HVAC
ATTACHMENT J-1502000-05
HVAC & REFRIGERATION INVENTORY
| HVAC and Refrigeration Systems commence at the utility isolation point of connection and terminate at the conditioned air point of delivery. The major components of each HVAC and Refrigeration System are provided below. | ||||||||||||
| Maximo Number | Bldg # | Zone/ Floor | Room | |||||||||
| # | Equipment Type | Equipment Name | Description | Quantity | Manufacturer | Model | Serial # | Install Date | ||||
| ORL-1-AHC-01 | 1 | Roof | PH#1 | Air Handling Unit | AHU 1 | 129.5 Ton, 75 HP | 1 | TEMPTROL | WFDH93 | 84063 | 1999 | |
| ORL-1-AHC-20 | 1 | 1C | 1078 | Air Handling Unit | - | 2 Ton, Wall- mounted AHU | 1 | Carrier | 40QNC01824-3 | 1106Y42569 | 2005 | |
| ORL-1-AHC-22 | 1 | 1C | 1134 | Air Handling Unit | - | 18,000 BTU wall- | ||||||
| mounted AHU | 1 | Carrier | 40QNB018 | 2800Y42021 | 2005 | |||||||
| ORL-1-AHC-26 | 1 | Roof | PH#2 | Air Handling Unit | AHU 2 | 150.2 Ton, 60 HP | 1 | TEMPTROL | IFT-DH82 | U1011527-001-00 | 1999 | |
| ORL-1-AHR-01 | 1 | Roof | PH#3 | Air Handling Unit | AHU 3 | 128.5 Ton, 50 HP | 1 | TEMPTROL | IFT-DH74 | U101527-002-00 | 1999 | |
| ORL-1-AHR-02 | 1 | Roof | PH#4 | Air Handling Unit | AHU 4 | 57.5 Ton, 25 HP | 1 | TEMPTROL | IFT-DH47 | U101960-001-00 | 1999 | |
| ORL-1-AHR-03 | 1 | Roof | PH#4 | Air Handling Unit | AHU 5 | 90.8 Ton, 40 HP | 1 | TEMPTROL | IFT-DH54 | U101960-002-00 | 1999 | |
| ORL-1-AHR-04 | 1 | Roof | PH#4 | Air Handling Unit | AHU 6 | 70.3 Ton, 25 HP | 1 | TEMPTROL | IFT-DH33 | U101960-003-00 | 1999 | |
| ORL-1-AHU-19 | 1 | 1C | 1045 | Air Handling Unit | AHU 25 | 5.0 Ton, 1.5 HP; supplies Elevator | ||||||
| #1/#2 equip room | 1 | Carrier | 42BH-4-A | 1988 | ||||||||
| ORL-1-AHU-20 | 1 | 1C | 1099 | Air Handling Unit | AHU 26 | 5.0 Ton, 1.5 HP; supplies Elevator |
#3 equip room
| (Room 1097) | 1 | Carrier | 42BH-4-A | 1988 | ||||||||
| ORL-1-CCU-01 | 1 | 1C | 1089 | Air Handling Unit | AHU 9 | 14.5 Ton | 1 | Data Aire | DACU-1534 | 20063863-E | 2006 | |
| ORL-1-CCU-02 | 1 | 1C | 1089 | Air Handling Unit | AHU 10 | 14.5 Ton | 1 | Data Aire | DACU-1534 | 20063864-E | 2006 | |
| ORL-1-CCU-03 | 1 | 1C | 1091 | Air Handling Unit | AHU 24A | 7.2 Ton | 1 | Data Aire | DACU-9034 | 20063865-E | 2006 | |
| ORL-1-CCU-04 | 1 | 1C | 1093 | Air Handling Unit | AHU 14 | 19.3 Ton | 1 | Data Aire | DACU-2234 | 20063867-E | 2006 | |
| ORL-1-CCU-05 | 1 | 1C | 1093 | Air Handling Unit | AHU 15 | 19.3 Ton | 1 | Data Aire | DACU-2234 | 20063866-E | 2006 | |
| ORL-1-CCU-06 | 1 | 1C | 1093 | Air Handling Unit | AHU 16 | 19.3 Ton | 1 | Data Aire | DACU-2234 | 20063868-E | 2006 | |
| ORL-1-CCU-07 | 1 | 1C | 1095 | Air Handling Unit | AHU 19 | 5.6 Ton | 1 | Data Aire | DACU-0734 | 20063870-E | 2006 | |
| ORL-1-CCU-08 | 1 | 1C | 1095 | Air Handling Unit | AHU 20 | 5.6 Ton | 1 | Data Aire | DACU-0734 | 20063869-E | 2006 | |
