GUS HARRISON 472-22350MNB PLANS 6 OF 6.pdf
PDF 4 MB Posted
- Solicitation number
- RFQ - 171 - 240000000186
- Issued by
- Lenawee County, Michigan
About this file
This document is a set of plans and specifications for the replacement of the HVAC system in Building 300 at the Gus Harrison Correctional Facility in Adrian, Michigan. The project involves the replacement of the existing air handling units, controls, piping, and associated equipment. Key details include the replacement of 5 air handling units, various pumps, and a new air-cooled condensing unit. The electrical work includes the replacement of existing disconnects, motor starters, and the connection of the new mechanical equipment. The project is being managed by the State of Michigan and Lenawee County. Bids for this project are due by 2:00 PM on a specified date, and the project specifications indicate that all work must be coordinated with the Owner and Temperature Control contractor.
The pricing terms and funding sources are not explicitly stated in the provided documents. However, the documents indicate that the work is a state and local contract opportunity, suggesting competitive bidding requirements. The documents do not mention any set-asides, incumbent contractors, or specific funding amounts or sources. The contract term and any renewal options are also not specified.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BLDG 300 HVAC
REPLACEMENT
FILE 472/22350.MNB
BLDG 300 HVAC
REPLACEMENT
FILE 472/22350.MNB
No. Description Date
Scale
Project number
Date
Drawn by
Checked by
Approved by
Sheet No.
M-300-TC-1
NOT TO SCALE
JKM
JKM
MES
04-21-23 23523.1
AHU-1 CONTROLS
REPLACEMENT
BLDG 300 HVAC
FILE 472/22350.MNB
GU
S H
AR
RIS
ON
CO
RR
EC
TIO
NA
L F
AC
ILI
TY
AD
RI
AN
, M
IC
HI
G
AN
E
. B
EE
C H
ER
S
T.
ST
A
TE
O
F M
IC
H
IG
A
N
ENGINEERS, DESIGNERS,
PROBLEM SOLVERS
PROUDLY SERVING MICHIGAN
517-437-6998 www.MendeEngineeringSolutions.com
CONSULTANTS:
TAC ASSOCIATES, LLC
Consulting Engineers
GENERAL TC NEW WORK NOTES:
1. TEMPERATURE CONTROLS (TC) FOR AHU-1 / P-5. REFER TO SHEET
TC-D1 AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.
2. REFER TO MECHANICAL SHEETS FOR DEVICE LOCATIONS AND
ADDITIONAL INFORMATION.
3. TC INTEGRATOR SHALL DETERMINE IF EXISTING DDC SYSTEM
REQUIRES UPGRADES FOR EXPANSION OF NEW DEVICES.
4. TC INTEGRATOR SHALL CLEAN AND RE-USE EXISTING CABINET FOR
INSTALLATION OF NEW DEVICES.
5. EXISTING CONDUIT TO BE RE-USED SHALL REMAIN.
6. COORDINATE WITH FIRE ALARM VENDOR AS REQUIRED. SEE
SEQUENCE OF OPERATION THIS SHEET.
SUPPLY
AHU-1
HEAT
COIL
N.C.C.
N.O.
HHWS
HHWR
P-5
L
OUTSIDE
AIR N.C.N.C.
FILTER
N.O.
SUPPLY
AIR
RETURN
AIR
EXHAUST
AIR
RETURN
RAF-1N.C.
N.O.
H
SEQUENCE OF OPERATION
1. WITH THE EXISTING SUPPLY AND RETURN MOTOR STARTER IN THE "AUTO" MODE, THE UNIT WILL BE ENABLED BY THE BUILDING MANAGEMENT SYSTEM (BMS). THE UNIT WILL OPERATE ACCORDING TO AN OCCUPIED AND NIGHT
SET BACK SCHEDULE.
A. OCCUPIED: RETURN AIR AND OUTDOOR AIR DAMPERS WILL OPEN WHEN AHU FANS ARE ENABLED. OUTSIDE
AIR DAMPER, RELIEF AIR, AND RETURN AIR DAMPER WILL OPEN TO MAINTAIN 55°F (ADJ).
B. WHEN BOTH SUPPLY & RETURN FANS ARE OPERATING THEIR ASSOCIATE PILOT LAMPS WILL BE ENERGIZED, INDICATING OPERATION AT THE TC PANEL.
C. IF CURRENT SENSOR DOES NOT INDICATE FAN OPERATION, AN ALARM SIGNAL WILL INDICATING FAN UNIT
FAILURE.
2. FACE AND BY-PASS DAMPERS AND TEMPERATURE CONTROL VALVE SHALL BE CONTROLLED TO MODULATE TO
MAINTAIN SUPPLY AIR TEMPERATURE SET-POINT OF 68F (ADJUSTABLE).
2.1. BELOW 35F TEMPERATURE CONTROL VALVE WILL BE IN NORMALLY OPEN POSITION. FACE AND BY-PASS
DAMPERS WILL BE MODULATED TO MAINTAIN SUPPLY AIR DISCHARGE TEMPERATURE SETTING.
2.2. ABOVE 35F THE FACE DAMPER WILL BE IN ITS NORMALLY OPEN POSITION. THE BY-PASS DAMPER WILL BE IN
ITS NORMALLY CLOSED POSITION. THE TEMPERATURE CONTROL VALVE WILL MODULATE TO MAINTAIN THE
DISCHARGE AIR TEMPERATURE SETPOINT.
3. TEMPERATURE CONTROL GRAPHICS WILL INDICATE TC VALVE POSITION AND FACE AND BY-PASS DAMPER
POSITION.
4. WHEN THE OUTSIDE AIR TEMPERATURE AND ENTHALPY IS SUITABLE, THE OUTSIDE AND RETURN AIR DAMPER
WILL MODULATE TO MAINTAIN A MIXED AIR TEMPERATURE OF 55 F (ADJ.).
5. WHEN THE OUTSIDE AIR TEMPERATURE AND ENTHALPY IS HIGHER THAN ECONOMIZER SETPOINTS, THE OUTSIDE AIR DAMPERS WILL MOVE TO A MINIMUM POSITION 30%OA (ADJ). THE RETURN AIR DAMPER WILL MOVE TO ITS
CORRESPONDING POSITION.
6. SAFETIES SHALL FUNCTION AS FOLLOWS:
A. FREEZE STAT (TSL) WILL STOP THE SUPPLY FAN AND CLOSE THE OUTSIDE & RELIEF AIR DAMPERS IF IT
SENSES A TEMPERATURE BELOW THE SETPOINT OF 38F (ADJ).
B. FREEZE STAT TRIP WILL INITIATE ALARM SIGNAL.
C. HIGH LIMIT (TSH) AIR SENSOR WILL STOP THE SUPPLY FAN AND CLOSE THE OUTSIDE AND RELIEF AIR
DAMPERS IF IT SENSES A TEMPERATURE ABOVE THE SETPOINT OF 125F (ADJ).
D. HIGH LIMIT AIR STAT TRIP WILL INITIATE ALARM SIGNAL.
E. ACTIVATION OF ANY SMOKE DETECTOR WILL INITIATE AN ALARM.
a. IF SMOKE IS DETECTED BY SMOKE DETECTOR (SD-3) OR IF ANY OTHER SMOKE/FIRE ALARM DEVICE IS
ACTIVATED WITHIN THE BUILDING THE UNIT WILL STOP AND ALL CONTROLLED DEVICES WILL GO TO THEIR NORMAL POSITIONS. THE STOP SIGNAL WILL BE FROM THE FIRE ALARM SYSTEM CONTROL PANEL. SMOKE DAMPERS SD-3 SHALL CLOSE. COORDINATION WITH EXISTING BUILDING FIRE ALARM
OPERATION IS REQUIRED.
F. PRESSURE DIFFERENTIAL SWITCH ACROSS THE AIR FILTER SHALL INDICATE ALARM WHEN SETTING REACHES
0.5" INWG (ADJ) INDICATING A DIRTY FILTER CONDITION.
6. DURING NIGHT SET BACK SCHEDULE, AHU-1 SUPPLY/RETURN FAN SHALL CYCLE THE UNIT ON/OFF TO MAINTAIN THE DESIRED SPACE NIGHT SETBACK TEMPERATURE. DURING NIGHT OPERATION THE OUTSIDE AIR AND RELIEF
AIR DAMPERS MOVES TO CLOSE AND RETURN AIR DAMPERS OPEN.
7. CIRCULATING PUMP (P-5) SHALL BE ENERGIZED WHEN TEMP OUTSIDE DROPS BELOW 55F (ADJ).
8. CURRENT SENSOR SHALL DETECT CIRCULATING PUMP (P-5) OPERATION. IF CURRENT SENSOR DOES NOT DETECT CURRENT, ALARM SIGNAL FOR PUMP FAILURE SHALL BE INDICATED ON AHU GRAPHIC. UPON PUMP FAILURE, FAN
WILL STOP, OUTSIDE AND RELIEF AIR DAMPERS WILL CLOSE.
AutoCAD SHX Text These prints are solely owned by MENDE ENGINEERING SOLUTIONS, LLC. The Drawings, Specifications and other documents prepared by MENDE ENGINEERING SOLUTIONS, LLC for this Project are instruments of MENDE ENGINEERING SOLUTIONS, LLC for use solely with respect to this Project and, unless otherwise provided, MENDE ENGINEERING SOLUTIONS, LLC shall be deemed the author of these documents and shall retain all common law, statutory and other reserved rights, including the copyright. MENDE ENGINEERING SOLUTIONS, LLC Drawings, Specifications or other documents shall not be used by the Owner or others on other projects, for additions to this Project or for completion of this Project by others, without the expressed written consent of MENDE ENGINEERING SOLUTIONS, LLC.
AutoCAD SHX Text DANGEROUS Architects, Pc
AutoCAD SHX Text 104 South Main Street Chelsea, Mi. 48118 734.475.3660 WWW.DANGEROUSARCHITECTS.COM zCopyright 2022, Dangerous Architects Pc.Copyright 2022, Dangerous Architects Pc.
AutoCAD SHX Text 4321 East Camden Road Osseo, MI 49266 Ph. (517) 254-4789 Fax (517) 254-4886 http://www.tac-associates.com
Project number
Date
Drawn by
Checked by
Approved by
Sheet No.
M-300-TC-2
NOT TO SCALE
JKM
JKM
MES
04-21-23 23523.1
AHU-2 CONTROLS
REPLACEMENT
BLDG 300 HVAC
FILE 472/22350.MNB
GU
S H
AR
RIS
ON
CO
RR
EC
TIO
NA
L F
AC
ILI
TY
AD
RI
AN
, M
IC
HI
G
AN
E
. B
EE
C H
ER
S
T.
