Final_Permit_(P119R1M3).pdf
PDF 675 KB Posted
- Attached to
- ID07180031-Cannon/Holloman AFB Fence to Fence
- Solicitation number
- ID07180031
- Issued by
-
GSA Federal Acquisition Service
About this file
Final Permit (P119R1M3)
View the file
Other files
Show 40 more
Latest 50 of 74 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SUSANA MARTINEZ
GOVERNOR
JOHN A. SANCHEZ
LT. GOVERNOR
New Mexico
ENVIRONMENT DEPARTMENT
525 Camino de los Marquez, Suite 1 Santa Fe, NM 87505-1816
Phone (505) 476-4300 Fax (505) 476-4375 www.env.nm.gov
BUTCH TONGATE
CABINET SECRETARY
J. C. BORREGO
DEPUTY SECRETARY
Template version: 5/5/17
Air Quality Bureau
TITLE V OPERATING PERMIT
Issued under 20.2.70 NMAC
Certified Mail No: 7016 2070 0000 6771 1355 Return Receipt Requested
Operating Permit No: P119-R1M3 Facility Name: Cannon Air Force Base
Permittee Name: US Air Force Fb4855 - Cannon AFB Mailing Address: 27 SOCES/CEIE 506 N. Air Commando Way Cannon AFB, NM 88103
TEMPO/IDEA ID No: 106 - PRT20170001 AIRS No: 350090004
Permitting Action: Permit Modification Source Classification: Title V Major, PSD Minor
Facility Location: UTM E 654998 m, UTM N 3805630 m, Zone 13 County: Curry, Datum: WGS84
Air Quality Bureau Contact Joseph Kimbrell Main AQB Phone No. (505) 476-4300
TV Permit Expiration Date: October 30, 2018
TV Renewal Application Due: October 30, 2017
August 1, 2017 Richard L. Goodyear, PE Date Bureau Chief http://www.env.nm.gov/
TV Permit No: P119-R1M3 Page: A2 of A30
TABLE OF CONTENTS
Part A FACILITY SPECIFIC REQUIREMENTS .................................................................. A3
A100 Introduction .............................................................................................................. A3 A101 Permit Duration (expiration) .................................................................................... A3 A102 Facility: Description................................................................................................. A3 A103 Facility: Applicable Regulations and Non-Applicable Regulations ........................ A4 A104 Facility: Regulated Sources ..................................................................................... A6 A105 Facility: Control Equipment .................................................................................. A12 A106 Facility: Allowable Emissions ............................................................................... A12 A107 Facility: Allowable Startup, Shutdown, & Maintenance (SSM) ........................... A13 A108 Facility: Hours of Operation .................................................................................. A14 A109 Facility: Reporting Schedules ................................................................................ A14 A110 Facility: Fuel and Fuel Sulfur Requirements ......................................................... A14 A111 Facility: 20.2.61 NMAC Opacity (as required) ..................................................... A14 A112 Alternative Operating Scenario – Not Required .................................................... A16 A113 Compliance Plan – Not Required .......................................................................... A16 A114 Reducing Facility Emissions – Not Required ........................................................ A16 A115 Facility Area Source HAP Compliance Demonstration ........................................ A16
EQUIPMENT SPECIFIC REQUIREMENTS ........................................................................... A17 A200 Oil and Gas Industry – Not Required .................................................................... A17 A300 Construction Industry – Not Required ................................................................... A17 A400 Power Generation Industry – Not Required........................................................... A17 A500 Solid Waste Disposal (Landfills) Industry– Not Required .................................... A17 A600 Cannon Air Force Base .......................................................................................... A17 A601 External Combustion ............................................................................................. A17 A602 Fuel Dispensing and Fuel Storage Tanks............................................................... A18 A603 Surface Coating – Paint Booths ............................................................................. A20 A604 Internal Combustion Engines ................................................................................. A21 A605 Miscellaneous Chemical Use ................................................................................. A30
PART B GENERAL CONDITIONS (Attached)
PART C MISCELLANEOUS: Supporting On-Line Documents; Definitions;
Acronyms (Attached)
TV Permit No: P119-R1M3 Page: A3 of A30
PART A FACILITY SPECIFIC REQUIREMENTS
A100 Introduction
A. Not Applicable
A101 Permit Duration (expiration)
A. This permit P119-R1M3 supersedes permit P119-R1M2, and will expire on October 30, 2018. Application for renewal of this permit is due twelve (12) months prior to the date of expiration. (20.2.70.300.B.2 and 302.B NMAC)
B. If a timely and complete application for a permit renewal is submitted, consistent with
20.2.70.300 NMAC, but the Department has failed to issue or disapprove the renewal permit before the end of the term of the previous permit, then the permit shall not expire and all the terms and conditions of the permit shall remain in effect until the renewal permit has been issued or disapproved. (20.2.70.400.D NMAC)
A102 Facility: Description
A. This facility is a military installation that is home to the U.S. Air Force 27th Special Operations Wing (SOW), whose primary mission is to plan and execute specialized contingency operations using advanced aircraft and tactics. This function requires the operation of several regulated air emission sources. Stationary sources include external combustion equipment, paint booths, fuel loading activities, fuel storage tanks, fuel dispensing activities, emergency internal combustion engines, emergency fire pump engines, and miscellaneous chemical usage.
B. This facility is located approximately 6.7 miles west of the intersection of 7th and Main Street in Clovis, NM in Curry County. (20.2.70.302.A(7) NMAC)
C. This minor modification consists of updating the 40 CFR 60 Subpart CCCCCC applicability for Units 15001 and 15002 in Specific Condition A602.B, based on actual gasoline throughput not potential throughput. The description of this modification is for informational purposes only and is not enforceable.
D. Table 102.A and Table 102.B show the total potential emissions from this facility for information only, not an enforceable condition, excluding insignificant or trivial activities.
TV Permit No: P119-R1M3 Page: A4 of A30
Table 102.A: Total Potential Pollutant Emissions from Entire Facility1
Pollutant Emissions (tons per year)
NSR 1517M5R1 TV P119R1M3
Nitrogen Oxides (NOx) 22.5 138.2 Carbon Monoxide (CO) 18.9 73.9 Volatile Organic Compounds (VOC) 106.2 107.1 Sulfur Dioxide (SO2) < 1 10.0 Total Suspended Particulates (TSP) 2.3 8.2 Particulate Matter less than 10 microns (PM10) 2.3 8.1 Particulate Matter less than 2.5 microns (PM2.5) 2.1 7.8 Green House Gas (GHG) (CO2e) < 100,000 < 100,000
1 Table 102.A does not include the PTE of Title V insignificant and trivial activities.
Table 102.B: Total Potential *HAPs that exceed 1.0 tons per year Pollutant Emissions (tons per year) Butyl Carbitol Acetate (TAP) 1.2 Ethylbenzene 3.0 Hexamethylene-1, 6-Diisocyanate 3.9 Methanol 2.1 Methyl Isobutyl Ketone (TAP) 6.7 Methylene Chloride 1.5 Methyl tert Butyl Ether 2.1 Toluene 7.2 Xylene 6.4 Individual HAP 9.92 Total HAPs* 24.92
1 Table 102.B does not include the PTE of Title V insignificant and trivial activities.
2 Individual and Total HAP emissions are limited to 9.9 and 24.9 tons per year, respectively. The permittee reported
Total HAPs in Table 2-I of the application as 36.6 tpy.
