This is a Design Development 50% fire protection calculations submittal for a sprinkler system replacement project at Ralph H. Johnson VA Medical Center in Charleston, South Carolina. The project is identified as Project No. 534-23-105 under Contract No. 36C77625D0020, Task Order No. 36C24726N0187, and was prepared by GDM-AE, Inc. as of June 26, 2026.
The calculations document comprehensive hydraulic analysis for a Light Hazard fire protection system serving the Radiology area with a 1,500 square foot application area at 0.10 GPM/SF density. The system requires 112.65 GPM at -77.20 psi from one water supply node and 365.96 GPM at -82.63 psi from a second supply node, with 100 GPM hose stream allowance included. Two fire protection pumps are specified: Node 10 rated at 780 GPM @ 108 psi (churn pressure 116 psi) and Node 12 rated at 1,100 GPM @ 105 psi (churn pressure 120 psi). The system utilizes 16 sprinklers with K-factor 5.6, ranging from 14.82 to 26.72 GPM individual flows at pressures between 7.00 and 22.76 psi. Friction loss calculations employ the Hazen-Williams method with C-factors of 100 and 120, featuring multiple pipe sizes from 1" to 9" schedule 40 steel pipe with various fittings and equivalent lengths documented throughout the distribution network.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Design Development 50% DD Submittal: Fire Protection Calculations June 26, 2026
Department of Veterans Health Administration
Ralph H. Johnson VA Health Care System
Replace Sprinklers & Ceilings
Project No. 534-23-105
Contract No. 36C77625D0020
Task Order No. 36C24726N0187
Ralph H. Johnson VA Medical Center 109 Bee Street Charleston, SC 29401
Prepared by:
GDM-AE, Inc.
GDM-AE, INC.
1308 NE 134th Street, Suite A Vancouver, WA 98685 P: 541.436.4723
Location: , , Project Name:
Drawing Name: Charleston Fire Model Calculation Date:6/26/2026
Hydraulic Calculations Summary for
Design
Light Hazard
RADIOLOGY RA LIGHT HAZARD
0.10 GPM/SF
Remote Area Name:
Occupancy Classification:
Density
Area of Application: 1500.00 SF (Actual Area: 1500.00 SF)
Coverage per Sprinkler:
Type of Sprinklers Calculated:
No. of Sprinklers Calculated:
100.00 SF (typical)
at Node:
Fire Protection Wet
N/AN/A
18100.00 GPM
0.0 galType of System:
In-rack Demand:
Hose Streams:
Volume of Dry or PreAction System:
at Node:
Type Allowance at Source
Total Water Required (including Hose Streams where applicable)
-77.20 psi@112.65 GPMFROM: Water Supply at Node 18:
115.92 psiSafety Margin:
-82.63 psi@365.96 GPMFROM: Water Supply at Node 1:
115.92 psiSafety Margin:
27.45 psi@12.65 GPMPump at Node: 10:
115.92 psiSafety Margin:
35.08 psi@265.96 GPMPump at Node: 12:
115.92 psiSafety Margin:
Hazen-Williams
None.
Applied Friction Loss Method:
Darcy-Weisbach Suppression Agent:
REPLACE CEILINGS & SPRINKLERS
Contact Name
Address:
Phone Number:
Authority Having Jurisdiction:
Name of Designer:
6/26/2026 Page 1AutoSPRINK RVT v8.3.14.0 3:46:09PMRADIOLOGY RA LIGHT HAZARD@ M.E.P.CAD
Location: , , Project Name:
Drawing Name: Charleston Fire Model Calculation Date:6/26/2026
Hydraulic Calculations Summary for
Automatic Peaking Results
Notes:
6/26/2026 Page 2AutoSPRINK RVT v8.3.14.0 3:46:09PMRADIOLOGY RA LIGHT HAZARD@ M.E.P.CAD
Hydraulic Graph
Water Supply
Node: 18
Job Name:
Remote Area Name: RADIOLOGY RA LIGHT HAZARD Date: 6/26/2026 N 1.85
Summary Sheet
No pressure is being required from the Source/Supply to meet the demand (by a margin of this negative value).
A negative result in Required Pressure indicates that the Pump is capable of furnishing all of the pressure required by the demand reported within this calculation.
6/26/2026 Page 1AutoSPRINK RVT v8.3.14.0 3:46:10PM@ M.E.P.CAD
Water Supply
Node: 1
Job Name:
Remote Area Name: RADIOLOGY RA LIGHT HAZARD Date: 6/26/2026 N 1.85
Summary Sheet
No pressure is being required from the Source/Supply to meet the demand (by a margin of this negative value).
A negative result in Required Pressure indicates that the Pump is capable of furnishing all of the pressure required by the demand reported within this calculation.
6/26/2026 Page 2AutoSPRINK RVT v8.3.14.0 3:46:10PM@ M.E.P.CAD
Pump
Node: 12
Job Name:
Remote Area Name: RADIOLOGY RA LIGHT HAZARD Date: 6/26/2026 N 1.85
1100.00 GPM @ 105.00 psi Static:39.00 psi
Residual:25.00 psi
Flowing:513.00 GPM
Summary Sheet
Pump Rating: Supply:
No pressure is being required from the Source/Supply to meet the demand (by a margin of this negative value).
A negative result in Required Pressure indicates that the Pump is capable of furnishing all of the pressure required by the demand reported within this calculation.