ST
A
TE
O
F M
IC
H
IG
A
N
ENGINEERS, DESIGNERS,
PROBLEM SOLVERS
PROUDLY SERVING MICHIGAN
517-437-6998 www.MendeEngineeringSolutions.com
CONSULTANTS:
TAC ASSOCIATES, LLC
Consulting Engineers
SUPPLY
AHU-2
HEAT
COIL
N.C.C.
N.O.
HHWS
HHWR
P-6
L
OUTSIDE
AIR N.C.N.C.
FILTER
N.O.
SUPPLY
AIR
RETURN
AIR
EXHAUST
AIR
RETURN
RAF-2N.C.
N.O.
H
GENERAL TC NEW WORK NOTES:
1. TEMPERATURE CONTROLS (TC) FOR AHU-2 / P-6. REFER TO SHEET
TC-D2 AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.
2. REFER TO MECHANICAL SHEETS FOR DEVICE LOCATIONS AND
ADDITIONAL INFORMATION.
3. TC INTEGRATOR SHALL DETERMINE IF EXISTING DDC SYSTEM
REQUIRES UPGRADES FOR EXPANSION OF NEW DEVICES.
4. TC INTEGRATOR SHALL CLEAN AND RE-USE EXISTING CABINET FOR
INSTALLATION OF NEW DEVICES.
5. EXISTING CONDUIT TO BE RE-USED SHALL REMAIN.
6. COORDINATE WITH FIRE ALARM VENDOR AS REQUIRED. SEE
SEQUENCE OF OPERATION THIS SHEET.
SEQUENCE OF OPERATION
1. WITH THE EXISTING SUPPLY AND RETURN MOTOR STARTER IN THE "AUTO" MODE, THE UNIT WILL BE ENABLED BY THE BUILDING MANAGEMENT SYSTEM (BMS). THE UNIT WILL OPERATE ACCORDING TO AN OCCUPIED AND NIGHT
SET BACK SCHEDULE.
A. OCCUPIED: RETURN AIR AND OUTDOOR AIR DAMPERS WILL OPEN WHEN AHU FANS ARE ENABLED. OUTSIDE
AIR DAMPER, RELIEF AIR AND RETURN AIR DAMPER WILL OPEN TO MAINTAIN 55°F (ADJ).
B. WHEN BOTH SUPPLY & RETURN FANS ARE OPERATING THEIR ASSOCIATE PILOT LAMPS WILL BE ENERGIZED, INDICATING OPERATION AT THE TC PANEL.
C. IF CURRENT SENSOR DOES NOT INDICATE FAN OPERATION, AN ALARM SIGNAL WILL INDICATING FAN UNIT
FAILURE.
2. FACE AND BY-PASS DAMPERS AND TEMPERATURE CONTROL VALVE SHALL BE CONTROLLED TO MODULATE TO
MAINTAIN SUPPLY AIR TEMPERATURE SET-POINT OF 68F (ADJUSTABLE).
2.1. BELOW 35F TEMPERATURE CONTROL VALVE WILL BE IN NORMALLY OPEN POSITION. FACE AND BY-PASS
DAMPERS WILL BE MODULATED TO MAINTAIN SUPPLY AIR DISCHARGE TEMPERATURE SETTING.
2.2. ABOVE 35F THE FACE DAMPER WILL BE IN ITS NORMALLY OPEN POSITION. THE BY-PASS DAMPER WILL BE IN
ITS NORMALLY CLOSED POSITION. THE TEMPERATURE CONTROL VALVE WILL MODULATE TO MAINTAIN THE
DISCHARGE AIR TEMPERATURE SETPOINT.
3. TEMPERATURE CONTROL GRAPHICS WILL INDICATE TC VALVE POSITION AND FACE AND BY-PASS DAMPER
POSITION.
4. WHEN THE OUTSIDE AIR TEMPERATURE AND ENTHALPY IS SUITABLE, THE OUTSIDE AND RETURN AIR DAMPER
WILL MODULATE TO MAINTAIN A MIXED AIR TEMPERATURE OF 55 F (ADJ.).
5. WHEN THE OUTSIDE AIR TEMPERATURE AND ENTHALPY IS HIGHER THAN ECONOMIZER SETPOINTS, THE OUTSIDE AIR DAMPERS WILL MOVE TO A MINIMUM POSITION 30%OA (ADJ). THE RETURN AIR DAMPER WILL MOVE TO ITS
CORRESPONDING POSITION.
6. SAFETIES SHALL FUNCTION AS FOLLOWS:
A. FREEZE STAT (TSL) WILL STOP THE SUPPLY FAN AND CLOSE THE OUTSIDE & RELIEF AIR DAMPERS IF IT
SENSES A TEMPERATURE BELOW THE SETPOINT OF 38F (ADJ).
B. FREEZE STAT TRIP WILL INITIATE ALARM SIGNAL.
C. HIGH LIMIT (TSH) AIR SENSOR WILL STOP THE SUPPLY FAN AND CLOSE THE OUTSIDE AND RELIEF AIR
DAMPERS IF IT SENSES A TEMPERATURE ABOVE THE SETPOINT OF 125F (ADJ).
D. HIGH LIMIT AIR STAT TRIP WILL INITIATE ALARM SIGNAL.
E. ACTIVATION OF ANY SMOKE DETECTOR WILL INITIATE AN ALARM.
a. IF SMOKE IS DETECTED BY SMOKE DETECTOR (SD-4) OR IF ANY OTHER SMOKE/FIRE ALARM DEVICE IS
ACTIVATED WITHIN THE BUILDING THE UNIT WILL STOP AND ALL CONTROLLED DEVICES WILL GO TO THEIR NORMAL POSITIONS. THE STOP SIGNAL WILL BE FROM THE FIRE ALARM SYSTEM CONTROL PANEL. SMOKE DAMPERS SD-4 SHALL CLOSE. COORDINATION WITH EXISTING BUILDING FIRE ALARM
OPERATION IS REQUIRED.
F. PRESSURE DIFFERENTIAL SWITCH ACROSS THE AIR FILTER SHALL INDICATE ALARM WHEN SETTING REACHES
0.5" INWG (ADJ) INDICATING A DIRTY FILTER CONDITION.
6. DURING NIGHT SET BACK SCHEDULE, AHU-2 SUPPLY/RETURN FAN SHALL CYCLE THE UNIT ON/OFF TO MAINTAIN THE DESIRED SPACE NIGHT SETBACK TEMPERATURE. DURING NIGHT OPERATION THE OUTSIDE AIR AND RELIEF
AIR DAMPERS MOVES TO CLOSE AND RETURN AIR DAMPERS OPEN.
7. CIRCULATING PUMP (P-6) SHALL BE ENERGIZED WHEN TEMP OUTSIDE DROPS BELOW 55F (ADJ).
8. CURRENT SENSOR SHALL DETECT CIRCULATING PUMP (P-6) OPERATION. IF CURRENT SENSOR DOES NOT DETECT CURRENT, ALARM SIGNAL FOR PUMP FAILURE SHALL BE INDICATED ON AHU GRAPHIC. UPON PUMP FAILURE, FAN
WILL STOP, OUTSIDE AND RELIEF AIR DAMPERS WILL CLOSE.
AutoCAD SHX Text These prints are solely owned by MENDE ENGINEERING SOLUTIONS, LLC. The Drawings, Specifications and other documents prepared by MENDE ENGINEERING SOLUTIONS, LLC for this Project are instruments of MENDE ENGINEERING SOLUTIONS, LLC for use solely with respect to this Project and, unless otherwise provided, MENDE ENGINEERING SOLUTIONS, LLC shall be deemed the author of these documents and shall retain all common law, statutory and other reserved rights, including the copyright. MENDE ENGINEERING SOLUTIONS, LLC Drawings, Specifications or other documents shall not be used by the Owner or others on other projects, for additions to this Project or for completion of this Project by others, without the expressed written consent of MENDE ENGINEERING SOLUTIONS, LLC.
AutoCAD SHX Text DANGEROUS Architects, Pc
AutoCAD SHX Text 104 South Main Street Chelsea, Mi. 48118 734.475.3660 WWW.DANGEROUSARCHITECTS.COM zCopyright 2022, Dangerous Architects Pc.Copyright 2022, Dangerous Architects Pc.
4321 East Camden Road Osseo, MI 49266 Ph. (517) 254-4789 Fax (517) 254-4886 http://www.tac-associates.com
Project number
Date
Drawn by
Checked by
Approved by
Sheet No.
M-300-TC-3
NOT TO SCALE
JKM
JKM
MES
04-21-23 23523.1
AHU-3 CONTROLS
REPLACEMENT
BLDG 300 HVAC
FILE 472/22350.MNB
GU
S H
AR
RIS
ON
CO
RR
EC
TIO
NA
L F
AC
ILI
TY
AD
RI
AN
, M
IC
HI
G
AN
E
. B
EE
C H
ER
S
T.
ST
A
TE
O
F M
IC
H
IG
A
N
ENGINEERS, DESIGNERS,
PROBLEM SOLVERS
PROUDLY SERVING MICHIGAN
517-437-6998 www.MendeEngineeringSolutions.com
CONSULTANTS:
TAC ASSOCIATES, LLC
Consulting Engineers
SUPPLY
AHU-3
HEAT
COIL
N.C.C.
N.O.
HHWS
HHWR
P-7
L
OUTSIDE
AIR N.C.
FILTER
RETURN
AIR
EXHAUST
AIR
RETURN
RAF-3
N.C.
N.O.
SUPPLY AIR TO
VAV's, VVR's
N.C.
SD-1
N.C.
SD-2
DX
COOL
COIL
STAGE 1
COOL
STAGE 2
COOL
STAGE 3
COOL
STAGE 4
COOL
AIR COOLED CONDENSING UNIT
N.O.
FAIL
OPEN
N.O.
FAIL
OPEN
HHWS
HHWR
N.O.
VVR
VAV
GENERAL TC NEW WORK NOTES:
1. TEMPERATURE CONTROLS (TC) FOR AHU-3 / P-7, ACCU-1. REFER TO
SHEET TC-D3 AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.
2. REFER TO MECHANICAL SHEETS FOR DEVICE LOCATIONS AND
ADDITIONAL INFORMATION.
3. TC INTEGRATOR SHALL DETERMINE IF EXISTING DDC SYSTEM
REQUIRES UPGRADES FOR EXPANSION OF NEW DEVICES.
