GUS HARRISON 472-22350MNB PLANS 6 OF 6.pdf

PDF 4 MB Posted

Attached to
472/22350. MNB; GHCF - BLDG 200 Boiler Replacement
Solicitation number
RFQ - 171 - 240000000186
Issued by
Lenawee County, Michigan

About this file

This document is a set of plans and specifications for the replacement of the HVAC system in Building 300 at the Gus Harrison Correctional Facility in Adrian, Michigan. The project involves the replacement of the existing air handling units, controls, piping, and associated equipment. Key details include the replacement of 5 air handling units, various pumps, and a new air-cooled condensing unit. The electrical work includes the replacement of existing disconnects, motor starters, and the connection of the new mechanical equipment. The project is being managed by the State of Michigan and Lenawee County. Bids for this project are due by 2:00 PM on a specified date, and the project specifications indicate that all work must be coordinated with the Owner and Temperature Control contractor.

The pricing terms and funding sources are not explicitly stated in the provided documents. However, the documents indicate that the work is a state and local contract opportunity, suggesting competitive bidding requirements. The documents do not mention any set-asides, incumbent contractors, or specific funding amounts or sources. The contract term and any renewal options are also not specified.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BLDG 300 HVAC

REPLACEMENT

FILE 472/22350.MNB

BLDG 300 HVAC

REPLACEMENT

FILE 472/22350.MNB

No. Description Date

Scale

Project number

Date

Drawn by

Checked by

Approved by

Sheet No.

M-300-TC-1

NOT TO SCALE

JKM

JKM

MES

04-21-23 23523.1

AHU-1 CONTROLS

REPLACEMENT

BLDG 300 HVAC

FILE 472/22350.MNB

GU

S H

AR

RIS

ON

CO

RR

EC

TIO

NA

L F

AC

ILI

TY

AD

RI

AN

, M

IC

HI

G

AN

E

. B

EE

C H

ER

S

T.

ST

A

TE

O

F M

IC

H

IG

A

N

ENGINEERS, DESIGNERS,

PROBLEM SOLVERS

PROUDLY SERVING MICHIGAN

517-437-6998 www.MendeEngineeringSolutions.com

CONSULTANTS:

TAC ASSOCIATES, LLC

Consulting Engineers

GENERAL TC NEW WORK NOTES:

1. TEMPERATURE CONTROLS (TC) FOR AHU-1 / P-5. REFER TO SHEET

TC-D1 AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.

2. REFER TO MECHANICAL SHEETS FOR DEVICE LOCATIONS AND

ADDITIONAL INFORMATION.

3. TC INTEGRATOR SHALL DETERMINE IF EXISTING DDC SYSTEM

REQUIRES UPGRADES FOR EXPANSION OF NEW DEVICES.

4. TC INTEGRATOR SHALL CLEAN AND RE-USE EXISTING CABINET FOR

INSTALLATION OF NEW DEVICES.

5. EXISTING CONDUIT TO BE RE-USED SHALL REMAIN.

6. COORDINATE WITH FIRE ALARM VENDOR AS REQUIRED. SEE

SEQUENCE OF OPERATION THIS SHEET.

SUPPLY

AHU-1

HEAT

COIL

N.C.C.

N.O.

HHWS

HHWR

P-5

L

OUTSIDE

AIR N.C.N.C.

FILTER

N.O.

SUPPLY

AIR

RETURN

AIR

EXHAUST

AIR

RETURN

RAF-1N.C.

N.O.

H

SEQUENCE OF OPERATION

1. WITH THE EXISTING SUPPLY AND RETURN MOTOR STARTER IN THE "AUTO" MODE, THE UNIT WILL BE ENABLED BY THE BUILDING MANAGEMENT SYSTEM (BMS). THE UNIT WILL OPERATE ACCORDING TO AN OCCUPIED AND NIGHT

SET BACK SCHEDULE.

A. OCCUPIED: RETURN AIR AND OUTDOOR AIR DAMPERS WILL OPEN WHEN AHU FANS ARE ENABLED. OUTSIDE

AIR DAMPER, RELIEF AIR, AND RETURN AIR DAMPER WILL OPEN TO MAINTAIN 55°F (ADJ).

B. WHEN BOTH SUPPLY & RETURN FANS ARE OPERATING THEIR ASSOCIATE PILOT LAMPS WILL BE ENERGIZED, INDICATING OPERATION AT THE TC PANEL.

C. IF CURRENT SENSOR DOES NOT INDICATE FAN OPERATION, AN ALARM SIGNAL WILL INDICATING FAN UNIT

FAILURE.

2. FACE AND BY-PASS DAMPERS AND TEMPERATURE CONTROL VALVE SHALL BE CONTROLLED TO MODULATE TO

MAINTAIN SUPPLY AIR TEMPERATURE SET-POINT OF 68F (ADJUSTABLE).

2.1. BELOW 35F TEMPERATURE CONTROL VALVE WILL BE IN NORMALLY OPEN POSITION. FACE AND BY-PASS

DAMPERS WILL BE MODULATED TO MAINTAIN SUPPLY AIR DISCHARGE TEMPERATURE SETTING.

2.2. ABOVE 35F THE FACE DAMPER WILL BE IN ITS NORMALLY OPEN POSITION. THE BY-PASS DAMPER WILL BE IN

ITS NORMALLY CLOSED POSITION. THE TEMPERATURE CONTROL VALVE WILL MODULATE TO MAINTAIN THE

DISCHARGE AIR TEMPERATURE SETPOINT.

3. TEMPERATURE CONTROL GRAPHICS WILL INDICATE TC VALVE POSITION AND FACE AND BY-PASS DAMPER

POSITION.

4. WHEN THE OUTSIDE AIR TEMPERATURE AND ENTHALPY IS SUITABLE, THE OUTSIDE AND RETURN AIR DAMPER

WILL MODULATE TO MAINTAIN A MIXED AIR TEMPERATURE OF 55 F (ADJ.).

5. WHEN THE OUTSIDE AIR TEMPERATURE AND ENTHALPY IS HIGHER THAN ECONOMIZER SETPOINTS, THE OUTSIDE AIR DAMPERS WILL MOVE TO A MINIMUM POSITION 30%OA (ADJ). THE RETURN AIR DAMPER WILL MOVE TO ITS

CORRESPONDING POSITION.

6. SAFETIES SHALL FUNCTION AS FOLLOWS:

A. FREEZE STAT (TSL) WILL STOP THE SUPPLY FAN AND CLOSE THE OUTSIDE & RELIEF AIR DAMPERS IF IT

SENSES A TEMPERATURE BELOW THE SETPOINT OF 38F (ADJ).

B. FREEZE STAT TRIP WILL INITIATE ALARM SIGNAL.

C. HIGH LIMIT (TSH) AIR SENSOR WILL STOP THE SUPPLY FAN AND CLOSE THE OUTSIDE AND RELIEF AIR

DAMPERS IF IT SENSES A TEMPERATURE ABOVE THE SETPOINT OF 125F (ADJ).

D. HIGH LIMIT AIR STAT TRIP WILL INITIATE ALARM SIGNAL.

E. ACTIVATION OF ANY SMOKE DETECTOR WILL INITIATE AN ALARM.

a. IF SMOKE IS DETECTED BY SMOKE DETECTOR (SD-3) OR IF ANY OTHER SMOKE/FIRE ALARM DEVICE IS

ACTIVATED WITHIN THE BUILDING THE UNIT WILL STOP AND ALL CONTROLLED DEVICES WILL GO TO THEIR NORMAL POSITIONS. THE STOP SIGNAL WILL BE FROM THE FIRE ALARM SYSTEM CONTROL PANEL. SMOKE DAMPERS SD-3 SHALL CLOSE. COORDINATION WITH EXISTING BUILDING FIRE ALARM

OPERATION IS REQUIRED.

F. PRESSURE DIFFERENTIAL SWITCH ACROSS THE AIR FILTER SHALL INDICATE ALARM WHEN SETTING REACHES

0.5" INWG (ADJ) INDICATING A DIRTY FILTER CONDITION.

6. DURING NIGHT SET BACK SCHEDULE, AHU-1 SUPPLY/RETURN FAN SHALL CYCLE THE UNIT ON/OFF TO MAINTAIN THE DESIRED SPACE NIGHT SETBACK TEMPERATURE. DURING NIGHT OPERATION THE OUTSIDE AIR AND RELIEF

AIR DAMPERS MOVES TO CLOSE AND RETURN AIR DAMPERS OPEN.

7. CIRCULATING PUMP (P-5) SHALL BE ENERGIZED WHEN TEMP OUTSIDE DROPS BELOW 55F (ADJ).

8. CURRENT SENSOR SHALL DETECT CIRCULATING PUMP (P-5) OPERATION. IF CURRENT SENSOR DOES NOT DETECT CURRENT, ALARM SIGNAL FOR PUMP FAILURE SHALL BE INDICATED ON AHU GRAPHIC. UPON PUMP FAILURE, FAN

WILL STOP, OUTSIDE AND RELIEF AIR DAMPERS WILL CLOSE.

AutoCAD SHX Text These prints are solely owned by MENDE ENGINEERING SOLUTIONS, LLC. The Drawings, Specifications and other documents prepared by MENDE ENGINEERING SOLUTIONS, LLC for this Project are instruments of MENDE ENGINEERING SOLUTIONS, LLC for use solely with respect to this Project and, unless otherwise provided, MENDE ENGINEERING SOLUTIONS, LLC shall be deemed the author of these documents and shall retain all common law, statutory and other reserved rights, including the copyright. MENDE ENGINEERING SOLUTIONS, LLC Drawings, Specifications or other documents shall not be used by the Owner or others on other projects, for additions to this Project or for completion of this Project by others, without the expressed written consent of MENDE ENGINEERING SOLUTIONS, LLC.

AutoCAD SHX Text DANGEROUS Architects, Pc

AutoCAD SHX Text 104 South Main Street Chelsea, Mi. 48118 734.475.3660 WWW.DANGEROUSARCHITECTS.COM zCopyright 2022, Dangerous Architects Pc.Copyright 2022, Dangerous Architects Pc.

AutoCAD SHX Text 4321 East Camden Road Osseo, MI 49266 Ph. (517) 254-4789 Fax (517) 254-4886 http://www.tac-associates.com

Project number

Date

Drawn by

Checked by

Approved by

Sheet No.

M-300-TC-2

NOT TO SCALE

JKM

JKM

MES

04-21-23 23523.1

AHU-2 CONTROLS

REPLACEMENT

BLDG 300 HVAC

FILE 472/22350.MNB

GU

S H

AR

RIS

ON

CO

RR

EC

TIO

NA

L F

AC

ILI

TY

AD

RI

AN

, M

IC

HI

G

AN

E

. B

EE

C H

ER

S

T.

