J01b Drawings.pdf
PDF 14 MB Posted
- Solicitation number
- 75H70124R00025
About this file
The provided document is a set of drawings and plans related to the renovation of the existing outpatient pharmacy at the Wagner IHS Healthcare Facility located in Wagner, South Dakota. The key details are:
The federal contract opportunity is a Solicitation from the Department of Health and Human Services Indian Health Service to renovate the existing outpatient pharmacy at the Wagner IHS Healthcare Facility to meet the latest United States Pharmacopeia (USP) compounding standards. The Solicitation Number is 75H70124R00025. The drawings and plans provided appear to be part of the technical requirements for the renovation project.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
OWNER ARCHITECT
DSGW Architects
2 West First St. Suite 201
Duluth, MN 55802
Phone: 218-727-2626
Contact: Ryan Turner, AIA, ACHA, EDAC Email: rturner@dsgw.com
Great Plains Area Indian Health Services
Office of Enviromental Health and Engineering
115 4th Av. SE, Room 309 Aberdeen, SD 57401
Phone: 605-266-7581
Contact: Kurt Petersen
Email: kurt.petersen@ihs.gov
MECH/ELECT. ENGINEER
EDI-Dolejs Consulting Engineers
1112 North 5th Street
Minneapolis, MN 55411
Phone: 612-343-5965
Contact: Jay Hruby, PE Email: jhruby@edi-dolejs.com
Project Team
EARTH
COMPACT FILL/SAND
POROUS FILL/GRAVEL
FACE BRICK
MORTAR/PLASTER
CMU
CONCRETE
RIGID INSULATION
BATT INSULATION
STUD WALL/METAL
PLYWOOD
GYPSUM BOARD
FINISHED WOOD
CONT. ROUGH WOOD
WOOD BLOCKING
BITUMINOUS
Materials
Symbols
DETAIL
NUMBER
SHEET
NUMBER
AREA TO BE
DETAILED OR
ENLARGED
ACTUAL NORTH
(IF DIFFERENT)
REVISION TYPE
SHEET NUMBER
SECTION NUMBER
A8.1
MATCH LINE
SHEET
NUMBER
ELEVATION
NUMBER
A7.2
NORTH ARROW
DETAIL REFERENCESECTION REFERENCE
REVISION IDENTIFICATIONTITLE MARKER
ROOM IDENTIFICATION
ROOM NAME
ROOM NUMBER
DOOR TAG
BREAKLINE
ELEVATION REFERENCE
WALL TAGWINDOW TAG
ELEVATION LABEL MATCHLINE IDENTIFICATION NOTE IDENTIFICATION
(LEADER
OPTIONAL)
A7.1
A5.1
TOILET
ROOM
T.O. STL.
100'-0"
VIEW TITLE
VIEW SCALE
W205
1A S
I
5A
SEQUENTIAL
INDICATOR
APPROXIMATE
THICKNESS IN INCHES
N
(WHEN REQ'D)
REPRESENTS NEW
DOOR
REPRESENTS
EXISTING DOOR
TO REMAIN
REPRESENTS
EXISTING DOOR
TO BE REMOVED.
WALLS WITH
HATCH
INDICATE NEW
CONSTRUCTION
WALLS SHADED
GRAY INDICATE
EXISTING TO
REMAIN
DASHED LINES
INDICATE WALLS
& ITEMS TO BE
REMOVED.
PLAN NORTH
REVISION NUMBER
5A 48"
PARTIAL
WALL; HT
IN INCHES
MAIN
ENTRY
PHASE 1
RADIOLOGY DEPT.
PHASE 1 TEMPORARY
PHARMACY
PHASE 1 MEDICAL
RECORDS OFFICE
PHASE 2
PHARMACY
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W
Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW
DULUTH I TWIN CITIES I VIRGINIA
www.dsgw.com
14817
10/6/2023 12:46:50 PM
023016.01
BC
RT
10/06/23
Wagner Pharmacy
USP
Compliance
G0.0
Title Sheet
111 Washington Ave. NW Wagner, SD 57380
Sheet Index 0-General
G0.0 Title Sheet
4-Architectural
A1.1 DEMOLITION PLANS
A1.2 DEMOLITION PLANS
A2.1 FLOOR PLANS
A2.2 FLOOR PLANS
A2.3 ROOF PLAN
A3.1 REFLECTED CEILING PLANS
A4.1 DOOR SCHEDULE AND TYPES
A4.2 ROOM FINISH SCHEDULE AND PLANS
5-Mechanical
M0.1 MECHANICAL TITLE SHEET
M1.1 PARTIAL FLOOR PLAN - PHASE 1 & 2 - FIRE PROTECTION
M2.0 PARTIAL UNDERFLOOR PLAN - PHASE 2 - PLUMNBING
M2.1 PARTIAL FLOOR PLAN - PHASE 2 PLUMBING
M2.2 PLUMBING RISER DIAGRAMS
M3.1 PARTIAL FLOOR PLAN - PHASE 1 - PIPING
M3.2 PARTIAL FLOOR PLAN - PHASE 2 - PIPING
M4.1 PARTIAL FLOOR PLAN - PHASE 1 - HVAC
M4.2 PARTIAL FLOOR PLAN - PHASE 2 = HVAC
M5.1 MECHANICAL SCHEDULES
M6.1 MECHANICAL DETAILS
6-Electrical
E0.1 ELECTRICAL TITLE SHEET
E1.1 PARTIAL FLOOR PLANS - DEMOLITION
E2.1 PARTIAL FLOOR PLANS - LIGHTING
E3.1 PARTIAL FLOOR PLANS - POWER
E4.1 PARTIAL FLOOR PLANS - SYSTEMS
E6.1 SCHEDULES - ELECTRICAL
E6.2 SCHEDULES - ELECTRICAL
E7.1 DETAILS - ELECTRICAL
KEY PLAN
Abbreviations
Project Number:
Wagner Pharmacy USP Compliance 111 Washington Ave. NW
Wagner, SD 57380
023016.01
Architectural General Notes
1. General Notes apply to all drawing sheets.
2. Review the Construction Documents prior to start of construction. Notify Architect upon encountering any unforeseen conditions, discrepancies, errors, or inconsistencies.
3. Work shall be done in accordance with all rules and regulations of all applicable safety and building codes. The General Contractor is responsible for securing and paying for all permits required and for the scheduling of all required inspections during the course of the project.
4. The General Contractor shall take precautions and be responsible for the safety of all building occupants from construction procedures during construction to minimize disturbances to adjacent spaces and /or structures and their occupants, property, public thoroughfares, etc. Maintain all required exits during construction.
5. All materials and systems shall be installed as per manufacturer's specifications and all construction shall be of industry standard or better.
6. Do not scale drawings. Verify all dimensions in the field for accuracy prior to construction. No extra charge or compensation shall be allowed because of difference between actual dimensions and those indicated on the drawings, unless they contribute to a change in the scope of work.
7. In the event of conflict between data shown on drawings and data shown in the Specification, the Work of greater quality or quantity shall be provided, in accordance with the Architect's interpretation, and no change in the Contract Sum will be permitted. Detail drawings take precedent over drawings of larger scope. Notify Architect if at any time an error or discrepancy is discovered.
8. Immediately notify Architect of any long lead items that will affect the completion date
9. All wood in contact with concrete or concrete block to be pressure treated - typical.
10. Provide metal backing and / or treated wood blocking for all wall mounted equipment (grab bars, toilet room accessories, TV mounts, headwalls, equipment rails, etc.) Verify height and length with actual equipment.
11. Patch all disturbed fireproofing as required to maintain rating. Repair and install all fireproofing as required by code. Fireproof any new penetrations required by the work. Refer to code summary for ratings.
12. All exposed metal to receive paint unless otherwise noted
13. All adjacent dissimilar materials to receive caulking, including equipment mounted to walls
ADJ ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
ALT ALTERNATE
ALUM ALUMINUM
APPROX APPROXIMATE
ARCH ARCHITECT
B.O. BOTTOM OF
B.SPLASH BACKSPLASH
BLDG BUILDING
BLKG BLOCKING
BRG BEARING
C-TOP COUNTERTOP
CG CORNER GUARD
CJ CONTROL JOINT
CLG CEILING
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONT CONTINOUS
CPT CARPET
CT CERAMIC TILE
D DEEP
DIA DIAMETER
DIM DIMENSION
DISP DISPENSER
DN DOWN
DS DOWNSPOUT
DW DISHWASHER
EA EACH
EIFS EXTERIOR INSULATION & FINISH SYSTEM
EJ EXPANSION JOINT
ELEC ELECTRICAL
EPDM ETHYLENE PROPYLENE DIENE TERPOLYMER
ROOFING
EQ EQUAL
EQUIP / EQPT. EQUIPMENT
EXST / EX. / EXIST. EXISTING
F.T. FIRE TREATED
F.V. FIELD VERIFY
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FFGB FIBERGLASS FACED GYPSUM BOARD
FLR FLOOR
FRP FIBERGLASS REINFORCED PANEL
FTG FOOTING
FUR FURRING
GALV GALVANIZED
GB GRAB BAR
GLAZ GLAZING
GYP. BD. / G.BD / GBD GYPSUM BOARD
HC HANDICAPPED
HM HOLLOW METAL
HT HEIGHT
ICF INSULATED (OR INSULATING) CONCRETE FORM
INSUL INSULATION
JST JOIST
LAM LAMINATE
LVT LUXURY VINYL TILE
MAX MAXIMUM
MECH MECHANICAL
MIN MINIMUM
MISC MISCELLANEOUS
MTL METAL
NIC NOT IN CONTRACT
NTS NOT TO SCALE
OC ON CENTER
OPCI OWNER PROVIDED CONTACTOR INSTALLED
P.T. PRESSURE TREATED
PC PRECAST
PLAM / P.LAM. PLASTIC LAMINATE
PLYWD PLYWOOD
PNT PAINT
PTD PAPER TOWEL DISPENSER
QT QUARRY TILE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REF REFRIGERATOR
REINF REINFORCED
REQD REQUIRED
RPF STRIP REINFORCED PERIMETER FASTENING STRIP
RTU ROOF TOP UNIT (MECH.)
