This document is an addendum to the construction documents for renovating the Wagner Pharmacy to comply with United States Pharmacopeia (USP) compounding standards. The addendum includes revisions to the specifications, drawings, and mechanical/electrical components. Key changes include updates to the gypsum board assemblies, addition of handrails, revisions to demolition plans and floor plans, and updates to the mechanical/electrical systems such as adding instrumentation and controls for the HVAC system. The contract opportunity for this renovation project is solicitation number 75H70124R00025, issued by the Department of Health and Human Services Indian Health Service to renovate the existing outpatient pharmacy at the Wagner IHS Healthcare Facility in Wagner, South Dakota.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

2 West 1st Street, Suite 201, Duluth, Minnesota 55802 tel (218) 727-2626 fax (218) 722-7467

ADDENDUM 3

project Wagner Pharmacy USP Compliance project # 023016.01 date 05/16/24 from DSGW Architects to All planholders for above project

The following addendum shall become part of the construction documents for the construction of the above referenced project.

This addendum supersedes and supplements all previous reference to similar items.

I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am duly a Licensed Architect under the laws of the State of Minnesota.

Signature

Registration # 14817 Date 05/16/24 general clarifications 1. None specifications SECTION DESCRIPTION

09 21 16

1. Revise section 09 21 16 Gypsum Board Assemblies per attached reissued section

09 21 16

10 26 01

1. Add InPro 800 Model Handrails w/ wall returns to section 10 26 01, color to be selected.

drawings SECTION DESCRIPTION

A1.1

A1.2

Demolition Plans

1. Revise Demo Plan Notes Per attached reissued sheet A1.1

2. Revise Demolition Plan – Phase 1 Temporary Pharmacy 1/A1.1 per attached reissued sheet A1.1

Demolition Plans

1. Revise Demo Plan Notes per attached reissued sheet A1.2

2. Revise Demolition Plan – Phase 1 – Pharmacy 1/A1.2 per attached reissued sheet

A1.2

3. Revise Demolition Plan – Phase 2 - Pharmacy 2/A1.2 per attached reissued sheet

A1.2

A2.1 Floor Plans

1. Revise Floor Plan Notes per attached reissued sheet A2.1

2. Add Floor Plan – Phase 1 Temp Pharmacy 3/A2.1 per attached reissued sheet A2.1

3. Revise Floor Plan – Phase 1 Temporary Pharmacy 1/A2.1 per attached reissued sheet A2.1

A2.2 Floor Plans

1. Revise Floor Plan Notes per attached reissued sheet A2.2

2. Revise Elev at Pharmacy – South 3/A2.2 per attached reissued sheet A2.2

3. Revise Elev at Transaction Counter 10/A2.2 per attached reissued sheet A2.2

A4.2 Room Finish Schedule and Plans

1. Revise Finish Plan – Phase 1 – Temporary Pharmacy 1/A4.2 per attached reissued sheet A4.2 mechanical / electrical consultant

Mechanical/Electrical Addendum 3, dated 5/16/24, is to be included with this addendum as attached enclosures J Spec section 09 21 16, Sheets A1.1, A1.2, A2.1, A2.2, and A4.2, Mechanical/Electrical

Addendum Three

This addendum shall become part of this bid. The bidder shall insert the addendum number in the space were indicated on the proposal form. Failure to comply may result in the bid being rejected.

END OF ADDENDUM 3

EYE EXAM

SUPPLY

JANITOR

HSKP/CLEAN

LINEN

HZD WASTE

STORAGE

EYE SCREENING

VISUAL FIELDS

VESTIBULE

MEDICAL

RECORDS

W1

W2

C1

C1

CLOSET

OPEN

OFFICE

D1

Z12

Z12

Z13

A d d en d u m

SPECIMEN

TOILET

SUPPLY

TOILET

ULTRASOUND

CORRIDOR

SUPPLY

DARK ROOM

OFFICE

DRESSING

DRESSING

FILM READING

WORK AREA

Çê~ïå=ÄóW

ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW

Ç~íÉW éêçàÉÅí=@W

Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW

DULUTH I TWIN CITIES I VIRGINIA

www.dsgw.com

14817

5/16/2024 4:26:09 PM

023016.01

BC

RT

10/06/23

Wagner Pharmacy

USP

Compliance

A1.1

DEMOLITION

PLANS

111 Washington Ave. NW Wagner, SD 57380

1/4" = 1'-0"

DEMOLITION PLAN - PHASE 1 -

TEMPORARY PHARMACY

1/4" = 1'-0"

DEMOLITION PLAN - PHASE 1 -

RADIOLOGY DEPT.

Demo Plan Notes

C1 DEMO EXISTING CASEWORK SHELVING

C2 DEMO EXISTING WALL CABINETS AND GYP BD SOFFIT

C3 DEMO EXISTING COUNTER TOP AND BASECABINETS

C4 DEMO EXISTING TALL STORAGE CABINET AND GYP BD SOFFIT ABOVE

C5 REMOVE AND RELOCATE TALL OPEN SHELVING CABINET TO PHASE 1 TEMPORARY PHARMACY

D1 DEMO INTERIOR DOOR, FRAME, AND HARDWARE

F1 DEMO VCT FLOORING, VINYL BASE, AND SUSPENDED ACOUSTICAL CEILING TILE

F2 DEMO SUSPENDED ACOUSTICAL TILE CEILING

F3 DEMO VCT FLOORING, VINYL BASE AND SUSPENDED ACOUSTICAL TILE CEILING WHERE REMODELING OCCURS

G1 DEMO INTERIOR HOLLOW METAL FRAMED WINDOW

W1 DEMO PORTION OF EXISTING WALL AS REQUIRED FOR NEW DOOR OPENING

W2 DEMO PORTION OF EXISTING WALL AS REQUIRED FOR NEW TRANSACTION WINDOW

Z1 REMOVE & SALVAGE EXISTING HIGH-DENSITY MOBILE SHELVING FOR RELOCATION TO PHASE 1 TEMPORARY

PHARMACY

Z2 DEMO EXISTING TRANSACTION WINDOW AND SILL

Z3 REMOVE AND SALVAGE EXISTING WILL CALL STORAGE HANGERS ON WALL STANDARDS FOR RELOCATION

Z4 DEMO EXISTING PASS-THRU DOOR

Z5 DEMO EXISTING HOOD, REMOVE HEPA FILTER AND SALVAGE FOR SCRAP

Z6 REMOVE AND RELOCATE EXISTING SCRIPTPRO PHARMACY NOTICE BOARD AND BRACKET, CONTRACTOR TO

SCHEDULE RELOCATION WITH SCRIPTPRO

Z7 REMOVE AND SALVAGE WALL MOUNTED ITEMS SUCH AS WHITEBOARDS, LITERATURE RACKS AND SIGNAGE FOR

RELOCATION

Z8 REMOVE AND RELOCATE PYXIS SAFE TO PHASE 1 TEMPORARY PHARMACY

Z9 REMOVE AND RELOCATE SCRIPTPRO TO PHASE 1 TEMPORARY PHARMACY, CONTRACTOR TO SUBCONTRACT WITH

SCRIPTPRO FOR MOVING AND CALIBRATING EQUIPMENT

Z10 REMOVE AND RELOCATE REFRIGERATOR TO PHASE 1 TEMPORARY PHARMACY

Z11 REMOVE METAL LOCKERS, SALVAGE AND TURN OVER TO OWNER

Z12 DEMO EXISTING WALLGUARD/ HANDRAIL

Z13 REMOVE EXISTING DISPLAY CASE, SALVAGE FOR RELOCATION IN PHASE 1

Demo General Notes

1. Demolition notes and plans are provided as a guide only. Contractor to verify existing conditions and examine drawings and details to determine extent and limits of demolition to accommodate new construction.

2. Contractor is responsible for coordination of all aspects of demolition and reconstruction. Contractor to coordinate new work plan dimensions and installation of new materials and finishes, as required, whether indicated on drawings or not.

3. Demolition notes without leaders indicate that the note applies to the entire room.

4. Contractors shall coordinate all demolition work phasing and sequencing with owner prior to start of construction.

5. Verify existing wall type at wall infill or wall extension areas. If existing wall type does not match the called out wall type, infill or extend to match existing wall type instead.

6. Verify existing wall materials to be removed (gypsum board, stud, cmu, brick, etc.).

7. Provide transition strip at areas of new flooring meeting existing flooring and at new door openings in existing walls. Patch floor as required.