| ORL-1-CCU-09 | 1 | 1C | 1072B | Air Handling Unit | AHU 31 | 3 Ton | 1 | Data Aire | DAPC0334 | 20102808A | 2010 | |
| ORL-1-CCU-10 | 1 | 1C | 1081A | Air Handling Unit | AHU xx | 6.4 Ton | 1 | Data Aire | DACU-0734 | 20063862-E | 2006 | |
| ORL-1-CCU-11 | 1 | 2D | 2151 | Air Handling Unit | AHU xx | 4.0 Ton, 1.5 HP | 1 | Liebert | MME040C | - | 2011 | |
| ORL-1-CCU-12 | 1 | 3B | 3025 | Air Handling Unit | AHU 25 | 3.6 Ton | 1 | Data Aire | DTCU-0534 | 20063873-E | 2006 | |
| ORL-1-CCU-13 | 1 | 3B | 3024A | Air Handling Unit | AHU 21 | 4 Ton | 1 | Data Aire | DTCU-0534 | 20063872-E | 2006 | |
| ORL-1-CCU-14 | 1 | 3B | 3024A | Air Handling Unit | AHU 22 | 4 Ton | 1 | Data Aire | DTCU-0534 | 20063871-E | 2006 | |
| ORL-1-CCU-15 | 1 | 3C | 3027 | Air Handling Unit | AHU 30 | 5.6 Ton | 1 | Data Aire | DACU-0734 | 20063873-E | 2006 | |
| ORL-1-CCU-16 | 1 | 2B | SAPF Rack Room | Air Handling Unit | ERROR:#VALUE! | 10 Ton CRAC UNIT | 1 | Stulz Air Technology | COS-042-C-U-EC | |||
| ORL-1-CCU-17 | 1 | 1090 | Air Handling Unit | CRU1 | CRAC UNIT 30.25 TON | 1 | Liebert | DH3636-AAES | 436689-001 | |||
| ORL-1-CCU-18 | 1 | 1090 | Air Handling Unit | CRU2 | CRAC UNIT 30.25 TON | 1 | Liebert | DH3636-AAES | 436689-002 | |||
| ORL-1-CCU-19 | 1 | 1090 | Air Handling Unit | CRU3 | CRAC UNIT 30.25 TON | 1 | Liebert | DH3636-AAES | 436689-003 | |||
| ORL-1-CCU-20 | 1 | 2033 | Air Handling Unit | CRAC-1 | CRAC UNIT 30.25 TON | 1 | Stulz Air Technology | |||||
| ORL-1-CCU-20 | 1 | 2033 | Air Handling Unit | CRAC-1 | CRAC UNIT 30.25 TON | 1 | Stulz Air Technology | |||||
| ORL-1-CDX-01 | 1 | - | - | Condensing Unit | 0 | Room 1078 |
ductless mini-split system; unit located behind building entry sign; 24,000 BTU; Fed from 1ELK CKT
| 19/21 | 1 | Carrier | 38HDF024-301 | 0706X62675 | 2005 | ||
| ORL-1-CDX-02 | 1 | - | - | Condensing Unit | - | Room 1134 |
ductless mini-split system; unit located behind building entry sign; 18,000 BTU; Fed from 1ELK CKT
| 22/24 | 1 | Carrier | 38HDC01834 | 2200X91126 | 2005 | |||||||
| ORL-1-CDX-03 | 1 | 1D | Loading Dock enclosure | Dry Cooler | DC2 | Dry Cooler 460V 3 Phase 4 Fans .75 hp FLA 1.7 (CRAC OUTSIDE UNIT) | 1 | Liebert | DDNT466A | N22HT2A024 | 2022 | |
| ORL-1-CDX-04 | 1 | 1D | Loading Dock enclosure | Dry Cooler | DC1 | Dry Cooler 460V 3 Phase 4 Fans .75 hp FLA 1.7 (CRAC OUTSIDE UNIT) | 1 | Liebert | DDNT466A | N22HT2A025 | 2022 | |
| ORL-1-CDX-05 | 1 | 1D | Loading Dock enclosure | Dry Cooler | DC3 | Dry Cooler 460V 3 Phase 4 Fans .75 hp FLA 1.7 (CRAC OUTSIDE UNIT) | 1 | Liebert | DDNT466A | N22HT2A026 | 2022 | |
| ORL-1-CDX-06 | 1 | SAPF Rack Room | Dry Cooler | 10 ton Cooler Split unit (OUTSIDE UNIT CRAC) | 1 | Stulz Air Technology | SCS-036-SEC | |||||
| ORL-1-CID-01 | 1 | 1090 | HVAC Changeover EQ | CONTROL SYSTEM | 1 | Liebert | AC4 | 072370206666C40 | ||||
