This document is an Invitation for Bid (IFB) attachment containing architectural construction drawings and project specifications for the EHRM Data Center Upgrades at the Ralph H Johnson VA Medical Center in Charleston, South Carolina (Project 534-24-706). The renovation scope encompasses a phased upgrade of data center room B200 located on the second floor of Building 1, requiring extensive demolition, mechanical/electrical/plumbing modifications, telecommunications infrastructure installation, fire protection system upgrades, and structural work.
The project is organized into six construction phases designed to maintain facility operations throughout the upgrade. Key deliverables include installation of new CRAC (Computer Room Air Conditioning) units, UPS systems with battery cabinets, server racks with static dissipative flooring, fire suppression and clean agent systems, cable tray and power distribution infrastructure, and associated mechanical ductwork and electrical panels. The work requires compliance with strict infection control risk assessment (ICRA) protocols, including dust barriers, negative air pressure maintenance, and specialized cleaning procedures appropriate for a healthcare facility. Critical design elements include one-hour rated fire barriers, firestopping at all penetrations, temporary cooling systems rated at 51.8 KW for general cooling and 10.5 KW for UPS support, and comprehensive coordination across mechanical, electrical, telecommunications, and fire protection disciplines. The Architect/Engineer of Record is AE Works, LTD, with structural engineering by Pennoni Associates and fire protection engineering by Koffel Engineers. All work must conform to the 2021 International Building Code, NFPA standards, VA Fire Protection Design Manual, and applicable federal, state, and local regulations.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
AE Works, LTD.
418 Beaver Street
Sewickley, PA 15143
Phone: 412-287-7333 www.aeworks.comAE WORKS®1900 Market Street, Suite 300 Philadelphia, PA 19103
215.222.3000
8815 Centre Park Drive, Suite 200 Philadelphia, MD 21045
410.750.2246
A u to d e s k D o c s /V
C H
A -0
C h a rl e s to n E
H R
M D a ta
C e n te r/ V
C H
A -0
C h a rl e s to n E
H R
M D a ta
C e n te r.
rv t
/4 /2
:4
:2
P M
G001
COVER SHEET EHRM DATA CENTER UPGRADES
FOR JSA-FDS - CHARLESTON, SC
109 BEE ST. CHARLESTON SC 29401
534-24-706
02.06.26 LP TW
BID DOCUMENTS
EHRM Data Center Upgrades for JSA-FDS Charleston, SC
PROJECT NO. 534-24-706
RALPH H JOHNSON VA MEDICAL CENTER
109 BEE STREET
CHARLESTON, SC 29401
PROJECT DIRECTORY
OWNER:
U.S. DEPARTMENT OF
VETERANS AFFAIRS
RALPH H JOHNSON VA
MEDICAL CENTER
109 BEE STREET
CHARLESTON, SC 29401
(843) 304-8910
ARCHITECT/ENGINEER:
AE WORKS, LTD
418 BEAVER STREET
SEWICKLEY, PA 15143
(412) 287-7333
FIRE PROTECTION ENGINEER:
KOFFEL ENGINEERS
8815 CENTRE PARK DRIVE
SUITE 200
COLUMBIA, MD 21045
VICINITY MAP
SITE
LOCATION MAP
GENERAL
G001 COVER SHEET
G101 PHASING PLANS
G102 PHASING PLANS
G121 ICRA AND ABATEMENT
LS101 LIFE SAFETY PLAN - DATA CENTER
S000 GENERAL NOTES
S001 DESIGN CRITERIA
S400 SECTIONS AND DETAILS
ARCHITECTURAL
A001 ABBREVIATIONS, NOTES AND SYMBOLS
A100 OVERALL PLAN
AD101 FLOOR AND REFLECTED CEILING DEMOLITION PLANS
A101 FLOOR AND CEILING PLANS
A121 ROOF PLAN
AI101 FINISH PLAN
A601 DOOR AND PARTITION SCHEDULE AND DETAILS
FIRE PROTECTION
FA001 FIRE ALARM COVER SHEET
FA101 PARTIAL SECOND FLOOR FIRE ALARM DEMO PLAN - DATA CENTER
FA201 PARTIAL SECOND FLOOR FIRE ALARM PLAN - DATA CENTER
FA501 FIRE ALARM DETAIL SHEET
FS001 FIRE SUPPRESSION COVER SHEET
FS100 PARTIAL SECOND FLOOR FIRE SUPPRESSION EXISTING PLAN - B SECTION
FS101 PARTIAL SECOND FLOOR FIRE SUPPRESSION DEMO PLAN - DATA CENTER
FS201 PARTIAL SECOND FLOOR FIRE SUPPRESSION PLAN - DATA CENTER
FS501 FIRE SUPPRESSION DETAIL SHEET
SITE
CONTACT: JOHN HOFFMAN, PECONTACT: JONATHAN STECKO CONTACT: MICHAEL CARROLL, PE
MECHANICAL
M001 MECHANICAL SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES
MD101 DATA CENTER HVAC - DEMOLITION PLAN
M100 OVERALL MECHANICAL PLAN
M101 DATA CENTER HVAC PLAN
M102 DATA CENTER SECTIONS
M501 HVAC DETAILS
M701 HVAC SCHEDULES
M801 CONTROL DIAGRAMS
ELECTRICAL
E001 ELECTRICAL SYMBOLS AND ABBREVIATIONS
E101 OVERALL ELECTRICAL PLAN
ED401 DATA CENTER LIGHTING DEMOLITION PLAN
ED402 DATA CENTER ELECTRICAL DEMOLITION PLANS
E401 DATA CENTER LIGHTING PLAN
E402 DATA CENTER POWER PLAN
E403 ENLARGED ELECTRICAL ROOM PLANS
E404 ENLARGED GROUNDING PLANS
E501 ELECTRICAL DETAILS
E502 ELECTRICAL DETAILS
E601 ELECTRICAL SCHEDULES
E602 PANEL SCHEDULES
E701 DATA CENTER PARTIAL ONE-LINE DIAGRAM
TELECOM
TN001 COMMUNICATIONS SYMBOLS AND GENERAL INFORMATION
TN100 COMMUNICATIONS FLOOR PLAN - SECOND FLOOR
TN201 COMMUNICATIONS CABINET ELEVATIONS
TN401 DATA CENTER ENLARGED PLAN
TN501 COMMUNICATIONS OUTLET DETAILS AND SCHEDULES
TN502 COMMUNICATIONS PATHWAY DETAILS
TN503 COMMUNICATIONS BONDING DETAILS
TN504 ELECTRONIC SAFETY AND SECURITY DETAILS AND SCHEDULES
STRUCTURAL AND ENVIRONMENTAL ENGINEERS:
PENNONI
1900 MARKET STREET
SUITE 300
PHILADELPHIA, PA 19103
CONTACT: RICHARD ROBERTS, PE
STRUCTURAL
# Revisions Date
SHEET INDEX
WS AA LM LO O
H F
T
02-06-26
DNDN
G
COR2BD1
DIAG IMG CORR
ELVLOB2
COMMON ELEV
LOBBY
B206F
DIAG IMG RM #1
B206E
DIAG IMG BONE
DENSITOMETER
(E) CRAC-3
(E) CRAC-1
(E) CRAC-2
(E) UPS-1
(E) UPS-2
(E) BATTERY CABINETS
CABINET
TO REMAIN
(E) CABINETS TO REMAIN (E) CABINETS TO REMAIN
ICRA BARRIER
CONSTRUCTION
BARRIER, TYP.
B200
DATA CENTER
(X) DISCONNECT SWITCH
2L13
2L12
2L11
CSI
G
COR2BD1
DIAG IMG CORR
ELVLOB2
COMMON ELEV
LOBBY
B206F
DIAG IMG RM #1
B206E
DIAG IMG BONE
DENSITOMETER
(E) BATTERY CABINETS
(X) CRAC-2
CONSTRUCTION
BARRIER, TYP.
CONSTRUCTION
BARRIER, TYP.
(E) UPS-1
(E) UPS-2
CONSTRUCTION
BARRIER, TYP.
(X) CRAC-1
B200
DATA CENTER
(E) CRAC-3
TEMPORARY COOLING AREATEMPORARY COOLING AREA
ICRA BARRIER
2L13
2L12
2L11
CSI
G
B206F
DIAG IMG RM #1
B206E
DIAG IMG BONE
DENSITOMETER
COR2BD1
DIAG IMG CORR
ELVLOB2
COMMON ELEV
LOBBY
DEMO CRAC-3
COORDINATE
REMOVAL OF THIS
DOOR WITH VA TO
LIMIT ACCESS TO
B206F.
(X) UPS-1
(X) UPS-2
(X) BATTERY CABINETS
CONSTRUCTION
BARRIER, TYP.
CONSTRUCTION
BARRIER, TYP.
DEMO RACKS
CONSTRUCTION
BARRIER, TYP.
B200
DATA CENTER
TEMPORARY COOLING AREA
TEMPORARY COOLING AREA
PDU-2
UPS-2
MBC-2
BATT
CAB 2
MTS-UPS-2
LP-DC
D-LP-DC
2L13
2L12
2L11
CSI
GB-DC
ICRA BARRIER
G
B206F
DIAG IMG RM #1
B206E
DIAG IMG BONE
DENSITOMETER
COR2BD1
DIAG IMG CORR
ELVLOB2
COMMON ELEV
LOBBY
(E) CRAC-3
(E) CRAC-2
(E) UPS-1
(E) UPS-2
(E) BATTERY CABINETS
LEGACY CABINETS
(E) CRAC-1
CONSTRUCTION
BARRIER, TYP.
B200
DATA CENTER
ICRA BARRIER
2L13
2L12
2L11
CSI
G
B206F
DIAG IMG RM #1
B206E
DIAG IMG BONE
DENSITOMETER
COR2BD1
DIAG IMG CORR
ELVLOB2
COMMON ELEV
LOBBY
(E) CRAC-3
NEW CABINETS
(E) UPS-1
(E) UPS-2
(E) BATTERY CABINETS
CONSTRUCTION
BARRIER, TYP.
B200
DATA CENTER
CONSTRUCTION
BARRIER, TYP.
TEMPORARY COOLING AREA
TEMPORARY COOLING AREA
PDU-2
UPS-2
MBC-2
BATT
CAB 2
ICRA BARRIER
MTS-UPS-2
LP-DC
D-LP-DC
2L13
2L12
2L11
CSI
GB-DC
G
B206F
DIAG IMG RM #1
B206E
DIAG IMG BONE
DENSITOMETER
COR2BD1
DIAG IMG CORR
ELVLOB2
COMMON ELEV
LOBBY
NEW CABINETS
CRAC-2
CONSTRUCTION
BARRIER, TYP.
