J-14 Pentagon Labeling Std Rev 9.pdf
PDF 1 MB Posted
- Attached to
- Roof Fall Protection Systems Services Federal contract opportunity
- Solicitation number
- HQ003426RE004
- Issued by
- DOD Washington Headquarters Service
About this file
This document is a Pentagon Equipment Labeling Standard, a comprehensive technical specification detailing standardized equipment identification and labeling protocols for mechanical, electrical, and fire protection systems within the Pentagon facility. The standard provides precise guidelines for creating unique equipment identifiers, which incorporate specific elements including unit type, floor location, ring designation, room number, and sequential numbering. The labeling methodology covers a wide range of equipment types such as air handling units, fan coil units, transformers, panelboards, exhaust fans, and fire protection valves, with each receiving a systematically constructed tag that enables precise location and identification.
The document includes an extensive abbreviation list with standardized codes for different equipment types and components, detailed instructions for numbering equipment within rooms and tenant spaces, and requirements for physical tag characteristics including size, lettering, and barcode implementation. The standard is designed to ensure consistency across all Pentagon facilities, with provisions for requesting new abbreviations through the Contracting Officer and alignment with National Institute of Building Sciences (NIBS) and American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) guidelines. Appendices provide additional reference materials like ring site grids and comprehensive equipment abbreviation lists to support implementation of the labeling system.
View the file
Other files for this federal contract opportunity
Show all 29
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Washington Headquarters Services Department of Defense
Pentagon Equipment Labeling Standard
March 4, 2021
[This page left intentionally blank.]
Pentagon Equipment Labeling Standard i
TABLE OF CONTENTS
PENTAGON EQUIPMENT LABELING STANDARD
1.1 Unit Type
1.2 Floor
1.2.1 Basement Center Courtyard
1.3 Ring
1.4 Room Number
1.5 Unit Number
1.5.1 Multiple Equipment in Fixed Equipment Rooms
1.5.2 Multiple Equipment in Tenant Space Grids
1.6 Component and Device Number
1.6.1 Bar Coding Requirements
1.7 Standard Abbreviations List
1.8 Appendix A. Ring Site Grid for Exterior Locations
Pentagon Equipment Labeling Standard 1
PENTAGON EQUIPMENT LABELING STANDARD
This revision of the Pentagon Equipment Labeling Standard includes, but is not limited to, the following changes:
Additional location abbreviations Additional equipment abbreviations Additional equipment location examples Additions to the “Allowed but not Approved” abbreviation list (Appendix B) Revised “Revision History” (Appendix C) Change in point of contact for abbreviations additions, comments or clarifications
This document represents the Pentagon Equipment Labeling Standard. The abbreviations and labeling methodology were obtained by using the National Institute of Building Sciences (NIBS) Guidelines and the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) Fundamentals abbreviations.
For abbreviations additions, comments or clarifications please contact the Building Manager at (703) 697-7351
Equipment tags and labels must incorporate the room number where the equipment is located and conform to the Pentagon Equipment Labeling Standard.
Examples:
i. Mechanical Equipment designation structure is described below, using AHU-1B313-01 as an example.
AHU-1B313-01 defines the Unit Type (Air Handling Unit) AHU-1B313-01 defines the room number were the equipment is physically located AHU-1B313-01 defines the floor location AHU-1B313-01 defines the ring location AHU-1B313-01 defines the corridor location AHU-1B313-01 defines the individual room number AHU-1B313-01 defines the Unit Number, how many individual AHU’s are located within this room
Additional components that support this piece of equipment are designated as described below, using a chilled water supply isolation valve as an example.
AHU-1B313-01-CHWS ISO VLV-01
AHU-1B313-01-CHWS ISO VLV-01 defined above AHU-1B313-01-CHWS ISO VLV-01 defines the stored energy media AHU-1B313-01-CHWS ISO VLV-01 defines the component function AHU-1B313-01-CHWS ISO VLV-01 defines the component type AHU-1B313-01-CHWS ISO VLV-01 defines the component number, how many components with the same function are installed in support of this equipment type
Pentagon Equipment Labeling Standard 2
Equipment located in stairwells designation structure is described below, using CUH- BHSTAIR87H-01 as an example.
CUH-BHSTAIR87H-01 defines the Unit Type (Cabinet Unit Heater) CUH-BHSTAIR87H-01 defines the room number where the equipment is physically located CUH-BHSTAIR87H-01 defines the floor location CUH-BHSTAIR87H-01 defines the ring location CUH-BHSTAIR87H-01 defines the stairwell number CUH-BHSTAIR87H-01 defines the Unit Number, how many individual CUH’s are located on this floor within this stairwell.
ii. Electrical Equipment designation structure is described below, using XFMRLV-1B313- 01 as an example.
XFMRLV-1B313-01 defines the Unit Type (Transformer Low Voltage) XFMRLV-1B313-01 defines the room number were the equipment is physically located XFMRLV-1B313-01 defines the floor location XFMRLV-1B313-01 defines the ring location XFMRLV-1B313-01 defines the corridor location XFMRLV-1B313-01 defines the individual room number XFMRLV-1B313-01 defines the Unit Number, how many individual XFMRLV’s are located within this room above in i.
iii. Fire Protection Equipment designation structure is described below, using VLVFCTRL-
1E620-01 as an example.
VLVFCTRL-1E620-01 defines the Unit Type (VALVE, FIRE CONTROL) VLVFCTRL-1E620-01 defines the room number were the equipment is physically located VLVFCTRL-1E620-01 defines the floor location VLVFCTRL-1E620-01 defines the ring location VLVFCTRL-1E620-01 defines the corridor location VLVFCTRL-1E620-01 defines the individual room number VLVFCTRL-1E620-01 defines the Unit Number, how many individual VLVFCTRL’s are located within this room above in i.
Equipment located in stairwells designation structure is described below, using VLVCTRL- MHSTAIR87H-01 as an example.
VLVFCTRL-MHSTAIR87H-01 defines the Unit Type (VALVE, FIRE CONTROL) VLVFCTRL-MHSTAIR87H-01 defines the stairwell were the equipment is physically located VLVFCTRL-MHSTAIR87H-01 defines the floor location VLVFCTRL-MHSTAIR87H-01 defines the ring location VLVFCTRL-MHSTAIR87H-01 defines the stairwell number VLVFCTRL-MHSTAIR87H-01 defines the Unit Number, how many individual
VLVFCTRL’s are located within this stairwell.
Pentagon Equipment Labeling Standard 3
1.1 UNIT TYPE
The standard abbreviations for unit type should be consistent in all the documentation by which the equipment is designed and managed (e.g., Drawings, Specifications, DMELs, etc.). All mechanical
(HVAC), electrical, plumbing, fire alarm, fire protection and related equipment must have a unique identifier that is consistently applied throughout the Pentagon.
Use the attached abbreviations list for identification of all equipment and components. If an abbreviation is required and does not appear on the list, the selection and use of a new abbreviation shall be coordinated and approved through the Contracting Officer at the discretion and approval of the PBMO. Requests for new abbreviations shall be based on the National Institute of Building Sciences (NIBS) abbreviation guidelines and ASHRAE Fundamental abbreviations.
1.2 FLOOR
The floor designator describes the vertical location of the component inside the building. It is generally a single alphanumeric character except as noted below.
Floors one through five: 1-5 Basement: B Mezzanine: M Roof: R Interstitial Space: I Sub-basement: SB Outside Ground Level: G Underground: U Basement Center Courtyard (CCUT): BCC Center Courtyard Café: CYC Memorial Equipment Control Center MECC Hazmat Response Facility HAZ
Additional characters may be required to denote other locations such as the steam pits or electrical vaults. Any new floor designation shall be coordinated and approved through the Contracting Officer at the discretion and approval of the PBMO.
1.2.1 Basement Center Courtyard
Equipment located in the Basement Center Courtyard, also known as the CCUT, will be labeled using the floor designator of BCC plus the corridor numbers that the piece of equipment is located between separated by a “/”. Equipment numbering will be determined by counting the corridors clockwise.
Example: A hot water supply isolation valve located in the CCUT between corridors 6 and 7 would be labeled HWS-BCC-6/7-ISO VLV-01
Equipment located in the ramps from the Apex mechanical rooms to the CCUT will be identified using the same corridor numbering scheme. However, the abbreviation BCC will be not used.
Example: A hot water supply isolation valve located on Apex ramp 5/6 would be labeled HWS-5/6-ISO VLV-01
Pentagon Equipment Labeling Standard 4
1.3 RING
The ring designator will correspond with the alphabetic ring designations “A” through “AR” as shown on the attached site grid (Appendix A).
Ring designators for other areas such as the PLC2, H&RP and the RDF will be identified using the site grid to maintain the identification scheme. Any new ring designation shall be coordinated and approved through the Contracting Officer at the discretion and approval of the PBMO.
1.4 ROOM NUMBER
Pentagon Room Numbering convention is established and maintained by SPAD (Space Policy and Acquisition Division). The room location will denote the exact location/room in which the equipment is located. That is, fixed equipment rooms such as electrical closets/vaults, communication closets, mechanical rooms, etc.