6/26/2026 Page 3AutoSPRINK RVT v8.3.14.0 3:46:10PM@ M.E.P.CAD
Pump
Node: 10
Job Name:
Remote Area Name: RADIOLOGY RA LIGHT HAZARD Date: 6/26/2026 N 1.85
780.00 GPM @ 108.00 psi Static:39.00 psi
Residual:25.00 psi
Flowing:513.00 GPM
Summary Sheet
Pump Rating: Supply:
No pressure is being required from the Source/Supply to meet the demand (by a margin of this negative value).
A negative result in Required Pressure indicates that the Pump is capable of furnishing all of the pressure required by the demand reported within this calculation.
6/26/2026 Page 4AutoSPRINK RVT v8.3.14.0 3:46:10PM@ M.E.P.CAD
(GPM) (GPM) (K) (psi)
Outflowing Devices Report Description: Light Hazard
Job Number: N/A
Device
Actual Flow Minimum Flow K-Factor Pressure
Sprinkler 101 15.61 GPM 14.82 GPM 5.6 7.77 psi
Sprinkler 102 15.40 GPM 14.82 GPM 5.6 7.56 psi
Sprinkler 112 26.72 GPM 14.82 GPM 5.6 22.76 psi
Sprinkler 111 19.38 GPM 14.82 GPM 5.6 11.97 psi
Sprinkler 108 16.08 GPM 14.82 GPM 5.6 8.25 psi
Sprinkler 106 17.70 GPM 14.82 GPM 5.6 9.99 psi
Sprinkler 104 16.88 GPM 14.82 GPM 5.6 9.09 psi
Sprinkler 109 15.59 GPM 14.82 GPM 5.6 7.75 psi
Sprinkler 107 16.41 GPM 14.82 GPM 5.6 8.59 psi
Sprinkler 105 16.18 GPM 14.82 GPM 5.6 8.35 psi
Sprinkler 110 20.13 GPM 14.82 GPM 5.6 12.92 psi
Sprinkler 103 15.70 GPM 14.82 GPM 5.6 7.86 psi
Sprinkler 102 14.88 GPM 14.82 GPM 5.6 7.06 psi
Sprinkler 101 14.82 GPM 14.82 GPM 5.6 7.00 psi
Sprinkler 104 15.95 GPM 14.82 GPM 5.6 8.11 psi
Sprinkler 104 21.20 GPM 14.82 GPM 5.6 14.33 psi
Most Demanding Sprinkler Data
6/26/2026 Page 1AutoSPRINK RVT v8.3.14.0 3:46:10PM@ M.E.P.CAD
Job Name:
Remote Area Name: RADIOLOGY RA LIGHT HAZARD Date: 6/26/2026
(psi) (psi)(GPM)(psi)(GPM)(psi)
Supply Analysis
Node Name Static Residual Flow Available Total Demand Required Pressure
25.00 psi18 -77.20 psi112.65 GPM513.00 GPM 38.71 psi39.00 psiWater Supply
25.00 psi1 -82.63 psi365.96 GPM513.00 GPM 33.29 psi39.00 psiWater Supply
@ @Churn
(psi)
Residual
(psi)
Flow
(GPM)
Available
(psi)
Total Demand
(GPM)
Required Pressure
(psi)
Pump Analysis
Node
10 116.00 psi 108.00 psi 780.00 GPM 143.37 psi 12.65 GPM 27.45 psi
12 120.00 psi 105.00 psi 1100.00 GPM 151.00 psi 265.96 GPM 35.08 psi
Node Analysis
Discharge at
Node
(GPM)
Pressure at
Node
(psi)
Elevation (ft)Node Number Node Type Notes
-8' - 6" 12.65 GPM-77.20 psi18 Supply
0' - 0" 265.96 GPM-82.63 psi1 Supply
18' - 10" 15.61 GPM7.77 psi101 Sprinklers
18' - 10 3/8" 14.82 GPM7.00 psi101 Sprinklers
18' - 10" 15.40 GPM7.56 psi102 Sprinklers
18' - 10 3/8" 14.88 GPM7.06 psi102 Sprinklers
18' - 10 3/8" 15.70 GPM7.86 psi103 Sprinklers
18' - 10" 16.88 GPM9.09 psi104 Sprinklers
18' - 10 3/8" 15.95 GPM8.11 psi104 Sprinklers
18' - 10 3/8" 21.20 GPM14.33 psi104 Sprinklers
18' - 10" 16.18 GPM8.35 psi105 Sprinklers
18' - 10" 17.70 GPM9.99 psi106 Sprinklers
18' - 10" 16.41 GPM8.59 psi107 Sprinklers
18' - 10" 16.08 GPM8.25 psi108 Sprinklers
18' - 10" 15.59 GPM7.75 psi109 Sprinklers
6/26/2026 Page 1AutoSPRINK RVT v8.3.14.0 3:46:11PM@ M.E.P.CAD
Discharge at
Node
(GPM)
Pressure at
Node
(psi)
Elevation (ft)Node Number Node Type Notes
18' - 10" 20.13 GPM12.92 psi110 Sprinklers
18' - 10" 19.38 GPM11.97 psi111 Sprinklers
18' - 10" 26.72 GPM22.76 psi112 Sprinklers
-8' - 6" -77.20 psi2
-8' - 6" 38.81 psi3
-8' - 6" 38.51 psi4
-8' - 6" 38.10 psi5
-8' - 6" 38.81 psi6
