General Drawings.pdf
PDF 5 MB Posted
- Solicitation number
- 36C24920B0003
About this file
This document package includes construction drawings and notes for a renovation project at the Memphis VA Medical Center.
The project involves renovating Building 7 to upgrade the Spinal Cord Injury Rehab Area. The work includes architectural, mechanical, electrical, plumbing and telecommunications upgrades. Detailed drawings show demolition plans, new construction plans, schedules and technical details. Notes specify infection control requirements and procedures to isolate the work area from occupied spaces. The documents provide specifications for constructing temporary barriers, maintaining negative air pressure, controlling dust and cleaning/decontamination.
The related federal contract opportunity is a pre-solicitation notice for solicitation number 36C24920B0003. The opportunity description states an Invitation for Bid will be issued under solicitation 36C24919B0001_1 to fulfill the pre-solicitation requirements. The contracting agency is the Department of Veterans Affairs Veterans Health Administration VISN 9. No other details are included regarding response dates, pricing terms, set-asides or other procurement requirements.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24920B0003 0007.docx | DOCX document | |
| 36C24920B0003 0006.docx | DOCX document | |
| 36C24920B0003 0005.docx | DOCX document | |
| 36C24920B0003 0004.docx | DOCX document | |
| Amendent_SPECS.pdf | ||
| Amend Rpt 0001.pdf | ||
| Amendment_DRAWINGS.pdf | ||
| 36C24920B0003 0003.docx | DOCX document | |
| RFI Form - Renovate Bldg. 7 SCI Rehab Area.docx | DOCX document | |
| Contractor EMR Certification Form 2020.docx | DOCX document | |
| 36C24920B0003 0002.docx | DOCX document | |
| 36C24920B0003 0001.docx | DOCX document | |
| Drawings 614-19-102.pdf | ||
| Electric-Telecom Drawings.pdf | ||
| 36C24920B0003_1.docx | DOCX document | |
| Addendum G-101.pdf | ||
| Architectural Drawings 2.pdf | ||
| Wage Determination - Shelby County.pdf | ||
| Specifications.pdf | ||
| Architectural Drawings 1.pdf | ||
| Mechanical Drawings.pdf | ||
| Fire-Plumbing Drawings.pdf |
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N
VICINITY MAP
SCALE: N.T.S.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592Revisions: Date:
ORIGINAL DRAWING SIZE (30"X42")
B
IM
/1
V A
B ld g
S p in a l C o rd
I n ju ry
R e h a b A re a /1
V
A B ld g
A rc h
V
.r v t
/1
/2
:2
:1
P
M
G-001
COVER SHEET RENOVATE BUILDING 7 SPINAL
CORD INJURY (SCI) REHAB AREA
VA MEDICAL CENTER, MEMPHIS, TN
614-19-102
BLDG 7
4/22/2020 MWD QVL
N
LOCATION MAP
SCALE: N.T.S.