Equipment located inside tenant space (i.e. VAV, Induction Units, etc.) will be labeled using the closest room number in the associated grid block as indicated on the Pentagon standard room labeling grid system, available from the Contracting Officer.
Locations with duplicate room numbers are labeled with an additional letter directly following the room number as a distinctive identifier. (i.e. 2D648, 2D648A).
Equipment located in the corridor areas (i.e. A-Ring, E-Ring, radial corridors) will be labeled as described with the addition of the letter “Z” directly following the room number.
Equipment located in a Stairwell will be labeled as described above, but the room number will be replaced with “STAIR” and the “Stairwell Number” i.e. 5B5STAIR51 room number represents Stairwell 51 on the 5th corridor, B ring, 5th Floor.
Room numbers previously defined by corridors located in un-renovated areas or new tenant space shall be labeled using the room number in the associated grid situated directly one grid towards the outer-most ring of the Pentagon. (See space grid provided in Illustration #1.)
1.5 UNIT NUMBER
The unit numbers will be two–character numbers that will allow for ninety-nine similar items of equipment in a room, grid, and ring or floor combination. These will be numbered “01” through “99” for each type of similar equipment.
Example: 4 Air Handler Units in 1 mechanical room would have the same abbreviation – same room number – with 01 thru 04 as a unique identifier.
1.5.1 Multiple Equipment in Fixed Equipment Rooms
In the event of multiple equipment located in the same room, the following equipment labeling system shall apply:
In front-to-back equipment rooms, unit/component numbers will run from “01” to “99” based upon their location in the equipment room. “01” designates equipment closest to the front of the room (where the entrance is located). “99” designates equipment farthest from the front of the room.
Pentagon Equipment Labeling Standard 5
In left-to-right equipment rooms, unit/component numbers will run from “01” to “99” based upon their location. “01” designates equipment to the left of the entrance. “99” designates equipment to the right.
In top-to-bottom equipment rooms, unit/ component numbers will designate equipment at the bottom as “01” and equipment at the top as “99.”
1.5.2 Multiple Equipment in Tenant Space Grids
In the event multiple pieces of equipment are located in tenant space grids as indicated on the Pentagon standard room labeling grid system, the following equipment labeling system shall apply:
Front-to-back equipment in each tenant space grid will start with unit/component number “01” in front as you enter the grid from the outer-most ring and will run through “99” to designate equipment towards the inner-most ring. (See Illustration #1 for grid entrance reference point.)
Left-to-right equipment in each tenant space grid will start with unit/component number “01” at the left as you walk into the room through “99” to designate equipment to the right.
Top-to-bottom equipment in each tenant space grid will start with unit/ component number “01” at the bottom as you walk into the room through “99”to designate equipment at the top.
1.6 COMPONENT AND DEVICE NUMBER
The listing of major components will include equipment that requires maintenance on a separate schedule or equipment required for Lockout/Tag-out procedures. The identification of devices and the major component they belong to will be accomplished by abbreviating the major component and abbreviating the device that controls it (the major component).
Example: AHU-1B350-03-CHWS DRNVLV-01 is uniquely identified to control the release of stored energy (CHW) for AHU-1B350-03 as required by LOTO. All equipment/system component abbreviations will follow the PBMO standard. (e.g.
components and devices may include valves, circuit breakers, disconnect switches, motor starters, etc.).
The numbering sequence will use two alphanumeric characters in sequential order. These will be numbered “01” through “99” for each type of similar components.
The only exception to the use of “01” through “99” will be on electrical switchgear and major distribution panels where the manufacturer or designer has assigned a cubical identification e.g. 1A, 1B, 1C, 2A, 2B, etc. In this situation the components sequential number “01 through “99” is replaced with the designated cubical designation.
Example: SWGR-1A532-01-CBLVPWR-1A would be a correct tag for a low voltage circuit breaker (component) installed within SWGR-1A532-01, in cubical 1A.
1.6.1 Bar Coding Requirements
All equipment and/or device tags shall be provided with bar-coded labels following the Pentagon bar coding standards. The tag number will be printed out below the bar code in addition to the main number pointed out at the top of the tag.
Pentagon Equipment Labeling Standard 6
1.6.1.1 Tags
Rigid strap-on tags for mechanical, electrical, and life safety equipment suitable for location in an industrial environment that meets the following requirements:
Approximately 2-1/4" high by 3-3/4" wide and rectangular in shape.
Black block lettering a minimum of 1/4" in height.
Slot or hole to accommodate a 1/4" wide strap, at a minimum.
1.6.1.2 Labels
Pressure-sensitive labels for mechanical, electrical, life safety equipment, and control panels suitable for location in an industrial environment that meets the following requirements:
Approximately 3" high by 5" wide and rectangular in shape.
Black block lettering a minimum of 1/2" in height.
Provide separately or in rolls with peel-off backing.
Illustration # 1: Sample of barcoded equipment label.
1.6.1.3 Tags and Labels
Both labels and tags shall meet the following requirements:
Includes equipment number and associated bar coding.
Heat-resistant.
Waterproof.
During printing, the bar code equipment designation can be read on the printer (i.e.
AHU-1B313-01-CHWS ISO VLV-01) as a back check with the text on the label/tag.
The attached Standard Abbreviations List
Note: If an abbreviation is required and does not appear on the list, the selection and use of a new abbreviation shall be coordinated and approved through the Contracting Officer at the discretion and approval of the PBMO. Requests for new abbreviations shall be based on the National Institute of Building Sciences (NIBS) abbreviation guidelines and ASHRAE Fundamental abbreviations. If a new abbreviation is created, it shall be added to this list by
PBMO.
Pentagon Equipment Labeling Standard 7
Illustration #1: Tenant Space Grid
EQUIP
2E648Z
Grid Entrance
Point
2E653AZ
2D646-01