-8' - 6" 38.81 psi8
-8' - 6" 39.18 psi9
17' - 8 1/2" 27.45 psi10
-8' - 6" 39.18 psi11
1' - 8 1/2" 35.08 psi12
17' - 7 13/32" -88.52 psi13
17' - 8 1/2" 27.45 psi14
18' - 6" 25.88 psi15
19' - 2 3/4" 25.95 psi17
-8' - 6" 38.12 psi19
19' - 6" 7.90 psi21
19' - 6" 7.86 psi22
19' - 6" 7.87 psi23
19' - 6" 7.70 psi24
19' - 6" 9.34 psi26
6/26/2026 Page 2AutoSPRINK RVT v8.3.14.0 3:46:11PM@ M.E.P.CAD
Discharge at
Node
(GPM)
Pressure at
Node
(psi)
Elevation (ft)Node Number Node Type Notes
19' - 6" 8.80 psi29
19' - 6" 8.56 psi30
19' - 6" 13.05 psi32
19' - 6" 10.29 psi33
19' - 6" 8.82 psi34
19' - 6" 9.23 psi35
19' - 6" 8.54 psi36
19' - 6" 7.68 psi37
19' - 6" 7.73 psi38
19' - 6" 13.37 psi39
-8' - 6" 39.34 psi40
0' - 0" -82.63 psi41
19' - 6" 23.09 psi42
1' - 7 13/32" -83.41 psi43
19' - 6" 25.55 psi44
1' - 8 1/2" 34.96 psi45
1' - 8 1/2" 35.07 psi46
7' - 1 5/16" -85.73 psi47
9' - 0 19/32" -86.62 psi48
18' - 6" 8.27 psi49
18' - 6" 8.27 psi50
18' - 6" 8.28 psi51
18' - 6" 8.29 psi52
6/26/2026 Page 3AutoSPRINK RVT v8.3.14.0 3:46:11PM@ M.E.P.CAD
Discharge at
Node
(GPM)
Pressure at
Node
(psi)
Elevation (ft)Node Number Node Type Notes
18' - 6" 25.37 psi53
-8' - 6" 38.44 psi54
-8' - 6" 38.45 psi55
-8' - 6" 38.43 psi56
19' - 6" 6.90 psi57
19' - 6" 7.86 psi58
19' - 6" 13.83 psi59
19' - 6" 14.11 psi60
19' - 6" 24.83 psi61
-8' - 6" 38.44 psi62
-8' - 6" 38.81 psi63
-8' - 6" 38.12 psi64
19' - 4 29/32" 22.64 psi65
19' - 6" 6.72 psi66
19' - 6" 25.86 psi67
19' - 6" 6.78 psi68
19' - 6" 7.58 psi69
19' - 6" 7.83 psi70
19' - 6" 9.61 psi71
19' - 6" 9.54 psi72
19' - 6" 9.50 psi73
19' - 6" 23.50 psi75
6/26/2026 Page 4AutoSPRINK RVT v8.3.14.0 3:46:11PM@ M.E.P.CAD
6/26/2026 Page 5AutoSPRINK RVT v8.3.14.0 3:46:11PM@ M.E.P.CAD
Date: 6/26/2026
Remote Area Name: RADIOLOGY RA LIGHT HAZARD
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction Loss
Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
3' - 0"
19' - 6" 3' - 7 5/8"
-0.28 psi
0.00 psi
18' - 10 3/8" 0' - 7 5/8"
1"
• • • • • Route 1 • • • • •
(See
Notes)
0"
7.00 psi
0.00 psi
Sprinkler,
14.82 GPM
5.6
T(3' - 0"), HW
0 FPS
14.82 GPM
8' - 0"
19' - 6" 19' - 0 11/32" 0.18 psi
19' - 6" 11' - 0 11/32"
2" (See
Notes)
2"
6.72 psi
0.01 psi14.82 GPM T(8' - 0"), Tr, HW
2 FPS
20' - 0"
18' - 6" 27' - 10 7/32"
0.43 psi
0.93 psi
19' - 6" 7' - 10 7/32"
2" (See
Notes)
2"
6.90 psi
0.03 psi
Flow (q) from Route 2
29.69 GPM 3E(4' - 0"), T(8' - 0"), HW
5 FPS
14.88 GPM
18' - 6" 1' - 0" 0.00 psi
18' - 6" 1' - 0"
3" (See
Notes)
3"
8.27 psi
0.00 psi29.69 GPM Tr, HW
2 FPS
18' - 6" 0' - 9 31/32" 0.01 psi
18' - 6" 0' - 9 31/32"
3" (See
Notes)
3"
8.27 psi
0.01 psi
Flow (q) from Route 6
45.39 GPM red, HW
3 FPS
15.70 GPM
6' - 0"
18' - 6" 13' - 3" 0.01 psi
18' - 6" 7' - 3"
4" (See
Notes)
4"
8.28 psi
0.00 psi45.39 GPM E(6' - 0"), HW
1 FPS
6' - 0"
19' - 6" 7' - 0"
-0.43 psi
0.00 psi
18' - 6" 1' - 0"
4" (See
Notes)
4"
8.29 psi
0.00 psi45.39 GPM E(6' - 0"), HW
1 FPS
6' - 0"
19' - 6" 17' - 4 17/32" 0.01 psi
19' - 6" 11' - 4 17/32"
4" (See
Notes)
4"
7.86 psi
0.00 psi45.39 GPM E(6' - 0"), Tr, HW
1 FPS
6' - 0"
19' - 6" 29' - 11 7/8" 0.03 psi
19' - 6" 23' - 11 7/8"
4" (See
Notes)
4"
7.87 psi
0.00 psi
Flow (q) from Route 5
61.01 GPM E(6' - 0"), Tr, HW
1 FPS
15.61 GPM
15' - 0"
19' - 6" 20' - 2 15/32" 1.64 psi
19' - 6" 5' - 2 15/32"
2" (See
Notes)
2"
7.90 psi
0.00 psi
Flow (q) from Route 3 and