ST

A

TE

O

F M

IC

H

IG

A

N

ENGINEERS, DESIGNERS,

PROBLEM SOLVERS

PROUDLY SERVING MICHIGAN

517-437-6998 www.MendeEngineeringSolutions.com

CONSULTANTS:

TAC ASSOCIATES, LLC

Consulting Engineers

SUPPLY

AHU-2

HEAT

COIL

N.C.C.

N.O.

HHWS

HHWR

P-6

L

OUTSIDE

AIR N.C.N.C.

FILTER

N.O.

SUPPLY

AIR

RETURN

AIR

EXHAUST

AIR

RETURN

RAF-2N.C.

N.O.

H

GENERAL TC NEW WORK NOTES:

1. TEMPERATURE CONTROLS (TC) FOR AHU-2 / P-6. REFER TO SHEET

TC-D2 AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.

2. REFER TO MECHANICAL SHEETS FOR DEVICE LOCATIONS AND

ADDITIONAL INFORMATION.

3. TC INTEGRATOR SHALL DETERMINE IF EXISTING DDC SYSTEM

REQUIRES UPGRADES FOR EXPANSION OF NEW DEVICES.

4. TC INTEGRATOR SHALL CLEAN AND RE-USE EXISTING CABINET FOR

INSTALLATION OF NEW DEVICES.

5. EXISTING CONDUIT TO BE RE-USED SHALL REMAIN.

6. COORDINATE WITH FIRE ALARM VENDOR AS REQUIRED. SEE

SEQUENCE OF OPERATION THIS SHEET.

SEQUENCE OF OPERATION

1. WITH THE EXISTING SUPPLY AND RETURN MOTOR STARTER IN THE "AUTO" MODE, THE UNIT WILL BE ENABLED BY THE BUILDING MANAGEMENT SYSTEM (BMS). THE UNIT WILL OPERATE ACCORDING TO AN OCCUPIED AND NIGHT

SET BACK SCHEDULE.

A. OCCUPIED: RETURN AIR AND OUTDOOR AIR DAMPERS WILL OPEN WHEN AHU FANS ARE ENABLED. OUTSIDE

AIR DAMPER, RELIEF AIR AND RETURN AIR DAMPER WILL OPEN TO MAINTAIN 55°F (ADJ).

B. WHEN BOTH SUPPLY & RETURN FANS ARE OPERATING THEIR ASSOCIATE PILOT LAMPS WILL BE ENERGIZED, INDICATING OPERATION AT THE TC PANEL.

C. IF CURRENT SENSOR DOES NOT INDICATE FAN OPERATION, AN ALARM SIGNAL WILL INDICATING FAN UNIT

FAILURE.

2. FACE AND BY-PASS DAMPERS AND TEMPERATURE CONTROL VALVE SHALL BE CONTROLLED TO MODULATE TO

MAINTAIN SUPPLY AIR TEMPERATURE SET-POINT OF 68F (ADJUSTABLE).

2.1. BELOW 35F TEMPERATURE CONTROL VALVE WILL BE IN NORMALLY OPEN POSITION. FACE AND BY-PASS

DAMPERS WILL BE MODULATED TO MAINTAIN SUPPLY AIR DISCHARGE TEMPERATURE SETTING.

2.2. ABOVE 35F THE FACE DAMPER WILL BE IN ITS NORMALLY OPEN POSITION. THE BY-PASS DAMPER WILL BE IN

ITS NORMALLY CLOSED POSITION. THE TEMPERATURE CONTROL VALVE WILL MODULATE TO MAINTAIN THE

DISCHARGE AIR TEMPERATURE SETPOINT.

3. TEMPERATURE CONTROL GRAPHICS WILL INDICATE TC VALVE POSITION AND FACE AND BY-PASS DAMPER

POSITION.

4. WHEN THE OUTSIDE AIR TEMPERATURE AND ENTHALPY IS SUITABLE, THE OUTSIDE AND RETURN AIR DAMPER

WILL MODULATE TO MAINTAIN A MIXED AIR TEMPERATURE OF 55 F (ADJ.).

5. WHEN THE OUTSIDE AIR TEMPERATURE AND ENTHALPY IS HIGHER THAN ECONOMIZER SETPOINTS, THE OUTSIDE AIR DAMPERS WILL MOVE TO A MINIMUM POSITION 30%OA (ADJ). THE RETURN AIR DAMPER WILL MOVE TO ITS

CORRESPONDING POSITION.

6. SAFETIES SHALL FUNCTION AS FOLLOWS:

A. FREEZE STAT (TSL) WILL STOP THE SUPPLY FAN AND CLOSE THE OUTSIDE & RELIEF AIR DAMPERS IF IT

SENSES A TEMPERATURE BELOW THE SETPOINT OF 38F (ADJ).

B. FREEZE STAT TRIP WILL INITIATE ALARM SIGNAL.

C. HIGH LIMIT (TSH) AIR SENSOR WILL STOP THE SUPPLY FAN AND CLOSE THE OUTSIDE AND RELIEF AIR

DAMPERS IF IT SENSES A TEMPERATURE ABOVE THE SETPOINT OF 125F (ADJ).

D. HIGH LIMIT AIR STAT TRIP WILL INITIATE ALARM SIGNAL.

E. ACTIVATION OF ANY SMOKE DETECTOR WILL INITIATE AN ALARM.

a. IF SMOKE IS DETECTED BY SMOKE DETECTOR (SD-4) OR IF ANY OTHER SMOKE/FIRE ALARM DEVICE IS

ACTIVATED WITHIN THE BUILDING THE UNIT WILL STOP AND ALL CONTROLLED DEVICES WILL GO TO THEIR NORMAL POSITIONS. THE STOP SIGNAL WILL BE FROM THE FIRE ALARM SYSTEM CONTROL PANEL. SMOKE DAMPERS SD-4 SHALL CLOSE. COORDINATION WITH EXISTING BUILDING FIRE ALARM

OPERATION IS REQUIRED.

F. PRESSURE DIFFERENTIAL SWITCH ACROSS THE AIR FILTER SHALL INDICATE ALARM WHEN SETTING REACHES

0.5" INWG (ADJ) INDICATING A DIRTY FILTER CONDITION.

6. DURING NIGHT SET BACK SCHEDULE, AHU-2 SUPPLY/RETURN FAN SHALL CYCLE THE UNIT ON/OFF TO MAINTAIN THE DESIRED SPACE NIGHT SETBACK TEMPERATURE. DURING NIGHT OPERATION THE OUTSIDE AIR AND RELIEF

AIR DAMPERS MOVES TO CLOSE AND RETURN AIR DAMPERS OPEN.

7. CIRCULATING PUMP (P-6) SHALL BE ENERGIZED WHEN TEMP OUTSIDE DROPS BELOW 55F (ADJ).

8. CURRENT SENSOR SHALL DETECT CIRCULATING PUMP (P-6) OPERATION. IF CURRENT SENSOR DOES NOT DETECT CURRENT, ALARM SIGNAL FOR PUMP FAILURE SHALL BE INDICATED ON AHU GRAPHIC. UPON PUMP FAILURE, FAN

WILL STOP, OUTSIDE AND RELIEF AIR DAMPERS WILL CLOSE.

AutoCAD SHX Text These prints are solely owned by MENDE ENGINEERING SOLUTIONS, LLC. The Drawings, Specifications and other documents prepared by MENDE ENGINEERING SOLUTIONS, LLC for this Project are instruments of MENDE ENGINEERING SOLUTIONS, LLC for use solely with respect to this Project and, unless otherwise provided, MENDE ENGINEERING SOLUTIONS, LLC shall be deemed the author of these documents and shall retain all common law, statutory and other reserved rights, including the copyright. MENDE ENGINEERING SOLUTIONS, LLC Drawings, Specifications or other documents shall not be used by the Owner or others on other projects, for additions to this Project or for completion of this Project by others, without the expressed written consent of MENDE ENGINEERING SOLUTIONS, LLC.

AutoCAD SHX Text DANGEROUS Architects, Pc

AutoCAD SHX Text 104 South Main Street Chelsea, Mi. 48118 734.475.3660 WWW.DANGEROUSARCHITECTS.COM zCopyright 2022, Dangerous Architects Pc.Copyright 2022, Dangerous Architects Pc.

4321 East Camden Road Osseo, MI 49266 Ph. (517) 254-4789 Fax (517) 254-4886 http://www.tac-associates.com

Project number

Date

Drawn by

Checked by

Approved by

Sheet No.

M-300-TC-3

NOT TO SCALE

JKM

JKM

MES

04-21-23 23523.1

AHU-3 CONTROLS

REPLACEMENT

BLDG 300 HVAC

FILE 472/22350.MNB

GU

S H

AR

RIS

ON

CO

RR

EC

TIO

NA

L F

AC

ILI

TY

AD

RI

AN

, M

IC

HI

G

AN

E

. B

EE

C H

ER

S

T.

ST

A

TE

O

F M

IC

H

IG

A

N

ENGINEERS, DESIGNERS,

PROBLEM SOLVERS

PROUDLY SERVING MICHIGAN

517-437-6998 www.MendeEngineeringSolutions.com

CONSULTANTS:

TAC ASSOCIATES, LLC

Consulting Engineers

SUPPLY

AHU-3

HEAT

COIL

N.C.C.

N.O.

HHWS

HHWR

P-7

L

OUTSIDE

AIR N.C.

FILTER

RETURN

AIR

EXHAUST

AIR

RETURN

RAF-3

N.C.

N.O.

SUPPLY AIR TO

VAV's, VVR's

N.C.

SD-1

N.C.

SD-2

DX

COOL

COIL

STAGE 1

COOL

STAGE 2

COOL

STAGE 3

COOL

STAGE 4

COOL

AIR COOLED CONDENSING UNIT

N.O.

FAIL

OPEN

N.O.

FAIL

OPEN

HHWS

HHWR

N.O.

VVR

VAV

GENERAL TC NEW WORK NOTES:

1. TEMPERATURE CONTROLS (TC) FOR AHU-3 / P-7, ACCU-1. REFER TO

SHEET TC-D3 AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.

2. REFER TO MECHANICAL SHEETS FOR DEVICE LOCATIONS AND

ADDITIONAL INFORMATION.

3. TC INTEGRATOR SHALL DETERMINE IF EXISTING DDC SYSTEM

REQUIRES UPGRADES FOR EXPANSION OF NEW DEVICES.

