MAIN BUILDING HEAT PUMP SCHEDULE
ITEM
HP-M1
HP-M2
HP-M3
HP-M4
HP-M5
HRC-M1
HRC-M2
NOTES:
1. SOURCE SIDE TEMPERATURES TO BE COORDINATED WITH WELL FIELD DESIGNER
2. R410A
3. PROVIDE MASTER CONTROLLER
4. PROVIDE SPRING ISOLATORS
5. PROVIDE SCROLL COMPRESSORS
MANUFACTURER
WATER FURNACE
WATER FURNACE
WATER FURNACE
WATER FURNACE
WATER FURNACE
WATER FURNACE
WATER FURNACE
MODEL NO.
NXW600R
NXW600R
NXW600R
NXW600R
NXW600R
NXW180R
NXW180R
LOCATION
MAIN. BLDG/MECH
MAIN. BLDG/MECH
MAIN. BLDG/MECH
MAIN. BLDG/MECH
MAIN. BLDG/MECH
HEAT RECOVERY/COOLING ONLY
HEAT RECOVERY/COOLING ONLY
SYSTEM
SERVED
SPACE HEATING/COOLING
SPACE HEATING/COOLING
SPACE HEATING/COOLING
SPACE HEATING/COOLING
SPACE HEATING/COOLING
LAN/IT/SECURITY COOLING
LAN/IT/SECURITY COOLING
COOLING
SOURCE
COOLING
CAPACITY
(KW)
192.2
192.2
192.2
192.2
192.2
66.9
66.9
ENT
LOAD
TEMP
(°C) 11.7
11.7
11.7
11.7
11.7
11.7
11.7
LVG
LOAD
TEMP
(°C) 6.4
6.4
6.4
6.4
6.4
6.2
6.2
LOAD
FLOW
RATE
(LPS)
8.8
8.8
8.8
8.8
8.8
2.9
2.9
LOAD
PRESSURE
DROP
(kPa) 26.0
26.0
26.0
26.0
26.0
18.0
18.0
ENT
SOURCE
TEMP
(°C) 18.3
18.3
18.3
18.3
18.3
18.3
18.3
LVG
SOURCE
TEMP
(°C) 24.2
24.2
24.2
24.2
24.2
24.9
24.9
SOURCE
FLOW
RATE
(LPS)
9.5
9.5
9.5
9.5
9.5
2.9
2.9
SOURCE
PRESSURE
DROP
(kPa) 39.6
39.6
39.6
39.6
39.6
19.2
19.2
HEATING
SOURCE
HEATING
CAPACITY
(KW)
148.0
148.0
148.0
148.0
148.0
39.6
39.6
ENT
LOAD
TEMP
(°C) 45.0
45.0
45.0
45.0
45.0
45.6
45.6
LVG
LOAD
TEMP
(°C) 49.0
49.0
49.0
49.0
49.0
49.9
49.9
LOAD
FLOW
RATE
(LPS)
8.8
8.8
8.8
8.8
8.8
2.9
2.9
LOAD
PRESSURE
DROP
(kPa) 21.8
21.8
21.8
21.8
21.8
13.9
13.9
ENT
SOURCE
TEMP
(°C) 1.7
1.7
1.7
1.7
1.7
1.7
1.7
LVG
SOURCE
TEMP
(°CF)
-0.9
-0.9
-0.9
-0.9
-0.9
-1.4
-1.4
SOURCE
FLOW
RATE
(LPS)
9.5
9.5
9.5
9.5
9.5
2.9
2.9
SOURCE
PRESSURE
DROP
(kPa) 41.6
41.6
41.6
41.6
41.6
21.8
21.8
ELECTRICAL DATA
VOLT
PH
HZ
MCA
96.5
96.5
96.5
96.5
96.5
27.5
27.5
MHACR
BREAKER
125.0
125.0
125.0
125.0
125.0
35.0
35.0
COMPRESSOR
SCROLL (2)
SCROLL (2)
SCROLL (2)
SCROLL (2)
SCROLL (2)
SCROLL (2)
SCROLL (2)
MIN.
EER/COP
18.8/2.9
18.8/2.9
18.8/2.10
18.8/2.11
18.8/2.12
21.5/3.1
21.5/3.2
PROP.
GLYCOL
(SOURCE SIDE)
15.0
15.0
15.0
15.0
15.0
15.0
PROP.
