IFB Attachment 6 - VAMC Charleston SC EHRM Upgrades ACM Survey-12-25.pdf

PDF 17 MB Posted

Attached to
Y1DA--534-24-706 EHRM Data Center Upgrades Construction - Charleston
Solicitation number
36C77626B0027
Issued by

About this file

This is a Pre-Construction Asbestos Survey Report documenting the results of an asbestos-containing materials (ACM) investigation conducted at the Ralph H. Johnson VA Medical Center in Charleston, South Carolina on December 10, 2025. The survey was performed by Pennoni Associates, Inc., an EPA-trained and State of South Carolina licensed environmental firm, in preparation for the Electronic Health Record Management (EHRM) Data Center Upgrades renovation project. The inspection focused on Room B200 (Data Center) and roof areas that would be impacted by the planned renovation work.

The survey identified and sampled 100 suspect ACM systems across 25 homogeneous identification numbers (HIDs), including drywall, joint compound, ceiling tiles, floor tiles and mastics, pipe insulation, roofing materials, and related components. Laboratory analysis by EMSL Analytical, Inc. using Polarized Light Microscopy and Transmission Electron Microscopy methods determined that two materials tested positive for asbestos content: HID 108 (Black mastic associated with 12"x12" floor tiles in Room B200, approximately 300 square feet, containing 2% Chrysotile in good condition) and HID 117 (Tar associated with foil wrap pipe insulation, approximately 82 linear feet, containing 7% Chrysotile in fair condition). The remaining 98 samples tested negative for asbestos. The survey's scope was limited to readily accessible areas within the renovation project footprint; the report notes that hazardous materials may be present in areas outside the survey scope, including concealed spaces, below-grade areas, and other operational utility systems.

View the file

Other files

File Type Posted
Special Notice Issuance of Bid Abstract 36C77626B0027.pdf PDF
36C77626B0027 Bid Abstract 9-14-2026.pdf PDF
36C77626B0027 Amendment 0005.pdf PDF
36C77626B0027 Amendment 0004.pdf PDF
Specification 07 51 00 - Built-Up Bituminous Roofing.pdf PDF
Fire Calculations and Fire Water Flow Testing Documentations.pdf PDF
Specification 02 08 13.19 - Asbestos Floor Tile and Mastic Abatement.pdf PDF
Tech Questions Tracker - EHRM Charleston Final.pdf PDF
ACM Survey_Data Center_AEWLA23075 VAMC Charleston SC EHRM Upgrades Pre-Construction ACM Survey-12-25.pdf PDF
Spec 28 05 28.33 - Conduits and Backboxes for Electronic Safety and Security.pdf PDF
36C77626B0027 Amendment 0003.pdf PDF
36C77626B0027 Amendment 0002.pdf PDF
Site Visit Sign In Sheet Charleston EHRM.pdf PDF
Updated IFB 36C77626B0027.pdf PDF
36C77626B0027 Amendment 0001.pdf PDF
IFB Attachment 7 - Site Visit - Charleston.pdf PDF
IFB Attachment 4 - PCRA_534-24-706_Upgrade Data Center for EHRM_100625.pdf PDF
IFB Attachment 3 - ICRA_534-24-706_Upgrade Data Center for EHRM.pdf PDF
IFB 36C77626B0027.pdf PDF
IFB Attachment 10 - Brand Name Justification - Charleston EHRM Data Center.pdf PDF
IFB Attachment 8 - Limitations on Subcontracting.docx DOCX document
IFB Attachment 2 - ORIGINAL DWG_534-24-706.pdf PDF
IFB Attachment 1 - FINAL SPECS_534-24-706.pdf PDF
IFB Attachment 9 - DBA Rates - Charleston - 5-18-26.pdf PDF
IFB Attachment 5 - NEPA_PCRA_534-24-706_Signed.pdf PDF
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1900 Market Street, Suite 300 T: 215-222-3000 www.pennoni.com Philadelphia, PA 19103 Page 1 of 2

January 5, 2026

AEWLA23075

AE Works Attn: Mr. Michael Carroll, Project Manager 418 Beaver Street Sewickley, PA 15143

RE: PRE-CONSTRUCTION ASBESTOS SURVEY

EHRM DATA CENTER UPGRADES

RALPH H. JOHNSON VA MEDICAL CENTER

109 BEE STREET

CHARLESTON, SC 29401

Dear Mr. Carroll:

Pennoni is providing this report to AE Works documenting the results of the pre-construction asbestos survey conducted at the above referenced location. Activities completed as part of the investigation included a survey and sampling of Room B200 (Data Center) and roof for asbestos-containing materials (ACM) in preparation for the planned renovation project in support of the Electronic Health Record Management (EHRM) infrastructure upgrades.

BACKGROUND

In preparation for the survey, Pennoni reviewed previous environmental documentation for the building (see Appendix F – Previous Environmental Documentation). Sampling of interior areas outside the project scope of renovation, exterior and roof areas not impacted by renovations were not included in Pennon’s scope of work.

PRE-CONSTRUCTION ASBESTOS SURVEY

Pennoni performed a pre-construction asbestos survey within Room B200 on December 10, 2025 to identify if accessible ACM may be disturbed by the planned renovation project. The survey was conducted by Mr. Thomas Adams, one of Pennoni’s United States Environmental Protection Agency (USEPA) trained and State of South Carolina licensed Asbestos Building Inspectors (see Appendix A – Inspector Credentials).

During this inspection, 100 samples of the following identified suspect ACM systems were collected (see Appendix B – Asbestos Field Inspection Forms, Appendix C – Site Photographs and Appendix D – Sample Location Drawing). The following suspect ACM, listed here by Homogeneous Identification Number (HID), were identified and sampled during this investigation:

101. Drywall (NAD)

102. Joint Compound (NAD)

103. 2’x4’ Lay-In Ceiling Tile, Dot (NAD)

104. 2’x2’ Lay-In Ceiling Tile, Dot (NAD)

105. 2’x2’ Lay-In Ceiling Tile, Rough Finish (NAD)

106. 2’x2’ Lay-In Ceiling Tile, Smooth Finish (NAD)

107. Covebase Molding Mastic (NAD)

108. 12”x12” Off-White with Tan Floor Tile (NAD), Tan Mastic (NAD) and Black Mastic (POS)

109. Raised Floor Pedestal Mastic (NAD)

110. Gray Floor Leveling Compound (NAD)

111. Ceramic Floor Mortar/Wetbed (NAD)

112. Fire Stop (NAD)

113. Plaster Wall (NAD)

114. Plaster Patch (NAD)

115. End Cap Mastic (NAD)

116. Fiberglass Pipe Insulation (Non-Suspect)

117. Tar (POS) associated with Foil Wrap Pipe

Insulation (NAD) and HID 118.

