General Drawings.pdf

PDF 5 MB Posted

Attached to
Z1DA--Project# 614-19-102 - Reno Bldg. 7 Spinal Cord Injury Rehab Area
Solicitation number
36C24920B0003
Issued by

About this file

This document package includes construction drawings and notes for a renovation project at the Memphis VA Medical Center.

The project involves renovating Building 7 to upgrade the Spinal Cord Injury Rehab Area. The work includes architectural, mechanical, electrical, plumbing and telecommunications upgrades. Detailed drawings show demolition plans, new construction plans, schedules and technical details. Notes specify infection control requirements and procedures to isolate the work area from occupied spaces. The documents provide specifications for constructing temporary barriers, maintaining negative air pressure, controlling dust and cleaning/decontamination.

The related federal contract opportunity is a pre-solicitation notice for solicitation number 36C24920B0003. The opportunity description states an Invitation for Bid will be issued under solicitation 36C24919B0001_1 to fulfill the pre-solicitation requirements. The contracting agency is the Department of Veterans Affairs Veterans Health Administration VISN 9. No other details are included regarding response dates, pricing terms, set-asides or other procurement requirements.

View the file

Other files

File Type Posted
36C24920B0003 0007.docx DOCX document
36C24920B0003 0006.docx DOCX document
36C24920B0003 0005.docx DOCX document
36C24920B0003 0004.docx DOCX document
Amendent_SPECS.pdf PDF
Amend Rpt 0001.pdf PDF
Amendment_DRAWINGS.pdf PDF
36C24920B0003 0003.docx DOCX document
RFI Form - Renovate Bldg. 7 SCI Rehab Area.docx DOCX document
Contractor EMR Certification Form 2020.docx DOCX document
36C24920B0003 0002.docx DOCX document
36C24920B0003 0001.docx DOCX document
Drawings 614-19-102.pdf PDF
Electric-Telecom Drawings.pdf PDF
36C24920B0003_1.docx DOCX document
Addendum G-101.pdf PDF
Architectural Drawings 2.pdf PDF
Wage Determination - Shelby County.pdf PDF
Specifications.pdf PDF
Architectural Drawings 1.pdf PDF
Mechanical Drawings.pdf PDF
Fire-Plumbing Drawings.pdf PDF
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

N

VICINITY MAP

SCALE: N.T.S.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592Revisions: Date:

ORIGINAL DRAWING SIZE (30"X42")

B

IM

/1

V A

B ld g

S p in a l C o rd

I n ju ry

R e h a b A re a /1

V

A B ld g

A rc h

V

.r v t

/1

/2

:2

:1

P

M

G-001

COVER SHEET RENOVATE BUILDING 7 SPINAL

CORD INJURY (SCI) REHAB AREA

VA MEDICAL CENTER, MEMPHIS, TN

614-19-102

BLDG 7

4/22/2020 MWD QVL

N

LOCATION MAP

SCALE: N.T.S.

PROJECT LOCATION:

1030 JEFFERSON AVENUE

MEMPHIS, TN 38104

PROJECT LOCATION:

1030 JEFFERSON AVENUE

MEMPHIS, TN 38104

RENOVATE BUILDING 7 SPINAL CORD INJURY (SCI) REHAB AREA

BUILDING 7, 2ND FLOOR

MEMPHIS VA MEDICAL CENTER

MEMPHIS, TN

BID DOCUMENTS

APRIL 22, 2020

Department of Veterans Affairs

PROJECT # 614-19-102

BID DOCUMENTS APPROVAL

NAME / TITLE DATE

NAME / TITLE DATE

NAME / TITLE DATE

SHEET INDEX

SHEET

NUMBER SHEET NAME

MECHANICAL

M-001 MECHANICAL GENERAL NOTES AND ABBREVIATIONS

M-002 MECHANICAL LEGENDS

MD101 MECHANICAL DEMOLITION PLANS

M-101 MECHANICAL NEW WORK PLANS

M-501 MECHANICAL DETAILS

M-502 MECHANICAL DETAILS

M-503 MECHANICAL DETAILS

M-601 MECHANICAL SCHEDULE AND CONTROL SEQUENCES

ELECTRICAL

E-001 ELECTRICAL GENERAL NOTES AND ABBREVIATIONS

E-002 ELECTRICAL LEGEND

ED101 ELECTRICAL DEMOLITION PLAN

E-101 LIGHTING AND PHOTOMETRIC PLAN

E-111 POWER PLAN

E-501 ELECTRICAL DETAILS

E-502 ELECTRICAL DETAILS

E-601 ELECTRICAL ONE-LINE DIAGRAM

E-602 LIGHT FIXTURE SCHEDULE

E-603 PANELBOARD SCHEDULES

TELECOMMUNICATIONS

T-001 TELECOM GENERAL NOTES, ABBREVIATIONS & LEGEND

TD101 TELECOMMUNICATIONS DEMOLITION PLAN

T-101 TELECOMMUNICATIONS PLAN

T-501 TELECOMMUNICATIONS DETAILS AND RISER DIAGRAMS

SHEET INDEX

SHEET

NUMBER SHEET NAME

GENERAL

G-001 COVER SHEET

G-002 INFECTION CONTROL PLAN AND RISK ASSESSMENT NOTES

G-101 BUILDING CODE SUMMARY & DEDUCTIVE ALTERNATES

G-102 LIFE SAFETY PLAN

ARCHITECTURAL

A-001 GENERAL NOTES, ABBREVIATIONS & SYMBOLS

AD101 PARTIAL 2ND LEVEL - DEMOLITION PLAN

AD102 EXISTING CONDITION PHOTOS

A-101 PARTIAL 2ND LEVEL - FLOOR PLAN

A-131 PARTIAL 2ND LEVEL - REFLECTED CEILING PLAN

A-171 PARTIAL 2ND LEVEL - FURNITURE / EQUIPMENT PLAN

A-371 PARTITION TYPES & DETAILS

A-401 ENLARGED PLANS

A-402 INTERIOR ELEVATIONS

A-501 MILLWORK DETAILS

A-571 MOUNTING HEIGHTS

A-572 DETAILS

A-601 DOOR SCHEDULE, DOOR/FRAME TYPES, AND DETAILS

A-631 FINISH SCHEDULE & DETAILS

A-701 SIGNAGE PLAN

FIRE PROTECTION

F-001 FIRE PROTECTION GENERAL NOTES AND SYMBOLS

F-101 FIRE PROTECTION & FIRE ALARM PLANS

PLUMBING

P-001 PLUMBING LEGEND, SYMBOLS, AND GENERAL NOTES

PD101 PLUMBING SUPPLY DEMOLITION PLANS

P-101 PLUMBING SUPPLY NEW WORK PLANS

P-102 PLUMBING SANITARY DEMOLITION AND NEW WORK PLANS

TYPE C

HIGH RISK

AREA OF WORK

2ND FLOOR

LEGEND

1 HOUR TEMPORARY PARTITION

WITH 3'-6" C-LABEL DOOR AND FRAME

CIRCULATION THAT MUST REMAIN

OPEN DURING CONSTRUCTION

EXISTING FINISHED FLOOR

BASE TO MATCH

ADJACENT SURFACE

(1) LAYER 5/8" TYPE "X" EACH SIDE, FINISH

& PAINT TO MATCH ADJACENT SURFACE

AT AREAS EXPOSED TO VIEW.

FOR EXTERIOR EXPOSURE ADD LAYER OF

5/8" EXTERIOR GYPSUM SHEATHING TO

EACH SIDE OF THE ASSEMBLY.

PROVIDE "L" BRACKET AT

CEILING TILE WITH

CONTINUOUS CAULKING

EXISTING CEILING

SYSTEM - MODIFY, PATCH,

& REPAIR AS REQUIRED

NON - CONSTRUCTION SIDE

EXISTING DUCTWORK,

CONDUITS, PIPING,

WIRING, ETC.