A103 Facility: Applicable Regulations and Non-Applicable Regulations
A. The permittee shall comply with all applicable sections of the requirements listed in Table 103.A.
Table 103.A: Applicable Requirements
Applicable Requirements Federally Enforceable
Unit No.
NSR Permit No: 1517M5R1 & M5R2 (Per 20.2.72 NMAC) X Entire facility
20.2.1 NMAC General Provisions X Entire Facility
20.2.7 NMAC Excess Emissions X Entire facility
TV Permit No: P119-R1M3 Page: A5 of A30
Applicable Requirements Federally Enforceable
Unit No.
20.2.61.109 NMAC Smoke and Visible Emissions X Basewide Combustion Units
20.2.70 NMAC Operating Permits X Entire facility
20.2.71 NMAC Operating Permit Emission Fees X Entire facility
20.2.72 NMAC Construction Permit X Entire facility
20.2.73 NMAC Notice of Intent and Emissions
Inventory Requirements X Entire facility
20.2.75 NMAC Construction Permit Fees X Entire facility
20.2.77 NMAC New Source Performance X Units subject to 40 CFR 60
20.2.82 NMAC MACT Standards for Source
Categories of HAPS X Units subject to 40 CFR 63 40 CFR 50 National Ambient Air Quality Standards X Entire facility 40 CFR 60, Subpart A, General Provisions X Units subject to 40 CFR 60 40 CFR 60, Subpart IIII X Emergency Engines 40 CFR 63, Subpart A, General Provisions X Units subject to 40 CFR 63 40 CFR 63, Subpart ZZZZ X Emergency & Fire pump engines
40 CFR 63, Subpart CCCCCC X 15001, 15002, 15003, 22001, 22002, 22003, 22004, 22005, 22006
B. Table 103.B lists requirements that are not applicable to this facility. This table only includes those requirements cited in the application as applicable and determined by the Department to be not applicable, or the Department determined that the requirement does not impose any conditions on a regulated piece of equipment.
Table 103.B: Non-Applicable Requirements
Non-Applicable Requirements (1) (2) Justification For Non-Applicability
20.2.2 NMAC Definitions X
20.2.3 NMAC Ambient Air Quality Standards X
20.2.5 NMAC Source Surveillance X
20.2.75 NMAC Permit Fees X
20.2.78 NMAC Hazardous Air Pollutants X
40 CFR 61, Subpart M, Asbestos X 40 CFR 80, Subparts A, B, & C X Not applicable under Title V
1. Not Applicable For This Facility: No existing or planned operation/activity at this facility triggers the applicability of these requirements.
2. No Requirements: Although these regulations may apply, they do not impose any specific requirements on the operation of the facility as described in this permit.
C. Compliance with the terms and conditions of this permit regarding source emissions and operation demonstrate compliance with national ambient air quality standards specified at 40 CFR 50, which were applicable at the time air dispersion modeling was performed for the facility’s NSR Permit 1517-M5.
TV Permit No: P119-R1M3 Page: A6 of A30
A104 Facility: Regulated Sources
A. Table 104.A lists the emission units authorized for this facility. Emission units identified as insignificant or trivial activities (as defined in 20.2.70.7 NMAC) and/or equipment not regulated pursuant to the Act are not included.
Table 104.A: Regulated Sources List Unit No. Source Description Make
Model Serial No. Capacity Construction Date 1
14001 External Combustion Heater, Building 199
Hastings/ L-240-105-8628 41794-2 8.628
MMBtu/hr 1992
14002 External Combustion Heater, Building 199
Hastings/ L-240-105-8628 41793-2 8.628
MMBtu/hr 1992
14003 External Combustion Heater, Building 199
Rapids SA Series/ SA89 919112 8.25 MMBtu/hr 1992
14004 External Combustion Heater, Building 199
Rapids SA Series/ SA89 919114 8.25 MMBtu/hr 1992
14007 External Combustion
Heater, Building
Camus/ Force Dyna
Series O41215453 5.0 MMBtu/hr 10/15/2012
14008 External Combustion
Heater, Building
Camus/ Force Dyna
Series 111114765 5.0 MMBtu/hr 10/15/2012
14009 External Combustion
Heater, Building
Camus/ Force Dyna
Series 111114766 5.0 MMBtu/hr 10/15/2012
14010 External Combustion
Heater, Building
HYDRO
ENGINEERING
/ EHGV 4/3000
13090075 0.36 MMBtu/hr 6/30/2014
14011 Parachute Drying
Tower Heater, Building 680
Rupp Air Systems / CFA-
M12 1858977 0.525
MMBtu/hr Aug 2015
14012 Paint Booth Heater, Building
Weather-Rite / 25 H2
U28183A/1 656485 2.0 MMBtu/hr 10/15/2012
14013 External Combustion
Heater, Building
HYDRO
ENGINEERING
/ EHGV 4/3000
13090076 0.36 MMBtu/hr 6/30/2014
15001 Fuel Dispensing for
Tanks 22001 and 22002
Not Reported Not Reported
1,212,924 gal/yr May 2009
15002 Fuel Dispensing for Tank 22003 Not Reported Not
Reported 51,000 gal/yr 4/5/2014
15003 Fuel Dispensing for
Tanks 22004, 22005, and 22006
Not Reported Not
Reported 6,387,500 gal/yr 1992
TV Permit No: P119-R1M3 Page: A7 of A30
No. Source Description Make
Model Serial No. Capacity Construction Date 1
19001 RICE - Fire Pump Engine - Bldg. 127
Cummins / NT855F4 11525127 320 hp 9/1/1990
19002 RICE - Fire Pump Engine - Bldg. 127
Cummins / NT855F4 11511938 320 hp 9/1/1990
19003 RICE - Fire Pump Engine - Bldg. 127
Detroit /
DDFPT6ATLH-
6A-466521 315 hp 8/1/1991
19004 RICE - Fire Pump Engine - Bldg. 160
John Deere /
6068HFC48
PE6068L2
26144 198 hp 2013
19005 RICE - Fire Pump Engine - Bldg. 179
Cummins / 6CTA8.3-G2 46885442 252 hp 12/7/2009
19006 RICE - Fire Pump Engine - Bldg. 179