RWL RAIN WATER LEADER
S.SPLASH SIDESPLASH
SACT SUSPENDED ACOUSTICAL CEILING TILE
SCHED SCHEDULE
SD SOAP DISPENSER
SEAL SEALANT
SF SQUARE FOOT (FEET)
SIM SIMILAR
SIP STRUCTURAL INSULATED (OR INSULATING)
PANEL
SND SANITARY NAPKIN DISPOSAL
SPEC SPECIFICATION
SS STAINLESS STEEL
SSM SOLID SURFACE MATERIAL
STL STEEL
STRUCT STRUCTURAL CONSULTANT
T.O. TOP OF
TBB TILE BACKER BOARD
TP TOILET PAPER
TRTD TREATED
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VB VINYL BASE
VCT VINYL COMPOSITION TILE
VIF VERIFY IN FIELD
VWC VINYL WALL COVERING
W/ WITH
W/O WITHOUT
WD WOOD
WRB WEATHER RESISTIVE BARRIER
êÉîáëáçå=L áëëìÉ åçK Ç~íÉ
D AE RR CE HT IS TI EG CE TR
. NG OE .R
14817
RYAN
TURNER
EYE EXAM
SUPPLY
JANITOR
HZD WASTE
STORAGE
EYE SCREENING
VISUAL FIELDS
VESTIBULE
W1
W2
C1
C1
CLOSET
OPEN
OFFICE
D1
SPECIMEN
TOILET
SUPPLY
TOILET
ULTRASOUND
CORRIDOR
SUPPLY
DARK ROOM
OFFICE
DRESSING
DRESSING
FILM READING
WORK AREA
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W
Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW
DULUTH I TWIN CITIES I VIRGINIA
www.dsgw.com
14817
10/6/2023 12:46:40 PM
023016.01
BC
RT
10/06/23
Wagner Pharmacy
USP
Compliance
A1.1
DEMOLITION
PLANS
111 Washington Ave. NW Wagner, SD 57380
1/4" = 1'-0"
DEMOLITION PLAN - PHASE 1 -
TEMPORARY PHARMACY
1/4" = 1'-0"
DEMOLITION PLAN - PHASE 1 -
RADIOLOGY DEPT.
Demo Plan Notes
C1 DEMO EXISTING CASEWORK SHELVING
C2 DEMO EXISTING WALL CABINETS AND GYP BD SOFFIT
C3 DEMO EXISTING COUNTER TOP AND BASECABINETS
C4 DEMO EXISTING TALL STORAGE CABINET AND GYP BD SOFFIT ABOVE
C5 REMOVE AND RELOCATE TALL OPEN SHELVING CABINET TO PHASE 1 TEMPORARY PHARMACY
D1 DEMO INTERIOR DOOR, FRAME, AND HARDWARE
F1 DEMO VCT FLOORING, VINYL BASE, AND SUSPENDED ACOUSTICAL CEILING TILE
F2 DEMO SUSPENDED ACOUSTICAL TILE CEILING
F3 DEMO VCT FLOORING, VINYL BASE AND SUSPENDED ACOUSTICAL TILE CEILING WHERE REMODELING OCCURS
G1 DEMO INTERIOR HOLLOW METAL FRAMED WINDOW
W1 DEMO PORTION OF EXISTING WALL AS REQUIRED FOR NEW DOOR OPENING
W2 DEMO PORTION OF EXISTING WALL AS REQUIRED FOR NEW TRANSACTION WINDOW
Z1 REMOVE & SALVAGE EXISTING HIGH-DENSITY MOBILE SHELVING FOR RELOCATION TO PHASE 1 TEMPORARY
PHARMACY
Z2 DEMO EXISTING TRANSACTION WINDOW AND SILL
Z3 REMOVE AND SALVAGE EXISTING WILL CALL STORAGE HANGERS ON WALL STANDARDS FOR RELOCATION
Z4 DEMO EXISTING PASS-THRU DOOR
Z5 DEMO EXISTING HOOD, REMOVE HEPA FILTER AND SALVAGE FOR SCRAP
Z6 DEMO EXISTING TV AND BRACKET, SALVAGE FOR RELOCATION
Z7 REMOVE AND SALVAGE WALL MOUNTED ITEMS SUCH AS WHITEBOARDS, LITERATURE RACKS AND SIGNAGE FOR
RELOCATION
Z8 REMOVE AND RELOCATE PYXIS SAFE TO PHASE 1 TEMPORARY PHARMACY
Z9 REMOVE AND RELOCATE SCRIPTPRO TO PHASE 1 TEMPORARY PHARMACY, CONTRACTOR TO SUBCONTRACT WITH
SCRIPTPRO FOR MOVING AND CALIBRATING EQUIPMENT
Z10 <varies>
Demo General Notes
1. Demolition notes and plans are provided as a guide only. Contractor to verify existing conditions and examine drawings and details to determine extent and limits of demolition to accommodate new construction.
2. Contractor is responsible for coordination of all aspects of demolition and reconstruction. Contractor to coordinate new work plan dimensions and installation of new materials and finishes, as required, whether indicated on drawings or not.
3. Demolition notes without leaders indicate that the note applies to the entire room.
4. Contractors shall coordinate all demolition work phasing and sequencing with owner prior to start of construction.
5. Verify existing wall type at wall infill or wall extension areas. If existing wall type does not match the called out wall type, infill or extend to match existing wall type instead.
6. Verify existing wall materials to be removed (gypsum board, stud, cmu, brick, etc.).
7. Provide transition strip at areas of new flooring meeting existing flooring and at new door openings in existing walls. Patch floor as required.
8. Prep floors as needed for new finishes.
9. Remove existing wall mounted items such as grab bars, mirrors, paper towel dispensers, toilet paper dispensers, soap dispensers, toilet partitions, etc in demolished areas. Patch existing walls as required.
10. Patch subfloor, walls, & ceilings disturbed by demolition. Patch to match existing finishes as required.
11. Remove all finishes, adhesives, or other materials that conflict with new finishes scheduled in existing or newly remodeled spaces.
12. Verify any items to be retained for owners use prior to removal.
13. Provide protection and be responsible for Owner's equipment, furniture and any existing finishes to remain and repair or replace any damaged areas as a result of the work. All existing finishes to remain shall be cleaned at the completion of construction. Document any existing conditions or damages prior to the start of construction.
Z1 êÉîáëáçå=L áëëìÉ åçK Ç~íÉ
D AE RR CE HT IS TI EG CE TR
. NG OE .R
14817
R e fr ig e ra to r
Z3
PHARMACY
OFFICE
CONSULT
OFFICE
OFFICE
OFFICE
ELEC
MEDICAL
RECORDS
SCA
CORRIDOR
CORRIDOR
CORRIDOR
Z8
Z9
Z10
C5
C5 C5
Z10
Z2
C2
C2
C3
C2Z4
C3
C4
C4
Z5
Z6
PHARMACY
OFFICE
CONSULT
OFFICE
OFFICE
OFFICE
ELEC
MEDICAL
RECORDS
SCA
CORRIDOR
CORRIDOR
CORRIDOR
D1
D1 D1
D1
D1 D1
D1
D1
Z7
Z7
F1
F1
F1
F1
F1
F1
F2
F3
W1
W1W1 G1
G1
Z10
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W
Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW
DULUTH I TWIN CITIES I VIRGINIA
www.dsgw.com
14817
10/6/2023 12:46:42 PM
023016.01
BC
RT
10/06/23
Wagner Pharmacy
USP
Compliance
A1.2
DEMOLITION
PLANS
111 Washington Ave. NW Wagner, SD 57380 êÉîáëáçå=L áëëìÉ åçK Ç~íÉ
1/4" = 1'-0"
DEMOLITION PLAN - PHASE 1 -
PHARMACY
1/4" = 1'-0"
DEMOLITION PLAN - PHASE 2 -
PHARMACY
Demo General Notes
1. Demolition notes and plans are provided as a guide only. Contractor to verify existing conditions and examine drawings and details to determine extent and limits of demolition to accommodate new construction.
2. Contractor is responsible for coordination of all aspects of demolition and reconstruction. Contractor to coordinate new work plan dimensions and installation of new materials and finishes, as required, whether indicated on drawings or not.
3. Demolition notes without leaders indicate that the note applies to the entire room.
4. Contractors shall coordinate all demolition work phasing and sequencing with owner prior to start of construction.
5. Verify existing wall type at wall infill or wall extension areas. If existing wall type does not match the called out wall type, infill or extend to match existing wall type instead.
6. Verify existing wall materials to be removed (gypsum board, stud, cmu, brick, etc.).
7. Provide transition strip at areas of new flooring meeting existing flooring and at new door openings in existing walls. Patch floor as required.
8. Prep floors as needed for new finishes.
9. Remove existing wall mounted items such as grab bars, mirrors, paper towel dispensers, toilet paper dispensers, soap dispensers, toilet partitions, etc in demolished areas. Patch existing walls as required.
10. Patch subfloor, walls, & ceilings disturbed by demolition. Patch to match existing finishes as required.
11. Remove all finishes, adhesives, or other materials that conflict with new finishes scheduled in existing or newly remodeled spaces.
12. Verify any items to be retained for owners use prior to removal.
13. Provide protection and be responsible for Owner's equipment, furniture and any existing finishes to remain and repair or replace any damaged areas as a result of the work. All existing finishes to remain shall be cleaned at the completion of construction. Document any existing conditions or damages prior to the start of construction.
Demo Plan Notes
C1 DEMO EXISTING CASEWORK SHELVING
C2 DEMO EXISTING WALL CABINETS AND GYP BD SOFFIT
C3 DEMO EXISTING COUNTER TOP AND BASECABINETS
C4 DEMO EXISTING TALL STORAGE CABINET AND GYP BD SOFFIT ABOVE
C5 REMOVE AND RELOCATE TALL OPEN SHELVING CABINET TO PHASE 1 TEMPORARY PHARMACY
D1 DEMO INTERIOR DOOR, FRAME, AND HARDWARE
F1 DEMO VCT FLOORING, VINYL BASE, AND SUSPENDED ACOUSTICAL CEILING TILE
F2 DEMO SUSPENDED ACOUSTICAL TILE CEILING
F3 DEMO VCT FLOORING, VINYL BASE AND SUSPENDED ACOUSTICAL TILE CEILING WHERE REMODELING OCCURS
G1 DEMO INTERIOR HOLLOW METAL FRAMED WINDOW
W1 DEMO PORTION OF EXISTING WALL AS REQUIRED FOR NEW DOOR OPENING
W2 DEMO PORTION OF EXISTING WALL AS REQUIRED FOR NEW TRANSACTION WINDOW
Z1 REMOVE & SALVAGE EXISTING HIGH-DENSITY MOBILE SHELVING FOR RELOCATION TO PHASE 1 TEMPORARY
PHARMACY
Z2 DEMO EXISTING TRANSACTION WINDOW AND SILL
Z3 REMOVE AND SALVAGE EXISTING WILL CALL STORAGE HANGERS ON WALL STANDARDS FOR RELOCATION
Z4 DEMO EXISTING PASS-THRU DOOR
Z5 DEMO EXISTING HOOD, REMOVE HEPA FILTER AND SALVAGE FOR SCRAP
Z6 DEMO EXISTING TV AND BRACKET, SALVAGE FOR RELOCATION
Z7 REMOVE AND SALVAGE WALL MOUNTED ITEMS SUCH AS WHITEBOARDS, LITERATURE RACKS AND SIGNAGE FOR
RELOCATION
Z8 REMOVE AND RELOCATE PYXIS SAFE TO PHASE 1 TEMPORARY PHARMACY
Z9 REMOVE AND RELOCATE SCRIPTPRO TO PHASE 1 TEMPORARY PHARMACY, CONTRACTOR TO SUBCONTRACT WITH
SCRIPTPRO FOR MOVING AND CALIBRATING EQUIPMENT
Z10 <varies>
D AE RR CE HT IS TI EG CE TR
. NG OE .R
14817
Refrigerator
STERILE
DRUG INFO
EYE EXAM
SUPPLY
JANITOR
HSKP/CLEAN
LINEN
HZD WASTE
STORAGE
EYE SCREENING
VESTIBULE
TEMPORARY
PHARMACY
DISPENSING
4 5
8'-0"
133B
OFFICE5B
5B
H M
-W
HM-W1
TA
-W
133B
MEDICAL
RECORDS
106B
MAIN
CORRIDOR
2'-0"
WOMEN TOILET
VENI
SPECIMEN
TOILET
SUPPLY
TOILET
ULTRASOUND
CORRIDOR
SUPPLY
DARK ROOM
OFFICE
DRESSING
DRESSING
FILM READING
WORK AREA
NEW SHEET VINYL
TO MATCH EXISTING
EXISTING FLOOR
TO REMAIN
NEW PAINT AND
VINYL BASE TO MATCH
EXISTING,
EXISTING COVE BASE
MANUFACTUER: VPI
COLOR: LONDON GRAY
EXISTING SHEET VINYL FLOOR
MANUFACTUER: CONGOLEUM
STYLE AND COLOR: AIR STEP
ADVANTAGE REMINISCE
CATCHING FIREFLIES
Wall Types
5A
3 5/8" METAL STUD
@ 16" O.C.
