAGNER, SD 57380
AE, LS
MD
M2.2
Plumbing Riser
Diagrams
NOT TO SCALEM2.2
2 DOMESTIC WATER RISER DIAGRAM
NOT TO SCALEM2.2
1 PLUMBING RISER DIAGRAM - WASTE AND VENT
RECEIVING/HZD
STORAGE
BREAKROOM
SCA
115B
PHARMACY
RECEIVING/HZD
STORAGE
BREAKROOM
SCA
115B
PHARMACY
êÉîáëáçå=L áëëìÉ åçK Ç~íÉ
^aa=@N N NOLONLOP
Refrigerator
T S
T S
TS
T S
TS
T S
U.C.
Refr.
Refrigerator
TS
TS
T S
T H
TS
SS
T S
S
TH
GENERAL NOTES
PLAN NOTES
EX.VAV TU-57
EX.VAV TU-58
EX.VAV TU-54
G
J
L
M
Q
12108742
CAP
CAP
MEDICAL
RECORDS
OFFICE
115A
SCA
115B
PHARMACY
CONSULT
114 NARCOTICS
115C
ELECTRICAL
RECEIVING/HZD
STORAGE
BREAKROOM
HSKP/CLEAN
LINEN
STORAGE
TEMPORARY
PHARMACY-1
107-1
JANITOR
EYE LAB
EYEGLASS
FITTING
VISUAL
FIELDS
EYE
SCREENING
EYE EXAM
SUPPLY
INTERVIEW
ROOM
HZD WASTE
STORAGE
OFFICE
133A
VAV TU-59 VAV TU-60
VAV TU-61
VAV TU-57
VAV TU-54
VAV TU-57-1
VAV TU-58
G
J
L
M
Q
128742
CONNECT 3/4"
HWS AND HWR TO
EXISTING 1 1/4"
HWS AND HWR.
FIELD VERIFY
EXSITING
CONDITIONS
3/4" CONDENSATE
DRAIN TO SINK
TAILPIECE
3/4" CONDENSATE DRAIN
TO SINK TAILPIECE
DH-2
DH-1
CORRIDOR
1. DISCONNECT AND REMOVE EXISTING VAV AND ASSOCIATED PIPING,
HANGERS, SUPPORTS AND CONTROLS BACK TO MAIN. REFER TO
DETAIL 2/M3.2 FOR NEW WORK.
2. EXISTING VAV TO REMAIN.
3. DISCONNECT AND REMOVE EXISTING TEMPERATURE SENSOR AND
ASSOCIATED WIRING. REFER TO DETAIL 2/M3.2 FOR NEW WORK.
4. AIR PRESSURE DIFERENTIAL INDICATING TRANSMITTER, SWITCH,
AND CONTROLLER. REFER TO SPECIFICATION 23 0993 FOR
SEQUENCE OF OPERATION.
5. CONNECT 3/4" HWS AND HWR TO EXISTING 3/4" HWS AND HWR.
FIELD VERIFY EXSITING CONDITIONS.
A. REFER TO SHEET M6.1 FOR PIPE HANGER AND SUPPORT
INSTALLATION REQUIREMENTS. TYPICAL.
B. REFER TO SHEET M6.1 FOR PIPE PENETRATION DETAIL INDICATING
INSTALLATION REQUIREMENTS. TYPICAL.
C. ALL RUNOUTS TO VAV BOX REHEAT COILS, SHALL BE 3/4" UNLESS
OTHERWISE NOTED.
D. UPGRADE THE EXISTING BUILDING AUTOMATION SYSTEM HEAD
END EQUIPMENT TO THE NEW JOHNSON CONTROLS METASYS
USER INTERFACE THROUGHOUT THE ENTIRE FACILITY. REFER TO
SPECIFICATION SECTION 230900 FOR ADDITIONAL INFORMATION.