B200
DATA CENTER
TEMPORARY COOLING AREA
TEMPORARY COOLING AREA
TEMPORARY COOLING AREA
PDU-2
UPS-2
MBC-2
BATT
CAB 2
ICRA BARRIER
MTS-UPS-2
LP-DC
D-LP-DC
2L13
2L12
2L11
CSI
GB-DC
PHASE ONE - DEMO NOTES
ARCHITECTURE
- REMOVE ACCESS FLOORING AS INDICATED
- REMOVE CEILING CORRESPONDING TO THE
AMOUNT OF FLOORING REMOVED
- REMOVE WALL SHELVING
- INSTALL CONSTRUCTION AND ICRA BARRIERS AS
INDICATED.
ELECTRICAL
- REMOVE UNSUED DISCONNECT SWITCH
MECHANICAL
- REMOVE UNNECESSARY SYSTEMS
TELECOMMUNICATIONS
- REMOVE UNUSED LEGACY CABLING, EQUIPMENT
CABINETS, AND INFRASTRUCTURE.
- VA TO RELOCATE/CONSOLIDATE EQUIPMENT IN
REMAINING LEGACY CABINETS TO
ACCOMMODATE NEW CABINETS AND
ENTRANCE DOOR.
- CONTRACTOR TO TEMPORARILY SUPPORT
EXISTING TO REMAIN EQUIPMENT CABINET TO
ALLOW FOR RAISED FLOOR REMOVAL. RESET
CABINET ONCE FINISHED FLOORING IS
COMPLETE.
FIRE PROTECTION
- REMOVE ALL HEADS WHEN CEILING IS REMOVED
PHASE ONE - NEW WORK NOTES
ARCHITECTURE
- NO NEW WORK
ELECTRICAL
- NO NEW WORK
MECHANICAL
- NO NEW WORK
TELECOMMUNICATIONS
- NO NEW WORK
FIRE PROTECTION
- NO NEW WORK
PHASE TWO - DEMO NOTES
ARCHITECTURE
- REMOVE ACCESS FLOORING AS INDICATED.
- INSTALL CONSTRUCTION BARRIERS AS
INDICATED.
- REMOVE CEILING CORRESPONDING TO THE
AMOUNT OF FLOORING REMOVED
ELECTRICAL
- NO WORK
MECHANICAL
- REMOVE E-CRAC-01 - EVAP
- REMOVE E-CRAC-01 - COND
- REMOVE E-CRAC-02 - EVAP
- REMOVE E-CRAC-02 - COND
- UTILIZE TEMP COOL UNITS
TELECOMMUNICATIONS
- VA TO RELOCATE/CONSOLIDATE EQUIPMENT
FROM REMAINING LEGACY CABINETS TO NEW
PHASE TWO CABINETS TO ACCOMMODATE NEW
CABINETS.
FIRE PROTECTION
- NO WORK
PHASE TWO - NEW WORK NOTES
ARCHITECTURE
- INSTALL CONSTRUCTION BARRIERS AS
INDICATED.
MECHANICAL
- PREPARE FOR CRAC-2 INSTALL.
- UTILIZE TEMP COOL UNITS.
TELECOMMUNICATIONS
- INSTALL NEW EQUIPMENT CABINETS, CABLE
TRAY, POWER DISTRIBUTION, AND BACKBONE
CABLING IN NOTED LOCATIONS.
- INSTALL TEMPORARY FIBER OPTIC CABLE
CHANNEL BETWEEN EXISTING AND NEW CORE
NETWORK EQUIPMENT. COORDINATE LOCATIONS
WITH LOCAL CLIENT REPRESENTATIVES.
- VA TO POPULATE NEW EQUIPMENT CABINETS.
FIRE PROTECTION
- NO WORK
PHASE THREE - DEMO NOTES
ARCHITECTURE
- DEMO DOOR INTO ROOM B206F.
- REMOVE ACCESS FLOORING AS INDICATED.
- INSTALL CONSTRUCTION BARRIERS AS
INDICATED.
- REMOVE CEILING CORRESPONDING TO THE
AMOUNT OF FLOORING REMOVED.
ELECTRICAL
- REMOVE EXISTING UPS-1 AND UPS-2
- REMOVE MTS-UPS-B200
- REMOVE EXISTING BATTERY CABINETS
MECHANICAL
- REMOVE E-CRAC-03 - EVAP.
- REMOVE E-CRAC-03 - COND.
- UTILIZE TEMP COOL UNITS.
TELECOMMUNICATIONS
- VA TO RELOCATE/CONSOLIDATE EQUIPMENT
FROM NOTED LEGACY CABINETS TO NEW
CABINETS.
FIRE PROTECTION
- NO WORK
PHASE THREE - NEW WORK NOTES
ARCHITECTURE
- INFILL WALL OPENING BETWEEN DATA CENTER
AND ROOM B206F
ELECTRICAL
- PROVIDE POWER TO NEW CRAC-2 (EVAP AND
COND).
- INSTALL TEMPORARY FEEDS FROM PDU-2 TO
PANELS CSI AND 2L13.
MECHANICAL
- INSTALL NEW CRAC-2 - EVAP.
- INSTALL NEW CRAC-2 - COND.
- UTILIZE TEMP COOL UNITS.
TELECOMMUNICATIONS
- INSTALL NEW EQUIPMENT CABINETS, CABLE
TRAY, POWER DISTRIBUTION, AND BACKBONE
CABLING IN NOTED LOCATIONS.
- VA TO POPULATE NEW EQUIPMENT CABINETS.
FIRE PROTECTION
- NO WORK
ELECTRICAL
- INSTALL TRANSFORMER T-LP-DC IN ROOM H200.
- INSTALL MTS-UPS-2
- INSTALL UPS-2, PDU-2, MBC-2
- INSTALL PANEL LP-DC
- INSTALL BATT CAB 2
- INSTALL ROW 1 BUS B
- INSTALL ROW 2 BUS B
- INSTALL 24" GROUND BAR (GB-DC)
TEMPORARY COOLING:
- TEMP COOL: 51.8 KW (MIDDLE) 16 TON SENSIBLE
- TEMP COOL FOR UPS 10.5 KW (LEFT) 5 TON SENSIBLE.
- EXHAUST HEAT DISSIPATION AND DUST CONTROL NEED NEW
TEMPORARY PENETRATIONS IN DATA CENTER AND ROOF.
TEMPORARY COOLING:
- TEMP COOL: 51.8 KW (MIDDLE) 16 TON SENSIBLE
- TEMP COOL FOR UPS 10.5 KW (LEFT) 5 TON SENSIBLE.
- EXHAUST HEAT DISSIPATION AND DUST CONTROL NEED NEW
TEMPORARY PENETRATIONS IN DATA CENTER AND ROOF.
TEMPORARY COOLING:
- TEMP COOL: 51.8 KW (MIDDLE) 16 TON SENSIBLE
- TEMP COOL FOR UPS 10.5 KW (LEFT) 5 TON SENSIBLE.
- EXHAUST HEAT DISSIPATION AND DUST CONTROL NEED NEW
TEMPORARY PENETRATIONS IN DATA CENTER AND ROOF.
TEMPORARY COOLING:
- TEMP COOL: 51.8 KW (MIDDLE) 16 TON SENSIBLE
- TEMP COOL FOR UPS 10.5 KW (LEFT) 5 TON SENSIBLE.
- EXHAUST HEAT DISSIPATION AND DUST CONTROL NEED NEW
TEMPORARY PENETRATIONS IN DATA CENTER AND ROOF.
ICRA BARRIER
SEE SHEET G121
CONSTRUCTION BARRIER. INSTALL SLAB TO
DECK DUST BARRIER. SIMILAR TO SWIFTWALL
PRO OR STARC LITEBARRIER.
ICRA BARRIER
SEE SHEET G121
CONSTRUCTION BARRIER. INSTALL SLAB TO
DECK DUST BARRIER. SIMILAR TO SWIFTWALL
PRO OR STARC LITEBARRIER.
ICRA BARRIER
SEE SHEET G121
CONSTRUCTION BARRIER. INSTALL SLAB TO
DECK DUST BARRIER. SIMILAR TO SWIFTWALL
PRO OR STARC LITEBARRIER.
ICRA BARRIER
SEE SHEET G121
CONSTRUCTION BARRIER. INSTALL SLAB TO
DECK DUST BARRIER. SIMILAR TO SWIFTWALL
PRO OR STARC LITEBARRIER.
ICRA BARRIER
SEE SHEET G121
CONSTRUCTION BARRIER. INSTALL SLAB TO
DECK DUST BARRIER. SIMILAR TO SWIFTWALL
PRO OR STARC LITEBARRIER.
ICRA BARRIER
SEE SHEET G121
CONSTRUCTION BARRIER. INSTALL SLAB TO
DECK DUST BARRIER. SIMILAR TO SWIFTWALL
PRO OR STARC LITEBARRIER.
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
AE Works, LTD.
418 Beaver Street
Sewickley, PA 15143
Phone: 412-287-7333 www.aeworks.comAE WORKS®1900 Market Street, Suite 300 Philadelphia, PA 19103
215.222.3000
8815 Centre Park Drive, Suite 200 Philadelphia, MD 21045
410.750.2246
A u to d e s k D o c s /V
C H
A -0
C h a rl e s to n E
H R
M D a ta
C e n te r/ V
C H
A -0
C h a rl e s to n E
H R
M D a ta
C e n te r.
rv t
/4 /2
:4
:3
P M
G101
PHASING PLANS EHRM DATA CENTER UPGRADES
FOR JSA-FDS - CHARLESTON, SC
109 BEE ST. CHARLESTON SC 29401
534-24-706
02.06.26 LP TW
BID DOCUMENTS
1/4" = 1'-0"
PARTIAL SECOND FLOOR PLAN - DEMO PHASE ONE
1/4" = 1'-0"
PARTIAL SECOND FLOOR PLAN - DEMO PHASE TWO
1/4" = 1'-0"
PARTIAL SECOND FLOOR PLAN - DEMO PHASE THREE
1/4" = 1'-0"
PARTIAL SECOND FLOOR PLAN - PHASE ONE
1/4" = 1'-0"
PARTIAL SECOND FLOOR PLAN - PHASE TWO
1/4" = 1'-0"
PARTIAL SECOND FLOOR PLAN - PHASE THREE
# Revisions Date
WS AA LM LO O
H F
G
CRAC- 2
B206F
DIAG IMG RM #1
B206E
DIAG IMG BONE
DENSITOMETER
CONSTRUCTION
BARRIER, TYP.
ICRA BARRIER
ICRA BARRIER
CONSTRUCTION
BARRIER, TYP.