4. TC INTEGRATOR SHALL CLEAN AND RE-USE EXISTING CABINET FOR
INSTALLATION OF NEW DEVICES.
5. EXISTING CONDUIT TO BE RE-USED SHALL REMAIN.
6. COORDINATE WITH FIRE ALARM VENDOR AS REQUIRED. SEE
SEQUENCE OF OPERATION THIS SHEET.
SEQUENCE OF OPERATION
1. WITH THE EXISTING SUPPLY AND RETURN MOTOR STARTER IN THE "AUTO" MODE,
THE UNIT WILL BE ENABLED BY THE BUILDING MANAGEMENT SYSTEM (BMS). THE
UNIT WILL OPERATE ACCORDING TO AN OCCUPIED AND NIGHT SET BACK SCHEDULE.
OCCUPIED:
A. WHEN FANS ARE ENABLED, SMOKE DAMPERS SD-1 AND SD-2 WILL OPEN.
B. RETURN AIR, OUTDOOR AIR AND RELIEF DAMPERS WILL OPEN TO MAINTAIN
MIXED AIR TEMPERATURE OF 55°F (ADJ).
C. HEATING VALVE WILL MODULATE OPEN TO MAINTAIN DESIRED DISCHARGE AIR
TEMPERATURE (ADJ).
D. WHEN BOTH SUPPLY & RETURN FANS ARE OPERATING THEIR ASSOCIATE PILOT
LAMPS WILL BE ENERGIZED, INDICATING OPERATION AT THE TC PANEL AS WELL
AS "ON" IN THE BMS GRAPHIC SCREEN.
E. IF CURRENT SENSORS DO NOT INDICATE FAN OPERATION, AN ALARM SIGNAL
WILL INDICATING SUPPLY AND RETURN FAN FAILURE.
2. WHEN THE OUTSIDE AIR TEMPERATURE AND ENTHALPY IS SUITABLE, THE OUTSIDE
AND RETURN AIR DAMPER WILL MODULATE TO MAINTAIN A MIXED AIR
TEMPERATURE OF 55 F (ADJ.).
3. WHEN THE OUTSIDE AIR TEMPERATURE AND ENTHALPY IS HIGHER THAN
ECONOMIZER SETPOINTS, THE OUTSIDE AIR DAMPERS WILL MOVE TO A MINIMUM
POSITION 15%OA (ADJ), THE RETURN AIR DAMPER WILL TRACK ITS POSITION, AND
STAGE 1 MECHANICAL COOLING WILL BE ENABLED.
3.1. ON A CONTINUED CALL FOR COOLING, STAGES 2, 3 AND 4 WILL BE ENGAGED, TO
SATISFY THE ZONE OF THE MOST CRITICAL COOLING DEMAND (AS SENSED BY
THE ZONE SENSORS).
3.2. MANUFACTURER OF ACCU-1 SHALL PROVIDE ALL CONTROLS EQUIPMENT
STAGING ONCE A CALL FOR COOLING IS OBTAINED FROM THE SYSTEM.
MORNING WARM UP:
4. MORNING WARM UP SCHEDULE SHALL BE SET UP THRU THE BMS.
5. AHU TEMPERATURE CONTROL SHALL BE BASED ON RETURN AIR TEMPERATURE.
6. RAF-4 SHALL BE ENERGIZED, HEATING CONTROL VALVE SHALL MODULATE OPEN TO
MAINTAIN THE RETURN AIR TEMPERATURE SETPOINT.
7. AT THE END OF THE MORNING WARM UP CYCLE, CONTROL OF THE HEATING VALVE
SHALL BE BASED ON DISCHARGE TEMPERATURE AS NOTED IN OCCUPIED MODE.
VARIABLE AIR VOLUME BOXES:
8. VAV BOXES SHALL BE MODULATED TO MAINTAIN SPACE TEMPERATURE SETTING
(ADJ).
9. VVR (VAV WITH REHEAT) SHALL BE MODULATED TO MAINTAIN SPACE TEMPERATURE
SETPOINT (ADJ). WHEN THE BOXES ARE MODULATED TO MIN POSITION AND IF THE
SPACE TEMPERATURE CONTINUES TO DROP THE 2-WAY CONTROL VALVE SHALL BE
MODULATED OPEN TO MAINTAIN SPACE TEMPERATURE (ADJ).
10. A STATIC PRESSURE SENSOR SHALL CONTROL THE OPERATION OF THE SUPPLY AND
RETURN FAN INLET VANES.
10.1. SYSTEM STATIC PRESSURE WILL MODULATE THE SUPPLY FAN INLET VANE
DAMPER IN SEQUENCE WITH THE RETURN FAN INLET VANE DAMPER TO
MAINTAIN THE DESIRED STATIC PRESSURE IN THE SUPPLY DUCT. RETURN FAN
INLET VANE DAMPER WILL LAG BEHIND THE SUPPLY FAN INLET VANE DAMPER
BY 15% (ADJ) OF THE MAX SUPPLY FAN VOLUME. SUPPLY FAN DISCHARGE DUCT
STATIC PRESSURE HIGH LIMIT WILL SHALL SIGNAL ALARM WHEN SET POINT IS
REACHED AND MOVE SUPPLY FAN INLET VANE TO MINIMUM POSITION (ADJ).
11. EXHAUST FANS (EF-1 THRU EF-8) WILL BE INTERLOCKED WITH AHU-3 DURING
OCCUPIED MODE.
11.1. EXHAUST FANS SHALL BE DISABLED DURING NIGHT SET BACK AND MORNING
WARM UP.
12. CIRCULATING PUMP (P-7) SHALL BE ENERGIZED WHEN TEMP OUTSIDE DROPS BELOW
55F (ADJ).
13. CURRENT SENSOR SHALL DETECT CIRCULATING PUMP (P-7) OPERATION. IF CURRENT
SENSOR DOES NOT DETECT CURRENT, ALARM SIGNAL FOR PUMP FAILURE SHALL BE
INDICATED ON AHU GRAPHIC. UPON PUMP FAILURE, FAN WILL STOP, OUTSIDE AND
RELIEF AIR DAMPERS WILL CLOSE.
14. SAFETIES SHALL FUNCTION AS FOLLOWS:
A. FREEZE STAT (TSL) WILL STOP THE SUPPLY FAN AND CLOSE THE OUTSIDE &
RELIEF AIR DAMPERS IF IT SENSES A TEMPERATURE BELOW THE SETPOINT OF
38F (ADJ).
B. FREEZE STAT TRIP WILL INITIATE ALARM SIGNAL.
C. PRESSURE DIFFERENTIAL SWITCH ACROSS THE AIR FILTER SHALL INDICATE
ALARM WHEN SETTING REACHES 0.5" INWG (ADJ) INDICATING A DIRTY FILTER
CONDITION.
D. IF SMOKE IS DETECTED BY SMOKE DETECTOR (SD-1, SD-2) OR IF ANY OTHER
SMOKE DETECTOR OR PULL STATION IS ACTIVATED WITHIN THE AREA SERVED
BY AHU-3, THE SUPPLY FAN AND RETURN FAN WILL STOP AND ALL CONTROLLED
DEVICES WILL GO TO THEIR NORMAL POSITIONS. THE STOP SIGNAL WILL BE
FROM THE FIRE ALARM SYSTEM CONTROL PANEL. ALARM SIGNAL WILL BE SENT
WHEN UNITS ARE SHUT DOWN. COORDINATION WITH EXISTING BUILDING FIRE
ALARM OPERATION IS REQUIRED.
AutoCAD SHX Text These prints are solely owned by MENDE ENGINEERING SOLUTIONS, LLC. The Drawings, Specifications and other documents prepared by MENDE ENGINEERING SOLUTIONS, LLC for this Project are instruments of MENDE ENGINEERING SOLUTIONS, LLC for use solely with respect to this Project and, unless otherwise provided, MENDE ENGINEERING SOLUTIONS, LLC shall be deemed the author of these documents and shall retain all common law, statutory and other reserved rights, including the copyright. MENDE ENGINEERING SOLUTIONS, LLC Drawings, Specifications or other documents shall not be used by the Owner or others on other projects, for additions to this Project or for completion of this Project by others, without the expressed written consent of MENDE ENGINEERING SOLUTIONS, LLC.
AutoCAD SHX Text DANGEROUS Architects, Pc
AutoCAD SHX Text 104 South Main Street Chelsea, Mi. 48118 734.475.3660 WWW.DANGEROUSARCHITECTS.COM zCopyright 2022, Dangerous Architects Pc.Copyright 2022, Dangerous Architects Pc.
AutoCAD SHX Text 4321 East Camden Road Osseo, MI 49266 Ph. (517) 254-4789 Fax (517) 254-4886 http://www.tac-associates.com
M
Project number
Date
Drawn by
Checked by
Approved by
Sheet No.
M-300-TC-4
NOT TO SCALE
JKM
JKM
MES
04-21-23 23523.1
AHU-4 CONTROLS
REPLACEMENT
BLDG 300 HVAC
FILE 472/22350.MNB
GU
S H
AR
RIS
ON
CO
RR
EC
TIO
NA
L F
AC
ILI
TY
AD
RI
AN
, M
IC
HI
G
AN
E
. B
EE
C H
ER
S
T.
ST
A
TE
O
F M
IC
H
IG
A
N
ENGINEERS, DESIGNERS,
PROBLEM SOLVERS
PROUDLY SERVING MICHIGAN
517-437-6998 www.MendeEngineeringSolutions.com
CONSULTANTS:
TAC ASSOCIATES, LLC
Consulting Engineers
GENERAL TC NEW WORK NOTES:
1. TEMPERATURE CONTROLS (TC) FOR AHU-4 / P-8. REFER TO SHEET
TC-D4 AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.
2. REFER TO MECHANICAL SHEETS FOR DEVICE LOCATIONS AND
ADDITIONAL INFORMATION.
3. TC INTEGRATOR SHALL DETERMINE IF EXISTING DDC SYSTEM
REQUIRES UPGRADES FOR EXPANSION OF NEW DEVICES.
4. TC INTEGRATOR SHALL CLEAN AND RE-USE EXISTING CABINET FOR
INSTALLATION OF NEW DEVICES.
5. EXISTING CONDUIT TO BE RE-USED SHALL REMAIN.
6. COORDINATE WITH FIRE ALARM VENDOR AS REQUIRED. SEE
SEQUENCE OF OPERATION THIS SHEET.
SUPPLY
AHU-4
HEAT
COIL
N.C.C.
N.O.
HHWS
HHWR
P-8
L
OUTSIDE
AIR N.C.N.C.
FILTER
N.O.