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW íóéÉÇLéêáåíÉ Ç=å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW
1112 North 5th Street Minneapolis, MN 55411
(612) 343-5965
1624 North Riverfront Drive Mankato, MN 56001
(507) 625-7869 ëÜÉÉí= íáíäÉW ëÜÉÉí= åìãÄÉêW
DULUTH I TWIN CITIES I VIRGINIA
www.dsgw.com
023016.00
10/06/2023
10/06/2023
EDI-DOLEJS #23-035
14204
MIKE S. DOLEJS
Wagner
Pharmacy
USP
Compliance
111 WASHINGTON AVE. NW
WAGNER, SD 57380
AE, LS
MD
M3.2
Partial Floor
Plan - Phase 2 -
Piping
NORTHNORTH
8' 16'4'0 1/8" = 1'-0"M3.2
1 Partial Floor Plan - Phase 2 - Piping Demolition
8' 16'4'0 1/8" = 1'-0"M3.2
2 Partial Floor Plan - Phase 2 - Piping êÉîáëáçå=L áëëìÉ åçK Ç~íÉ
A. ALL LIGHT FIXTURE LUMEN VALUES LISTED ARE DELIVERED LUMEN.
B. REFER TO DETAILS FOR INDEPENDENTLY SUPPORTING OF LIGHT FIXTURES LOCATED IN ACOUSTICAL TILE CEILINGS.
C. ALL LED DRIVERS SHALL BE 0-10 VOLT DIMMING DRIVER UNLESS NOTED OTHERWISE.
D. ALL ADDITIONAL HARDWARE FOR MOUNTING OF SURFACE, RECESSED, OR PENDANT FIXTURES SHALL BE INCLUDED UNDER THIS CONTRACT.
E. REFER TO THE MANUFACTURES INSTALLATION INSTRUCTIONS FOR THE MOUNTING REQUIREMENTS OF EACH FIXTURE TYPE PRIOR TO THE INSTALLATION OF THE FIXTURES. GOOD WORKMANSHIP SHALL BE EVIDENT IN THE FINISHED INSTALLATION OR THE ELECTRICAL CONTRACTOR WILL BE REQUIRED TO CORRECT THE POOR WORKMANSHIP AT NO ADDITIONAL COST TO THE OWNER.
F. EMERGENCY FIXTURES SHALL BE PROVIDED WITH AN INTEGRAL ILLUMINATED TEST SWITCH.
G. REFER TO SPECIFICATION SECTION 26 5100 - INTERIOR LIGHTING, FOR ADDITIONAL FIXTURE REQUIREMENTS.
H. REFER TO SPECIFICATION SECTION 25 5600 - EXTERIOR LIGHTING, FOR ADDITIONAL FIXTURE REQUIREMENTS.
I. COORDINATE WITH ARCHITECTURAL CEILING GRID TYPE WITH FIXTURES SPECIFIC GRID TYPE MOUNTING.
GENERAL NOTES:
1. PROVIDE WITH LONG LIFE NICKEL CADMIUM BATTERY.
2. PROVIDE WITH EMERGENCY BACK UP RATED FOR MINIMUM OF 90 MINUTES RUNTIME.
3. EMERGENCY BATTER PACK TO CONTROL 4' LENGTH/S AS SHOWN ON PLANS.
4. PAINT AFTER FABRICATION.
5. PROVIDE FIXTURE WITH DRYWALL FRAME KIT OPTION.
6. CUSTOM COLOR FINISH SELECTED BY OWNER/ARCHITECT.
SCHEDULE NOTES:
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
2-SPD TWO SPEED
VFD VARIABLE FREQUENCY DRIVE
RVS REDUCED VOLTAGE
STARTER TYPES:
FS FUSED SWITCH
NFS NON-FUSED SWITCH
MCP MOTOR CIRCUIT PROTECTOR
CB CIRCUIT BREAKER
COMBINATION DISCONNECT TYPES:
HOA HAND-OFF-AUTO SWITCH
RP RED (RUN) PILOT LIGHT
GP GREEN (POWER) PILOT LIGHT
0/0 ON-OFF SELECTOR SWITCH
S/S STOP-START PUSHBUTTONS
CONTROL DEVICES:
EC ELECTRICAL CONTRACTOR
MC MECHANICAL CONTRACTOR
GC GENERAL CONTRACTOR
TC TEMPERATURE CONTROL
OWN OWNER
ABBREVIATIONS:
MOTOR NOTES:
GENERAL:
A. ALL WORK BY THIS CONTRACTOR TO COMPLY WITH ALL LOCAL, STATE AND NATIONAL ELECTRICAL CODES.
B. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION WITH OTHER TRADES TO AVOID CONFLICTS AND TO VERIFY ALL EQUIPMENT CONNECTION REQUIREMENTS.
C. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING A COMPLETE…
This is the start of the file's text. The full file is on GovTribe.