B200
DATA CENTER
TEMPORARY COOLING AREA
TEMPORARY COOLING AREA
PDU-2
UPS-2
MBC-2
BATT
CAB 2
BATT
CAB 1 UPS-1 PDU-1
MBC-1
MTS-UPS-1 MTS-UPS-2
LP-DC
D-LP-DC
2L13
2L12
2L11
CSI
GB-DC
G
CRAC- 2
CRAC- 1
B206F
DIAG IMG RM #1
B206E
DIAG IMG BONE
DENSITOMETER
B200
DATA CENTER
TEMPORARY COOLING AREA
PDU-2
UPS-2
MBC-2
BATT
CAB 2
BATT
CAB 1 UPS-1 PDU-1
MBC-1
MTS-UPS-1 MTS-UPS-2
LP-DC
D-LP-DC
2L13
2L12
2L11
CSI
GB-DC
ICRA BARRIER
G
B206F
DIAG IMG RM #1
B206E
DIAG IMG BONE
DENSITOMETER
COR2BD1
DIAG IMG CORR
ELVLOB2
COMMON ELEV
LOBBY
CRAC-1
CRAC- 2
B200
DATA CENTER
PDU-2
UPS-2
MBC-2
BATT
CAB 2
BATT
CAB 1 UPS-1 PDU-1
MBC-1
MTS-UPS-1 MTS-UPS-2
LP-DC
D-LP-DC
GB-DC
ICRA BARRIER
G
11 1/4" 5' - 4"
CRAC- 2
B206F
DIAG IMG RM #1
B206E
DIAG IMG BONE
DENSITOMETER
CONSTRUCTION
BARRIER, TYP.
ICRA BARRIER
ICRA BARRIER
B200
DATA CENTER
TEMPORARY COOLING AREA
TEMPORARY COOLING AREA
PDU-2
UPS-2
MBC-2
BATT
CAB 2
MTS-UPS-2
LP-DC
D-LP-DC
2L13
2L12
2L11
CSI
GB-DC
G
CRAC- 2
B206F
DIAG IMG RM #1
B206E
DIAG IMG BONE
DENSITOMETER
B200
DATA CENTER
ICRA BARRIER
TEMPORARY COOLING AREA
TEMPORARY COOLING AREA
PDU-2
UPS-2
MBC-2
BATT
CAB 2
BATT
CAB 1 UPS-1 PDU-1
MBC-1
MTS-UPS-1 MTS-UPS-2
LP-DC
D-LP-DC
2L13
2L12
2L11
CSI
GB-DC
G
CRAC- 2
CRAC- 1
B206F
DIAG IMG RM #1
B206E
DIAG IMG BONE
DENSITOMETER
B200
DATA CENTER
MTS-UPS-1
PDU-2
UPS-2
MBC-2
BATT
CAB 2
BATT
CAB 1 UPS-1 PDU-1
MBC-1
MTS-UPS-2
LP-DC
D-LP-DC
2L13
2L12
2L11
CSI
GB-DC
ICRA BARRIER
PHASE FOUR - NEW WORK NOTES
ARCHITECTURE
- INSTALL NEW DOOR, FRAME AND HARDWARE
- INFILL CORRIDOR WALL WITH RATED
CONSTRUCTION.
- REPLACE CORRIDOR WALL PANELING AND
FLOORING.
ELECTRICAL
- INSTALL MTS-UPS-1
- INSTALL UPS-1, PDU-1, MBC-1
- INSTALL BATT CAB 1
- INSTALL ROW 1 BUS A
- INSTALL ROW 2 BUS A
MECHANICAL
- PREPARE FOR CRAC-1 INSTALL.
- INSTALL CAV-B200.
TELECOMMUNICATIONS
- INSTALL NEW EQUIPMENT CABINETS, CABLE
TRAY, POWER DISTRIBUTION, AND BACKBONE
CABLING IN NOTED LOCATIONS.
- VA TO POPULATE NEW EQUIPMENT CABINETS.
FIRE PROTECTION
- NO WORK
ICRA BARRIER
SEE SHEET G121
CONSTRUCTION BARRIER. INSTALL SLAB TO
DECK DUST BARRIER. SIMILAR TO SWIFTWALL
PRO OR STARC LITEBARRIER.
PHASE FOUR - DEMO NOTES
ARCHITECTURE
- REMOVE DOUBLE DOOR, FRAME AND HARDWARE.
- REMOVE RAMP AND RAILING.
- REMOVE OPENING IN CORRIDOR WALL AS
INDICATED.
- INSTALL CONSTRUCTION BARRIERS AS
INDICATED.
ELECTRICAL
- NO WORK
MECHANICAL
- UTILIZE TEMP COOL UNITS.
TELECOMMUNICATIONS
- VA TO RELOCATE/CONSOLIDATE EQUIPMENT
FROM REMAINING LEGACY CABINETS TO NEW
CABINETS.
FIRE PROTECTION
- NO WORK
TEMPORARY COOLING:
- TEMP COOL: 51.8 KW (MIDDLE) 16 TON SENSIBLE
- TEMP COOL FOR UPS 10.5 KW (LEFT) 5 TON SENSIBLE.
ICRA BARRIER
SEE SHEET G121
CONSTRUCTION BARRIER. INSTALL SLAB TO
DECK DUST BARRIER. SIMILAR TO SWIFTWALL
PRO OR STARC LITEBARRIER.
PHASE FIVE - DEMO NOTES
ARCHITECTURE
- INSTALL CONSTRUCTION BARRIERS AS
INDICATED.
- REMOVE REMAINING ACCESS FLOORING AND
CEIILING.
- PREP EXISTING SLAB FLOOR FOR NEW FINISHES.
- COMPLETE CORRIDOR WORK
ELECTRICAL
- NO WORK
MECHANICAL
- UTILIZE TEMP COOL UNITS.
TELECOMMUNICATIONS
- VA TO RELOCATE/CONSOLIDATE EQUIPMENT
FROM REMAINING LEGACY CABINETS TO NEW
CABINETS.
FIRE PROTECTION
- NO WORK
TEMPORARY COOLING:
- TEMP COOL: 51.8 KW (MIDDLE) 16 TON SENSIBLE
- TEMP COOL FOR UPS 10.5 KW (LEFT) 5 TON SENSIBLE.
ICRA BARRIER
SEE SHEET G121
CONSTRUCTION BARRIER. INSTALL SLAB TO
DECK DUST BARRIER. SIMILAR TO SWIFTWALL
PRO OR STARC LITEBARRIER.
PHASE FIVE - NEW WORK NOTES
ARCHITECTURE
- INSTALL FLOOR AND WALL FINISHES AS
INSTALLATION OF EQUIPMENT ALLOWS.
- INSTALL CHASE WITH SHAFT WALLS.
ELECTRICAL
- PROVIDE POWER TO NEW CRAC-1 (EVAP AND COND)
MECHANICAL
- INSTALL CRAC-1 EVAP.
- INSTALL CRAC-1 COND.
- INSTALL NEW RETURN AIR DUCTS.
- UTILIZE TEMP COOL UNITS.
TELECOMMUNICATIONS
- INSTALL NEW EQUIPMENT CABINETS, CABLE TRAY,
POWER DISTRIBUTION, AND BACKBONE CABLING IN
NOTED LOCATIONS.
- VA TO POPULATE NEW EQUIPMENT CABINETS.
FIRE PROTECTION
- NO WORK
ICRA BARRIER
SEE SHEET G121
CONSTRUCTION BARRIER. INSTALL SLAB TO
DECK DUST BARRIER. SIMILAR TO SWIFTWALL
PRO OR STARC LITEBARRIER.
PHASE SIX - NEW WORK NOTES
ARCHITECTURE
- PAINT WALLS
- INSTALL SIGNAGE
ELECTRICAL
- ESTABLISH EPO SYSTEM
MECHANICAL
- COMPLETE RETURN AIR DUCTWORK TO CRACS.
- INSTALL RACK SENSOR SYSTEM.
- BRING CRAC UNITS ONLINE.
TELECOMMUNICATIONS
- INSTALL NEW EQUIPMENT CABINETS, CABLE
TRAY, POWER DISTRIBUTION, AND BACKBONE
CABLING IN NOTED LOCATIONS.
- VA TO POPULATE NEW EQUIPMENT CABINETS.
FIRE PROTECTION
- INSTALL NEW SPRINKLER HEADS (GRIDS 15-16)
- INSTALL NEW SPRINKLER HEADS (GRIDS 16-17)
- INSTALL NEW SPRINKLER HEADS (GRIDS 17-18.25)
- INSTALL NEW GASEOUS TANKS AND PIPING
- INSTALL NEW FIRE ALARM DEVICES
ICRA BARRIER
SEE SHEET G121
CONSTRUCTION BARRIER. INSTALL SLAB TO
DECK DUST BARRIER. SIMILAR TO SWIFTWALL
PRO OR STARC LITEBARRIER.
PHASE SIX - DEMO NOTES
ARCHITECTURE
- REMOVE WALLS AND FURRING AROUND COLUMN
ELECTRICAL
- REMOVE PANELS CSI / 2L11 / 2L12 / 2L13
MECHANICAL
- REMOVE TEMP COOL UNITS.
TELECOMMUNICATIONS
- NO WORK
FIRE PROTECTION
- NO WORK
TEMPORARY COOLING:
- REMOVE TEMPORARY COOLING AND PATCH TEMPORARY
PENETRATIONS WHEN CRAC-1 AND 2 ARE OPERATIONAL
AND COMMISSIONED WITH COMPLETION OF RETURN AIR
DUCTWORK INSTALLTION.
ICRA BARRIER
SEE SHEET G121
CONSTRUCTION BARRIER. INSTALL SLAB TO
DECK DUST BARRIER. SIMILAR TO SWIFTWALL
PRO OR STARC LITEBARRIER.
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
AE Works, LTD.
418 Beaver Street
Sewickley, PA 15143
Phone: 412-287-7333 www.aeworks.comAE WORKS®1900 Market Street, Suite 300 Philadelphia, PA 19103
215.222.3000
8815 Centre Park Drive, Suite 200 Philadelphia, MD 21045
410.750.2246
A u to d e s k D o c s /V
C H
A -0
C h a rl e s to n E
H R
M D a ta
C e n te r/ V
C H
A -0
C h a rl e s to n E
H R
M D a ta
C e n te r.
rv t
/4 /2
:4
:4
P M
G102
PHASING PLANS EHRM DATA CENTER UPGRADES
FOR JSA-FDS - CHARLESTON, SC
109 BEE ST. CHARLESTON SC 29401
534-24-706
02.06.26 LP TW
BID DOCUMENTS
1/4" = 1'-0"
PARTIAL SECOND FLOOR PLAN - PHASE FOUR
1/4" = 1'-0"
PARTIAL SECOND FLOOR PLAN - PHASE FIVE
1/4" = 1'-0"
PARTIAL SECOND FLOOR PLAN - PHASE SIX
1/4" = 1'-0"
PARTIAL SECOND FLOOR PLAN - DEMO PHASE FOUR
1/4" = 1'-0"
PARTIAL SECOND FLOOR PLAN - PHASE FIVE DEMO
1/4" = 1'-0"
PARTIAL SECOND FLOOR PLAN - PHASE SIX DEMO
# Revisions Date
WS AA LM LO O
H F
INFECTION CONTROL RISK ASSESSMENT FOR CONSTRUCTION
TABLE 1: CONSTRUCTION, RENOVATION, AND/OR MAINTENANCE ACTIVITY
CATEGORIES:
CATEGORY A
INSPECTION AND/OR FACILITY UPKEEP
• WORK CAN BE COMPLETED IN A SINGLE SHIFT, NOT EXCEEDING 10 DAYS.