92.35 GPM red, E(5' - 0"), T(10' - 0"), HW
9 FPS
15.40 GPM +
15.95 GPM
19' - 6" 5' - 9 23/32" 0.06 psi
19' - 6" 5' - 9 23/32"
3" (See
Notes)
3"
9.54 psi
0.01 psi
Flow (q) from Route 8
103.89 GPM , HW
4 FPS
11.54 GPM
6/26/2026 Page 1AutoSPRINK RVT v8.3.14.0 3:46:12PMRADIOLOGY RA LIGHT HAZARD@ M.E.P.CAD
Remote Area Name: RADIOLOGY RA LIGHT HAZARD
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction Loss
Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
12' - 0"
19' - 6" 47' - 9" 16.26 psi
19' - 6" 35' - 9"
2" (See
Notes)
2"
9.61 psi
0.34 psi
E(4' - 0")
103.89 GPM 2E(4' - 0"), HW
16 FPS
10' - 0"
-8' - 6" 38' - 0"
12.14 psi
0.11 psi
19' - 6" 28' - 0"
4" (See
Notes)
4"
25.86 psi
0.00 psi103.89 GPM E(10' - 0"), HW
2 FPS
30' - 0"
-8' - 6" 105' - 3 27/32" 0.32 psi
-8' - 6" 75' - 3 27/32"
4" (See
Notes)
4"
38.12 psi
0.00 psi103.89 GPM E(10' - 0"), T(20' - 0"), HW
2 FPS
49' - 0"
-8' - 6" 365' - 1 5/8" 0.38 psi
-8' - 6" 316' - 1 5/8"
5" (See
Notes)
5"
38.43 psi
0.00 psi77.23 GPM 4E(6' - 0"), T(25' - 0"), HW
1 FPS
-8' - 6" 0' - 0" 0.00 psi
-8' - 6" 0' - 0"
5" (See
Notes)
5"
38.81 psi
0.00 psi12.65 GPM red, HW
0 FPS
6' - 0"
-8' - 6" 36' - 9 15/32" 0.00 psi
-8' - 6" 30' - 9 15/32"
6" (See
Notes)
6"
38.81 psi
0.00 psi12.65 GPM E(6' - 0"), HW
0 FPS
24' - 0"
-8' - 6" 45' - 4 1/32" 0.00 psi
-8' - 6" 21' - 4 1/32"
6" (See
Notes)
6"
38.81 psi
0.00 psi12.65 GPM 4E(6' - 0"), HW
0 FPS
6' - 0"
17' - 8 1/2" 32' - 2 1/2"
-11.36 psi
0.00 psi
-8' - 6" 26' - 2 1/2"
6" (See
Notes)
6"
38.81 psi
0.00 psi12.65 GPM E(6' - 0"), HW
0 FPS
17' - 8 1/2" 0' - 8 25/32" 0.00 psi
17' - 8 1/2" 0' - 8 25/32"
6" (See
Notes)
6"
27.45 psi
0.00 psi12.65 GPM , HW
0 FPS
(See
Notes)
27.45 psi Rating: 108.00 psi @ 780.00
GPM
Churn Pressure: 116.00 psi0 FPS
12.65 GPM
18' - 0"
17' - 7 13/32" 21' - 3 23/32" 0.00 psi
17' - 7 15/16" 3' - 3 23/32"
8" (See
Notes)
9"
-88.52 psi
0.00 psi12.65 GPM E(18' - 0"), HW
0 FPS
6/26/2026 Page 2AutoSPRINK RVT v8.3.14.0 3:46:12PMRADIOLOGY RA LIGHT HAZARD@ M.E.P.CAD
Remote Area Name: RADIOLOGY RA LIGHT HAZARD
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction Loss
Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
18' - 0"
-8' - 6" 44' - 1 13/32"
11.32 psi
0.00 psi
17' - 7 13/32" 26' - 1 13/32"
8" (See
Notes)
9"
-88.52 psi
0.00 psi12.65 GPM E(18' - 0"), HW
0 FPS
-8' - 6" 17' - 10 21/32" 0.00 psi
-8' - 6" 17' - 10 21/32"
8" (See
Notes)
9"
-77.20 psi
0.00 psi12.65 GPM Water Supply, HW
0 FPS
Hose Allowance At Source
378.62 GPM
Route 1
-77.20 psi
Total(Pt)
100.00 GPM
3' - 0"
19' - 6" 3' - 7 5/8"
-0.28 psi
0.00 psi
18' - 10 3/8" 0' - 7 5/8"
1"
• • • • • Route 2 • • • • •
(See
Notes)
0"
7.06 psi
0.00 psi
Sprinkler,
14.88 GPM
5.6
T(3' - 0"), HW
0 FPS
14.88 GPM
8' - 0"
19' - 6" 12' - 8 11/16" 0.12 psi
19' - 6" 4' - 8 11/16"
2" (See
Notes)
2"
6.78 psi
0.01 psi14.88 GPM T(8' - 0"), HW
2 FPS
6.90 psi Route 2Total(Pt)
24' - 0"
19' - 6" 27' - 10 1/8"
-0.29 psi
0.63 psi
18' - 10" 3' - 10 1/8"
1"
• • • • • Route 3 • • • • •
(See
Notes)
1"
7.56 psi
0.08 psi
Flow (q) from Route 2
15.40 GPM
5.6
2E(2' - 0"), red, C(20' - 0"), HW
6 FPS
14.88 GPM
7.90 psi Route 3Total(Pt)
2' - 0"
19' - 6" 2' - 8"
-0.29 psi
0.22 psi
18' - 10" 0' - 8"
1"
• • • • • Route 4 • • • • •
(See
Notes)
1"
7.75 psi
0.08 psi
Sprinkler,
15.59 GPM
5.6
E(2' - 0"), HW
6 FPS
15.59 GPM
10' - 0"