SMOKE SEAL ALL PENETRATIONS,

TYP. BOTH SIDES

FIRESTOP ALL VOIDS & PROVIDE

PREMOLDED NEOPRENE FLUTE

INSERTS; EXTEND GWB TIGHT TO DECK

CONTINUOUS FIRE CAULK,

SMOKE SEAL, TYP.,

INCLUDE INTERIOR SIDE

WHERE ACCESSIBLE

3 5/8" METAL STUDS @ 16"

O.C.

CONSTRUCTION SIDE

CONTINUOUS PERIMETER CAULKING

WHERE NEW CONSTRUCTION

OVERLAPS EXISTING WALL

EXISTING WALL TO REMAIN

CAREFULLY PATCH & REPAIR

EXISTING SPRAY ON FIREPROOFING

FOR FULL COVERAGE & CODE

COMPLIANT CONDITION, TYP.

EXISTING FLOOR OR ROOF DECK

CORRIDOR

C2-30

ELEVATOR ELEVATOR ELEVATOR

STAIR

NO 4

STAIR

NO 5

COMM

2C100

EC

2C101

LACK

2C103

STORAGE

2C106B

WHEEL CHAIR STORAGE

2C106A

STORAGE

2C106

PHYSICAL THERAPY

2C110

TOILET

2C-08

CORRIDOR

C2-27

STORAGE

2C110A

OFFICE

2C110B

COMM

2C117

EC

2C118

CORRIDOR

C2-29

CORRIDOR

C2-28

STORAGE

2C121

R.T. CLINIC

2C120DRIVER CLINIC

2C115

MEN TOILET

2C113

WOMEN TOILET

2C114

TOILET

2C116

JAN.

CLOSET

2C119

STORAGE /

BREAK ROOM

2C112A

MED REHAB

2C112

STORAGE

2C111B

O.T. CLINIC

2C111

2C111C

OFFICE

2C111A

PRIVATE TREATMENT

2C109

K.T. CLINIC

2C107

OFFICE

2C107A TOILET

2C104

JAN. CLOSET

2C102

OPEN COURTYARD

OPEN COURTYARD

PROVIDE

CONSTRUCTION

SIGNAGE ON

DOOR AND

STAIR

FOR EXTERIOR

TEMPORARY

CONSTRUCTION BARRIER

ASSEMBLY, PROVIDE

EXTERIOR GYPSUM

SHEATHING.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592Revisions: Date:

ORIGINAL DRAWING SIZE (30"X42")

B

IM

/1

V A

B ld g

S p in a l C o rd

I n ju ry

R e h a b A re a /1

V

A B ld g

A rc h

V

.r v t

/1

/2

:2

:1

P

M

G-002

INFECTION CONTROL PLAN AND

RISK ASSESSMENT NOTES

RENOVATE BUILDING 7 SPINAL

CORD INJURY (SCI) REHAB AREA

VA MEDICAL CENTER, MEMPHIS, TN

614-19-102

BLDG 7

4/22/2020 MWD QVL

1. G.C. IS TO FOLLOW ALL VA/ ICRA REGULATIONS IN PERFORMING ALL WORK.

2. G.C. IS TO COORDINATE WITH THE VA FOR OFF-HOURS ACCESS TO THE FLOORS ABOVE AND BELOW THE WORK NEEDED FOR

MECHANICAL TIE-INS. TEMPORARY ICRA BARRIERS ARE TO BE INSTALLED AROUND ALL WORK AREAS PRIOR TO CONSTRUCTION.

3. G.C. IS RESPONSIBLE FOR PERFORMING ALL WORK SHOWN IN THE CONTRACT DOCUMENTS IN THE WORK AREA DESIGNATED, AND

FOR PROVIDING ICRA AT EVERY WORK LOCATION.

4. FOLLOW ALL FIRE SAFETY CODES DURING CONSTRUCTION.

5. PAINT ALL HARDWALL ICRA BARRIERS ON THE PUBLIC SIDE OF BARRIERS.

6. G.C. TO PROVIDE THE VA 15 CALENDAR DAYS NOTICE OF ANY WORK TO BE PERFORMED OFF HOURS.

7. G.C. TO COORDINATE CONSTRUCTION WITH THE OWNER AND PROVIDE CRITICAL PATH TIMELINE/GANTT CHART FOR ENTRY OF

PROJECT WITH OWNER APPROVED MILESTONES.