8. Prep floors as needed for new finishes.

9. Remove existing wall mounted items such as grab bars, mirrors, paper towel dispensers, toilet paper dispensers, soap dispensers, toilet partitions, etc in demolished areas. Patch existing walls as required.

10. Patch subfloor, walls, & ceilings disturbed by demolition. Patch to match existing finishes as required.

11. Remove all finishes, adhesives, or other materials that conflict with new finishes scheduled in existing or newly remodeled spaces.

12. Verify any items to be retained for owners use prior to removal.

13. Provide protection and be responsible for Owner's equipment, furniture and any existing finishes to remain and repair or replace any damaged areas as a result of the work. All existing finishes to remain shall be cleaned at the completion of construction. Document any existing conditions or damages prior to the start of construction.

Z1 êÉîáëáçå=L áëëìÉ åçK Ç~íÉ

^ÇÇÉåÇìã P RLNSLOQ

A d d en d u m

D AE RR CE HT IS TI EG CE TR

. NG OE .R

14817

RYAN

TURNER

R e fr ig e ra to r

Z3

PHARMACY

OFFICE

CONSULT

OFFICE

OFFICE

OFFICE

ELEC

MEDICAL

RECORDS

SCA

CORRIDOR

CORRIDOR

CORRIDOR

Z8

Z9

Z10

C5

C5 C5

Z10

Z6

A d d en d u m

Z2

C2

C2

C3

C2Z4

C3

C4

C4

Z5

PHARMACY

OFFICE

CONSULT

OFFICE

OFFICE

OFFICE

ELEC

MEDICAL

RECORDS

SCA

CORRIDOR

CORRIDOR

CORRIDOR

D1

D1 D1

D1

D1 D1

D1

D1

Z7

Z7

F1

F1

F1

F1

F1

F1

F2

F3

W1

W1W1 G1

G1

Z11

A d d en d u m

Çê~ïå=ÄóW

ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW

Ç~íÉW éêçàÉÅí=@W

Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW

DULUTH I TWIN CITIES I VIRGINIA

www.dsgw.com

14817

5/16/2024 4:26:09 PM

023016.01

BC

RT

10/06/23

Wagner Pharmacy

USP

Compliance

A1.2

DEMOLITION

PLANS

111 Washington Ave. NW Wagner, SD 57380 êÉîáëáçå=L áëëìÉ åçK Ç~íÉ

^ÇÇÉåÇìã P RLNSLOQ

1/4" = 1'-0"

DEMOLITION PLAN - PHASE 1 -

PHARMACY

1/4" = 1'-0"

DEMOLITION PLAN - PHASE 2 -

PHARMACY

Demo General Notes

1. Demolition notes and plans are provided as a guide only. Contractor to verify existing conditions and examine drawings and details to determine extent and limits of demolition to accommodate new construction.

2. Contractor is responsible for coordination of all aspects of demolition and reconstruction. Contractor to coordinate new work plan dimensions and installation of new materials and finishes, as required, whether indicated on drawings or not.

3. Demolition notes without leaders indicate that the note applies to the entire room.

4. Contractors shall coordinate all demolition work phasing and sequencing with owner prior to start of construction.

5. Verify existing wall type at wall infill or wall extension areas. If existing wall type does not match the called out wall type, infill or extend to match existing wall type instead.

6. Verify existing wall materials to be removed (gypsum board, stud, cmu, brick, etc.).

7. Provide transition strip at areas of new flooring meeting existing flooring and at new door openings in existing walls. Patch floor as required.

8. Prep floors as needed for new finishes.

9. Remove existing wall mounted items such as grab bars, mirrors, paper towel dispensers, toilet paper dispensers, soap dispensers, toilet partitions, etc in demolished areas. Patch existing walls as required.

10. Patch subfloor, walls, & ceilings disturbed by demolition. Patch to match existing finishes as required.

11. Remove all finishes, adhesives, or other materials that conflict with new finishes scheduled in existing or newly remodeled spaces.

12. Verify any items to be retained for owners use prior to removal.

13. Provide protection and be responsible for Owner's equipment, furniture and any existing finishes to remain and repair or replace any damaged areas as a result of the work. All existing finishes to remain shall be cleaned at the completion of construction. Document any existing conditions or damages prior to the start of construction.

Demo Plan Notes

C1 DEMO EXISTING CASEWORK SHELVING

C2 DEMO EXISTING WALL CABINETS AND GYP BD SOFFIT

C3 DEMO EXISTING COUNTER TOP AND BASECABINETS

C4 DEMO EXISTING TALL STORAGE CABINET AND GYP BD SOFFIT ABOVE

C5 REMOVE AND RELOCATE TALL OPEN SHELVING CABINET TO PHASE 1 TEMPORARY PHARMACY

D1 DEMO INTERIOR DOOR, FRAME, AND HARDWARE

F1 DEMO VCT FLOORING, VINYL BASE, AND SUSPENDED ACOUSTICAL CEILING TILE

F2 DEMO SUSPENDED ACOUSTICAL TILE CEILING

F3 DEMO VCT FLOORING, VINYL BASE AND SUSPENDED ACOUSTICAL TILE CEILING WHERE REMODELING OCCURS

G1 DEMO INTERIOR HOLLOW METAL FRAMED WINDOW

W1 DEMO PORTION OF EXISTING WALL AS REQUIRED FOR NEW DOOR OPENING

W2 DEMO PORTION OF EXISTING WALL AS REQUIRED FOR NEW TRANSACTION WINDOW

Z1 REMOVE & SALVAGE EXISTING HIGH-DENSITY MOBILE SHELVING FOR RELOCATION TO PHASE 1 TEMPORARY

PHARMACY

Z2 DEMO EXISTING TRANSACTION WINDOW AND SILL

Z3 REMOVE AND SALVAGE EXISTING WILL CALL STORAGE HANGERS ON WALL STANDARDS FOR RELOCATION

Z4 DEMO EXISTING PASS-THRU DOOR

Z5 DEMO EXISTING HOOD, REMOVE HEPA FILTER AND SALVAGE FOR SCRAP

Z6 REMOVE AND RELOCATE EXISTING SCRIPTPRO PHARMACY NOTICE BOARD AND BRACKET, CONTRACTOR TO

SCHEDULE RELOCATION WITH SCRIPTPRO

Z7 REMOVE AND SALVAGE WALL MOUNTED ITEMS SUCH AS WHITEBOARDS, LITERATURE RACKS AND SIGNAGE FOR

RELOCATION

Z8 REMOVE AND RELOCATE PYXIS SAFE TO PHASE 1 TEMPORARY PHARMACY

Z9 REMOVE AND RELOCATE SCRIPTPRO TO PHASE 1 TEMPORARY PHARMACY, CONTRACTOR TO SUBCONTRACT WITH

SCRIPTPRO FOR MOVING AND CALIBRATING EQUIPMENT

Z10 REMOVE AND RELOCATE REFRIGERATOR TO PHASE 1 TEMPORARY PHARMACY

Z11 REMOVE METAL LOCKERS, SALVAGE AND TURN OVER TO OWNER

Z12 DEMO EXISTING WALLGUARD/ HANDRAIL

Z13 REMOVE EXISTING DISPLAY CASE, SALVAGE FOR RELOCATION IN PHASE 1

A d d en d u m

D AE RR CE HT IS TI EG CE TR

. NG OE .R

14817

Refrigerator

STERILE

DRUG INFO

EYE EXAM

SUPPLY

JANITOR

HSKP/CLEAN

LINEN

HZD WASTE

STORAGE

EYE SCREENING

VESTIBULE

TEMPORARY

PHARMACY

DISPENSING

4 5

8'-0"

133B

OFFICE5B

5B

H M

-W

HM-W1

TA

-W

133B

MEDICAL

RECORDS

106B

MAIN

CORRIDOR

2'-0"

A d d en d u m

WOMEN TOILET

VENI

SPECIMEN

TOILET

SUPPLY

TOILET

ULTRASOUND

CORRIDOR

SUPPLY

DARK ROOM

OFFICE

DRESSING

DRESSING

FILM READING

WORK AREA

NEW SHEET VINYL

TO MATCH EXISTING

EXISTING FLOOR

TO REMAIN

NEW PAINT AND

VINYL BASE TO MATCH

EXISTING,

EXISTING COVE BASE

MANUFACTUER: VPI

COLOR: LONDON GRAY

EXISTING SHEET VINYL FLOOR

MANUFACTUER: CONGOLEUM

STYLE AND COLOR: AIR STEP

ADVANTAGE REMINISCE

CATCHING FIREFLIES

Wall Types

5A

3 5/8" METAL STUD

@ 16" O.C.