5/8" GYP.BD. EA. SIDE
BATT INSULATION
METAL STUD WALL TO
STRUCTURE
5B
OMIT BATT INSULATION, GYP BD
TO EXTEND TO 6" ABOVE CEILING
3 5/8" METAL STUD
CHANNEL
3 5/8" METAL STUD
DEFLECTION TRACK
BASE - SEE
SCHEDULE
ROOF OR FLOOR
STRUCTURE
CLG WHERE APPLICABLE;
SEE RCP
1A
5/8" GYP.BD.
FURRING OVER
EXISTING WALL TO
STRUCTURE
BASE - SEE
SCHEDULE
ROOF OR FLOOR
STRUCTURE
CLG WHERE
APPLICABLE; SEE
RCP
3A
3 5/8" METAL STUD @
16" O.C.
5/8" GYP.BD.
FURRING OVER
EXISTING WALL TO
STRUCTURE
3 5/8" METAL STUD
CHANNEL
BASE - SEE SCHEDULE
ROOF OR FLOOR
STRUCTURE
CLG WHERE APPLICABLE;
SEE RCP
3 5/8" METAL STUD
DEFLECTION TRACK
ACOUSTIC SEALANT
EA. SIDE
ACOUSTIC SEALANT
NOTE: ALL WALLS SHALL BE BUILT TO STRUCTURE ABOVE UNLESS OTHERWISE NOTED
7/8" 4 3/8"
4 7/8"
SECTION
@ FLOOR
SECTION
@ HEAD
SECTION
@ FLOOR
PLAN
VIEW
SECTION
@ HEAD
SECTION
@ FLOOR
PLAN
VIEW
SECTION
@ HEAD
SECURITY BARRIER
MESH
SECURITY BARRIER
MESH
EXTEND EXISTING WALL
TO STR ABOVE: 3 5/8"
METAL STUD @ 16" O.C.
EXISTING WALL
1B
5/8" GYP.BD.
FURRING OVER
EXISTING WALL TO
STRUCTURE
BASE - SEE
SCHEDULE
ROOF OR FLOOR
STRUCTURE
CLG WHERE
APPLICABLE; SEE
RCP
7/8"
SECTION
@ FLOOR
SECTION
@ HEAD
SECURITY BARRIER
MESH
EXISTING WALL
5C
3 5/8" METAL STUD
@ 16" O.C.
5/8" GYP.BD. EA. SIDE
BATT INSULATION
METAL STUD WALL TO
STRUCTURE W/
SECURITY BARRIER
MESH
3 5/8" METAL STUD
CHANNEL
3 5/8" METAL STUD
DEFLECTION TRACK
BASE - SEE
SCHEDULE
ROOF OR FLOOR
STRUCTURE
CLG WHERE APPLICABLE;
SEE RCP
ACOUSTIC SEALANT
EA. SIDE
5 1/8"
SECTION
@ FLOOR
PLAN
VIEW
SECTION
@ HEAD
SECURITY BARRIER
MESH
5D
3 5/8" METAL STUD
@ 16" O.C.
5/8" GYP.BD. EA. SIDE
BATT INSULATION
METAL STUD WALL TO
STRUCTURE W/
BULLET RESISTANT
PANEL
3 5/8" METAL STUD
CHANNEL
3 5/8" METAL STUD
DEFLECTION TRACK
BASE - SEE
SCHEDULE
ROOF OR FLOOR
STRUCTURE
CLG WHERE APPLICABLE;
SEE RCP
ACOUSTIC SEALANT
EA. SIDE
5 3/8"
SECTION
@ FLOOR
PLAN
VIEW
SECTION
@ HEAD
BULLET RESISTANT
PANEL
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W
Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW
DULUTH I TWIN CITIES I VIRGINIA
www.dsgw.com
14817
10/6/2023 12:46:43 PM
023016.01
BC
RT
10/06/23
Wagner Pharmacy
USP
Compliance
A2.1
FLOOR PLANS
111 Washington Ave. NW Wagner, SD 57380
1/4" = 1'-0"
FLOOR PLAN - PHASE 1 - TEMPORARY
PHARMACY
Floor Plan Notes 1 EXISTING RELOCATED HIGH DENSITY MOBILE SHELVING UNIT FROM PHASE 1 DEMO - RADIOLOGY DEPT.
2 NEW PORTABLE HAND WASHING CART, SEE SECTION 10 28 00
3 EXISTING RELOCATED SCRIPTPRO, CONTRACTOR TO SUBCONTRACT WITH SCRIPTPRO FOR MOVING AND
CALIBRATING EQUIPMENT.
4 NEW 30"x60" SIT-STAND DESK (NIC)
5 NEW 30"x48" SIT-STAND DESK (NIC)
6 NEW 24"x60" SIT-STAND DESK (NIC)
7 EXISTING RELOCATED PYXIS SAFE
8 EXISTING RELOCATED UNDERCOUNTER REFRIGERATOR
9 EXISTING RELOCATED REFRIGERATOR
10 EXISTING RELOCATED WALL MOUNTED WILL CALL HANGING BRACKETS FROM PHASE 1 PHARMACY DEMO
11 EXISTING RELOCATED TALL OPEN SHELVING CABINET FROM PHASE 1 PHARMACY DEMO
12 RELOCATED CORROSIVE CABINET
13 STEEL PACKAGE RECIEVER
14 ELECTRICAL POWER POLE - SEE ELEC
15 UPPER CABINETS, SEE SECTION 12 00 50
16 NEW 4'-0" WIDE WALL MOUNTED WILL CALL HANGING BRACKETS, SEE SECTION 10 28 00
17 WIRE MESH PARTITION
18 CART (NIC)
19 3'-0" x 4'-0" TACKBOARD
20 LITERATURE RACK
21 (2) ROBE HOOKS, MOUNT 5'-0" A.F.F.
23 BOUFFANT CAP BOX HOLDER, MOUNT 5'-0" A.F.F. TO CENTERLINE, SEE SECTION 10 28 00
24 SHOE COVER BOX HOLDER, MOUNT 5'-0" A.F.F. TO CENTERLINE, SEE SECTION 10 28 00
25 EXISTING RELOCATED TV AND BRACKET, PROVIDE WALL BACKING
26 HIGH-DENSITY SHELVING UNIT, SEE SECTION 12 00 50
27 CONSULT DESK, SEE SECTION 12 00 50
1/4" = 1'-0"
FLOOR PLAN - PHASE 1 - RADIOLOGY
DEPT.
êÉîáëáçå=L áëëìÉ åçK Ç~íÉ
D AE RR CE HT IS TI EG CE TR
. NG OE .R
14817
U.C.
Refr.
Refrigerator
PHARMACY
CONSULT
ELECTRICAL
ALCOVE
CORRIDOR
CORRIDOR
OFFICE
115A
SCA
115B
BREAKROOM
RECEIVING/HZD
STORAGE
NARCOTICS
115C
A2.2
A2.2
A2.2
A2.2
A2.24
A2.2
A2.2
/8
/4
4A
5A
5A
5A
5B
5 3
1A
1A
1B
5C
5C
1B
1B
1B
1A
1B
1A
1A
1A
1B
1A 1A 1B
1B
5D 5D
5A
1B
1B
8'-0"
TA-W1
A
B
146A
146B
145B145A
114A
B
7'-6" 9'-1 1/2"
MEDICAL
RECORDS
3'-0" 4'-0"
OUTPATIENT/PHARMACY
WAITING
17 18
A2.2
A2.2 12
SD (OPCI)
PTH (OPCI)
VERIFY
3'-0"
1"1"
2'-3" 2'-0" 2'-0" 2'-0" 2'-7"
RELOCATED
REFR.
RELOCATED
U/C REFR.
TA-W1
STEEL PACKAGE
RECIEVER
3'-1" 3'-0"
PULL OUT
PINTER
SHELF
WALL CABINET
SEE SECTION
12 00 50
BASE CABINETS
AND COUNTERTOP,
SEE SECTION
12 00 50
FILLMASTER
ON SIDE WALL
(OPCI)
PTH (OPCI)
SD (OPCI)
FILLMASTER
FILTRATION
SYSTEM MOUNTED
IN CABINET
1"
3'-6"3'-0"
NEW WALL
MOUNTED
WILL CALL
BRACKETS
BASE CABINETS
AND COUNTERTOP,
SEE SECTION
12 00 50
TALL CABINET,
SEE SECTION
12 00 50
3'-0" 3'-0" 2'-6" 3'-0"
OPEN
1"2'-0"2'-0"2'-0"2'-0"2'-0"2'-0"2'-1"
BASE CABINETS
AND COUNTERTOP,
SEE SECTION
12 00 50
WALL CABINETS,
SEE SECTION
12 00 50
6'-0"
OPEN 3
PTH (OPCI)
SD (OPCI)
EYEWASH,
SEE MECH 3
3'-6"
EXHAUST
GRILLS, SEE
MECH
BASE CABINETS
AND COUNTERTOP,
SEE SECTION
12 00 50
WALL CABINETS,
SEE SECTION
12 00 50
(5) ROBE HOOKS
6 TIER METAL
LOCKERS, SEE
SECTION 12 00 50
3'-9"
4'-0" 3'-6"
QUICKSERVE
TRANSACTION
WINDOW W/
INTERCOM SYSTEM
STEEL PACKAGE
RECEIVER
RELOCATED TV AND
BRACKET PROVIDE
BLOCKING
COUNTERTOP,
SEE SECTION
12 00 50
SUPPORT
BRACKETS
5'-3"
COUNTERTOP,
SEE SECTION
12 00 50
1"1" 2'-0" 1'-6" 2'-0"
2'-6"3'-0"
PTH (OPCI) ON
SIDE WALL
SD (OPCI)
WAST BIN BEHIND
DOOR
MICROWAVE
(NIC)
COFFEE
(NIC)
U/C REFR
(NIC)
BASE CABINETS
AND COUNTERTOP,
SEE SECTION
12 00 50
WALL CABINETS,
SEE SECTION
12 00 50
Wall Types
5A
3 5/8" METAL STUD
@ 16" O.C.