8. PRIOR TO THE START OF DEMOLITION, ISOLATE ALL HVAC SYSTEMS IN AREAS WHERE WORK IS BEING PERFORMED. REFER TO

MECHANICAL DRAWINGS FOR ISOLATION AND/ OR REMOVAL. INSTALL ALL TEMPORARY PARTITIONS AND COORDINATE NEW CONSTRUCTION NECESSARY TO MEET ICRA STANDARDS. ESTABLISH NEGATIVE PRESSURE AT ICRA BARRIERS EQUIVALENT TO

0.001 WATER GAUGE. NEGATIVE PRESSURE SHALL BE ACCOMPLISHED BY HEPA EXHAUST FILTRATION UNITS MONITORED BY

DIGITAL RECORDING MANOMETER AND BALL IN TUBE INDICATOR VISIBLE IN PUBLIC AREAS.

9. PATCH AND REPAIR ANY EXISTING WALLS, FLOORS AND CEILINGS AFFECTED BY DEMOLITION AND/OR CONSTRUCTION.

10. CONTRACTOR TO UTILIZE HEPA FILTERED FANS TO CONTROL DUST AND ACHIEVE NEGATIVE PRESSURIZATION IN WORK SITE

THROUGHOUT PROJECT.

11. DO NOT REMOVE BARRIERS/ DUST PARTITIONS FROM WORK AREA UNTIL PROJECT PHASE IS COMPLETED AND PROJECT AREA IS

THOROUGHLY CLEANED AND APPROVED BY ENGINEERING SERVICES.

12. VACUUM WORK WITH HEPA FILTERED VACUUMS. WET MOP WITH DISINFECTANT AFTER VACUUMING - DAILY OR MORE FREQUENTLY

AS NEEDED TO MAINTAIN CLEANLINESS SUITABLE TO VAMC PERSONNEL AND MINIMIZE DUST GENERATION.

13. REMOVE BARRIER/ DUST PARTITION MATERIALS CAREFULLY TO MINIMIZE SPREADING OF DIRT AND DEBRIS ASSOCIATED WITH

CONSTRUCTION.

14. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED CONTAINERS. COVER TRANSPORT RECEPTACLES OR

CARTS, TAPE COVERING. ALL WASTE INSIDE CONSTRUCTION AREA TO BE CONTAINED AND TIGHTLY COVERED AT ALL TIMES.

15. CONTRACTOR SHALL MAINTAIN TEMPORARY LIFE SAFETY DEVICES WITHIN THE CONSTRUCTION SITE THROUGHOUT THE DURATION

OF THE PROJECT AS DIRECTED BY THE VA AND VA SAFETY OFFICE.

16. ROUTE DISCHARGE DUCT OF HEPA FILTER TO EXTERIOR OF BUILDING (THROUGH ADJACENT MECHANICAL ROOM) WHERE

NEGATIVE PRESSURE IS MAINTAINED FOR WORK SPACE. VAMC ICRA GROUP TO MONITOR AIR DURING CONSTRUCTION.

CONTRACTOR TO FOLLOW THE VAMC GUIDELINES AND PREVENTATIVE MEASURES PROVIDED BY THE VAMC ICRA GROUP.

CONTRACTOR TO PREPARE A PLAN OF PROTECTION MEASURES, STATUS REPORTS AND SUBMIT FOR REVIEW AND COMPLIANCE TO THE VAMC ICRA GROUP. ALL CONTRACTORS PERSONNEL INVOLVED ARE TO BE TRAINED ON INFECTIONS PREVENTION MEASURES ESTABLISHED BY THE VAMC. CONTRACTOR TO PROVIDE RECORDING MANOMETER THROUGHOUT CONSTRUCTION DURATION.

17. PROVIDE TEMPORARY 1 HR. RATED CONSTRUCTION BARRIER (ul465) PRIOR TO THE START OF DEMOLITION. CONSTRUCTION DUST PARTITIONS OF 3-5/8" METAL STUDS W/ 5/8" GWB. ON BOTH SIDES AND CONTINUOUS FIRESTOP SEALANT AS REQUIRED. PAINT BARRIER EXPOSED TO THE PUBLIC. ERECT PARTITION TIGHT TO THE FLOOR, SIDE WALLS AND THE UNDERSIDE OF THE

STRUCTURE. SEAL HOLES, PIPES, CONDUITS AND PENETRATIONS APPROPRIATELY.