• WORK THAT DOES NOT CREATE DUST OR DEBRIS.
• REMOVAL OF CEILING TILES OR ACCESS TO MECHANICAL OR ELECTRICAL
CHASE FOR VISUAL INSPECTION LIMITED TO 1 TILE PER 50 SQUARE FEET
WITH LIMITED EXPOSURE TIME (NOT TO EXCEED AN HOUR FOR EACH
TILE) WITHIN THE SHIFT.
• MINOR INTERIOR UPDATES (E.G., REPLACING FLOOR OR CEILING TILES,
CARPENTRY WORK TO INCLUDE HANGING SIGNAGE, AND PAINTING
WITHOUT SANDING) THAT DO NOT CREATE DUST OR DEBRIS.
• LIMITED BUILDING SYSTEM MAINTENANCE SUCH AS PLUMBING ON
POTABLE SYSTEMS LIMITED TO FAUCET REPLACEMENT ETC. AND
ELECTRICAL WORK SUCH AS REPLACEMENT OF BULBS, RECEPTACLES,
OR SWITCHES.
CATEGORY B
GENERAL MAINTENANCE AND REPAIR WORK GENERALLY DEFINED AS
FOLLOWS:
• PROLONGED INSPECTION AND WORK THAT MAY TAKE LONGER THAN A
SINGLE SHIFT BUT NOT EXCEEDING A WEEK.
• PATIENTS AND EMPLOYEES ARE NOT TO BE IN THE AREA UNTIL ACTIVITY
IS COMPLETED.
• WORK THAT CREATES MINIMAL DUST AND DEBRIS.
• INTERIOR FINISH OR SURFACE REPAIRS, UPDATES, OR MODIFICATIONS
SUCH AS REPAIR OF FIREWALLS AND BARRIERS, AND NEW FLOORING
THAT PRODUCES MINIMAL DUST AND DEBRIS. CONTROLLED SANDING
ACTIVITIES (E.G. WET OR DRY SANDING) THAT PRODUCE MINIMAL DUST
AND DEBRIS.
• PLUMBING WORK SUCH AS INSTALLATION OR REPLACEMENT OF SINGLE
FIXTURE OR PIPING FOR A SINGLE FIXTURE. ANY WORK ON SANITARY
PLUMBING INCLUDING SNAKING OF DRAINS.
• ELECTRICAL WORK SUCH AS INSTALLATION OF CABLING/WIRING/CONDUIT
FOR A SINGLE DEVICE, INSTALLATION OF NEW DEVICE SUCH AS A LIGHT
FIXTURE THAT PRODUCES MINIMAL DUST AND DEBRIS.
TYPE C
SMALL-SCALE CONSTRUCTION, RENOVATION, OR MAINTENANCE
GENERALLY DEFINED AS FOLLOWS:
• AIR HANDLER AND/OR FAN SHUTDOWN/STARTUP AND HVAC WORK SUCH
AS REPLACEMENT OF A SINGLE DIFFUSER, SINGLE TERMINAL UNIT OR A
SINGLE DEVICE THAT PRODUCES MINIMAL DUST AND DEBRIS.
• PATIENTS AND EMPLOYEES ARE NOT TO BE IN THE AREA UNTIL ACTIVITY
IS COMPLETED.
• DEMOLITION/REMOVAL OF PREEXISTING FLOOR COVERING, CASEWORK,
LAY-IN CEILING, OR OTHER ARCHITECTURAL ELEMENTS
• DEMOLITION/REMOVAL OF MORE THAN 32 FT2 OF DRYWALL/FRAMING,
HARD CEILINGS, AND DOORS/FRAMING AND MINIMAL INFRASTRUCTURE
SUCH AS ELECTRICAL CIRCUITS AND BRANCH PIPING.
• INSTALLATION OF NEW WALLS, CEILINGS AND DOORS INCLUDING
FRAMING, DRYWALL/PLASTER AND ASSOCIATED WORK.
• PLUMBING WORK SUCH AS THE INSTALLATION OF NEW SINKS, SHOWERS
AND TOILETS AND ASSOCIATED PLUMBING.
• SHUT DOWN OF SECTIONS OF POTABLE WATER SYSTEMS.
• ELECTRICAL WORK SUCH AS INSTALLATION OF CONDUIT AND WIRE FOR
LIGHTING, RECEPTACLES AND SWITCHES FOR AN AREA, THE
INSTALLATION OF CONDUIT AND WIRE FOR NEW DEVICES SUCH AS
TERMINAL UNITS, FANS ETC.
• MODIFICATION OF EXISTING FIRE ALARM AND SUPPRESSION SYSTEMS.
• MECHANICAL WORK SUCH AS THE INSTALLATION OF DUCTWORK,
DIFFUSERS, AND TERMINAL UNITS FOR AN AREA.
STEP #2: SELECT RISK GROUP BELOW AND MARK BOTTOM OF COLUMN
A) INFECTION CONTROL RISK GROUPS
GROUP 1 - LOW: OFFICE AREAS:
GROUP 2 - MEDIUM: CARDIOLOGY, ECHOCARDIOGRAPHY, ENDOSCOPY,
NUCLEAR MEDICINE, PHYSICAL THERAPY, RADIOLOGY/MRI, RESPIRATORY
THERAPY
GROUP 3 - HIGH RISK: CCU, EMERGENCY ROOM, LABORATORIES,
OUTPATIENT SURGERY, PHARMACY, POST ANESTHESIA CARE UNIT,
SURGICAL UNITS
GROUP 4 - HIGHEST RISK: ANY AREA CARING FOR IMMUNOCOMPROMISED
PATIENTS, CARDIAC CATH LAB, CENTRAL SUPPLY, INTENSIVE CARE UNITS,
MEDICAL UNITS, NEGATIVE AIRFLOW ROOMS, ONCOLOGY, OPERATING
ROOMS
TABLE 4: LEVEL OF INFECTION PREVENTION AND CONTROL PRECAUTIONS
MATCH THE OVERALL PATIENT RISK CATEGORY (LOW, MEDIUM, HIGH,
HIGHEST) DETERMINED FROM TABLE 3 WITH THE PLANNED
CONSTRUCTION/RENOVATION/MAINTENANCE ACTIVITY CATEGORY (A, B, C,
D) FROM TABLE 1 TO DETERMINE THE MINIMUM LEVEL OF INFECTION
PREVENTION AND CONTROL PRECAUTIONS (I, II, III, OR IV) USING
TABLE 4 BELOW
PATIENT RISK
CATEGORY A B C D
LOW RISK I II II III
MEDIUM RISK I II III IV
HIGH RISK I II IV IV
HIGHEST RISK II III IV IV
ELECTRICAL
YES
POTABLE
WATER
YES
HVAC
YES
MEDICAL
VACUUM
YES
SEWER
YES
PROJECTED UTILITY OUTAGES IMPACTING INFECTION CONTROL
STEP #4: COMPLETE THE INFECTION CONTROL CONSTRUCTION PERMIT:
1. EXECUTE WORK BY METHOD TO MINIMIZE RAISING DUST FROM
CONSTRUCTION OPERATIONS
2. IMMEDIATELY REPLACE A CEILING TILE DISPLACED FOR VISUAL INSPECTION
1. PROVIDE ACTIVE MEANS TO PREVENT AIRBORNE DUST FROM DISPERSING
INTO ATMOSPHERE.
2. WATER MIST WORK SURFACES TO CONTROL DUST WHILE CUTTING
3. SEAL UNUSED DOORS WITH DUCT TAPE
4. BLOCK OFF AND SEAL AIR VENTS.
5. PLACE DUST MAT AT ENTRANCE AND EXIT OF WORK AREA.
6. REMOVE OR ISOLATE HVAC SYSTEM IN AREAS WHERE WORK IS BEING
PERFORMED.
1. REMOVE OR ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE
TO PREVENT CONTAMINATION OF DUCT SYSTEM.
2. COMPLETE ALL CRITICAL BARRIERS, I.E. SHEETROCK, PLYWOOD, PLASTIC,
TO SEAL AREA FROM NON-WORK AREA OR IMPLEMENT CONTROL CUBE
METHOD (CART WITH PLASTIC COVERING & SEALED CONNECTION TO WORK
SITE WITH HEPA VACUUM FOR VACUUMING PRIOR TO EXIT) BEFORE
CONSTRUCTION BEGINS.
3. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORKSITE UTILIZING HEPA-
EQUIPPED AIR FILTRATION UNITS.
4. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORTATION IN TIGHTLY
COVERED CONTAINERS.
5. COVER TRANSPORT RECEPTACLES OR CARTS. TAPE COVERING UNLESS
SOLID LID IS USED.
1. ISOLATE HVAC SYSTEM IN AREA WHERE WORK IS BEING DONE TO
PREVENT CONTAMINATION OF DUCT SYSTEM.
2. COMPLETE ALL CRITICAL BARRIERS, I.E., SHEETROCK, PLYWOOD, PLASTIC,
TO SEAL AREA FROM NON-WORK AREA OR IMPLEMENT CONTROL CUBE
METHOD (CART WITH PLASTIC COVERING & SEALED CONNECTION TO WORK
SITE WITH HEPA VACUUM FOR VACUUMING PRIOR TO EXIT) BEFORE
CONSTRUCTION BEGINS.
3. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORKSITE UTILIZING HEPA-
EQUIPPED AIR FILTRATION UNITS.
4. SEAL HOLES, PIPES, CONDUITS AND PUNCTURES APPROPRIATELY.
5. CONSTRUCT ANTEROOM AND REQUIRE ALL PERSONNEL TO PASS
THROUGH THIS ROOM SO THEY CAN BE VACUUMED USING A HEPA VACUUM
CLEANER BEFORE LEAVING WORK SITE; OR THE CAN WEAR CLOTH OR PAPER
COVERALLS THAT ARE REMOVED EACH TIME THEY LEAVE THE WORK SITE.
6. ALL PERSONNEL ENTERING THE WORK SITE ARE REQUIRED TO WEAR
SHOE COVERS. SHOE COVERS MUST BE CHANGED EACH TIME THE WORKER
EXITS THE WORK AREA.
7. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED
PROJECT IS INSPECTED BY SAFETY MANAGEMENT & INFECTION CONTROL &
THOROUGHLY CLEANED BY ENVIRONMENTAL MANAGEMENT.