GLYCOL
(LOAD SIDE)
0.0
0.0
0.0
0.0
0.0
0.0
OPERATING
WEIGHT
(KG)
839.0
839.0
839.0
839.0
383.0
383.0
NOTES
ALL
ALL
ALL
ALL
ALL
ALL
ALL
MAIN BUILDING COMPUTER ROOM AIR CONDITIONING UNIT
ITEM
CAC-M1
CAC-M2
CAC-M3
CAC-M4
CAC-M5
NOTES:
1. PROVIDE FACTORY CONDENSATE PUMP FOR AUTOMATIC REMOVAL OF CONDENSATE AND HUMIDIFIER FLUSH WATER.
2. THE CONDENSATE PUMP SHALL BE SPECIFICALLY DESIGNED TO OPERATE WITH THE HIGHER CONDENSATE TEMPERATURES CAUSED BY THE FLUSH AND DRAIN CYCLES OF THE ELECTRODE CANISTER HUMIDIFIERS.
3. IN ADDITION TO THE STANDARD CONDENSATE PAN OVERFLOW SAFETY FLOAT(S), THE CONDENSATE PUMP SHALL INCLUDE AN INTERNAL OVERFLOW SAFETY FLOAT SWITCH WIRED TO THE A/C'S REMOTE STOP/START TERMINALS WHICH SHALL OPEN THE A/C'S CONTROL CIRCUIT, THEREBY SHUTTING THE A/C DOWN IN THE EVENT OF A CONDENSATE OVERFLOW.
4. DISCHARGE FROM CONDENSATE PUMP SHALL RUN TO THE NEAREST JANITOR'S CLOSET OR MER.
AREA SERVED
LAN DATA ROOM
LAN DATA ROOM
HOMELAND SEC DATA
HOMELAND SEC DATA
HOMELAND SEC DATA
MODEL
OHS-072-C
OHS-072-C
OHS-018-C
OHS-018-C
OHS-048-C
FAN DATA
FLOW
RATE
LPS
EXT
SP
PA
75.0
75.0
75.0
75.0
75.0
CHILLED WATER COOLING COIL DATA
COOLING LOAD
TOTAL
KW
21.3
21.3
5.9
5.9
13.4
SENSIBLE
SENSIBLE
KW
20.0
20.0
5.3
5.3
12.6
AIR SIDE
EAT DB
°C 23.9
23.9
23.9
23.9
23.9
EAT WB
°C 16.1
16.1
16.1
16.1
16.1
LAT DB
°C 11.7
11.7
11.2
11.2
13.1
LAT WB
°C 10.9
10.9
10.6
10.6
11.9
WATER SIDE
EWT
°C 7.1
7.1
7.1
7.1
7.1
LWT
°C
12.2
12.2
13.2
LPS
0.7
0.7
0.7
0.7
0.7
UNIT DATA
FLA
9.3
9.3
5.3
5.3
9.3
MCA
11.6
11.6
6.6
6.6
12.0
ELECTRICAL
MFS
V/PH/HZ
460/3/60
460/3/60
460/3/60
460/3/60
460/3/60
HUMIDIFIER
MOISTURE
FLOW
KG/HR
1.8 - 6.8
1.8 - 6.8
0.9 - 2.3
0.9 - 2.3
1.8 - 4.5
NOTES
DUTY
STANDBY
DUTY
STANDBY
DUTY
MAIN BUILDING PUMP SCHEDULE
ITEM
PCWP-M1
PCWP-M2
PCWP-M3
PCWP-M4
PCWP-M5
PCWP-M6
PCWP-M7
CWP-M1
CWP-M2
PCHWP-M1
PCHWP-M2
PCHWP-M3
PCHWP-M4
PCHWP-M5
PCHWP-M6
PCHWP-M7
CHWP-M1
CHWP-M2
HHWP-M1
HHWP-M2
P-M1
P-M2
P-M3
P-M4
NOTE:
1. FOR ALL POLYPHASE PUMPS NOT ON VFD, PROVIDE COMBINATION STARTER/DISCONNECT TO MATCH
2. FINAL PUMP IMPELLER SIZE TO OPERATE AT REQUIRED FLOW AT MIN. 80% OF 60HZ SELECTION.
MANUFACTURER
BELL & GOSSETT
BELL & GOSSETT
BELL & GOSSETT
BELL & GOSSETT
BELL & GOSSETT
BELL & GOSSETT
BELL & GOSSETT
BELL & GOSSETT
BELL & GOSSETT
BELL & GOSSETT
BELL & GOSSETT
BELL & GOSSETT
BELL & GOSSETT
BELL & GOSSETT
BELL & GOSSETT
BELL & GOSSETT
BELL & GOSSETT
BELL & GOSSETT
BELL & GOSSETT
BELL & GOSSETT
BELL & GOSSETT
BELL & GOSSETT
BELL & GOSSETT
BELL & GOSSETT
MODEL
e-80 4X4X7B e-80 4X4X7B e-80 4X4X7B e-80 4X4X7B e-80 4X4X7B e-90-2AAC e-90-2AAC e-1510-4BD e-1510-4BD
E80 3X3X7C
E80 3X3X7C
E80 3X3X7C
E80 3X3X7C
E80 3X3X7C e-90-2AAC e-90-2AAC e-1510-3EB e-1510-3EB e-1510-3EB e-1510-3EB
PL-36
PL-30
PL-36
PL-130
TYPE
INLINE
INLINE
INLINE
INLINE
INLINE
INLINE
INLINE
END-SUCTION
END-SUCTION
INLINE
INLINE
INLINE
INLINE
INLINE
INLINE
INLINE
END-SUCTION
END-SUCTION
END-SUCTION
END-SUCTION
INLINE
INLINE
INLINE
INLINE
LOCATION
MAIN BUILDING
MAIN BUILDING
MAIN BUILDING
MAIN BUILDING
MAIN BUILDING
MAIN BUILDING
MAIN BUILDING
MAIN BUILDING
MAIN BUILDING
MAIN BUILDING
MAIN BUILDING
MAIN BUILDING
MAIN BUILDING
MAIN BUILDING
MAIN BUILDING
MAIN BUILDING
MAIN BUILDING
MAIN BUILDING
MAIN BUILDING
MAIN BUILDING
MAIN BUILDING
MAIN BUILDING
MAIN BUILDING
MAIN BUILDING
SERVICE
PRIMARY CONDENSER WATER
PRIMARY CONDENSER WATER
PRIMARY CONDENSER WATER
PRIMARY CONDENSER WATER
PRIMARY CONDENSER WATER
PRIMARY CONDENSER WATER
PRIMARY CONDENSER WATER
CONDENSER WATER
CONDENSER WATER
PRIMARY CHILLED WATER
PRIMARY CHILLED WATER
PRIMARY CHILLED WATER
PRIMARY CHILLED
PRIMARY CHILLED
PRIMARY CHILLED WATER
PRIMARY CHILLED WATER
SECONDARY CHILLED WATER
SECONDARY CHILLED WATER
SECONDARY HOT WATER
SECONDARY HOT WATER
FREEZE PROTECTION
FREEZE PROTECTION
FREEZE PROTECTION
FREEZE PROTECTION
FLOW RATE
L/S
9.5
9.5
9.5
9.5
9.5
2.9
2.9
42.5
42.5
8.8
8.8
8.8
8.8
8.8
2.9
2.9
1.5
1.1
1.1
HEAD
(M)
1.0
1.3
1.0
0.4
RPM
PROP.
GLYCOL %
MOTOR KW
0.56
0.56
0.56
0.56
0.56
0.19
0.19
11.19
11.19
0.56
0.56
0.56
0.56
0.56
0.19
0.19
14.91
14.91
14.91
14.91
0.13
0.06
0.13
0.30
MOTOR HP
0.75
0.75
0.75
0.75
0.75
0.25
0.25
0.75
0.75
0.75
0.75
0.75
0.25
0.25
0.17
0.08
0.17
0.4
VOLT
PH
HZ
NOTES
RUN
RUN
RUN
RUN
STANDBY
RUN
STANDBY
RUN, VFD
STANDBY, VFD
RUN
RUN
RUN
RUN
RUN
RUN
STANDBY
RUN, VFD
STANDBY, VFD
RUN, VFD
STANDBY, VFD
RUN
RUN
RUN
RUN
E D C B A
DESCRIPTIONDATEMARK
C O
N
TR
A C
TO
R
S B
U
IL
D
IN
G P
R O
JE
C
T D
R A
W
IN
G
SEQUENCETYPEDISCIPLINE
OFSHEET
GENERAL SERVICES ADMINISTRATION
R
EV
IS
IO
N N
O
TE
S
KE
Y
PL
AN
C
E R
TI
FI
C
AT
IO
N