5/8" GYP.BD. EA. SIDE

BATT INSULATION

METAL STUD WALL TO

STRUCTURE

5B

OMIT BATT INSULATION, GYP BD

TO EXTEND TO 6" ABOVE CEILING

3 5/8" METAL STUD

CHANNEL

3 5/8" METAL STUD

DEFLECTION TRACK

BASE - SEE

SCHEDULE

ROOF OR FLOOR

STRUCTURE

CLG WHERE APPLICABLE;

SEE RCP

1A

5/8" GYP.BD.

FURRING OVER

EXISTING WALL TO

STRUCTURE

BASE - SEE

SCHEDULE

ROOF OR FLOOR

STRUCTURE

CLG WHERE

APPLICABLE; SEE

RCP

3A

3 5/8" METAL STUD @

16" O.C.

5/8" GYP.BD.

FURRING OVER

EXISTING WALL TO

STRUCTURE

3 5/8" METAL STUD

CHANNEL

BASE - SEE SCHEDULE

ROOF OR FLOOR

STRUCTURE

CLG WHERE APPLICABLE;

SEE RCP

3 5/8" METAL STUD

DEFLECTION TRACK

ACOUSTIC SEALANT

EA. SIDE

ACOUSTIC SEALANT

NOTE: ALL WALLS SHALL BE BUILT TO STRUCTURE ABOVE UNLESS OTHERWISE NOTED

7/8" 4 3/8"

4 7/8"

SECTION

@ FLOOR

SECTION

@ HEAD

SECTION

@ FLOOR

PLAN

VIEW

SECTION

@ HEAD

SECTION

@ FLOOR

PLAN

VIEW

SECTION

@ HEAD

SECURITY BARRIER

MESH

SECURITY BARRIER

MESH

EXTEND EXISTING WALL

TO STR ABOVE: 3 5/8"

METAL STUD @ 16" O.C.

EXISTING WALL

1B

5/8" GYP.BD.

FURRING OVER

EXISTING WALL TO

STRUCTURE

BASE - SEE

SCHEDULE

ROOF OR FLOOR

STRUCTURE

CLG WHERE

APPLICABLE; SEE

RCP

7/8"

SECTION

@ FLOOR

SECTION

@ HEAD

SECURITY BARRIER

MESH

EXISTING WALL

5C

3 5/8" 16 GAUGE METAL

STUD @ 16" O.C.

5/8" GYP.BD. EA. SIDE

BATT INSULATION

METAL STUD WALL TO

STRUCTURE W/

SECURITY BARRIER

MESH

3 5/8" 16 GAUGE METAL

STUD CHANNEL

3 5/8" 16 GAUGE METAL

STUD DEFLECTION TRACK

BASE - SEE

SCHEDULE

ROOF OR FLOOR

STRUCTURE

CLG WHERE APPLICABLE;

SEE RCP

ACOUSTIC SEALANT

EA. SIDE

5 1/8"

SECTION

@ FLOOR

PLAN

VIEW

SECTION

@ HEAD

SECURITY BARRIER

MESH

5D

3 5/8" METAL STUD

@ 16" O.C.

5/8" GYP.BD. EA. SIDE

BATT INSULATION

METAL STUD WALL TO

STRUCTURE W/

BULLET RESISTANT

PANEL

3 5/8" METAL STUD

CHANNEL

3 5/8" METAL STUD

DEFLECTION TRACK

BASE - SEE

SCHEDULE

ROOF OR FLOOR

STRUCTURE

CLG WHERE APPLICABLE;

SEE RCP

ACOUSTIC SEALANT

EA. SIDE

5 3/8"

SECTION

@ FLOOR

PLAN

VIEW

SECTION

@ HEAD

BULLET RESISTANT

PANEL

CONSULT

OUTPATIENT/PHARMACY

WAITING

CONSULT

PHARMACY

Çê~ïå=ÄóW

ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW

Ç~íÉW éêçàÉÅí=@W

Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW

DULUTH I TWIN CITIES I VIRGINIA

www.dsgw.com

14817

5/17/2024 8:48:39 AM

023016.01

BC

RT

10/06/23

Wagner Pharmacy

USP

Compliance

A2.1

FLOOR PLANS

111 Washington Ave. NW Wagner, SD 57380

1/4" = 1'-0"

FLOOR PLAN - PHASE 1 - TEMPORARY

PHARMACY

Floor Plan Notes 1 EXISTING RELOCATED HIGH DENSITY MOBILE SHELVING UNIT FROM PHASE 1 DEMO - RADIOLOGY DEPT.

2 NEW PORTABLE HAND WASHING CART, SEE SECTION 10 28 00

3 EXISTING RELOCATED SCRIPTPRO, CONTRACTOR TO SUBCONTRACT WITH SCRIPTPRO FOR MOVING AND CALIBRATING EQUIPMENT.

4 NEW 30"x60" SIT-STAND DESK (NIC)

5 NEW 30"x48" SIT-STAND DESK (NIC)

6 NEW 24"x60" SIT-STAND DESK (NIC)

7 EXISTING RELOCATED PYXIS SAFE

8 EXISTING RELOCATED UNDERCOUNTER REFRIGERATOR

9 EXISTING RELOCATED REFRIGERATOR

10 EXISTING RELOCATED WALL MOUNTED WILL CALL HANGING BRACKETS FROM PHASE 1 PHARMACY DEMO

11 EXISTING RELOCATED TALL OPEN SHELVING CABINET FROM PHASE 1 PHARMACY DEMO

12 RELOCATED CORROSIVE CABINET

13 STEEL PACKAGE RECIEVER

14 ELECTRICAL POWER POLE - SEE ELEC

15 UPPER CABINETS, SEE SECTION 12 00 50

16 NEW 4'-0" WIDE WALL MOUNTED WILL CALL HANGING BRACKETS, SEE SECTION 10 28 00

17 WIRE MESH PARTITION

18 CART (NIC)

19 3'-0" x 4'-0" TACKBOARD

20 LITERATURE RACK

21 (2) ROBE HOOKS, MOUNT 5'-0" A.F.F.

23 BOUFFANT CAP BOX HOLDER, MOUNT 5'-0" A.F.F. TO CENTERLINE, SEE SECTION 10 28 00

24 SHOE COVER BOX HOLDER, MOUNT 5'-0" A.F.F. TO CENTERLINE, SEE SECTION 10 28 00

25 EXISTING RELOCATED SCRIPTPRO PHARMACY NOTICE BOARD AND BRACKET,CONTRACTOR TO PROVIDE WALL BACKING AND SCHEDULE

RELOCATION WITH SCRIPTPRO.

26 HIGH-DENSITY SHELVING UNIT, SEE SECTION 12 00 50

27 CONSULT DESK, SEE SECTION 12 00 50

28 EXISTING DISPLAY CASE RELOCATED FROM PHASE 1 DEMO

29 NEW HANDRAIL, INPRO 800 MODEL W/ WALL RETURNS. MOUNT 3'-0" A.F.F TO TOP OF HANDRAIL

1/4" = 1'-0"

FLOOR PLAN - PHASE 1 - RADIOLOGY

DEPT.

êÉîáëáçå=L áëëìÉ åçK Ç~íÉ

^ÇÇÉåÇìã O PLOOLOQ

^ÇÇÉåÇìã P RLNSLOQ

A d d en d u m

1/4" = 1'-0"

FLOOR PLAN - PHASE 1 TEMP

PHARMACY

A d d en d u m

A d d en d u m

D AE RR CE HT IS TI EG CE TR

. NG OE .R

14817

U.C.

Refr.