118. Fitting (NAD) associated with Fiberglass Pipe

Insulation

119. Roofing Field – Built-up Roofing (NAD), Flashing (NAD), Felt (NAD), Insulation (NAD) and Foam (NAD)

120. Roof Flashing, Equipment – Flashing1 (NAD), Flashing2 (NAD) and Insulation (NAD)

121. Equipment Flashing, Cap Caulk (NAD)

122. Equipment Flashing, Silver Coating (NAD)

123. Endcap Mastic (NAD) associated with Pipe

Insulation

AEWLA23075 Pre-Construction ACM Survey Mr. Michael Carroll January 5, 2026 Page 2 of 2

124. Pitch Pocket (NAD) 125. Equipment Penetration Patch Tar (NAD)

(NAD) – No Asbestos Detected; (POS) – Positive for Asbestos Content

The samples were properly packaged, labeled, and transported to EMSL Analytical, Inc. (EMSL) of Cinnaminson, New Jersey. EMSL is accredited under the National Voluntary Laboratory Accreditation Program (NVLAP). The samples were analyzed for asbestos utilizing Polarized Light Microscopy (PLM) via EPA Method 600/R-93/116. Non-friable organically bound materials (NOBs) with inconclusive results were re-analyzed utilizing Transmission Electron Microscopy (TEM) via EPA Method 600/R-93/116b Section 2.5.5.1 with Gravimetric Reduction.

Analytical results indicate the following sampled material systems were identified as asbestos-containing materials.

Results are summarized in the following table below with the full analytical certificates included in Appendix E.

Table 1 – Identified Asbestos-Containing Materials – 12/10/25 EHRM Data Center Upgrades

Ralph H. Johnson VA Medical Center 109 Bee Street

Charlestown, SC 29401

Homogenous No. and Material Location Approx.

Quantity Type Percentage Condition

108. Black mastic associated with 12”x12” Off-White with Tan Floor Tile B200 300 SF Chrysotile 2% Good

117. Tar associated with non-ACM Foil Wrap Pipe Insulation and HID 118 B200 82 LF Chrysotile 7% Fair

LIMITATIONS

The goal of the pre-construction survey was to identify readily accessible ACM that may be impacted by the renovation project associated within Room B200 and roofing system in support of the EHRM infrastructure upgrades. Pennoni’s survey did not include areas outside the scope of renovation as well as operational utility systems, below-grade or subfloor sampling, concealed pipe chase spaces, inaccessible crawlspaces associated with foundations, or the exterior. Hazardous materials may be present in these areas. Pennoni should be contacted immediately if renovation or demolition activities uncover materials that are not identified in this report.

If you have any questions concerning this report or require additional information, please feel free to contact us at 856-547-0505.

Sincerely, PENNONI ASSOCIATES INC.

Thomas Adams, CIEC Jeremy Humble Senior Industrial Hygienist EHS Division Manager tp

Attachments Appendix A – Inspector Credentials Appendix B – Asbestos Field Inspection Forms Appendix C – Site Photographs Appendix D – Sample Location Drawing Appendix E – Asbestos Laboratory Analytical Certificates Appendix F – Previous Environmental Documentation

U:\Accounts\AEWLA\AEWLA23075 - VAMC Charleston SC EHRM Upgrades\DOCUMENTS\EHS\Site Inspection 12.10.25\AEWLA23075 VAMC Charleston SC EHRM Upgrades Pre-Construction ACM Survey 20251210.docx

APPENDIX A

Inspector Credentials

APPENDIX B

Asbestos Field Inspection Forms

APPENDIX C

Site Photographs

Job No. Date Taken:

SITE PHOTOGRAPHS

PRE-CONSTRUCTION ASBESTOS SURVEY

EHRM DATA CENTER UPGRADES

RALPH H. JOHNSON VA MEDICAL CENTER

109 BEE STREET, CHARLESTON, SC 29401

AEWLA23075

Pennoni Associates, Inc.

515 Grove Street, Suite 1B

Haddon Heights, New Jersey 08035

DECEMBER 10, 2025

Photograph 1: HID 101. Drywall (NAD) and

HID 102. Joint Compound (NAD)

Photograph 2: HID 103. 2’x4’ Lay-In Dot Fissure

Ceiling Tile (NAD)

Photograph 3: HID 104. 2’x2’ Lay-In Dot Fissure

Ceiling Tile (NAD)

Photograph 4: HID 105. 2’x2’ Lay-In Rough Surface

Ceiling Tile (NAD)

PRE-CONSTRUCTION ASBESTOS SURVEY

EHRM DATA CENTER UPGRADES

RALPH H. JOHNSON VA MEDICAL CENTER

109 BEE STREET, CHARLESTON, SC 29401

AEWLA23075

Pennoni Associates, Inc.

515 Grove Street, Suite 1B

Haddon Heights, New Jersey 08035

DECEMBER 10, 2025

Photograph 5: HID 106. 2’x2’ Smooth Vinyl Ceiling Tile (NAD) Photograph 6: Non-Suspect Asbestos-Containing

Fiberglass Pipe Insulation

Photograph 7: HID 107. Covebase Mastic (NAD) Photograph 8: HID 108. 12”x12” Off-White with Tan Floor Tile

(NAD), Tan Mastic (NAD), Black Mastic (ACM) and

HID 110. Gray Leveling Compound (NAD)

PRE-CONSTRUCTION ASBESTOS SURVEY

EHRM DATA CENTER UPGRADES

RALPH H. JOHNSON VA MEDICAL CENTER

109 BEE STREET, CHARLESTON, SC 29401

AEWLA23075

Pennoni Associates, Inc.

515 Grove Street, Suite 1B

Haddon Heights, New Jersey 08035

DECEMBER 10, 2025

Photograph 9: HID 109. Raised Floor Pedestal Mastic (NAD) Photograph 10: HID 111. Ceramic Floor Mortar/Wetbed (NAD)

Photograph 11: HID 112. Fire Stop (NAD) Photograph 12: HID 113. Plaster Wall (NAD)

PRE-CONSTRUCTION ASBESTOS SURVEY

EHRM DATA CENTER UPGRADES

RALPH H. JOHNSON VA MEDICAL CENTER

109 BEE STREET, CHARLESTON, SC 29401

AEWLA23075

Pennoni Associates, Inc.

515 Grove Street, Suite 1B

Haddon Heights, New Jersey 08035

DECEMBER 10, 2025

Photograph 13: HID 113. Plaster Wall (NAD) Photograph 14: HID 113. Plaster Wall (NAD)

Photograph 15: HID 114. Plaster, Patch White (NAD) Photograph 16: HID 115. End Cap Mastic (NAD)

PRE-CONSTRUCTION ASBESTOS SURVEY

EHRM DATA CENTER UPGRADES

RALPH H. JOHNSON VA MEDICAL CENTER

109 BEE STREET, CHARLESTON, SC 29401

AEWLA23075

Pennoni Associates, Inc.

515 Grove Street, Suite 1B

Haddon Heights, New Jersey 08035

DECEMBER 10, 2025

Photograph 17: HID 117. Tar (ACM) associated with

Foil Wrap Pipe Insulation (NAD)

Photograph 18: HID 118. Fitting (NAD) associated with

Fiberglass Pipe Insulation with HID 117. Tar (ACM)

Photograph 19: HID 118. Fitting (NAD) associated with

Fiberglass Pipe Insulation with HID 117. Tar (ACM)

Photograph 20: HID 119. Roof Field and Associated Layers (NAD)

PRE-CONSTRUCTION ASBESTOS SURVEY

EHRM DATA CENTER UPGRADES

RALPH H. JOHNSON VA MEDICAL CENTER

109 BEE STREET, CHARLESTON, SC 29401

AEWLA23075

Pennoni Associates, Inc.