SUPPLY
AIR
RETURN
AIR
EXHAUST
AIR
RETURN
RAF-4N.C.
N.O.
H
SEQUENCE OF OPERATION
1. WITH THE EXISTING SUPPLY AND RETURN MOTOR STARTER IN THE "AUTO" MODE, THE UNIT WILL BE ENABLED BY THE BUILDING MANAGEMENT SYSTEM (BMS). THE UNIT WILL OPERATE ACCORDING TO AN OCCUPIED AND NIGHT
SET BACK SCHEDULE.
A. OCCUPIED: RETURN AIR AND OUTDOOR AIR DAMPERS WILL OPEN WHEN AHU FANS ARE ENABLED. OUTSIDE
AIR DAMPER, RELIEF AIR AND RETURN AIR DAMPER WILL OPEN TO MAINTAIN 55°F (ADJ).
B. WHEN BOTH SUPPLY & RETURN FANS ARE OPERATING THEIR ASSOCIATE PILOT LAMPS WILL BE ENERGIZED, INDICATING OPERATION AT THE TC PANEL.
C. IF CURRENT SENSOR DOES NOT INDICATE FAN OPERATION, AN ALARM SIGNAL WILL INDICATING FAN UNIT
FAILURE.
2. FACE AND BY-PASS DAMPERS AND TEMPERATURE CONTROL VALVE SHALL BE CONTROLLED TO MODULATE TO
MAINTAIN SUPPLY AIR TEMPERATURE SET-POINT OF 68F (ADJUSTABLE).
2.1. BELOW 35F TEMPERATURE CONTROL VALVE WILL BE IN NORMALLY OPEN POSITION. FACE AND BY-PASS
DAMPERS WILL BE MODULATED TO MAINTAIN SUPPLY AIR DISCHARGE TEMPERATURE SETTING.
2.2. ABOVE 35F THE FACE DAMPER WILL BE IN ITS NORMALLY OPEN POSITION. THE BY-PASS DAMPER WILL BE IN
ITS NORMALLY CLOSED POSITION. THE TEMPERATURE CONTROL VALVE WILL MODULATE TO MAINTAIN THE
DISCHARGE AIR TEMPERATURE SETPOINT.
3. TEMPERATURE CONTROL GRAPHICS WILL INDICATE TC VALVE POSITION AND FACE AND BY-PASS DAMPER
POSITION.
4. WHEN THE OUTSIDE AIR TEMPERATURE AND ENTHALPY IS SUITABLE, THE OUTSIDE AND RETURN AIR DAMPER
WILL MODULATE TO MAINTAIN A MIXED AIR TEMPERATURE OF 55 F (ADJ.).
5. WHEN THE OUTSIDE AIR TEMPERATURE AND ENTHALPY IS HIGHER THAN ECONOMIZER SETPOINTS, THE OUTSIDE AIR DAMPERS WILL MOVE TO A MINIMUM POSITION 30%OA (ADJ). THE RETURN AIR DAMPER WILL MOVE TO ITS
CORRESPONDING POSITION.
6. SAFETIES SHALL FUNCTION AS FOLLOWS:
A. FREEZE STAT (TSL) WILL STOP THE SUPPLY FAN AND CLOSE THE OUTSIDE & RELIEF AIR DAMPERS IF IT
SENSES A TEMPERATURE BELOW THE SETPOINT OF 38F (ADJ).
B. FREEZE STAT TRIP WILL INITIATE ALARM SIGNAL.
C. HIGH LIMIT (TSH) AIR SENSOR WILL STOP THE SUPPLY FAN AND CLOSE THE OUTSIDE AND RELIEF AIR
DAMPERS IF IT SENSES A TEMPERATURE ABOVE THE SETPOINT OF 125F (ADJ).
D. HIGH LIMIT AIR STAT TRIP WILL INITIATE ALARM SIGNAL.
E. ACTIVATION OF ANY SMOKE DETECTOR WILL INITIATE AN ALARM.
a. IF SMOKE IS DETECTED BY SMOKE DETECTOR (SD-3) OR IF ANY OTHER SMOKE/FIRE ALARM DEVICE IS
ACTIVATED WITHIN THE BUILDING THE UNIT WILL STOP AND ALL CONTROLLED DEVICES WILL GO TO THEIR NORMAL POSITIONS. THE STOP SIGNAL WILL BE FROM THE FIRE ALARM SYSTEM CONTROL PANEL. SMOKE DAMPERS SD-3 SHALL CLOSE. COORDINATION WITH EXISTING BUILDING FIRE ALARM
OPERATION IS REQUIRED.
F. PRESSURE DIFFERENTIAL SWITCH ACROSS THE AIR FILTER SHALL INDICATE ALARM WHEN SETTING REACHES
0.5" INWG (ADJ) INDICATING A DIRTY FILTER CONDITION.
6. DURING NIGHT SET BACK SCHEDULE, AHU-4 SUPPLY/RETURN FAN SHALL CYCLE THE UNIT ON/OFF TO MAINTAIN THE DESIRED SPACE NIGHT SETBACK TEMPERATURE. DURING NIGHT OPERATION THE OUTSIDE AIR AND RELIEF
AIR DAMPERS MOVES TO CLOSE AND RETURN AIR DAMPERS OPEN.
7. CIRCULATING PUMP (P-8) SHALL BE ENERGIZED WHEN TEMP OUTSIDE DROPS BELOW 55F (ADJ).
8. CURRENT SENSOR SHALL DETECT CIRCULATING PUMP (P-8) OPERATION. IF CURRENT SENSOR DOES NOT DETECT CURRENT, ALARM SIGNAL FOR PUMP FAILURE SHALL BE INDICATED ON AHU GRAPHIC. UPON PUMP FAILURE, FAN
WILL STOP, OUTSIDE AND RELIEF AIR DAMPERS WILL CLOSE.
AutoCAD SHX Text These prints are solely owned by MENDE ENGINEERING SOLUTIONS, LLC. The Drawings, Specifications and other documents prepared by MENDE ENGINEERING SOLUTIONS, LLC for this Project are instruments of MENDE ENGINEERING SOLUTIONS, LLC for use solely with respect to this Project and, unless otherwise provided, MENDE ENGINEERING SOLUTIONS, LLC shall be deemed the author of these documents and shall retain all common law, statutory and other reserved rights, including the copyright. MENDE ENGINEERING SOLUTIONS, LLC Drawings, Specifications or other documents shall not be used by the Owner or others on other projects, for additions to this Project or for completion of this Project by others, without the expressed written consent of MENDE ENGINEERING SOLUTIONS, LLC.
AutoCAD SHX Text DANGEROUS Architects, Pc
AutoCAD SHX Text 104 South Main Street Chelsea, Mi. 48118 734.475.3660 WWW.DANGEROUSARCHITECTS.COM zCopyright 2022, Dangerous Architects Pc.Copyright 2022, Dangerous Architects Pc.
4321 East Camden Road Osseo, MI 49266 Ph. (517) 254-4789 Fax (517) 254-4886 http://www.tac-associates.com
Project number
Date
Drawn by
Checked by
Approved by
Sheet No.
M-300-TC-5
NOT TO SCALE
JKM
JKM
MES
04-21-23 23523.1
AHU-5 CONTROLS
REPLACEMENT
BLDG 300 HVAC
FILE 472/22350.MNB
GU
S H
AR
RIS
ON
CO
RR
EC
TIO
NA
L F
AC
ILI
TY
AD
RI
AN
, M
IC
HI
G
AN
E
. B
EE
C H
ER
S
T.
ST
A
TE
O
F M
IC
H
IG
A
N
ENGINEERS, DESIGNERS,
PROBLEM SOLVERS
PROUDLY SERVING MICHIGAN
517-437-6998 www.MendeEngineeringSolutions.com
CONSULTANTS:
TAC ASSOCIATES, LLC
Consulting Engineers
GENERAL TC NEW WORK NOTES:
1. TEMPERATURE CONTROLS (TC) FOR AHU-5 / P-9 AND EF-10. REFER
TO SHEET TC-D5 AND SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
2. REFER TO MECHANICAL SHEETS FOR DEVICE LOCATIONS AND
ADDITIONAL INFORMATION.
3. TC INTEGRATOR SHALL DETERMINE IF EXISTING DDC SYSTEM
REQUIRES UPGRADES FOR EXPANSION OF NEW DEVICES.
4. TC INTEGRATOR SHALL CLEAN AND RE-USE EXISTING CABINET FOR
INSTALLATION OF NEW DEVICES.
5. EXISTING CONDUIT TO BE RE-USED SHALL REMAIN.
6. COORDINATE WITH FIRE ALARM VENDOR AS REQUIRED. SEE
SEQUENCE OF OPERATION THIS SHEET.
SUPPLY
AHU-5
HEAT
COIL
N.C.C.
N.O.
HHWS
HHWR
P-9
L
OUTSIDE
AIR N.C.N.C.
FILTER
N.O.
SUPPLY
AIR
RETURN
AIR
EXHAUST
AIR
RETURN
RAF-5N.C.
N.O.
H
BACKDRAFT
DAMPER
EXHAUST FAN EF-10
(KITCHEN HOOD)
EF-10
SEQUENCE OF OPERATION
1. UNIT IS ENABLED THRU THE BMS AND FAN IS STARTED AND STOP THRU EXISTING PUSH BUTTON
SWITCH FOR EF-10.
A. SUPPLY FAN ACTIVATION WILL OPEN OUTSIDE AIR DAMPER.
B. WHEN SUPPLY FAN IS OPERATING ITS ASSOCIATE PILOT LAMP WILL BE ENERGIZED,
INDICATING OPERATION AT THE TC PANEL.
C. IF CURRENT SENSOR DOES NOT INDICATE FAN OPERATION, AN ALARM SIGNAL WILL
INDICATING FAN UNIT FAILURE.
2. FACE AND BY-PASS DAMPERS AND TEMPERATURE CONTROL VALVE SHALL BE CONTROLLED TO
MODULATE TO MAINTAIN SUPPLY AIR TEMPERATURE SET-POINT OF 68F (ADJUSTABLE).
2.1. BELOW 35F TEMPERATURE CONTROL VALVE WILL BE IN NORMALLY OPEN POSITION. FACE
AND BY-PASS DAMPERS WILL BE MODULATED TO MAINTAIN SUPPLY AIR DISCHARGE
TEMPERATURE SETTING
2.2. ABOVE 35F THE FACE DAMPER WILL BE IN ITS NORMALLY OPEN POSITION. THE BY-PASS
DAMPER WILL BE IN ITS NORMALLY CLOSED POSITION. THE TEMPERATURE CONTROL
VALVE WILL MODULATE TO MAINTAIN THE MINIMUM DISCHARGE TEMPERATURE
SETPOINT.