Refrigerator

PHARMACY

CONSULT

ELECTRICAL

ALCOVE

CORRIDOR

CORRIDOR

OFFICE

115A

SCA

115B

BREAKROOM

RECEIVING/HZD

STORAGE

NARCOTICS

115C

A2.2

A2.2

A2.2

A2.2

A2.24

A2.2

A2.2

/8

/4

4A

5A

5A

5A

5B

5 3

1A

1A

1B

5C

5C

1B

1B

1B

1A

1B

1A

1A

1A

1B

1A 1A 1B

1B

5D 5D

5A

1B

1B

8'-0"

TA-W1

A

B

146A

146B

145B145A

114A

B

7'-6" 9'-1 1/2"

MEDICAL

RECORDS

3'-0" 4'-0"

OUTPATIENT/PHARMACY

WAITING

17 18

A2.2

A2.2 12

SD (OPCI)

PTH (OPCI)

VERIFY

3'-0"

1"1"

2'-3" 2'-0" 2'-0" 2'-0" 2'-7"

RELOCATED

REFR.

RELOCATED

U/C REFR.

TA-W1

STEEL PACKAGE

RECIEVER

3'-1" 3'-0"

PULL OUT

PINTER

SHELF

WALL CABINET

SEE SECTION

12 00 50

BASE CABINETS

AND COUNTERTOP,

SEE SECTION

12 00 50

WALL PORT W/

2" I.D.

GROMMET IN

COUNTERTOP

FILLMASTER

ON SIDE WALL

(OPCI)

PTH (OPCI)

SD (OPCI)

FILLMASTER

FILTRATION

SYSTEM MOUNTED

IN CABINET

1"

3'-6"3'-0"

NEW WALL

MOUNTED

WILL CALL

BRACKETS

BASE CABINETS

AND COUNTERTOP,

SEE SECTION

12 00 50

TALL CABINET,

SEE SECTION

12 00 50

3'-0" 3'-0" 2'-6" 3'-0"

OPEN

1"2'-0"2'-0"2'-0"2'-0"2'-0"2'-0"2'-1"

BASE CABINETS

AND COUNTERTOP,

SEE SECTION

12 00 50

WALL CABINETS,

SEE SECTION

12 00 50

6'-0"

OPEN 3

PTH (OPCI)

SD (OPCI)

EYEWASH,

SEE MECH 3

3'-6"

EXHAUST

GRILLS, SEE

MECH

BASE CABINETS

AND COUNTERTOP,

SEE SECTION

12 00 50

WALL CABINETS,

SEE SECTION

12 00 50

(5) ROBE HOOKS

6 TIER METAL

LOCKERS, SEE

SECTION 12 00 50

3'-9"

4'-0" 3'-0"

QUICKSERVE

TRANSACTION

WINDOW W/

INTERCOM SYSTEM

STEEL PACKAGE

RECEIVER

RELOCATED TV AND

BRACKET PROVIDE

BLOCKING

COUNTERTOP, SEE

SECTION 12 00 50

4" GROMMET IN C-TOP

WALL PORT W/ 2" I.D.SUPPORT

BRACKETS

5'-3"

COUNTERTOP,

SEE SECTION

12 00 50

1"1" 2'-0" 1'-6" 2'-0"

2'-6"3'-0"

PTH (OPCI) ON

SIDE WALL

SD (OPCI)

WAST BIN BEHIND

DOOR

MICROWAVE

(NIC)

COFFEE

(NIC)

U/C REFR

(NIC)

BASE CABINETS

AND COUNTERTOP,

SEE SECTION

12 00 50

WALL CABINETS,

SEE SECTION

12 00 50

Wall Types

5A

3 5/8" METAL STUD

@ 16" O.C.

5/8" GYP.BD. EA. SIDE

BATT INSULATION

METAL STUD WALL TO

STRUCTURE

5B

OMIT BATT INSULATION, GYP BD

TO EXTEND TO 6" ABOVE CEILING

3 5/8" METAL STUD

CHANNEL

3 5/8" METAL STUD

DEFLECTION TRACK

BASE - SEE

SCHEDULE

ROOF OR FLOOR

STRUCTURE

CLG WHERE APPLICABLE;

SEE RCP

1A

5/8" GYP.BD.

FURRING OVER

EXISTING WALL TO

STRUCTURE

BASE - SEE

SCHEDULE

ROOF OR FLOOR

STRUCTURE

CLG WHERE

APPLICABLE; SEE

RCP

3A

3 5/8" METAL STUD @

16" O.C.

5/8" GYP.BD.

FURRING OVER

EXISTING WALL TO

STRUCTURE

3 5/8" METAL STUD

CHANNEL

BASE - SEE SCHEDULE

ROOF OR FLOOR

STRUCTURE

CLG WHERE APPLICABLE;

SEE RCP

3 5/8" METAL STUD

DEFLECTION TRACK

ACOUSTIC SEALANT

EA. SIDE

ACOUSTIC SEALANT

NOTE: ALL WALLS SHALL BE BUILT TO STRUCTURE ABOVE UNLESS OTHERWISE NOTED

7/8" 4 3/8"

4 7/8"

SECTION

@ FLOOR

SECTION

@ HEAD

SECTION

@ FLOOR

PLAN

VIEW

SECTION

@ HEAD

SECTION

@ FLOOR

PLAN

VIEW

SECTION

@ HEAD

SECURITY BARRIER

MESH

SECURITY BARRIER

MESH

EXTEND EXISTING WALL

TO STR ABOVE: 3 5/8"

METAL STUD @ 16" O.C.

EXISTING WALL

1B

5/8" GYP.BD.

FURRING OVER

EXISTING WALL TO

STRUCTURE

BASE - SEE

SCHEDULE

ROOF OR FLOOR

STRUCTURE

CLG WHERE

APPLICABLE; SEE

RCP

7/8"

SECTION

@ FLOOR

SECTION

@ HEAD

SECURITY BARRIER

MESH

EXISTING WALL

5C

3 5/8" 16 GAUGE METAL

STUD @ 16" O.C.

5/8" GYP.BD. EA. SIDE

BATT INSULATION

METAL STUD WALL TO

STRUCTURE W/

SECURITY BARRIER

MESH

3 5/8" 16 GAUGE METAL

STUD CHANNEL

3 5/8" 16 GAUGE METAL

STUD DEFLECTION TRACK

BASE - SEE

SCHEDULE

ROOF OR FLOOR

STRUCTURE

CLG WHERE APPLICABLE;

SEE RCP

ACOUSTIC SEALANT

EA. SIDE

5 1/8"

SECTION

@ FLOOR

PLAN

VIEW

SECTION

@ HEAD

SECURITY BARRIER

MESH

5D

3 5/8" METAL STUD

@ 16" O.C.

5/8" GYP.BD. EA. SIDE

BATT INSULATION

METAL STUD WALL TO

STRUCTURE W/

BULLET RESISTANT

PANEL

3 5/8" METAL STUD

CHANNEL

3 5/8" METAL STUD

DEFLECTION TRACK

BASE - SEE

SCHEDULE

ROOF OR FLOOR

STRUCTURE

CLG WHERE APPLICABLE;

SEE RCP

ACOUSTIC SEALANT

EA. SIDE

5 3/8"

SECTION

@ FLOOR

PLAN

VIEW

SECTION

@ HEAD

BULLET RESISTANT

PANEL

3'-0"

TALL CABINET ,

SEE SECTION

12 00 50

1" 3'-0" 1'-11"

EXISTING

RELOCATED

PYXIS SAFE

3'-0"

WALL CABINET

SEE SECTION

12 00 50

BASE CABINET

AND COUNTERTOP

SEE SECTION

12 00 50

OPEN

Çê~ïå=ÄóW

ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW

Ç~íÉW éêçàÉÅí=@W

Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW

DULUTH I TWIN CITIES I VIRGINIA

www.dsgw.com

14817

5/17/2024 8:48:40 AM

023016.01

BC

RT

10/06/23

Wagner Pharmacy

USP

Compliance

A2.2

FLOOR PLANS

111 Washington Ave. NW Wagner, SD 57380

1/4" = 1'-0"

FLOOR PLAN - PHASE 2 - PHARMACY

1/4" = 1'-0"

ELEV AT SCA - SOUTH

1/4" = 1'-0"

ELEV AT PHARMACY - SOUTH

1/4" = 1'-0"

ELEV AT PHARMACY - WEST

1/4" = 1'-0"

ELEV AT PHARMACY - NORTH

1/4" = 1'-0"

ELEV AT RECEIVING / HZRD STOR

1/4" = 1'-0"

ELEV BREAK RM - NORTH

1/4" = 1'-0"

ELEV AT TRANSACTION COUNTER

Floor Plan Notes 1 EXISTING RELOCATED HIGH DENSITY MOBILE SHELVING UNIT FROM PHASE 1 DEMO - RADIOLOGY DEPT.