1. CLEAN WORK UPON COMPLETION OF TASK
1. WIPE WORK SURFACES WITH DISINFECTANT.
2. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY
COVERED CONTAINERS.
3. WET MOP &/OR VACUUM BEFORE LEAVING WORK AREA.
4. REMOVE ISOLATION OF HVAC SYSTEM IN AREA WHERE WORK IS BEING
PERFORMED.
1. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED
PROJECT IS INSPECTED BY SAFETY MANAGEMENT & INFECTION
CONTROL & THOROUGHLY CLEANED BY ENVIRONMENTAL MANAGEMENT.
2. REMOVE BARRIER MATERIALS CAREFULLY TO MINIMIZE SPREADING
OF DIRT & DEBRIS ASSOCIATED WITH CONSTRUCTION.
3. VACUUM WORK AREA WITH HEPA-FILTERED VACUUMS.
4. WET MOP WITH DISINFECTANT.
5. REMOVE ISOLATION OF HVAC SYSTEM IN AREAS WHERE WORK IS
BEING PERFORMED.
1. REMOVE BARRIER MATERIALS CAREFULLY TO MINIMIZE SPREADING
OF DIRT & DEBRIS ASSOCIATED WITH CONSTRUCTION.
2. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY
COVERED CONTAINERS.
3. COVER TRANSPORT RECEPTACLES OR CARTS. TAPE COVERING
UNLESS SOLID LID.
4. VACUUM WORK AREA WITH HEPA-FILTERED VACUUMS.
5. WET MOP WITH DISINFECTANT.
6. REMOVE ISOLATION OF HVAC SYSTEM IN AREAS WHERE WORK IS
BEING PERFORMED.
CLASS I - DURING CONSTRUCTION PROJECT
CLASS I - UPON COMPLETION OF PROJECTS
CLASS II - DURING CONSTRUCTION PROJECT
CLASS II - UPON COMPLETION OF PROJECTS
CLASS III - DURING CONSTRUCTION PROJECT
CLASS III - UPON COMPLETION OF PROJECTS
CLASS IV - DURING CONSTRUCTION PROJECT
CLASS IV - UPON COMPLETION OF PROJECTS
(TO BE COMPLETED BY CONTRACTOR AND SIGNED BY INFECTION CONTROL NURSE)
CONTRACTOR'S SIGNATURE AND DATE
INFECTION CONTROL NURSE'S SIGNATURE AND DATE
ACTIVITY CATEGORY
TYPE D
LARGE-SCALE CONSTRUCTION, RENOVATION, OR MAINTENANCE
GENERALLY DEFINED AS FOLLOWS:
• WORK EXCEEDING 6 MONTHS IN DURATION.
• PATIENTS AND EMPLOYEES ARE NOT TO BE IN THE AREA UNTIL ACTIVITY
IS COMPLETED.
• LARGE-SCALE DEMOLITION OF BUILDING COMPONENTS AND
INFRASTRUCTURE INCLUDING REMOVAL OF MULTIPLE DOORS, WALLS,
FRAMING, CEILINGS, FLOORING, PIPING, ELECTRICAL AND HVAC.
• THE INSTALLATION BUILDING COMPONENTS SUCH AS NEW WALLS,
CEILINGS AND DOORS INCLUDING FRAMING, DRYWALL AND ASSOCIATED
PLASTER WORK.
• PLUMBING WORK SUCH AS THE INSTALLATION OF:
- NEW MEDICAL GAS SYSTEMS,
- STEAM/HEATING HOT WATER, CONDENSATE SYSTEMS,
- MULTIPLE SINKS, SHOWERS AND TOILETS INCLUDING ASSOCIATED
PLUMBING.
• SHUTDOWN OF POTABLE WATER, STEAM/HEATING HOT WATER,
CONDENSATE, AND MEDICAL GAS SYSTEMS.
• ELECTRICAL WORK SUCH AS INSTALLATION OF ELECTRICAL FEEDERS,
DISTRIBUTION PANELS, CONDUIT AND WIRE FOR LIGHTING, RECEPTACLES
AND SWITCHES FOR AN AREA, THE INSTALLATION OF CONDUIT AND WIRE
FOR NEW DEVICES SUCH AS TERMINAL UNITS, FANS ETC.
• INSTALLATION OF FIRE ALARM AND SUPPRESSION SYSTEMS.
• ELECTRICAL SHUTDOWN OF MULTIPLE PANELS.
• MECHANICAL WORK SUCH AS THE INSTALLATION OF AIR HANDLING
EQUIPMENT, ASSOCIATED DUCTWORK, DIFFUSERS, HEAT EXCHANGERS,
TERMINAL UNITS AND CONTROLS.
DUST CONTROL PLAN NOTES / DUST CONTROL PLAN HAZARD ASSESSMENT
PRIOR TO INITIATING WORK, CONTRACTOR WILL ASSESS THE SCOPE OF THE CONSTRUCTION ACTIVITIES AND
DETERMINE THE POTENTIAL RISK GROUPS INVOLVED BASED ON THE LOCATION OF ACTIVITIES AND EXTENT AND
DURATION OF THE WORK. LOW RISK GROUPS ARE CONSIDERED "OFFICE WORKERS", MEDIUM RISK GROUPS ARE
CONSIDERED ALL INPATIENT AND OUTPATIENT AREAS NOT IN THE HIGH RISK GROUP. HIGH RISK GROUP
DESIGNATION INCLUDES INPATIENT AREAS SUCH AS PEDIATRIC AND ADULT OPERATING/DELIVERY ROOMS, CATH
LABS, MYELO SUPPRESSION UNITS, ICUS, DIALYSIS, NURSERIES AS WELL AS CLINIC AREAS (CLINICS ASSOCIATED
WITH HEMATOLOGY, ONCOLOGY, PEDIATRIC INFECTION DISEASE, OR TRANSPLANT SERVICES) AND SERVICE
AREAS (CENTRAL PROCESSING, STERILE PROCESSING, FOOD PREP & SERVICE AREA AND PHARMACIES. THE
VAMC INFECTION CONTROL GROUP WILL CONFIRM AND APPROVE THE DESIGNATION PROVIDED IN THIS
SUBMITTED DUST CONTROL PLAN. VAMC IS ALSO RESPONSIBLE FOR ANY AND ALL INFECTION CONTROL
MEASURES DETERMINED AND ESTABLISHED BY VAMC POLICY, SUCH AS THE RELOCATION OF HIGH RISK
PATIENTS, APPROVING ALTERNATE TRAFFIC PATHS FOR CONSTRUCTION WORKERS OR ESTABLISH ALTERNATE
TRAFFIC PATTERNS FOR STAFF, PATIENTS AND VISITORS. THE PLAN SHOULD BE REVISED ACCORDING TO
SPECIFIC VAMC POLICIES OR CHANGING CONDITIONS AT THE SITE AS THEY MAY OCCUR.
CHARLESTON VAMC RENOVATION
FOR THE PURPOSE OF THIS RENOVATION, THE CONSTRUCTION WORK IS CONSIDERED ADJACENT TO MEDIUM
RISK AND COMPRISES WORK WHICH COULD GENERATE MODERATE TO HIGH LEVELS OF DUST NOT WITHIN THE
CONFINES OF A SUITE OR OFFICE AND INCLUDES EXTENSIVE CONSTRUCTION WORK (DEMOLITION) IN BUILDING
100 THROUGHOUT THE CORE AND SERVICE BAYS ON THE FIRST FLOOR. THE DUST CONTROL PLAN SHALL BE
DISTRIBUTED AND REVIEWED BY ALL CONTRACTORS PERFORMING WORK ON THIS CONSTRUCTION PROJECT.
A. EXTERNAL DEMOLITION AND CONSTRUCTION ACTIVITIES
• DETERMINE IF THE IMPACTED AREAS OF THE FACILITY CAN OPERATE TEMPORARILY ON RECIRCULATED AIR; IF
FEASIBLE SEAL OFF ADJACENT AIR INTAKES.
• IF THIS IS NOT POSSIBLE OR PRACTICAL, CHECK THE LOW-EFFICIENCY FILTER BANKS FREQUENTLY AND
REPLACE AS NEEDED TO AVOID BUILDUP OF PARTICULATE.
• SEAL WINDOWS AND REDUCE WHEREVER POSSIBLE OTHER SOURCES OF OUTSIDE AIR INTRUSION (OPEN
DOORS IN STAIRWELLS AND CORRIDORS) ESPECIALLY IN PROTECTIVE ENVIRONMENT (PE) AREAS.
B. INTERNAL DEMOLITION AND CONSTRUCTION ACTIVITIES DUST AND DEBRIS CONTROL
• BARRIER SYSTEMS: THE AREA SHOULD BE ISOLATED, AS THE PROJECT REQUIRES. SMALL, SHORT DURATION
PROJECTS GENERATING MINIMAL DUST MAY USE FIRE-RATED PLASTIC SHEETING, BUT SHOULD BE SEALED AT
FULL CEILING HEIGHT WITH AT LEAST 2-FOOT OVERLAPPING FLAPS FOR ACCESS TO ENTRY. PROJECTS THAT
PRODUCE MODERATE TO HIGH LEVELS OF DUST REQUIRE RIGID, DUST-PROOF, AND FIRE-RATED BARRIER
WALLS (E.G., DRYWALL) WITH CAULKED SEAMS FOR A TIGHT SEAL EXTENDING FLOOR TO CEILING. SEAL OFF
AND BLOCK RETURN AIR VENTS IF RIGID BARRIERS ARE USED FOR CONTAINMENT. LARGE DUST PROJECTS
NEED AN ENTRY VESTIBULE FOR CLOTHING CHANGES AND TOOL STORAGE AND TIGHT SEALS SHOULD BE
MAINTAINED AT THE FULL PERIMETER OF WALLS AND WALL PENETRATIONS. AN INTERIM PLASTIC DUST
BARRIER (MINIMUM 4-MIL) MAY BE REQUIRED TO PROTECT THE AREA WHILE THE RIGID IMPERVIOUS BARRIER
IS BEING CONSTRUCTED. ANY DUST SHALL BE IMMEDIATELY CLEANED IF TRACKED OUTSIDE OF THE
CONSTRUCTION BARRIER. UPON COMPLETION OF THE CONSTRUCTION PROJECT DUST BARRIERS SHALL BE
REMOVED CAREFULLY TO MINIMIZE SPREADING OF DUST AND THE CONTRACTOR SHALL HAVE TEMPORARY
DUST PROTECTION IN PLACE BEFORE REMOVAL OF A PERMANENT BARRIER. CONTRACTOR PERSONNEL
SHALL MONITOR AND PERFORM BARRIER MAINTENANCE AND BE EDUCATED TO NOTICE SIMPLE CLUES SUCH
AS ACCUMULATIONS OF VISIBLE DUST EVIDENCED BY FOOTPRINTS, OPENED DOORS/WINDOWS EVIDENCED BY
PRESENCE OF INSECTS AND FLIES, WET CEILING TILE, ETC.