5/8" GYP.BD. EA. SIDE
BATT INSULATION
METAL STUD WALL TO
STRUCTURE
5B
OMIT BATT INSULATION, GYP BD
TO EXTEND TO 6" ABOVE CEILING
3 5/8" METAL STUD
CHANNEL
3 5/8" METAL STUD
DEFLECTION TRACK
BASE - SEE
SCHEDULE
ROOF OR FLOOR
STRUCTURE
CLG WHERE APPLICABLE;
SEE RCP
1A
5/8" GYP.BD.
FURRING OVER
EXISTING WALL TO
STRUCTURE
BASE - SEE
SCHEDULE
ROOF OR FLOOR
STRUCTURE
CLG WHERE
APPLICABLE; SEE
RCP
3A
3 5/8" METAL STUD @
16" O.C.
5/8" GYP.BD.
FURRING OVER
EXISTING WALL TO
STRUCTURE
3 5/8" METAL STUD
CHANNEL
BASE - SEE SCHEDULE
ROOF OR FLOOR
STRUCTURE
CLG WHERE APPLICABLE;
SEE RCP
3 5/8" METAL STUD
DEFLECTION TRACK
ACOUSTIC SEALANT
EA. SIDE
ACOUSTIC SEALANT
NOTE: ALL WALLS SHALL BE BUILT TO STRUCTURE ABOVE UNLESS OTHERWISE NOTED
7/8" 4 3/8"
4 7/8"
SECTION
@ FLOOR
SECTION
@ HEAD
SECTION
@ FLOOR
PLAN
VIEW
SECTION
@ HEAD
SECTION
@ FLOOR
PLAN
VIEW
SECTION
@ HEAD
SECURITY BARRIER
MESH
SECURITY BARRIER
MESH
EXTEND EXISTING WALL
TO STR ABOVE: 3 5/8"
METAL STUD @ 16" O.C.
EXISTING WALL
1B
5/8" GYP.BD.
FURRING OVER
EXISTING WALL TO
STRUCTURE
BASE - SEE
SCHEDULE
ROOF OR FLOOR
STRUCTURE
CLG WHERE
APPLICABLE; SEE
RCP
7/8"
SECTION
@ FLOOR
SECTION
@ HEAD
SECURITY BARRIER
MESH
EXISTING WALL
5C
3 5/8" METAL STUD
@ 16" O.C.
5/8" GYP.BD. EA. SIDE
BATT INSULATION
METAL STUD WALL TO
STRUCTURE W/
SECURITY BARRIER
MESH
3 5/8" METAL STUD
CHANNEL
3 5/8" METAL STUD
DEFLECTION TRACK
BASE - SEE
SCHEDULE
ROOF OR FLOOR
STRUCTURE
CLG WHERE APPLICABLE;
SEE RCP
ACOUSTIC SEALANT
EA. SIDE
5 1/8"
SECTION
@ FLOOR
PLAN
VIEW
SECTION
@ HEAD
SECURITY BARRIER
MESH
5D
3 5/8" METAL STUD
@ 16" O.C.
5/8" GYP.BD. EA. SIDE
BATT INSULATION
METAL STUD WALL TO
STRUCTURE W/
BULLET RESISTANT
PANEL
3 5/8" METAL STUD
CHANNEL
3 5/8" METAL STUD
DEFLECTION TRACK
BASE - SEE
SCHEDULE
ROOF OR FLOOR
STRUCTURE
CLG WHERE APPLICABLE;
SEE RCP
ACOUSTIC SEALANT
EA. SIDE
5 3/8"
SECTION
@ FLOOR
PLAN
VIEW
SECTION
@ HEAD
BULLET RESISTANT
PANEL
3'-0"
TALL CABINET ,
SEE SECTION
12 00 50
1" 3'-0" 1'-11"
EXISTING
RELOCATED
PYXIS SAFE
3'-0"
WALL CABINET
SEE SECTION
12 00 50
BASE CABINET
AND COUNTERTOP
SEE SECTION
12 00 50
OPEN
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W
Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW
DULUTH I TWIN CITIES I VIRGINIA
www.dsgw.com
14817
10/6/2023 12:46:44 PM
023016.01
BC
RT
10/06/23
Wagner Pharmacy
USP
Compliance
A2.2
FLOOR PLANS
111 Washington Ave. NW Wagner, SD 57380
1/4" = 1'-0"
FLOOR PLAN - PHASE 2 - PHARMACY
1/4" = 1'-0"
ELEV AT SCA - SOUTH
1/4" = 1'-0"
ELEV AT PHARMACY - SOUTH
1/4" = 1'-0"
ELEV AT PHARMACY - WEST
1/4" = 1'-0"
ELEV AT PHARMACY - NORTH
1/4" = 1'-0"
ELEV AT RECEIVING / HZRD STOR
1/4" = 1'-0"
ELEV BREAK RM - NORTH
1/4" = 1'-0"
ELEV AT TRANSACTION COUNTER
Floor Plan Notes 1 EXISTING RELOCATED HIGH DENSITY MOBILE SHELVING UNIT FROM PHASE 1 DEMO - RADIOLOGY DEPT.
2 NEW PORTABLE HAND WASHING CART, SEE SECTION 10 28 00
3 EXISTING RELOCATED SCRIPTPRO, CONTRACTOR TO SUBCONTRACT WITH SCRIPTPRO FOR MOVING AND
CALIBRATING EQUIPMENT.
4 NEW 30"x60" SIT-STAND DESK (NIC)
5 NEW 30"x48" SIT-STAND DESK (NIC)
6 NEW 24"x60" SIT-STAND DESK (NIC)
7 EXISTING RELOCATED PYXIS SAFE
8 EXISTING RELOCATED UNDERCOUNTER REFRIGERATOR
9 EXISTING RELOCATED REFRIGERATOR
10 EXISTING RELOCATED WALL MOUNTED WILL CALL HANGING BRACKETS FROM PHASE 1 PHARMACY DEMO
11 EXISTING RELOCATED TALL OPEN SHELVING CABINET FROM PHASE 1 PHARMACY DEMO
12 RELOCATED CORROSIVE CABINET
13 STEEL PACKAGE RECIEVER
14 ELECTRICAL POWER POLE - SEE ELEC
15 UPPER CABINETS, SEE SECTION 12 00 50
16 NEW 4'-0" WIDE WALL MOUNTED WILL CALL HANGING BRACKETS, SEE SECTION 10 28 00
17 WIRE MESH PARTITION
18 CART (NIC)
19 3'-0" x 4'-0" TACKBOARD
20 LITERATURE RACK
21 (2) ROBE HOOKS, MOUNT 5'-0" A.F.F.
23 BOUFFANT CAP BOX HOLDER, MOUNT 5'-0" A.F.F. TO CENTERLINE, SEE SECTION 10 28 00
24 SHOE COVER BOX HOLDER, MOUNT 5'-0" A.F.F. TO CENTERLINE, SEE SECTION 10 28 00
25 EXISTING RELOCATED TV AND BRACKET, PROVIDE WALL BACKING
26 HIGH-DENSITY SHELVING UNIT, SEE SECTION 12 00 50
27 CONSULT DESK, SEE SECTION 12 00 50
1/4" = 1'-0"
ELEV BREAK RM - EAST
1/4" = 1'-0"
ELEV BREAK RM - SOUTH
êÉîáëáçå=L áëëìÉ åçK Ç~íÉ
1/4" = 1'-0"
ELEV OFFICE - NORTH
1/4" = 1'-0"
ELEV AT NARCOTICS - WEST
D AE RR CE HT IS TI EG CE TR
. NG OE .R
14817
A
B C
E
D
G
J
K
L
M
P
R
S
H
Q
4 8 11 13 14 177 125 910 16 18
F
7.1
EXISTING PENTHOUSE
A2.3
NEW EXHAUST FAN,
SEE MECHANICAL
MECHANICAL CURB
PRESSURE TREATED
WOOD BLOCKING,
MATCH INS. THICKNESS
EXISTING ROOF DECKING
EXISTING EPDM ROOFING
AND INSULATION
STEEL ANGLE ALL AROUND
OPENING, ATTACHED TO
ADJACENT ROOF JOIST
EPDM MEMBRANE FLASHING,
EXTEND OVER CURB, TIE INTO
EXISTING ROOFING PER
MANUFACTURES
INSTRUCTIONS
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W
Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW
DULUTH I TWIN CITIES I VIRGINIA
www.dsgw.com
14817
10/6/2023 12:46:44 PM
023016.01
BC
RT
10/06/23
Wagner Pharmacy
USP
Compliance
A2.3
ROOF PLAN
111 Washington Ave. NW Wagner, SD 57380 êÉîáëáçå=L áëëìÉ åçK Ç~íÉ
1/8" = 1'-0"
ROOF PLAN
1 1/2" = 1'-0"
MECHANICAL ROOF CURB
D AE RR CE HT IS TI EG CE TR
. NG OE .R
14817
TEMPORARY
PHARMACY
133B
OFFICE
9'-0"
MEDICAL
RECORDS
EXISTING CLG
TO REMAIN
9'-0"
NEW CEILING IN
PHASE 2
PHARMACY
CONSULT
EYE EXAM
ELECTRICAL
ALCOVE
EYE SCREENING
VISUAL FIELDS
STORAGE
OFFICE
115A SCA
115B
BREAKROOM
RECEIVING/HZD
STORAGE
NARCOTICS
115C
8'-0"
8'-0" 8'-5"
8'-0"
8'-0"
MEDICAL
RECORDS
8'-6"
9'-0"
9'-0"
GYP BD AND SECURITY BARRIER MESH CEILING
SEE DETAIL 3/A3.1
GYP BD CEILING
SEE DETAIL 4/A3.1
STRUCTURE/FRAMING ABOVE
DRYWALL SUSPENSION SYSTEM OR
3 5/8" METAL STUD FRAMING -
CONTRACTOR'S CHOICE
5/8" GYP. BD.