18. PROVIDE STICKY MATS AND HEPA VACUUM FOR WORKERS CLOTHING. REMOVE AT COMPLETION OF WORK. MATS TO BE CHANGED

AS SOON AS VISIBLY SOILED.

19. ALL CONSTRUCTION ENTRANCES SHALL HAVE CYPHER LOCK WITH KEY OVERRIDE. COORDINATE WITH VA FOR LOCK CORE

INSTALLATION.

20. ADJACENT SPACES SHALL REMAIN OCCUPIED AND OPERATIONAL. MAINTAIN USER ACCESS AND MEANS OF EGRESS THROUGH THE EXISTING CORRIDORS. MAINTAIN NEGATIVE PRESSURE AND POSITIVE PRESSURE AS REQUIRED.

21. TEMPORARY SERVICE SHUT-OFFS AND HOURS OF OPERATION ARE TO BE COORDINATED WITH THE VA.

22. COORDINATE MOVEMENT OF CONSTRUCTION EQUIPMENT INTO AND WITHIN THE AREA OF WORK. COORDINATION SHALL BE

REVIEWED ON A DAILY BASIS WITH THE VA.

23. CONTRACTOR TO MEET WITH THE VA SECURITY PRIOR TO CONSTRUCTION.

24. CONTRACTOR SHALL FIELD VERIFY THE LOCATION OF EXISTING UTILITIES WITHIN THE LIMITS OF CONSTRUCTION. THE

CONTRACTOR SHALL EXERCISE CAUTION TO AVOID DAMAGE OF EXISTING UTILITIES.

25. GC TO VERIFY AND CONFIRM THAT ALL NEW AND EXISTING PENETRATIONS IN THE EXISTING RATED WALLS ARE FIRESTOPPED TO

MEET CODE.

ICRA GENERAL CONSTRUCTION NOTES:

1. G.C. TO PROVIDE TEMPORARY EXIT SIGNS & LIGHTS INSIDE OF CONSTRUCTION BARRIERS.

2. G.C. TO PROVIDE CONTINUOUS CAULKING & SMOKE SEALS AS REQ'D FOR COMPLETELY SEALED CONDITION SEPARATING

OPERATIONAL AREAS FROM CONSTRUCTION AREAS.

3. G.C. TO PROVIDE CONSTRUCTION SIGNAGE PER THE GENERAL REQUIREMENTS.

4. ALL SMOKE DETECTORS SHALL BE HEAT DETECTORS.

5. G.C. TO CONSTRUCT ALL CONSTRUCTION BARRIERS AT NIGHT AND PROVIDE PLASTIC IN PLACE FOR DUST CONTROL DURING

FABRICATION. PROVIDE FOR NEGATIVE AIR WITH HEPA FILTER TO OUTSIDE.

6. G.C. TO PROVIDE SELF CLOSING FIRE-RATED DOORS AND METAL FRAMES COMMENSURATE WITH PARTITION. IN ROOMS REQUIRING

ACCESS, G.C. TO COORDINATE EXACT QUANTITY REQUIRED. DOORS SHALL BE ABLE TO ACCEPT A VA SCSR LOCK BY KABA FOR KEY CARD ACCESS. G.C. TO PROVIDE LOCK AND KEY CARD ACCESS. PAINT DOOR AND FRAME TO MATCH ADJACENT WALL.

7. G.C. TO PROVIDE TEAR-OFF WALK OFF MATS IMMEDIATELY INSIDE OF EVERY CONSTRUCTION ENTRANCE DOOR. G.C. TO CHANGE WALK OFF MATS ON AVERAGE OF 8 TIMES PER DAY. G.C. TO COORDINATE EXACT QUANTITY REQUIRED.

