This document is an Addendum 4 to the construction documents for the Wagner Pharmacy USP Compliance project. The addendum revises Section 10 26 01 for Corner Guards, including specifications for the stainless steel corner guards, such as 3-inch wing size, eased corners, and 8-foot length to be installed throughout the building. It also references the related federal contract opportunity, Solicitation Number 75H70124R00025, which is for the renovation of the existing outpatient pharmacy at the Wagner IHS Healthcare Facility to meet the latest United States Pharmacopeia (USP) compounding standards. The solicitation is being issued by the Department of Health and Human Services Indian Health Service.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2 West 1st Street, Suite 201, Duluth, Minnesota 55802 tel (218) 727-2626 fax (218) 722-7467
ADDENDUM 4
project Wagner Pharmacy USP Compliance project # 023016.01 date 05/30/24 from DSGW Architects to All planholders for above project
The following addendum shall become part of the construction documents for the construction of the above referenced project.
This addendum supersedes and supplements all previous reference to similar items.
I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am duly a Licensed Architect under the laws of the State of Minnesota.
Signature
Registration # 14817 Date 05/30/24 general clarifications 1. None specifications SECTION DESCRIPTION
10 26 01
1. Revise section 10 26 01 Corner Guards per attached reissued section 10 26 01 drawings SECTION DESCRIPTION
None mechanical / electrical consultant enclosures J Spec section 10 26 01
This addendum shall become part of this bid. The bidder shall insert the addendum number in the space were indicated on the proposal form. Failure to comply may result in the bid being rejected.
END OF ADDENDUM 4
23016.10 – Wagner Pharmacy USP Compliance
10 26 01 - 1 CORNER GUARDS – REVISED
ADDENDUM #4
SECTION 10 26 01
CORNER GUARDS - REVISED
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Corner guards.
PART 2 PRODUCTS
2.01 MANUFACTURERS
A. Corner Guards: SS
1. Inpro SS Corner Guards
2. Material: SS – Standard Type 460 Stainless Steel
3. Width of Wings: 3 inches.
4. Corner: Eased
5. Color: SS
6. Length: One piece, above base to ceiling 8 Foot
7. Installation: Standard
8. Substitutions: See Section 01 60 00 - Product Requirements.
2.02 FABRICATION
A. Fabricate components with tight joints, corners and seams.
PART 3 EXECUTION
3.01 EXAMINATION
A. Verify that rough openings, concealed blocking, and anchors are correctly sized and located.
3.02 INSTALLATION
A. Install components in accordance with manufacturer's instructions, level and plumb, secured rigidly in position to wall framing members only.
B. Position corner guard recommended inches above finished floor to recommended inches high.
C. Schedule: Provide corner guards at all interior outside corners throughout the building. SS shall be selected for use throughout. Provide a total of 9 Corner Guards.
3.03 SCHEDULE
A. Inpro Surface Mount Stainless Steel Corner Guard
1. 3" wing size
2. 16 Gauge (Standard)
3. Heights: 8’
B. Inpro 800 Model Handrails w/wall returns
1. 5 ½” height x 1 ½” gripping diameter, extends 3” from the wall.
2. Color: To be selected.
3. .080” (2mm) vinyl cover.
END OF SECTION