• TRAFFIC CONTROL; DESIGNATED ENTRY AND EXIT PROCEDURES SHALL BE DEFINED. EGRESS PATHS SHOULD
BE FREE OF DEBRIS; DESIGNATED ELEVATORS SHOULD BE USED DURING SCHEDULED TIMES; AND ONLY
AUTHORIZED PERSONNEL SHOULD BE ALLOWED TO ENTER THE CONSTRUCTION ZONE. SIGNAGE SHOULD
DIRECT PEDESTRIAN TRAFFIC AWAY FROM THE CONSTRUCTION AREA AND MATERIALS.
• DEMOLITION DEBRIS: DEBRIS SHOULD BE REMOVED IN CARTS WITH TIGHTLY FITTED COVERS, USING
DESIGNATED TRAFFIC ROUTES. EFFORTS SHOULD BE MADE TO MINIMIZE USE OF ELEVATORS WITH AN
EMPHASIS ON TRANSPORT DURING THE LOWEST PERIOD OF ACTIVITY. DEBRIS SHOULD BE REMOVED DAILY
AND AT TIMES SPECIFIED BY THE VAMC. IF CHUTES ARE USED TO DIRECT DEBRIS OUTSIDE, HIGH EFFICIENCY
PARTICULATE AIR (HEPA) FILTERED NEGATIVE AIR MACHINES SHOULD BE USED, AND THE CHUTE OPENING
SHOULD BE SEALED WHEN NOT IN USE. FILTERS SHOULD BE BAGGED AND SEALED BEFORE BEING
TRANSPORTED OUT OF THE CONSTRUCTION AREA. THE CONTRACTOR SHALL NOT HAUL DEBRIS THROUGH
PATIENT-CARE AREAS WITH PRIOR APPROVAL OF THE VAMC.
• EXTERIOR WINDOWS: WINDOWS SHOULD BE SEALED TO MINIMIZE INFILTRATION FROM ANY ADJACENT
EXCAVATION DEBRIS.
• CEILINGS THAT ARE REMOVED/MODIFIED TO ALLOW CONSTRUCTION OF ICRA BARRIERS SHOULD BE
REINSTALLED TO PRE-CONSTRUCTION CONDITIONS.
VENTILATION AND ENVIRONMENTAL CONTROLS
• AIR SYSTEM FLOW: DETERMINE WHETHER THE CONSTRUCTION AREA USES FRESH/OUTSIDE OR
RECIRCULATED AIR; FILTERS SHOULD BE ADDED OR RETURN VENTS COVERED AS NEEDED WITH FILTER
MATERIAL OR PLASTIC. AIR MUST FLOW FROM CLEAN TO DIRTY AREAS.
• NEGATIVE AIR PRESSURE: THE AIR WITHIN THE CONSTRUCTION AREA MUST BE NEGATIVE WITH RESPECT TO
SURROUNDING AREAS AND WITH NO DISRUPTION OF AIR SYSTEMS OF ADJACENT AREAS. USE OF THE
NEGATIVE AIR PRESSURE SYSTEM WITHIN THE ENCLOSURE TO REMOVE DUST SHOULD PASS AIR THROUGH AN
INDUSTRIAL GRADE, PORTABLE HEPA FILTER CAPABLE OF FILTRATION RATES OF 300-800 CUBIC FEET PER
MINUTE (FT3//MIN), OR EXHAUST AIR DIRECTLY TO THE OUTSIDE IF APPROVED BY VAMC. IF EXHAUST MUST BE
TIED INTO A RE-CIRCULATED AIR SYSTEM, A PRE-FILTER AND HEPA FILTER SHOULD BE USED BEFORE
EXHAUST TO PREVENT CONTAMINATION OF THE DUCTS.
• ADJACENT AREAS: THE STATUS OF SEALED PENETRATIONS AND INTACT CEILING SHOULD BE VERIFIED DAILY.
• AIR EXCHANGE RATES AND PRESSURE RELATIONSHIPS: VAMC AND/OR CONTRACTOR WILL VERIFY AND
MAINTAIN PROPER RATES IN CRITICAL AREAS NEAR CONSTRUCTION ACTIVITY AND ENSURE AIR IS NOT BEING
RE-CIRCULATED WITHOUT FILTRATION FROM THE CONSTRUCTION AREA ELSEWHERE. VAMC WILL MAKE
DETERMINATION ON PROVIDING FOR THE ACCOUNTABILITY AND FREQUENCY OF TESTING AIR PRESSURE
THROUGHOUT THE PROJECT.
• MANOMETERS SHOULD BE LOCATED ON ICRA PARTITION DOOR AND ON THE NON-CONSTRUCTION SIDE OF THE
PARTITION.
CONTAMINATION OF PATIENT ROOMS
• WORKSITE CLOTHING: CONTRACTOR PERSONNEL CLOTHING SHOULD BE FREE OF LOOSE SOIL AND DEBRIS
BEFORE LEAVING THE CONSTRUCTION AREA. IF PROTECTIVE APPAREL IS NOT WORK (E.G. COVERALLS, FOOTGEAR AND HEADGEAR) A HEPA-FILTERED VACUUM SHOULD BE USED TO REMOVE DUST FROM CLOTHING
BEFORE LEAVING THE BARRICADE. IF PROTECTIVE APPAREL IS UTILIZED THE CONTRACTOR SHALL
CONSTRUCT A SPACE OR ANTEROOM FOR CHANGING CLOTHING AND STORING EQUIPMENT (DESIGNATED
AREA). ALL EQUIPMENT, TOOLS, TOOL CARTS, MATERIALS, ETC. TRANSPORTED THROUGH OCCUPIED AREAS
SHALL BE MADE FREE FROM DUST AND MOISTURE BY VACUUMING AND WET WIPING BEFORE THEIR REMOVAL
FROM THE CONSTRUCTION ZONE OR WORK AREA.
• CONTRACTOR CLEANING: THE CONSTRUCTION ZONE SHOULD BE MAINTAINED IN A CLEAN MANNER BY
CONTRACTORS AND SWEPT OR HEPA-VACUUMED DAILY FOR MORE FREQUENTLY AS NEEDED TO MINIMIZE
DUST. ADJACENT AREAS THAT MAY BE IMPACTED BY THE CONSTRUCTION SHOULD BE DAMP MOPPED DAILY
OR MORE FREQUENTLY AS NEEDED. WALK-OFF MATS WITH TACKY OR ADHESIVE SURFACES SHOULD BE
UTILIZED TO MINIMIZE TRACKING OF HEAVY DIRT AND DUST FROM CONSTRUCTION AREAS.
ACCESSIBLE ACM LOCATIONS
AE WORKS' SUBCONSULTANT PENNONI ENGINEERING PERFORMORMED A LIMITED ASBESTOS SURVEY ON DECEMBER 10, 2025 TO IDENTIFY IF ACCESSIBLE ACM (ASBESTOS CONTAINING MATERIAL) MAY BE DISTURBED BY THE PLANNED RENOVATION
PROJECT. THE SURVEY WAS CONDUCTED BY MR. THOMAS ADAMS, ONE OF PENNONI'S UNITED STATES ENVIRONMENTAL PROTECTION AGENCY (USEPA) TRAINED IN THE STATE OF SOUTH CAROLINA, LICENSED ASBESTOS BUILDING INSPECTORS.
DURING THIS INSPECTION, 100 SAMPLES OF THE FOLLOWING IDENTIFIED SUSPECT ACM SYSTEMS WERE COLLECTED (SEE APPENDIX B – ASBESTOS FIELD INSPECTION FORMS, APPENDIX C – SITE PHOTOGRAPHS AND APPENDIX D – SAMPLE LOCATION
DRAWING). THE FOLLOWING SUSPECT ACM, LISTED HERE BY HOMOGENEOUS IDENTIFICATION NUMBER (HID), WERE IDENTIFIED AND SAMPLED DURING THIS INVESTIGATION:
101. DRYWALL (NAD)
102. JOINT COMPOUND (NAD)
103. 2’X4’ LAY-IN CEILING TILE, DOT (NAD)
104. 2’X2’ LAY-IN CEILING TILE, DOT (NAD)
105. 2’X2’ LAY-IN CEILING TILE, ROUGH FINISH (NAD)
106. 2’X2’ LAY-IN CEILING TILE, SMOOTH FINISH (NAD)
107. COVEBASE MOLDING MASTIC (NAD)
108. 12”X12” OFF-WHITE WITH TAN FLOOR TILE (NAD), TAN MASTIC (NAD) AND BLACK MASTIC (POS)
109. RAISED FLOOR PEDESTAL MASTIC (NAD)
110. GRAY FLOOR LEVELING COMPOUND (NAD)
111. CERAMIC FLOOR MORTAR/WETBED (NAD)
112. FIRE STOP (NAD)
113. PLASTER WALL (NAD)
114. PLASTER PATCH (NAD)
115. END CAP MASTIC (NAD)
(NAD) - NO ASBESTOS DETECTED; (POS) - POSITIVE FOR ASBESTOS CONTENT.
116. FIBERGLASS PIPE INSULATION (NON-SUSPECT)
117. TAR (POS) ASSOCIATED WITH FOIL WRAP PIPE INSULATION (NAD) AND HID 118.
118. FITTING (NAD) ASSOCIATED WITH FIBERGLASS PIPE INSULATION
119. ROOFING FIELD – BUILT-UP ROOFING (NAD), FLASHING (NAD), FELT (NAD), INSULATION (NAD) AND FOAM (NAD)
120. ROOF FLASHING, EQUIPMENT – FLASHING1 (NAD), FLASHING2 (NAD) AND INSULATION (NAD)
121. EQUIPMENT FLASHING, CAP CAULK (NAD)
122. EQUIPMENT FLASHING, SILVER COATING (NAD)
123. ENDCAP MASTIC (NAD) ASSOCIATED WITH PIPE INSULATION
124. PITCH POCKET (NAD)
125. EQUIPMENT PENETRATION PATCH TAR (NAD)
THE GOAL OF THE PRE-CONSTRUCTION SURVEY WAS TO IDENTIFY READILY ACCESSIBLE ACM THAT MAY BE IMPACTED BY THE RENOVATION PROJECT ASSOCIATED WITHIN ROOM B200 AND ROOFING SYSTEM IN SUPPORT OF THE EHRM
INFRASTRUCTURE UPGRADES. PENNONI’S SURVEY DID NOT INCLUDE AREAS OUTSIDE THE SCOPE OF RENOVATION AS WELL AS OPERATIONAL UTILITY SYSTEMS, BELOW-GRADE OR SUBFLOOR SAMPLING, CONCEALED PIPE CHASE SPACES, INACCESSIBLE CRAWLSPACES ASSOCIATED WITH FOUNDATIONS, OR THE EXTERIOR. HAZARDOUS MATERIALS MAY BE PRESENT IN THESE AREAS. THE VA SHOULD BE CONTACTED IMMEDIATELY IF RENOVATION OR DEMOLITION ACTIVITIES
UNCOVER MATERIALS THAT ARE NOT IDENTIFIED IN THIS REPORT.