SECURITY BARRIER MESH
STRUCTURE/FRAMING ABOVE
DRYWALL SUSPENSION SYSTEM OR
3 5/8" METAL STUD FRAMING -
CONTRACTOR'S CHOICE
5/8" GYP. BD.
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W
Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW
DULUTH I TWIN CITIES I VIRGINIA
www.dsgw.com
14817
10/6/2023 12:46:45 PM
023016.01
BC
RT
10/06/23
Wagner Pharmacy
USP
Compliance
A3.1
REFLECTED
CEILING PLANS
111 Washington Ave. NW Wagner, SD 57380
1/8" = 1'-0"
REFLECTED CEILING PLAN - PHASE 1
1/4" = 1'-0"
REFLECTED CEILING PLAN - PHASE 2
êÉîáëáçå=L áëëìÉ åçK Ç~íÉ
1" = 1'-0"
Gyp. Bd. Ceiling Detail 1" = 1'-0"
Gyp. Bd. Ceiling Detail1
D AE RR CE HT IS TI EG CE TR
. NG OE .R
14817
Door Types
WD-D1
Solid Core
Wood Flush
WD-D2
Solid Core Wood w/Quarter Lite
8" 8"
WD-D3
Solid Core Wood w/Half Lite
8" 8"
1/4" TEMPERED
GLASS
1/4" TEMPERED
GLASS
Frame Types
HM-F1
Hollow Metal
FRAME WIDTH IS 2" UNLESS OTHERWISE DIMENSIONED. FRAME DEPTH TO MATCH WALL THICKNESS
PER INDUSTRY STANDARDS UNLESS OTHERWISE NOTED. SEE DETAILS.
SEE SCHED
S E
E S
C H
E D
U
LE
HM-W1
Hollow Metal
3'-0"
1/4" TEMPERED
GLASS
TA-W1
QUICKSERV
SPEAK AROUND 36X36
3'-0"
LEVEL 3 BULLET
RESISTANT GLAZING
TA-W2
3'-0"
1/4" PLEXIGLASS
4" DIA. HOLE
12" DIA. CUTOUT
SSM SILL
WALL, SEE PLAN
FOR WALL TYPES
METAL STUD
LINTEL
HOLLOW METAL
FRAME
DOOR, SEE SCHED.
CONT. SEALANT,
BOTH SIDES
WALL, SEE PLAN
FOR WALL TYPES
DOUBLE STUDS
AT JAMB
HOLLOW METAL
FRAME
DOOR, SEE SCHED.
CONT. SEALANT,
BOTH SIDES
WALL, SEE PLAN
FOR WALL TYPES
METAL STUD
LINTEL
HOLLOW METAL
FRAME
GLASS, SEE SCHED.
CONT. SEALANT
BOTH SIDES
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W
Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW
DULUTH I TWIN CITIES I VIRGINIA
www.dsgw.com
14817
10/6/2023 12:46:46 PM
023016.01
BC
RT
10/06/23
Wagner Pharmacy
USP
Compliance
A4.1
DOOR
SCHEDULE AND
TYPES
111 Washington Ave. NW Wagner, SD 57380
DOOR AND FRAME SCHEDULE
DOOR FRAME
FIRE LABEL
HDW.
NO. NOTESNO. WIDTH HEIGHT TYPE TYPE
DETAIL
HEAD JAMB SILL
106B 3'-0" 7'-0" WD-D1 HM-F1 1/A4.1 2/A4.1 03
107 3'-0" 7'-0" WD-D1 HM-F1 1/A4.1 2/A4.1 -- 06
133B 3'-0" 7'-0" WD-D1 HM-F1 1/A4.1 2/A4.1 03
1 1/2" = 1'-0"
H.M. Head Detail 1 1/2" = 1'-0"
H.M. Jamb Detail
1 1/2" = 1'-0"
H.M. Window Head Detail
DOOR AND FRAME SCHEDULE
DOOR FRAME
FIRE LABEL
HDW.
NO. NOTESNO. WIDTH HEIGHT TYPE TYPE
DETAIL
HEAD JAMB SILL
114A 3'-0" 7'-0" EXISTING TO
REMAIN
EXISTING TO
REMAIN
-- -- 04
114B 3'-0" 7'-0" WD-D2 HM-F1 1/A4.1 2/A4.1 -- 05
115A 3'-0" 7'-0" WD-D1 HM-F1 1/A4.1 2/A4.1 01
115B 3'-0" 7'-0" WD-D2 HM-F1 1/A4.1 2/A4.1 02
145A 3'-0" 7'-0" WD-D3 HM-F1 1/A4.1 2/A4.1 05
145B 3'-0" 7'-0" WD-D1 HM-F1 1/A4.1 2/A4.1 05
146A 3'-0" 7'-0" WD-D3 HM-F1 1/A4.1 2/A4.1 01
146B 3'-0" 7'-0" WD-D1 HM-F1 1/A4.1 2/A4.1 05
êÉîáëáçå=L áëëìÉ åçK Ç~íÉ
D AE RR CE HT IS TI EG CE TR
. NG OE .R
14817
STERILE
DRUG INFO
EYE EXAM
SUPPLY
JANITOR
HSKP/CLEAN
LINEN
HZD WASTE
STORAGE
EYE SCREENING
VESTIBULE
TEMPORARY
PHARMACY
DISPENSING
133B
OFFICE
MEDICAL
RECORDS
MAIN
CORRIDOR
CG-1
PNT-1
PNT-1
PNT-5
PHARMACY
CONSULT
ELECTRICAL
ALCOVE
CORRIDOR
CORRIDOR
OFFICE
115A
SCA
115B
BREAKROOM
RECEIVING/HZD
STORAGE
NARCOTICS
115C
TA-W1
MEDICAL
RECORDS
OUTPATIENT/PHARMACY
WAITING
PNT-5
PNT-5
PNT-5
PNT-5
CG-1 CG-1
CG-1 CG-1
SV-2
SV-3
FRP WAINSCOT
4'-4" AFF
PNT-2
Finish Abbreviations
ACT ACOUSTICAL CEILING TILE
CT PORCELAIN/CERAMIC TILE
EXIST. EXISTING
GYP. BD. GYPSUM BOARD
LVT LUXURY VINYL TILE
T.B.B. TILE BACKER BOARD
VCT VINYL COMPOSITION TILE
QT QUARRY TILE
EP EPOXY
PNT PAINT
CPT CARPET
VWC VYNL WALLCOVERING
WB WOOD BASE
WS WINDOW SHADE
WD WOOD
FRP FIBER REFORCED PANEL
CG CORNER GUARD
VB VINYL BASE
1. SEE FINISH PLAN FOR CLARIFICATION OF FLOOR AND WALL FINISH LOCATIONS.
2. ALL WALLS TO RECIEVE PNT-1 UNLESS OTHERWISE NOTED
3. ALL CEILING TO RECEIVE PNT-4 UNLESS OTHERWISE NOTED
4. ALL HM FRAMES AND DOORS TO RECEIVE PNT-3 UNLESS OTHERWISE NOTED
5. ALL FLOORS TO RECEIVE RB-1 UNLESS OTHERWISE NOTED IN FINISH SCHEDULE
Finish Notes
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W
Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW
DULUTH I TWIN CITIES I VIRGINIA
www.dsgw.com
14817
10/6/2023 12:46:48 PM
023016.01
BC
RT
10/06/23
Wagner Pharmacy
USP
Compliance
A4.2
ROOM FINISH
SCHEDULE AND
PLANS
111 Washington Ave. NW Wagner, SD 57380
ROOM FINISH SCHEDULE - PHASE 2
NO. NAME
FLOOR WALL FINISH CEILING
NOTESFINISH BASE NORTH EAST SOUTH WEST MAT'L FINISH
108 OUTPATIENT/PHARMACY WAITING -- SEE NOTES PNT PNT -- -- -- -- PATCH TO MATCH WERE REMODELING OCCURS
114 CONSULT LVT-1 RB PNT PNT-2 PNT PNT SACT-1 --
115 PHARMACY SV-1 RB PNT-1/PNT-2 PNT PNT PNT SACT-1 --
115A OFFICE LVT-1 RB PNT-2 PNT PNT PNT SACT-1 --
115B SCA SV-2, SV-3 SV-2, SV-3 EPOXY PNT EPOXY PNT EPOXY PNT EPOXY PNT GYP BD EPOXY PAINT PROVIDE CLEAN ROOM SEALANT AT TOP CAP OF BASE AND
WALL
115C NARCOTICS SV-2 RB PNT PNT PNT PNT GYP BD PNT
133 MEDICAL RECORDS -- SEE NOTES -- -- PNT PNT SACT-1 -- PATCH TO MATCH WERE REMODELING OCCURS
145 RECEIVING/HZD STORAGE SV-2 RB FRP/ EPOXY PNT EPOXY PNT EPOXY PNT EPOXY PNT SACT-1 --
146 BREAKROOM LVT-1 RB PNT PNT PNT PNT-2 SACT-1 --
161 CORRIDOR -- SEE NOTES -- -- -- PNT -- -- PATCH TO MATCH WERE REMODELING OCCURS
170 CORRIDOR -- SEE NOTES PNT -- -- -- -- -- PATCH TO MATCH WERE REMODELING OCCURS
ROOM FINISH SCHEDULE - PHASE 1
NO. NAME
FLOOR WALL FINISH CEILING
NOTESFINISH BASE NORTH EAST SOUTH WEST MAT'L FINISH
101 MAIN CORRIDOR -- SEE NOTES -- SEE NOTES -- -- -- -- PATCH TO MATCH WERE REMODELING OCCURS
106 DISPENSING -- -- PNT PNT PNT PNT -- --
107 TEMPORARY PHARMACY -- -- -- -- -- -- -- --
133 MEDICAL RECORDS - SEE NOTES PNT PNT - - - -- PATCH TO MATCH WERE REMODELING OCCURS
133B OFFICE LVT-1 RB PNT PNT PNT PNT SACT-1 --
202 WORK AREA SEE NOTES SEE NOTES PNT PNT -- PNT -- -- PATCH TO MATCH WERE REMODELING OCCURS
1/4" = 1'-0"
FINISH PLAN - PHASE 1 - TEMPORARY
PHARMACY
1/4" = 1'-0"
FINISH PLAN - PHASE 2 - PHARMACY
êÉîáëáçå=L áëëìÉ åçK Ç~íÉ
D AE RR CE HT IS TI EG CE TR
. NG OE .R
14817
PLUMBING AND PIPING SYMBOLS
KEYNOTE
CONTINUATION SYMBOL
NUMBER OF SHEET WHERE DETAIL APPEARS
NUMBER OF DETAIL ON SHEET
REVISION NUMBER - SHOWN ON PLANS
GENERAL MECHANICAL SYMBOLS
ROOM NAME AND NUMBER
POINT WHERE NEW CONNECTS TO EXISTING
EXISTING PIPE TAG
ITEM TO BE DEMOLISHED
AREA NOT IN CONTRACT
PIPING BEING DEMOLISHED
ABOVE GROUND PIPING
PIPE SIZE TAG (DIAMETER)
DRAIN SIZE
PIPE RISE
PIPE DROP
PIPE TEE REDUCING 45
DEGREE TEE
45 DEGREE TEE
BELOW GROUND PIPING
PIPE INVERT ELEVATION TAG
PIPE SLOPE TAG