2D648Z
2D646-02
Pentagon Equipment Labeling Standard 8
1.7 STANDARD ABBREVIATIONS LIST
ABBREVIATION DESCRIPTION
AAV AUTOMATIC AIR VENT
AC AIR CONDITIONING UNIT, CEILING/WALL MOUNTED
ACCU AIR-COOLED CONDENSER
ACDX AIR CONDITIONING UNIT, SPLIT SYSTEM
ACOMPR AIR COMPRESSOR
ACPU AIR CONDITIONING UNIT, PACKAGE UNIT
AD AIR DRYER, REFRIGERATED OR REGENERATIVE DESICCANT TYPE
AFCLR AFTER-COOLER
AHU AIR HANDLING UNIT
AIRCUR HTR ELECTRIC HEATED AIR CURTAIN
AMB AUTOMATIC MIXING BOX
AS AIR SEPARATOR
ATS AUTOMATIC TRANSFER SWITCH
AW AIR WASHER, WET COIL SYSTEM
BALVLV BALANCING VALVE
BAT BATTERY CELL
BATT BATTERY
BC BATTERY CHARGER
BCHWR BLENDED CHILLED WATER RETURN
BCHWR ISO BAL VLV BLENDED CHILLED WATER RETURN COMBINATION ISOLATION
BALANCING VALVE
BCHWR ISO VLV BLENDED CHILLED WATER RETURN ISOLATION VALVE
BCHWS BLENDED CHILLED WATER SUPPLY
BCHWS CTRL VLV BLENDED CHILLED WATER SUPPLY CONTROL VALVE
BCHWS DRN VLV BLENDED CHILLED WATER SUPPLY DRAIN VALVE
BCHWS ISO BAL VLV BLENDED CHILLED WATER SUPPLY ISOLATION BALANCE VALVE
BCHWS ISO STRNR VLV BLENDED CHILLED WATER SUPPLY ISOLATION STRAINER VALVE
BCHWS ISO VLV BLENDED CHILLED WATER SUPPLY ISOLATION VALVE
BCHWS STRNR BLENDED CHILLED WATER SUPPLY STRAINER
BHWR VLVCHK BLENDED HOT WATER RETURN CHECK VALVE
BHWR ISO VLV BLENDED HOT WATER RETURN ISOLATION VALVE
BHWS ISO VLV BLENDED HOT WATER SUPPLY ISOLATION VALVE
BD BUS DUCT
BFP BACKFLOW PREVENTER
BLR BOILER
BLRCTRL BOILER CONTROLS
CA COMPRESSED AIR
CA CTRL VLV COMPRESSED AIR CONTROL VALVE
CA DRN VLV COMPRESSED AIR DRAIN VALVE
CA ISO VLV COMPRESSED AIR ISOLATION VALVE
CA STRNR COMPRESSED AIR STRAINER
CAV CONSTANT AIR VOLUME TERMINAL UNIT
(COLLECTIVE PROTECTION SYSTEM SUPPORT DEVICE)
Pentagon Equipment Labeling Standard 9
CBHV CIRCUIT BREAKER, HIGH VOLTAGE AIR CIRCUIT BREAKER
CBLVMC CIRCUIT BREAKER, LOW VOLTAGE MOLDED CASE
CBLVPWR CIRCUIT BREAKER, LOW VOLTAGE POWER OVER 50 AMPS
CBR CHEMICAL, BIOLOGICAL AND RADIOLOGICAL
CDWR CHILLED DRINKING WATER RETURN
CDWR BAL VLV CHILLED DRINKING WATER RETURN BALANCING VALVE
CDWR CTRL VLV CHILLED DRINKING WATER RETURN CONTROL VALVE
CDWR DRN VLV CHILLED DRINKING WATER RETURN DRAIN VALVE
CDWR ISO VLV CHILLED DRINKING WATER RETURN ISOLATION VALVE
CDWR MAV CHILLED DRINKING WATER MANUAL AIR VENT
CDWR STRNR CHILLED DRINKING WATER RETURN STRAINER
CDWS CHILLED DRINKING WATER SUPPLY
CDWS BAL VLV CHILLED DRINKING WATER SUPPLY BALANCING VALVE
CDWS CTRL VLV CHILLED DRINKING WATER SUPPLY CONTROL VALVE
CDWS DRN VLV CHILLED DRINKING WATER SUPPLY DRAIN VALVE
CDWS ISO VLV CHILLED DRINKING WATER SUPPLY ISOLATION VALVE
CDWS MAV CHILLED DRINKING WATER SUPPLY MANUAL AIR VENT
CDWS STRNR CHILLED DRINKING WATER SUPPLY STRAINER
CF CHEMICAL FEEDER
CH CHILLER, (ABSORPTION, CENTRIFUGAL, RECIPROCATING
AND SCROLL, SCREW)
CHWR CHILLED WATER RETURN
CHWR BAL VLV CHILLED WATER RETURN BALANCING VALVE
CHWR CTRL VLV CHILLED WATER RETURN CONTROL VALVE
CHWR DRN VLV CHILLED WATER RETURN DRAIN VALVE
CHWR ISO BAL VLV CHILLED WATER RETURN COMBINATION ISOLATION & BALANCING
VALVE
CHWR ISO VLV CHILLED WATER RETURN ISOLATION VALVE
CHWR MAV CHILLED WATER RETURN MANUAL AIR VENT
CHWR STRNR CHILLED WATER RETURN STRAINER
CHWS CHILLED WATER SUPPLY
CHWS BAL VLV CHILLED WATER SUPPLY BALANCING VALVE
CHWS CTRL VLV CHILLED WATER SUPPLY CONTROL VALVE
CHWS DRN VLV CHILLED WATER SUPPLY DRAIN VALVE
CHWS ISO STRNR VLV CHILLED WATER SUPPLY COMBINATION ISOLATION VALVE &
STRAINER
CHWS ISO VLV CHILLED WATER SUPPLY ISOLATION VALVE
CHWS MAV CHILLED WATER SUPPLY MANUAL AIR VENT
CHWS STRNR CHILLED WATER SUPPLY STRAINER
CLK CLOCKS, CENTRAL SYSTEM
COMP REFRIGERATION COMPRESSOR
COND CONDENSER
COND BALVLV CONDENSER WATER RETURN BALANCING VALVE
COND DRN VLV CONDENSER WATER DRAIN VALVE
CONDR CONDENSER WATER RETURN
CONDR ISOVLV CONDENSER WATER RETURN ISOLATION VALVE
Pentagon Equipment Labeling Standard 10
CONDS CONDENSER WATER SUPPLY
CONDS ISOVLV CONDENSER WATER SUPPLY ISOLATION VALVE
CONV CONVECTOR, HEATING
CRP CONDENSATE RETURN PUMP
CT COOLING TOWER
CTRLVLV CONTROL VALVE
CUH CABINET UNIT HEATER
DC GLYCOL DRY COOLER
DCW DOMESTIC COLD WATER
DCW DOMESTIC COLD WATER
DCW AAV DOMESTIC COLD WATER AUTOMATIC AIR VENT
DCW BAL VLV DOMESTIC COLD WATER BALANCING VALVE
DCW CTRL VLV DOMESTIC COLD WATER CONTROL VALVE
DCW DRN VLV DOMESTIC COLD WATER DRAIN VALVE
DCW ISO VLV DOMESTIC COLD WATER ISOLATION VALVE
DCW MAV DOMESTIC COLD WATER MANUAL AIR VENT
DCW STRNR DOMESTIC COLD WATER STRAINER
DCW VLVCHK DOMESTIC COLD WATER CHECK VALVE
DH DUCT HEATER
DHWR DOMESTIC HOT WATER RETURN
DHWR BAL VLV DOMESTIC HOT WATER RETURN BALANCING VALVE
DHWR DRN VLV DOMESTIC HOT WATER RETURN DRAIN VALVE
DHWR ISO VLV DOMESTIC HOT WATER RETURN ISOLATION VALVE
DHWR STRNR DOMESTIC HOT WATER RETURN STRAINER
DHWR VLVCHK DOMESTIC HOT WATER RETURN CHECK VALVE
DHWR VLVS DOMESTIC HOT WATER RETURN SAFETY VALVE
DHWS DOMESTIC HOT WATER SUPPLY
DHWS BAL VLV DOMESTIC HOT WATER SUPPLY BALANCING VALVE
DHWS DRN VLV DOMESTIC HOT WATER SUPPLY DRAIN VALVE
DHWS ISO VLV DOMESTIC HOT WATER SUPPLY ISOLATION VALVE
DHWS STRNR DOMESTIC HOT WATER SUPPLY STRAINER
DHWS VLVCHK DOMESTIC HOT WATER SUPPLY CHECK VALVE
DHWS VLVS DOMESTIC HOT WATER SUPPLY SAFETY VALVE
DMPR REMOTE AIR INTAKE DAMPER
DP DISTRIBUTION PANEL
DPLS DISTRIBUTION PANEL LIFE SAFETY
DPSB DISTRIBUTION PANEL STANDBY
DPMC DISTRIBUTION PANEL MISSION CRITICAL
DRNVLV DRAIN VALVE
DWCH CHILLER, PACKAGE UNIT (DOMESTIC DRINKING WATER)
DWH DOMESTIC WATER HEATER
EADMPR EXHAUST AIR DAMPER
ECU EVAPORATIVE COOLING UNIT
EF EXHAUST AIR FAN
EGEN EMERGENCY GENERATOR, ELECTRIC, GASOLINE, NAT. GAS
Pentagon Equipment Labeling Standard 11
EGEN EMERGENCY GENERATOR, STEAM TURBINE DRIVEN
EJ EXPANSION JOINT, IN PIPING
EL EMERGENCY LIGHTS (BATTERY OPERATED)
ELT FLUOR EMERGENCY FLORESCENT LIGHTING FIXTURE
ELT INCAN EMERGENCY INCANDESCENT LIGHTING FIXTURE
ENCB ENCLOSED CIRCUIT BREAKER
ENT DR ENTRANCE DOOR, ALL OTHER DOORS
ET EXPANSION TANK
EWC ELECTRIC WATER FOUNTAIN
EWS EYE WASH STATION
EXT LT EXIT LIGHT FIXTURE
FANCENT FAN, CENTRIFUGAL
FANPROP FAN, PROPELLER
FCU FAN COIL UNIT, (CEILING HUNG, UNDER WINDOW TYPE)
FDMPR, SDMPR, FSDMPR DAMPER, FIRE AND SMOKE
FDR FIRE DOORS, STAIRWELL, EXIT
FE FIRE EXTINGUISHER
FFU FAN FILTER UNIT
FO ISO VLV FUEL OIL ISOLATION VALVE
FLSW AUTOMATIC FIRE DETECTION, WATER FLOW ALARMS
FLTR FILTER
FOP FUEL OIL PUMP
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FOTK FUEL OIL TANK
FOUNT FOUNTAIN SYSTEM
FPIU FAN POWERED INDUCTION UNIT
FPV FAN POWERED INDUCTION UNIT, VARIABLE VOLUME
FS FIRE SYSTEM
FTR FINNED TUBE RADIATION, HEATING
FURN FURNACE, HOT AIR
GDP GAS DETECTION PANEL
GDS GAS DETECTION SENSOR
GEN GENERATOR, PORTABLE UP TO 5KW, GASOLINE POWERED