2 NEW PORTABLE HAND WASHING CART, SEE SECTION 10 28 00

3 EXISTING RELOCATED SCRIPTPRO, CONTRACTOR TO SUBCONTRACT WITH SCRIPTPRO FOR MOVING AND CALIBRATING EQUIPMENT.

4 NEW 30"x60" SIT-STAND DESK (NIC)

5 NEW 30"x48" SIT-STAND DESK (NIC)

6 NEW 24"x60" SIT-STAND DESK (NIC)

7 EXISTING RELOCATED PYXIS SAFE

8 EXISTING RELOCATED UNDERCOUNTER REFRIGERATOR

9 EXISTING RELOCATED REFRIGERATOR

10 EXISTING RELOCATED WALL MOUNTED WILL CALL HANGING BRACKETS FROM PHASE 1 PHARMACY DEMO

11 EXISTING RELOCATED TALL OPEN SHELVING CABINET FROM PHASE 1 PHARMACY DEMO

12 RELOCATED CORROSIVE CABINET

13 STEEL PACKAGE RECIEVER

14 ELECTRICAL POWER POLE - SEE ELEC

15 UPPER CABINETS, SEE SECTION 12 00 50

16 NEW 4'-0" WIDE WALL MOUNTED WILL CALL HANGING BRACKETS, SEE SECTION 10 28 00

17 WIRE MESH PARTITION

18 CART (NIC)

19 3'-0" x 4'-0" TACKBOARD

20 LITERATURE RACK

21 (2) ROBE HOOKS, MOUNT 5'-0" A.F.F.

23 BOUFFANT CAP BOX HOLDER, MOUNT 5'-0" A.F.F. TO CENTERLINE, SEE SECTION 10 28 00

24 SHOE COVER BOX HOLDER, MOUNT 5'-0" A.F.F. TO CENTERLINE, SEE SECTION 10 28 00

25 EXISTING RELOCATED SCRIPTPRO PHARMACY NOTICE BOARD AND BRACKET,CONTRACTOR TO PROVIDE WALL BACKING AND SCHEDULE

RELOCATION WITH SCRIPTPRO.

26 HIGH-DENSITY SHELVING UNIT, SEE SECTION 12 00 50

27 CONSULT DESK, SEE SECTION 12 00 50

28 EXISTING DISPLAY CASE RELOCATED FROM PHASE 1 DEMO

29 NEW HANDRAIL, INPRO 800 MODEL W/ WALL RETURNS. MOUNT 3'-0" A.F.F TO TOP OF HANDRAIL

1/4" = 1'-0"

ELEV BREAK RM - EAST

1/4" = 1'-0"

ELEV BREAK RM - SOUTH

êÉîáëáçå=L áëëìÉ åçK Ç~íÉ

^ÇÇÉåÇìã O PLOOLOQ

^ÇÇÉåÇìã P RLNSLOQ

1/4" = 1'-0"

ELEV OFFICE - NORTH

1/4" = 1'-0"

ELEV AT NARCOTICS - WEST

A d d en d u m

A d d en d u m

A d d en d u m

A d d en d u m

D AE RR CE HT IS TI EG CE TR

. NG OE .R

14817

STERILE

DRUG INFO

EYE EXAM

SUPPLY

JANITOR

HSKP/CLEAN

LINEN

HZD WASTE

STORAGE

EYE SCREENING

VESTIBULE

TEMPORARY

PHARMACY

DISPENSING

133B

OFFICE

MEDICAL

RECORDS

MAIN

CORRIDOR

CG-1

PNT-1

PNT-1

PNT-5

PNT-5

INPRO 800 MODEL HANDRAIL

W/ WALL RETURNS,

COLOR TO BE SELECTED

INPRO 800 MODEL HANDRAIL

W/ WALL RETURNS,

COLOR TO BE SELECTED

INPRO 800 MODEL HANDRAIL

W/ WALL RETURNS,

COLOR TO BE SELECTED

A d d en d u m

PHARMACY

CONSULT

ELECTRICAL

ALCOVE

CORRIDOR

CORRIDOR

OFFICE

115A

SCA

115B

BREAKROOM

RECEIVING/HZD

STORAGE

NARCOTICS

115C

TA-W1

MEDICAL

RECORDS

OUTPATIENT/PHARMACY

WAITING

PNT-5

PNT-5

PNT-5

PNT-5

CG-1 CG-1

CG-1 CG-1

SV-2

SV-3

FRP WAINSCOT

4'-4" AFF

PNT-2

Finish Abbreviations

ACT ACOUSTICAL CEILING TILE

CT PORCELAIN/CERAMIC TILE

EXIST. EXISTING

GYP. BD. GYPSUM BOARD

LVT LUXURY VINYL TILE

T.B.B. TILE BACKER BOARD

VCT VINYL COMPOSITION TILE

QT QUARRY TILE

EP EPOXY

PNT PAINT

CPT CARPET

VWC VYNL WALLCOVERING

WB WOOD BASE

WS WINDOW SHADE

WD WOOD

FRP FIBER REFORCED PANEL

CG CORNER GUARD

VB VINYL BASE

1. SEE FINISH PLAN FOR CLARIFICATION OF FLOOR AND WALL FINISH LOCATIONS.

2. ALL WALLS TO RECIEVE PNT-1 UNLESS OTHERWISE NOTED

3. ALL CEILING TO RECEIVE PNT-4 UNLESS OTHERWISE NOTED

4. ALL HM FRAMES AND DOORS TO RECEIVE PNT-3 UNLESS OTHERWISE NOTED

5. ALL FLOORS TO RECEIVE RB-1 UNLESS OTHERWISE NOTED IN FINISH SCHEDULE

Finish Notes

Çê~ïå=ÄóW

ÅÜÉÅâÉÇ=ÄóW éêáåíÉÇ= å~ãÉW êÉÖK=@W ëáÖå=Ç~íÉW

Ç~íÉW éêçàÉÅí=@W

Ryan Turner, AIA, ACHA, EDAC ëÜÉÉí=íáíäÉW ëÜÉÉí= åìãÄÉêW

DULUTH I TWIN CITIES I VIRGINIA

www.dsgw.com

14817

5/16/2024 4:32:11 PM

023016.01

BC

RT

10/06/23

Wagner

Pharmacy

USP

Compliance

A4.2

ROOM FINISH

SCHEDULE AND

PLANS

111 Washington Ave. NW

Wagner, SD 57380

ROOM FINISH SCHEDULE - PHASE 2

NO. NAME

FLOOR WALL FINISH CEILING

NOTESFINISH BASE NORTH EAST SOUTH WEST MAT'L FINISH

108 OUTPATIENT/PHARMACY WAITING -- SEE NOTES PNT PNT -- -- -- -- PATCH TO MATCH WERE REMODELING OCCURS

114 CONSULT LVT-1 RB PNT PNT-2 PNT PNT SACT-1 --

115 PHARMACY SV-1 RB PNT-1/PNT-2 PNT PNT PNT SACT-1 --

115A OFFICE LVT-1 RB PNT-2 PNT PNT PNT SACT-1 --

115B SCA SV-2, SV-3 SV-2, SV-3 EPOXY PNT EPOXY PNT EPOXY PNT EPOXY PNT GYP BD EPOXY PAINT PROVIDE CLEAN ROOM SEALANT AT TOP CAP OF BASE AND

WALL

115C NARCOTICS SV-2 RB PNT PNT PNT PNT GYP BD PNT

133 MEDICAL RECORDS -- SEE NOTES -- -- PNT PNT SACT-1 -- PATCH TO MATCH WERE REMODELING OCCURS

145 RECEIVING/HZD STORAGE SV-2 RB FRP/ EPOXY PNT EPOXY PNT EPOXY PNT EPOXY PNT SACT-1 --

146 BREAKROOM LVT-1 RB PNT PNT PNT PNT-2 SACT-1 --

161 CORRIDOR -- SEE NOTES -- -- -- PNT -- -- PATCH TO MATCH WERE REMODELING OCCURS

170 CORRIDOR -- SEE NOTES PNT -- -- -- -- -- PATCH TO MATCH WERE REMODELING OCCURS

ROOM FINISH SCHEDULE - PHASE 1

NO. NAME

FLOOR WALL FINISH CEILING

NOTESFINISH BASE NORTH EAST SOUTH WEST MAT'L FINISH

101 MAIN CORRIDOR -- SEE NOTES -- SEE NOTES -- -- -- -- PATCH TO MATCH WERE REMODELING OCCURS

106 DISPENSING -- -- PNT PNT PNT PNT -- --

107 TEMPORARY PHARMACY -- -- -- -- -- -- -- --

133 MEDICAL RECORDS - SEE NOTES PNT PNT - - - -- PATCH TO MATCH WERE REMODELING OCCURS

133B OFFICE LVT-1 RB PNT PNT PNT PNT SACT-1 --

202 WORK AREA SEE NOTES SEE NOTES PNT PNT -- PNT -- -- PATCH TO MATCH WERE REMODELING OCCURS

1/4" = 1'-0"