TYPE (SEE SCHEDULE)
GRILLES, REGISTERS & DIFFUSERS TAG
CFM
EXISTING DUCT TAG
OVAL DUCT SIZE TAG (WIDTH / HEIGHT)
SQUARE DUCT SIZE TAG (WIDTH x HEIGHT)
HVAC SYMBOLS
RECTANGULAR SUPPLY/OUTSIDE AIR DUCT RISE
RECTANGULAR RETURN/TRANSFER AIR DUCT RISE
MECHANICAL EQUIPMENT TAGS
ROUND DUCT SIZE TAG (DIAMETER)
LINEAR DIFFUSER TAG
CFM
TYPE (SEE SCHEDULE)
ACTIVE SLOT LENGTH /
NUMBER OF SLOTS
DUCT BEING DEMOLISHED
ROUND SUPPLY/OUTSIDE AIR DUCT RISE
ROUND RETURN/TRANSFER AIR DUCT RISE
RECTANGULAR EXHAUST/RELIEF AIR DUCT RISE
ROUND EXHAUST/RELIEF AIR DUCT RISE
DROP
DROP
DROP
DROP
DROP
DROP
EQUIPMENT BY OTHERS
(REFER TO OTHER DISCIPLINE
FOR ADDITIONAL INFORMATION)
EXISTING EQUIPMENT
TO REMAIN
Ø ROUND
ABV ABOVE
AD AREA DRAIN
ADD ADDENDUM
AFF ABOVE FINISHED FLOOR
AFUE ANNUAL FUEL UTILIZATION EFFICIENCY
ALT ALTERNATE
AP ACCESS PANEL
ARCH ARCHITECT/ARCHITECTURAL
BFF BELOW FINISHED FLOOR
BLW BELOW
BTU BRITISH THERMAL UNITS
BTUH BRITISH THERMAL UNITS PER HOUR
CAP CAPACITY
CB CATCH BASIN
CFM CUBIC FEET PER MINUTE
CLG CEILING
CO CLEAN OUT
CW COLD WATER
D DEGREE
DB DRY BULB
DIA DIAMETER
DN DOWN
DW DISTILLED WATER
EA EACH
EAT ENTERING AIR TEMPERATURE
ELEC ELECTRICAL
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EWT ENTERING WATER TEMPERATURE
E/A EXHAUST AIR
EXIST EXISTING
F DEGREES FAHRENHEIT
FCO FLOOR CLEAN OUT
FD FLOOR DRAIN
FD FIRE DAMPER
FDV FIRE DEPARTMENT VALVE
FL FLOOR
ABBREVIATIONS
AC AIR CONDITIONING UNIT
ACC AIR COOLED CONDENSER
ACCU AIR COOLING CONDENSING UNIT
AFMS AIR FLOW MEASURING STATION
AHU AIR HANDLING UNIT
AS AIR SEPARATOR
B BOILER
CF CABINET FAN
CF CHEMICAL FEEDER
CFP CHEMICAL FEEDER PUMP
CH CHILLER
CRU CONDENSATE RETURN UNIT
CT COOLING TOWER
CUH CABINET UNIT HEATER
CHWP CHILLED WATER PUMP
CWP CONDESATE WATER PUMP
DBP DOMESTIC WATER BOOSTER PUMP
DC DUCT MOUNTED COIL
DCP DOMESTIC WATER CIRCULATING PUMP
EF EXHAUST FAN
EDC ELECTRIC DUCT COIL
ET EXPANSION TANK
EWH ELECTRIC WATER HEATER
FCU FAN COIL UNIT
FP FIRE PUMP
GI GREASE INTERCEPTOR
GRV GRAVITY ROOF VENTILATOR
H HUMIDIFIER
HWP HEATING WATER PUMP
HX HEAT EXCHANGER
HPU HEAT PUMP UNIT
HRU HEAT RECOVERY UNIT
PF PROPELLER FAN
PRV POWER ROOF VENTILATOR
PWF POWER WALL FAN
RE RETURN/EXHAUST FAN
RTU ROOFTOP UNIT
SA SHOCK ABSORBER
SAT SOUND ATTENUATOR
SEP SEWAGE EJECTOR PUMP
SF SUPPLY FAN
SP SUMP PUMP
UH UNIT HEATER
US UTILITY SET
UV UNIT VENTILATOR
WFMS WATER FLOW MEASURING STATION
WH WATER HEATER
EQUIPMENT ABBREVIATIONS
TYPE (SEE SCHEDULE)
BOTTOM OF EQUIPMENT
ELEVATION
HEATING
COIL
FLOW OPERATING WEIGHT
NOT INCLUDING CURB
FUEL INPUT
GAS PIPE FLOW
NOMINAL COOLING
CAPACITY
DRAIN TAGS
"P" - INDICATES
PRIMER CONNECTION
FIXTURE UNITS
ROOF AREA
SERVED BY DRAIN
PIPE ACCESSORY TAGS
DATA DEVICE TAGS
DAMPER TAGS
EQUIPMENT ID
SYMBOL
FIXTURE UNITS
PIPE ACCESORY
TAG
PLUMBING FIXTURE TAGS
TYPE (SEE SCHEDULE)
EXISTING RELOCATED
EQUIPMENT
FO FUEL OIL
FOV FUEL OIL VENT
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FPM FEET PER MINUTE
FS FLOOR SINK
FT FOOT/FEET
FTR FIN TUBE RADIATION
GAL GALLON
GC GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
GW GREASE WASTE
HB HOSE BIB
HP HORSE POWER
HTG HEATING
HTR HEATER
HW HOT WATER
HYD HYDRANT
ID INDIRECT
IN INCH
INV INVERT
LB POUND
LB/HR POUNDS PER HOUR
LAT LEAVING AIR TEMPERATURE
LP LOW PRESSURE
LPG LIQUEFIED PETROLEUM GAS
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
M/A MIXED AIR
MAX MAXIMUM
MBH ONE THOUSAND BTU PER HOUR
MCF ONE THOUSAND CUBIC FEET
MD MOTORIZED DAMPER
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MTR MOTOR
MU/A MAKE-UP/AIR
NC NOISE CRITERIA
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NUMBER
NO NORMALLY OPEN
NTS NOT TO SCALE
O OXYGEN
O/A OUTSIDE AIR
ORD OVERFLOW ROOF DRAIN
PD PRESSURE DROP
PIV POST INDICATOR VALVE
PLBG PLUMBING
PRESS PRESSURE
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAUGE
PWR POWER
R DUCT RISER
R/A RETURN AIR
RCP RADIANT CEILING PANEL
RD ROOF DRAIN
REC RECESSED
RED REDUCER
RH RELATIVE HUMIDITY
RL/A RELIEF AIR
RM ROOM
RPM REVOLUTIONS PER MINUTE
RW RAIN WATER
SF SQUARE FOOT
S/A SUPPLY AIR
SAN SANITARY
SF SQUARE FOOT
SD SMOKE DAMPER
SM SURFACE MOUNT
SP STANDPIPE
SP STATIC PRESSURE
STM STEAM
T THERMOSTAT
TD TEMPERATURE DROP
TDR TRENCH DRAIN
TEMP TEMPERATURE
TYP TYPICAL
UG UNDERGROUND
VAC VACUUM
V VENT
VAV VARIABLE AIR VOLUME
VENT VENTILATION
VTR VENT THROUGH ROOF
W WASTE
WB WET BULB
WCO WALL CLEAN OUT
WH WALL HYDRANT
MECHANICAL SHEET INDEX
CD-XXX
CFM
TYPE (SEE SCHEDULE)
CG-XXX
24x24 SIZE (NOTED IF DIFFERENT
THAN 24x12)
CFM
TYPE (SEE SCHEDULE)
CD-XXX
CFMSR-XXX
24x24 SIZE
TYPE (SEE SCHEDULE)
CFMRR-XXX
24x24 SIZE
TYPE (SEE SCHEDULE)
LSD-XXX
48" x (2) 3/4" SLOTS
VAV-XX
RTU-XX
SENSOR
MANUAL SWITCH
THERMOSTAT
TEMPERATURE SENSOR
TEMPERATURE & HUMIDITY SENSOR
HUMIDITY SENSOR
NITROGEN DIOXIDE SENSOR
CARBON MONOXIDE SENSOR
CARBON DIOXIDE SENSOR
HUMIDISTAT
LINEAR SLOT
DIFFUSER
ROUND DIFFUSER
WITH ADJUSTABLE
PATTERNS
SUPPLY
REGISTER/GRILLE
CEILING DIFFUSER
RETURN/EXHAUST
REGISTER/GRILLE
CEILING RETURN
GRILLE
4000 SF
6" SD-1
4" FD-1FLOOR DRAIN 4" AD-6 AREA DRAIN
4" FS-4FLOOR SINK
4" SD-29 DECK DRAIN4" FD-3PFLOOR DRAIN
8 WFU
4" FD-13
HUB DRAIN
FLOW CONTROL
DRAIN
4" SD-12
COMBINATION
DRAINS
STORM DRAIN4" SD-15
WATER CLOSET -
WALL HUNG - ADA WC-1
U-1
1 WFU
LAV-1
1.5 CWFU
1.5 HWFU
LAV-1
WC-1A
VAV-XX
10' - 0"
(E)VAV-XX
VAV-XX
590 lb
RTU-XX
4.0 ton
RTU-XX
115000 Btu/h
115 CFH
RTU-XX
Htg: 3.7 GPM
VAV-XX
VAV BOX
ROOFTOP UNIT
(R)VAV-XX
16/8
16/8
(E)
F
FS
M
B
D
FS
16Ø
MANUAL BALANCING DAMPER
BACKDRAFT DAMPER
COMBINATION FIRE/SMOKE
DAMPER
FIRE DAMPER
SMOKE DAMPER
MOTORIZED DAMPER
Room
CHWS
CWV
CA
CD
CDR
CWR
CWS
CW
F-CW
H-CW
S-CW
HW
HW 140°
HW-R
HW-R 140°
GV
GW
HWR
HWS
G
OV
OW
PD
V
SS
SHWR
SHWS
STM
SD
OSD
(E)
CHWR CHILLED WATER RETURN
CHILLED WATER SUPPLY
COMBINATION WASTE & VENT
COMPRESSED AIR
CONDENSATE DRAINAGE
CONDENSATE RETURN
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
DOMESTIC COLD WATER
FILTERED COLD WATER
HARD COLD WATER
SOFT COLD WATER
HOT WATER
HOT WATER 140°
HOT WATER RECIRCULATION
HOT WATER RECIRCULATION 140°
GREASE VENT
GREASE WASTE
HEATING WATER RETURN
HEATING WATER SUPPLY
NATURAL GAS
OIL VENT
OIL WASTE
PUMP DISCHARGE
SANITARY VENT
SANITARY SEWER
SOLAR HOT WATER RETURN
SOLAR HOT WATER SUPPLY
STEAM
STORM DRAINAGE
OVERFLOW STORM DRAINAGE
REF-L
REF-S
REFRIGERANT-LIQUID
REFRIGERANT-SUCTION
2"
2"
4"
4"
REF-HG REFRIGERANT-HOT GAS
PG PROPANE GAS
INVERT: -105' - 1"
1/8" / 12" SLOPE
RO REVERSE OSMOSIS WATER
IW INDIRECT WASTE
2" DOM. WM
DOMESTIC WATER METER