GF GLYCOL FEED
GI GREASE INTERCEPTOR
HC COILS, PREHEAT, REHEAT (REMOTE LOCATIONS)
HD AUTOMATIC FIRE DETECTION, HEAT DETECTORS
HMD HUMIDIFICATION SYSTEM
HP HEAT PUMP
HPR HIGH PRESSURE CONDENSATE RETURN
HPR DRN VLV HIGH PRESSURE CONDENSATE RETURN DRAIN VALVE
HPR ISO VLV HIGH PRESSURE CONDENSATE RETURN ISOLATION VALVE
HPR STRNR HIGH PRESSURE CONDENSATE RETURN STRAINER
HPR VLVCHK HIGH PRESSURE CONDENSATE RETURN CHECK VALVE
Pentagon Equipment Labeling Standard 12
HPS HIGH PRESSURE STEAM
HPS BAL VLV HIGH PRESSURE STEAM BALANCING VALVE
HPS CTRL VLV HIGH PRESSURE STEAM CONTROL VALVE
HPS DRN VLV HIGH PRESSURE STEAM DRAIN VALVE
HPS ISO VLV HIGH PRESSURE STEAM ISOLATION VALVE
HPS STRNR HIGH PRESSURE STEAM STRAINER
HPS VLVR HIGH PRESSURE STEAM REGULATING VALVE
HPS VLVS HIGH PRESSURE STEAM SAFETY VALVE
HRR HEAT RECOVERY UNIT RETURN (LIQUID SIDE ONLY)
HRR BAL VLV HEAT RECOVERY UNIT RETURN BALANCING VALVE
HRR CTRL VLV HEAT RECOVERY UNIT RETURN CONTROL VALVE
HRR DRN VLV HEAT RECOVERY UNIT RETURN DRAIN VALVE
HRR ISO BAL VLV HEAT RECOVERY UNIT RETURN COMBINATION ISOLATION &
BALANCING VALVE
HRR ISO VLV HEAT RECOVERY UNIT RETURN ISOLATION VALVE
HRR MAV HEAT RECOVERY UNIT RETURN MANUAL AIR VENT
HRR STRNR HEAT RECOVERY UNIT RETURN STRAINER
HRS HEAT RECOVERY UNIT SUPPLY (LIQUID SIDE ONLY)
HRS BAL VLV HEAT RECOVERY UNIT SUPPLY BALANCING VALVE
HRS CTRL VLV HEAT RECOVERY UNIT SUPPLY CONTROL VALVE
HRS DRN VLV HEAT RECOVERY UNIT SUPPLY DRAIN VALVE
HRS ISO STRNR
VLV
HEAT RECOVERY UNIT SUPPLY COMBINATION
ISOLATION VALVE & STRAINER
HRS ISO VLV HEAT RECOVERY UNIT SUPPLY ISOLATION VALVE
HRS MAV HEAT RECOVERY UNIT SUPPLY MANUAL AIR VENT
HRS STRNR HEAT RECOVERY UNIT SUPPLY STRAINER
HS HAND SINK
HTR HEATER UNIT, ELECTRIC
HTR HEATER, FUEL OIL
HVL HIGH VOLTAGE LOAD INTERRUPTER
HWH HOT WATER HEATER
HWR HOT WATER RETURN
HWR BAL VLV HOT WATER RETURN BALANCING VALVE
HWR CTRL VLV HOT WATER RETURN CONTROL VALVE
HWR DRN VLV HOT WATER RETURN DRAIN VALVE
HWR ISO BAL VLV HOT WATER RETURN COMBINATION ISOLATION & BALANCING
VALVE
HWR ISO VLV HOT WATER RETURN ISOLATION VALVE
HWR MAV HOT WATER RETURN MANUAL AIR VENT
HWR STRNR HOT WATER RETURN STRAINER
HWR VLVCHK HOT WATER RETURN CHECK VALVE
HWS HOT WATER SUPPLY
HWS BAL VLV HOT WATER SUPPLY BALANCING VALVE
HWS CTRL VLV HOT WATER SUPPLY CONTROL VALVE
HWS DRN VLV HOT WATER SUPPLY DRAIN VALVE
HWS ISO STRNR VLV HOT WATER SUPPLY COMBINATION ISOLATION VALVE & STRAINER
Pentagon Equipment Labeling Standard 13
HWS ISO VLV HOT WATER SUPPLY ISOLATION VALVE
HWS MAV HOT WATER SUPPLY MANUAL AIR VENT
HWS STRNR HOT WATER SUPPLY STRAINER
HWS VLVCHK HOT WATER SUPPLY CHECK VALVE
HX HOT WATER CONVERTER (ELECTRIC, GAS, STEAM, PLATE)
ISO VLV ISOLATION VALVE
IU INDUCTION UNIT, UNDER WINDOW TYPE
IW IRRIGATION WATER
LP LIGHTING PANEL
LPLS LIGHTING PANEL LIFE SAFETY
LPMC LIGHTING PANEL MISSION CRITICAL
LPR LOW PRESSURE CONDENSATE RETURN
LPR AAV LOW PRESSURE CONDENSATE RETURN AUTOMATIC AIR VENT
LPR DRN VLV LOW PRESSURE CONDENSATE RETURN DRAIN VALVE
LPR ISO VLV LOW PRESSURE CONDENSATE RETURN ISOLATION VALVE
LPR STRNR LOW PRESSURE CONDENSATE RETURN STRAINER
LPR VLVCHK LOW PRESSURE CONDENSATE RETURN CHECK VALVE
LPS LOW PRESSURE STEAM
LPS BAL VLV LOW PRESSURE STEAM BALANCING VALVE
LPS CTRL VLV LOW PRESSURE STEAM CONTROL VALVE
LPS DRN VLV LOW PRESSURE STEAM DRAIN VALVE
LPS ISO VLV LOW PRESSURE STEAM ISOLATION VALVE
LPS STRNR LOW PRESSURE STEAM STRAINER
LPS VLVR LOW PRESSURE STEAM REGULATING VALVE
LPS VLVS LOW PRESSURE STEAM SAFETY VALVE
LT FLUOR FLORESCENT LIGHTING FIXTURE
LT INCAN INCANDESCENT LIGHTING FIXTURE
LT PK LOT PARKING LOT LIGHTING FIXTURE
LVR LOUVER
MAV MANUAL AIR VENT
MBC MAINTENANCE BYPASS CABINET
MBS MAINTENANCE BYPASS SWITCH
MCC MOTOR CONTROL CENTER
MON REFRIGERANT MONITOR
MP MECHANICAL EQUIPMENT PANEL BOARD
MPMC MECHANICAL EQUIPMENT PANEL BOARD MISSION CRITICAL
MS MOTOR STARTER
MTR MOTOR
MTSHV MANUAL TRANSFER SWITCH HIGH VOLTAGE
MTSLV MANUAL TRANSFER SWITCH LOW VOLTAGE
MV MIXING VALVE
NFDS NOT FUSIBLE DISCONNECT
NG NATURAL GAS
NG DRN VLV NATURAL GAS DRAIN VALVE
NWP NETWORK PROTECTOR
Pentagon Equipment Labeling Standard 14
OADMPR OUTDOOR AIR DAMPER
OASF OUTSIDE AIR SUPPLY FAN
OCR OVER CURRENT RELAY, INDUCTION DISK
OZGEN OZONE GENERATOR
PDU POWER DISTRIBUTION UNIT
PG PRESSURE GAUGE
PMP CONDENSATE OR VACUUM PUMP
PMP PUMP, CONDENSATE W/ RECEIVER, VACUUM
PMPCENTR PUMP, CENTRIFUGAL
PMPFIRE PUMP, FIRE (DIESEL ENGINE, ELECTRIC MOTOR DRIVEN )
PMPSMP PUMP, SUMP
PMPSWG PUMP, SEWAGE
PNLCTRL CONTROLS, CENTRAL SYSTEM (EMCS)
PNLCTRLFA CONTROLS, FIRE ALARM SYSTEM
PNLCTRLIW CONTROLS IRRIGATION WATER
PNLPWR ELECTRICAL PANELS
PP POWER PANEL
PPLS POWER PANEL LIFE SAFETY
PPMC POWER PANEL MISSION CRITICAL
PPSB POWER PANEL STANDBY
RAC AIR CONDITIONING UNIT, WINDOW (ROOM AIR CONDITIONER)
RAD RADIATOR, HEATING
RADMPR RETURN AIR DAMPER
RD ROOF DRAIN
RF RETURN AIR FAN
RHC REHEAT COIL
RHCE ELECTRIC REHEAT COIL
RHCH HYDRONIC REHEAT COIL
RO REVERSE OSMOSIS WATER FILTER
RTN RETURN
SAN SANITARY
SAN ISO VLV SANITARY ISOLATION VALVE
SAN VLVCHK SANITARY CHECK VALVE
SBS STATIC BYPASS SWITCH
SD AUTOMATIC FIRE DETECTION, SMOKE DETECTORS
SDMPR DAMPER, SMOKE
SF SUPPLY AIR FAN
SPLY SUPPLY
STMPRS STEAM PRESSURE REDUCING STATION
STMTRP STEAM TRAP
STRNR STRAINER
STRNRD STRAINER, DUAL
STRNRF STRAINER, BOLTED FLANGE
STRNRY STRAINER, Y-TYPE
STS STATIC TRANSFER SWITCH
Pentagon Equipment Labeling Standard 15
SWBRD SWITCHBOARD, PER CUBICAL
SWDISC DISCONNECT SWITCH OR ISOLATING SWITCH
SWGR SWITCHGEAR
TANK TANK, ALL TYPES
TANK PNL CTRL TANK CONTROL PANEL
TMS THERMOSTATIC MIXING STATION
TNKEXP TANK EXPANSION
TP TRAP PRIMER
TU TERMINAL UNIT WITHOUT REHEAT (VAV)
TUR TERMINAL UNIT WITH REHEAT (VAV)
UH UNIT HEATER (GAS, OIL, STEAM, HOT WATER)
UPS UNINTERRUPTIBLE POWER SYSTEM
UPC UNITIZE POWER CENTER
UR URINAL
UR URINAL
VFD VARIABLE FREQUENCY DRIVE
VLVCHK CHECK VALVE
VLVFALCHK VALVE, ALARM CHECK AND ACCESSORIES
VLVCNTRL VALVE, CONTROL
VLVFCTRL VALVE, FIRE CONTROL
VLVFPPA VALVE, PRE-ACTION DRY TYPE
VLVM VALVE, MANUALLY OPERATED, MAIN LINE OR CRITICAL
VLVMTR VALVE, MOTOR OPERATED (HYDRAULIC/PNEUMATIC/ELECTRIC)
VLVNCRIT VALVE, APPROX. NUMBER OF NON-CRITICAL VALVES UNDER 2"
VLVR VALVE, REGULATING
VLVR VALVE, REGULATING
VAV VARIABLE AIR VOLUME
VLVS SAFETY RELIEF VALVE
VLVS VALVE, SAFETY RELIEF
WSFTNR WATER SOFTENER
WC WATER CLOSET
WT WATER TREATMENT
XFMRHV TRANSFORMER, HIGH VOLTAGE NETWORK AND POWER TYPE (DRY
TYPE)
XFMRHV TRANSFORMER, HIGH VOLTAGE NETWORK AND POWER TYPE (OIL
FILLED)
XFMRLV TRANSFORMER, LOW VOLTAGE (DRY TYPE)
Pentagon Equipment Labeling Standard 16
1.8 APPENDIX A. RING SITE GRID FOR EXTERIOR LOCATIONS
Pentagon Equipment Labeling Standard 17
Turnover Const.