2.3. TEMPERATURE CONTROL GRAPHICS WILL INDICATE TC VALVE POSITION AND FACE AND
BY-PASS DAMPER POSITION.
3. SAFETIES SHALL FUNCTION AS FOLLOWS:
A. FREEZE STAT (TSL) WILL STOP THE SUPPLY FAN AND CLOSE THE OUTSIDE AIR DAMPER IF
IT SENSES A TEMPERATURE BELOW THE SETPOINT OF 38F (ADJ).
B. FREEZE STAT TRIP WILL INITIATE ALARM SIGNAL.
C. ACTIVATION OF ANY SMOKE DETECTOR WILL INITIATE AN ALARM.
a. IF SMOKE IS DETECTED BY SMOKE DETECTOR (SD-5) OR IF ANY OTHER SMOKE/FIRE
ALARM DEVICE IS ACTIVATED WITHIN THE BUILDING THE UNIT WILL STOP AND
ALL CONTROLLED DEVICES WILL GO TO THEIR NORMAL POSITIONS. THE STOP
SIGNAL WILL BE FROM THE FIRE ALARM SYSTEM CONTROL PANEL. SMOKE
DAMPERS SD-5, SHALL CLOSE. COORDINATION WITH EXISTING BUILDING FIRE
ALARM OPERATION IS REQUIRED.
D. PRESSURE DIFFERENTIAL SWITCH ACROSS THE AIR FILTER SHALL INDICATE ALARM
WHEN SETTING REACHES 0.5" INWG (ADJ) INDICATING A DIRTY FILTER CONDITION.
4. CIRCULATING PUMP (P-9) SHALL BE ENERGIZED WHEN TEMP OUTSIDE DROPS BELOW 55F (ADJ).
5. CURRENT SENSOR SHALL DETECT CIRCULATING PUMP (P-9) OPERATION. IF CURRENT SENSOR
DOES NOT DETECT CURRENT, ALARM SIGNAL FOR PUMP FAILURE SHALL BE INDICATED ON AHU
GRAPHIC. UPON PUMP FAILURE, FAN WILL STOP, OUTSIDE AIR DAMPERS WILL CLOSE.
AutoCAD SHX Text These prints are solely owned by MENDE ENGINEERING SOLUTIONS, LLC. The Drawings, Specifications and other documents prepared by MENDE ENGINEERING SOLUTIONS, LLC for this Project are instruments of MENDE ENGINEERING SOLUTIONS, LLC for use solely with respect to this Project and, unless otherwise provided, MENDE ENGINEERING SOLUTIONS, LLC shall be deemed the author of these documents and shall retain all common law, statutory and other reserved rights, including the copyright. MENDE ENGINEERING SOLUTIONS, LLC Drawings, Specifications or other documents shall not be used by the Owner or others on other projects, for additions to this Project or for completion of this Project by others, without the expressed written consent of MENDE ENGINEERING SOLUTIONS, LLC.
AutoCAD SHX Text DANGEROUS Architects, Pc
AutoCAD SHX Text 104 South Main Street Chelsea, Mi. 48118 734.475.3660 WWW.DANGEROUSARCHITECTS.COM zCopyright 2022, Dangerous Architects Pc.Copyright 2022, Dangerous Architects Pc.
4321 East Camden Road Osseo, MI 49266 Ph. (517) 254-4789 Fax (517) 254-4886 http://www.tac-associates.com
Project number
Date
Drawn by
Checked by
Approved by
Sheet No.
M-300-TC-6
NOT TO SCALE
JKM
JKM
MES
04-21-23 23523.1
HHWS/R CONTROLS
REPLACEMENT
BLDG 300 HVAC
FILE 472/22350.MNB
GU
S H
AR
RIS
ON
CO
RR
EC
TIO
NA
L F
AC
ILI
TY
AD
RI
AN
, M
IC
HI
G
AN
E
. B
EE
C H
ER
S
T.
ST
A
TE
O
F M
IC
H
IG
A
N
ENGINEERS, DESIGNERS,
PROBLEM SOLVERS
PROUDLY SERVING MICHIGAN
517-437-6998 www.MendeEngineeringSolutions.com
CONSULTANTS:
TAC ASSOCIATES, LLC
Consulting Engineers
GENERAL TC NEW WORK NOTES:
1. TEMPERATURE CONTROLS (TC) FOR PERIMETER RADIATION PUMPS,
RADIATION PUMPS, DOMESTIC HOT WATER PUMPS.
2. REFER TO AHU TC SHEETS FOR AHU PUMP OPERATION.
3. TC INTEGRATOR SHALL DETERMINE IF EXISTING DDC SYSTEM
REQUIRES UPGRADES FOR EXPANSION OF NEW DEVICES.
4. TC INTEGRATOR SHALL CLEAN AND RE-USE EXISTING CABINET FOR
INSTALLATION OF NEW DEVICES.
5. DOMESTIC HOT WATER PUMPS ARE EXISTING TO REMAIN. NEW
CURRENT SENSOR SWITCH SHALL BE INSTALLED FOR MONITORING.
DWH-2DWH-1
P-3
P-4
DHWR
DHWR
DHWS
HHWS / R TO AHU
COILS & VVR
REHEAT COILS
HHWSHHWR
HHWS
FROM B200
HHWR TO
B200
P-1
P-2
SEQUENCE OF OPERATION
A. HOT WATER RADIATION PUMPS P-1 AND P-2 WILL BE ENABLED BY THE
BMS TO OPERATE WHEN OUTDOOR AIR TEMPERATURE IS 55° (ADJ).
SUPPLY WATER TEMPERATURE IS PROVIDED BY BUILDING 200
ACCORDING TO BOILER REHEAT SCHEDULE.
B. P-1 SHALL OPERATE IN LEAD MODE AND P-2 SHALL BE IN STAND-BY
MODE. P-1 AND P-2 SHALL OPERATE IN LEAD-LAG CYCLES, EVERY 30
DAYS (ADJ).
1. P-1 AND P-2 SHALL ALLOW FOR VFD SETPOINTS TO BE
MONITORED AND CHANGED. CURRENT SENSOR SHALL INDICATE
OPERATION. UPON LOSS OF OPERATION, PUMP ALARM WILL
INDICATE, AND LAG PUMP SHALL BE INITIATED.
C. DOMESTIC HOT WATER PUMPS P-5 AND P-6 ARE EXISTING TO REMAIN.
A CURRENTS SENSOR SHALL BE INSTALLED TO MONITOR UMPM
OPERATION. LOSS OF CURRENT SHALL INDICATE PUMP FAILURE
ALARM.
HHWS / R TO
PERIMETER HEAT
AND CABINET
UNIT HEATERS
AutoCAD SHX Text These prints are solely owned by MENDE ENGINEERING SOLUTIONS, LLC. The Drawings, Specifications and other documents prepared by MENDE ENGINEERING SOLUTIONS, LLC for this Project are instruments of MENDE ENGINEERING SOLUTIONS, LLC for use solely with respect to this Project and, unless otherwise provided, MENDE ENGINEERING SOLUTIONS, LLC shall be deemed the author of these documents and shall retain all common law, statutory and other reserved rights, including the copyright. MENDE ENGINEERING SOLUTIONS, LLC Drawings, Specifications or other documents shall not be used by the Owner or others on other projects, for additions to this Project or for completion of this Project by others, without the expressed written consent of MENDE ENGINEERING SOLUTIONS, LLC.
AutoCAD SHX Text DANGEROUS Architects, Pc
AutoCAD SHX Text 104 South Main Street Chelsea, Mi. 48118 734.475.3660 WWW.DANGEROUSARCHITECTS.COM zCopyright 2022, Dangerous Architects Pc.Copyright 2022, Dangerous Architects Pc.
4321 East Camden Road Osseo, MI 49266 Ph. (517) 254-4789 Fax (517) 254-4886 http://www.tac-associates.com
Project number
Date
Drawn by
Checked by
Approved by
Sheet No.
M-300-TC-7
NOT TO SCALE
JKM
JKM
MES
04-21-23 23523.1
FAN & MISC CONTROLS
REPLACEMENT
BLDG 300 HVAC
FILE 472/22350.MNB
GU
S H
AR
RIS
ON
CO
RR
EC
TIO
NA
L F
AC
ILI
TY
AD
RI
AN
, M
IC
HI
G
AN
E
. B
EE
C H
ER
S
T.
ST
A
TE
O
F M
IC
H
IG
A
N
ENGINEERS, DESIGNERS,
PROBLEM SOLVERS
PROUDLY SERVING MICHIGAN
517-437-6998 www.MendeEngineeringSolutions.com
CONSULTANTS:
TAC ASSOCIATES, LLC
Consulting Engineers
GENERAL TC NEW WORK NOTES:
1. TEMPERATURE CONTROLS (TC) FOR
VENTILATION FANS AND HOODS AND TERMINAL
HEATING UNITS.
2. TC INTEGRATOR SHALL DETERMINE IF EXISTING
DDC SYSTEM REQUIRES UPGRADES FOR
EXPANSION OF NEW DEVICES.
3. EXISTING CONDUIT TO BE RE-USED SHALL
REMAIN.
4. ANY EXISTING CONDUIT WHICH WILL NOT TO BE
RE-USED, SHALL BE REMOVED.
FILTER
OUTSIDE
AIR N.C. SF-2 SUPPLY
AIR
FILTER
OUTSIDE
AIR N.C. SF-1 SUPPLY
AIR
N.C.
EXHAUST
AIR
ELECTRICAL ROOM
VENTILATION CONTROL (SF-2)
SEQUENCE OF OPERATION
A. SF-1 SHALL BE ENABLED THRU BMS WITH FAN
STARTER IN THE "AUTO" MODE. SPACE
THERMOSTAT SHALL CYCLE FAN ON AT 80°F (ADJ).
DAMPER MOTOR IN EXHAUST HOOD EH-1 SHALL
BE INTERLOCKED WITH SF-1.
1. CURRENT SENSOR IN SF-1 SHALL MONITOR FAN
OPERATION. ALARM SIGNAL SHALL INDICATE
WHEN FAN FAILS TO START ON TSTAT
COMMAND.
B. SF-2 SHALL BE ENABLED THRU BMS WITH FAN
STARTER IN THE "AUTO" MODE. SPACE
THERMOSTAT SHALL CYCLE FAN ON AT 80°F (ADJ).
DAMPER MOTOR IN EXHAUST HOOD EH-2 SHALL
BE INTERLOCKED WITH SF-2.