BALANCING VALVE
1/4 TURN BALL VALVE
CHECK VALVE
3-WAY MIXING VALVE
MOTORIZED CONTROL VALVE
3 WAY MOTORIZED CONTROL VALVE
PRESSURE REDUCING VALVE
REFRIGERANT SOLENOID VALVE
BUTTERFLY VALVE
2" BALANCING
2" SHUTOFF
2" CHECK
2" TMV
2" M-CNTRL
2" 3-WAY CNTRL
2" PRV
3/8" SOLENOID
2" BUTTERFLY
4" WCO 4" WCO
CAP
PLUG
GWR
GWS
GEOTHERMAL WATER RETURN
GEOTHERMAL WATER SUPPLY
CO2
CO
H
HS
NO2
S
TH
TS
T
MS
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW íóéÉÇLéêáåíÉ Ç=å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW
MECHANICAL DRAWINGS
1112 North 5th Street Minneapolis, MN 55411
(612) 343-5965
1624 North Riverfront Drive Mankato, MN 56001
(507) 625-7869 ëÜÉÉí= íáíäÉW ëÜÉÉí= åìãÄÉêW
DULUTH I TWIN CITIES I VIRGINIA
www.dsgw.com
023016.00
10/06/2023
10/06/2023
EDI-DOLEJS #23-035
Wagner Pharmacy USP Compliance
111 WASHINGTON AVE. NW
WAGNER, SD 57380
14204
MIKE S. DOLEJS
Wagner
Pharmacy
USP
Compliance
111 WASHINGTON AVE. NW
WAGNER, SD 57380
AE, LS
MD
M0.1
Mechanical
Title Sheet
M0.1 Mechanical Title Sheet
M1.1 Partial Floor Plan - Phase 1 & 2 - Fire Protection
M2.0 Partial Underfloor Plan - Phase 2 - Plumbing
M2.1 Partial Floor Plan - Phase 2 - Plumbing
M2.2 Plumbing Riser Diagrams
M3.1 Partial Floor Plan - Phase 1 - Piping
M3.2 Partial Floor Plan - Phase 2 - Piping
M4.1 Partial Floor Plan - Phase 1 - HVAC
M4.2 Partial Floor Plan - Phase 2 - HVAC
M5.1 Mechanical Schedules
M6.1 Mechanical Details êÉîáëáçå=L áëëìÉ åçK Ç~íÉ
PLAN NOTES
GENERAL NOTES
MEDICAL
RECORDS
OFFICE
115A SCA
115B
PHARMACY
CONSULT
NARCOTICS
115C ELECTRICAL
RECEIVING/HZD
STORAGE
BREAKROOM
HSKP/CLEAN
LINEN
STORAGE
TEMPORARY
PHARMACY-1
107-1
JANITOR
EYE LAB
EYEGLASS
FITTING
VISUAL
FIELDS
EYE
SCREENING
EYE EXAM
SUPPLY
INTERVIEW
ROOM
HZD WASTE
STORAGE
E
G
J
K
L
M
Q
121087542
1. DISCONNECT AND REMOVE EXISTING SPRINKLER HEADS, FITTINGS,
ESCUTCHEONS AND RELATED PIPING AS REQUIRED TO
ACCOMMODATE NEW CONSTRUCTION. PROVIDE NEW SPRINKLER
HEADS, FITTINGS, ESCUTCHEONS AND PIPING TO COORDINATE
WITH CEILINGS, WALLS, RELATED MECHANICAL AND ELECTRICAL
SYSTEMS AND CEILING DEVICES. SPRINKLER DESIGN AND
INSTALLATION SHALL COMPLY WITH NFPA 13, OWNER INSURANCE
REQUIREMENTS AND AUTHORITIES HAVING JURISDICTION. NEW
SPRINKLER HEADS SHALL MATCH EXISTING HEADS IN
APPEARANCE AND FUNCTION.
2. MINIMUM OCCUPANCY CLASSIFICATION FOR BIDDING PURPOSES:
ORDINARY HAZARD GROUP 1.
A. THIS DRAWING IS A BID DOCUMENT AND IS NOT A DESIGN DRAWING.
CONFIRMATION OF FINAL DESIGN VIA SHOP DRAWINGS, HYDRAULIC
CALCULATIONS, PRODUCT SUBMITTALS, ETC. IS THE SOLE
RESPONSIBILITY OF THE FIRE PROTECTION DESIGN/BUILD
CONTRACTOR.
B. REFER TO ARCHITECTURAL PLANS FOR COMPLETE
CEILING/FLOOR/ROOM PLAN INFORMATION.
C. ALL AREAS SHALL BE DESIGNED AS LIGHT HAZARD OCCUPANCY
UNLESS INDICATED OTHERWISE OR AS REQUIRED BY AUTHORITIES
HAVING JURISDICTION.
D. PROVIDE PROTECTION ABOVE AND BELOW OBSTRUCTIONS AS
REQUIRED, WHETHER INDICATED OR NOT.
E. ALL SPRINKLERS LOCATED IN FINISHED AREAS SHALL BE
SYMMETRICAL IN PATTERN FOR THE AREA SERVED.
F. HIGH TEMPERATURE SPRINKLERS SHALL BE PROVIDED NEAR ALL
HEAT PRODUCING EQUIPMENT IN ACCORDANCE WITH NFPA 13.
G. DRY TYPE PENDANT AND SIDEWALL SPRINKLER HEADS SHALL
FOLLOW THE MANUFACTURER'S REQUIREMENTS FOR THE MINIMUM
BARREL LENGTH IN THE HEATED AREA.
H. PROVIDE AUXILIARY DRAINS WITH PIPING TO APPROVED LOCATIONS
FOR ALL TRAPPED PIPING. DRAIN PIPING SHALL BE SIZED PER NFPA
13 REQUIREMENTS.
I. ALL WALL AND FLOOR PENETRATIONS WITH FIRE PROTECTION
PIPING SHALL BE FULLY SLEEVED AND SEALED.
J. APPROVED THROUGH PENETRATION FIRE STOP SYSTEMS SHALL BE
USED FOR ALL RATED WALLS AND FLOORS TO MAINTAIN RATING.
K. NO STORAGE IS PERMITTED IN MECHANICAL OR ELECTRICAL ROOMS.
L. EXTENDED COVERAGE SPRINKLERS SHALL NOT BE INSTALLED IN
MECHANICAL ROOMS.
M. DESIGN AREA REDUCTION FOR QUICK RESPONSE SPRINKLERS
ALLOWED BY NFPA 13 SHALL NOT APPLY TO AREAS WITH CLOUD
CEILINGS.
N. ALL MATERIALS USED IN THE INSTALLATION OF THE FIRE
PROTECTION SYSTEMS SHALL BE NEW AND OF CURRENT ISSUE,
APPROVED BY U.L. AND/OR F.M. AND THE AUTHORITIES HAVING
JURISDICTION.
O. ALL FIRE PROTECTION WET AND DRY TYPE SYSTEM PIPING SHALL BE
STEEL. DRY TYPE SYSTEM PIPING SHALL BE SCHEDULE 40.
P. WHERE NEW SPRINKLER HEADS ARE INSTALLED IN AREAS WITH
CEILINGS THEY SHALL BE CENTERED IN THE CEILING TILES.
Q. FIRE PROTECTION CONTRACTOR SHALL BE RESPONSIBLE FOR
CONFIRMING FINAL SPRINKLER TYPES. LOCATIONS AND FINISHES IN
ALL AREAS WITH ARCHITECT.
R. TAMPER SWITCHES AND FLOW SWITCHES SHALL BE FURNISHED AND
INSTALLED BY FIRE PROTECTION CONTRACTOR. WIRING OF SUCH
DEVICES IS THE RESPONSIBILITY OF THE FIRE ALARM CONTRACTOR.
COORDINATE ALL FIRE PROTECTION WORK WITH FIRE ALARM
CONTRACTOR.
S. FIRE/SMOKE DETECTION SYSTEMS FOR DOUBLE INTERLOCK
PREACTION FIRE PROTECTION SYSTEMS AND CLEAN AGENT
SYSTEMS SHALL BE FURNISHED AND INSTALLED BY FIRE
PROTECTION CONTRACTOR. COORDINATE WITH FIRE ALARM
CONTRACTOR.
T. UNLESS OTHERWISE NOTED, ALL AREAS WITHOUT CEILINGS SHALL
HAVE BRASS UPRIGHT SPRINKLER HEADS WITH EXPOSED PIPING.
STAFF AND PUBLIC AREAS WITH GYP BOARD OR LAY-IN CEILINGS
SHALL HAVE CONCEALED SPRINKLER HEADS WITH COVER PLATES
AND CONCEALED PIPING.
MEDICAL
RECORDS
OFFICE
115A SCA
115B
PHARMACY
CONSULT
NARCOTICS
115C ELECTRICAL
RECEIVING/HZD
STORAGE
BREAKROOM
HSKP/CLEAN
LINEN
STORAGE
TEMPORARY
PHARMACY-1
107-1
JANITOR
EYE LAB
EYEGLASS
FITTING
VISUAL
FIELDS
EYE
SCREENING
EYE EXAM
SUPPLY
INTERVIEW
ROOM
HZD WASTE
STORAGE
E
G
J
K
L
M
Q
121087542
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW íóéÉÇLéêáåíÉ Ç=å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW
1112 North 5th Street Minneapolis, MN 55411
(612) 343-5965
1624 North Riverfront Drive Mankato, MN 56001
(507) 625-7869 ëÜÉÉí= íáíäÉW ëÜÉÉí= åìãÄÉêW
DULUTH I TWIN CITIES I VIRGINIA
www.dsgw.com
023016.00
10/06/2023
10/06/2023
EDI-DOLEJS #23-035
14204
MIKE S. DOLEJS
Wagner
Pharmacy
USP
Compliance
111 WASHINGTON AVE. NW
WAGNER, SD 57380
AE, LS
MD
M1.1
Partial Floor
Plan - Phase 1 &
2 - Fire
Protection
NORTH NORTH
8' 16'4'0 1/8" = 1'-0"M1.1
1 Partial Floor Plan - Phase 2 - Fire Protection
1/8" = 1'-0"M1.1
2 Partial Floor Plan - Phase 1 - Fire Protection
E
F
G
H
J
K
L
M
P
Q
121110987.175432
2" SS UP TO SK-1
2" SS UP TO FCO
2" SS
2" SS UP TO SK-2
2" SS
2" SS UP
TO FCO
2" SS UP TO SK-3
2" SS UP TO SK-4
2" SS
2" SS
EX. 8" SS
EX. 8" SS
(BELOW GRADE)
(BELOW GRADE)
(CRAWL SPACE)
(CRAWL SPACE)
(CRAWL SPACE)
(CRAWL SPACE)
CONNECT NEW 2" SS (CRAWL SPACE)
TO EXISTING 8" SS (BELOW GRADE).