Area Discipline Tag No
System Type System
Equipment Type
Equipment Description Service
Control Type Floor Ring Room
Room Description Manufacturer Model No Serial No Comments Change Notes Change Date Prefix
Generic Type of Equipment
T14 AB12 Mechanical AHU-1B943-01 Ventilation AHU-1B943-01 AHU-15 Air Handling Unit
Floors 1-5, Corridor
AHU-
T19
1 B 1B943 Mechanical Room 1B943
Temtrol Modular Custom
Turnover updated from T14 to T15, 9/24/2007 - Moved from Wedge 3
18-Aug-08 AHU Air Handling Unit
T14 AB12 Mechanical FPI-1B949Z-01 Ventilation HVAC FPI-7 Bottom Access Fan Powered Induction Unit
Corridor 9, 1st Floor
FPIU-
T28
1 B 1B9479Z Corridor Enviro-Tec CFRCCX
Tag correction from FPI-
1B9479Z-01; MOVED
FROM WEDGE 3 -
9/24/2007
24-Sep-07 FPI Fan Powered Induction Unit
T14 AB12 Mechanical FPI-2B947AZ-
Ventilation AHU-1B913A- 01/02
FPI-7 Bottom Access Fan Powered Induction Unit
Corridor 9, 2nd Floor
FPIU-
T26
2 B 2B947AZ Corridor Enviro-Tec CFRCCX
MOVED FROM WEDGE 3 24-Sep-07 FPI Fan Powered Induction Unit
T14 AB12 Mechanical FPI-2B949Z-01 Ventilation HVAC FPI-7 Bottom Access Fan Powered Induction Unit
Corridor 9, 2nd Floor
FPIU-
2 B 2B949Z Corridor Enviro-Tec CFRCCX
T14 AB12 Mechanical FPI-3B948AZ-
Ventilation AHU-1C913- 01/02
FPI-7 Bottom Access Fan Powered Induction Unit
Corridor 9, 3rd Floor
FPIU-
3 B 3B948AZ Corridor Enviro-Tec CFRCCX
T14 AB12 Mechanical FPI-3B949Z-01 Ventilation HVAC FPI-7 Bottom Access Fan Powered Induction Unit
Corridor 9, 3rd Floor
FPIU-
3 B 3B949Z Corridor Enviro-Tec CFRCCX
T14 AB12 Mechanical FPI-4B948AZ-
Ventilation HVAC FPI-7 Bottom Access Fan Powered Induction Unit
Corridor 9, 4th Floor
FPIU-
4 B 4B948AZ Corridor Enviro-Tec CFRCCX
T14 AB12 Mechanical FPI-4B949Z-01 Ventilation HVAC FPI-7 Bottom Access Fan Powered Induction Unit
Corridor 9, 4th Floor
FPIU-
4 B 4B949AZ Corridor Enviro-Tec CFRCCX
Corrected from FPI- 4B949AZ-01 to match SI
DMEL; MOVED FROM
WEDGE 3 - 9/24/2007
24-Sep-07 FPI Fan Powered Induction Unit
T14 AB12 Mechanical FPI-5B948AZ-
Ventilation HVAC FPI-7 Bottom Access Fan Powered Induction Unit
Corridor 9, 5th Floor
FPIU-
5 B 5B948AZ Corridor Enviro-Tec CFRCCX
T14 AB12 Mechanical FPI-5B949Z-01 Ventilation HVAC FPI-7 Bottom Access Fan Powered Induction Unit
Corridor 9, 5th Floor
FPIU-
5 B 5B949Z Corridor Enviro-Tec CFRCCX
T14 AB12 Fire Protection
VAVCTRL-1A-
STA9-01
Control Valve Standpipe
Standpi pe FA9 Control Valve
1 A Corr 9 Corridor Multiple
VAVCTRL Fire Protection
T14 AB12 Fire Protection
VAVCTRL-1B-
ST91-04
Standpi pe F91
1 B STAIR 91 Stairwell Multiple
Protection
VAVCTRL-3B-
Assembly - Control Valve
Control Valve Standpipe
Standpi pe F91
3 B STAIR 91 Stairwell Multiple
Protection
VAVCTRL-5B-
ST91-05
Control Valve
Control Valve Standpipe
Standpi pe F91
5 B STAIR 91 Stairwell Multiple
Protection
VAVFCTRL-1B-
ST91-03
Wet Zone Sprinkler Zone Assembly
WSZA-
A1AB90
1 B STAIR 91 Stairwell Multiple
. VAVFCTRL Fire Protection
Protection
VAVFCTRL-2B-
Assembly
WSZA-
A2AB90
2 B STAIR 91 Stairwell Multiple
VAVFCTRL Fire Protection
Protection
VAVFCTRL-3B-
Assembly
WSAZA
A3AB90
3 B STAIR 91 Stairwell Multiple
Protection
VAVFCTRL-4B-
Assembly
WSZA-
A4AB90
4 B STAIR 91 Stairwell Multiple
Protection
VAVFCTRL-5B-
Assembly
WSZA-
A5AB90
5 B STAIR 91 Stairwell Multiple
T14 AB17 Mechanical AC-2B960-01 CRAC Standalone AC-11 Vertical Downflow Chilled Water Comp. Room Air Conditioner
Consoli dated Server Room 2B960
CRAC-
2 B 2B960 Server Room Liebert FH74C
Control Type Updated 8/14/2008
Room number revision from 2B1053 (RFI- 0189);AC change form 10 to 11 (DCN4024),11-12-07
3-Dec-07 CRAC Computer Rm AC Unit
T14 AB17 Mechanical AC-2B960-02 CRAC Standalone AC-10 Vertical Downflow Chilled Water Comp. Room Air Conditioner
Consoli dated Server Room 2B960
CRAC-
Room number revision from 2B1053 (RFI-0189);
Add,11-12-07
3-Dec-07 CRAC Computer Rm AC Unit
14 AB17 Mechanical AC-2B960-03 CRAC Standalone AC-10 Vertical Downflow Chilled Water Comp. Room Air Conditioner
Consoli dated Server Room 2B960
CRAC-
Room number revision from 2B1053 (RFI-0189)
3-Dec-07 CRAC Computer Rm AC Unit
Pentagon Equipment Labeling Standard 18
Const.
Area Discipline Tag No
System Type System
Equipment Type
Equipment Description Service
Control Type Floor Ring Room
Room Description Manufacturer Model No Serial No Comments Change Notes Change Date Prefix
Generic Type of Equipment
T14 AB17 Mechanical AC-2B960-04 CRAC Standalone AC-10 Vertical Downflow Chilled Water Comp. Room Air Conditioner
Consoli dated Server Room 2B960
CRAC-
Room number revision from 2B1053 (RFI-0189)
3-Dec-07 CRAC Computer Rm AC Unit
T14 AB17 Mechanical AC-2B960-05 CRAC Standalone AC-11 Vertical Downflow Chilled Water Comp. Room Air Conditioner
Consoli dated Server Room 2B960
CRAC-
Room number revision from 2B1053 (RFI- 0189);AC change from 10 to 11 (DCN 4024),11/12/2007
3-Dec-07 CRAC Computer Rm AC Unit
T14 AB17 Mechanical AC-2B960-06 CRAC Standalone AC-11 Vertical Downflow Chilled Water Comp. Room Air Conditioner
Consoli dated Server Room 2B960
CRAC-
Room number revision from 2B1053 (RFI- 0189);AC change from 10 to 11 (DCN 4024),11/12/2007
3-Dec-07 CRAC Computer Rm AC Unit
T14 AB17 Mechanical AC-2C1059A-01 CRAC C1053 Riser AC-1 Vertical Upflow Chilled Water Comp.