19' - 6" 16' - 8 7/32" 0.05 psi
19' - 6" 6' - 8 7/32"
2" (See
Notes)
2"
7.68 psi
0.00 psi15.59 GPM T(10' - 0"), HW
1 FPS
5' - 0"
19' - 6" 13' - 3 7/16" 1.09 psi
19' - 6" 8' - 3 7/16"
1" (See
Notes)
1"
7.73 psi
0.08 psi15.59 GPM T(5' - 0"), HW
6 FPS
19' - 6" 13' - 6 9/32" 1.47 psi
19' - 6" 13' - 6 9/32"
1" (See
Notes)
1"
8.82 psi
0.11 psi
Flow (q) from Route 21
18.11 GPM Tr, HW
7 FPS
2.52 GPM
6/26/2026 Page 3AutoSPRINK RVT v8.3.14.0 3:46:12PMRADIOLOGY RA LIGHT HAZARD@ M.E.P.CAD
Remote Area Name: RADIOLOGY RA LIGHT HAZARD
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction Loss
Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
5' - 0"
19' - 6" 7' - 2 5/8" 2.76 psi
19' - 6" 2' - 2 5/8"
1" (See
Notes)
1"
10.29 psi
0.38 psi
Flow (q) from Route 12
35.81 GPM T(5' - 0"), HW
13 FPS
17.70 GPM
19' - 6" 9' - 9 1/4" 0.33 psi
19' - 6" 9' - 9 1/4"
2" (See
Notes)
2"
13.05 psi
0.03 psi
Flow (q) from Route 11
57.24 GPM Tr, HW
5 FPS
21.43 GPM
19' - 6" 7' - 10 1/2" 0.46 psi
19' - 6" 7' - 10 1/2"
2" (See
Notes)
2"
13.37 psi
0.06 psi
Flow (q) from Route 14
77.37 GPM Tr, HW
7 FPS
20.13 GPM
19' - 6" 3' - 1 5/16" 0.27 psi
19' - 6" 3' - 1 5/16"
2" (See
Notes)
2"
13.83 psi
0.09 psi
Flow (q) from Route 13
96.74 GPM Tr, HW
9 FPS
19.38 GPM
15' - 0"
19' - 6" 84' - 1 15/32" 10.73 psi
19' - 6" 69' - 1 15/32"
2" (See
Notes)
2"
14.11 psi
0.13 psi
Flow (q) from Route 15
117.94 GPM Tr, E(5' - 0"), T(10' - 0"), HW
11 FPS
21.20 GPM
6' - 0"
18' - 6" 7' - 0"
0.43 psi
0.10 psi
19' - 6" 1' - 0"
3" (See
Notes)
3"
24.83 psi
0.01 psi117.94 GPM E(6' - 0"), HW
5 FPS
18' - 0"
18' - 6" 36' - 8 5/32" 0.52 psi
18' - 6" 18' - 8 5/32"
3" (See
Notes)
3"
25.37 psi
0.01 psi117.94 GPM Tr, 3E(6' - 0"), HW
5 FPS
6' - 0"
19' - 6" 7' - 0"
-0.43 psi
0.10 psi
18' - 6" 1' - 0"
3" (See
Notes)
3"
25.88 psi
0.01 psi117.94 GPM E(6' - 0"), HW
5 FPS
12' - 0"
19' - 2 3/4" 20' - 6"
0.12 psi
0.29 psi
19' - 6" 8' - 6"
3" (See
Notes)
3"
25.55 psi
0.01 psi117.94 GPM UNK, 2E(6' - 0"), red, HW
5 FPS
6' - 0"
-8' - 6" 33' - 8 3/4"
12.02 psi
0.13 psi
19' - 2 3/4" 27' - 8 3/4"
4" (See
Notes)
4"
25.95 psi
0.00 psi117.94 GPM E(6' - 0"), HW
3 FPS
-8' - 6" 3' - 4 3/4" 0.01 psi
-8' - 6" 3' - 4 3/4"
4" (See
Notes)
4"
38.10 psi
0.00 psi117.94 GPM , HW
3 FPS
6/26/2026 Page 4AutoSPRINK RVT v8.3.14.0 3:46:12PMRADIOLOGY RA LIGHT HAZARD@ M.E.P.CAD
Remote Area Name: RADIOLOGY RA LIGHT HAZARD
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction Loss
Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
38' - 0"
-8' - 6" 73' - 2 1/16" 0.39 psi
-8' - 6" 35' - 2 1/16"
4" (See
Notes)
4"
38.12 psi
0.01 psi
E(6' - 0")
117.94 GPM 2E(6' - 0"), T(20' - 0"), HW
3 FPS
37' - 0"
-8' - 6" 110' - 1 25/32" 0.68 psi
-8' - 6" 73' - 1 25/32"
5" (See
Notes)
5"
38.51 psi
0.01 psi
Flow (q) from Route 9
201.39 GPM 2E(6' - 0"), T(25' - 0"), HW
3 FPS
83.45 GPM
6' - 0"
-8' - 6" 47' - 7 7/16" 0.16 psi
-8' - 6" 41' - 7 7/16"
6" (See
Notes)
6"
39.18 psi
0.00 psi
Flow (q) from Route 17
265.96 GPM E(6' - 0"), HW
3 FPS
64.58 GPM
6' - 0"
1' - 8 1/2" 16' - 2 1/2"
-4.43 psi
0.04 psi
-8' - 6" 10' - 2 1/2"
6" (See
Notes)
6"
39.34 psi
0.00 psi265.96 GPM E(6' - 0"), HW
3 FPS
6' - 0"
1' - 8 1/2" 47' - 0 15/16" 0.11 psi
1' - 8 1/2" 41' - 0 15/16"
6" (See
Notes)
6"
34.96 psi
0.00 psi265.96 GPM E(6' - 0"), HW
3 FPS
1' - 8 1/2" 1' - 11" 0.01 psi
1' - 8 1/2" 1' - 11"
6" (See