| ORL-1-CPS-01 | 1 | 1C | 1078 | Condensate Pump | - | - | 1 | NXTGEN Little Giant | VCMX-204LS | 10G1739598 | 2013 | |
| ORL-1-DDC-01 | 1 | - | - | DDC Controls, VAV Box | - | - | LOT | Automated Logic Controls | T-340V | 1998 | ||
| ORL-1-DDC-02 | 1 | 2D | 2121 | DDC Controls, Main Nodes | - | Located in Room 2121 | 1 | Automated Logic Controls | GCM2 | 1998 | ||
| ORL-1-DDC-03 | 1 | Roof | PH#1 | DDC Controls, AHU | AHU 1 | - | 1 | Automated Logic Controls | G410PX880 | - | 1998 | |
| ORL-1-DDC-04 | 1 | Roof | PH#2 | DDC Controls, AHU | AHU 2 | - | 1 | Automated Logic Controls | G410PX880 | - | 1998 | |
| ORL-1-DDC-05 | 1 | Roof | PH#3 | DDC Controls, AHU | AHU 3 | - | 1 | Automated Logic Controls | G410PX880 | - | 1998 | |
| ORL‐1‐DDC‐06 | 1 | Roof | PH#4 | DDC Controls, TERMINAL UNITS | AHU 4 | - | 1 | Automated Logic Controls | G410PX880 | - | 1998 | |
| ORL-1-DDC-07 | 1 | Roof | PH#4 | DDC Controls, TERMINAL UNITS | AHU 5 | - | 1 | Automated Logic Controls | G410PX880 | - | 1998 | |
| ORL-1-DDC-08 | 1 | Roof | PH#4 | DDC Controls, TERMINAL UNITS | AHU 6 | - | 1 | Automated Logic Controls | G410PX880 | - | 1998 | |
| ORL-1-FCD-01 | 1 | Roof | PH #1 | Fan Coil Unit | FCU 1 | 28.7 MBH, 3/4 HP | 1 | TEMPTROL | FC-182 | 84067 | 1999 | |
| ORL-1-FCD-02 | 1 | Roof | PH #2 | Fan Coil Unit | FCU 2 | 2 Ton, 1/2 HP | 1 | TEMPTROL | FC-DH182 | U101527-004-00 | 1999 | |
| ORL-1-FCD-03 | 1 | Roof | PH #3 | Fan Coil Unit | FCU 3 | 2 Ton, 1/2 HP | 1 | TEMPTROL | FC-DH182 | U101527-005-00 | 1999 | |
| ORL-1-FCD-04 | 1 | Roof | PH #4 | Fan Coil Unit | FCU 4 | 2 Ton, 1/2 HP | 1 | TEMPTROL | FC-DH182 | U101960-004-00 | 1999 | |
| ORL-1-FCD-05 | 1 | Roof | PH #5 | Fan Coil Unit | FCU 5 | 2 Ton, 1/2 HP | 1 | CARRIER | 42BH-4-A | 1999 | ||
| ORL-1-OIE-01 | 1 | 1C | 1083 | Ice Machine | - | 30" Air Cooled Half Size Cube Ice Machine - 115V, 1 Phase, 550 lb. | 1 | Manitowoc | IYT0500A | unavailable | 2022 | |
| ORL-1-STF-01 | 1 | Diesel Tank EQ | Genarator fuel tank | 1 | ||||||||
| ORL-1-STF-02 | 1 | Diesel Tank EQ | Genarator fuel tank | |||||||||
| ORL-1-VAF-01 | 1 | - | - | Re-heat Controller, VAV | - | - | LOT | Automated Logic Controls | T-540V | 1998 | ||
| ORL-1-VAT-001 | 1 | PARENT RECORD FOR AHU 1 FOR 68 VAVS PM AND DCR | 68 | 1988 | ||||||||
| ORL-1-VAT-002 | 1 | PARENT RECORD FOR AHU 2 FOR 68 VAVS PM AND DCR | 68 | 1988 | ||||||||
| ORL-1-VAT-003 | 1 | PARENT RECORD FOR AHU 3 FOR 47 VAVS PM AND DCR | 47 | 1988 | ||||||||
| ORL-1-VAT-004 | 1 | PARENT RECORD FOR AHU 4 FOR 20 VAVS PM AND DCR | 20 | 1988 | ||||||||
| ORL-1-VAT-005 | 1 | PARENT RECORD FOR AHU 5 FOR 25 VAVS PM AND DCR | 25 | 1988 | ||||||||
| ORL-1-VAT-006 | 1 | PARENT RECORD FOR AHU 6 FOR 27 VAVS PM AND DCR | 27 | 1988 | ||||||||
| ORL-1-VFD-01 | 1 | Roof | PH#1 | Variable Frequency Drive (VFD) | AHU 1 | 75 HP | 1 | Graham Company | VLT6000 | F12771-8-1-HY | 1999 | |