Cummins / 6CTA8.3-G2 46876079 252 hp 12/7/2009
19007 RICE - Fire Pump Engine - Bldg. 200
Caterpillar / 3306BD1 64Z08130 231 hp 10/1/1990
19008 RICE - Fire Pump Engine - Bldg. 200
Caterpillar / 3306BD1 64Z08332 231 hp 10/1/1990
19009 RICE - Fire Pump Engine - Bldg. 233
Detroit /
DDFP-04AT-
R7239 4A-285965 216 hp 8/20/1992
19010 RICE - Fire Pump Engine - Bldg. 845
John Deere /
4045TF290C
PE4045R9
38448 74 hp 6/4/2014
19011 RICE - Fire Pump Engine - Bldg. 1403
Cummins/ 6BTA5.9-F2 44741903 130 hp 1995
19012 RICE - Fire Pump Engine - Bldg. 2326
Cummins / NH-220-IF 10341879 275 hp 8/5/1987
19013 RICE - Fire Pump Engine - Bldg. 3208
Caterpillar / 3208 DIT 03Z12543 235 hp 2/20/1996
19014 RICE - Fire Pump Engine - Bldg. 3208
Caterpillar / 3208 DIT 03Z12547 235 hp 2/20/1996
19015 RICE - Fire Pump Engine - Bldg. 3208
Caterpillar / 3208 DIT 03Z12545 235 hp 2/20/1996
19016 RICE - Fire Pump Engine - Bldg. 74605
John Deere /
6068HFC48A
PE6068L1
50056 260 hp 7/1/2012
19017 RICE - Fire Pump Engine - Bldg. 74605
John Deere /
6068HFC48A
PE6068L1
49039 260 hp 7/1/2012
19018 RICE - Fire Pump Engine - Bldg. 74610
John Deere /
6090HFC47
RG6090L1
17338 235 10/2/2014
19019 RICE - Fire Pump Engine - Bldg. 74676
John Deere /
4045HFZ8H
PE4045L2
73221 121 8/14/2015
TV Permit No: P119-R1M3 Page: A8 of A30
No. Source Description Make
Model Serial No. Capacity Construction Date 1
19020
19023
RICE - Future Fire Pump Engines TBD TBD TBD TBD
19301 RICE - Emergency Generator - Bldg. 10
Cummins / 6CTA8.3-G2 46631569 252 hp 10/20/2006
19302 RICE - Emergency Generator - Bldg. 12 Caterpillar / C9 S9L00982 398 hp 10/15/2009
19303 RICE - Emergency Generator - Bldg. 77
Cummins / 4B3.9-G2 46655605 68 hp 2009
19304 RICE - Emergency Generator - Bldg. 116
Caterpillar / 3412 BPG00402 896 hp 4/25/2003
19305 RICE - Emergency Generator - Bldg. 123
Cummins /
QSM11-G4
NR3
35212613 470 hp 4/14/2009
19306 RICE - Emergency Generator - Bldg. 128
Caterpillar / 3406 1DZ04164 519 hp 8/1/2003
19307 RICE - Emergency Generator - Bldg. 135
Cummins /
QSM11-G4
NR3
35212810 470 hp 6/24/2009
19308 RICE - Emergency Generator - Bldg. 158
Cummins / VTA28-G5 25283911 900 hp 7/1/2004
19310 RICE - Emergency Generator - Bldg. 216
Cummins / 4B3.9-G2 46417261 68 hp 9/21/2004
19311 RICE - Emergency Generator - Bldg. 281
Cummins / QSB7-G3 NR3 46916691 250 hp 1/24/2012
19312 RICE - Emergency Generator - Bldg. 317 Caterpillar / C15 FSE02255 546 hp 8/25/2009
19313 RICE - Emergency Generator - Bldg. 336
Cummins / QSB5-G3 NR3 21844691 126 hp 11/25/2009
19314 RICE - Emergency Generator - Bldg. 337
Cummins / QSL9-G3 NR3 46899227 399 hp 8/19/2008
19315 RICE - Emergency Generator - Bldg. 356
Kubota / V2203- BG-ES 05L6027 27 hp 9/13/2005
19316 RICE - Emergency Generator - Bldg. 575
Caterpillar / 3412 BPG02452 823 hp 6/30/2005
19317 RICE - Emergency Generator - Bldg. 600
Cummins / QSB5-G3 NR3 21844697 126 hp 8/25/2008
19318 RICE - Emergency Generator - Bldg. 620
Caterpillar / 3054C E4M02853 168 hp 4/29/2009
19319 RICE - Emergency Generator - Bldg. 622 Caterpillar / C27 MJE01219 1214 hp 8/15/2012
19320 RICE - Emergency Generator - Bldg. 724 Caterpillar / C9 S9L02284 398 hp 1/10/2012
TV Permit No: P119-R1M3 Page: A9 of A30
No. Source Description Make
Model Serial No. Capacity Construction Date 1
19321 RICE - Emergency Generator - Bldg. 724 Caterpillar / C15 FTE00826 865 hp 5/1/2013
19322 RICE - Emergency Generator - Bldg. 728
Cummins / 6CTA8.3-G2 46317176 201 hp 2/5/2004
19324 RICE - Emergency Generator - Bldg. 777
Cummins / QSX15-G9 NR2 79503419 755 hp 11/1/2013
19325 RICE - Emergency Generator - Bldg. 777
Cummins / QSX15-G9 NR2 49503421 755 hp 11/1/2013
19326 RICE - Emergency Generator - Bldg. 777
Cummins / QSX15-G9 NR2 79544951 755 hp 11/1/2013
19327 RICE - Emergency Generator - Bldg. 780
Cummins / QSK23-G7 NR2 00316558 1220 hp 9/15/2008
19328 RICE - Emergency Generator - Bldg. 780
Cummins / QSK23-G7 NR2 00316531 1220 hp 9/15/2008
19329 RICE - Emergency Generator - Bldg. 780
Cummins / QSK23-G7 NR2 00316469 1220 hp 9/15/2008
19330 RICE - Emergency Generator - Bldg. 780
Cummins / QSK23-G7 NR2 00316723 1220 hp 9/15/2008
19331 RICE - Emergency
Generator - Bldg. 790
(UPS)
Cummins / QSX15-G9 79419742 755 hp 2/25/2011
19332 RICE - Emergency Generator - Bldg. 848
Volvo Penta /
TWD1643GE
D16*06949 7*C3*A 917 hp 12/1/2013
19333 RICE - Emergency Generator - Bldg. 848
Volvo Penta /
TWD1643GE
D16*06980 3*C3*A 917 hp 12/1/2013
19334 RICE - Emergency Generator - Bldg. 848
Volvo Penta /
TWD1643GE
D16*06980 4*C3*A 917 hp 12/1/2013
19335 RICE - Emergency Generator - Bldg. 848
Volvo Penta /
TWD1643GE
D16*06932 7*C3*A 917 hp 12/1/2013
19336 RICE - Emergency Generator - Bldg.
Caterpillar / 3208 5YF02252 299 hp 1995
19337 RICE - Emergency Generator - Bldg.
Caterpillar / 3208 5YF02253 299 hp 1995
19338 RICE - Emergency Generator - Bldg.
Cummins / QSB5-G3 NR3 46940148 145 hp 4/1/2009
19339 RICE - Emergency Generator - Bldg.
Kubota / F2803 1J0400 34 hp 3/13/2002
TV Permit No: P119-R1M3 Page: A10 of A30
No. Source Description Make
Model Serial No. Capacity Construction Date 1
19340 RICE - Emergency Generator - Bldg.
Kubota / F2803 1J1294 34 hp 3/7/2002
19341 RICE - Emergency Generator - Bldg.
2358 (DASR)