4. TC INTEGRATOR SHALL CLEAN AND RE-USE EXISTING CABINET FOR

INSTALLATION OF NEW DEVICES.

5. EXISTING CONDUIT TO BE RE-USED SHALL REMAIN.

6. COORDINATE WITH FIRE ALARM VENDOR AS REQUIRED. SEE

SEQUENCE OF OPERATION THIS SHEET.

SEQUENCE OF OPERATION

1. WITH THE EXISTING SUPPLY AND RETURN MOTOR STARTER IN THE "AUTO" MODE,

THE UNIT WILL BE ENABLED BY THE BUILDING MANAGEMENT SYSTEM (BMS). THE

UNIT WILL OPERATE ACCORDING TO AN OCCUPIED AND NIGHT SET BACK SCHEDULE.

OCCUPIED:

A. WHEN FANS ARE ENABLED, SMOKE DAMPERS SD-1 AND SD-2 WILL OPEN.

B. RETURN AIR, OUTDOOR AIR AND RELIEF DAMPERS WILL OPEN TO MAINTAIN

MIXED AIR TEMPERATURE OF 55°F (ADJ).

C. HEATING VALVE WILL MODULATE OPEN TO MAINTAIN DESIRED DISCHARGE AIR

TEMPERATURE (ADJ).

D. WHEN BOTH SUPPLY & RETURN FANS ARE OPERATING THEIR ASSOCIATE PILOT

LAMPS WILL BE ENERGIZED, INDICATING OPERATION AT THE TC PANEL AS WELL

AS "ON" IN THE BMS GRAPHIC SCREEN.

E. IF CURRENT SENSORS DO NOT INDICATE FAN OPERATION, AN ALARM SIGNAL

WILL INDICATING SUPPLY AND RETURN FAN FAILURE.

2. WHEN THE OUTSIDE AIR TEMPERATURE AND ENTHALPY IS SUITABLE, THE OUTSIDE

AND RETURN AIR DAMPER WILL MODULATE TO MAINTAIN A MIXED AIR

TEMPERATURE OF 55 F (ADJ.).

3. WHEN THE OUTSIDE AIR TEMPERATURE AND ENTHALPY IS HIGHER THAN

ECONOMIZER SETPOINTS, THE OUTSIDE AIR DAMPERS WILL MOVE TO A MINIMUM

POSITION 15%OA (ADJ), THE RETURN AIR DAMPER WILL TRACK ITS POSITION, AND

STAGE 1 MECHANICAL COOLING WILL BE ENABLED.

3.1. ON A CONTINUED CALL FOR COOLING, STAGES 2, 3 AND 4 WILL BE ENGAGED, TO

SATISFY THE ZONE OF THE MOST CRITICAL COOLING DEMAND (AS SENSED BY

THE ZONE SENSORS).

3.2. MANUFACTURER OF ACCU-1 SHALL PROVIDE ALL CONTROLS EQUIPMENT

STAGING ONCE A CALL FOR COOLING IS OBTAINED FROM THE SYSTEM.

MORNING WARM UP:

4. MORNING WARM UP SCHEDULE SHALL BE SET UP THRU THE BMS.

5. AHU TEMPERATURE CONTROL SHALL BE BASED ON RETURN AIR TEMPERATURE.

6. RAF-4 SHALL BE ENERGIZED, HEATING CONTROL VALVE SHALL MODULATE OPEN TO

MAINTAIN THE RETURN AIR TEMPERATURE SETPOINT.

7. AT THE END OF THE MORNING WARM UP CYCLE, CONTROL OF THE HEATING VALVE

SHALL BE BASED ON DISCHARGE TEMPERATURE AS NOTED IN OCCUPIED MODE.

VARIABLE AIR VOLUME BOXES:

8. VAV BOXES SHALL BE MODULATED TO MAINTAIN SPACE TEMPERATURE SETTING

(ADJ).

9. VVR (VAV WITH REHEAT) SHALL BE MODULATED TO MAINTAIN SPACE TEMPERATURE

SETPOINT (ADJ). WHEN THE BOXES ARE MODULATED TO MIN POSITION AND IF THE

SPACE TEMPERATURE CONTINUES TO DROP THE 2-WAY CONTROL VALVE SHALL BE

MODULATED OPEN TO MAINTAIN SPACE TEMPERATURE (ADJ).

10. A STATIC PRESSURE SENSOR SHALL CONTROL THE OPERATION OF THE SUPPLY AND

RETURN FAN INLET VANES.

10.1. SYSTEM STATIC PRESSURE WILL MODULATE THE SUPPLY FAN INLET VANE

DAMPER IN SEQUENCE WITH THE RETURN FAN INLET VANE DAMPER TO

MAINTAIN THE DESIRED STATIC PRESSURE IN THE SUPPLY DUCT. RETURN FAN

INLET VANE DAMPER WILL LAG BEHIND THE SUPPLY FAN INLET VANE DAMPER

BY 15% (ADJ) OF THE MAX SUPPLY FAN VOLUME. SUPPLY FAN DISCHARGE DUCT

STATIC PRESSURE HIGH LIMIT WILL SHALL SIGNAL ALARM WHEN SET POINT IS

REACHED AND MOVE SUPPLY FAN INLET VANE TO MINIMUM POSITION (ADJ).

11. EXHAUST FANS (EF-1 THRU EF-8) WILL BE INTERLOCKED WITH AHU-3 DURING

OCCUPIED MODE.

11.1. EXHAUST FANS SHALL BE DISABLED DURING NIGHT SET BACK AND MORNING

WARM UP.

12. CIRCULATING PUMP (P-7) SHALL BE ENERGIZED WHEN TEMP OUTSIDE DROPS BELOW

55F (ADJ).

13. CURRENT SENSOR SHALL DETECT CIRCULATING PUMP (P-7) OPERATION. IF CURRENT

SENSOR DOES NOT DETECT CURRENT, ALARM SIGNAL FOR PUMP FAILURE SHALL BE

INDICATED ON AHU GRAPHIC. UPON PUMP FAILURE, FAN WILL STOP, OUTSIDE AND

RELIEF AIR DAMPERS WILL CLOSE.

14. SAFETIES SHALL FUNCTION AS FOLLOWS:

A. FREEZE STAT (TSL) WILL STOP THE SUPPLY FAN AND CLOSE THE OUTSIDE &

RELIEF AIR DAMPERS IF IT SENSES A TEMPERATURE BELOW THE SETPOINT OF

38F (ADJ).

B. FREEZE STAT TRIP WILL INITIATE ALARM SIGNAL.

C. PRESSURE DIFFERENTIAL SWITCH ACROSS THE AIR FILTER SHALL INDICATE

ALARM WHEN SETTING REACHES 0.5" INWG (ADJ) INDICATING A DIRTY FILTER

CONDITION.

D. IF SMOKE IS DETECTED BY SMOKE DETECTOR (SD-1, SD-2) OR IF ANY OTHER

SMOKE DETECTOR OR PULL STATION IS ACTIVATED WITHIN THE AREA SERVED

BY AHU-3, THE SUPPLY FAN AND RETURN FAN WILL STOP AND ALL CONTROLLED

DEVICES WILL GO TO THEIR NORMAL POSITIONS. THE STOP SIGNAL WILL BE

FROM THE FIRE ALARM SYSTEM CONTROL PANEL. ALARM SIGNAL WILL BE SENT

WHEN UNITS ARE SHUT DOWN. COORDINATION WITH EXISTING BUILDING FIRE

ALARM OPERATION IS REQUIRED.

AutoCAD SHX Text These prints are solely owned by MENDE ENGINEERING SOLUTIONS, LLC. The Drawings, Specifications and other documents prepared by MENDE ENGINEERING SOLUTIONS, LLC for this Project are instruments of MENDE ENGINEERING SOLUTIONS, LLC for use solely with respect to this Project and, unless otherwise provided, MENDE ENGINEERING SOLUTIONS, LLC shall be deemed the author of these documents and shall retain all common law, statutory and other reserved rights, including the copyright. MENDE ENGINEERING SOLUTIONS, LLC Drawings, Specifications or other documents shall not be used by the Owner or others on other projects, for additions to this Project or for completion of this Project by others, without the expressed written consent of MENDE ENGINEERING SOLUTIONS, LLC.

AutoCAD SHX Text DANGEROUS Architects, Pc

AutoCAD SHX Text 104 South Main Street Chelsea, Mi. 48118 734.475.3660 WWW.DANGEROUSARCHITECTS.COM zCopyright 2022, Dangerous Architects Pc.Copyright 2022, Dangerous Architects Pc.

AutoCAD SHX Text 4321 East Camden Road Osseo, MI 49266 Ph. (517) 254-4789 Fax (517) 254-4886 http://www.tac-associates.com

M

Project number

Date

Drawn by

Checked by

Approved by

Sheet No.

M-300-TC-4

NOT TO SCALE

JKM

JKM

MES

04-21-23 23523.1

AHU-4 CONTROLS

REPLACEMENT

BLDG 300 HVAC

FILE 472/22350.MNB

GU

S H

AR

RIS

ON

CO

RR

EC

TIO

NA

L F

AC

ILI

TY

AD

RI

AN

, M

IC

HI

G

AN

E

. B

EE

C H

ER

S

T.

ST

A

TE

O

F M

IC

H

IG

A

N

ENGINEERS, DESIGNERS,

PROBLEM SOLVERS

PROUDLY SERVING MICHIGAN

517-437-6998 www.MendeEngineeringSolutions.com

CONSULTANTS:

TAC ASSOCIATES, LLC

Consulting Engineers

GENERAL TC NEW WORK NOTES:

1. TEMPERATURE CONTROLS (TC) FOR AHU-4 / P-8. REFER TO SHEET

TC-D4 AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.

2. REFER TO MECHANICAL SHEETS FOR DEVICE LOCATIONS AND

ADDITIONAL INFORMATION.

3. TC INTEGRATOR SHALL DETERMINE IF EXISTING DDC SYSTEM

REQUIRES UPGRADES FOR EXPANSION OF NEW DEVICES.

4. TC INTEGRATOR SHALL CLEAN AND RE-USE EXISTING CABINET FOR

INSTALLATION OF NEW DEVICES.

5. EXISTING CONDUIT TO BE RE-USED SHALL REMAIN.

6. COORDINATE WITH FIRE ALARM VENDOR AS REQUIRED. SEE

SEQUENCE OF OPERATION THIS SHEET.

SUPPLY

AHU-4

HEAT

COIL

N.C.C.

N.O.

HHWS

HHWR

P-8

L

OUTSIDE

AIR N.C.N.C.

FILTER

N.O.