FINISH PLAN - PHASE 1 - TEMPORARY

PHARMACY

1/4" = 1'-0"

FINISH PLAN - PHASE 2 - PHARMACY

êÉîáëáçå=L áëëìÉ åçK Ç~íÉ

^ÇÇÉåÇìã P RLNSLOQ

D AE RR CE HT IS TI EG CE TR

. NG OE .R

14817

May 16, 2024 EDI-Dolejs, Inc. # 23-035

23016.10 – Wagner Pharmacy ADDENDUM THREE- 1 USP Compliance

MECHANICAL/ELECTRICAL ADDENDUM THREE

DIVISION 21 – FIRE PROTECTION

CHANGES TO THE PROJECT MANUAL:

None.

CHANGES TO THE MECHANICAL DRAWINGS:

DIVISION 22 – PLUMBING

DIVISION 23 – HEATING, VENTILATION, AND AIR CONDITIONING

Table of Contents:

23 0900 – INSTRUMENTATION AND CONTROL FOR HVAC section has been added to the Table of Contents. Refer to attached TOC.

Section 23 0900 – INSTRUMENTATION AND CONTROL FOR HVAC

1. The section has been added. Refer to attached section 230900.

Section 23 0993 – SEQUENCE OF OPERATION FOR HVAC CONTROLS

2. The section has been updated. Refer to attached section 230993.

Section 23 3300 – AIR DUCT ACCESSORIES

1. Cable Operated Dampers have been added as follow:

CABLE OPERATED MANUAL VOLUME DAMPERS

a. Manufacturers:

i. Young Regulator Co.

b. Round Damper:

i. Model 5020CC with Model 270-896C Bowden Cable Controller with Torx head tamperproof screw.

c. Rectangular Damper:

May 16, 2024 EDI-Dolejs, Inc. # 23-035

23016.10 – Wagner Pharmacy ADDENDUM THREE- 2 USP Compliance

i. Model 830ACC with Model 270-896C Bowden Cable Controller with Torx head tamperproof screw.

DIVISION 26 – ELECTRICAL

CHANGES TO THE ELECTRICAL DRAWINGS:

Drawing E2.1 – Partial Floor Plans – Lighting: (Reissued)

1. Refer to revised sheet for revisions and additional information.

Drawing E3.1 – Partial Floor Plans – Power: (Reissued)

1. Refer to revised sheet for revisions and additional information.

Drawing E4.1 – Partial Floor Plans – Systems: (Reissued)

1. Refer to revised sheet for revisions and additional information.

Drawing E6.1 – Schedules - Electrical: (Reissued)

1. Refer to revised sheet for revisions and additional information.

END OF MECHANICAL/ELECTRICAL ADDENDUM THREE

23016.10 - Wagner Pharmacy 23 00 00 - 1 TABLE OF CONTENTS

USP Compliance

Division ........ Section Title ................................................................................................................Pages

DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)

230010 ......... GENERAL PROVISIONS

230130 ......... HVAC AIR-DISTRIBUTION SYSTEM CLEANING

230500 ......... COMMON WORK RESULTS FOR HVAC

230513 ......... COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT

230523 ......... GENERAL-DUTY VALVES FOR HVAC PIPING

230529 ......... HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

230548 ......... VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT

230553 ......... IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT

230593 ......... TESTING, ADJUSTING, AND BALANCING FOR HVAC

230700 ......... HVAC INSULATION

230800 ......... COMMISSIONING OF HVAC

230900 ......... INSTRUMENTATION AND CONTROL FOR HVAC

230993 ......... SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

232113 ......... HYDRONIC PIPING

233113 ......... METAL DUCTS

233300 ......... AIR DUCT ACCESSORIES

233423 ......... HVAC POWER VENTILATORS

233600 ......... AIR TERMINAL UNITS

233713 ......... DIFFUSERS, REGISTERS, AND GRILLES

23016.10 - Wagner Pharmacy 23 09 00 - 1 INSTRUMENTATION AND CONTROL USP Compliance FOR HVAC

SECTION 23 09 00

INSTRUMENTATION AND CONTROL FOR HVAC

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including Divisions 00 and 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes BAS equipment for the monitoring and control of the new VAVs and Exhaust Fan.

B. The scope of work includes the upgrade of the existing Johnson Control system graphics that includes all areas of the facility.

C. The system shall be Johnson Controls Metasys User Interface. No exceptions or substitutions allowed. Approved Contractors are:

1. Johnson Controls of Sioux Falls, SD.

D. The Contractor shall provide all unit controllers, sensors, valves, actuators and wiring necessary to perform the sequence of operations for the systems described herein.

E. Contractor shall provide all necessary wiring to the head end and workstation as related to the points list.

F. Field devices shall be the latest version of Delta Controls consistent with existing similar field devices.

G. All setpoints and reset schedules shall be adjustable.

H. Submit examples of all graphics screens for IHS approval.

1.3 GENERAL REQUIREMENTS

A. All setpoints and reset schedules shall be adjustable.

B. Provide low voltage wiring, power wiring, installation, and termination of all remote panels, sensors, and control devices furnished as specified in mechanical Division 23 Sections for field installation. Provide labor and materials for complete and operating control systems.

C. Provide an ALARM indication in the event that a fan and/or pump output command does not match status.

23016.10 - Wagner Pharmacy 23 09 00 - 2 INSTRUMENTATION AND CONTROL

D. Provide an ALARM indication in the event that the temperature in any space falls below 40F.

E. Update graphical interface generation. Coordinate graphical design with Owner.

F. Provide additional field hardware points and devices as necessary to accomplish the sequences of operation. Control Contractor is responsible for field verifying and providing the required points needed to accomplish the sequences of operation whether all points were specified or not.

G. Control Contractor is responsible for contacting equipment manufacturers for any field verification necessary to determine details of control connections required to the equipment.

H. Provide 8 hours of on-site training for facility personnel on the use of the new interface.

1.4 DEFINITIONS

A. ASC: Adjustable Speed Controller (Variable frequency drive or VFD).

B. BAS: Building Automation System.

C. CFM: Cubic Feet per Minute.

D. DDC: Direct digital control.

E. DP: Differential Pressure.

F. DPS: Differential Pressure Sensor.

G. MFR: Manufacturer.

H. OA: Outdoor Air.

I. TAB: Test and Balance

J. TCC: Temperature Control Contractor.

K. VFD: Variable Frequency Drive

PART 2 - PRODUCTS

2.1 BUILDING AUTOMATION SYSTEM

A. This Section includes BAS equipment for the monitoring and control of the new VAVs and Exhaust Fan.

B. The scope of work includes the upgrade of the existing Johnson Control system graphics that includes all areas of the facility.

C. The system shall be Johnson Controls Metasys User Interface. No exceptions or substitutions allowed. Approved Contractors are:

23016.10 - Wagner Pharmacy 23 09 00 - 3 INSTRUMENTATION AND CONTROL

1. Johnson Controls of Sioux Falls, SD.

D. The Contractor shall provide all unit controllers, sensors, valves, actuators and wiring necessary to perform the sequence of operations for the systems described herein.

E. Contractor shall provide all necessary wiring to the head end and workstation as related to the points list.

F. Field devices shall be latest version of Delta Controls consistent with existing similar field devices.

G. All setpoints and reset schedules shall be adjustable.

H. Submit examples of all graphics screens for IHS approval.

2.2 UNITARY CONTROLLERS

A. Unitized, capable of stand-alone operation with sufficient memory to support its operating system, database, and programming requirements, and with sufficient I/O capacity for the application.

1. Configuration: Local keypad and display; diagnostic LEDs for power, communication, and processor; wiring termination to terminal strip or card connected with ribbon cable;

memory with bios; and 72-hour battery backup.