Room Air Conditioner
Combin ed TC/Clas s TC Closet
CRAC-
2 C 2C1059A TelMech Closet
Liebert UH200C
Control Type Added 2/22/08
CRAC Computer Rm AC Unit
T14 AB17 Mechanical AC-2C1059A-02 CRAC C1053 Riser AC-1 Vertical Upflow Chilled Water Comp.
Room Air Conditioner
Combin ed TC/Clas s TC Closet
CRAC-
2 C 2C1059A TelMech
CRAC Computer Rm AC Unit
T14 AB17 Mechanical AC-3B957-01 CRAC Standalone AC-11 Vertical Downflow Chilled Water Comp. Room Air Conditioner
Consoli dated Server Room 3B953
CRAC-
3 B 3B957 Server Room Liebert FH74C
Change from ID# 3B953- 01(DCN 4045); Unit ID change form 3B952- 01/change AC 10 to 11
(DCN4024),11-12-07
21-Jan-08 CRAC Computer Rm AC Unit
T14 AB17 Mechanical AC-3B957-02 CRAC Standalone AC-11 Vertical Downflow Chilled Water Comp. Room Air Conditioner
Consoli dated Server Room 3B953
CRAC-
Change from ID# 3B953- 02(DCN 4045); Unit ID change form 3B952- 02/change AC 10 to 11
(DCN4024)11/12/2007
21-Jan-08 CRAC Computer Rm AC Unit
T14 AB17 Mechanical AC-3B957-03 CRAC Standalone AC-11 Vertical Downflow Chilled Water Comp. Room Air Conditioner
Consoli dated Server Room 3B953
CRAC-
Change from ID# 3B953- 03(DCN 4045); Unit ID change from 3B952- 03/change AC 10 to 11
(DCN4024)11/12/2007
21-Jan-08 CRAC Computer Rm AC Unit
T14 AB17 Mechanical AC-3B957-04 CRAC Standalone AC-10 Vertical Downflow Chilled Water Comp. Room Air Conditioner
Consoli dated Server Room 3B953
CRAC-
Change from ID# 3B9573- 04(DCN 4045);Unit ID change from 3B952-
04(DCN4024)11/12/2007
21-Jan-08 CRAC Computer Rm AC Unit
T14 AB17 Mechanical AC-3B957-05 CRAC Standalone AC-10 Vertical Downflow Chilled Water Comp. Room Air Conditioner
Consoli dated Server Room 3B953
CRAC-
Change from ID# 3B953- 05 (DCN 4045;Unit ID change from 3B952-
05(DCN4024)11/12/2007
21-Jan-08 CRAC Computer Rm AC Unit
T14 AB17 Mechanical AC-3B957-06 CRAC Standalone AC-10 Vertical Downflow Chilled Water Comp. Room Air Conditioner
Consoli dated Server Room 3B953
CRAC-
Change from ID# 3B953- 06(DCN 4045); Unit ID change from 3B952-
06(DCN4024)11/12/2007
21-Jan-08 CRAC Computer Rm AC Unit
T14 AB17 Mechanical AC-3C1057A-01 CRAC C1053 Riser AC-1 Vertical Upflow Chilled Water Comp.
Room Air Conditioner
Combin ed TC/Clas s TC Closet
CRAC-
3 C 3C1057A TelMech
CRAC Computer Rm AC Unit
T14 AB17 Mechanical AC-4C1057A-01 CRAC C1053 Riser AC-1 Vertical Upflow Chilled Water Comp.
Room Air Conditioner
Combin ed TC/Clas s TC Closet
CRAC-
4 C 4C1057A TelMech
CRAC Computer Rm AC Unit
T14 AB17 Mechanical AC-5B1057-01 CRAC Standalone AC-5 Vertical Upflow Chilled Water Comp.
Room Air Conditioner
5th floor
AB-17
CRAC-
5 B 5B1057 Server Room Liebert FH248C
Unit Added (DCN 4105) 4-Aug-08 CRAC Computer Rm AC Unit
T14 AB17 Mechanical AC-5B1057-02 CRAC Standalone AC-5 Vertical Upflow Chilled Water Comp.
Room Air Conditioner
5th floor
AB-17
CRAC-
5 B 5B1057 Server Room Liebert FH248C
Unit Added (DCN 4105) 4-Aug-08 CRAC Computer Rm AC Unit
T14 AB17 Mechanical AC-5C1057A-01 CRAC C1053 Riser AC-1 Vertical Upflow Chilled Water Comp.
Room Air Conditioner
Combin ed TC/Clas s TC Closet
CRAC-
5 C 5C1057A TelMech
CRAC Computer Rm AC Unit
T14 AB17 Electrical BD-4B1036A-01 Normal Power
C10 Normal Power
Busway Riser Bus Duct, 480Y/277V, 3
PH, 4W, 600A
4 B 4B1036A
Cutler- Hammer
Pow-R- Way III
MLY0216
changed from ABC18 to AB17;Added, 11/12/2007-missed in previous DMEL
4-Aug-08 BD Busway Riser
Pentagon Equipment Labeling Standard 19
Const.
Area Discipline Tag No
System Type System
Equipment Type
Equipment Description Service
Control Type Floor Ring Room
Room Description Manufacturer Model No Serial No Comments Change Notes Change Date Prefix
Generic Type of Equipment
T14 AB17 Mechanical CAV-1A1064Z-
Ventilation AHU-1B943- 01 CAV-3 Constant Air Valve
Serves
FCU-
1A1066-
CAV-01 1 A 1A1064Z Supply Room
Enviro-Tec Model
SGX
Accel 2
Ring correction from C ring( Quarterly 2/08/08);
5/5/2008 - Floor correction from FL-2( Quarterly 2/08/08)3/10/2008; Add
CAV -3 (DCN 4070)
Correct ID# is on the quarterly update 2/08/08, 2/28/2008
5-May-08 CAV Constant Air Valve
T14 AB17 Mechanical CAV-1B952-01 Ventilation AHU-1E985A- 01/02/03/04/05
CAV-1 Constant Air Valve
Serves
FCU-
1B957-
CAV-01 1 B 1B952 Customer Service Center
Enviro-Tec Model
Add 11-Feb-08 CAV Constant Air Valve
T14 AB17 Mechanical CAV-1C1035-01 Ventilation AHU-1E985A- 01/02/03/04/05
CAV-1 Constant Air Valve
Serves
FCU-
1C1035-
CAV-01 1 C 1C1035 Server Room Enviro-Tec Model
Floor correction from FL-2 ( Quarterly 2/08/08); Add
CAV-1 ( DCN
4025)12/3/2007
10-Mar-08 CAV Constant Air Valve
T14 AB17 Mechanical CAV-1C1056A-
Ventilation AHU-1E985A- 01/02/03/04/05
CAV-2 Constant Air Valve
Serves
FCU-
1C1057 A-01
CAV-01 1 C 1C1056A Server Room Enviro-Tec Model
Floor correction from FL-2 ( Quarterly 2/08/08); Add
CAV-2 ( DCN
4025)12/3/2007
10-Mar-08 CAV Constant Air Valve
T14 AB17 Mechanical CAV-2B954-01 Ventilation AHU-1E985A- 01/02/03/04/05
CAV-1 Constant Air Valve
Serves
FCU-
2B954-
CAV-01 2 B 2B954 Customer Service Center
Enviro-Tec Model
? Add 12-Nov-07 CAV Constant Air Valve
T14 AB17 Mechanical CAV-2B954-02 Ventilation AHU-1E985A- 01/02/03/04/05
CAV-1 Constant Air Valve
Serves
FCU-
2B954-
CAV-01 2 B 2B954 Customer Service Center
Enviro-Tec Model
CAV Constant Air Valve
T14 AB17 Mechanical CAV-2B960-01 Ventilation AHU-1E985A- 01/02/03/04/05
CAV-1 Constant Air Valve
Consoli dated Server Room 2B960
CAV-01 2 B 2B960 Server Room Enviro-Tec Model
4/8/2008
Room number revision from 2B1053 (RFI- 0189);CAV change from 10 to 1 ( DCN 4024)11/12/2007
3-Dec-07 CAV Constant Air Valve
T14 AB17 Mechanical CAV-3B956-01 Ventilation AHU-1E985A- 01/02/03/04/05
CAV-1 Constant Air Valve
Serves
FCU-
3B956-
CAV-01 3 B 3B956 Customer Service Center
Enviro-Tec Model
Change from ID# 3B954- 01 ( Update incorporated in 1/4 with RFI );Change from CAV-8 / unit ID change from 3B954-01 ( DCN
4025), 12-03-07;CAV
change from 8 to 1 / unit ID change from 3B953-01(
DCN 4024),11/12/2007
21-Jan-08 CAV Constant Air Valve
T14 AB17 Mechanical CAV-3B957-01 Ventilation AHU-1E985A- 01/02/03/04/05
CAV-1 Constant Air Valve
Consoli dated Server Room 3B953