515 Grove Street, Suite 1B

Haddon Heights, New Jersey 08035

DECEMBER 10, 2025

Photograph 21: HID 120. Roof Flashing, Equipment (NAD) Photograph 22: HID 121. Equipment Flashing, Cap Caulk (NAD) and HID 122. Equipment Flashing, Silver Coat (NAD)

Photograph 23: HID 123. Endcap Mastic (NAD) associated with

Pipe Insulation on Roof

Photograph 24: HID 124. Pitch Pocket (NAD)

PRE-CONSTRUCTION ASBESTOS SURVEY

EHRM DATA CENTER UPGRADES

RALPH H. JOHNSON VA MEDICAL CENTER

109 BEE STREET, CHARLESTON, SC 29401

AEWLA23075

Pennoni Associates, Inc.

515 Grove Street, Suite 1B

Haddon Heights, New Jersey 08035

DECEMBER 10, 2025

Photograph 25: HID 125. Equipment Penetration Patch Tar (NAD)

APPENDIX D

Sample Location Drawing

101A & B, 102A & B, 103A & B 104A & B, 105A & B, 106A & B

107A & B, 108A & B. 108MA & MB

109A & B, 110A & B, 111A & B 112A & B, 113A, B & C 114A, B & C, 115A & B, 117A & B, 118A & B

119 A, B & C 120 A, B & C 121 A, B & C 122 A, B & C 123 A, B & C 124 A, B & C 125 A, B & C

APPENDIX E

Asbestos Laboratory Analytical Certificates

EMSL Analytical, Inc.

3303 PARKWAY CENTER COURT Orlando, FL 32808

Tel/Fax: (407) 599-5887 / (407) 599-9063 http://www.EMSL.com / orlandolab@emsl.com

342525972EMSL Order:

Customer ID: PADB75

Customer PO:

Project ID:

Attention: Phone:Thomas Adams (856) 904-2220

Fax:Pennoni Associates, Inc.

Received Date:220 Congress Park Drive 12/15/2025 9:18 AM

Analysis Date:ste 232 12/15/2025

Collected Date:Delray Beach, FL 33445 12/10/2025

Project: AEQLA 23075 Ralph H Johnson VA 109 Be Street Charleston, SC 29401

Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E

Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

AEWLA 23075 101A

342525972-0001

None DetectedNon-fibrous (Other)90%Cellulose

Glass

10%

<1%

Brown/White

Fibrous

Heterogeneous

Room B200 - Drywall

AEWLA 23075 101B

342525972-0002

None DetectedNon-fibrous (Other)90%Cellulose

Glass

10%

<1%

Brown/White

Fibrous

Heterogeneous

Room B200 - Drywall

AEWLA 23075 101C

342525972-0003

None DetectedNon-fibrous (Other)90%Cellulose

Glass

10%

<1%

Brown/White

Fibrous

Heterogeneous

Room B200 - Drywall

AEWLA 23075 102A

342525972-0004

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Room B200 - Joint

Compound

AEWLA 23075 102B

342525972-0005

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Room B200 - Joint

Compound

AEWLA 23075 102C

342525972-0006

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Room B200 - Joint

Compound

AEWLA 23075 103A

342525972-0007

None DetectedNon-fibrous (Other)30%Cellulose

Min. Wool

40%

30%

Gray/White

Fibrous

Homogeneous

Room B200 - 2x4 Lay

In LT DOT

AEWLA 23075 103B

342525972-0008

None DetectedNon-fibrous (Other)30%Cellulose

Min. Wool

40%

30%

Gray/White

Fibrous

Homogeneous

Room B200 - 2x4 Lay

In LT DOT

AEWLA 23075 103C

342525972-0009

None DetectedNon-fibrous (Other)30%Cellulose

Min. Wool

40%

30%

Tan/White

Fibrous

Heterogeneous

Room B200 - 2x4 Lay

In LT DOT

AEWLA 23075 104A

342525972-0010

None DetectedNon-fibrous (Other)30%Cellulose

Min. Wool

40%

30%

Gray/White

Fibrous

Homogeneous

Room B200 - 2x2 Lay

In LT DOT

AEWLA 23075 104B

342525972-0011

None DetectedNon-fibrous (Other)30%Cellulose

Min. Wool

40%

30%

Gray/White

Fibrous

Homogeneous

Room B200 - 2x2 Lay

In LT DOT

AEWLA 23075 104C

342525972-0012

None DetectedNon-fibrous (Other)30%Cellulose

Min. Wool

40%

30%

Tan/White

Non-Fibrous

Homogeneous

Room B200 - 2x2 Lay

In LT DOT

AEWLA 23075 105A

342525972-0013

None DetectedNon-fibrous (Other)15%Glass85%White

Fibrous

Homogeneous

Room B200 - 2x2 Lay

In LT Rough Finish

AEWLA 23075 105B

342525972-0014

None DetectedNon-fibrous (Other)20%Glass80%White

Non-Fibrous

Homogeneous

Room B200 - 2x2 Lay

In LT Rough Finish

AEWLA 23075 105C

342525972-0015

None DetectedNon-fibrous (Other)15%Cellulose

Min. Wool

10%

75%

White

Fibrous

Heterogeneous

Room B200 - 2x2 Lay

In LT Rough Finish

AEWLA 23075 106A

342525972-0016

None DetectedNon-fibrous (Other)90%Cellulose

Glass

10%

<1%

Brown/White

Fibrous

Heterogeneous

Room B200 - 2x2 Lay

In LT Smooth Finish

Initial report from: 12/16/2025 09:27:33

Page 1 of 7ASB_PLM_0008_0002 - 2.31 Printed: 12/16/2025 9:27 AM

Tel/Fax: (407) 599-5887 / (407) 599-9063 http://www.EMSL.com / orlandolab@emsl.com

342525972EMSL Order:

Customer ID: PADB75

Customer PO:

Project ID:

Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E

Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

AEWLA 23075 106B

342525972-0017

None DetectedNon-fibrous (Other)90%Cellulose

Glass

10%

<1%

Brown/White

Fibrous

Heterogeneous

Room B200 - 2x2 Lay

In LT Smooth Finish

AEWLA 23075 106C

342525972-0018

None DetectedNon-fibrous (Other)90%Cellulose10%Brown/White

Fibrous

Heterogeneous

Room B200 - 2x2 Lay

In LT Smooth Finish

AEWLA 23075 107A

342525972-0019

None DetectedNon-fibrous (Other)100%Tan

Non-Fibrous

Homogeneous

Room B200 - Cove

Mold Mastic

AEWLA 23075 107B

342525972-0020

None DetectedNon-fibrous (Other)100%Brown/Tan

Non-Fibrous

Homogeneous

Room B200 - Cove

Mold Mastic

AEWLA 23075 107C

342525972-0021

None DetectedNon-fibrous (Other)100%Tan

Non-Fibrous

Homogeneous

Room B200 - Cove

Mold Mastic

AEWLA 23075

108A-Floor Tile

342525972-0022

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Room B200 - 12x12

Off Wht w Tan FT &

Mastic

AEWLA 23075

108A-Tan Mastic

342525972-0022A

None DetectedNon-fibrous (Other)100%Tan

Non-Fibrous

Homogeneous

Room B200 - 12x12

Off Wht w Tan FT &

Mastic

AEWLA 23075

108A-Black Mastic

342525972-0022B

2% ChrysotileNon-fibrous (Other)98%Black

Non-Fibrous

Homogeneous

Room B200 - 12x12

Off Wht w Tan FT &

Mastic

AEWLA 23075

108B-Floor Tile

342525972-0023

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Room B200 - 12x12

Off Wht w Tan FT &

Mastic

AEWLA 23075

108B-Tan Mastic

342525972-0023A

None DetectedNon-fibrous (Other)100%Tan

Non-Fibrous

Homogeneous

Room B200 - 12x12

Off Wht w Tan FT &

Mastic

AEWLA 23075

108B-Black Mastic

342525972-0023B

Positive Stop (Not Analyzed)Room B200 - 12x12

Off Wht w Tan FT &

Mastic

AEWLA 23075

108C-Floor Tile

342525972-0024

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Room B200 - 12x12

Off Wht w Tan FT &

Mastic

AEWLA 23075

108C-Tan Mastic

342525972-0024A

None DetectedNon-fibrous (Other)100%Tan

Non-Fibrous

Homogeneous

Room B200 - 12x12

Off Wht w Tan FT &

Mastic

AEWLA 23075

108C-Black Mastic

342525972-0024B

Positive Stop (Not Analyzed)Room B200 - 12x12

Off Wht w Tan FT &

Mastic

AEWLA 23075 109A

342525972-0025

None DetectedNon-fibrous (Other)100%Black

Non-Fibrous

Homogeneous

Room B200 - Raised

Floor Pedistal Mastic

AEWLA 23075 109B

342525972-0026

None DetectedNon-fibrous (Other)100%Black

Non-Fibrous

Homogeneous

Room B200 - Raised

Floor Pedistal Mastic

Page 2 of 7ASB_PLM_0008_0002 - 2.31 Printed: 12/16/2025 9:27 AM

Tel/Fax: (407) 599-5887 / (407) 599-9063 http://www.EMSL.com / orlandolab@emsl.com

342525972EMSL Order:

Customer ID: PADB75

Customer PO:

Project ID:

Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E

Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

AEWLA 23075 109C

342525972-0027

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

Room B200 - Raised

Floor Pedistal Mastic

AEWLA 23075 110A

342525972-0028

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

Room B200 - Gray Flr

Leveling Compound

AEWLA 23075 110B

342525972-0029

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

Room B200 - Gray Flr

Leveling Compound

AEWLA 23075 110C

342525972-0030

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

Room B200 - Gray Flr

Leveling Compound

AEWLA 23075 111A

342525972-0031

None DetectedNon-fibrous (Other)100%Tan

Non-Fibrous

Homogeneous

Room B200 -

Ceramic Floor Mortar

AEWLA 23075 111B

342525972-0032

None DetectedNon-fibrous (Other)100%Tan

Non-Fibrous

Homogeneous

Room B200 -

Ceramic Floor Mortar

AEWLA 23075 111C

342525972-0033

None DetectedNon-fibrous (Other)100%Tan

Non-Fibrous

Homogeneous

Room B200 -

Ceramic Floor Mortar

AEWLA 23075 112A

342525972-0034

None DetectedNon-fibrous (Other)97%Glass3%Red

Non-Fibrous

Homogeneous

Room B200 - Fire

Stop

AEWLA 23075 112B

342525972-0035

None DetectedNon-fibrous (Other)100%Red

Non-Fibrous

Homogeneous

Room B200 - Fire

Stop

AEWLA 23075 112C

342525972-0036

None DetectedNon-fibrous (Other)100%Red

Non-Fibrous

Homogeneous

Room B200 - Fire

Stop

AEWLA 23075 113A

342525972-0037

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

Room B200 - Plaster

(Wall)

AEWLA 23075 113B

342525972-0038

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

Room B200 - Plaster

(Wall)

AEWLA 23075 113C

342525972-0039

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

Room B200 - Plaster

(Wall)

AEWLA 23075 113D

342525972-0040

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

Room B200 - Plaster

(Wall)

AEWLA 23075 113E

342525972-0041

None DetectedNon-fibrous (Other)100%Gray

Non-Fibrous

Homogeneous

Room B200 - Plaster

(Wall)

AEWLA 23075 114A

342525972-0042

None DetectedNon-fibrous (Other)98%Cellulose2%Gray/Tan

Non-Fibrous

Homogeneous

Room B200 - Plaster

Patch

AEWLA 23075 114B

342525972-0043

None DetectedNon-fibrous (Other)100%Gray/Tan

Non-Fibrous

Homogeneous

Room B200 - Plaster

Patch

AEWLA 23075 114C

342525972-0044

None DetectedNon-fibrous (Other)100%Gray/Tan

Non-Fibrous

Homogeneous

Room B200 - Plaster

Patch

AEWLA 23075 115A

342525972-0045

None DetectedNon-fibrous (Other)94%Wollastonite6%White/Silver

Non-Fibrous

Homogeneous

Room B200 - End

Cap Material

Page 3 of 7ASB_PLM_0008_0002 - 2.31 Printed: 12/16/2025 9:27 AM

Tel/Fax: (407) 599-5887 / (407) 599-9063 http://www.EMSL.com / orlandolab@emsl.com

342525972EMSL Order:

Customer ID: PADB75

Customer PO:

Project ID:

Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E

Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

AEWLA 23075 115B

342525972-0046

None DetectedNon-fibrous (Other)94%Wollastonite6%Gray

Non-Fibrous

Homogeneous

Room B200 - End

Cap Material

AEWLA 23075 115C

342525972-0047

None DetectedNon-fibrous (Other)94%Wollastonite6%White

Non-Fibrous

Homogeneous

Room B200 - End

Cap Material

AEWLA 23075

117A-Tar

342525972-0048

7% ChrysotileNon-fibrous (Other)88%Fibrous (Other)5%Black

Non-Fibrous

Homogeneous

Room B200 - Tar

A/W Foil Wrap PI

AEWLA 23075

117A-Wrap

342525972-0048A

None DetectedNon-fibrous (Other)35%Cellulose

Glass

60%

5%

White/Silver

Fibrous

Homogeneous

Room B200 - Tar

A/W Foil Wrap PI

AEWLA 23075

117B-Tar

342525972-0049

Positive Stop (Not Analyzed)Room B200 - Tar

A/W Foil Wrap PI

AEWLA 23075

117B-Wrap

342525972-0049A

None DetectedNon-fibrous (Other)20%Cellulose80%White

Fibrous

Homogeneous

Room B200 - Tar

A/W Foil Wrap PI

AEWLA 23075

117C-Tar

342525972-0050

Positive Stop (Not Analyzed)Room B200 - Tar

A/W Foil Wrap PI

AEWLA 23075

117C-Wrap

342525972-0050A

None DetectedNon-fibrous (Other)20%Cellulose80%White

Fibrous

Homogeneous

Room B200 - Tar

A/W Foil Wrap PI

AEWLA 23075 118A

342525972-0051

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Room B200 - Fitting

A/W FG PI

AEWLA 23075 118B

342525972-0052

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Room B200 - Fitting

A/W FG PI

AEWLA 23075 118C

342525972-0053

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Room B200 - Fitting

A/W FG PI

AEWLA 23075

119A-Built Up Roofing

342525972-0054

None DetectedNon-fibrous (Other)80%Cellulose

Glass

10%

10%

Black

Fibrous

Heterogeneous

Roof - Roofing Field

AEWLA 23075

119A-Flashing

342525972-0054A

None DetectedNon-fibrous (Other)85%Synthetic

Glass

10%

5%

Black

Fibrous

Heterogeneous

Roof - Roofing Field

AEWLA 23075

119A-Felt

342525972-0054B

None DetectedNon-fibrous (Other)10%Cellulose90%Brown

Fibrous

Homogeneous

Roof - Roofing Field

AEWLA 23075

119A-Insulation

342525972-0054C

None DetectedNon-fibrous (Other)95%Glass5%White

Non-Fibrous

Homogeneous

Roof - Roofing Field

AEWLA 23075

119A-Foam

342525972-0054D

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Roof - Roofing Field

Page 4 of 7ASB_PLM_0008_0002 - 2.31 Printed: 12/16/2025 9:27 AM

Tel/Fax: (407) 599-5887 / (407) 599-9063 http://www.EMSL.com / orlandolab@emsl.com