SUPPLY

AIR

RETURN

AIR

EXHAUST

AIR

RETURN

RAF-4N.C.

N.O.

H

SEQUENCE OF OPERATION

1. WITH THE EXISTING SUPPLY AND RETURN MOTOR STARTER IN THE "AUTO" MODE, THE UNIT WILL BE ENABLED BY THE BUILDING MANAGEMENT SYSTEM (BMS). THE UNIT WILL OPERATE ACCORDING TO AN OCCUPIED AND NIGHT

SET BACK SCHEDULE.

A. OCCUPIED: RETURN AIR AND OUTDOOR AIR DAMPERS WILL OPEN WHEN AHU FANS ARE ENABLED. OUTSIDE

AIR DAMPER, RELIEF AIR AND RETURN AIR DAMPER WILL OPEN TO MAINTAIN 55°F (ADJ).

B. WHEN BOTH SUPPLY & RETURN FANS ARE OPERATING THEIR ASSOCIATE PILOT LAMPS WILL BE ENERGIZED, INDICATING OPERATION AT THE TC PANEL.

C. IF CURRENT SENSOR DOES NOT INDICATE FAN OPERATION, AN ALARM SIGNAL WILL INDICATING FAN UNIT

FAILURE.

2. FACE AND BY-PASS DAMPERS AND TEMPERATURE CONTROL VALVE SHALL BE CONTROLLED TO MODULATE TO

MAINTAIN SUPPLY AIR TEMPERATURE SET-POINT OF 68F (ADJUSTABLE).

2.1. BELOW 35F TEMPERATURE CONTROL VALVE WILL BE IN NORMALLY OPEN POSITION. FACE AND BY-PASS

DAMPERS WILL BE MODULATED TO MAINTAIN SUPPLY AIR DISCHARGE TEMPERATURE SETTING.

2.2. ABOVE 35F THE FACE DAMPER WILL BE IN ITS NORMALLY OPEN POSITION. THE BY-PASS DAMPER WILL BE IN

ITS NORMALLY CLOSED POSITION. THE TEMPERATURE CONTROL VALVE WILL MODULATE TO MAINTAIN THE

DISCHARGE AIR TEMPERATURE SETPOINT.

3. TEMPERATURE CONTROL GRAPHICS WILL INDICATE TC VALVE POSITION AND FACE AND BY-PASS DAMPER

POSITION.

4. WHEN THE OUTSIDE AIR TEMPERATURE AND ENTHALPY IS SUITABLE, THE OUTSIDE AND RETURN AIR DAMPER

WILL MODULATE TO MAINTAIN A MIXED AIR TEMPERATURE OF 55 F (ADJ.).

5. WHEN THE OUTSIDE AIR TEMPERATURE AND ENTHALPY IS HIGHER THAN ECONOMIZER SETPOINTS, THE OUTSIDE AIR DAMPERS WILL MOVE TO A MINIMUM POSITION 30%OA (ADJ). THE RETURN AIR DAMPER WILL MOVE TO ITS

CORRESPONDING POSITION.

6. SAFETIES SHALL FUNCTION AS FOLLOWS:

A. FREEZE STAT (TSL) WILL STOP THE SUPPLY FAN AND CLOSE THE OUTSIDE & RELIEF AIR DAMPERS IF IT

SENSES A TEMPERATURE BELOW THE SETPOINT OF 38F (ADJ).

B. FREEZE STAT TRIP WILL INITIATE ALARM SIGNAL.

C. HIGH LIMIT (TSH) AIR SENSOR WILL STOP THE SUPPLY FAN AND CLOSE THE OUTSIDE AND RELIEF AIR

DAMPERS IF IT SENSES A TEMPERATURE ABOVE THE SETPOINT OF 125F (ADJ).

D. HIGH LIMIT AIR STAT TRIP WILL INITIATE ALARM SIGNAL.

E. ACTIVATION OF ANY SMOKE DETECTOR WILL INITIATE AN ALARM.

a. IF SMOKE IS DETECTED BY SMOKE DETECTOR (SD-3) OR IF ANY OTHER SMOKE/FIRE ALARM DEVICE IS

ACTIVATED WITHIN THE BUILDING THE UNIT WILL STOP AND ALL CONTROLLED DEVICES WILL GO TO THEIR NORMAL POSITIONS. THE STOP SIGNAL WILL BE FROM THE FIRE ALARM SYSTEM CONTROL PANEL. SMOKE DAMPERS SD-3 SHALL CLOSE. COORDINATION WITH EXISTING BUILDING FIRE ALARM

OPERATION IS REQUIRED.

F. PRESSURE DIFFERENTIAL SWITCH ACROSS THE AIR FILTER SHALL INDICATE ALARM WHEN SETTING REACHES

0.5" INWG (ADJ) INDICATING A DIRTY FILTER CONDITION.

6. DURING NIGHT SET BACK SCHEDULE, AHU-4 SUPPLY/RETURN FAN SHALL CYCLE THE UNIT ON/OFF TO MAINTAIN THE DESIRED SPACE NIGHT SETBACK TEMPERATURE. DURING NIGHT OPERATION THE OUTSIDE AIR AND RELIEF

AIR DAMPERS MOVES TO CLOSE AND RETURN AIR DAMPERS OPEN.

7. CIRCULATING PUMP (P-8) SHALL BE ENERGIZED WHEN TEMP OUTSIDE DROPS BELOW 55F (ADJ).

8. CURRENT SENSOR SHALL DETECT CIRCULATING PUMP (P-8) OPERATION. IF CURRENT SENSOR DOES NOT DETECT CURRENT, ALARM SIGNAL FOR PUMP FAILURE SHALL BE INDICATED ON AHU GRAPHIC. UPON PUMP FAILURE, FAN

WILL STOP, OUTSIDE AND RELIEF AIR DAMPERS WILL CLOSE.

AutoCAD SHX Text These prints are solely owned by MENDE ENGINEERING SOLUTIONS, LLC. The Drawings, Specifications and other documents prepared by MENDE ENGINEERING SOLUTIONS, LLC for this Project are instruments of MENDE ENGINEERING SOLUTIONS, LLC for use solely with respect to this Project and, unless otherwise provided, MENDE ENGINEERING SOLUTIONS, LLC shall be deemed the author of these documents and shall retain all common law, statutory and other reserved rights, including the copyright. MENDE ENGINEERING SOLUTIONS, LLC Drawings, Specifications or other documents shall not be used by the Owner or others on other projects, for additions to this Project or for completion of this Project by others, without the expressed written consent of MENDE ENGINEERING SOLUTIONS, LLC.

AutoCAD SHX Text DANGEROUS Architects, Pc

AutoCAD SHX Text 104 South Main Street Chelsea, Mi. 48118 734.475.3660 WWW.DANGEROUSARCHITECTS.COM zCopyright 2022, Dangerous Architects Pc.Copyright 2022, Dangerous Architects Pc.

4321 East Camden Road Osseo, MI 49266 Ph. (517) 254-4789 Fax (517) 254-4886 http://www.tac-associates.com

Project number

Date

Drawn by

Checked by

Approved by

Sheet No.

M-300-TC-5

NOT TO SCALE

JKM

JKM

MES

04-21-23 23523.1

AHU-5 CONTROLS

REPLACEMENT

BLDG 300 HVAC

FILE 472/22350.MNB

GU

S H

AR

RIS

ON

CO

RR

EC

TIO

NA

L F

AC

ILI

TY

AD

RI

AN

, M

IC

HI

G

AN

E

. B

EE

C H

ER

S

T.

ST

A

TE

O

F M

IC

H

IG

A

N

ENGINEERS, DESIGNERS,

PROBLEM SOLVERS

PROUDLY SERVING MICHIGAN

517-437-6998 www.MendeEngineeringSolutions.com

CONSULTANTS:

TAC ASSOCIATES, LLC

Consulting Engineers

GENERAL TC NEW WORK NOTES:

1. TEMPERATURE CONTROLS (TC) FOR AHU-5 / P-9 AND EF-10. REFER

TO SHEET TC-D5 AND SPECIFICATIONS FOR ADDITIONAL

INFORMATION.

2. REFER TO MECHANICAL SHEETS FOR DEVICE LOCATIONS AND

ADDITIONAL INFORMATION.

3. TC INTEGRATOR SHALL DETERMINE IF EXISTING DDC SYSTEM

REQUIRES UPGRADES FOR EXPANSION OF NEW DEVICES.

4. TC INTEGRATOR SHALL CLEAN AND RE-USE EXISTING CABINET FOR

INSTALLATION OF NEW DEVICES.

5. EXISTING CONDUIT TO BE RE-USED SHALL REMAIN.

6. COORDINATE WITH FIRE ALARM VENDOR AS REQUIRED. SEE

SEQUENCE OF OPERATION THIS SHEET.

SUPPLY

AHU-5

HEAT

COIL

N.C.C.

N.O.

HHWS

HHWR

P-9

L

OUTSIDE

AIR N.C.N.C.

FILTER

N.O.

SUPPLY

AIR

RETURN

AIR

EXHAUST

AIR

RETURN

RAF-5N.C.

N.O.

H

BACKDRAFT

DAMPER

EXHAUST FAN EF-10

(KITCHEN HOOD)

EF-10

SEQUENCE OF OPERATION

1. UNIT IS ENABLED THRU THE BMS AND FAN IS STARTED AND STOP THRU EXISTING PUSH BUTTON

SWITCH FOR EF-10.

A. SUPPLY FAN ACTIVATION WILL OPEN OUTSIDE AIR DAMPER.

B. WHEN SUPPLY FAN IS OPERATING ITS ASSOCIATE PILOT LAMP WILL BE ENERGIZED,

INDICATING OPERATION AT THE TC PANEL.

C. IF CURRENT SENSOR DOES NOT INDICATE FAN OPERATION, AN ALARM SIGNAL WILL

INDICATING FAN UNIT FAILURE.

2. FACE AND BY-PASS DAMPERS AND TEMPERATURE CONTROL VALVE SHALL BE CONTROLLED TO

MODULATE TO MAINTAIN SUPPLY AIR TEMPERATURE SET-POINT OF 68F (ADJUSTABLE).

2.1. BELOW 35F TEMPERATURE CONTROL VALVE WILL BE IN NORMALLY OPEN POSITION. FACE

AND BY-PASS DAMPERS WILL BE MODULATED TO MAINTAIN SUPPLY AIR DISCHARGE

TEMPERATURE SETTING

2.2. ABOVE 35F THE FACE DAMPER WILL BE IN ITS NORMALLY OPEN POSITION. THE BY-PASS

DAMPER WILL BE IN ITS NORMALLY CLOSED POSITION. THE TEMPERATURE CONTROL

VALVE WILL MODULATE TO MAINTAIN THE MINIMUM DISCHARGE TEMPERATURE

SETPOINT.