| ORL-1-VFD-02 | 1 | Roof | PH#2 | Variable Frequency Drive (VFD) | AHU 2 | 60 HP | 1 | Graham Company | VLT6000H106 | G12771-7-1-HY | 1999 | |
| ORL-1-VFD-03 | 1 | Roof | PH#3 | Variable Frequency Drive (VFD) | AHU 3 | 50 HP | 1 | Graham Company | VLT6000H77 | 16G269 | 1999 | |
| ORL-1-VFD-04 | 1 | Roof | PH#4 | Variable Frequency Drive (VFD) | AHU 4 | 40 HP | 1 | Graham Company | VLT6000 | 6G269 | 1999 | |
| ORL-1-VFD-05 | 1 | Roof | PH#4 | Variable Frequency Drive (VFD) | AHU 5 | 50 HP | 1 | Graham Company | VLT6000 | 6G270 | 1999 | |
| ORL-1-VFD-06 | 1 | Roof | PH#4 | Variable Frequency Drive (VFD) | AHU 6 | 25 HP | 1 | Graham Company | VLT6000 | G12222 | 1999 | |
| 1 | - | - | Damper Actuator, Variable Air Volume Contoller | - | - | LOT | Belimo | LM24-S | 1998 | |||
| 1 | - | - | Re-heat Actuator, VAV | - | - | LOT | Siebe | MF22203 | 1998 | |||
| 1 | - | - | Variable Air Volume Box | - | - | LOT | Enviro-tec | SSD-SA-II | 1998 | |||
| 1 | - | - | Hot Water Reheat Coil, VAV Box | - | - | LOT | Enviro-tec | SSD-WC-SA-II | 1998 | |||
| 1 | - | - | DDC Controls, TNI Card | - | - | 13 | Automated Logic Controls | TNI | 1998 | |||
| 1 | 1C | 1080 | Fan Coil Unit | - | 800 CFM nominal, |
1HP max, 1800
| RPM max | 1 | Trane | BCHC024B2A0A4G01G | T03K67540 | 2006 | |||||||
| 1 | 1C | 1178 | Air Handling Unit | - | 24,000 BTU wall- | |||||||
| mounted AHU | 1 | Carrier | 40QNB01824-3 | 1106Y42569 | 2005 | |||||||
| ORL-2-AHC-01 | 2 | T2035 | AIR HANDLING UNIT | Liebert | MEME040C | 30 | 1992 | |||||
| ORL-2-AHC-02 | 2 | Roof | PH#5 | Air Handling Unit | AHU 7 | 76 Ton, 40 HP | 1 | TEMPTROL | IFT-DH51 | U101527-003-00 | 1999 | |
| ORL-2-AHC-03 | 2 | 1E | T1032 | Air Handling Unit | AHU 27 | 5.0 Ton, 1.5 HP; supplies Elevator | ||||||
| #4 equip room (T1033) | 1 | Carrier | 42BH-4-A | - | 1988 | |||||||
| ORL-2-AHC-04 | 2 | 1E | T1057 | Air Handling Unit | AHU 23 | 18.8 Ton | 1 | Data Aire | DACD-1834 | 20063869-E | 2006 | |
| ORL-2-DDC-01 | 2 | Roof | PH#5 | DDC Controls, AHU | AHU 7 | - | 1 | Automated Logic Controls | G410PX880 | - | 1998 | |
| ORL-2-VAT-007 | 2 | PARENT RECORD FOR AHU 7 FOR 60 VAVS PM AND DCR | 60 | 1988 | ||||||||
| ORL-2-VFD-01 | 2 | Roof | PH#5 | Variable Frequency Drive (VFD) | AHU 7 | 40 HP | 1 | Graham Company | VLT6000H52 | G12771-5-1-HY | 1999 | |
| 2 | - | - | Damper Actuator, Variable Air Volume Contoller | - | - | LOT | Belimo | LM24-S | - | 1998 | ||
| 2 | - | - | Re-heat Controller, VAV | - | - | LOT | Automated Logic Controls | T-540V | - | 1998 | ||
| 2 | - | - | DDC Controls, VAV Box | - | - | LOT | Automated Logic Controls | T-340V | - | 1998 | ||
| 2 | - | - | Re-heat Actuator, VAV | - | - | LOT | Siebe | MF22203 | - | 1998 | ||
| 2 | - | - | Variable Air Volume Box | - | - | LOT | Enviro-tec | SSD-SA-II | - | 1998 | ||