John Deere /
4045HF285
PE4045L0
99988 158 hp 5/15/2012
19342 RICE - Emergency Generator - Bldg.
Cummins / QSB5-G3 NR3 46738406 145 hp 7/16/2007
19343 RICE - Emergency Generator - Bldg.
Cummins / QSX15-G9 79393155 755 hp 2/4/2010
19344 RICE - Emergency Generator - Bldg.
Perkins / CM51035 U219524M 27 hp 1/11/2006
19345 RICE - Emergency Generator - Bldg.
Perkins / CM51035 U218926L 27 hp 1/11/2006
19346 RICE - Emergency Generator - Bldg.
Kubota / F2803 XG4901 34 hp 9/9/1999
19347 RICE - Emergency Generator - Bldg.
Kubota / D1703 01C0107 20 hp 6/23/2003
19354 RICE - Emergency Generator - Bldg.
Hercules /
DTI2300X11
GC347025
5 80 hp 5/6/1996
19356 RICE - Emergency Generator - Bldg.
MT-DD (Detroit Diesel) /
12V2000G85-
TB
535201132 3 1193 hp 7/1/2013
19357 RICE - Emergency Generator - Bldg.
Perkins / YD51206 U838110L 168 hp 4/12/2005
19358 RICE – Emergency Generator – Bldg.
Cummins / QSB5-G3 NR3 73315969 132 hp 5/1/2013
19359 RICE – Emergency Generator – Bldg.
Cummins / QSB7-G3 NR3 73314473 295 hp 2/1/2013
19360 RICE - Future
Emergency Generator
- Bldg. 4619
TBD TBD TBD TBD
TV Permit No: P119-R1M3 Page: A11 of A30
No. Source Description Make
Model Serial No. Capacity Construction Date 1
19361 RICE – Emergency Generator – Bldg.
V3300-BG-
ET01 2DE1903 49 12/1/2013
19362 RICE - Emergency Generator - Bldg.
Cummins / QSL9-G2 NR3 46875394 364 hp 2008
19363 RICE - Emergency Generator - Bldg.
Cummins / 6BT5.9-G6 46251765 170 hp 10/4/2004
19364 RICE - Emergency Generator - Bldg.
Cummins / 6CTA8.3-G2 46654695 231 hp 10/19/2006
19365 RICE - Emergency Generator - Bldg.
74618
Cummins / QSX15-G9 79606085 755 hp 8/1/2012
19366
19375
RICE -Future Emergency Generator TBD TBD TBD TBD
21003 Paint Booth, Building
Miscellaneous Parts
TBD NA TBD
21005 Aircraft Paint Booth, Building 4607
Miscellaneous Parts
TBD NA 12/2012
21006 Parts Paint Booth, Building 4607
Global Finishing Solutions/
IDB-3012
TBD
NA 12/2012
22001 E-85 Storage Tank
TESCA/
STI-F911 UL-
Not Reported 12,000 gallon 5/2009
22002 Gasoline Storage Tank 314
TESCA/
STI-F911 UL-
Not Reported 12,000 gallon 5/2009
22003 Gasoline Storage Tank 374 TBD Not
Reported 300 gallon 4/25/2014
22004 Gasoline Storage Tank 1111R TBD Not
Reported 10,000 gallon 1/2014
22005 Gasoline Storage Tank 1111M TBD Not
Reported 10,000 gallon 1/2014
22006 Gasoline Storage Tank 1111P TBD Not
Reported 10,000 gallon 1/2014
31999 Miscellaneous Chemical Use NA Not
Reported NA NA
All TBD (to be determined) units and like-kind engine replacements must be evaluated for applicability to NSPS and MACT requirements.
1 Construction Date is synonymous with Installation Date.
TV Permit No: P119-R1M3 Page: A12 of A30
A105 Facility: Control Equipment
A. Table 105.A lists all the pollution control equipment required for this facility. Each emission point is identified by the same number that was assigned to it in the permit application.
Table 105.A: Control Equipment List:
Control Equipment Unit No. Control Description Pollutant being controlled
Control for Unit
Number1
21003 Paint Booth Filters PM, including some HAP and TAP species. 21003
21005 Paint Booth Filters PM, including some HAP and TAP species. 21005
21006 Paint Booth Filters PM, including some HAP and TAP species. 21006
1 Control for unit number refers to a unit number from the Regulated Equipment List
A106 Facility: Allowable Emissions
A. The following Section lists the emission units, and their allowable emission limits.
(40 CFR 50, 40 CFR 60, Subparts A & IIII, 40 CFR 63, Subparts A, ZZZZ, & CCCCCC (6-C), Paragraphs 1, 7, and 8 of 20.2.70.302.A NMAC and NSR Permits 1517M5R1, & M5R2).
Table 106.A: Allowable Emissions
Unit No.
Source
Category (Section No.)
NOx1 tpy CO tpy VOC tpy
SO2
tpy
TSP
tpy
PM10
tpy
PM2.5
tpy HAP* tpy
14001 - 14004, 14007 – 14011, 14012, 14013
External Combustion
(A601)
21.5 18.0 1.2 0.1 1.6 1.6 1.6 *
15001 - 15003
Fuel Dispensing (A602A) - - 44.8 - - - - *
22001- 22006
Fuel Storage Tanks (A602C) - - 9.9 - - - - *
21003, 21005, 21006
Surface Coating
– Paint Booths
(A603)
- - 36.2 - 0.7 0.7 0.4 *
TV Permit No: P119-R1M3 Page: A13 of A30
Unit No.
Source
Category (Section No.)
NOx1 tpy CO tpy VOC tpy
SO2
tpy
TSP
tpy
PM10
tpy
PM2.5
tpy HAP* tpy
19001 - 19023, 19301 – 19308, 19310- 19322, 19324- 19350, 19354, 19356 - 19375
Internal Combustion
(A604)
116.7 55.9 15.1 9.8 5.8 5.8 5.8 *
31999 Miscellaneous Chemical Use
(A605)
Total (ton/yr)2 138.2 73.9 107.1 10.0 8.2 8.1 7.8
* 9.9 per individual /
24.9 combined
HAP
1 Nitrogen dioxide emissions include all oxides of nitrogen expressed as NO2.
2 Title V annual fee assessments are based on the sum of allowable tons per year emission limits in Sections A106 and A107.
3 To report excess emissions for sources with no pound per hour and/or ton per year emission limits, see condition
B110.E.
“-” indicates the application represented emissions as not expected for this pollutant.
“<” indicates that the application represented the uncontrolled mass emission rates are less than 1.0 pph or 1.0 tpy for this emissions unit and this air pollutant. The Department determined that allowable mass emission limits were not required for this unit and this pollutant.
“*” indicates individual and category tons per year are included in the facility-wide CAPs of 9.9 per individual and
24.9 combined HAP.
B. Individual HAP and Total HAP emissions are limited from the entire facility to 9.9 and 24.9 tons per year, respectively.
A107 Facility: Allowable Startup, Shutdown, & Maintenance (SSM)
A. Separate allowable startup, shutdown, and maintenance (SSM) emission limits are not required for this facility since the SSM emissions are predicted to be less than the limits established in Table 106.A. The permittee shall maintain records in accordance with Condition B109.E.
TV Permit No: P119-R1M3 Page: A14 of A30
A108 Facility: Hours of Operation
A. Except for limits on annual operating hours, this facility is authorized for continuous operation. Monitoring, recordkeeping, and reporting are not required to demonstrate compliance with continuous hours of operation.
A109 Facility: Reporting Schedules
A. A Semi-Annual Report of monitoring activities is due within 45 days following the end of every 6-month reporting period. The 6-month reporting periods start on October 1st and April 1st of each year.
B. The Annual Compliance Certification Report is due within 30 days of the end of every 12-month reporting period. The 12-month reporting period starts on October 1st of each year.