1. CURRENT SENSOR IN SF-2 SHALL MONITOR FAN
OPERATION. ALARM SIGNAL SHALL INDICATE
WHEN FAN FAILS TO START ON TSTAT
COMMAND.
A. SPACE THERMOSTAT SHALL CYCLE CABINET UNIT
HEATER FAN ON AND OFF TO MAINTAIN SPACE
TEMPERATURE OF 65°F (ADJ) . CURRENT SENSOR
SHALL INDICATE FAN STATUS. ALARM SIGNAL
WILL BE INITIATED IF CURRENT IS NOT
DETECTED. HEATING HOT WATER FLOW THRU
THE CUH WILL BE CONTINUOUS.
B. SPACE THERMOSTAT SHALL CYCLE UNIT HEATER
FAN ON AND OFF TO MAINTAIN SPACE
TEMPERATURE OF 65°F (ADJ) . CURRENT SENSOR
SHALL INDICATE FAN STATUS. ALARM SIGNAL
WILL BE INITIATED IF CURRENT IS NOT
DETECTED. HEATING HOT WATER FLOW THRU
THE UH WILL BE CONTINUOUS.
C. 2-WAY TEMPERATURE CONTROL VALVE ON FIN
TUBE RADIATION SHALL BE MODULATED TO
MAINTAIN SPACE TEMPERATURE OF 68°F (ADJ).
VALVE POSITION SHALL BE MONITORED ON THE
BMS. ALARM SIGNAL WILL BE INITIATED ON A
CONTINUED CALL FOR HEAT WITH THE VALVE
CLOSED. ON LOSS OF POWER, VALVE SHALL
RETURN TO NORMALLY OPEN.
EXHAUST HOOD
EH-2
N.C.
EXHAUST
AIR
EXHAUST HOOD
EH-1
MECHANICAL ROOM
VENTILATION CONTROL (SF-1)
HHWS
HHWR
HHWS
HHWR
CABINET HEATER CONTROL UNIT HEATER CONTROL
UH-1, 2, 3 & 4
FIN TUBE RADIATION CONTROL
NON INMATE AREAS
HHWS
HHWR
AutoCAD SHX Text These prints are solely owned by MENDE ENGINEERING SOLUTIONS, LLC. The Drawings, Specifications and other documents prepared by MENDE ENGINEERING SOLUTIONS, LLC for this Project are instruments of MENDE ENGINEERING SOLUTIONS, LLC for use solely with respect to this Project and, unless otherwise provided, MENDE ENGINEERING SOLUTIONS, LLC shall be deemed the author of these documents and shall retain all common law, statutory and other reserved rights, including the copyright. MENDE ENGINEERING SOLUTIONS, LLC Drawings, Specifications or other documents shall not be used by the Owner or others on other projects, for additions to this Project or for completion of this Project by others, without the expressed written consent of MENDE ENGINEERING SOLUTIONS, LLC.
AutoCAD SHX Text DANGEROUS Architects, Pc
AutoCAD SHX Text 104 South Main Street Chelsea, Mi. 48118 734.475.3660 WWW.DANGEROUSARCHITECTS.COM zCopyright 2022, Dangerous Architects Pc.Copyright 2022, Dangerous Architects Pc.
AutoCAD SHX Text 4321 East Camden Road Osseo, MI 49266 Ph. (517) 254-4789 Fax (517) 254-4886 http://www.tac-associates.com
M
Project number
Date
Drawn by
Checked by
Approved by
Sheet No.
CONSULTANTS:
23523.1
AS NOTED
TGC
TGC
CAD
10-12-23
FILE 472/22350.MNB
BLDG 200 BOILER &
BLDG 300 HVAC
REPLACEMENT
S T
A T
E
O
F
M
I C
H I G
A N
G U
S
H
A R
R I S
O N
C
R
R E
C T
I O
N
F A
C I L
I T
Y
E
B
E E
C H
R
S
T
A D
R I A
N
M
I C
H I G
A
TAC ASSOCIATES, LLC
4321 East Camden Road Osseo, MI 49266
Ph. (517) 254-4789 * Fax (517) 254-4886 http://www.tac-associates.com
TAC Project No. 23-016
Consulting Engineers
ENGINEERS, DESIGNERS,
PROBLEM SOLVERS
PROUDLY SERVING MICHIGAN
517-437-6998 www.MendeEngineeringSolutions.com
SEAL:
THOMAS
GERARD
CROW
License No.
6201055658
ENGINEER
ELECTRICAL DRAWING INDEX, SYMBOL LIST AND GENERAL ELECTRICAL NOTESE001
SHEET NUMBER SHEET TITLE
ELECTRICAL DRAWING INDEX
AS WALL MOUNTED OCCUPANCY SENSOR. REFER TO SCHEDULE ON LIGHTING DRAWINGS
3S THREE WAY SWITCH
EM
N.L.
EXISTING ELECTRICAL DEVICE OR FIXTURE TO REMAIN
ABOVE FINISH FLOOR
WEATHER PROOF
GROUND FAULT INTERRUPTERG.F.I.
W.P.
A.F.F.
(E)
DEVICE OR LIGHTING FIXTURE SERVED FROM EMERGENCY POWER
NIGHT LIGHT
EM
ELECTRICAL SYMBOL LIST
RECESSED ROUND LED OR FLUORESCENT FIXTURE
EXIT LIGHT DOUBLE FACE (SHADING INDICATES FACE OF FIXTURE)
SPECIAL PURPOSE OUTLET - TYPE AND SIZE AS INDICATED ON PLAN
WALL MOUNTED COMBINATION TELEPHONE/DATA OUTLET, MOUNTED AT 54" A.F.F.
DUPLEX RECEPTACLE / DUPLEX RECEPTACLE SERVED FROM EMERG. POWER
DOUBLE DUPLEX RECEPTACLE (SHADING INDICATES SERVED FROM EMERG. POWER)
PANEL BOARD
JUNCTION BOX
DUPLEX RECEPTACLE MOUNTED AT 6" ABOVE COUNTER TOP
J J
W
EXIT LIGHT, SINGLE FACE
NIGHT LIGHT / EMERGENCY FLUORESCENT FIXTURE
NIGHT LIGHT OR EMERGENCY LIGHT
WALL MOUNTED LIGHT FIXTURE
SINGLE POLE SWITCH
FOUR WAY SWITCH
2' X 4' FLUORESCENT FIXTURE
1' X 4' FLUORESCENT FIXTURE
2' X 2' FLUORESCENT FIXTURE
SYMBOL DESCRIPTION
S 4
N.L.
15 CANDELA SYNCHRONIZED FIRE ALARM SPEAKER/STROBE, WALL MOUNTED
15 CANDELA SYNCHRONIZED FIRE ALARM STROBE, WALL MOUNTED
SYNCHRONIZED FIRE ALARM STROBE, WALL MOUNTED (XX=CANDELA RATING, i.e. 30)
SYNCHRONIZED FIRE ALARM SPEAKER/STROBE, WALL MOUNTED (XX=CANDELA RATING, i.e. 30)XX
XX
SITE LIGHTING FIXTURE - BUILDING MOUNTED. SEE FIXTURE SCHEDULE
SITE LIGHTING FIXTURE - POLE MOUNTED (DOUBLE HEAD INDICATED)
F
R DUCT MOUNTED SMOKE DETECTOR (R = MOUNTED ON COMMON RETURN AIR DUCT)
CEILING MOUNTED FIRE ALARM SMOKE DETECTOR
FIRE ALARM SYSTEM MANUAL PULL STATION
TELEPHONE ONLY OUTLET
NEW LOCATION OF RELOCATED ELECTRICAL DEVICE OR FIXTURE(R)
EM
EMERGENCY FLUORESCENT FIXTURE
EM
EM
COMBINATION TELEPHONE/DATA OUTLET
WALL MOUNTED TELEPHONE ONLY OUTLET, MOUNTED AT 54" A.F.F.
W
FIRE ALARM SYSTEM CONTROL MODULE
B200 MECHANICAL ROOM FLOOR PLAN - ELECTRICAL DEMOLITIONED100.1
DISCONNECT SWITCH
MANUAL MOTOR STARTER WITH OVERLOADS (P= WITH PILOT LIGHT)
SINGLE PHASE MOTOR
P
THREE PHASE MOTOR
CONTROL PANEL
COMBINATION MAGNETIC MOTOR STARTER WITH OVERLOADS
1. EXTENT OF DEMOLITION IS NOT INTENDED TO BE SHOWN IN FULL ON THESE DRAWINGS. FINAL DESIGNED CONDITIONS ARE SHOWN. EACH TRADE/CONTRACTOR IS RESPONSIBLE FOR REMOVAL AS REQUIRED TO ACHIEVE FINAL DESIGN CONDITIONS. REFERENCES TO EXISTING AS IDENTIFIED ARE TO CLARIFY SCOPE OF
NEW CONSTRUCTION.
2. ALL WORK CONDITIONS ARE TO BE FIELD VERIFIED AND DETAILS ADJUSTED AS REQUIRED TO MAINTAIN FIRE RESISTIVE RATINGS. INTEGRITY OF INSTALLED SYSTEMS (EXISTING AND NEW) AND THE MATCHING OF
WORK WITH EXISTING CONDITIONS AND FINISHES.
3. REMOVAL WORK SHALL BE EXECUTED WITH DUE CARE, INCLUDING PROTECTION OF EXISTING MATERIALS/SYSTEMS TO REMAIN SHORING, BRACING, ETC. EACH TRADE/SUBCONTRACTORS WILL BE
RESPONSIBLE FOR ANY DAMAGE THEY CAUSE TO OTHER'S WORK.
4. THE FULL EXTENT OF THE WORK FOR EACH TRADE IS IDENTIFIED THROUGHOUT ALL THE DRAWINGS. DO NOT ASSUME OR OMIT INDIVIDUAL TRADE WORK NOT SHOWN IN THE INDIVIDUAL TRADE DRAWINGS.
FAILURE TO REVIEW ALL DRAWINGS FOR AN INDIVIDUAL TRADE’S COMPLETE SCOPE OF WORK WILL RESULT
IN DENIAL FOR ANY CHANGE ORDER REQUESTS FOR MISSED ITEMS DURING BIDDING.
5. SUBCONTRACTORS AND ALL TRADES MUST EXAMINE AREAS, DIMENSIONS CONDITIONS AND SUBSTRATES AFFECTING THE WORK AND THE CONDITIONS UNDER WHICH THE WORK IS TO BE INSTALLED, APPLIED AND COMPLETED. NOTIFY THE ARCHITECT IN WRITING OF UNSATISFACTORY CONDITIONS AND OTHER
CONDITIONS DETRIMENTAL TO THE PROPER AND TIMELY COMPLETION OF THE WORK.