2. Operating System: Manage I/O communication to allow distributed controllers to share real and virtual object information and allow central monitoring and alarms. Perform scheduling with real-time clock. Perform automatic system diagnostics; monitor system and report failures.

3. ASHRAE 135 Compliance: Communicate using read (execute and initiate) and write (execute and initiate) property services defined in ASHRAE 135. Reside on network using MS/TP datalink/physical layer protocol and have service communication port for connection to diagnostic terminal unit.

4. Enclosure: Dustproof rated for operation at 32 to 120 deg F.

2.3 ROOM PRESSURE MONITOR AND CONTROLLER

A. Air-Pressure Differential Indicating Transmitter, Switch, and Controller:

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:

a. Critical Room Control.

b. TSI Incorporated.

c. Setra Systems, Inc

2. General Description of Requirements:

a. The room pressure monitor shall be capable of monitoring the differential pressure between a minimum of three individual spaces (compounding room, anteroom, pharmacy relationships) at all specified locations on the drawings. Each monitor shall have an internal differential pressure sensor with the ability to send an analog

23016.10 - Wagner Pharmacy 23 09 00 - 4 INSTRUMENTATION AND CONTROL output of 4 to 20 mA, 0 to 5 VDC, or 0 to 10 VDC to a system controller, as well as the option to bring in a secondary differential pressure sensor through an analog input on the device. The device shall have a display resolution of 0.0001” WC.

b. Each monitor shall have a 7” dimmable, full color touch-screen display with a minimum 480 x 272 resolution. The touch screen shall display the current differential pressure, the room status (green – ok, red – in alarm, yellow - warning) as well integral room condition banner” in one device.

c. Monitors shall utilize a direct pressure sensing device for differential pressure measurement. The monitor shall have an internal pressure sensor as well as the capability to use an external (remote) pressure sensor input. Each monitor shall be provided with a NIST traceable calibration certificate for the internal differential pressure transducer.

d. Each monitor shall have the ability to communicate through the BACnet protocol as installed or have the ability to be field upgradable to BACnet without being sent back to the manufacturer.

e. Field configurable for pressure, velocity, and volumetric flow applications through user interface.

f. Select instrument range based on application. Range shall be approximately 2 times set point.

g. The display shall have customizable text for “Room ID” and “Room Condition” panels to allow for unique site nomenclature.

h. Each Monitor shall have two levels of password protection; user and supervisory.

Room type and alarm set points shall only be changed using the supervisory security level. Each monitor shall have 1 touch room status to “Occupied” or “Unoccupied” under the user security level. Key switches are not acceptable.

3. Performance:

a. Accuracy RSS = +/- 0.5%

b. Non-Linearity (BFSL) = +/- 0.49%

c. Hysteresis = +/- 0.05%

d. Stability: Within 1 percent per year.

e. Response Time: 250 ms.

f. Overpressure: 5 psig for instrument ranges less than 50 in wg and 9 psig for 100

in. wg range.

g. Temperature Limits: 32 to 140 deg F.

h. Thermal Effects: 0.020 percent per degree F.

i. Warm-up Period: One hour.

4. Controller Programming through Menu Keys to Access Five Menus:

a. Security level.

b. Pressure, velocity, or flow application.

c. Engineering units.

d. K-factor for use with flow application.

e. Set-point control only; set-point and alarm operation; and alarm operation as high, low, or high/low with manual or automatic reset and delay.

f. View high and low readings.

g. Digital dampening for smoothing erratic applications.

h. Scaling of analog output to fit range and field calibration.

i. Ability to change deadband and timings to reduce nuisance alarms.

5. Display:

23016.10 - Wagner Pharmacy 23 09 00 - 5 INSTRUMENTATION AND CONTROL

a. Digital display with backlight, with 0.4-inch-high alphanumeric characters.

b. Four indicators; two for set point and two for alarm status.

c. The touch screen shall display the current differential pressure, the room status

(green – ok, red – in alarm, yellow - warning) as well integral “Room Condition Banner” in one device.

6. Operator Interface:

a. Set-point adjustment through keypad on face of instrument.

b. Zero and span adjustments accessible through menu.

c. Programming through keypad.

7. Analog Output Signal:

a. Two-wire, 4- to 20-mA dc current source.

b. Signal capable of operating into a 900-ohm load.

8. Digital Output Signal:

a. Two SPDT relays.

b. Each rated for one amp at 30-V ac or dc.

9. Construction:

a. Die cast-aluminum casing and bezel.

b. Threaded, NPS 1/8 connections on side and back.

c. Vertical plane mounting.

d. NEMA 250, Type 1.

e. Nominal 4-inch-diameter face.

f. Mounting Bracket: Appropriate for installation (flush or wall mounted. Refer to architectural set).

2.4 ELECTRONIC SENSORS

A. Description: Vibration and corrosion resistant; for wall, immersion, or duct mounting as required.

B. Temperature Sensors and Transmitters:

1. Temperature Sensors for DDC temperature sensing shall have an accuracy of +/- 0.36 degrees F @ 70 degrees F or better.

a. Provide sensors with a range of –30 to 220 F or wider to prevent unreliable temperature readings and the control problems that result when the temperature exceeds the range of the sensor. During commissioning, any sensor that has an error of more than 3 deg F must be replaced by the control contractor, rather than be calibrated.

2. Pipe / tank temperature sensing.

a. Furnish well-mounted temperature sensors complete with a stainless steel or brass well for installation by the piping contractor. Wells shall be filled with thermal conductive grease before installation of temperature sensor.

23016.10 - Wagner Pharmacy 23 09 00 - 6 INSTRUMENTATION AND CONTROL

b. Control Contractor to coordinate with the piping contractor for proper installation and placement of wells to ensure wells are installed per manufacturer recommendations and that the well is installed directly in the water flow of the pipe.

c. Hot water supply and return temperature monitoring, RTD temperature sensors must be used.

3. Mixed air and discharge air duct temperature sensing.

a. Provide a continuous averaging sensor that averages temperatures over the entire length and have an element length of a 10 foot or longer.

b. Averaging (10 feet or longer) sensors are required for all mixed and discharge air sensing applications.

c. If there is not access available to install the averaging duct sensor, the contractor will wind the element around a piece of conduit or rigid copper tubing and drill a hole in the bottom of the duct and install the sensor to traverse the duct diagonally.

4. A duct probe type sensor shall be used for measuring return air temperature.

5. For outside air temperature sensing.

a. Provide an outside air sensor with weatherproof shield to protect sensing elements. Sensor shall be located so that it accurately senses the outside air temperature and is unaffected by the sun.

b. The conduit for the outside air sensor shall be caulked with sealant to prevent building air from infiltrating to the outside air temperature sensor.

6. Room Sensors: Refer to the hydronics drawings for locations and types:

a. Staff spaces: Lockable cover, LED display, slide switch and override button.

b. Public spaces: Flat-plate sensors with stainless steel or bronze cover.

7. Encapsulated Thermistor and RTD Sensor:

a. Manufactures:

1) Kele Model ST-R*R

b. Applications – Embed in concrete at the following:

1) Indoor radiant concrete slab.

C. Room sensor accessories include the following:

1. Insulating Bases: For sensors located on exterior walls.

2. Adjusting Key: As required for calibration and cover screws.

D. Humidity Sensors: Thin film polymer capacitive design.

1. Manufacturers:

a. Vaisala – HMW40/50 Series.

b. Honeywell

2. Accuracy: 3 percent full range with linear output.

3. Room Sensor Range: 0 to 90 percent relative humidity.

23016.10 - Wagner Pharmacy 23 09 00 - 7 INSTRUMENTATION AND CONTROL

4. Room Sensor Cover Construction: Manufacturer's standard locking covers.

E. Pressure Transmitters/Transducers:

1. Manufacturers:

a. Setra

b. Modus

c. Veris Industries.

d. Dwyer

2. Static-Pressure Transmitter: Nondirectional sensor with suitable range for expected input, and temperature compensated.

a. Accuracy: 2 percent of full scale with repeatability of 0.5 percent.

b. Output: 4 to 20 mA or 0-10vdc.

c. Building Static-Pressure Range: bi-directional, -0.25 to 0.25 inch wg.

1) When referencing “outside air”, install surge dampeners, model SD-030, manufactured by Modus.

d. Duct Static-Pressure Range: 0 to 5 inch wg.