1 LAYER TYPE "X" GWB EACH SIDE. REFER
TO UL DOCUMENT FOR PANEL THICKNESS -
COORDINATE WITH METAL STUD SIZE
PROVIDE BATT INSULATION IF REQUIRED
BY UL DOCUMENT BASED ON STUD SIZE
AND GWB THICKNESS
5/8" G.W.B.
METAL STUDS FRAMING - REFER TO UL
DOCUMENT FOR SIZE, SPACING AND WIDTH -
COORDINATE WITH GWB THICKNESS
BASE - SEE FINISH
SCHEDULE FOR TYPE
STEEL TRACK, FASTEN 2'-0" OC MAX.
FLOOR SLAB
S E
E S
C H
E D
U
LE
P A
R T
IT
IO
N W
ID
T
H
FIRE RATED SEALANT, BOTH SIDES -
REFER TO UL DOCUMENT
UNDERSIDE OF
STRUCTURE
ICRA GENERAL NOTES:
1. FOR EXISTING PARTITIONS USED AS ICRA BARRIERS, THE CONTRACTOR
SHALL COMPLETE THE FOLLOWING:
· MODIFY EXISTING PARTITION TO A ONE-HOUR RATED ICRA BARRIER
· EXTEND PARTITION TO FLOOR DECK WITH 5/8” G.W.B. ON EACH SIDE
· FINISH WALL PARTITION AS DIRECTED BY UL RATING
REQUIREMENTS
· INFILL EXISTING OPENINGS WITH 5/8” G.W.B ON EACH SIDE
· PROVIDE FIRESTOPPING AT ALL EXISTING PENETRATIONS
2. PROVIDE 45 MINUTE RATED DOOR TO ACCESS CONSTRUCTION AREA AT
ALL NEW AND EXISTING ICRA BARRIERS. DOORS SHALL BE 3X7. SELF
CLOSING WITH POSITIVE LATCHING. PROVIDE STOREROOM FUNCTION
LOCKSETS.
3. THE CONTRACTOR SHALL NOT BLOCK SPRINKLER PROTECTION ON THE
VA-OCCUPIED SIDE OF THE ICRA BARRIER.
BASE
HEAD
PLAN
EXISTING CEILING OUTSIDE CONSTRUCTION
AREA - MODIFY AS REQUIRED FOR
TEMPORARY PARTITION.
UL NO. U419 - 1 HOUR RATED
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
AE Works, LTD.
418 Beaver Street
Sewickley, PA 15143
Phone: 412-287-7333 www.aeworks.comAE WORKS®1900 Market Street, Suite 300 Philadelphia, PA 19103
215.222.3000
8815 Centre Park Drive, Suite 200 Philadelphia, MD 21045
410.750.2246
A u to d e s k D o c s /V
C H
A -0
C h a rl e s to n E
H R
M D a ta
C e n te r/ V
C H
A -0
C h a rl e s to n E
H R
M D a ta
C e n te r.
rv t
/4 /2
:4
:5
P M
G121
ICRA AND ABATEMENT EHRM DATA CENTER UPGRADES
FOR JSA-FDS - CHARLESTON, SC
109 BEE ST. CHARLESTON SC 29401
534-24-706
02.06.26 LP TW
BID DOCUMENTS
# Revisions Date
ICRA BARRIER
WS AA LM LO O
H F
174 SF / 16.1 m²
VOL SVC
NO NAME
B201 240 SF / 22.3 m²
DIAG IMG
NUCLEAR MEDICINE PHYSICIANS
OFFICES
B202
179 SF / 16.7 m²
DIAG IMG
NUC MED WAIT RM
B203
200 SF / 18.6 m²
DIAG IMG
BONE DENSITOMETER
B206E
576 SF / 53.5 m²
DIAG IMG
WAIT AREA
D200
283 SF / 26.3 m²
DIAG IMG
X-RAY RM - 1
D243 52 SF / 4.8 m²
DIAG IMG
CLEAN LINEN
D244
79 SF / 7.3 m²
DIAG IMG
PAT HOLDING
D245
166 SF / 15.4 m²
DIAG IMG
NO SIGN
D246
COMMON
CORR
COR2CD1
205 SF / 19 m²
VERTICAL SPACE
STAIR
44 SF / 4.1 m²
COMMON
ELEC CLO
A290
VERTICAL SPACE
387 SF / 36 m²
COMMON
ELEV LOBBY
ELVLOB2
VERTICAL SPACE
89 SF / 8.3 m²
VERTICAL SPACE
ELEV
P-4
40 SF / 3.7 m²
CONTROL RM
17 SF / 1.6 m²
COMMON
ELEC CLO
D200A
69 SF / 6.4 m²
COMMON
TELECOM CLO
B280
98 SF / 9.1 m²
VERTICAL SPACE
ELEV
S-1
93 SF / 8.6 m²
VERTICAL SPACE
ELEV
S-2
84 SF / 7.8 m²
DIAG IMG
NRS PRACTITIONER
B202A
97 SF / 9 m²
DIAG IMG
STAFF RAD
B202F
982 SF / 91.2 m²
DIAG IMG
CORR
COR2BD1
33 SF / 3 m²
VERTICAL SPACE
CHASE
RCC209C
56 SF / 5.2 m²
VERTICAL SPACE
CHASE
RCC223C
46 SF / 4.3 m²
VERTICAL SPACE
CHASE
RCC224C
188 SF / 17.4 m²
7 SF / 0.7 m²
COMMON
FAC
RCC201R
21 SF / 1.9 m²
SURGICAL
CHASE
RCC235C
349 SF / 32.4 m²
DIAG IMG
IMAGING RM #1
B206F
FEC
FEC
115'-6" MTD
56'-10" CPT
PROJECT AREA
SECOND FLOOR
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
AE Works, LTD.
418 Beaver Street Sewickley, PA 15143 Phone: 412-287-7333 www.aeworks.comAE WORKS®1900 Market Street, Suite 300
Philadelphia, PA 19103 215.222.3000
8815 Centre Park Drive, Suite 200 Philadelphia, MD 21045
410.750.2246
EHRM DATA CENTER UPGRADES
FOR JSA-FDS - CHARLESTON, SC
109 BEE ST. CHARLESTON SC 29401
534-24-706
02.06.26 JAH BWE
100% CONSTRUCTION
DOCUMENTS
# Revisions Date
LS101
LIFE SAFETY PLAN -
DATA CENTER
1/4" = 1'-0"1 LIFE SAFETY PLAN - DATA CENTER
XX m MTD
GROSS DOOR WIDTH
(NET CLEAR WIDTH)
(MM)
EXIT
SMOKE RESISTIVE
1-HOUR SMOKE BARRIER
1-HOUR FIRE BARRIER
2-HOUR FIRE BARRIER
3-HOUR FIRE WALL
EXISTING FIRE EXTINGUISHER
(2-A:C CO2)
AREA NOT IN SCOPE
XXX XXX
XXXXXX
CAPACITY
# OF PEOPLE
STAIR WIDTH
(MM)
ACTUAL LOAD
# OF PEOPLE
LEGEND
XX m CPT
TRAVEL DISTANCE TO EXIT
COMMON PATH OF TRAVEL
DEAD END DISTANCE
EXIT CAPACITY
FEC
XX m MDE
IBC: TYPE 1B
NFPA 220: TYPE II (222)
FIRE-RESISTANCE RATING OF FLOOR/CEILING ASSEMBLY:
2 HOUR
CONSTRUCTION TYPE
· NFPA 101®, LIFE SAFETY CODE®, 2021 EDITION
· INTERNATIONAL BUILDING CODE, 2021 EDITION
· VA FIRE PROTECTION DESIGN MANUAL(VAFPDM) - NINTH EDITION, NOVEMBER 2023
· NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS - 2022 EDITION
· NFPA 25, STANDARD FOR THE INSPECTION, TESTING, AND MAINTENANCE OF WATER-BASED FIRE
PROTECTION SYSTEMS - 2023 EDITION
· NFPA 70, NATIONAL ELECTRICAL CODE - 2023 EDITION
· NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE - 2022 EDITION
· NFPA 75, STANDARD OF THE FIRE PROTECTION OF INFORMATION TECHNOLOGY EQUIPMENT - 2020 EDITION
· NFPA 2001, STANDARD ON CLEAN AGENT FIRE EXTINGUISHING SYSTEMS - 2022 EDITION
APPLICABLE CODES & STANDARDS
COMPLETELY SPRINKLER-PROTECTED
IBC: GROUP I-2 (SECTION 308.3.1.2)
NFPA 101: EXISTING HEALTH CARE (CHAPTER 19)
USE AND OCCUPANCY TYPE
GENERAL NOTES
1. THIS RENOVATION DOES NOT IMPACT THE OCCUPANT LOAD WITHIN THE AREA
OF WORK. THE MEANS OF EGRESS FOR THE BUILDING IS AN EXISTING
APPROVED CONDITION.
2. INTERIM LIFE SAFETY MEASURES (ILSM'S) MUST BE PLANNED, REVIEWED AND
IMPLEMENTED PRIOR TO ANY CHANGES/CONSTRUCTION IN EGRESS
CORRIDORS DUE TO DOOR AND WALL WORK.
3. EXISTING DATA ROOM ENCLOSURE PROVIDED WITH 1-HOUR FIRE BARRIERS
AND 60-MINUTE FIRE-RATED DOORS. EXISTING DATA ROOM DOES NOT HAVE
ANY SMOKE BARRIER WALLS SHOWN.
4. PENETRATIONS OF FIRE-RATED ASSEMBLIES SHALL BE SEALED WITH A U.L.
CERTIFIED THROUGH-PENETRATION SYSTEM APPROPRIATE FOR THE
MATERIALS INVOLVED AND THE RATING OF THE WALL PENETRATED.
5. THE NEW DATA ROOM SHALL BE CLASSIFIED AS A MISSION CRITICAL
TELECOMMUNICATION SPACE.
6. THERE ARE NUMEROUS PENETRATIONS IN THE EXISTING RATED WALLS. ALL
PENETRATIONS IN ALL ROOM RATED WALLS SHALL BE FIRESTOPPED WITH
APPROPRIATE UL CERTIFIED SYSTEMS.
7. PATCH AND REPAIR EXISTING WALLS BOTH ABOVE AND BELOW EXISTING
CEILING TO ENSURE SPACE IS AIR-TIGHT PRIOR TO NEW WORK.