Notes)
6"
35.07 psi
0.00 psi265.96 GPM , HW
3 FPS
(See
Notes)
35.08 psi Rating: 105.00 psi @ 1100.00
GPM
Churn Pressure: 120.00 psi2 FPS
265.96 GPM
14' - 4 31/32"
1' - 7 13/32" 15' - 5 21/32" 0.02 psi
1' - 7 15/16" 1' - 0 11/16"
8" (See
Notes)
8"
-83.43 psi
0.00 psi265.96 GPM E(14' - 4 31/32"), HW
2 FPS
14' - 4 31/32"
9' - 0 19/32" 21' - 10 5/32"
-3.22 psi
0.02 psi
1' - 7 13/32" 7' - 5 3/16"
8" (See
Notes)
8"
-83.41 psi
0.00 psi265.96 GPM UNK, 2Tr, E(14' - 4 31/32"), HW
2 FPS
28' - 9 29/32"
7' - 1 5/16" 39' - 3 1/4"
0.84 psi
0.04 psi
9' - 0 19/32" 10' - 5 5/16"
8" (See
Notes)
8"
-86.62 psi
0.00 psi265.96 GPM 2E(14' - 4 31/32"), HW
2 FPS
14' - 4 31/32"
0' - 0" 21' - 2 3/4"
3.08 psi
0.02 psi
7' - 1 5/16" 6' - 9 25/32"
8" (See
Notes)
8"
-85.73 psi
0.00 psi265.96 GPM UNK, E(14' - 4 31/32"), HW
2 FPS
6/26/2026 Page 5AutoSPRINK RVT v8.3.14.0 3:46:12PMRADIOLOGY RA LIGHT HAZARD@ M.E.P.CAD
Remote Area Name: RADIOLOGY RA LIGHT HAZARD
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction Loss
Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
0' - 0" 10' - 8" 0.01 psi
0' - 0" 10' - 8"
8" (See
Notes)
9"
-82.63 psi
0.00 psi265.96 GPM Water Supply, HW
1 FPS
-82.63 psi Route 4Total(Pt)
2' - 0"
19' - 6" 2' - 8"
-0.29 psi
0.22 psi
18' - 10" 0' - 8"
1"
• • • • • Route 5 • • • • •
(See
Notes)
1"
7.77 psi
0.08 psi
Flow (q) from Route 1
15.61 GPM
5.6
E(2' - 0"), HW
6 FPS
14.82 GPM
12' - 0"
19' - 6" 15' - 4 27/32" 0.16 psi
19' - 6" 3' - 4 27/32"
2" (See
Notes)
2"
7.70 psi
0.01 psi15.61 GPM T(8' - 0"), E(4' - 0"), HW
2 FPS
15' - 0"
19' - 6" 24' - 2" 0.01 psi
19' - 6" 9' - 2"
3" (See
Notes)
3"
7.86 psi
0.00 psi15.61 GPM UNK, T(15' - 0"), HW
1 FPS
7.87 psi Route 5Total(Pt)
3' - 0"
19' - 6" 3' - 7 5/8"
-0.28 psi
0.00 psi
18' - 10 3/8" 0' - 7 5/8"
1"
• • • • • Route 6 • • • • •
(See
Notes)
0"
7.86 psi
0.00 psi
Sprinkler,
15.70 GPM
5.6
T(3' - 0"), HW
0 FPS
15.70 GPM
16' - 0"
18' - 6" 24' - 8 25/32"
0.43 psi
0.26 psi
19' - 6" 8' - 8 25/32"
2" (See
Notes)
2"
7.58 psi
0.01 psi15.70 GPM 2E(4' - 0"), T(8' - 0"), HW
2 FPS
8.27 psi Route 6Total(Pt)
3' - 0"
19' - 6" 3' - 7 5/8"
-0.28 psi
0.00 psi
18' - 10 3/8" 0' - 7 5/8"
1"
• • • • • Route 7 • • • • •
(See
Notes)
0"
8.11 psi
0.00 psi
Sprinkler,
15.95 GPM
5.6
T(3' - 0"), HW
0 FPS
15.95 GPM
20' - 0"
19' - 6" 26' - 3 1/16" 0.07 psi
19' - 6" 6' - 3 1/16"
2" (See
Notes)
2"
7.83 psi
0.01 psi15.95 GPM red, C(20' - 0"), HW
3 FPS
7.90 psi Route 7Total(Pt)
9' - 0"
19' - 6" 14' - 7 1/4"
-0.29 psi
1.27 psi
18' - 10" 5' - 7 1/4"
1"
• • • • • Route 8 • • • • •
(See
Notes)
1"
8.25 psi
0.09 psi
Sprinkler,
16.08 GPM
5.6
2E(2' - 0"), T(5' - 0"), HW
6 FPS
16.08 GPM
6/26/2026 Page 6AutoSPRINK RVT v8.3.14.0 3:46:12PMRADIOLOGY RA LIGHT HAZARD@ M.E.P.CAD
Remote Area Name: RADIOLOGY RA LIGHT HAZARD
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction Loss
Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
4' - 0"
19' - 6" 5' - 8 19/32" 0.27 psi
19' - 6" 1' - 8 19/32"
1" (See
Notes)
1"
9.23 psi
0.05 psi11.54 GPM 2E(2' - 0"), HW
4 FPS
10' - 0"
19' - 6" 25' - 1 7/8" 0.04 psi
19' - 6" 15' - 1 7/8"
2" (See
Notes)
2"
9.50 psi
0.00 psi11.54 GPM T(10' - 0"), HW
1 FPS
9.54 psi Route 8Total(Pt)
5' - 0"
19' - 6" 5' - 8"
-0.29 psi
0.50 psi
18' - 10" 0' - 8"
1"
• • • • • Route 9 • • • • •
(See
Notes)
1"
8.35 psi
0.09 psi
Sprinkler,
16.18 GPM
5.6
T(5' - 0"), HW