CAV-01 3 B 3B957 Server Room Enviro-Tec Model
Change from ID# 3B953- 01( DCN 4045); unit ID change from CAV-3B952-
01( DCN 4024), 11-12-07
21-Jan-08 CAV Constant Air Valve
T14 AB17 Mechanical CAV-4B952-01 Ventilation AHU-1E985A- 01/02/03/04/05
CAV-1 Constant Air Valve
Serves
FCU-
4B952-
CAV-01 4 B 4B952 Customer Service Center
Enviro-Tec Model
CAV Constant Air Valve
T14 AB17 Mechanical CAV-4B952-02 Ventilation AHU-1E985A- 01/02/03/04/05
CAV-1 Constant Air Valve
Serves
FCU-
4B1040-
CAV-01 4 B 4B952 Customer Service Center
Enviro-Tec Model
Change from CAV- 4B1040-01; Change from CAV-3 ( DCN 4023) Unit ID # change from 4B952-02 - 11/12/07
31-Mar-08 CAV Constant Air Valve
T14 AB17 Mechanical CAV-5B1055-01 Ventilation AHU-1B1040A-
CAV-1 Constant Air Valve
Tenant Space
JCI 5 B 5B1055 Tenant Enviro-Tec CFRCCX
Unit Added (DCN 4105) 4-Aug-08 CAV Constant Air Valve
T14 AB17 Mechanical CAV-5B952-01 Ventilation AHU-1E985A- 01/02/03/04/05
CAV-1 Constant Air Valve
Serves
FCU-
5B953-
CAV-01 5 B 5B952 Customer Service Center
Enviro-Tec Model
Change from CAV-9 ( DCN 4023) Unit ID # change from 5B953-01 (DCN 4025);Change from CAV-9 ( DCN 4023) Unit ID # change from 5B956- 01,11/12/2007
3-Dec-07 CAV Constant Air Valve
T14 AB17 Mechanical CAV-5B952-02 Ventilation AHU-1E985A- 01/02/03/04/05
CAV-1 Constant Air Valve
Serves
FCU-
5B1040-
CAV-01 5 B 5B952 Customer Service Center
Enviro-Tec Model
Change from CAV-9 ( DCN 4023) Unit ID # change from 5B1040-01
(DCN
4025);Add,11/12/2007
3-Dec-07 CAV Constant Air Valve
T14 AB17 Mechanical CUH-1A1062-01 Space Heating
HWP-MB955-
01/02
CUH-1 Surface Mount Cabinet Heater
Stair
CUH-1 1 A 1A1062 Stairwell Sterling F-1000-y CUH Cabinet Unit Heater
T14 AB17 Mechanical CUH-1B954-01 Space Heating
HWP-MB955-
01/02
CUH-1 Surface Mount Cabinet Heater
Stair 91 CUH-1 1 B 1B954 Stairwell Sterling F-1000-y Unit relocated (DCN 4057)
SI Eng to issue future DCN to reflect ID change from 1B952-01
5-May-08 CUH Cabinet Unit Heater
T14 AB17 Electrical DP-MA9/10-01 Normal Power
C9 Normal Power
Distribution Panelboard
Distribution Panelboard, 480Y/277V, 3PH, 4W, 800A, 800A MCB
M A MA9/10
Moved from Wedge 3 to Wedge 4 per H.P. request
12-Nov-07 PNL Panelboard
T14 AB17 Mechanical EF-1C1037A-01 Exhaust HVAC EF-36 Centrifugal Roof Ventilator
C Ring, Corridor 10, A/E Drive
EF-T7 1 C 1C1037A C Ring 1st floor
Greenheck BSQ-160 y Tag correction from EF- 1B1037A-01; ChangeID# from 1B1038A -01 (DCN 4025) - 12/3/07
31-Mar-08 EF Exhaust Fan
Pentagon Equipment Labeling Standard 20
Const.
Area Discipline Tag No
System Type System
Equipment Type
Equipment Description Service
Control Type Floor Ring Room
Room Description Manufacturer Model No Serial No Comments Change Notes Change Date Prefix
Generic Type of Equipment
T14 AB17 Mechanical EF-1C1041-01 Exhaust HVAC EF-26 Centrifugal In-line Ventilator
B Ring , A/E Drive, CVS
Storage and Cleanin g Crew
TBD 1 C 1C1041 C Ring 1st
Greenheck BSQ-80 y Add EF-26 (DCN 4025) 3-Dec-07 EF Exhaust Fan
T14 AB17 Mechanical EF-2B960-01 Exhaust HVAC EF-55 Centrifugal Inline Ventilator
B Ring, CSR
Exhaust
TBD 2 B 2B960 B Ring Consolidated Server Room
Greenheck BSQ - 80 -3 y Room number revision from 2B1053 (RFI- 0189);Add EF-55 (DCN 4024),11/12/2007
3-Dec-07 EF Exhaust Fan
T14 AB17 Mechanical EF-RB1053A-01 Exhaust HVAC EF-2 Centrifugal Roof Ventilator
A Ring, Bathroo m Exhaust
EF-T9 R C RC1055A A Ring Apex Roof
Greenheck GB-220
? Unit ID corrected from EF-
RB1055A-01; 8/20/2007 -
Unit ID changed from EF-
RC1054B-01 (DCN 4009
17-Mar-08 EF Exhaust Fan
T14 AB17 Mechanical EF-RB953-01 Exhaust HVAC EF-54 Centrifugal Roof Ventilator
B Ring, Exhaust
TBD R B RB953 B Ring Roof Greenheck GB-
141HP-4
Added (DCN 4024) TFO 10-Mar-08 EF Exhaust Fan
T14 AB17 Mechanical FCU-1A1060-02 Ventilation HVAC FCU-1 Vertical Fan Coil Unit
Electrica l Closet
FCU-05 1 A 1A1060 Electrical
Enviro-Tec VHC
Tag ID Changed from
1A1060-01 (DCN 4118);
3/17/2008Correct dwg # from HE-17 / model # change from VHE
4-Aug-08 FCU Fan Coil Unit
T14 AB17 Mechanical FCU-1A1066-01 Ventilation AHU-1E985A- 01/02/03/04/05
FCU-14A Hi- Performance Horizontal Fan Coil Unit
Supplies 1A1066
FCU-02 1 A 1A1066 Supply
Enviro-Tec HPP_14
Change ID# from 1A1066- 01 (Update incorporated in 1/4 with RFI ); Change from FCU-14 (DCN 4025), 12-03-07
21-Jan-08 FCU Fan Coil Unit
T14 AB17 Mechanical FCU-1B1056A-
Ventilation AHU-1B1040A-
FCU-20 Hi- Performance Horizontal Fan Coil Unit
Mainten ance Shop 1C1051
FCU-02 1 B 1B1056A Maintenance Shop
Enviro-Tec HPP-14
Add FCU - 20 (DCN 4025) 3-Dec-07 FCU Fan Coil Unit
T14 AB17 Mechanical FCU-1B952-01 Ventilation AHU-1E985A- 01/02/03/04/05
FCU-12 Hi- Performance Horizontal Fan Coil Unit
Custom er Service Center
FCU-02 1 B 1B957 Customer Service Center
Enviro-Tec HPE-16
Unit ID corrected from FCU-1B957-01; Unit ID changed from FCU-1B953-
01 (DCN 4030) - 08/20/07
11-Feb-08 FCU Fan Coil Unit
T14 AB17 Mechanical FCU-1C1035-01 Ventilation AHU-1E985A- 01/02/03/04/05
FCU-19 Hi- Performance Horizontal Fan Coil Unit
Mainten ance Shop 1C1051
FCU-02 1 C 1C1035 Maintenance Shop
Enviro-Tec HPP-12
Model # correction from HPP-14; Add FCU - 19
(DCN 4025)12/3/2007
17-Mar-08 FCU Fan Coil Unit
T14 AB17 Mechanical FCU-2A1060-01 Ventilation HVAC FCU-1 Vertical Fan Coil Unit
Electrica l Closet
FCU-05 2 A 2A1060 Electrical
Model # correction from
VHE
17-Mar-08 FCU Fan Coil Unit
T14 AB17 Mechanical FCU-2B954-01 Ventilation AHU-1E985A- 01/02/03/04/05
FCU-13 Hi- Performance Horizontal Fan Coil Unit
Custom er Service Center 2B954
FCU-02 2 B 2B954 Customer Service
FCU Fan Coil Unit
T14 AB17 Mechanical FCU-2B954-02 Ventilation AHU-1E985A- 01/02/03/04/05
FCU-10 Vertical Fan Coil Unit
Custom er Service Center 2B954
FCU-02 2 B 2B954 Customer Service
Enviro-Tec CDV-20
FCU Fan Coil Unit
T14 AB17 Mechanical FCU-3A1060-01 Ventilation HVAC FCU-1 Vertical Fan Coil Unit
Electrica l Closet
FCU-05 3 A 3A1060 Electrical
Model # correction from
VHE
17-Mar-08 FCU Fan Coil Unit
T14 AB17 Mechanical FCU-3B956-01 Ventilation AHU-1E985A- 01/02/03/04/05
FCU-14 Hi- Performance Horizontal Fan Coil Unit