THE PROJECT INVOLVES THE RENOVATION OF DATA CENTER ROOM (B200) LOCATED ON FLOOR 2 OF THE CHARLESTON, SOUTH CAROLINA VA MEDICAL CENTER, BUILDING 1. THE NEW DATA CENTER WILL CONTAIN
ITS OWN WET-PIPE SPRINKLER, CLEAN AGENT, AND FIRE ALARM SYSTEMS.
SCOPE OF WORK
EXISTING HEALTHCARE
ZONE PACU/SURGERY
20,890 SQ FT
EXISTING HEALTHCARE
ZONE RADIOLOGY
17,310 SQ FT
EXISTING HEALTHCARE
ZONE SLEEP LAB / SPEC. CLINIC
11,235 SQ FT
1. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE "2021 INTERNATIONAL BUILDING CODE" (IBC 2021) AS ADOPTED BY THE STATE OF SOUTH
CAROLINA AS WELL AS ALL APPLICABLE FEDERAL, STATE AND LOCAL CODES.
2. ALL CODES AND STANDARDS REFERENCED IN THESE NOTES APPLY TO THE DESIGN, CONSTRUCTION, DEMOLITION, QUALITY CONTROL AND SAFETY OF ALL WORK PERFORMED ON THE PROJECT. UNLESS SPECIFICALLY STATED, USE THE LATEST ADOPTED EDITIONS OF THE CODES AND STANDARDS.
3. THE STRUCTURAL DRAWINGS ARE INTENDED TO BE USED IN CONJUNCTION WITH THE ARCHITECTURAL AND ALL OTHER APPLICABLE DISCIPLINE DRAWINGS. IN CASE OF CONFLICT BETWEEN THE NOTES, DETAILS, AND SPECIFICATIONS, THE MOST RIGID REQUIREMENTS SHALL GOVERN. IF THERE IS A DISCREPANCY BETWEEN DRAWINGS, IT IS THE CONTRACTOR'S RESPONSIBILITY TO NOTIFY THE DESIGNER'S OF RECORD PRIOR TO PERFORMING THE WORK.
4. ALL SECTIONS AND DETAILS, WHETHER EXPLICITLY CUT ON PLAN OR NOT, SHALL BE CONSIDERED TYPICAL AND APPLY AT SIMILAR CONDITIONS. MINOR DETAILS OR INCIDENTAL ITEMS NOT SHOWN OR SPECIFIED, BUT NECESSARY FOR A PROPER AND COMPLETE INSTALLATION SHALL BE INCLUDED IN THE WORK AT NO ADDITIONAL COST. SIGNIFICANT ADJUSTMENTS ACCOUNTING FOR VARYING CONDITIONS IN THE FIELD SHOULD BE SUBMITTED TO THE DESIGNER'S OF
RECORD FOR APPROVAL AND BE RESOLVED PRIOR TO BEGINNING WORK.
5. GENERAL CONTRACTOR'S RESPONSIBILITIES:
A. THE CONTRACTOR SHALL NOT MAKE DEVIATIONS FROM THE DESIGN DOCUMENTS WITHOUT WRITTEN APPROVAL FROM THE DESIGNER'S OF RECORD.
CHANGES BY THE CONTRACTOR, DUE TO CONTRACTOR PROPOSED ALTERNATIVES OR TO CORRECT CONTRACTOR ERRORS/OMISSIONS, MUST BE SUBMITTED TO THE DESIGNER'S OF RECORD FOR APPROVAL. THE CONTRACTOR IS RESPONSIBLE FOR ALL COSTS, INCLUDING ENGINEERING FEES FOR REVIEW, SITE OBSERVATIONS, STRUCTURAL CALCULATIONS AND DRAWING REVISIONS. THE CONTRACTOR SHALL ALSO PROCESS THE REVISED PLANS REFLECTING ALL SUBSTITUTIONS THROUGH THE APPROPRIATE OFFICE OF ALL GOVERNING AGENCIES.
B. THE CONTRACTOR SHALL ASSUME SOLE AND COMPLETE RESPONSIBILITY FOR JOB SITE CONDITIONS DURING THE COURSE OF CONSTRUCTION OF THIS PROJECT, INCLUDING THE SAFETY OF ALL PERSONS AND PROPERTY. THIS REQUIREMENT SHALL APPLY CONTINUOUSLY AND NOT BE LIMITED TO NORMAL WORKING HOURS. THE CONTRACTOR SHALL DEFEND, INDEMNIFY, AND HOLD THE ENGINEER FREE AND HARMLESS OF LIABILITY, REAL OR ALLEGED, IN CONNECTION WITH THE PERFORMANCE OF WORK ON THE PROJECT, EXCEPT FOR LIABILITY ARISING FROM THE SOLE NEGLIGENCE OF THE ENGINEER.
C. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK AND COORDINATION INVOLVED TO PROVIDE OPENINGS, CHASES, CONCRETE HOUSEKEEPING PADS, INSERTS, SLEEVES AND DEPRESSIONS INDICATED ON THE ARCHITECTURAL, STRUCTURAL, MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS.
OPENINGS SHOWN ON THE STRUCTURAL DRAWINGS SHALL NOT BE REVISED WITHOUT APPROVAL FROM THE ENGINEER.
D. IT IS THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THAT THE WEIGHT OF SUPERIMPOSED DEAD LOADS RESULTING FROM MEP EQUIPMENT INSTALLED IN THE FIELD DOES NOT EXCEED THE ALLOWABLE MEP LOADS DESIGNATED ON THE LOAD MAPS AND PLANS. THE CONTRACTOR SHALL NOTIFY THE STRUCTURAL ENGINEER IF THE WEIGHT OF PROVIDED MEP EQUIPMENT EXCEEDS THAT SHOWN ON THE LOAD MAPS AND PLANS AND PROVIDE
REINFORCING AS NECESSARY AT HIS/HER OWN EXPENSE.
E. THE CONTRACTOR SHALL VISIT THE SITE AND VERIFY AND ESTABLISH ALL EXISTING SITE CONDITIONS, DIMENSIONS, ELEVATIONS AND LOCATE ALL UTILITIES PRIOR TO STARTING ANY CONSTRUCTION. IF THE EXISTING FIELD CONDITIONS DO NOT PERMIT THE INSTALLATION OF THE WORK IN ACCORDANCE WITH THE DETAILS SHOWN, THE CONTRACTOR SHALL NOTIFY THE DESIGNER'S OF RECORD IMMEDIATELY AND PROVIDE A SKETCH OF THE CONDITION WITH HIS/HER PROPOSED MODIFICATION OF THE DETAILS FOR APPROVAL PRIOR TO COMMENCING WORK. FAILURE TO NOTIFY THE DESIGNER'S OF RECORD OF UNSATISFACTORY CONDITIONS CONSTITUTES ACCEPTANCE OF THE UNSATISFACTORY CONDITIONS.
F. THE CONTRACTOR SHALL VERIFY ALL EXISTING STRUCTURES RELATED TO THE PROJECT. STRUCTURAL MEMBERS IDENTIFIED ON THESE DRAWINGS AS EXISTING (EXST) WERE OBTAINED DURING LIMITED FIELD OBSERVATIONS AND/OR FROM LIMITED EXISTING DRAWINGS (IF AVAILABLE.) ACTUAL CONDITIONS MAY DIFFER FROM THAT WHICH IS INDICATED ON THE PLANS AND DETAILS. IF FIELD CONDITIONS VARY FROM THOSE SHOWN ON THESE DRAWINGS, THE CONTRACTOR SHALL CONTACT THE DESIGNER'S OF RECORD IMMEDIATELY. ALL FIELD DIMENSIONS ARE TO BE VERIFIED AND NOTED AS
SUCH ON SHOP DRAWINGS PRIOR TO FABRICATION OF ANY NEW STRUCTURAL MEMBERS.
G. WHERE PROPOSED WORK INVOLVES ALTERATIONS OF THE EXISTING SUPPORTING STRUCTURE, THE CONTRACTOR SHALL PROVIDE TEMPORARY SHORING AND PROTECTION REQUIRED TO ENSURE THE STRUCTURAL INTEGRITY OF THE EXISTING STRUCTURE.
H. THE CONTRACTOR SHALL ASSUME SOLE AND COMPLETE RESPONSIBILITY FOR SAFEGUARDS DURING CONSTRUCTION, AS REQUIRED PER THE APPLICABLE EDITION OF THE INTERNATIONAL BUILDING CODE AS WELL AS ALL APPLICABLE FEDERAL, STATE, AND LOCAL CODES. WHERE ADDITIONAL ENGINEERING SERVICES OUTSIDE THE SCOPE OF THESE CONSTRUCTION DOCUMENTS ARE REQUIRED AS PART OF SAFEGUARDS DURING CONSTRUCTION, THE
CONTRACTOR SHALL NOTIFY THE OWNER AND ENGINEER PRIOR TO CONSTRUCTION COMMENCING.
6. THE STRUCTURAL DRAWINGS SHALL GOVERN THE WORK FOR ALL STRUCTURAL FEATURES, UNLESS NOTED OTHERWISE. THE ARCHITECTURAL DRAWINGS SHALL GOVERN THE WORK FOR ALL DIMENSIONS AND INFORMATION NOT SHOWN. WORKING DIMENSIONS SHALL NOT BE SCALED FROM STRUCTURAL PLANS, SECTIONS, OR DETAILS. ANY REFERENCE TO WATERPROOFING AND FIREPROOFING ON THE STRUCTURAL DRAWINGS ARE FOR REFERENCE ONLY, REFER TO
THE ARCHITECTURAL DRAWINGS FOR SPECIFIC REQUIREMENTS.
7. THE STRUCTURAL DRAWINGS ARE ONLY INTENDED TO CONVEY THE REQUIREMENTS OF THE STRUCTURE DOCUMENTED IN THESE PLANS. THE STRUCTURAL DRAWINGS SHOULD NOT BE USED AS MEANS OF COORDINATING BETWEEN TRADES OR DISCIPLINES.
8. THE CONTRACTOR IS TO PROVIDE SUBMITTALS FOR ALL STRUCTURAL MATERIALS, TO THE DESIGNER'S OF RECORD FOR REVIEW PRIOR TO THE START OF
FABRICATION OR THE COMMENCEMENT OF WORK.
A. REPRODUCTION OF ANY PORTION OF THE STRUCTURAL CONTRACT DRAWINGS FOR RE-SUBMITTAL AS SHOP DRAWINGS IS PROHIBITED AND SUBMITTAL
OF SUCH DRAWINGS WILL BE REJECTED AND RETURNED.
B. SUBMITTALS SHALL BEAR THE CONTRACTOR'S STAMP OF APPROVAL WHICH CONSTITUTES CERTIFICATION THAT THE CONTRACTOR HAS VERIFIED ALL CONSTRUCTION CRITERIA, MATERIALS, AND SIMILAR DATA AND HAS CHECKED EACH DRAWING FOR COMPLETENESS, COORDINATION, AND…