FIELD VERIFY EXISTING SIZE,
LOCATION AND INVERT ELEVATION.
E
F
G
H
J
K
L
M
P
Q
121110987.175432
DISCONNECT AND REMOVE
EXISTING 2" SS, LOCATED IN
CRAWL SPACE, ASSOCIATED WITH
EXISTING SINK TO BE REMOVED.
REMOVE EXISTING 2" SS BRANCH
LINE BACK TO MAIN. REFER TO
SHEET 2/M2.0 FOR NEW WORK.EX. 8" SS
BELOW GRADE
TO REMAIN.
EX. 8" SS
BELOW GRADE
TO REMAIN.
A. FIELD VERIFY EXISTING CONDITIONS PRIOR TO COMMENCING
WORK. FIELD VERIFY LOCATIONS AND SIZES OF DUCTWORK AND
PIPING AND EQUIPMENT TO BE REMOVED.
B. NOTIFY ENGINEER OF ANY DISCREPANCIES.
C. CUT AND PATCH EXISTING SURFACES (WALLS, FLOORS, AND/OR
CEILINGS) AS REQUIRED TO PERFORM WORK. PATCHING SHALL
MATCH SURROUNDING SURFACES.
D. REFER TO WASTE AND VENT RISER DIAGRAMS AND DOMESTIC
WATER RISER DIAGRAMS FOR ADDITIONAL SIZES, PIPE ROUTING,
VALVES AND PLUMBING SPECIALTY DEVICES. REFER TO SHEET
M5.1 FOR PLUMBING ROUGH IN SCHEDULE, TYPICAL.
E. PROVIDE SLEEVES OR CORE DRILLING FOR ALL PIPING PASSING
THROUGH STRUCTURAL FOOTINGS AND FOUNDATION WALLS.
REFER TO SPECIFICATION SECTION 22 0500 AND DETAIL ON SHEET
M6.1 FOR ADDITIONAL INFORMATION. COORDINATE AND VERIFY
EXACT LOCATIONS AND ELEVATIONS WITH STRUCTURAL. TYPICAL.
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW íóéÉÇLéêáåíÉ Ç=å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW
1112 North 5th Street Minneapolis, MN 55411
(612) 343-5965
1624 North Riverfront Drive Mankato, MN 56001
(507) 625-7869 ëÜÉÉí= íáíäÉW ëÜÉÉí= åìãÄÉêW
DULUTH I TWIN CITIES I VIRGINIA
www.dsgw.com
023016.00
10/06/2023
10/06/2023
EDI-DOLEJS #23-035
14204
MIKE S. DOLEJS
Wagner
Pharmacy
USP
Compliance
111 WASHINGTON AVE. NW
WAGNER, SD 57380
AE, LS
MD
M2.0
Partial
Underfloor
Plan - Phase 2 -
Plumbing
8' 16'4'0 1/8" = 1'-0"M2.0
2 Partial Underfloor Plan - Phase 2 - Plumbing
NORTHNORTH
8' 16'4'0 1/8" = 1'-0"M2.0
1 Partial Underfloor Plan - Phase 2 - Plumbing Demolition
RefrigeratorRefrigerator
GENERAL NOTES
MEDICAL
RECORDS
OFFICE
115A
SCA
115B
PHARMACY
CONSULT
NARCOTICS
115C
ELECTRICAL
RECEIVING/HZD
STORAGE
BREAKROOM
HSKP/CLEAN
LINEN
STORAGE
TEMPORARY
PHARMACY-1
107-1
JANITOR
EYE LAB
EYEGLASS
FITTING
VISUAL
FIELDS
EYE
SCREENING
EYE EXAM
SUPPLY
INTERVIEW
ROOM
HZD WASTE
STORAGE
EEW-1
ETMV-1
INSTALL THERMOSTATIC
MIXING VALVES BELOW
THE SINK
EX. 1" HW-R
EX. 1 1/2" HW
EX. 2 1/2" CW
EX. 2 1/2" CW
EX. 1 1/2" HW
EX. 1" HW-R
3/4" HW-R
1" HW
1" CW
SK-1
SK-2
2" V
3/4" HW-R
1" HW
1" CW
2" V
3/4" CW
3/4" HW
3/4" HW-R
2" V UP
TO 4" VTR
1 1/2" V
SK-3
3/4" HW
3/4" CW
SK-4 / TMV-13/4" HW-R
THERMOSTATIC
RECIRCULATION
VALVE ASSEMBLY.
E
F
G
H
J
K
L
M
P
Q
121110987.175432
2" FCO
2" FCO
CONNECT NEW 1" CW, 1" HW AND 3/4"
HW-R TO EXISTING 2-1/2" CW, 1-1/2"
HW AND 1" HW-R. FIELD VERIFY
EXISTING SIZE AND LOCATION.
DISCONNECT AND REMOVE EXISTING
PLUMBING FIXTURE AND ASSOCIATED CW,
HW, WASTE AND VENT BACK TO MAINS AND
CAP. REFER TO DETAIL 2/M2.1 FOR NEW
WORK
E
F
G
H
J
K
L
M
P
Q
121110987.175432
DISCONNECT AND REMOVE EXISTING
CLEANOUT AND ASSOCIATED PIPING BACK
TO MAINS AND CAP. REFER TO DETAIL
2/M2.1 FOR NEW WORK
A. PROVIDE A WALL OR FLOOR CLEANOUT AS REQUIRED TO SERVE
EACH PLUMBING FIXTURE, SPECIALITY DEVICE, ETC. THAT HAS A
NON-ACCESSIBLE TRAP, TYPICAL.
B. PROVIDE A WALL CLEANOUT AT THE VERTICAL DRAIN, TO SERVE
EACH SINK, IN ACCORDANCE WITH CODE REQUIREMENTS.
TYPICAL.
C. PROVIDE A WALL CLEANOUT AT THE VERTICAL DRAIN, ABOVE THE
WASTE CONNECTION TO EACH URINAL IN ACCORDANCE WITH
CODE REQUIREMENTS. TYPICAL.
D. REFER TO PIPE HANGER AND SUPPORT DETAIL ON SHEET M6.1
INDICATING INSTALLATION REQUIREMENTS, TYPICAL.
E. REFER TO PIPE PENETRATION DETAIL ON SHEET M6.1 FOR PIPE
PENETRATION INSTALLATION REQUIREMENTS, TYPICAL.
F. REFER TO WASTE AND VENT RISER DIAGRAMS AND DOMESTIC
WATER RISER DIAGRAMS FOR ADDITIONAL SIZES, PIPE ROUTING,
VALVES AND PLUMBING SPECIALITY DEVICES. REFER TO SHEET
M5.1 FOR PLUMBING ROUGH-IN SCHEDULE. TYPICAL.
1. INDICATES PLUMBING FIXTURE OR PLUMBIG SPECIALTY DEVICE
IDENTIFICATION. PROVIDE PLUMBING ROUGH-INS AND FINAL
CONNECTIONS. REFER TO SPECIFICATION DIVISION 22 FOR MODEL,
DESCRIPTION, ACCESSORIES, ETC. REFER TO PLUMBING ROUGH-IN
SCHEDULE FOR ROUGH-IN SIZES, TYPICAL.
2. SHUT-OFF VALVE, TYPICAL, UNLESS OTHERWISE NOTED.
3. THERMOSTATIC RECIRCULATION VALVE ASSEMBLY. REFER TO
DIVISION 22 SPECIFICATION AND DETAIL FOR ADDITIONAL
INFORMATION AND REQUIREMENTS.
4. REFER TO DETAIL ON SHEET M6.1 FOR ADDITIONAL INFORMATION
AND REQUIREMENTS.
Çê~ïå=ÄóW
ÅÜÉÅâÉÇ=ÄóW íóéÉÇLéêáåíÉ Ç=å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW
Ç~íÉW éêçàÉÅí=@W ëáÖå~íìêÉW
1112 North 5th Street Minneapolis, MN 55411
(612) 343-5965
1624 North Riverfront Drive Mankato, MN 56001
(507) 625-7869 ëÜÉÉí= íáíäÉW ëÜÉÉí= åìãÄÉêW
DULUTH I TWIN CITIES I VIRGINIA
www.dsgw.com
023016.00
10/06/2023
10/06/2023
EDI-DOLEJS #23-035
14204
MIKE S. DOLEJS
Wagner
Pharmacy
USP
Compliance
111 WASHINGTON AVE. NW
WAGNER, SD 57380
AE, LS
MD
M2.1
Partial Floor
Plan - Phase 2 -
Plumbing
NORTH
8' 16'4'0 1/8" = 1'-0"M2.1
2 Partial Floor Plan - Phase 2 - Plumbing
NORTH
8' 16'4'0 1/8" = 1'-0"M2.1
1 Partial Floor Plan - Phase 2 - Plumbing Demolition
SK-4 / TMV-1
3/4" ETMVEEW-1
3/4" CW
3/4" HW
3/4" HW-R
SHUT OFF VALVE,
TYPICAL UNLESS
OTHERWISE NOTED.
THERMOSTATIC
RECIRCULATION
VALVE ASSEMBLY.
THERMOSTATIC
RECIRCULATION
VALVE ASSEMBLY.
SK-3
3/4" CW
3/4" HW
3/4" HW-R
SK-2
1" CW
1" HW
3/4" HW-R
1" CW
1" HW
3/4" HW-R
SK-1
SHUT OFF VALVE,
TYPICAL UNLESS
OTHERWISE NOTED.
EX. 2 1/2" CW
EX. 1 1/2" HW
EX. 1 1/2" HW
EX. 2 1/2" CW
EX. 1" HW-REX. 1" HW-R
EX. 8" SS
EX. 8" SS
8" SS
SK-3
SK-4 / TMV-1
2" SS
2" FCO 2" SS
SK-2
SK-1
2" FCO
2" V
1 1/2" V
2"…