A110 Facility: Fuel and Fuel Sulfur Requirements
A. Fuel and Fuel Sulfur Requirements (All external combustion units in Table 104.A)
Requirement: All external combustion emission units listed in Table 104.A shall fire only natural gas containing no more than 0.2 grains of total sulfur per 100 dry standard cubic feet.
(NSR Permit 1517M5R1, Condition A110.A and revised)
Monitoring: The use of natural gas fuel, as defined in this permit, shall constitute compliance with this permit condition.
Recordkeeping: The permittee shall demonstrate compliance with the natural gas limit on total sulfur content by maintaining records of a current, valid purchase contract, tariff sheet or transportation contract for the gaseous fuel, specifying the allowable limit or less.
Reporting: The permittee shall report in accordance with Section B110.
A111 Facility: 20.2.61 NMAC Opacity (as required)
A. 20.2.61 NMAC Opacity Limit (All external combustion units)
Requirement: Visible emissions from all external stationary combustion emission stacks shall not equal or exceed an opacity of 20 percent in accordance with the requirements at 20.2.61.109 NMAC. (NSR Permit 1517M5R1, Condition A111.A and revised)
Monitoring: Use of natural gas fuel constitutes compliance with 20.2.61 NMAC unless opacity equals or exceeds 20% averaged over a 10-minute period. When any visible emissions are observed during operation other than during startup mode, opacity shall be measured over a 10-minute period, in accordance with the procedures at 40 CFR 60, Appendix A, Reference Method 9 (EPA Method 9) as required by 20.2.61.114 NMAC, or the operator will be allowed to shut down the equipment to perform maintenance/repair to eliminate the visible emissions.
Following completion of equipment maintenance/repair, the operator shall conduct visible
TV Permit No: P119-R1M3 Page: A15 of A30 emission observations following startup in accordance with the following procedures:
• Visible emissions observations shall be conducted over a 10-minute period during operation after completion of startup mode in accordance with the procedures at 40 CFR 60, Appendix A, Reference Method 22 (EPA Method 22). If no visible emissions are observed, no further action is required.
• If any visible emissions are observed during completion of the EPA Method 22 observation, subsequent opacity observations shall be conducted over a 10-minute period, in accordance with the procedures at EPA Method 9 as required by 20.2.61.114
NMAC.
For the purposes of this condition, Startup mode is defined as the startup period that is described in the facility’s startup plan.
Recordkeeping: If no visible emissions were observed, none.
If any visible emissions observations were conducted, the permittee shall keep records in accordance with the requirements of Section B109 and as follows:
• For any visible emissions observations conducted in accordance with EPA Method 22, record the information on the form referenced in EPA Method 22, Section 11.2.
For any opacity observations conducted in accordance with the requirements of EPA Method 9, record the information on the form referenced in EPA Method 9, Sections 2.2 and 2.4.
Reporting: The permittee shall report in accordance with Section B110.
B. 20.2.61 NMAC Opacity Limit (Emergency and fire pump engines)
Requirement: Visible emissions from all compression ignition stationary combustion emission stacks shall not equal or exceed an opacity of 20 percent in accordance with the requirements at
20.2.61.109 NMAC.
Monitoring:
(1) For compression ignition engines that are used to generate facility power and/or used for facility processing and are not emergency, black start, or limited use engines as defined at 40 CFR 63, Subpart ZZZZ, the permittee shall, at least once every 90 days of operation, perform an opacity measurement on each Unit for a minimum of 10 minutes in accordance with the procedures of 40 CFR 60, Appendix A, Reference Method 9.
(2) For emergency, standby, or limited use compression ignition engines, the permittee shall, at least once every calendar year during routine maintenance startup, an opacity measurement shall be performed on each Unit for a minimum of 10 minutes in accordance with the procedures of 40 CFR 60, Appendix A, Reference Method 9. The permittee shall also measure opacity on a Unit’s emissions stack when any visible emissions are observed during steady state operation.
(3) Alternatively, for any compression ignition engine, if visible emissions are observed during steady state operation, within 1 hour of seeing visible emissions, the permittee shall shut down the engine and perform maintenance and/or repair to eliminate the visible emissions. Following
TV Permit No: P119-R1M3 Page: A16 of A30 completion of equipment maintenance/repair, the operator shall perform visible emission observations following startup in accordance with the following procedures:
• Visible emissions observations shall be conducted over a 10-minute period during operation after completion of startup mode in accordance with the procedures for opacity in accordance with 40 CFR 60, Appendix A, Reference Method 22. If no visible emissions are observed, no further action is required.
• If any visible emissions are observed during completion of the Reference Method 22 observation, subsequent opacity observations shall be measured over a 10-minute period, in accordance with the procedures at 40 CFR 60, Appendix A, Reference Method 9 as required by 20.2.61.114 NMAC.
For the purposes of this condition, Startup mode is defined as the startup period that is described in the facilities startup plan.
Recordkeeping:
If any visible emissions observations were conducted, the permittee shall keep records in accordance with the requirements of Section B109 and as follows:
• For any visible emissions observations conducted in accordance with EPA Method 22, record the information on the form referenced in EPA Method 22, Section 11.2.
• For any opacity observations conducted in accordance with the requirements of EPA Method 9, record the information on the form referenced in EPA Method 9, Sections
2.2 and 2.4.
• For each emergency, black start, and limited use compression ignition engine, the permittee shall also record the number of operating hours per year of each Unit and the reason for operating the unit.
Reporting: The permittee shall report in accordance with Section B110.
A112 Alternative Operating Scenario – Not Required
A113 Compliance Plan – Not Required
A114 Reducing Facility Emissions – Not Required
A115 Facility Area Source HAP Compliance Demonstration
A. Facility Area Source HAP Compliance Demonstration
Requirement: All Hazardous Air Pollutants (HAP) emissions listed at Section 112 of CAA and subsequently revised at 40 CFR 63, Subpart C from Cannon AFB shall not exceed 9.9 tons per year of any individual hazardous air pollutant and 24.9 tons per year of all hazardous pollutants combined. All regulated stack and fugitive HAP emissions from all regulated units in Table 104.A and all Title V insignificant stationary sources of HAPs shall be included in this limit.
TV Permit No: P119-R1M3 Page: A17 of A30
(NSR Permit 1517M5R1, Condition A605.A and revised)
Monitoring: Monthly, the permittee shall calculate the monthly rolling 12-month total HAPs emissions (stack and fugitive) from all Title V regulated equipment and all Title V insignificant activities that are stationary sources of HAPs.
Recordkeeping: The permittee shall make a record of a monthly rolling 12-month total HAPs calculation, and include the following information in the record:
1. a description of the calculation methodology;
2. the electronic MS-Excel spreadsheet containing all calculations;
3. the results of the monthly HAPs calculations;
4. the emission factors relied upon in the calculation;
5. the date of the calculation; and
6. the unit numbers of all equipment represented by these calculations.
Reporting: The permittee shall report in accordance with Section B110.