2.3. TEMPERATURE CONTROL GRAPHICS WILL INDICATE TC VALVE POSITION AND FACE AND

BY-PASS DAMPER POSITION.

3. SAFETIES SHALL FUNCTION AS FOLLOWS:

A. FREEZE STAT (TSL) WILL STOP THE SUPPLY FAN AND CLOSE THE OUTSIDE AIR DAMPER IF

IT SENSES A TEMPERATURE BELOW THE SETPOINT OF 38F (ADJ).

B. FREEZE STAT TRIP WILL INITIATE ALARM SIGNAL.

C. ACTIVATION OF ANY SMOKE DETECTOR WILL INITIATE AN ALARM.

a. IF SMOKE IS DETECTED BY SMOKE DETECTOR (SD-5) OR IF ANY OTHER SMOKE/FIRE

ALARM DEVICE IS ACTIVATED WITHIN THE BUILDING THE UNIT WILL STOP AND

ALL CONTROLLED DEVICES WILL GO TO THEIR NORMAL POSITIONS. THE STOP

SIGNAL WILL BE FROM THE FIRE ALARM SYSTEM CONTROL PANEL. SMOKE

DAMPERS SD-5, SHALL CLOSE. COORDINATION WITH EXISTING BUILDING FIRE

ALARM OPERATION IS REQUIRED.

D. PRESSURE DIFFERENTIAL SWITCH ACROSS THE AIR FILTER SHALL INDICATE ALARM

WHEN SETTING REACHES 0.5" INWG (ADJ) INDICATING A DIRTY FILTER CONDITION.

4. CIRCULATING PUMP (P-9) SHALL BE ENERGIZED WHEN TEMP OUTSIDE DROPS BELOW 55F (ADJ).

5. CURRENT SENSOR SHALL DETECT CIRCULATING PUMP (P-9) OPERATION. IF CURRENT SENSOR

DOES NOT DETECT CURRENT, ALARM SIGNAL FOR PUMP FAILURE SHALL BE INDICATED ON AHU

GRAPHIC. UPON PUMP FAILURE, FAN WILL STOP, OUTSIDE AIR DAMPERS WILL CLOSE.

AutoCAD SHX Text These prints are solely owned by MENDE ENGINEERING SOLUTIONS, LLC. The Drawings, Specifications and other documents prepared by MENDE ENGINEERING SOLUTIONS, LLC for this Project are instruments of MENDE ENGINEERING SOLUTIONS, LLC for use solely with respect to this Project and, unless otherwise provided, MENDE ENGINEERING SOLUTIONS, LLC shall be deemed the author of these documents and shall retain all common law, statutory and other reserved rights, including the copyright. MENDE ENGINEERING SOLUTIONS, LLC Drawings, Specifications or other documents shall not be used by the Owner or others on other projects, for additions to this Project or for completion of this Project by others, without the expressed written consent of MENDE ENGINEERING SOLUTIONS, LLC.

AutoCAD SHX Text DANGEROUS Architects, Pc

AutoCAD SHX Text 104 South Main Street Chelsea, Mi. 48118 734.475.3660 WWW.DANGEROUSARCHITECTS.COM zCopyright 2022, Dangerous Architects Pc.Copyright 2022, Dangerous Architects Pc.

4321 East Camden Road Osseo, MI 49266 Ph. (517) 254-4789 Fax (517) 254-4886 http://www.tac-associates.com

Project number

Date

Drawn by

Checked by

Approved by

Sheet No.

M-300-TC-6

NOT TO SCALE

JKM

JKM

MES

04-21-23 23523.1

HHWS/R CONTROLS

REPLACEMENT

BLDG 300 HVAC

FILE 472/22350.MNB

GU

S H

AR

RIS

ON

CO

RR

EC

TIO

NA

L F

AC

ILI

TY

AD

RI

AN

, M

IC

HI

G

AN

E

. B

EE

C H

ER

S

T.

ST

A

TE

O

F M

IC

H

IG

A

N

ENGINEERS, DESIGNERS,

PROBLEM SOLVERS

PROUDLY SERVING MICHIGAN

517-437-6998 www.MendeEngineeringSolutions.com

CONSULTANTS:

TAC ASSOCIATES, LLC

Consulting Engineers

GENERAL TC NEW WORK NOTES:

1. TEMPERATURE CONTROLS (TC) FOR PERIMETER RADIATION PUMPS,

RADIATION PUMPS, DOMESTIC HOT WATER PUMPS.

2. REFER TO AHU TC SHEETS FOR AHU PUMP OPERATION.

3. TC INTEGRATOR SHALL DETERMINE IF EXISTING DDC SYSTEM

REQUIRES UPGRADES FOR EXPANSION OF NEW DEVICES.

4. TC INTEGRATOR SHALL CLEAN AND RE-USE EXISTING CABINET FOR

INSTALLATION OF NEW DEVICES.

5. DOMESTIC HOT WATER PUMPS ARE EXISTING TO REMAIN. NEW

CURRENT SENSOR SWITCH SHALL BE INSTALLED FOR MONITORING.

DWH-2DWH-1

P-3

P-4

DHWR

DHWR

DHWS

HHWS / R TO AHU

COILS & VVR

REHEAT COILS

HHWSHHWR

HHWS

FROM B200

HHWR TO

B200

P-1

P-2

SEQUENCE OF OPERATION

A. HOT WATER RADIATION PUMPS P-1 AND P-2 WILL BE ENABLED BY THE

BMS TO OPERATE WHEN OUTDOOR AIR TEMPERATURE IS 55° (ADJ).

SUPPLY WATER TEMPERATURE IS PROVIDED BY BUILDING 200

ACCORDING TO BOILER REHEAT SCHEDULE.

B. P-1 SHALL OPERATE IN LEAD MODE AND P-2 SHALL BE IN STAND-BY

MODE. P-1 AND P-2 SHALL OPERATE IN LEAD-LAG CYCLES, EVERY 30

DAYS (ADJ).

1. P-1 AND P-2 SHALL ALLOW FOR VFD SETPOINTS TO BE

MONITORED AND CHANGED. CURRENT SENSOR SHALL INDICATE

OPERATION. UPON LOSS OF OPERATION, PUMP ALARM WILL

INDICATE, AND LAG PUMP SHALL BE INITIATED.

C. DOMESTIC HOT WATER PUMPS P-5 AND P-6 ARE EXISTING TO REMAIN.

A CURRENTS SENSOR SHALL BE INSTALLED TO MONITOR UMPM

OPERATION. LOSS OF CURRENT SHALL INDICATE PUMP FAILURE

ALARM.

HHWS / R TO

PERIMETER HEAT

AND CABINET

UNIT HEATERS

AutoCAD SHX Text These prints are solely owned by MENDE ENGINEERING SOLUTIONS, LLC. The Drawings, Specifications and other documents prepared by MENDE ENGINEERING SOLUTIONS, LLC for this Project are instruments of MENDE ENGINEERING SOLUTIONS, LLC for use solely with respect to this Project and, unless otherwise provided, MENDE ENGINEERING SOLUTIONS, LLC shall be deemed the author of these documents and shall retain all common law, statutory and other reserved rights, including the copyright. MENDE ENGINEERING SOLUTIONS, LLC Drawings, Specifications or other documents shall not be used by the Owner or others on other projects, for additions to this Project or for completion of this Project by others, without the expressed written consent of MENDE ENGINEERING SOLUTIONS, LLC.

AutoCAD SHX Text DANGEROUS Architects, Pc

AutoCAD SHX Text 104 South Main Street Chelsea, Mi. 48118 734.475.3660 WWW.DANGEROUSARCHITECTS.COM zCopyright 2022, Dangerous Architects Pc.Copyright 2022, Dangerous Architects Pc.

4321 East Camden Road Osseo, MI 49266 Ph. (517) 254-4789 Fax (517) 254-4886 http://www.tac-associates.com

Project number

Date

Drawn by

Checked by

Approved by

Sheet No.

M-300-TC-7

NOT TO SCALE

JKM

JKM

MES

04-21-23 23523.1

FAN & MISC CONTROLS

REPLACEMENT

BLDG 300 HVAC

FILE 472/22350.MNB

GU

S H

AR

RIS

ON

CO

RR

EC

TIO

NA

L F

AC

ILI

TY

AD

RI

AN

, M

IC

HI

G

AN

E

. B

EE

C H

ER

S

T.

ST

A

TE

O

F M

IC

H

IG

A

N

ENGINEERS, DESIGNERS,

PROBLEM SOLVERS

PROUDLY SERVING MICHIGAN

517-437-6998 www.MendeEngineeringSolutions.com

CONSULTANTS:

TAC ASSOCIATES, LLC

Consulting Engineers

GENERAL TC NEW WORK NOTES:

1. TEMPERATURE CONTROLS (TC) FOR

VENTILATION FANS AND HOODS AND TERMINAL

HEATING UNITS.

2. TC INTEGRATOR SHALL DETERMINE IF EXISTING

DDC SYSTEM REQUIRES UPGRADES FOR

EXPANSION OF NEW DEVICES.

3. EXISTING CONDUIT TO BE RE-USED SHALL

REMAIN.

4. ANY EXISTING CONDUIT WHICH WILL NOT TO BE

RE-USED, SHALL BE REMOVED.

FILTER

OUTSIDE

AIR N.C. SF-2 SUPPLY

AIR

FILTER

OUTSIDE

AIR N.C. SF-1 SUPPLY

AIR

N.C.

EXHAUST

AIR

ELECTRICAL ROOM

VENTILATION CONTROL (SF-2)

SEQUENCE OF OPERATION

A. SF-1 SHALL BE ENABLED THRU BMS WITH FAN

STARTER IN THE "AUTO" MODE. SPACE

THERMOSTAT SHALL CYCLE FAN ON AT 80°F (ADJ).

DAMPER MOTOR IN EXHAUST HOOD EH-1 SHALL

BE INTERLOCKED WITH SF-1.

1. CURRENT SENSOR IN SF-1 SHALL MONITOR FAN

OPERATION. ALARM SIGNAL SHALL INDICATE

WHEN FAN FAILS TO START ON TSTAT

COMMAND.

B. SF-2 SHALL BE ENABLED THRU BMS WITH FAN

STARTER IN THE "AUTO" MODE. SPACE

THERMOSTAT SHALL CYCLE FAN ON AT 80°F (ADJ).