Custom er Service Center 3B956
FCU-01 3 B 3B956 Customer Service
Change from FCU-13
(DCN 4045)
21-Jan-08 FCU Fan Coil Unit
T14 AB17 Mechanical FCU-4A1060-01 Ventilation HVAC FCU-1 Vertical Fan Coil Unit
Electrica l Closet
FCU-05 4 A 4A1060 Electrical
Model # correction from
VHE
17-Mar-08 FCU Fan Coil Unit
T14 AB17 Mechanical FCU-4B1036A-
Ventilation HVAC FCU-1 Vertical Fan Coil Unit
Electrica l Closet
FCU-05 4 B 4B1036A Electrical
Model # correction from
VHE
17-Mar-08 FCU Fan Coil Unit
T14 AB17 Mechanical FCU-4B952-01 Ventilation AHU-1E985A- 01/02/03/04/05
FCU-13 Hi- Performance Horizontal Fan Coil Unit
Custom er Service Center 4B952
FCU-04 4 B 4B952 Customer Service
Change ID# from FCU- 4B953-01 (DCN 4025);Unit ID # change from FCU- 4B952-01, 11/12/07
3-Dec-07 FCU Fan Coil Unit
T14 AB17 Mechanical FCU-4B952-02 Ventilation AHU-1E985A- 01/02/03/04/05
FCU-13 Hi- Performance Horizontal Fan Coil Unit
Custom er Service Center 4B952
FCU-04 4 B 4B952 Customer Service
Change ID# from FCU-
4B1040-01 (DCN
4025);Unit ID # change from FCU-4B952- 02,11/12/2007
12-Nov-07 FCU Fan Coil Unit
T14 AB17 Mechanical FCU-5A1060-01 Ventilation HVAC FCU-1 Vertical Fan Coil Unit
Electrica l Closet
FCU-05 5 A 5A1060 Electrical
Model # correction from VHE; Floor and ring correction 3/10/2008
17-Mar-08 FCU Fan Coil Unit
T14 AB17 Mechanical FCU-5B1036A-
Ventilation HVAC FCU-1 Vertical Fan Coil Unit
Electrica l Closet
FCU-05 5 B 5B1036A Electrical
Model # correction from
VHE
17-Mar-08 FCU Fan Coil Unit
T14 AB17 Mechanical FCU-5B952-01 Ventilation AHU-1E985A- 01/02/03/04/05
FCU-13 Hi- Performance Horizontal Fan Coil Unit
Custom er Service Center 5B952
FCU-06 5 B 5B952 Customer Service
Room number revision from 2B1053 (RFI- 0189);FCU ID change from 5B956-01,11/12/2007
3-Dec-07 FCU Fan Coil Unit
T14 AB17 Mechanical FCU-5B952-02 Ventilation AHU-1E985A- 01/02/03/04/05
FCU-13 Hi- Performance Horizontal Fan Coil Unit
Custom er Service Center 5B952
FCU-06 5 B 5B952 Customer Service
FCU ID change from
5B953-01(DCN 4025);FCU
ID change from FCU- 5B956-02,11/12/2007
3-Dec-07 FCU Fan Coil Unit
Pentagon Equipment Labeling Standard 21
Const.
Area Discipline Tag No
System Type System
Equipment Type
Equipment Description Service
Control Type Floor Ring Room
Room Description Manufacturer Model No Serial No Comments Change Notes Change Date Prefix
Generic Type of Equipment
T14 AB17 Mechanical FPI-2A1056BZ-
Ventilation HVAC FPI-10 Bottom Access Fan Powered Induction Unit
Corridor 10, 1st floor
FPIU-
T14
2 A 2A1056BZ Corridor Enviro-Tec CFRCCX
FPI Fan Powered Induction Unit
T14 AB17 Mechanical FPI-2B1056-01 Ventilation AHU-1B1040A-
FPI-5 Bottom Access Fan Powered Induction Unit
Tenant Space
FPIU-
T10
2 B 2B1056 Tenant Enviro-Tec CFRCCX
FPI change from 1 to 5
(DCN 4024)
12-Nov-07 FPI Fan Powered Induction Unit
T14 AB17 Mechanical FPI-2B1056-02 Ventilation AHU-1B1040A-
FPI-5 Bottom Access Fan Powered Induction Unit
Tenant Space
FPIU-
T12
FPI change from 1 to 5
(DCN 4024)
12-Nov-07 FPI Fan Powered Induction Unit
T14 AB17 Mechanical FPI-2B1056-03 Ventilation AHU-1B1040A-
FPI-1 Bottom Access Fan Powered Induction Unit
Tenant Space
FPIU-
Add FPI - 1 (DCN 4024) 12-Nov-07 FPI Fan Powered Induction Unit
T14 AB17 Mechanical FPI-2B1057-01 Ventilation AHU-1B1040A-
FPI-5 Bottom Access Fan Powered Induction Unit
Tenant Space
FPIU-
2 B 2B1057 Tenant Enviro-Tec CFRCCX
Add FPI - 5 (DCN 4024) 12-Nov-07 FPI Fan Powered Induction Unit
T14 AB17 Mechanical FPI-2B958A-01 Ventilation AHU-1E985A- 01/02/03/04/05
FPI-3 Bottom Access Fan Powered Induction Unit
Tenant
FPIU-T8 2 B 2B958A Tenant Enviro-Tec CFRCCX
Add FPI-3 (DCN 4024) 12-Nov-07 FPI Fan Powered Induction Unit
T14 AB17 Mechanical FPI-2C955A-01 Ventilation AHU-1E985A- 01/02/03/04/05
FPI-1 Bottom Access Fan Powered Induction Unit
Tenant Space
FPIU-
2 C 2C955A Tenant Enviro-Tec CFRCCX
FPI Fan Powered Induction Unit
T14 AB17 Mechanical FPI-2C959A-01 Ventilation AHU-1E985A- 01/02/03/04/05
FPI-1 Bottom Access Fan Powered Induction Unit
Tenant Space
FPIU-
T10
2 C 2C959A Tenant Enviro-Tec CFRCCX
FPI Fan Powered Induction Unit
T14 AB17 Mechanical FPI-2C962A-01 Ventilation AHU-1E985A- 01/02/03/04/05
FPI-3 Bottom Access Fan Powered Induction Unit
Tenant
FPIU-T8 2 C 2C962A Tenant Enviro-Tec CFRCCX
FPI Fan Powered Induction Unit
T14 AB17 Mechanical FPI-3A1056BZ-
Ventilation HVAC FPI-10 Bottom Access Fan Powered Induction Unit
Corridor 10, 3rd floor
FPIU-
3 A 3A1056BZ Corridor Enviro-Tec CFRCCX
FPI Fan Powered Induction Unit
T14 AB17 Mechanical FPI-3B1036AZ-
Ventilation AHU-1E985A- 01/02/03/04/05
FPI-8 Bottom Access Fan Powered Induction Unit
Ramp, 3rd floor
FPIU-
T15
3 B 3B1036AZ Ramp Enviro-Tec CFRCCX
FPI Fan Powered Induction Unit
T14 AB17 Mechanical FPI-3B1043AZ-
Ventilation AHU-1B1040A-
FPI-8 Bottom Access Fan Powered Induction Unit
Ramp, 3rd floor
FPIU-
T17
3 B 3B1043AZ Ramp Enviro-Tec CFRCCX
FPI Fan Powered Induction Unit
T14 AB17 Mechanical FPI-3B1044AZ-
Ventilation AHU-1B1040A-
FPI-7 Bottom Access Fan Powered Induction Unit
Ramp, 3rd Floor
FPIU-
3 B 3B1044AZ Ramp Enviro-Tec CFRCCX
2/28/2008 FPI Fan Powered Induction Unit
T14 AB17 Mechanical FPI-3B1054-01 Ventilation HVAC FPI-8 Bottom Access Fan Powered Induction Unit
Ramp, 3rd floor
FPIU-
3 B 3B1054 Tenant Enviro-Tec CFRCCX
Org ID# FPI -3B1053Z - 01 relocated off ramp
(DCN 4070)
10-Mar-08 FPI Fan Powered Induction Unit
T14 AB17 Mechanical FPI-3B1054-02 Ventilation AHU-1B1040A-
FPI-5 Bottom Access Fan Powered Induction Unit
Tenant Space
FPIU-
3 B 3B1054 Tenant Enviro-Tec CFRCCX
Updated 4/8/2008
Org ID# FPI -3B1054 -01 relocated in tenant space
(DCN 4070)
10-Mar-08 FPI Fan Powered Induction Unit
T14 AB17 Mechanical FPI-3B1056A-01 Ventilation AHU-1B1040A-
FPI-1 Bottom Access Fan Powered Induction Unit
Tenant Space
FPIU-
3 B 3B1056A Tenant Enviro-Tec CFRCCX
FPI Fan Powered Induction Unit
T14 AB17 Mechanical FPI-3C955A-01 Ventilation AHU-1E985A- 01/02/03/04/05
FPI-3 Bottom Access Fan Powered Induction Unit
Tenant
FPIU-T8 3 C 3C955A Tenant Enviro-Tec CFRCCX
Change from…
This is the start of the file's text. The full file is on GovTribe.