EQUIPMENT SPECIFIC REQUIREMENTS
A200 Oil and Gas Industry – Not Required
A300 Construction Industry – Not Required
A400 Power Generation Industry – Not Required
A500 Solid Waste Disposal (Landfills) Industry– Not Required
A600 Cannon Air Force Base
A601 External Combustion
A. Fuel Usage (Units 14001, 14002, 14003, 14004, 14007, 14008, 14009, 14010, 14011, 14012, and 14013)
Requirement: Total natural gas throughput for external combustion units 14001, 14002, 14003, 14004, 14007, 14008, 14009, 14010, 14011, 14012 and 14013 shall not exceed 429.42 million scf/yr. Compliance with this throughput limitation demonstrates compliance with the allowable emissions for these units in Table 601.A and also Table 106.A except for HAPs. (NSR Permit 1517M5R1, Condition A601.A)
Monitoring: The permittee shall monitor the monthly and monthly rolling 12-month total throughput of natural gas for all external combustion units listed in Table 104.A.
TV Permit No: P119-R1M3 Page: A18 of A30
Recordkeeping: The permittee shall calculate and record the total monthly and monthly rolling 12-month total of natural gas throughput for all external combustion units listed in Table 104.A.
Reporting: In accordance with Section B110 of this permit.
Table 601.A Allowable Emissions for External Combustion Units Unit No.
NOx1 tpy
CO
tpy
VOC
pph
VOC
tpy
TSP
pph
TSP
tpy
PM10
pph
PM10
tpy
PM2.5
pph
PM2.5
tpy
14001 3.7 3.1 < < < < < < < < 14002 3.7 3.1 < < < < < < < < 14003 3.5 3.0 < < < < < < < < 14004 3.5 3.0 < < < < < < < < 14007 2.2 1.8 < < < < < < < < 14008 2.2 1.8 < < < < < < < < 14009 2.2 1.8 < < < < < < < < 14010 < < < < < < < < < < 14011 < < < < < < < < < < 14012 < < < < < < < < < <
14013 < < < < < < < < < < 1 Nitrogen dioxide emissions include all oxides of nitrogen expressed as NO2.
“<” indicates the application represented emissions are less than 1.0 pph or 1.0 tpy for this pollutant.
A602 Fuel Dispensing and Fuel Storage Tanks
A. Units 15001, 15002, and 15003
Requirement: Total fuel dispensed shall not exceed the following:
1) Unit 15001 shall not exceed 1,212,924 gallons per year.
2) Unit 15002 shall not exceed 51,000 gallons per year.
3) Unit 15003 shall not exceed 6,387,500 gallons per year.
Compliance with the throughput limitations demonstrates compliance with the allowable VOC emission limits in Tables 602.A and 106.A, except for HAPs for these units. (NSR Permit 1517M5R1, Condition A602.A and revised)
Monitoring: The permittee shall monitor the monthly and monthly rolling 12-month total amount of fuel dispensed from units 15001, 15002, and 15003.
Recordkeeping: The permittee shall calculate and record the monthly and monthly rolling 12-month total of fuel dispensed for each unit.
Reporting: In accordance with Section B110 of this permit.
TV Permit No: P119-R1M3 Page: A19 of A30
Table 602.A Allowable Emissions for Fuel Dispensing and Fuel Storage Tanks
Unit No.
NOx1 tpy
CO
tpy
VOC
pph
VOC
tpy
TSP
pph
TSP
tpy
PM10
pph
PM10
tpy
PM2.5
pph
PM2.5
tpy
15001, 15002, 150032
- - 10.2 44.8 - - - - - -
1 Nitrogen dioxide emissions include all oxides of nitrogen expressed as NO2.
2 Represents total emissions from the source category made of the group of units.
“-” indicates emissions of this pollutant are not expected.
B. 40 CFR 63 Subpart CCCCCC Applicability to Gasoline Dispensing Facilities and Associated Gasoline Storage Tanks
Requirement: Units 15001, 15002, 15003, 22001, 22002, 22003, 22004, 22005, and 22006 are subject to federal NESHAP found in 40 CFR 63, Subpart A – General Provisions, and Subpart CCCCCC – NESHAP for Gasoline Dispensing Facilities and shall comply with both the notification requirements in Subpart A and with the specific requirements of Subpart CCCCCC.
1) Units 15003, 22004, 22005, and 22006 must comply with the requirements in §63.11118.
2) Units 15001, 15002, 22001, 22002, and 22003 must comply with §63.11116.
(NSR Permit 1517M5R1, Condition A602.B and revised)
Monitoring: The permittee shall comply with all applicable monitoring requirements of 40 CFR 63, Subparts A and CCCCCC.
Recordkeeping: The permittee shall comply with all applicable recordkeeping requirements of 40 CFR 63, Subparts A and CCCCCC.
Reporting: The permittee shall comply with all applicable reporting requirements of 40 CFR 63, Subparts A and CCCCCC.
C. Throughput Limitations for Units 22001, 22002, 22003, 22004, 22005, 22006
Requirement: Total throughput for the fuel storage tanks shall not exceed the following:
1. Units 22001 and 22002 shall each not exceed 606,462 gallons per year;
2. Unit 22003 shall not exceed 51,000 gallons per year;
3. Unit 22004 shall not exceed 3,650,000 gallons per year;
4. Unit 22005 shall not exceed 1,825,000 gallons per year;
5. Unit 22006 shall not exceed 912,500 gallons per year; and
Compliance with this throughput limitation demonstrates compliance with the allowable emission limits in Table 106.A except for HAPs for these units. (NSR Permit 1517M5R1, Condition A602.C and revised)
Monitoring: The permittee shall monitor the monthly and monthly rolling 12-month total throughput for each storage tank.
TV Permit No: P119-R1M3 Page: A20 of A30
Recordkeeping: The permittee shall keep records of the amount of fuel delivered to each storage tank. The permittee shall calculate the total throughput for each month and the monthly rolling 12-month total.
Reporting: The permittee shall report in accordance with Section B110.
A603 Surface Coating – Paint Booths
A. Allowable Emissions for Paint Booths Paint Booths
VOC TSP PM10 PM2.5
lb/hr tpy lb/hr tpy lb/hr tpy lb/hr tpy
21003 127.10 13.43 49.51 1.83 45.13 1.67 4.56 0.17 21005 & 21006
198.05 22.76 66.26 9.67 60.40 8.82 6.11 0.89
B. Limits on usage for Units 21003, 21005, 21006
Requirement: The permittee shall not exceed the following hourly and annual usage rates.
The usage rates are derived from a master materials list of materials used at the facility, assigned an MSDS #, and submitted as part of the air permit application. Compliance with the usage rates shall be demonstrated by cross-referencing the master materials list and MSDS # with the usage records. General usage rates are provided by paint booth and material type, and the more restrictive usage limitations are given in parentheses. Compliance with the maximum hourly and annual usage rates demonstrates compliance with the allowable emission limits in Table A603.A for these units.