| 2 | - | - | Hot Water Reheat Coil, VAV Box | - | - | LOT | Enviro-tec | SSD-WC-SA-II | - | 1998 | ||
| 2 | - | - | DDC Controls, TNI Card | - | - | LOT | Automated Logic Controls | TNI | - | 1998 | ||
| ORL-3-AHC-01 | 3 | 1 | M1004 | Fan Coil Unit | AHU xx | 115V, 1PH, 60Hz, |
1 HP, Drive 1000-
| 1417 RPM | 1 | Trane | BCVC036P1D0A3AM4G0000 001ER2ER204000000 | T09G12826 | 2005 | |||||||
| ORL-3-AHC-02 | 3 | 1 | AIR HANDLING UNIT #3 | TRANE | BCHB | 2000 | ||||||
| ORL-3-AHC-03 | 3 | Roof | - | Air Handling Unit | AHU xx | 12.5 Ton, 3600 | ||||||
| CFM Unitary Unit; Supplies M1001; | 1 | Carrier | M350HI-014G-631HE | 3799G30582 | 1999 | |||||||
| ORL-3-AHC-04 | 3 | 1 | M1001 | AIR HANDLING UNIT #2 | CARRIER | 39NC09 | 0401V00301 | 2009 | ||||
| ORL-3-AHC-05 | 3 | Roof | - | Air Handling Unit | AHU 8 | 12.5 Ton, supplies Room M1001 | 1 | Carrier | 3799G30582 | 39NC-07 | 1999 | |
| ORL-3-CCC-01 | 3 | 1 | M1000 | Refrigeration | ||||||||
| Machine, Screw- Type | RM 4 | 165 Ton, 1400 lbs HFC-134A | 1 | Carrier | 30HXC186R2-6WKA 6001456 | 4208217007 | 2013 | |||||
| ORL-3-CCC-02 | 3 | 1 | M1000 | Refrigeration | ||||||||
| Machine, Screw- Type | RM 3 | 165 Ton, 1400 lbs HFC-134A | 1 | Carrier | 30HXC186R2-6WKA 6001456 | 4208217006 | 2013 | |||||
| ORL-3-CCC-03 | 3 | 1 | CHILLER, CENTRIFUGAL, WTR COOLED | CHILLGARD RT | A-RT-D-4-1-1-3-0-0-0-D-0-0-0- 0-0-0-0 | JO8-2935181-10 | ||||||
| ORL-3-CCC-04 | 3 | 1 | M1000 | Refrigeration | ||||||||
| Machine, Centrifugal | RM 1 | Turbocor | ||||||||||
| Compressors; 134A Refigerant | 1 | Smardt | SWA096-2MG71-2A2AS | FF00101018Q227 | 2013 | |||||||
| ORL-3-CCC-05 | 3 | 1 | M1000 | Refrigeration | ||||||||
| Machine, Centrifugal | RM 2 | Turbocor | ||||||||||
| Compressors; 134A Refigerant | 1 | Smardt | SWA096-2MG71-2A2AS | FF00101018Q226 | 2013 | |||||||
| ORL-3-CPS-01 | 3 | 1 | M1000 | Pump Motor, Chilled Water | PP 7 | 595 GPM, 7.5 HP | 1 | Armstrong | ED-4380BF | - | 1988 | |
| ORL-3-CPS-02 | 3 | 1 | M1000 | Pump Motor, Hot Water | PP 17 | 190 GPM, 1.5 HP | 1 | Armstrong | S-615 | 102105M | 1988 | |
| ORL‐3‐CPS‐03 | 3 | 1 | M1000 | Pump Motor, Chilled Water | PP 10 | Vertical, In-line; 1016 GPM, 50 HP | 1 | Baldor | JMM2543T | Z0109200171 | 1988 | |
| ORL-3-CPS-04 | 3 | 1 | M1000 | Pump Motor, Chilled Water | PP 9 | Vertical, In-line; 1016 GPM, 50 HP | 1 | Baldor | JMM2543T | Z0809241751 | 1988 | |
| ORL-3-CPS-05 | 3 | 1 | M1000 | Pump Motor, Hot Water | PP 11 | 500 GPM, 5 HP | 1 | Baldor | JMM3309T | - | 1988 | |
| ORL-3-CPS-06 | 3 | 1 | M1000 | Pump Motor, Hot Water | PP 16 | 190 GPM, 1.5 HP | 1 | Armstrong | S-615 | BU5035 | 1988 | |
| ORL-3-CPS-07 | 3 | 1 | M1000 | Pump Motor, Condensing Water | PP 1 | xx GPM, 20 HP, 1800 RPM, | 1 | Marathon | GT0025 | 3812030 | 2012 | |
| ORL-3-CPS-08 | 3 | 1 | M1000 | Pump Motor, Hot Water | PP 14 | 318 GPM, 20 HP | 1 | Baldor | JMM2514T | - | 1988 | |