6 FPS
16.18 GPM
15' - 0"
19' - 6" 20' - 8 25/32" 0.24 psi
19' - 6" 5' - 8 25/32"
2" (See
Notes)
2"
8.56 psi
0.01 psi
Flow (q) from Route 10
32.59 GPM E(5' - 0"), T(10' - 0"), HW
3 FPS
16.41 GPM
4' - 0"
19' - 6" 51' - 7 3/4" 14.29 psi
19' - 6" 47' - 7 3/4"
1" (See
Notes)
1"
8.80 psi
0.28 psi30.07 GPM 2E(2' - 0"), 2Tr, HW
11 FPS
19' - 6" 0' - 5 13/32" 0.40 psi
19' - 6" 0' - 5 13/32"
1" (See
Notes)
1"
23.09 psi
0.90 psi
Flow (q) from Route 16
56.79 GPM red, HW
21 FPS
26.72 GPM
25' - 0"
-8' - 6" 85' - 3 3/32"
12.14 psi
2.81 psi
19' - 6" 60' - 3 3/32"
2" (See
Notes)
2"
23.50 psi
0.03 psi56.79 GPM 3E(5' - 0"), T(10' - 0"), HW
5 FPS
6' - 0"
-8' - 6" 49' - 7 9/16" 0.06 psi
-8' - 6" 43' - 7 9/16"
5" (See
Notes)
5"
38.45 psi
0.00 psi
Flow (q) from Route 19
83.45 GPM E(6' - 0"), Tr, HW
1 FPS
26.66 GPM
38.51 psi Route 9Total(Pt)
2' - 0"
19' - 6" 2' - 8"
-0.29 psi
0.24 psi
18' - 10" 0' - 8"
1"
• • • • • Route 10 • • • • •
(See
Notes)
1"
8.59 psi
0.09 psi
Sprinkler,
16.41 GPM
5.6
E(2' - 0"), HW
6 FPS
16.41 GPM
19' - 6" 5' - 0" 0.02 psi
19' - 6" 5' - 0"
2" (See
Notes)
2"
8.54 psi
0.00 psi16.41 GPM Tr, HW
2 FPS
6/26/2026 Page 7AutoSPRINK RVT v8.3.14.0 3:46:12PMRADIOLOGY RA LIGHT HAZARD@ M.E.P.CAD
Remote Area Name: RADIOLOGY RA LIGHT HAZARD
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction Loss
Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
8.56 psi Route 10Total(Pt)
5' - 0"
19' - 6" 5' - 8"
-0.29 psi
0.54 psi
18' - 10" 0' - 8"
1"
• • • • • Route 11 • • • • •
(See
Notes)
1"
9.09 psi
0.10 psi
Flow (q) from Route 7
16.88 GPM
5.6
T(5' - 0"), HW
6 FPS
15.95 GPM
13' - 0"
19' - 6" 25' - 0 25/32" 3.71 psi
19' - 6" 12' - 0 25/32"
1" (See
Notes)
1"
9.34 psi
0.15 psi
Flow (q) from Route 20
21.43 GPM 4E(2' - 0"), T(5' - 0"), HW
8 FPS
4.54 GPM
13.05 psi Route 11Total(Pt)
5' - 0"
19' - 6" 5' - 8"
-0.29 psi
0.59 psi
18' - 10" 0' - 8"
1"
• • • • • Route 12 • • • • •
(See
Notes)
1"
9.99 psi
0.10 psi
Sprinkler,
17.70 GPM
5.6
T(5' - 0"), HW
7 FPS
17.70 GPM
10.29 psi Route 12Total(Pt)
7' - 0"
19' - 6" 17' - 6 7/32"
-0.29 psi
2.15 psi
18' - 10" 10' - 6 7/32"
1"
• • • • • Route 13 • • • • •
(See
Notes)
1"
11.97 psi
0.12 psi
Sprinkler,
19.38 GPM
5.6
E(2' - 0"), T(5' - 0"), HW
7 FPS
19.38 GPM
13.83 psi Route 13Total(Pt)
5' - 0"
19' - 6" 5' - 8"
-0.29 psi
0.75 psi
18' - 10" 0' - 8"
1"
• • • • • Route 14 • • • • •
(See
Notes)
1"
12.92 psi
0.13 psi
Sprinkler,
20.13 GPM
5.6
T(5' - 0"), HW
7 FPS
20.13 GPM
13.37 psi Route 14Total(Pt)
10' - 0"
19' - 6" 10' - 7 5/8"
-0.28 psi
0.06 psi
18' - 10 3/8" 0' - 7 5/8"
2"
• • • • • Route 15 • • • • •
(See
Notes)
2"
14.33 psi
0.01 psi
Flow (q) from Route 11
21.20 GPM
5.6
T(10' - 0"), HW
2 FPS
16.88 GPM
14.11 psi Route 15Total(Pt)
19' - 4 29/32" 0' - 6 29/32"
-0.25 psi
0.13 psi
18' - 10" 0' - 6 29/32"
1"
• • • • • Route 16 • • • • •
(See
Notes)
1"
22.76 psi
0.22 psi
Sprinkler,
26.72 GPM
5.6 red, HW
10 FPS
26.72 GPM
17' - 0"
19' - 6" 52' - 6 3/16"
-0.04 psi
0.49 psi
19' - 4 29/32" 35' - 6 3/16"
3" (See
Notes)
3"
22.64 psi
0.22 psi26.72 GPM E(2' - 0"), T(15' - 0"), HW
1 FPS
6/26/2026 Page 8AutoSPRINK RVT v8.3.14.0 3:46:12PMRADIOLOGY RA LIGHT HAZARD@ M.E.P.CAD
Remote Area Name: RADIOLOGY RA LIGHT HAZARD
Flow added this step
Pipe Information
Node 1
Node 2
Elev 1 ft
Elev 2 ft
K-Factor
Q
Total Flow
Q
Nominal ID
Actual ID
Fittings &
Devices
Equiv.