8. G.C. TO PROVIDE FOOT PRE-WASH PRIOR TO WALKING OUT OF THE CONSTRUCTION AREA. G.C. TO COORDINATE EXACT QUANTITY

REQUIRED.

9. ALL EXTERIOR AREAS TO BE KEPT CLEAN FOR ANY DEBRIS BEING CARRIED OUT.

10. SEE TEMPORARY CONSTRUCTION BARRIER DETAIL F7/G-002.

TEMPORARY CONSTRUCTION BARRIER GENERAL NOTES:

SCALE: = 1'-0"

0 8 168

1/8"

N

KEYPLAN

SCALE: N.T.S.F7

TEMPORARY CONSTRUCTION BARRIER DETAIL

SCALE: 1/8" = 1'-0"F1

PARTIAL 2ND LEVEL - INFECTION CONTROL PLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592Revisions: Date:

ORIGINAL DRAWING SIZE (30"X42")

G-101

BUILDING CODE SUMMARY &

DEDUCTIVE ALTERNATES

RENOVATE BUILDING 7 SPINAL

CORD INJURY (SCI) REHAB AREA

VA MEDICAL CENTER, MEMPHIS, TN

614-19-102

BLDG 7

4/22/2020 MWD QVL

VHAMEMFONGL

Polygon

VHAMEMFONGL

Typewritten Text Revision 1 - Remove Schedule of Deductive Alternates

VHAMEMFONGL

Typewritten Text 11/9/2020

VHAMEMFONGL

Typewritten Text Revision 1

UP

2B119

C2-23

C2-24

2C122 2C123

C2-26

NO 4

C2-30

2C1012C100

C2-25

2D100B

2D100A

2D100 2D101

2B118

HOPTEL

CORRIDOR

MENS TOILET WOMENS TOILET

STAIR

CORRIDOR

ECCOMM

CORRIDOR

ELEVATOR ELEVATOR OFFICEELEVATOR

KITCHEN

PVA OFFICE MECH RM

REF.

1. DEVICES HAVE BEEN SHOWN; BUT THE CONTRACTOR SHALL ENSURE

THE INSTALLATION OF ALL LIFE SAFETY DEVICES INDICATED ON THE

ENGINEERING DRAWINGS.

2. CONTRACTOR SHALL FIELD VERIFY THE LOCATION OF ANY EXISTING

FIRE RATED WALLS. ANY WORK DONE AROUND EXISTING FIRE RATED

WALLS SHALL BE DONE WITH CARE SO AS NOT TO COMPROMISE THE

RATING'S INTEGRITY. ANY DAMAGE SHALL BE REPAIRED IMMEDIATELY.

3. CONTRACTORS SHALL FOLLOW EM-385-1-1 AND NFPA 241, ALONG WITH

THE INSTALLATION’S FIRE REGULATIONS.

4. FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS AND

SMOKE PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE

PROTECTED OPENINGS OR PENETRATIONS SHALL BE EFFECTIVELY AND

PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING. SUCH

IDENTIFICATION SHALL:

a. BE LOCATED WITHIN 15 FEET OF THE END OF EACH WALL AND

AT INTERVALS NOT EXCEEDING 30 FEET MEASURED

HORIZONTALLY ALONG WITH WALL OR PARTITION.

b. INCLUDE LETTERING NOT LESS THAN 3 INCHES IN HEIGHT WITH

A MINIMUM 3/8-INCH STROKE IN A CONTRASTING COLOR

INCORPORATING THE SUGGESTED WORDING, “FIRE AND/OR

SMOKE BARRIER – PROTECT ALL OPENINGS,” OR OTHER

WORDING

GENERAL LIFE SAFETY NOTES:

LIFE SAFETY PLAN LEGEND

45'-0" TRAVEL DISTANCE

FEC

SEMI- RECESSED FIRE EXTINGUISHER CABINET -

EXISTING TO REMAIN.

WALL MOUNTED FIRE EXTINGUISHER -

EXISTING TO REMAIN.

FIRE EXTINGUISHER NOTE:

1. GC TO COORDINATE WITH HANDRAIL &

CRASH RAIL. PROVIDE STICK - ON

LETTERING AND DIRECTIONAL ARROWS TO

IDENTIFY THE CABINET OR EXTINGUISHERS

LOCATION.