| ORL‐3‐CPS‐09 | 3 | 1 | M1000 | HOT WATER GENERATOR PUMP | HOT WATER GENERATOR PUMP, 190 GPM 1.5 HP, PP- | |||||||
| 24 | 1 | ARMSTRONG | S-615 | 1988 | ||||||||
| ORL‐3‐CPS‐11 | 3 | 1 | M1000 | CIRCULATING PUMP, END SUCTION | CIRCULATING PUMP, END SUCTION, 15 HP, | |||||||
| 1000 GPM | 1 | ARMSTRONG | 4030 | 2002 | ||||||||
| ORL‐3‐CPS‐12 | 3 | 1 | M1000 | CIRCULATING PUMP, END SUCTION | CIRCULATING PUMP, END SUCTION, 15 HP, | |||||||
| 1000 GPM | 1 | ARMSTRONG | 4030 | 2002 | ||||||||
| ORL‐3‐CPS‐13 | 3 | 1 | M1000 | CIRCULATING PUMP, END SUCTION | CIRCULATING PUMP, END SUCTION, 15 HP, | |||||||
| 1000 GPM | 1 | Armstrong | 4030 | 2002 | ||||||||
| ORL-3-CPS-14 | 3 | 1 | M1000 | CIRCULATING | ||||||||
| PUMP, END SUCTION | CIRCULATING | |||||||||||
| PUMP, END SUCTION, 15 HP, | 1 | ARMSTRONG | 4030 | 2002 | ||||||||
| ORL-3-CPS-15 | 3 | 1 | M1000 | Pump Motor, Condensing Water | PP 4 | xx GPM, 20 HP, 1800 RPM, | 1 | Marathon | GT0025 | 3927075 | 2012 | |
| ORL‐3‐CPS‐16 | 3 | 1 | M1000 | Pump Motor, Chilled Water | PP 6 | 595 GPM, 7.5 HP | 1 | Armstrong | ED-4380BF | - | 1988 | |
| ORL-3-CPS-17 | 3 | 1 | M1000 | Pump Motor, Chilled Water | PP 5 | 595 GPM, 7.5 HP | 1 | Armstrong | ED-4380BF | - | 1988 | |
| ORL‐3‐CPS‐18 | 3 | 1 | M1000 | CIRCULATING PUMP, END SUCTION | CIRCULATING PUMP, END SUCTION, 15 HP, | |||||||
| 1000 GPM | 1 | Armstrong | 4E 4380 BF | 2002 | ||||||||
| ORL‐3‐CPS‐22 | 3 | 1 | CT | CIRCULATING PUMP, END SUCTION | CIRCULATING PUMP, END SUCTION, 700 GPM | 1 | SF-8000-AK | 2000 | ||||
| ORL-3-CPS-23 | 3 | 1 | M1000 | Pump Motor, Hot Water | PP 19 | xx GPM, 0.5 HP | 1 | Bell & Gossett | FVH48T | 903581 | 1988 | |
| ORL-3-CPS-24 | 3 | 1 | M1000 | Pump Motor, Hot Water | PP 15 | 318 GPM, 20 HP | 1 | Baldor | JMM2514T | - | 1988 | |
| ORL-3-CPS-25 | 3 | 1 | M1000 | Pump Motor, Condensing Water | PP 3 | xx GPM, 20 HP, 1800 RPM, | 1 | Marathon | GT0025 | 3920769 | 2012 | |
| ORL‐3‐CPS‐26 | 3 | 1 | CT | CIRCULATING PUMP, END SUCTION | CIRCULATING PUMP, END SUCTION, 700 GPM | 1 | JO8-29355181 | 2000 | ||||
| ORL-3-CTG-01 | 3 | Roof | M1001 | DDC Controls, AHU | AHU 8 | - | 1 | Automated Logic Controls | G1010PX16160 | - | 1998 | |
| ORL-3-DDC-01 | 3 | 1 | M1000 | DDC Controls, | ||||||||
| Refrigeration Machine | - | - | 2 | Automated Logic Controls | G1010PX16160 | 1998 | ||||||
| ORL-3-FSU-01 | 3 | 1 | M1000 | Supply Fan | SA Fan 1 | 5220 CFM, 2 HP | 1 | Greenback | LBP-10-4 | 86101238 | 1988 | |
| ORL-3-FSU-02 | 3 | 1 | M1002 | Supply Fan | SA Fan 2 | 5220 CFM, 1.5 HP | 1 | Loren Cook Company | 120-CFS | - | 1988 | |
| ORL-3-HEP-01 | 3 | 1 | M1000 | Heat Exchanger | - | Flat Plate, Comfort |
Heating; 500 GPM
| / 750 GPM | 1 | Mueller AccuTherm | AT405HV-V-F20 | - | 2001 | |||||||
| ORL-3-HEP-02 | 3 | 1 | M1000 | Heat Exchanger | - | Flat Plate, Potable Water; 144 GPM | 1 | Mueller AccuTherm | AT-20-C-20 | - | 2001 | |