342525972EMSL Order:

Customer ID: PADB75

Customer PO:

Project ID:

Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E

Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

AEWLA 23075

119B-Built Up Roofing

342525972-0055

None DetectedNon-fibrous (Other)80%Cellulose

Glass

10%

10%

Black

Fibrous

Heterogeneous

Roof - Roofing Field

AEWLA 23075

119B-Flashing

342525972-0055A

None DetectedNon-fibrous (Other)90%Synthetic

Glass

5%

5%

Black

Fibrous

Heterogeneous

Roof - Roofing Field

AEWLA 23075

119B-Felt

342525972-0055B

None DetectedNon-fibrous (Other)25%Glass75%White

Fibrous

Homogeneous

Roof - Roofing Field

AEWLA 23075

119B-Insulation

342525972-0055C

None DetectedNon-fibrous (Other)95%Glass5%White

Non-Fibrous

Homogeneous

Roof - Roofing Field

AEWLA 23075

119B-Foam

342525972-0055D

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Roof - Roofing Field

AEWLA 23075

119C-Built Up Roofing

342525972-0056

None DetectedNon-fibrous (Other)80%Cellulose

Glass

10%

10%

Black

Non-Fibrous

Homogeneous

Roof - Roofing Field

AEWLA 23075

119C-Flashing

342525972-0056A

None DetectedNon-fibrous (Other)88%Synthetic

Glass

5%

7%

Black

Non-Fibrous

Homogeneous

Roof - Roofing Field

AEWLA 23075

119C-Felt

342525972-0056B

None DetectedNon-fibrous (Other)10%Glass90%White

Non-Fibrous

Homogeneous

Roof - Roofing Field

AEWLA 23075

119C-Insulation

342525972-0056C

None DetectedNon-fibrous (Other)97%Glass3%White

Non-Fibrous

Homogeneous

Roof - Roofing Field

AEWLA 23075

119C-Foam

342525972-0056D

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Roof - Roofing Field

AEWLA 23075

120A-Flashing 1

342525972-0057

None DetectedNon-fibrous (Other)82%Cellulose

Glass

10%

8%

Black

Fibrous

Heterogeneous

Roof - Roofing

Flashing (Equip)

AEWLA 23075

120A-Flashing 2

342525972-0057A

None DetectedNon-fibrous (Other)85%Glass15%Black

Fibrous

Heterogeneous

Roof - Roofing

Flashing (Equip)

AEWLA 23075

120A-Insulation

342525972-0057B

None DetectedNon-fibrous (Other)95%Glass5%White

Non-Fibrous

Homogeneous

Roof - Roofing

Flashing (Equip)

AEWLA 23075

120B-Flashing 1

342525972-0058

None DetectedNon-fibrous (Other)82%Cellulose

Glass

10%

8%

Black

Fibrous

Heterogeneous

Roof - Roofing

Flashing (Equip)

AEWLA 23075

120B-Flashing 2

342525972-0058A

None DetectedNon-fibrous (Other)75%Cellulose

Glass

20%

5%

Black

Non-Fibrous

Homogeneous

Roof - Roofing

Flashing (Equip)

Page 5 of 7ASB_PLM_0008_0002 - 2.31 Printed: 12/16/2025 9:27 AM

Tel/Fax: (407) 599-5887 / (407) 599-9063 http://www.EMSL.com / orlandolab@emsl.com

342525972EMSL Order:

Customer ID: PADB75

Customer PO:

Project ID:

Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E

Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

AEWLA 23075

120B-Insulation

342525972-0058B

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Roof - Roofing

Flashing (Equip)

AEWLA 23075

120C-Flashing 1

342525972-0059

None DetectedNon-fibrous (Other)83%Cellulose

Glass

10%

7%

Black

Non-Fibrous

Homogeneous

Roof - Roofing

Flashing (Equip)

AEWLA 23075

120C-Flashing 2

342525972-0059A

None DetectedNon-fibrous (Other)68%Cellulose

Glass

20%

12%

Black

Non-Fibrous

Homogeneous

Roof - Roofing

Flashing (Equip)

AEWLA 23075 121A

342525972-0060

None DetectedNon-fibrous (Other)100%Silver

Non-Fibrous

Homogeneous

Roof - Equipment

Flashing Cap Caulk

AEWLA 23075 121B

342525972-0061

None DetectedNon-fibrous (Other)100%Silver

Non-Fibrous

Homogeneous

Roof - Equipment

Flashing Cap Caulk

AEWLA 23075 121C

342525972-0062

None DetectedNon-fibrous (Other)100%Silver

Non-Fibrous

Homogeneous

Roof - Equipment

Flashing Cap Caulk

AEWLA 23075 122A

342525972-0063

None DetectedNon-fibrous (Other)100%Silver/Yellow

Non-Fibrous

Homogeneous

Roof - Equipment

Flashing Cap Silver

Coating

AEWLA 23075 122B

342525972-0064

None DetectedNon-fibrous (Other)90%Cellulose10%Black/Silver/Yellow

Non-Fibrous

Homogeneous

Roof - Equipment

Flashing Cap Silver

Coating

AEWLA 23075 122C

342525972-0065

None DetectedNon-fibrous (Other)88%Cellulose12%Black/Silver

Non-Fibrous

Homogeneous

Roof - Equipment

Flashing Cap Silver

Coating

AEWLA 23075 123A

342525972-0066

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Roof - End Cap

Mastic A/W PI

AEWLA 23075 123B

342525972-0067

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Roof - End Cap

Mastic A/W PI

AEWLA 23075 123C

342525972-0068

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Roof - End Cap

Mastic A/W PI

AEWLA 23075 124A

342525972-0069

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Roof - Pitch Pocked

AEWLA 23075 124B

342525972-0070

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Roof - Pitch Pocked

AEWLA 23075 124C

342525972-0071

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Roof - Pitch Pocked

AEWLA 23075 125A

342525972-0072

None DetectedNon-fibrous (Other)90%Glass10%Brown/Black

Non-Fibrous

Homogeneous

Roof - Equip

Penetration Patch Tar

AEWLA 23075 125B

342525972-0073

None DetectedNon-fibrous (Other)80%Cellulose

Synthetic

10%

10%

Brown/Black

Non-Fibrous

Homogeneous

Roof - Equip

Penetration Patch Tar

AEWLA 23075 125C

342525972-0074

None DetectedNon-fibrous (Other)95%Glass5%Brown/Black

Non-Fibrous

Homogeneous

Roof - Equip

Penetration Patch Tar

Page 6 of 7ASB_PLM_0008_0002 - 2.31 Printed: 12/16/2025 9:27 AM

Tel/Fax: (407) 599-5887 / (407) 599-9063 http://www.EMSL.com / orlandolab@emsl.com

342525972EMSL Order:

Customer ID: PADB75

Customer PO:

Project ID:

Analyst(s)

Cassidy Delbango (20)

Jason Stuhr (55)

Laura Vera (21)

Laura Vera, Asbestos Supervisor or Other Approved Signatory

EMSL maintains liability limited to cost of analysis . Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations . The report reflects the samples as received.

Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted. The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 “Interim Method”) but augmented with procedures outlined in the 1993 (”final”) version of the method. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non- friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis . Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Estimation of uncertainty is available on request.

Samples analyzed by EMSL Analytical, Inc. Orlando, FL NVLAP Lab Code 101151-0

Page 7 of 7ASB_PLM_0008_0002 - 2.31 Printed: 12/16/2025 9:27 AM

Tel/Fax: (407) 599-5887 / (407) 599-9063 http://www.EMSL.com / orlandolab@emsl.com

EMSL Order: 342525972

Customer ID: PADB75

Customer PO:

Project ID:

Attention: Thomas Adams Phone: (856) 904-2220

Pennoni Associates, Inc. Fax:

220 Congress Park Drive Received Date: 12/15/2025 9:18 AM ste 232 Analysis Date: 12/18/2025

Delray Beach, FL 33445 Collected Date: 12/10/2025

AEQLA 23075 Ralph H Johnson VA 109 Be Street Charleston, SC 29401Project:

Test Report: Asbestos Analysis of Non-Friable Organically Bound Materials by TEM via

EPA/600/R-93/116 Section 2.5.5.1

Sample ID Description Appearance % Matrix Material % Non-Asbestos Fibers Asbestos Types

AEWLA 23075

101A

342525972-0001

Room B200 - Drywall Brown/White

Fibrous

Heterogeneous

92.7 Fibrous_Other No Asbestos Detected7.3Other

AEWLA 23075

107A

342525972-0019

Room B200 - Cove Mold

Mastic

Tan

Fibrous

Heterogeneous

100.0 None No Asbestos DetectedOther

AEWLA 23075

108A-Floor Tile

342525972-0022

Room B200 - 12x12 Off

Wht w Tan FT & Mastic

White

Fibrous

Heterogeneous

100.0 None No Asbestos DetectedOther

AEWLA 23075

109A

342525972-0025

Room B200 - Raised

Floor Pedistal Mastic

Black

Fibrous

Heterogeneous

100.0 None No Asbestos DetectedOther

AEWLA 23075

112A

342525972-0034

Room B200 - Fire Stop Red

Fibrous

Heterogeneous

100.0 None No Asbestos DetectedOther

AEWLA 23075

115A

342525972-0045

Room B200 - End Cap

Material

White/Silver

Fibrous

Heterogeneous

100.0 None No Asbestos DetectedOther

AEWLA 23075

119A-Built Up

Roofing

342525972-0054

Roof - Roofing Field Black

Fibrous

Heterogeneous

100.0 None No Asbestos DetectedOther

AEWLA 23075

119A-Flashing

342525972-0054A

Roof - Roofing Field Black

Fibrous

Heterogeneous

100.0 None No Asbestos DetectedOther

AEWLA 23075

120A-Flashing 1

342525972-0057

Roof - Roofing Flashing

(Equip)

Black

Fibrous

Heterogeneous

100.0 None No Asbestos DetectedOther

AEWLA 23075

120A-Flashing 2

342525972-0057A

Roof - Roofing Flashing

(Equip)

Black

Fibrous

Heterogeneous

100.0 None No Asbestos DetectedOther

AEWLA 23075

121A

342525972-0060

Roof - Equipment

Flashing Cap Caulk

Silver

Fibrous

Heterogeneous

100.0 None No Asbestos DetectedOther

AEWLA 23075

122A

342525972-0063

Roof - Equipment

Flashing Cap Silver

Coating

Silver/Yellow

Fibrous

Heterogeneous

100.0 None No Asbestos DetectedOther

EMSL maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received.

Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted. EMSL recommends that samples reported as none detected or <1% undergo additional analysis via PLM to avoid the possibility of false negatives.

Samples analyzed by EMSL Analytical, Inc. Orlando, FL

Initial report from: 12/18/2025 16:53:55

ASB_PLMEPANOB_0012_0002 Printed 12/18/2025 4:55:20PM Page 1 of 2

Tel/Fax: (407) 599-5887 / (407) 599-9063 http://www.EMSL.com / orlandolab@emsl.com

EMSL Order: 342525972

Customer ID: PADB75

Customer PO:

Project ID:

Attention: Thomas Adams Phone: (856) 904-2220

Pennoni Associates, Inc. Fax:

220 Congress Park Drive Received Date: 12/15/2025 9:18 AM ste 232 Analysis Date: 12/18/2025

Delray Beach, FL 33445 Collected Date: 12/10/2025

AEQLA 23075 Ralph H Johnson VA 109 Be Street Charleston, SC 29401Project:

Test Report: Asbestos Analysis of Non-Friable Organically Bound Materials by TEM via

EPA/600/R-93/116 Section 2.5.5.1

Sample ID Description Appearance % Matrix Material % Non-Asbestos Fibers Asbestos Types

AEWLA 23075

123A

342525972-0066

Roof - End Cap Mastic

A/W PI

White

Fibrous

Heterogeneous

100.0 None No Asbestos DetectedOther

AEWLA 23075

124A

342525972-0069

Roof - Pitch Pocked White

Fibrous

Heterogeneous

100.0 None No Asbestos DetectedOther

AEWLA 23075

125A

342525972-0072

Roof - Equip Penetration

Patch Tar

Brown/Black

Fibrous

Heterogeneous

100.0 None No Asbestos DetectedOther

Analyst(s)

Jason Stuhr (15) Laura Vera, Asbestos Supervisor or other approved signatory

EMSL maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received.

Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted. EMSL recommends that samples reported as none detected or <1% undergo additional analysis via PLM to avoid the possibility of false negatives.

Samples analyzed by EMSL Analytical, Inc. Orlando, FL

Initial report from: 12/18/2025 16:53:55

ASB_PLMEPANOB_0012_0002 Printed 12/18/2025 4:55:20PM Page 2 of 2

OrderID: 342525972

OrderID: 342525972

APPENDIX F

Previous Environmental Documentation

BASELINE ASBESTOS INSPECTION REPORT

LOCATION:

RALPH H. JOHNSON VA HEALTHCARE SYSTEM

CHARLESTON, SC MEDICAL CENTER

109 BEE STREET

CHARLESTON, SC 29401

CONTRACT NO.: 36C24721P1334

INSPECTION DATES:

NOVEMBER 15-17, 2021

PRIME CONTRACTOR:

CASTLE HILL ASSOCIATES, LLC

1197 FARNSWORTH RD., SUITE E

WATERVILLE, OH 43566

567-952-0212

RALPH H. JOHNSON VA HEALTHCARE SYSTEM - CHARLESTON, SC

ASBESTOS BASELINE INSPECTION REPORT

NOVEMBER 2021

TABLE OF CONTENTS

1.0 ASBESTOS INSPECTION REPORT

• Table 1 – List of Acronyms

• Table 2 - Removal Priority Protocols

2.0 APPENDICES

Appendix A – Asbestos Sampling Data

Appendix B – Asbestos Quantities, Assessments, & Abatement Cost Estimates

Appendix C – Photographs of Asbestos Materials

Appendix D – Asbestos Material Locations and Sample Location Drawings

Appendix E – Asbestos Laboratory Reports

Appendix F - Inspector Certifications

Appendix G - Lab Certifications

Appendix H – O&M Plan (Operations & Maintenance)

1.0 PROJECT OVERVIEW & SUMMARY OF WORK

From November 15-17, 2021, Castle Hill Associates, LLC was contracted by the US Department of Veterans Affairs (VA) to perform a baseline asbestos inspection of the Ralph H. Johnson VA Healthcare System, Charleston, SC Medical Center. The survey was performed as part of the VA Contract 36C24721P1334. The Performance Work Statement (PWS) issued by the VA defined the scope of work for the asbestos survey.