Length ft
Length ft
Fitting ft
Total ft
C Factor or
Roughness
Pf Friction Loss
Per Unit psi
Total(Pt)
Elev(Pe)
Friction(Pf)
Notes
Fitting/Device (Equivalent Length)
Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value.
Velocity
23.09 psi Route 16Total(Pt)
6' - 0"
-8' - 6" 23' - 2 19/32" 0.01 psi
-8' - 6" 17' - 2 19/32"
6"
• • • • • Route 17 • • • • •
(See
Notes)
6"
39.18 psi
0.00 psi
Flow (q) from Route 18
64.58 GPM E(6' - 0"), Tr, HW
1 FPS
64.58 GPM
39.18 psi Route 17Total(Pt)
48' - 0"
-8' - 6" 485' - 0" 0.36 psi
-8' - 6" 437' - 0"
5"
• • • • • Route 18 • • • • •
(See
Notes)
5"
38.81 psi
0.00 psi
Flow (q) from Route 1
64.58 GPM 8E(6' - 0"), red, HW
1 FPS
12.65 GPM
39.18 psi Route 18Total(Pt)
6' - 0"
-8' - 6" 63' - 10 3/8" 0.01 psi
-8' - 6" 57' - 10 3/8"
5"
• • • • • Route 19 • • • • •
(See
Notes)
5"
38.43 psi
0.00 psi
Flow (q) from Route 1
26.66 GPM E(6' - 0"), HW
0 FPS
77.23 GPM
6' - 0"
-8' - 6" 7' - 6" 0.00 psi
-8' - 6" 1' - 6"
5" (See
Notes)
5"
38.44 psi
0.00 psi26.66 GPM E(6' - 0"), HW
0 FPS
-8' - 6" 24' - 1 1/32" 0.00 psi
-8' - 6" 24' - 1 1/32"
5" (See
Notes)
5"
38.44 psi
0.00 psi26.66 GPM Tr, HW
0 FPS
38.45 psi Route 19Total(Pt)
2' - 0"
19' - 6" 13' - 3 11/32" 0.11 psi
19' - 6" 11' - 3 11/32"
1"
• • • • • Route 20 • • • • •
(See
Notes)
1"
9.23 psi
0.01 psi
Flow (q) from Route 8
4.54 GPM E(2' - 0"), Tr, HW
2 FPS
11.54 GPM
9.34 psi Route 20Total(Pt)
5' - 0"
19' - 6" 6' - 5 13/16" 0.02 psi
19' - 6" 1' - 5 13/16"
1"
• • • • • Route 21 • • • • •
(See
Notes)
1"
8.80 psi
0.00 psi
Flow (q) from Route 9
2.52 GPM T(5' - 0"), HW
1 FPS
30.07 GPM
8.82 psi Route 21Total(Pt)
6/26/2026 Page 9AutoSPRINK RVT v8.3.14.0 3:46:12PMRADIOLOGY RA LIGHT HAZARD@ M.E.P.CAD
Remote Area Name: RADIOLOGY RA LIGHT HAZARD
1.51
Notes Legend
C Cross Flow Turn 90° E 90° Elbow HW Hazen-Williams red Reducer/Adapter S Supply Spr Sprinkler
T Tee Flow Turn 90° Tr Tee run UNK Undefined Accessory
4.87
1.33
1.16
0.713
Equivalent Pipe Lengths of Valves and Fittings (C=120 only)
Actual Inside Diameter
Schedule 40 Steel Pipe Inside Diameter = Factor
C Value Multiplier
Value Of C
Multiplying Factor
6/26/2026 Page 10AutoSPRINK RVT v8.3.14.0 3:46:12PMRADIOLOGY RA LIGHT HAZARD@ M.E.P.CAD
Pressure(psi) K-Factor(K) Flow(GPM)
Check Point Gauge Data Report Description: Light Hazard
Job Number: N/A
Inlet Static Pressure(psi) Elevation(ft)Gauge
6/26/2026 Page 1AutoSPRINK RVT v8.3.14.0 3:46:12PM@ M.E.P.CAD
File details come from the government source that posted it. Updated .