A. DO NOT PROCEED WITH THE WORK UNTIL THE UNSATISFACTORY CONDITIONS HAVE BEEN
CORRECTED IN THE MANNER ACCEPTABLE TO THE CONTRACTOR OR TRADE PERFORMING THE
WORK. PROCEED WITH INSTALLATION ONLY AFTER UNSAFE OR UNSATISFACTORY CONDITIONS
HAVE BEEN CORRECTED.
B. BEGINNING WORK MEANS ACCEPTANCE OF THE CONDITIONS.
C. NO CHANGE ORDERS FOR ADDITIONAL WORK WILL BE ACCEPTED FOR CONDITIONS NOT
IDENTIFIED DURING THE EXAMINATION PERIOD PRIOR TO THE COMMENCING OF WORK.
6. CONTRACTOR(S) WARRANTS THEY HAVE EXAMINED THOROUGHLY ALL DRAWINGS AND SPECIFICATIONS DIRECTLY AND INDIRECTLY RELATED TO THEIR WORK. BY BEGINNING THE WORK, CONTRACTOR CERTIFIES THAT ALL NECESSARY ITEMS REQUIRED TO PERFORM HIS WORK HAVE BEEN IDENTIFIED AND DOCUMENTED
IN THE DRAWINGS AND/OR SPECIFICATIONS.
A. NOTIFY THE ARCHITECT IN WRITING OF ANY DISCREPANCIES, MISSING INFORMATION OR ANY
UNCLEAR ITEMS WHICH WILL AFFECT THE WORK TO BE PERFORMED. DO NOT PROCEED WITH
THE WORK UNTIL THE DISCREPANCIES, MISSING INFORMATION OR ANY UNCLEAR ITEMS HAVE
BEEN CLARIFIED OR CORRECTED TO THE CONTRACTOR OR TRADE PERFORMING THE WORK.
B. BEGINNING THE WORK INDICATES FULL ACCEPTANCE AND CORRECTNESS OF THE
INFORMATION PROVIDED.
C. NO CHANGE ORDERS FOR ADDITIONAL WORK WILL BE ACCEPTED FOR ANY DISCREPANCIES,
MISSING INFORMATION OR UNCLEAR ITEMS OR INFORMATION NOT IDENTIFIED DURING THE
EXAMINATION PERIOD PRIOR TO THE COMMENCING OF WORK.
7. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL NECESSARY FIRESTOPPING AROUND ALL PENETRATIONS OF FIRE RATED WALLS, CEILINGS AND FLOORS. REFER TO ARCHITECTURAL
AND ELECTRICAL SPECIFICATIONS FOR ADDITIONAL INFORMATION REGARDING THE SPECIFIC
FIRESTOPPING REQUIREMENTS AND PRODUCT SPECIFICATIONS.
8. ALL ANCHORS FOR ELECTRICAL SYSTEMS SHALL BE STEEL. REFER TO SPECIFICATIONS FOR SPECIFIC
APPROVED PRODUCTS. UNDER NO CIRCUMSTANCES SHALL PLASTIC ANCHORS BE USED.
ELECTRICAL GENERAL NOTES
E001
SYMBOL LIST, DRAWING INDEX, AND
GENERAL ELECTRICAL NOTES
E200.1 B200 ELECTRICAL SCHEDULES AND MISCELLANEOUS WIRING DIAGRAMS
B200 MECHANICAL ROOM FLOOR PLAN - ELECTRICAL NEW WORKE100.1
TAMPER-RESISTANT DUPLEX RECEPTACLE, TYPE AS INDICATED (i.e. WP, GFI, ETC.)
FIXTURE TYPE "OA" MOUNTING DETAIL (SECTION)
NO SCALE
ARCHITECTURAL SECTIONS FOR
EXTERIOR WALL. REFER TO
ADDITIONAL INFORMATION.
COVER
LOCKNUT
REQUIRED.
BETWEEN STUDS AS
STEEL FOR BOX SUPPORT
PROVIDE MISCELLANEOUS
CONDUIT TO NEXT FIXTURE OR HOMERUN.
FIXTURE TYPE "OA"
BACKPLATE AND ANCHORS.
(TYPICAL)
TO WALL.
ANCHORED DIRECTLY
BUSH BOTH ENDS.
SHALL BE RIGID STEEL AND
THRU THE WALL CONDUIT
JUNCTION BOX MOUNTED INSIDE BUILDING,
ABOVE ACCESSIBLE CEILING SPACE OR FLUSH
IN EXTERIOR WALL CONSTRUCTION. WHERE
MOUNTED FLUSH IN WALL CONSTRUCTION,
PROVIDE BLANK COVERPLATE TO MATCH
SURROUND WALL SURFACE.
NOTE: FIXTURE SHAPE CONVEYED IN THE ABOVE DETAIL IS INTENDED TO REPRESENT THE GENERAL SHAPE OF THE LIGHT FIXTURE; HOWEVER THE DETAIL IS NOT INTENDED TO BE AN EXACT GRAPHICAL REPRESENTATION OF THE SPECIFIED FIXTURE. REFER TO THE LIGHTING FIXTURE SCHEDULE AND ASSOCIATED CUT SHEET FOR AN EXACT
DESCRIPTION AND REPRESENTATION OF THE SPECIFIED FIXTURE.
TYPE DESCRIPTION
“OA” LED FULL CUT-OFF TYPE WALL MOUNTED LUMINAIRE. HIGH OUTPUT LED LIGHT ENGINE VISUAL COMFORT FORWARD THROW DISTRIBUTION, AND PROVIDING A TOTAL DELIVERED LUMEN OUTPUT OF 2,023 LUMENS AT A COLOR TEMPERATURE OF 4,000 DEGREE K AND A MINIMUM OF 80 CRI, RATED FOR A MINUMUM OF 100,000 HOURS OF CONTINUOUS OPERATION FROM MINUS 30 DEGREE C TO PLUS 40 DEGREE C. FIXTURE TO BE DLC COMPLIANT. FIXTURE TO HAVE A B.U.G.
RATING OF B1-U0-G0. ALUMINUM HOUSING. 11.5” WIDE X 9” HIGH X 7” DEEP. BRONZE FINISH. TOTAL FIXTURE WATTAGE TO BE 15 WATTS. FIXTURE TO BE UL LISTED FOR WET LOCATION USE. FIXTURE TO INCLUDE INTEGRAL POWER SUPPLY (DRIVER), UL LISTED. FIXTURE TO INCLUDE STANDALONE CONTROLS CONSISTING OF BI-LEVEL MOTION SENSOR CONTROL (100%/35%) AND INTEGRAL PHOTOCELL FOR DUSK TO DAWN OPERATION. FIXTURE SHALL OPERATE FROM DUSK TO DAWN BASED ON THE PHOTOCELL CONTROL. WHEN NO MOTION IS DETECTED, THE FIXTURE SHALL DIM TO 35% LIGHT OUTPUT;
WHEN MOTION IS DETECTED THE FIXTURE SHALL GO TO 100% FULL LIGHT OUTPUT. UNIVERSAL 120-277 VOLT OPERATION.
5-YEAR WARRANTY. LITHONIA “WDGE2 LED” WDGE2 LED-P2W-40K-80CRI-VF-MVOLT-PIR1FC3V-DDBXD, WITH EXACT FINISH TO BE SELECTED BY ARCHITECT PRIOR TO ORDERING OF FIXTURE, OR EQUAL BY MCGRAW-EDISON OR BEACON LIGHTING.
LIGHTING FIXTURE SCHEDULE
B300 MECHANICAL ROOM FLOOR PLAN - ELECTRICAL DEMOLITIONED100.2
E200.2 B300 ELECTRICAL SCHEDULES AND MISCELLANEOUS WIRING DIAGRAMS
B300 MECHANICAL ROOM FLOOR PLAN - ELECTRICAL NEW WORKE100.2
WP
GFI
No. Description Date
Scale
Project number
Date
Drawn by
Checked by
Approved by
Sheet No.
CONSULTANTS:
23523.1
AS NOTED
TGC
TGC
CAD
10-12-23
FILE 472/22350.MNB
BLDG 200 BOILER
REPLACEMENT
S T
A T
E
O
F
M
I C
H I G
A N
G U
S
H
A R
R I S
R
R E
C T
I O
N
F A
C I L
I T
Y
B
E E
C H
A D
R I A
N
M
I C
H I G
TAC ASSOCIATES, LLC
4321 East Camden Road Osseo, MI 49266
Ph. (517) 254-4789 * Fax (517) 254-4886 http://www.tac-associates.com
TAC Project No. 23-016
Consulting Engineers
ENGINEERS, DESIGNERS,
PROBLEM SOLVERS
PROUDLY SERVING MICHIGAN
517-437-6998 www.MendeEngineeringSolutions.com
SEAL:
THOMAS
GERARD
CROW
License No.
6201055658
ENGINEER
SCALE:
NORTH
B-200 MECHANICAL ROOM FLOOR PLAN - ELECTRICAL DEMOLITION
1/4" = 1'-0"
CONTRACTORS PRE-BID NOTIFICATION:
ALL EXISTING ITEMS INDICATED IN THE CONTRACT DRAWINGS HAVE BEEN TAKEN FROM THE
OWNER'S LIMITED RECORD DRAWINGS AND SUBSTANTIAL FIELD OBSERVATIONS AND VERIFICATION.
THIS CONTRACTOR AND ALL RELATED SUB-CONTRACTORS SHALL VISIT THE SITE AND COMPLETELY
UNDERSTAND THE CONDITIONS UNDER WHICH THE WORK MUST BE PERFORMED. IF A DEPARTURE
FROM THE DESIGN INTENT OF THE DOCUMENTS IS REQUIRED DUE TO THE ACTUAL FIELD
CONDITIONS OBSERVED BY THE CONTRACTOR, THE CONTRACTOR SHALL NOTIFY THE ARCHITECT IN WRITING FOR RESOLUTION PRIOR TO SUBMITTING FINAL BID OR ENTERING INTO A CONTRACT FOR CONSTRUCTION. FAILURE TO PROVIDE THE ARCHITECT WITH NOTIFICATION SHALL RESULT IN THE
CONTRACTOR BEING HELD RESPONSIBLE TO COMPLETE ALL WORK TO MEET THE DESIGN INTENT
WITH NO ADDITIONAL COST BEING INCURRED BY THE OWNER.