The inspection was conducted by Brett Brumbaugh and Sam Ansara. The South Carolina licensed asbestos inspector and project manager was Mr. Brumbaugh who has been conducting asbestos surveys, sampling, and consulting work since 1987. He is licensed to conduct asbestos surveys in 29 states. Sam Ansara has been conducting asbestos surveys, sampling, and consulting work since 1988.

There was a previous asbestos baseline reinspection and numerous reinspections conducted at the facility. In addition, many bulk sampling projects have been completed in the facility prior to minor and major renovation project. All of this data was reviewed and incorporated into this baseline inspection report. There were no limitations or exceptions to the PWS for the surveys conducted.

All accessible functional areas in the building were surveyed, with the exception of the inaccessible wall and ceiling chases which would require demolition of building components to access the suspect ACM. These areas would need to be accessed as part of future NESHAP surveys prior to renovation or demolition.

Previous sampling results and inventory spreadsheets from the previous survey and additional asbestos information provided by the current staff of the VAMC were used in this report. All additional samples that were collected during this inspection are included in this report.

2.0 FEDERAL AND STATE ASBESTOS REGULATIONS

2.1 Federal Regulations

The United States Environmental Protection Agency (EPA), the Occupational Safety and Health Administration (OSHA), and delegated states are responsible for regulating environmental exposure and protecting workers from asbestos exposure. OSHA is responsible for the health and safety of workers who may be exposed to asbestos in connection with their jobs (Occupational Exposure to Asbestos; Title 29, Code of Federal Regulations (CFR) Parts 1910.1001 and 1926.1101). The EPA and state regulators are responsible for developing and enforcing regulations necessary to protect the general public from exposure to airborne contaminants that are known to be hazardous to human health.

In 1979, EPA began an asbestos technical assistance program for building owners, environmental groups, contractors, and industry. In May 1982, EPA issued the first regulation intended to control asbestos in schools under the authority of the Toxic Substances Control Act (TSCA); this regulation is known as the Asbestos-in-Schools Rule.

Two EPA regulations govern asbestos: the Asbestos Hazard Emergency Response Act (AHERA) and the National Emission Standards for Hazardous Air Pollutants (NESHAP).

AHERA

In 1986, Congress enacted AHERA (Title 40, CFR Part 763) which mandated a regulatory program to address the asbestos hazards in schools. A part of AHERA deals with the mandatory training and accreditation of persons who perform certain types of asbestos-related work in schools.

Subsequently, in 1990 Congress amended AHERA to extend some of the training and accreditation requirements to persons performing such work in public and commercial buildings.

AHERA requires inspections of school buildings to determine the conditions of ACBM and preparation of management plans which recommend the best way to reduce the asbestos hazards. The United States Veterans Administration (VA) has adopted the requirements of AHERA by Executive Order for asbestos activities conducted at all VA facilities. In addition, the AHERA response methods mandated include removal, encapsulation, enclosure, repair, and operations and maintenance to protect human health and the environment from ACBM.

NESHAP

The Clean Air Act (CAA) of 1970 required EPA to develop and enforce regulations to protect the general public from exposure to airborne contaminants that are known to be hazardous to human health; therefore, EPA promulgated NESHAP (Title 40, CFR Part 61) on April 6, 1973.

NESHAP is intended to minimize the release of asbestos fibers during certain activities (i.e., renovations, demolition, and installations). It specifies work practices to be followed during renovations of buildings (except apartment buildings that have no more than four dwelling units) which contain a specific amount of friable asbestos. NESHAP requires that buildings be inspected for ACBM prior to renovation/demolition projects.

NESHAP also requires owners and operators subject to the asbestos rules to notify delegated state and local agencies and/or the regional EPA offices before demolition or renovation activities begin. In addition, NESHAP requires the removal of all friable ACBM prior to demolition.

OSHA

OSHA began regulating workplace asbestos exposure in 1970, adopting a permissible exposure limit (PEL) to regulate worker exposure. The original asbestos standard has been revised several times to better protect workers. On August 10, 1994, OSHA issued a revised final standard regulating asbestos exposure in all industries. The newly revised standard for the construction industry lowers the PEL. The revised standard also establishes a new classification system for asbestos construction work, which clearly spells out mandatory work practices to follow to reduce worker exposures (see Occupational Exposure to Asbestos, Title 29, CFR 1926.1101).

2.2 State and Local Regulations

South Carolina state regulations are similar to the Federal regulations, with the exception of the requirement to analyze bulk samples by TEM for all non-organically bound samples (NOB). South Carolina asbestos regulations also include requirements for licensing and certification of personnel who will perform asbestos-related work activities. All personnel who engage in asbestos-related activities must comply with the state licensing/certification requirements as well as with all Federal requirements.

3.0 SAMPLE ANALYTICAL METHODS

3.1 Asbestos Sampling Protocol

EPA and OSHA define an ACBM as any material which contains greater than 1 percent asbestos.

The ACBM inspection and bulk sampling were performed in accordance with the methods outlined in the EPA guidance document titled Guidance for Controlling Asbestos-Containing Materials in Buildings (Document No. 560/5-85/024). In addition, bulk sampling of asbestos was performed in accordance with 40 CFR Part 763, AHERA requirements for number of samples and types of ACBM to be sampled. According to these requirements, materials are classified as either surfacing (e.g., decorative plaster, spray-applied fireproofing), thermal system insulation (e.g., pipe insulation, pipe fitting insulation, boiler insulation), or miscellaneous materials (e.g., floor tile, ceiling tile, plaster, wallboard, mastics).

The number of samples collected from each material varies based on the classification of the material and increases as the potential for a non-uniform mixture of asbestos in the material increases.

Typically, regulations require a minimum number of samples to be collected from the different classifications of suspect ACBM.

A total of 235 bulk samples were collected as part of this survey and analyzed by PLM. An additional 110 samples were analyzed by TEM via gravimetric reduction for those samples which were non-friable, organically bound (NOB) in accordance with South Carolina asbestos regulations. All samples were analyzed by EMSL Analytical laboratory in Cinnaminson, NJ. EMSL is accredited by the NIST, NVLAP program (National Institute of Standards and Technology, National Voluntary Laboratory Accreditation Program) and also an American Industrial Hygiene Association (AIHA) accredited laboratory.

4.0 SUMMARY OF INSPECTION FINDINGS

4.1 Asbestos-Containing Building Materials

The tables below summarize the asbestos containing materials, locations, quantities of materials.

Homog.