(NSR Permit 1517M5R1, Condition A603.A and revised)
Unit No. Material Maximum Hourly and Annual Usage Control
21003 Paint/Solvent General usage rates shall be limited to: 12 gal/hr and 2,535 gal/yr (MSDS# 1, 2, 7 = 1000 gal/yr each)
Paint Booth Filter
21005 and 21006
Paint/Solvent General usage rates shall be limited to: 15 gal/hr and 4,800 gal/yr (MSDS# 34a,b; 47a,b; 49a,b; 61; 107a,b = 1 gal/hr) (MSDS# 3b, 20b, 88 = 2000 gal/yr each) Paint
Booth Filter Non-spray
General usage rates shall be limited to: 10 gal/hr and 900 gal/yr (MSDS# 1, 25 = 450 gal/yr each)
Aerosol 2 gal/hr and 300 gal/yr
Monitoring:
1. The permittee shall monitor the usage of each material that is a source of VOC, HAP, or particulate matter emissions from surface coating operations;
TV Permit No: P119-R1M3 Page: A21 of A30
2. The permittee shall continuously monitor the differential pressure across each paint booth filter; and
3. Air filters will be replaced in accordance with manufacturer specifications regarding differential pressure.
Recordkeeping:
1. The permittee shall record the usage of each coating material, including any new material which shall be identified as new. Records, at a minimum, shall include the date, time, material name, MSDS ID corresponding to the spreadsheets developed for this application, location of usage, and the amount of material used;
2. The permittee shall calculate the actual emission rate (tons/month) and the monthly rolling 12-month total (tons/year) for each HAP emitted, total combined HAPs and total VOCs for the previous calendar month (tons/month). This calculation shall be based on usage logs and emission factors for each material. The emission factors shall be based on the spreadsheets developed by the applicant and submitted with the application for NSR 1517M5.
3. The permittee shall calculate the actual emission rate (tons/month) and the monthly rolling 12-month total (tons/year) emission rate for particulate matter. This calculation shall be based on usage logs and the emission factors developed for NSR 1517M5R1, for each paint booth.
4. The permittee shall keep onsite a copy of the manufacturer specifications and the records for each paint booth of the date filters are changed.
5. Prior to using any new coating material, the permittee shall evaluate the material and calculate the emission factor (lb/quantity) of all the pollutants that would result from using that material. The record of the calculation shall include a copy of the information that was relied upon when making the calculation.
Reporting: The permittee shall report in accordance with Section B110.
A604 Internal Combustion Engines
A. Table 604.A, Internal Combustion - Emergency Generators Engine Allowable Emissions Emergency Generator Engines Emissions (lb/hr)
Unit ID Building / Location Capacity
(hp) HC NOx CO SOx PM/10/2.5 VOC
19001 RICE - Fire Pump Engine -
Bldg. 127 320 9.92 2.14 0.66 0.70 0.81
19002 RICE - Fire Pump Engine -
Bldg. 127 320 9.92 2.14 0.66 0.70 0.81
19003 RICE - Fire Pump Engine -
Bldg. 127 315 9.77 2.10 0.65 0.69 0.79
19004 RICE - Fire Pump Engine -
Bldg. 160 198 0.09 1.22 1.13 0.41 0.07 0.50
19005 RICE - Fire Pump Engine -
Bldg. 179 252 0.11 1.56 1.44 0.52 0.08 0.64
TV Permit No: P119-R1M3 Page: A22 of A30
A. Table 604.A, Internal Combustion - Emergency Generators Engine Allowable Emissions Emergency Generator Engines Emissions (lb/hr)
Unit ID Building / Location Capacity
(hp) HC NOx CO SOx PM/10/2.5 VOC
19006 RICE - Fire Pump Engine -
Bldg. 179 252 0.11 1.56 1.44 0.52 0.08 0.64
19007 RICE - Fire Pump Engine -
Bldg. 200 231 7.16 1.54 0.47 0.51 0.58
19008 RICE - Fire Pump Engine -
Bldg. 200 231 7.16 1.54 0.47 0.51 0.58
19009 RICE - Fire Pump Engine -
Bldg. 233 216 6.70 1.44 0.44 0.48 0.54
19010 RICE - Fire Pump Engine -
Bldg. 845 74 0.03 0.54 0.60 0.15 0.05 0.19
19011 RICE - Fire Pump Engine -
Bldg. 1403 130 4.03 0.87 0.27 0.29 0.33
19012 RICE - Fire Pump Engine -
Bldg. 2326 275 8.53 1.84 0.56 0.61 0.69
19013 RICE - Fire Pump Engine -
Bldg. 3208 235 7.29 1.57 0.48 0.52 0.59
19014 RICE - Fire Pump Engine -
Bldg. 3208 235 7.29 1.57 0.48 0.52 0.59
19015 RICE - Fire Pump Engine -
Bldg. 3208 235 7.29 1.57 0.48 0.52 0.59
19016 RICE - Fire Pump Engine -
Bldg. 74605 260 0.11 1.60 1.49 0.53 0.09 0.66
19017 RICE - Fire Pump Engine -
Bldg. 74605 260 0.11 1.60 1.49 0.53 0.09 0.66
19018 RICE – 74610 Fire Pump
Engines 235 0.10 1.45 1.35 0.48 0.08 0.59
19019 RICE 74676 Fire Pump
Engines 121 0.05 0.75 0.69 0.25 0.04 0.30 19020 - 19023
RICE - Future Fire Pump Engines
(each) 0.88 12.35 11.46 4.10 0.66 5.04
19301 RICE - Emergency
Generator - Bldg. 10 252 0.11 1.56 1.44 0.52 0.08 0.64
19302 RICE - Emergency
Generator - Bldg. 12 398 0.18 2.46 2.3 0.82 0.13 1.00
19303 RICE - Emergency
Generator - Bldg. 77 68 0.03 0.49 0.55 0.14 0.04 0.17
19304 RICE - Emergency
Generator - Bldg. 116 896 21.50 4.93 0.01 0.63 0.57
19305 RICE - Emergency
Generator - Bldg. 123 470 0.21 2.90 2.7 0.96 0.16 1.18
TV Permit No: P119-R1M3 Page: A23 of A30
Unit ID Building / Location Capacity
(hp) HC NOx CO SOx PM/10/2.5 VOC
19306 RICE - Emergency
Generator - Bldg. 128 519 16.09 3.47 1.06 1.14 1.31
19307 RICE - Emergency
Generator - Bldg. 135 470 0.21 2.90 2.7 0.96 0.16 1.18
19308 RICE - Emergency
Generator - Bldg. 158 900 21.6 4.95 0.01 0.63 0.58
19310 RICE - Emergency
Generator - Bldg. 216 68 2.11 0.45 0.14 0.15 0.17
19311 RICE - Emergency
Generator - Bldg. 281 250 0.11 1.54 1.43 0.51 0.08 0.63
19312 RICE - Emergency
Generator - Bldg. 317 546 0.24 3.37 3.1 1.12 0.18 1.38
19313 RICE - Emergency
Generator - Bldg. 336 126 0.06 0.78 1.03 0.26 0.06 0.32
19314 RICE - Emergency
Generator - Bldg. 337 399 0.18 2.46 2.3 0.82 0.13 1.01
19315 RICE - Emergency
Generator - Bldg. 356 27 0.84 0.18 0.06 0.06 0.07
19316 RICE - Emergency
Generator - Bldg. 575 823 19.75 4.53 0.01 0.58 0.53
19317 RICE - Emergency
Generator - Bldg. 600 126 0.06 0.78 1.03 0.26 0.06 0.32
19318 RICE - Emergency
Generator - Bldg. 620 168 0.07 1.04 1.37 0.34 0.08 0.42