EXIT SIGN-

SEE ELECT. DWGS.

EGRESS CLEAR WIDTH

CAPACITY/NO. OF OCCUPANTS

36" 100/100

FE

NEW RATED WALL LEGEND

1-HR RATED FIRE BARRIER

2-HR RATED FIRE BARRIER

1-HR FIRE RATED SMOKE BARRIER

SMOKE PARTITION

GC TO MODIFY EXISTING REMAIN WALLS/PARTITIONS

AS REQUIRED TO MEET FIRE RATED REQUIREMENT AS

SHOWN ON NEW FLOOR PLAN

OCCUPANT LOAD CALCULATION

MARK

69 PPL

OCCUPANT (USE) TYPE OCCUPANT LOAD

INSTITUTIONAL

(AMBULATORY)

52 PPLASSEMBLY

(ACCESSORY <10%)

TOTAL OCCUPANT LOAD 121 PPL

HORIZONTAL (EXIT WIDTH)

INCHES OF EGRESS REQUIRED (121 X 0.2)

INCHES OF EGRESS PROVIDED

VERTICAL (STAIR WIDTH)

INCHES OF EGRESS REQUIRED (121 X 0.3)

INCHES OF EGRESS PROVIDED

24"

165"

36"

86"

ELEVATOR ELEVATOR ELEVATOR

STAIR

NO 4

STAIR

NO 5

COMM

2C100

EC

2C101

CORRIDOR

C2-30

WAITING

2C102

PRIVATE

TREATMENT

2C104

CHECK-IN

DESK

2C103

CORRIDOR

C2-27

PHYSICAL

THERAPY

(PT)

2C111

STORAGE

2C105

DRIVER

THERAPY

2C106

KINESIO-THERAPY

(KT)

2C112

OCCUPATIONAL

THERAPY

(OT)

2C113

BREAKROOM

2C114 RECREATIONAL

THERAPY

2C120

STORAGE

2C121

JAN

2C119

MEN

(STAFF)

2C116

WOMEN

(STAFF)

2C115

COMM

2C117

EL

2C118

EQUIP.

STORAGE

2C110

MULTI-PURPOSE

ROOM

2C107

WOMEN

(PATIENT)

2C109

MEN

(PATIENT)

2C108

SCI CLINIC SUITE

NON SLEEPING PATIENT CARE

I-2 NEW AMBULATORY (NFPA CHAPTER 20)

AREA: 7,655 SF

121'

AREA: 6, 878 SF

OCC. CLASSIFICATION INSTITUTIONAL

(AMBULATORY)

OCC. LOAD FACTOR: 100 GROSS

TOTAL OCC. LOAD: 69

FEC

AREA: 343 SF

OCC. CLASSIFICATION ASSEMBLY

OCC. LOAD FACTOR: 15 NET

TOTAL OCC. LOAD: 23

AREA: 428 SF

OCC. CLASSIFICATION ASSEMBLY

OCC. LOAD FACTOR: 15 NET

TOTAL OCC. LOAD: 29

33" 165/61

STORAGE

2C111A

CHARTING

2C112A

CHARTING

2C113A

STORAGE

2C114A

OPEN COURTYARD

OPEN COURTYARD

FE

68" 340/61

AREA OF WORK

2ND FLOOR

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592Revisions: Date:

ORIGINAL DRAWING SIZE (30"X42")

B

IM

/1

V A

B ld g

S p in a l C o rd

I n ju ry

R e h a b A re a /1

V

A B ld g

A rc h

V

.r v t

/1

/2

:2

:2

P

M

G-102

LIFE SAFETY PLAN RENOVATE BUILDING 7 SPINAL

CORD INJURY (SCI) REHAB AREA

VA MEDICAL CENTER, MEMPHIS, TN

614-19-102

BLDG 7

4/22/2020 MWD QVL

SCALE: = 1'-0"

0 8 168

1/8"

N

SCALE: 1/8" = 1'-0"F1

PARTIAL 2ND LEVEL - LIFE SAFETY PLAN

KEYPLAN