DAMPER MOTOR IN EXHAUST HOOD EH-2 SHALL

BE INTERLOCKED WITH SF-2.

1. CURRENT SENSOR IN SF-2 SHALL MONITOR FAN

OPERATION. ALARM SIGNAL SHALL INDICATE

WHEN FAN FAILS TO START ON TSTAT

COMMAND.

A. SPACE THERMOSTAT SHALL CYCLE CABINET UNIT

HEATER FAN ON AND OFF TO MAINTAIN SPACE

TEMPERATURE OF 65°F (ADJ) . CURRENT SENSOR

SHALL INDICATE FAN STATUS. ALARM SIGNAL

WILL BE INITIATED IF CURRENT IS NOT

DETECTED. HEATING HOT WATER FLOW THRU

THE CUH WILL BE CONTINUOUS.

B. SPACE THERMOSTAT SHALL CYCLE UNIT HEATER

FAN ON AND OFF TO MAINTAIN SPACE

TEMPERATURE OF 65°F (ADJ) . CURRENT SENSOR

SHALL INDICATE FAN STATUS. ALARM SIGNAL

WILL BE INITIATED IF CURRENT IS NOT

DETECTED. HEATING HOT WATER FLOW THRU

THE UH WILL BE CONTINUOUS.

C. 2-WAY TEMPERATURE CONTROL VALVE ON FIN

TUBE RADIATION SHALL BE MODULATED TO

MAINTAIN SPACE TEMPERATURE OF 68°F (ADJ).

VALVE POSITION SHALL BE MONITORED ON THE

BMS. ALARM SIGNAL WILL BE INITIATED ON A

CONTINUED CALL FOR HEAT WITH THE VALVE

CLOSED. ON LOSS OF POWER, VALVE SHALL

RETURN TO NORMALLY OPEN.

EXHAUST HOOD

EH-2

N.C.

EXHAUST

AIR

EXHAUST HOOD

EH-1

MECHANICAL ROOM

VENTILATION CONTROL (SF-1)

HHWS

HHWR

HHWS

HHWR

CABINET HEATER CONTROL UNIT HEATER CONTROL

UH-1, 2, 3 & 4

FIN TUBE RADIATION CONTROL

NON INMATE AREAS

HHWS

HHWR

AutoCAD SHX Text These prints are solely owned by MENDE ENGINEERING SOLUTIONS, LLC. The Drawings, Specifications and other documents prepared by MENDE ENGINEERING SOLUTIONS, LLC for this Project are instruments of MENDE ENGINEERING SOLUTIONS, LLC for use solely with respect to this Project and, unless otherwise provided, MENDE ENGINEERING SOLUTIONS, LLC shall be deemed the author of these documents and shall retain all common law, statutory and other reserved rights, including the copyright. MENDE ENGINEERING SOLUTIONS, LLC Drawings, Specifications or other documents shall not be used by the Owner or others on other projects, for additions to this Project or for completion of this Project by others, without the expressed written consent of MENDE ENGINEERING SOLUTIONS, LLC.

AutoCAD SHX Text DANGEROUS Architects, Pc

AutoCAD SHX Text 104 South Main Street Chelsea, Mi. 48118 734.475.3660 WWW.DANGEROUSARCHITECTS.COM zCopyright 2022, Dangerous Architects Pc.Copyright 2022, Dangerous Architects Pc.

AutoCAD SHX Text 4321 East Camden Road Osseo, MI 49266 Ph. (517) 254-4789 Fax (517) 254-4886 http://www.tac-associates.com

M

Project number

Date

Drawn by

Checked by

Approved by

Sheet No.

CONSULTANTS:

23523.1

AS NOTED

TGC

TGC

CAD

10-12-23

FILE 472/22350.MNB

BLDG 200 BOILER &

BLDG 300 HVAC

REPLACEMENT

S T

A T

E

O

F

M

I C

H I G

A N

G U

S

H

A R

R I S

O N

C

R

R E

C T

I O

N

F A

C I L

I T

Y

E

B

E E

C H

R

S

T

A D

R I A

N

M

I C

H I G

A

TAC ASSOCIATES, LLC

4321 East Camden Road Osseo, MI 49266

Ph. (517) 254-4789 * Fax (517) 254-4886 http://www.tac-associates.com

TAC Project No. 23-016

Consulting Engineers

ENGINEERS, DESIGNERS,

PROBLEM SOLVERS

PROUDLY SERVING MICHIGAN

517-437-6998 www.MendeEngineeringSolutions.com

SEAL:

THOMAS

GERARD

CROW

License No.

6201055658

ENGINEER

ELECTRICAL DRAWING INDEX, SYMBOL LIST AND GENERAL ELECTRICAL NOTESE001

SHEET NUMBER SHEET TITLE

ELECTRICAL DRAWING INDEX

AS WALL MOUNTED OCCUPANCY SENSOR. REFER TO SCHEDULE ON LIGHTING DRAWINGS

3S THREE WAY SWITCH

EM

N.L.

EXISTING ELECTRICAL DEVICE OR FIXTURE TO REMAIN

ABOVE FINISH FLOOR

WEATHER PROOF

GROUND FAULT INTERRUPTERG.F.I.

W.P.

A.F.F.

(E)

DEVICE OR LIGHTING FIXTURE SERVED FROM EMERGENCY POWER

NIGHT LIGHT

EM

ELECTRICAL SYMBOL LIST

RECESSED ROUND LED OR FLUORESCENT FIXTURE

EXIT LIGHT DOUBLE FACE (SHADING INDICATES FACE OF FIXTURE)

SPECIAL PURPOSE OUTLET - TYPE AND SIZE AS INDICATED ON PLAN

WALL MOUNTED COMBINATION TELEPHONE/DATA OUTLET, MOUNTED AT 54" A.F.F.

DUPLEX RECEPTACLE / DUPLEX RECEPTACLE SERVED FROM EMERG. POWER

DOUBLE DUPLEX RECEPTACLE (SHADING INDICATES SERVED FROM EMERG. POWER)

PANEL BOARD

JUNCTION BOX

DUPLEX RECEPTACLE MOUNTED AT 6" ABOVE COUNTER TOP

J J

W

EXIT LIGHT, SINGLE FACE

NIGHT LIGHT / EMERGENCY FLUORESCENT FIXTURE

NIGHT LIGHT OR EMERGENCY LIGHT

WALL MOUNTED LIGHT FIXTURE

SINGLE POLE SWITCH

FOUR WAY SWITCH

2' X 4' FLUORESCENT FIXTURE

1' X 4' FLUORESCENT FIXTURE

2' X 2' FLUORESCENT FIXTURE

SYMBOL DESCRIPTION

S 4

N.L.

15 CANDELA SYNCHRONIZED FIRE ALARM SPEAKER/STROBE, WALL MOUNTED

15 CANDELA SYNCHRONIZED FIRE ALARM STROBE, WALL MOUNTED

SYNCHRONIZED FIRE ALARM STROBE, WALL MOUNTED (XX=CANDELA RATING, i.e. 30)

SYNCHRONIZED FIRE ALARM SPEAKER/STROBE, WALL MOUNTED (XX=CANDELA RATING, i.e. 30)XX

XX

SITE LIGHTING FIXTURE - BUILDING MOUNTED. SEE FIXTURE SCHEDULE

SITE LIGHTING FIXTURE - POLE MOUNTED (DOUBLE HEAD INDICATED)

F

R DUCT MOUNTED SMOKE DETECTOR (R = MOUNTED ON COMMON RETURN AIR DUCT)

CEILING MOUNTED FIRE ALARM SMOKE DETECTOR

FIRE ALARM SYSTEM MANUAL PULL STATION

TELEPHONE ONLY OUTLET

NEW LOCATION OF RELOCATED ELECTRICAL DEVICE OR FIXTURE(R)

EM

EMERGENCY FLUORESCENT FIXTURE

EM

EM

COMBINATION TELEPHONE/DATA OUTLET

WALL MOUNTED TELEPHONE ONLY OUTLET, MOUNTED AT 54" A.F.F.

W

FIRE ALARM SYSTEM CONTROL MODULE

B200 MECHANICAL ROOM FLOOR PLAN - ELECTRICAL DEMOLITIONED100.1

DISCONNECT SWITCH

MANUAL MOTOR STARTER WITH OVERLOADS (P= WITH PILOT LIGHT)

SINGLE PHASE MOTOR

P

THREE PHASE MOTOR

CONTROL PANEL

COMBINATION MAGNETIC MOTOR STARTER WITH OVERLOADS

1. EXTENT OF DEMOLITION IS NOT INTENDED TO BE SHOWN IN FULL ON THESE DRAWINGS. FINAL DESIGNED CONDITIONS ARE SHOWN. EACH TRADE/CONTRACTOR IS RESPONSIBLE FOR REMOVAL AS REQUIRED TO ACHIEVE FINAL DESIGN CONDITIONS. REFERENCES TO EXISTING AS IDENTIFIED ARE TO CLARIFY SCOPE OF

NEW CONSTRUCTION.

2. ALL WORK CONDITIONS ARE TO BE FIELD VERIFIED AND DETAILS ADJUSTED AS REQUIRED TO MAINTAIN FIRE RESISTIVE RATINGS. INTEGRITY OF INSTALLED SYSTEMS (EXISTING AND NEW) AND THE MATCHING OF

WORK WITH EXISTING CONDITIONS AND FINISHES.

3. REMOVAL WORK SHALL BE EXECUTED WITH DUE CARE, INCLUDING PROTECTION OF EXISTING MATERIALS/SYSTEMS TO REMAIN SHORING, BRACING, ETC. EACH TRADE/SUBCONTRACTORS WILL BE

RESPONSIBLE FOR ANY DAMAGE THEY CAUSE TO OTHER'S WORK.

4. THE FULL EXTENT OF THE WORK FOR EACH TRADE IS IDENTIFIED THROUGHOUT ALL THE DRAWINGS. DO NOT ASSUME OR OMIT INDIVIDUAL TRADE WORK NOT SHOWN IN THE INDIVIDUAL TRADE DRAWINGS.

FAILURE TO REVIEW ALL DRAWINGS FOR AN INDIVIDUAL TRADE’S COMPLETE SCOPE OF WORK WILL RESULT

IN DENIAL FOR ANY CHANGE ORDER REQUESTS FOR MISSED ITEMS DURING BIDDING.