1) For low side sensing tube runs greater than 100 feet use 3/8” tubing for duct static sensing.

2) Provide tees with plugs in the sensing lines next to the transducer for calibration purposes

3. Water Pressure Transducers: Stainless-steel diaphragm construction, suitable for service; minimum 150-psig operating pressure; linear output 4 to 20 mA or 0-10vdc.

a. The sensor shall be rated for full system pressure without damage

4. Water Differential-Pressure Transducers: Stainless-steel diaphragm construction, suitable for service; minimum 150-psig operating pressure and tested to 300-psig; linear output 4 to 20 mA or 0-10vdc.

a. The sensor MUST be provided with a three valve manifold and piping to allow the sensor to be isolated from the system for calibration an service.

5. Differential-Pressure Switch (Air or Water): Snap acting, with pilot-duty rating and with suitable scale range and differential.

a. The sensor shall be rated for full system pressure without damage

6. Pressure Transmitters: Direct acting for gas, liquid, or steam service; range suitable for system; linear output 4 to 20 mA or 0-10vdc.

F. Water Sensor/Switch

1. Manufacturers:

a. Kele, Model LD1-24

23016.10 - Wagner Pharmacy 23 09 00 - 8 INSTRUMENTATION AND CONTROL

2. Electronic control relay for detecting a rising water level.

3. All components shall be safely encapsulated against moisture ingress.

4. Power supply: 24 VAC

5. Power input: 1W

2.5 STATUS SENSORS

A. Electronic Valve/Damper Position Indicator: Visual scale indicating percent of travel and 2 to 10vdc, feedback signal.

B. Current Relays

1. Manufacturers:

a. Veris Industries

b. Nielsen Kuljian

2. Self-powered, solid-state, selected to match current and system output requirements.

3. Current relays shall have adjustable switching set point and status LED indicator.

4. Current relays should be used to sense status of fans / pumps.

5. Provide current relays with a “split core” for easy installation and service, solid core current relays are not allowed.

2.6 RELAYS AND CONTACTORS

A. Manufacturers

1. Functional Devices

2. Idec

3. Omron

B. Relays:

1. All Energy Management System relays will have a LED status indicator. Provide relays or contactors with appropriate current ratings and number of poles based on the required application. If interfacing to existing pumps and fans, the control contractor shall verify and perform any and all modifications necessary so that the EMS can start/stop the fans or pumps (i.e. momentary pushbuttons, no magnetic starter, no hand-off-auto switch, etc.).

2.7 ELECTRONIC DAMPER ACTUATORS

A. Manufacturers:

1. Belimo Aircontrols (USA), Inc.

2. Control system manufacturer as listed in Paragraph 2.2.

B. Dampers: Size for running torque calculated as follows:

1. Parallel-Blade Damper with Edge Seals: 7 inch-lb/sq. ft. of damper.

2. Opposed-Blade Damper with Edge Seals: 5 inch-lb/sq. ft. of damper.

3. Parallel-Blade Damper without Edge Seals: 4 inch-lb/sq. ft of damper.

4. Opposed-Blade Damper without Edge Seals: 3 inch-lb/sq. ft. of damper.

23016.10 - Wagner Pharmacy 23 09 00 - 9 INSTRUMENTATION AND CONTROL

5. Dampers with 2- to 3-Inch wg of Pressure Drop or Face Velocities of 1000 to 2500 fpm:

Increase running torque by 1.5.

6. Dampers with 3- to 4-Inch wg of Pressure Drop or Face Velocities of 2500 to 3000 fpm:

Increase running torque by 2.0.

C. Electronic actuators, less than 600 in-lb. of rated torque, shall have ISO 9001 quality certification and be cULus listed under standard 60730-1 or UL listed under standard 873, CSA C22.2 No. 24 and have CE certification.

D. Electronic actuators used on dampers shall be designed to directly couple and mount to a stem, shaft or ISO style-mounting pad. Actuator mounting clamps shall be a V-bolt with a toothed V-clamp creating a cold weld, positive grip effect. Single point, bolt, or single screw actuator type fastening techniques or direct-coupled actuators requiring field assembly of the universal clamp is not acceptable.

E. Actuators shall be fully modulating/proportional, pulse width, floating/tri-state, or two position as required and be factory or field selectable. Actuators shall have visual position indicators and shall operate in sequence with other devices if required.

F. Optional auxiliary switches shall be available.

G. Actuators shall have an operating range of –22° to 122°F.

H. Proportional actuators shall accept a 0-10 VDC or 0-20 mA input signal and provide a 2-10 VDC or 4-20 mA (with a 500 W load resistor) operating range.

I. Actuators shall be capable of operating on 24, 120 or 230VAC, or 24VDC and Class 2 wiring as dictated by the application. Power consumption shall not exceed 10 VA for AC, including 120VAC actuators, and 8 watts per actuator for DC applications.

J. NEMA 2 rated actuators shall be provided with a three foot (minimum), pre-wired, electrical cable. Actuators requiring removal of the actuator cover for access to wiring terminals, exposing electronic, printed circuit boards to damage, are unacceptable.

K. Actuators shall have electronic overload protection or digital rotation sensing circuitry to prevent actuator damage throughout the entire rotation. End switches to deactivate the actuator at the end rotation or magnetic clutches are not acceptable.

L. For power-failure/safety applications, an internal mechanical spring return mechanism shall be built into the actuator housing. Spring return actuators shall be capable of CW or CCW mounting orientation. Spring return models > 60 in-lbs. and non-spring return models > 90 in-lbs. will be capable of mounting on shafts up to 1.05"in diameter. Spring return actuators with more than 60 in-lb. of torque shall have a metal, manual override crank.

M. Actuators using "on-board" chemical storage systems, capacitors, or other "on-board" non-mechanical forms of fail-safe operation are unacceptable.

N. Upon loss of control signal, a proportional actuator shall fail open or closed based on the minimum control signal. Upon loss of power, a non-spring return actuator shall maintain the last position.

O. Actuators shall be capable of being mechanically and electrically paralleled to increase torque if required. Valves and dampers requiring greater torque or higher close off may be assembled with multiple low torque actuators.

23016.10 - Wagner Pharmacy 23 09 00 - 10 INSTRUMENTATION AND CONTROL

P. Dual mounted actuators using additional anti-rotation strap mechanical linkages, or special factory wiring to function are not acceptable. Actuators in a tandem pair must be "off the shelf," standard actuators ready for field wiring.

Q. Damper and valve actuators will not produce more than 62 dB (A) when furnished with a mechanical fail-safe spring. Non-spring return actuators shall conform to a maximum noise rating of 45 dB(A) with power on or in the running or driving mode.

R. Proportional actuators shall be fully programmable. Control input, position feedback and running time shall be factory or field programmable. Diagnostic feedback shall provide indications of hunting or oscillation, mechanical overload, mechanical travel and mechanical load limit. The actuators shall also provide actuator service data, at minimum, number of hours powered and number of hours in motion.

S. Proportional actuators shall be capable of digital communication, as built.

2.8 ELECTRONIC VALVE ACTUATORS

A. Manufacturers:

1. Belimo Aircontrols (USA), Inc.

2. Control system mfg.

B. Electronic actuators, less than 600 in-lb. of rated torque, shall have ISO 9001 quality certification and be cULus listed under standard 60730-1 or UL listed under standard 873, CSA C22.2 No. 24 and have CE certification.

C. Electronic actuators used on valves shall be designed to directly couple and mount to a stem, shaft or ISO style-mounting pad.

D. Actuators shall be fully modulating/proportional, floating/tri-state, or two position as required and be factory or field selectable.

E. Optional auxiliary switches shall be available.

F. Actuators shall have an operating range of –22° to 122°F.

G. Proportional actuators shall accept a 0-10 VDC or 0-20 mA input signal and provide a 2-10 VDC or 4-20 mA (with a load resistor) operating range.

H. Actuators shall be capable of operating on 24VAC, 120VAC or 230VAC, or 24VDC and Class 2 wiring as dictated by the application. Power consumption shall not exceed 10 VA for AC, including 120VAC actuators, and 8 watts per actuator for DC applications.

I. NEMA 2 rated actuators shall be provided with either a covered terminal strip, or a three, six, or ten foot pre-wired, electrical cable.

J. For power-failure/safety applications, an internal mechanical spring return mechanism shall be built into the actuator housing.