1 ELECTRICAL CONTRACTOR SHALL DISCONNECT AND REMOVE EXISTING BRANCH CIRCUIT
CONNECTION TO EXISTING MECHANICAL EQUIPMENT INDICATED TO BE REPLACED BY
MECHANICAL TRADES. REVISE EXISTING JUNCTION BOX CONNECTION AT EQUIPMENT TO BE
REPLACED WITH NEW AS REQUIRED TO FACILITATE SERVING NEW EQUIPMENT TO BE INSTALLED
AT THIS LOCATION WITH THE EXISTING BRANCH CIRCUIT. REFER TO GENERAL NOTE #5 FOR
CIRCUIT TRACING REQUIRED TO BE PERFORMED BY THE ELECTRICAL CONTRACTOR PRIOR TO
START OF CONSTRUCTION TO IDENTIFY THE EXISTING BRANCH CIRCUIT SERVING THE
EQUIPMENT TO BE REPLACED. BRANCH CIRCUIT IDENTIFIED BY CIRCUIT TRACING SHALL BE
REFLECTED ON THE AS-BUILT RECORD DRAWINGS. DISCONNECT AND REMOVE EXISTING
DISCONNECT SWITCH AND/OR MOTOR STARTER SERVING EQUIPMENT AND SALVAGE FOR
OWNER'S USE IF THE SWITCH AND/OR STARTER IS STILL IN GOOD CONDITION. IF SWITCH
AND/OR MOTOR STARTER IS IN POOR CONDITION, DISPOSE OF SWITCH AND/OR MOTOR
STARTER WITH OTHER MATERIALS IN A LEGAL MANNER. MATERIALS THAT ARE CAPABLE OF
BEING RECYCLED SHALL BE DISPOSED OF AT A LOCAL RECYCLING CENTER. REFER TO THE NEW
WORK POWER AND SYSTEMS FLOOR PLANS FOR ADDITIONAL INFORMATION.
ELECTRICAL CONTRACTOR SHALL DISCONNECT AND REMOVE EXISTING BRANCH CIRCUIT
CONDUIT AND WIRING SERVING MECHANICAL EQUIPMENT INDICATED COMPLETE TO
SOURCE. EXISTING CONDUIT MAY REMAIN AND BE RECONFIGURED TO SUPPORT SERVING THE
NEW EQUIPMENT TO BE INSTALLED IN THE SAME LOCATION FROM THE EXISTING POWER
PANEL. EXISTING SWITCH TO BE REUSED TO SERVE NEW EQUIPMENT. EXISTING FUSES TO BE
REPLACED WITH NEW FUSES AS INDICATED ON THE NEW WORK PLAN. DISCONNECT AND
REMOVE EXISTING DISCONNECT SWITCH FROM UNIT AND SALVAGE FOR OWNER'S USE IF THE
SWITCH IS STILL IN GOOD CONDITION. IF SWITCH IS IN POOR CONDITION, DISPOSE OF
SWITCH WITH OTHER MATERIALS IN A LEGAL MANNER. MATERIALS THAT ARE CAPABLE OF
BEING RECYCLED SHALL BE DISPOSED OF AT A LOCAL RECYCLING CENTER. REFER TO GENERAL
NOTE #5 FOR CIRCUIT TRACING TO BE PERFORMED BY ELECTRICAL CONTRACTOR PRIOR TO
START OF CONSTRUCTION TO IDENTIFY THE EXISTING BRANCH CIRCUIT SERVING THE
EQUIPMENT TO BE REPLACED WITH NEW.
ELECTRICAL CONTRACTOR SHALL DISCONNECT AND REMOVE EXISTING BRANCH CIRCUIT
CONDUIT AND WIRING SERVING MECHANICAL EQUIPMENT INDICATED COMPLETE TO
SOURCE. EXISTING CONDUIT MAY REMAIN AND BE RECONFIGURED TO SUPPORT SERVING THE
NEW EQUIPMENT TO BE INSTALLED IN THE SAME LOCATION FROM THE EXISTING POWER
PANEL. EXISTING CIRCUIT BREAKER TO BE REMOVED AND REPLACED WITH A NEW CIRCUIT
BREAKER WITH THE TRIP RATING AS INDICATED ON THE NEW WORK PLAN. DISCONNECT AND
REMOVE EXISTING DISCONNECT SWITCH FROM UNIT AND SALVAGE FOR OWNER'S USE IF THE
SWITCH IS STILL IN GOOD CONDITION. IF SWITCH IS IN POOR CONDITION, DISPOSE OF
SWITCH WITH OTHER MATERIALS IN A LEGAL MANNER. MATERIALS THAT ARE CAPABLE OF
BEING RECYCLED SHALL BE DISPOSED OF AT A LOCAL RECYCLING CENTER. REFER TO GENERAL
NOTE #5 FOR CIRCUIT TRACING TO BE PERFORMED BY ELECTRICAL CONTRACTOR PRIOR TO
START OF CONSTRUCTION TO IDENTIFY THE EXISTING BRANCH CIRCUIT SERVING THE
EQUIPMENT TO BE REPLACED WITH NEW.
ELECTRICAL CONTRACTOR SHALL DISCONNECT AND REMOVE EXISTING BRANCH CIRCUIT
CONDUIT AND WIRING SERVING MECHANICAL EQUIPMENT INDICATED COMPLETE TO
SOURCE. LABEL EXISTING CIRCUIT BREAKER SERVING EQUIPMENT AS "SPARE". REFER TO
GENERAL NOTE #5 FOR CIRCUIT TRACING REQUIRED TO BE PERFORMED BY THE ELECTRICAL
CONTRACTOR PRIOR TO START OF CONSTRUCTION TO IDENTIFY THE EXISTING BRANCH
CIRCUIT SERVING THE EQUIPMENT TO BE REPLACED. BRANCH CIRCUIT IDENTIFIED BY CIRCUIT
TRACING SHALL BE REFLECTED ON THE AS-BUILT RECORD DRAWINGS. DISCONNECT AND
REMOVE EXISTING DISCONNECT SWITCH AND MOTOR STARTER SERVING EQUIPMENT AND
SALVAGE FOR OWNER'S USE IF THE SWITCH AND/OR STARTER IS STILL IN GOOD CONDITION.
IF SWITCH AND/OR MOTOR STARTER IS IN POOR CONDITION, DISPOSE OF SWITCH AND/OR
MOTOR STARTER WITH OTHER MATERIALS IN A LEGAL MANNER. MATERIALS THAT ARE CAPABLE
OF BEING RECYCLED SHALL BE DISPOSED OF AT A LOCAL RECYCLING CENTER. NOTE THAT THE EXISTING "SPARE" CIRCUIT MAY BE REUSED TO SERVE NEW EQUIPMENT, WHERE INDICATED ON
THE NEW WORK PLANS.
ELECTRICAL CONTRACTOR SHALL DISCONNECT, REMOVE AND SALVAGE FOR THE OWNER THE
EXISTING MOTOR STARTER SERVING EXISTING PUMP REMOVED BY DEMOLITION WORK.
ELECTRICAL CONTRACTOR SHALL DISCONNECT AND REMOVE EXISTING WEATHER-PROOF /
GFCI DUPLEX RECEPTACLE AT MECHANICAL EQUIPMENT TO BE REMOVED. DISCONNECT AND
REMOVE EXISTING BRANCH CIRCUIT CONDUIT AND WIRING SERVING RECEPTACLE TO NEAREST
JUNCTION BOX TO ALLOW FOR REUSE TO SERVE NEW RECEPTACLE TO BE MOUNTED AT NEW
EQUIPMENT TO BE INSTALLED IN THE SAME LOCATION. REFER TO NEW WORK PLAN FOR
ADDITIONAL INFORMATION.
DEMOLITION KEY NOTES
ED100.1
B200 MECHANICAL ROOM FLOOR
PLAN - ELECTRICAL DEMOLITION
ED100.1
1.
2.
ALL DEVICES INDICATED WITH SOLID LIGHT LINES ARE EXISTING DEVICES TO REMAIN.
ALL DEVICES AND FIXTURES INDICATED WITH SOLID DARK CROSS-HATCHED LINES ARE
EXISTING TO BE REMOVED OR RELOCATED BY THIS ELECTRICAL CONTRACTOR.
ELECTRICAL CONTRACTOR SHALL PROVIDE DEMOLITION OF ELECTRICAL DEVICES, CONDUIT,
WIRING, FIXTURES, EQUIPMENT, ETC. AS REQUIRED TO ACCOMMODATE ARCHITECTURAL,
MECHANICAL AND ELECTRICAL REVISIONS. ELECTRICAL DEMOLITION SHEET PROVIDES A
GENERAL GUIDELINE AS TO THE SCOPE OF THE WORK. HOWEVER, ALL DEMOLITION
REQUIREMENTS MAY NOT BE INDICATED. PROVIDE DEMOLITION AS REQUIRED TO
ACCOMMODATE PROJECT REVISIONS.
COORDINATE DEMOLITION REQUIREMENTS WITH THE WORK OF OTHER TRADES.
PRIOR TO START OF CONSTRUCTION, AND PRIOR TO ANY DEMOLITION WORK THE
ELECTRICAL CONTRACTOR SHALL PERFORM CIRCUIT TRACING TO IDENTIFY ALL EXISTING 120
VOLT AND 480 VOLT BRANCH CIRCUITS SERVING THE RENOVATION AREA, AND TO IDENTIFY
THE AVAILABLE BRANCH CIRCUITS THAT MAY BE RE-USED AS PART OF THE PROPOSED
RENOVATION, AS WELL AS CIRCUITS THAT SERVE EXISTING DEVICES OR EQUIPMENT OUTSIDE
OF THE WORK AREA THAT ARE TO REMAIN AND BE MAINTAINED.
ELECTRICAL GENERAL NOTES:
3.
4.
5.
MECH
EQUIPMENT
ELECTRICAL
EQUIPMENT
LOW ROOF
EXISTING PANEL "MPB BLDG-200"
480Y/277V-3Ø-4W
(TO REMAIN)
STAIR
ROOF
EXISTING AC-1
480V-3Ø
TO BE REMOVED
EXISTING P-7
120V, TO BE REMOVED
AND REPLACED.
EXISTING AHU-1
(TO REMAIN)
EXISTING AHU-2
(TO REMAIN)
EXISTING AHU-3
(TO REMAIN)
EXISTING AHU-4
(TO REMAIN)
EXISTING BOILER
COMBUSTION AIR FAN
TO BE REMOVED
EXISTING BOILER "B-1"
TO BE REMOVED
EXISTING…
This is the start of the file's text. The full file is on GovTribe.