| 3 | 1 | M1000 | Air Separator | - | Hot water supply; 1250 GPM | 1 | Armstrong Vortex | VAS-8 | - | 1988 | ||
| 3 | 1 | M1000 | Air Separator | - | Chilled water supply; 2800 GPM | 1 | Armstrong Vortex | VAS-12 | - | 1988 | ||
| ORL-4-SDI-001 | 4 | PARENT FOR 7 WELCOME CTR MINI-SPLITS | 7 | Mitsubishi | 2009 | |||||||
| ORL-4-EVP-01 | 4 | 1 | 101 | Fan Coil Unit | FCU-3 | 24" x 24" | ||||||
| Resessed, Ceiling- Mounted, 4-way | 1 | Mitsubishi | PLFY-P08NCMU-E | PLFY-P08NCMU- ER4.TH | 2013 | |||||||
| ORL‐4‐EVP‐02 | 4 | 1 | 105 | Fan Coil Unit | FCU-1 | 24" x 24" | ||||||
| Resessed, Ceiling- Mounted, 4-way | 1 | Mitsubishi | PLFY-P24NBMU-E | 27A00834D | 2013 | |||||||
| ORL-4-EVP-03 | 4 | 1 | 106 | Fan Coil Unit | FCU-2 | 24" x 24" | ||||||
| Resessed, Ceiling- Mounted, 4-way | 1 | Mitsubishi | PLFY-P18NBMU-E | 27A00474D | 2013 | |||||||
| ORL-4-EVP-04 | 4 | 1 | 107 | Fan Coil Unit | FCU-4 | 24" x 24" | ||||||
| Resessed, Ceiling- Mounted, 4-way | 1 | Mitsubishi | PLFY-P15NCMU-E | PLFY-P15NCMU- ER4.TH | 2013 | |||||||
| ORL-4-EVP-05 | 4 | 1 | 108 | Fan Coil Unit | FCU-6 | 12" x 24" | ||||||
| Resessed, Ceiling- Mounted, 1-way | 1 | Mitsubishi | PLFY-P08NCMU-E | PLFY-P08NCMU- ER4.TH | 2013 | |||||||
| ORL‐4‐EVP‐06 | 4 | 1 | 111 | Fan Coil Unit | FCU-5 | 24" x 24" | ||||||
| Resessed, Ceiling- Mounted, 4-way | 1 | Mitsubishi | PLFY-P12NCMU-E | PLFY-P12NCMU- ER4.TH | 2013 | |||||||
| ORL-4-EVP-07 | 4 | 1 | 114 | Fan Coil Unit | FCU-7 | 12" x 24" | ||||||
| Resessed, Ceiling- Mounted, 1-way | 1 | Mitsubishi | PLFY-P06NCMU-E | PLFY-P06NCMU- ER4.TH | 2013 | |||||||
| ORL-4-SSC-01 | 4 | - | - | Heat Pump Unit | HPU-1 | 3 ton, pad-mounted | 1 | Mitsubishi | PUMY-PS69NHMU | 25U01442C | 2013 | |
| ORL-4-SSC-02 | 4 | - | - | Heat Pump Unit | HPU-2 | 4 ton, pad-mounted | 1 | Mitsubishi | PUMY-P48NHMU | 24U02690C | 2013 | |
| ORL-5-AHC-01 | 5 | 1 | 1 | Air Handling unit | 5 ton, ceiling mounted | 1 | Lennox | CBX32MV-060-230-06-01 | 166D06334 | 2016 |
| ORL-5-SDH-01 | 5 | 1 | 1 | Heat pump unit | 5 ton, pad mounted | 1 | Lennox | XP21-060-230-01 | 5816B13121 | 2017 | ||
| ORL-39-ACE-01 | 39 | - | - | Package Unit | - | 3.5 ton, 16 SEER, package unit, | ||||||
| Operations Bldg | 1 | Goodman Company | GPH1642H41AA | 1604331027 | 2016 | |||||||
| OKA-40-SDI-01 | 40 | 1 | - | Fan Coil Unit | - | 3/4 ton fan coil | ||||||
| unit, wall-mount, in entry room, Electronic System Bldg | 1 | Daiken Industries | FXAQ09PVJU | E001025 | 2012 | |||||||
| OKA-40-SDI-02 | 40 | 1 | - | Fan Coil Unit | - | 2 ton fan coil unit, wall-mount, in control room, Electronic System Bldg (1 of 2 units) | 1 | Daiken Industries | FXAQ24PVJU | E000521 | 2012 | |
| OKA-40-SDI-03 | 40 | 1 | - | Fan Coil Unit | - | 2 ton fan coil unit, wall-mount, in control room of Electronic System Bldg (2 of 2 units) | 1 | Daiken Industries | FXAQ24PVJU | E000509 | 2012 | |