Area Asbestos Material Locations

H-01 Duct Sealant - Red/reddish-brown sealant applied directly to the metal seams and joints of HVAC ducts above ceilings

Throughout Original Blocks (A,B, & C)

H-02B Duct Insulation Mastic - Black mastic applied to foil faced fiberglass HVAC duct insulation Crawlspace

H-09 Pipe fitting mud insulation-cloth wrapped hand shaped insulation "mud" applied over fiberglass insulation at fittings on heating water piping

D134

H-12 Pipe fitting mud insulation-cloth wrapped hand shaped insulation "mud" applied over fiberglass insulation at fittings on roof drain piping

D134

H-14 Pipe insulation-cloth wrapped calcium silicate type, pre-formed dense insulation installed in short sections at hangers D134

H-15 Floor Tile-9"x9" floor tile (multiple colors) and associated ACM mastic

Corridor 2B9, B223, B240, B580, B554

H-16 Floor Tile-9"x9" floor tile (multiple colors) and associated non- ACM mastic C123A, C124, A568A

H-20 Pipe Insulation- cloth wrapped, calcium silicate type, pre-formed dense insulation installed in short sections at domestic water pipe hangers

C105

H-21 Floor mastic-black mastic found below yellow mastic at the stairway landings Stairs 1, 2, 3, 4, 5, 6

H-25 Floor tile-12"x12" tan and white marbled floor tile adhered by tan mastic over grey/tan, thin brittle tile (likely 9") and black mastic

B506, B510, B514- 517, B526, B506B, Corridor 5B5 Fire

H-27 Floor mastic-black mastic below gray leveling compound below carpet B559, B570, B571

H-28 Sink undercoat-gray, white or lavender colored coating applied to the bottom of stainless-steel sinks

Original stainless steel sink throughout original blocks

H-29 Pipe insulation mastic-black mastic applied over fiberglass insulation on pipes above ceiling on Kraft-faced piping

Throughout Original Blocks (A,B, & C)

H-32 Floor tile and mastic-12"x12" vinyl composition floor tile and tan mastic installed over white floor tile and black mastic

C322, C416, AHU11

H-36A

Floor tile and mastic-12"x12" white floor tile with small black dots and tan mastic installed over white tile and black mastic

Corridor 3A3, Corridor 3A9, A533

H-36B Floor tile and mastic-12"x12" white vinyl composition floor tile and black mastic below carpet A357

H-37A

Floor tile and mastic-12"x12" white vinyl composition floor tile and black mastic A358

H-61 Pipe insulation mastic-white mastic on fiberglass insulation at fittings of domestic water piping Throughout Original A, B, C Blocks

H-63 Metal 2-hour Fire Doors Throughout

H-64

Round cementitious "transite" ACM pipe

2nd-5th Floors B wing (Extends between levels & above ceiling on 5)

H-65

Pipe fitting mud insulation- hand shaped insulation "mud" applied between cloth wrapped and fiberglass insulation on Kathbar system

Penthouse/Roof (Extends between levels)

H-66

Gray and black mastic- applied to short sections on non-ACM foam glass insulation at hangers along chilled water piping

Crawlspace

H-67

Multi-colored layered mastics-applied to open mesh wrapped, foil-kraft, rigid cellular foam insulation on water piping

H-68

Black mastic-below white non-ACM mastic applied to sections of foam glass at hangers insulated with kraft faced fiberglass

H-69 Hard gray and black mastic/coating- applied to non-

ACM black, flexible, cellular rubber foam insulation Crawlspace

H-70 White mastic-applied to fiberglass insulation Crawlspace

H-71 Off-white mastic-applied over fiberglass insulation on HVAC piping

Corridor2BB1, throughout Block BB

H-72 Off-white/gray mastic- applied to fiberglass duct insulation Roof

H-73 White mastic-applied to fiberglass on roof drain insulation Penthouse (Extends between levels)

H-74 Brownish-black mastics/sealants- applied to non- ACM insulation on induction unit piping (some covered by newer white ACM mastic)

Throughout Original Blocks (A, B, & C)

H-75 White mastic-applied to non-ACM insulation on induction unit piping

Throughout Original Blocks (A, B, & C)

H-84 Black mastic beneath 12' blue Tile with mastic and underlying tile

A317-326, A331, A335- 342, A369

6.0 EXPLANATION OF ASSESSMENT OF ASBESTOS CONTAINING MATERIALS

The inspection protocol is based on the Asbestos Hazard Emergency Response Act (AHERA), Environmental Protection Act’s (EPA’s) revised Asbestos Model Accreditation Plan (MAP) mandated by the Asbestos School Hazard Abatement Reauthorization Act (ASHARA), and the Department of Veterans Affairs (VA) Directive 7700. The tabular listing included in this report contains Building Number, Floor, Room Number, Material Category (i.e., TSI, SM or MM), Material Type, quantity, a numerical priority ranking, condition, potential for damage, potential for human exposure, drawing number, hazard ranking, recommended response action and associated cost estimate for implementation of those response actions.

The material assessment categories of the ACM identified in the building is formatted in the following order for the summary tables enclosed in this report:

• Material Category - Surfacing Material (SUR); Thermal System Insulation (TSI); Miscellaneous (MM)

• Material Type - Friable (F); Non-Fable (NF)

• Condition of Material - Good; Fair; Poor

• Potential for Damage - Low; Medium; High

• Physical Assessment - Low; Medium; High

• Recommended Response Action - 1 through 7

Material category is the type of material such as surfacing material (SUR), thermal system insulation (TSI), and miscellaneous (MM)

• Surfacing Material (SUR) - Surfacing ACM means surfacing material that is ACM. Surfacing material means material in a school building that is sprayed-on, troweled-on, or otherwise applied to surfaces, such as acoustical plaster on ceilings and fireproofing materials on structural members, or other materials on surfaces for acoustical, fireproofing, or other purposes.

• Thermal System Insulation (TSI) - Thermal system insulation ACM means thermal system insulation that is ACM. Thermal system insulation means material in a school building applied to pipes, fittings, boilers, breeching, tanks, ducts, or other interior structural components to prevent heat loss or gain, or water condensation, or for other purposes.

• Miscellaneous (MM) - Miscellaneous ACM means miscellaneous material that is ACM Miscellaneous material means interior building material on structural components, structural members or fixtures, such as floor and ceiling tiles, and does not include surfacing material or thermal system insulation. Material type refers to the hardness of a material to be crumbled, pulverized, or reduced to powder by hand pressure as friable (F), and includes previously non-friable (NF) material after such previously non-friable material becomes damaged to the extent that when dry it may be crumbled, pulverized, or reduced to powder by hand pressure.

Seven Categories define in the AHERA regulation one of which must be assigned to each friable surfacing and miscellaneous ACBM and each asbestos-containing TSI during the inspection/re-inspection.

1. Damaged or significantly damaged TSI ACBM - Damaged or significantly damaged thermal system insulation ACM means thermal system insulation ACM on pipes, boilers, tanks, ducts, and other thermal system insulation equipment where the insulation has lost its structural integrity, or its covering, in whole or in part, is crushed, water-stained, gouged, punctured, missing, or not intact such that it is not able to contain fibers. Damage may be further illustrated by occasional punctures, gouges or other signs of physical injury to ACM; occasional water damage on the protective coverings/jackets; or exposed ACM ends or joints. Asbestos debris originating from the ACBM in question may also indicate damage.

2. Damaged friable surfacing ACBM - Damaged friable surfacing ACM means friable surfacing ACM which has deteriorated or sustained physical injury such that the internal structure (cohesion) of the material is inadequate or which has delaminated such that its bond to the substrate (adhesion) is inadequate, or which, for any other reason, lacks fiber cohesion or adhesion qualities.

This is the start of the file's text. The full file is on GovTribe.