5. SUBCONTRACTORS AND ALL TRADES MUST EXAMINE AREAS, DIMENSIONS CONDITIONS AND SUBSTRATES AFFECTING THE WORK AND THE CONDITIONS UNDER WHICH THE WORK IS TO BE INSTALLED, APPLIED AND COMPLETED. NOTIFY THE ARCHITECT IN WRITING OF UNSATISFACTORY CONDITIONS AND OTHER

CONDITIONS DETRIMENTAL TO THE PROPER AND TIMELY COMPLETION OF THE WORK.

A. DO NOT PROCEED WITH THE WORK UNTIL THE UNSATISFACTORY CONDITIONS HAVE BEEN

CORRECTED IN THE MANNER ACCEPTABLE TO THE CONTRACTOR OR TRADE PERFORMING THE

WORK. PROCEED WITH INSTALLATION ONLY AFTER UNSAFE OR UNSATISFACTORY CONDITIONS

HAVE BEEN CORRECTED.

B. BEGINNING WORK MEANS ACCEPTANCE OF THE CONDITIONS.

C. NO CHANGE ORDERS FOR ADDITIONAL WORK WILL BE ACCEPTED FOR CONDITIONS NOT

IDENTIFIED DURING THE EXAMINATION PERIOD PRIOR TO THE COMMENCING OF WORK.

6. CONTRACTOR(S) WARRANTS THEY HAVE EXAMINED THOROUGHLY ALL DRAWINGS AND SPECIFICATIONS DIRECTLY AND INDIRECTLY RELATED TO THEIR WORK. BY BEGINNING THE WORK, CONTRACTOR CERTIFIES THAT ALL NECESSARY ITEMS REQUIRED TO PERFORM HIS WORK HAVE BEEN IDENTIFIED AND DOCUMENTED

IN THE DRAWINGS AND/OR SPECIFICATIONS.

A. NOTIFY THE ARCHITECT IN WRITING OF ANY DISCREPANCIES, MISSING INFORMATION OR ANY

UNCLEAR ITEMS WHICH WILL AFFECT THE WORK TO BE PERFORMED. DO NOT PROCEED WITH

THE WORK UNTIL THE DISCREPANCIES, MISSING INFORMATION OR ANY UNCLEAR ITEMS HAVE

BEEN CLARIFIED OR CORRECTED TO THE CONTRACTOR OR TRADE PERFORMING THE WORK.

B. BEGINNING THE WORK INDICATES FULL ACCEPTANCE AND CORRECTNESS OF THE

INFORMATION PROVIDED.

C. NO CHANGE ORDERS FOR ADDITIONAL WORK WILL BE ACCEPTED FOR ANY DISCREPANCIES,

MISSING INFORMATION OR UNCLEAR ITEMS OR INFORMATION NOT IDENTIFIED DURING THE

EXAMINATION PERIOD PRIOR TO THE COMMENCING OF WORK.

7. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL NECESSARY FIRESTOPPING AROUND ALL PENETRATIONS OF FIRE RATED WALLS, CEILINGS AND FLOORS. REFER TO ARCHITECTURAL

AND ELECTRICAL SPECIFICATIONS FOR ADDITIONAL INFORMATION REGARDING THE SPECIFIC

FIRESTOPPING REQUIREMENTS AND PRODUCT SPECIFICATIONS.

8. ALL ANCHORS FOR ELECTRICAL SYSTEMS SHALL BE STEEL. REFER TO SPECIFICATIONS FOR SPECIFIC

APPROVED PRODUCTS. UNDER NO CIRCUMSTANCES SHALL PLASTIC ANCHORS BE USED.

ELECTRICAL GENERAL NOTES

E001

SYMBOL LIST, DRAWING INDEX, AND

GENERAL ELECTRICAL NOTES

E200.1 B200 ELECTRICAL SCHEDULES AND MISCELLANEOUS WIRING DIAGRAMS

B200 MECHANICAL ROOM FLOOR PLAN - ELECTRICAL NEW WORKE100.1

TAMPER-RESISTANT DUPLEX RECEPTACLE, TYPE AS INDICATED (i.e. WP, GFI, ETC.)

FIXTURE TYPE "OA" MOUNTING DETAIL (SECTION)

NO SCALE

ARCHITECTURAL SECTIONS FOR

EXTERIOR WALL. REFER TO

ADDITIONAL INFORMATION.

COVER

LOCKNUT

REQUIRED.

BETWEEN STUDS AS

STEEL FOR BOX SUPPORT

PROVIDE MISCELLANEOUS

CONDUIT TO NEXT FIXTURE OR HOMERUN.

FIXTURE TYPE "OA"

BACKPLATE AND ANCHORS.

(TYPICAL)

TO WALL.

ANCHORED DIRECTLY

BUSH BOTH ENDS.

SHALL BE RIGID STEEL AND

THRU THE WALL CONDUIT

JUNCTION BOX MOUNTED INSIDE BUILDING,

ABOVE ACCESSIBLE CEILING SPACE OR FLUSH

IN EXTERIOR WALL CONSTRUCTION. WHERE

MOUNTED FLUSH IN WALL CONSTRUCTION,

PROVIDE BLANK COVERPLATE TO MATCH

SURROUND WALL SURFACE.

NOTE: FIXTURE SHAPE CONVEYED IN THE ABOVE DETAIL IS INTENDED TO REPRESENT THE GENERAL SHAPE OF THE LIGHT FIXTURE; HOWEVER THE DETAIL IS NOT INTENDED TO BE AN EXACT GRAPHICAL REPRESENTATION OF THE SPECIFIED FIXTURE. REFER TO THE LIGHTING FIXTURE SCHEDULE AND ASSOCIATED CUT SHEET FOR AN EXACT

DESCRIPTION AND REPRESENTATION OF THE SPECIFIED FIXTURE.

TYPE DESCRIPTION

“OA” LED FULL CUT-OFF TYPE WALL MOUNTED LUMINAIRE. HIGH OUTPUT LED LIGHT ENGINE VISUAL COMFORT FORWARD THROW DISTRIBUTION, AND PROVIDING A TOTAL DELIVERED LUMEN OUTPUT OF 2,023 LUMENS AT A COLOR TEMPERATURE OF 4,000 DEGREE K AND A MINIMUM OF 80 CRI, RATED FOR A MINUMUM OF 100,000 HOURS OF CONTINUOUS OPERATION FROM MINUS 30 DEGREE C TO PLUS 40 DEGREE C. FIXTURE TO BE DLC COMPLIANT. FIXTURE TO HAVE A B.U.G.

RATING OF B1-U0-G0. ALUMINUM HOUSING. 11.5” WIDE X 9” HIGH X 7” DEEP. BRONZE FINISH. TOTAL FIXTURE WATTAGE TO BE 15 WATTS. FIXTURE TO BE UL LISTED FOR WET LOCATION USE. FIXTURE TO INCLUDE INTEGRAL POWER SUPPLY (DRIVER), UL LISTED. FIXTURE TO INCLUDE STANDALONE CONTROLS CONSISTING OF BI-LEVEL MOTION SENSOR CONTROL (100%/35%) AND INTEGRAL PHOTOCELL FOR DUSK TO DAWN OPERATION. FIXTURE SHALL OPERATE FROM DUSK TO DAWN BASED ON THE PHOTOCELL CONTROL. WHEN NO MOTION IS DETECTED, THE FIXTURE SHALL DIM TO 35% LIGHT OUTPUT;

WHEN MOTION IS DETECTED THE FIXTURE SHALL GO TO 100% FULL LIGHT OUTPUT. UNIVERSAL 120-277 VOLT OPERATION.

5-YEAR WARRANTY. LITHONIA “WDGE2 LED” WDGE2 LED-P2W-40K-80CRI-VF-MVOLT-PIR1FC3V-DDBXD, WITH EXACT FINISH TO BE SELECTED BY ARCHITECT PRIOR TO ORDERING OF FIXTURE, OR EQUAL BY MCGRAW-EDISON OR BEACON LIGHTING.

LIGHTING FIXTURE SCHEDULE

B300 MECHANICAL ROOM FLOOR PLAN - ELECTRICAL DEMOLITIONED100.2

E200.2 B300 ELECTRICAL SCHEDULES AND MISCELLANEOUS WIRING DIAGRAMS

B300 MECHANICAL ROOM FLOOR PLAN - ELECTRICAL NEW WORKE100.2

WP

GFI

No. Description Date

Scale

Project number

Date

Drawn by

Checked by

Approved by

Sheet No.

CONSULTANTS:

23523.1

AS NOTED

TGC

TGC

CAD

10-12-23

FILE 472/22350.MNB

BLDG 200 BOILER

REPLACEMENT

S T

A T

E

O

F

M

I C

H I G

A N

G U

S

H

A R

R I S

R

R E

C T

I O

N

F A

C I L

I T

Y

B

E E

C H

A D

R I A

N

M

I C

H I G

TAC ASSOCIATES, LLC

4321 East Camden Road Osseo, MI 49266

Ph. (517) 254-4789 * Fax (517) 254-4886 http://www.tac-associates.com

TAC Project No. 23-016

Consulting Engineers

ENGINEERS, DESIGNERS,

PROBLEM SOLVERS

PROUDLY SERVING MICHIGAN

517-437-6998 www.MendeEngineeringSolutions.com

SEAL:

THOMAS

GERARD

CROW

License No.

6201055658

ENGINEER

SCALE:

NORTH

B-200 MECHANICAL ROOM FLOOR PLAN - ELECTRICAL DEMOLITION

1/4" = 1'-0"

CONTRACTORS PRE-BID NOTIFICATION:

ALL EXISTING ITEMS INDICATED IN THE CONTRACT DRAWINGS HAVE BEEN TAKEN FROM THE

OWNER'S LIMITED RECORD DRAWINGS AND SUBSTANTIAL FIELD OBSERVATIONS AND VERIFICATION.

THIS CONTRACTOR AND ALL RELATED SUB-CONTRACTORS SHALL VISIT THE SITE AND COMPLETELY

UNDERSTAND THE CONDITIONS UNDER WHICH THE WORK MUST BE PERFORMED. IF A DEPARTURE

FROM THE DESIGN INTENT OF THE DOCUMENTS IS REQUIRED DUE TO THE ACTUAL FIELD

CONDITIONS OBSERVED BY THE CONTRACTOR, THE CONTRACTOR SHALL NOTIFY THE ARCHITECT IN WRITING FOR RESOLUTION PRIOR TO SUBMITTING FINAL BID OR ENTERING INTO A CONTRACT FOR CONSTRUCTION. FAILURE TO PROVIDE THE ARCHITECT WITH NOTIFICATION SHALL RESULT IN THE

CONTRACTOR BEING HELD RESPONSIBLE TO COMPLETE ALL WORK TO MEET THE DESIGN INTENT

WITH NO ADDITIONAL COST BEING INCURRED BY THE OWNER.