| OKA-40-SSC-01 | 40 | - | - | Condensing Unit | - | 4 ton Condensing Unit on shore adjacent to gangway entry, Electronic System Bldg | 1 | Daiken Industries | RXYMQ48PVJU | E00225294 | 2012 | |
| OKA-44-SDI-01 | 44 | 1 | - | Fan Coil Unit | - | 3/4 ton fan coil unit, wall-mount, in secure room | 1 | Daiken Industries | FXAQ09PVJU | E001019 | 2012 | |
| OKA-44-SDI-02 | 44 | 1 | - | Fan Coil Unit | - | 2 ton fan coil unit, wall-mount, in main room | 1 | Daiken Industries | FXAQ24PVJU | E000512 | 2012 | |
| OKA-44-SDI-03 | 44 | 1 | - | Fan Coil Unit | - | 3 ton fan coil unit, ceiling-mount, in main room | 1 | Daiken Industries | FXHQ36MVJU | E001580 | 2012 | |
| OKA-44-SSC-01 | 44 | - | - | Condensing Unit | - | 6 ton Condensing Unit on east side of Bulk & Assembly Building | 1 | Daiken Industries | RXYQ72PBTJ | A000645 | 2012 | |
| ORL-101-HPR-01 | 101 | - | - | Heat Pump, Window-Style | - | Research Gate Sentry House System; unit located on roof | 1 | Trane | WCC024F100BH | 5273J812H | 2005 | |
| 103 | - | - | Heat Pump, Window-Style | - | Science Gate Sentry House System; unit located on south wall | 1 | LG | LW1213HR | - | 2013 | ||
| 104 | - | - | Heat Pump, Window-Style | - | CVIS Sentry House System; unit located on north wall (CKTs 1,3) | 1 | General Electric | - | - | 2011 | ||
| ORL-3-CTG-02 | Grounds | - | - | Cooling Tower, Ceramic | Cooling Tower 1 | 1605 GPM | 1 | Ceramic Cooling Tower Company | JOB-NO-CT-1164 | - | 2014 | |
| ORL-3-CTG-03 | Grounds | - | - | Cooling Tower, Ceramic | Cooling Tower 2 | 1605 GPM | 1 | Ceramic Cooling Tower Company | JOB-NO-CT-1164 | - | 2014 | |
| Grounds | - | - | Cooling Tower Fan Motor | Cooling Tower 1 | 50HP, 230/460V, | |||||||
| 1765 RPM | 1 | Marathon | NVJ326TTFS16574BPL | C0236895-08/22-01 | 2015 | |||||||
| Grounds | - | - | Cooling Tower Motor Gear Box | Cooling Tower 1 | Right Angle Fan Drive, 1765 RPM | 1 | Amarillo Gear Company | F110 | 324620 | 2015 | ||
| Grounds | - | - | Cooling Tower Fan Motor | Cooling Tower 2 | 50HP, 230/460V, | |||||||
| 1765 RPM | 1 | Marathon | NVJ326TTFS16574BPL | C0241904-09/02-01 | 2015 | |||||||
| Grounds | - | - | Cooling Tower Motor Gear Box | Cooling Tower 2 | Right Angle Fan Drive, 1765 RPM | 1 | Amarillo Gear Company | F110 | 324619 | 2015 | ||
| Grounds | - | - | Water Treatment System | - | Treament system | |||||||
| for all condensing water for all | 1 | Varies | - | - | 2009 | |||||||
| Grounds | - | - | - | Water Meter | Makeup Water, |
Cooling Towers 1
| & 2 | 1 | Advantage Ctr | MJR-150-100G-205 | 15119 | 2009 | ||
| Grounds | - | - | - | Water Meter | Blowdown, |
Cooling Towers 1
| & 2 | 1 | Advantage Ctr | MJR-150-100G-205 | 14510 | 2009 | |||||||
| LL1 | 1 | - | Air Handling Unit | - | ? | 1 | Trane | ? | ? | 1995 |