19319 RICE - Emergency
Generator - Bldg. 622 1214 0.80 12.04 6.96 0.01 0.40 0.78
19320 RICE - Emergency
Generator - Bldg. 724 398 0.18 2.46 2.3 0.82 0.13 1.00
19321 RICE - Emergency
Generator - Bldg. 724 865 0.57 8.58 4.96 0.01 0.29 0.55
19322 RICE - Emergency
Generator - Bldg. 728 201 6.23 1.34 0.41 0.44 0.51
19324 RICE - Emergency
Generator - Bldg. 777 755 0.50 7.49 4.33 0.01 0.25 0.48
19325 RICE - Emergency
Generator - Bldg. 777 755 0.50 7.49 4.33 0.01 0.25 0.48
19326 RICE - Emergency
Generator - Bldg. 777 755 0.50 7.49 4.33 0.01 0.25 0.48
19327
Generator - Bldg. 780 1220 0.81 12.10 6.99 0.01 0.40 0.78
TV Permit No: P119-R1M3 Page: A24 of A30
Unit ID Building / Location Capacity
(hp) HC NOx CO SOx PM/10/2.5 VOC
19328 RICE - Emergency
Generator - Bldg. 780 1220 0.81 12.10 6.99 0.01 0.40 0.78
19329 RICE - Emergency
Generator - Bldg. 780 1220 0.81 12.10 6.99 0.01 0.40 0.78
19330 RICE - Emergency
Generator - Bldg. 780 1220 0.81 12.10 6.99 0.01 0.40 0.78
19331
RICE - Emergency Generator - Bldg. 790
(UPS) 755 0.50 7.49 4.33 0.01 0.25 0.48
19332 RICE - Emergency
Generator - Bldg. 848 917 0.61 9.10 5.26 0.01 0.30 0.59
19333 RICE - Emergency
Generator - Bldg. 848 917 0.61 9.10 5.26 0.01 0.30 0.59
19334 RICE - Emergency
Generator - Bldg. 848 917 0.61 9.10 5.26 0.01 0.30 0.59
19335 RICE - Emergency
Generator - Bldg. 848 917 0.61 9.10 5.26 0.01 0.30 0.59
19336 RICE - Emergency
Generator - Bldg. 1400 299 9.27 2.00 0.61 0.66 0.75
19337 RICE - Emergency
Generator - Bldg. 1400 299 9.27 2.00 0.61 0.66 0.75
19338 RICE - Emergency
Generator - Bldg. 2134 145 0.06 0.90 1.18 0.30 0.07 0.37
19339 RICE - Emergency
Generator - Bldg. 2300 34 1.05 0.23 0.07 0.07 0.09
19340 RICE - Emergency
Generator - Bldg. 2302 34 1.05 0.23 0.07 0.07 0.09
19341
RICE - Emergency Generator - Bldg. 2358
(DASR) 158 0.07 0.98 1.29 0.32 0.08 0.40
19342 RICE - Emergency
Generator - Bldg. 2360 145 0.06 0.90 1.18 0.30 0.07 0.37
19343 RICE - Emergency
Generator - Bldg. 2373 755 0.50 7.49 4.33 0.01 0.25 0.48
19344 RICE - Emergency
Generator - Bldg. 3010 27 0.84 0.18 0.06 0.06 0.07
19345 RICE - Emergency
Generator - Bldg. 3033 27 0.84 0.18 0.06 0.06 0.07
19346 RICE - Emergency
Generator - Bldg. 3050 34 1.05 0.23 0.07 0.07 0.09
19347
Generator - Bldg. 3060 20 0.62 0.13 0.04 0.04 0.05
TV Permit No: P119-R1M3 Page: A25 of A30
Unit ID Building / Location Capacity
(hp) HC NOx CO SOx PM/10/2.5 VOC
19354 RICE - Emergency
Generator - Bldg. 4077 80 2.48 0.53 0.16 0.18 0.20
19356 RICE - Emergency
Generator - Bldg. 4085 1193 0.79 11.84 6.84 0.01 0.39 0.77
19357 RICE - Emergency
Generator - Bldg. 4086 168 5.21 1.12 0.34 0.37 0.42
19358 RICE - Emergency
Generator - Bldg. 4606 132 0.06 0.81 1.08 0.27 0.06 0.33
19359 RICE - Emergency
Generator - Bldg. 4607 295 0.13 1.82 1.69 0.60 0.10 0.74
19360 6 RICE - Future Emergency
Generator - Bldg. 4619 500 0.22 3.09 2.9 1.03 0.17 1.26
19361 RICE - Emergency
Generator - Bldg. 4734 49 0.02 0.36 0.44 0.10 0.05 0.12
19362 RICE - Emergency
Generator - Bldg. 5038 364 0.16 2.25 2.1 0.75 0.12 0.92
19363 RICE - Emergency
Generator - Bldg. 9971 170 5.27 1.14 0.35 0.37 0.43
19364 RICE - Emergency
Generator - Bldg. 9973 231 7.16 1.54 0.47 0.51 0.58
19365 RICE - Emergency
Generator - Bldg. 74618 755 0.50 7.49 4.33 0.01 0.25 0.48 19366 - 19375
RICE - Future Emergency Generators
(each)5 2.20 30.86 28.7 10.25 1.65 12.60
B. Operating Restrictions for Emergency Generators and Fire Pump Engines (Units listed in Table 104.A)
Requirement: To demonstrate compliance with the allowable emission limits in Tables 106.A and A604.A, units shall operate no more than 500 hours on a monthly rolling 12-month total..
Monitoring: The permittee shall monitor the monthly rolling 12-month total hours of operation for all units using a no-resettable hour meter.
Recordkeeping: The permittee shall maintain the following records in accordance with Section B109:
1) The permittee shall keep records of the monthly rolling 12-month total hours of operation of all units, as indicated on the non-resettable hour meter.
2) The permittee shall document how many hours are spent for emergency operation; including what classified the operation as emergency and how many hours are spent for maintenance checks and readiness testing.
TV Permit No: P119-R1M3 Page: A26 of A30
C. Fuel and Fuel Sulfur Requirements – All Reciprocating Internal Combustion Engines
(RICE)
Requirement: All RICE listed in Table 104.A at the facility shall combust only Non-Road Diesel (Ultra-Low Sulfur Diesel, ULSD) containing no more than 15 ppm total sulfur.
Monitoring: None. Compliance is demonstrated through records.
Recordkeeping: The permittee shall demonstrate compliance with the limit on total fuel sulfur content by maintaining records of a current, valid purchase contract, tariff sheet or transportation contract for the fuel, or fuel analysis, specifying the fuel grade and certification or allowable sulfur limit. If fuel analysis is used, the analysis shall not be older than one year. Alternatively, compliance may be demonstrated by keeping a receipt or invoice from a commercial fuel supplier with each fuel delivery, which shall include the delivery date, the fuel type delivered, amount of fuel delivered, and the maximum sulfur content of the fuel.
Reporting: The permittee shall report in accordance with Section B110.
D. Emission Calculations (All RICE)
Requirement: Compliance with the allowable emission limits in Tables 106.A and 604.A shall be demonstrated by calculating RICE emissions using performance test data, manufacturer’s certified emissions, NSPS emission standards, AP-42 emission factors, or other emission factors deemed acceptable by the Air Quality Bureau.
Monitoring: The permittee shall:
1) Calculate the actual emissions rate (tons/month) for the RICE emission units listed in Table 104.A.
2) Calculate the monthly rolling 12-month total emissions rate…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it.