1 ELECTRICAL CONTRACTOR SHALL DISCONNECT AND REMOVE EXISTING BRANCH CIRCUIT

CONNECTION TO EXISTING MECHANICAL EQUIPMENT INDICATED TO BE REPLACED BY

MECHANICAL TRADES. REVISE EXISTING JUNCTION BOX CONNECTION AT EQUIPMENT TO BE

REPLACED WITH NEW AS REQUIRED TO FACILITATE SERVING NEW EQUIPMENT TO BE INSTALLED

AT THIS LOCATION WITH THE EXISTING BRANCH CIRCUIT. REFER TO GENERAL NOTE #5 FOR

CIRCUIT TRACING REQUIRED TO BE PERFORMED BY THE ELECTRICAL CONTRACTOR PRIOR TO

START OF CONSTRUCTION TO IDENTIFY THE EXISTING BRANCH CIRCUIT SERVING THE

EQUIPMENT TO BE REPLACED. BRANCH CIRCUIT IDENTIFIED BY CIRCUIT TRACING SHALL BE

REFLECTED ON THE AS-BUILT RECORD DRAWINGS. DISCONNECT AND REMOVE EXISTING

DISCONNECT SWITCH AND/OR MOTOR STARTER SERVING EQUIPMENT AND SALVAGE FOR

OWNER'S USE IF THE SWITCH AND/OR STARTER IS STILL IN GOOD CONDITION. IF SWITCH

AND/OR MOTOR STARTER IS IN POOR CONDITION, DISPOSE OF SWITCH AND/OR MOTOR

STARTER WITH OTHER MATERIALS IN A LEGAL MANNER. MATERIALS THAT ARE CAPABLE OF

BEING RECYCLED SHALL BE DISPOSED OF AT A LOCAL RECYCLING CENTER. REFER TO THE NEW

WORK POWER AND SYSTEMS FLOOR PLANS FOR ADDITIONAL INFORMATION.

ELECTRICAL CONTRACTOR SHALL DISCONNECT AND REMOVE EXISTING BRANCH CIRCUIT

CONDUIT AND WIRING SERVING MECHANICAL EQUIPMENT INDICATED COMPLETE TO

SOURCE. EXISTING CONDUIT MAY REMAIN AND BE RECONFIGURED TO SUPPORT SERVING THE

NEW EQUIPMENT TO BE INSTALLED IN THE SAME LOCATION FROM THE EXISTING POWER

PANEL. EXISTING SWITCH TO BE REUSED TO SERVE NEW EQUIPMENT. EXISTING FUSES TO BE

REPLACED WITH NEW FUSES AS INDICATED ON THE NEW WORK PLAN. DISCONNECT AND

REMOVE EXISTING DISCONNECT SWITCH FROM UNIT AND SALVAGE FOR OWNER'S USE IF THE

SWITCH IS STILL IN GOOD CONDITION. IF SWITCH IS IN POOR CONDITION, DISPOSE OF

SWITCH WITH OTHER MATERIALS IN A LEGAL MANNER. MATERIALS THAT ARE CAPABLE OF

BEING RECYCLED SHALL BE DISPOSED OF AT A LOCAL RECYCLING CENTER. REFER TO GENERAL

NOTE #5 FOR CIRCUIT TRACING TO BE PERFORMED BY ELECTRICAL CONTRACTOR PRIOR TO

START OF CONSTRUCTION TO IDENTIFY THE EXISTING BRANCH CIRCUIT SERVING THE

EQUIPMENT TO BE REPLACED WITH NEW.

ELECTRICAL CONTRACTOR SHALL DISCONNECT AND REMOVE EXISTING BRANCH CIRCUIT

CONDUIT AND WIRING SERVING MECHANICAL EQUIPMENT INDICATED COMPLETE TO

SOURCE. EXISTING CONDUIT MAY REMAIN AND BE RECONFIGURED TO SUPPORT SERVING THE

NEW EQUIPMENT TO BE INSTALLED IN THE SAME LOCATION FROM THE EXISTING POWER

PANEL. EXISTING CIRCUIT BREAKER TO BE REMOVED AND REPLACED WITH A NEW CIRCUIT

BREAKER WITH THE TRIP RATING AS INDICATED ON THE NEW WORK PLAN. DISCONNECT AND

REMOVE EXISTING DISCONNECT SWITCH FROM UNIT AND SALVAGE FOR OWNER'S USE IF THE

SWITCH IS STILL IN GOOD CONDITION. IF SWITCH IS IN POOR CONDITION, DISPOSE OF

SWITCH WITH OTHER MATERIALS IN A LEGAL MANNER. MATERIALS THAT ARE CAPABLE OF

BEING RECYCLED SHALL BE DISPOSED OF AT A LOCAL RECYCLING CENTER. REFER TO GENERAL

NOTE #5 FOR CIRCUIT TRACING TO BE PERFORMED BY ELECTRICAL CONTRACTOR PRIOR TO

START OF CONSTRUCTION TO IDENTIFY THE EXISTING BRANCH CIRCUIT SERVING THE

EQUIPMENT TO BE REPLACED WITH NEW.

ELECTRICAL CONTRACTOR SHALL DISCONNECT AND REMOVE EXISTING BRANCH CIRCUIT

CONDUIT AND WIRING SERVING MECHANICAL EQUIPMENT INDICATED COMPLETE TO

SOURCE. LABEL EXISTING CIRCUIT BREAKER SERVING EQUIPMENT AS "SPARE". REFER TO

GENERAL NOTE #5 FOR CIRCUIT TRACING REQUIRED TO BE PERFORMED BY THE ELECTRICAL

CONTRACTOR PRIOR TO START OF CONSTRUCTION TO IDENTIFY THE EXISTING BRANCH

CIRCUIT SERVING THE EQUIPMENT TO BE REPLACED. BRANCH CIRCUIT IDENTIFIED BY CIRCUIT

TRACING SHALL BE REFLECTED ON THE AS-BUILT RECORD DRAWINGS. DISCONNECT AND

REMOVE EXISTING DISCONNECT SWITCH AND MOTOR STARTER SERVING EQUIPMENT AND

SALVAGE FOR OWNER'S USE IF THE SWITCH AND/OR STARTER IS STILL IN GOOD CONDITION.

IF SWITCH AND/OR MOTOR STARTER IS IN POOR CONDITION, DISPOSE OF SWITCH AND/OR

MOTOR STARTER WITH OTHER MATERIALS IN A LEGAL MANNER. MATERIALS THAT ARE CAPABLE

OF BEING RECYCLED SHALL BE DISPOSED OF AT A LOCAL RECYCLING CENTER. NOTE THAT THE EXISTING "SPARE" CIRCUIT MAY BE REUSED TO SERVE NEW EQUIPMENT, WHERE INDICATED ON

THE NEW WORK PLANS.

ELECTRICAL CONTRACTOR SHALL DISCONNECT, REMOVE AND SALVAGE FOR THE OWNER THE

EXISTING MOTOR STARTER SERVING EXISTING PUMP REMOVED BY DEMOLITION WORK.

ELECTRICAL CONTRACTOR SHALL DISCONNECT AND REMOVE EXISTING WEATHER-PROOF /

GFCI DUPLEX RECEPTACLE AT MECHANICAL EQUIPMENT TO BE REMOVED. DISCONNECT AND

REMOVE EXISTING BRANCH CIRCUIT CONDUIT AND WIRING SERVING RECEPTACLE TO NEAREST

JUNCTION BOX TO ALLOW FOR REUSE TO SERVE NEW RECEPTACLE TO BE MOUNTED AT NEW

EQUIPMENT TO BE INSTALLED IN THE SAME LOCATION. REFER TO NEW WORK PLAN FOR

ADDITIONAL INFORMATION.

DEMOLITION KEY NOTES

ED100.1

B200 MECHANICAL ROOM FLOOR

PLAN - ELECTRICAL DEMOLITION

ED100.1

1.

2.

ALL DEVICES INDICATED WITH SOLID LIGHT LINES ARE EXISTING DEVICES TO REMAIN.

ALL DEVICES AND FIXTURES INDICATED WITH SOLID DARK CROSS-HATCHED LINES ARE

EXISTING TO BE REMOVED OR RELOCATED BY THIS ELECTRICAL CONTRACTOR.

ELECTRICAL CONTRACTOR SHALL PROVIDE DEMOLITION OF ELECTRICAL DEVICES, CONDUIT,

WIRING, FIXTURES, EQUIPMENT, ETC. AS REQUIRED TO ACCOMMODATE ARCHITECTURAL,

MECHANICAL AND ELECTRICAL REVISIONS. ELECTRICAL DEMOLITION SHEET PROVIDES A

GENERAL GUIDELINE AS TO THE SCOPE OF THE WORK. HOWEVER, ALL DEMOLITION

REQUIREMENTS MAY NOT BE INDICATED. PROVIDE DEMOLITION AS REQUIRED TO

ACCOMMODATE PROJECT REVISIONS.

COORDINATE DEMOLITION REQUIREMENTS WITH THE WORK OF OTHER TRADES.

PRIOR TO START OF CONSTRUCTION, AND PRIOR TO ANY DEMOLITION WORK THE

ELECTRICAL CONTRACTOR SHALL PERFORM CIRCUIT TRACING TO IDENTIFY ALL EXISTING 120

VOLT AND 480 VOLT BRANCH CIRCUITS SERVING THE RENOVATION AREA, AND TO IDENTIFY

THE AVAILABLE BRANCH CIRCUITS THAT MAY BE RE-USED AS PART OF THE PROPOSED

RENOVATION, AS WELL AS CIRCUITS THAT SERVE EXISTING DEVICES OR EQUIPMENT OUTSIDE

OF THE WORK AREA THAT ARE TO REMAIN AND BE MAINTAINED.

ELECTRICAL GENERAL NOTES:

3.

4.

5.

MECH

EQUIPMENT

ELECTRICAL

EQUIPMENT

LOW ROOF

EXISTING PANEL "MPB BLDG-200"

480Y/277V-3Ø-4W

(TO REMAIN)

STAIR

ROOF

EXISTING AC-1

480V-3Ø

TO BE REMOVED

EXISTING P-7

120V, TO BE REMOVED

AND REPLACED.

EXISTING AHU-1

(TO REMAIN)

EXISTING AHU-2

(TO REMAIN)

EXISTING AHU-3

(TO REMAIN)

EXISTING AHU-4

(TO REMAIN)

EXISTING BOILER

COMBUSTION AIR FAN

TO BE REMOVED

EXISTING BOILER "B-1"

TO BE REMOVED

EXISTING…