PROJECT LOCATION:
1030 JEFFERSON AVENUE
MEMPHIS, TN 38104
PROJECT LOCATION:
1030 JEFFERSON AVENUE
MEMPHIS, TN 38104
RENOVATE BUILDING 7 SPINAL CORD INJURY (SCI) REHAB AREA
BUILDING 7, 2ND FLOOR
MEMPHIS VA MEDICAL CENTER
MEMPHIS, TN
BID DOCUMENTS
APRIL 22, 2020
Department of Veterans Affairs
PROJECT # 614-19-102
BID DOCUMENTS APPROVAL
NAME / TITLE DATE
NAME / TITLE DATE
NAME / TITLE DATE
SHEET INDEX
SHEET
NUMBER SHEET NAME
MECHANICAL
M-001 MECHANICAL GENERAL NOTES AND ABBREVIATIONS
M-002 MECHANICAL LEGENDS
MD101 MECHANICAL DEMOLITION PLANS
M-101 MECHANICAL NEW WORK PLANS
M-501 MECHANICAL DETAILS
M-502 MECHANICAL DETAILS
M-503 MECHANICAL DETAILS
M-601 MECHANICAL SCHEDULE AND CONTROL SEQUENCES
ELECTRICAL
E-001 ELECTRICAL GENERAL NOTES AND ABBREVIATIONS
E-002 ELECTRICAL LEGEND
ED101 ELECTRICAL DEMOLITION PLAN
E-101 LIGHTING AND PHOTOMETRIC PLAN
E-111 POWER PLAN
E-501 ELECTRICAL DETAILS
E-502 ELECTRICAL DETAILS
E-601 ELECTRICAL ONE-LINE DIAGRAM
E-602 LIGHT FIXTURE SCHEDULE
E-603 PANELBOARD SCHEDULES
TELECOMMUNICATIONS
T-001 TELECOM GENERAL NOTES, ABBREVIATIONS & LEGEND
TD101 TELECOMMUNICATIONS DEMOLITION PLAN
T-101 TELECOMMUNICATIONS PLAN
T-501 TELECOMMUNICATIONS DETAILS AND RISER DIAGRAMS
SHEET INDEX
SHEET
NUMBER SHEET NAME
GENERAL
G-001 COVER SHEET
G-002 INFECTION CONTROL PLAN AND RISK ASSESSMENT NOTES
G-101 BUILDING CODE SUMMARY & DEDUCTIVE ALTERNATES
G-102 LIFE SAFETY PLAN
ARCHITECTURAL
A-001 GENERAL NOTES, ABBREVIATIONS & SYMBOLS
AD101 PARTIAL 2ND LEVEL - DEMOLITION PLAN
AD102 EXISTING CONDITION PHOTOS
A-101 PARTIAL 2ND LEVEL - FLOOR PLAN
A-131 PARTIAL 2ND LEVEL - REFLECTED CEILING PLAN
A-171 PARTIAL 2ND LEVEL - FURNITURE / EQUIPMENT PLAN
A-371 PARTITION TYPES & DETAILS
A-401 ENLARGED PLANS
A-402 INTERIOR ELEVATIONS
A-501 MILLWORK DETAILS
A-571 MOUNTING HEIGHTS
A-572 DETAILS
A-601 DOOR SCHEDULE, DOOR/FRAME TYPES, AND DETAILS
A-631 FINISH SCHEDULE & DETAILS
A-701 SIGNAGE PLAN
FIRE PROTECTION
F-001 FIRE PROTECTION GENERAL NOTES AND SYMBOLS
F-101 FIRE PROTECTION & FIRE ALARM PLANS
PLUMBING
P-001 PLUMBING LEGEND, SYMBOLS, AND GENERAL NOTES
PD101 PLUMBING SUPPLY DEMOLITION PLANS
P-101 PLUMBING SUPPLY NEW WORK PLANS
P-102 PLUMBING SANITARY DEMOLITION AND NEW WORK PLANS
TYPE C
HIGH RISK
AREA OF WORK
2ND FLOOR
LEGEND
1 HOUR TEMPORARY PARTITION
WITH 3'-6" C-LABEL DOOR AND FRAME
CIRCULATION THAT MUST REMAIN
OPEN DURING CONSTRUCTION
EXISTING FINISHED FLOOR
BASE TO MATCH
ADJACENT SURFACE
(1) LAYER 5/8" TYPE "X" EACH SIDE, FINISH
& PAINT TO MATCH ADJACENT SURFACE
AT AREAS EXPOSED TO VIEW.
FOR EXTERIOR EXPOSURE ADD LAYER OF
5/8" EXTERIOR GYPSUM SHEATHING TO
EACH SIDE OF THE ASSEMBLY.
PROVIDE "L" BRACKET AT
CEILING TILE WITH
CONTINUOUS CAULKING
EXISTING CEILING
SYSTEM - MODIFY, PATCH,
& REPAIR AS REQUIRED
NON - CONSTRUCTION SIDE
EXISTING DUCTWORK,
CONDUITS, PIPING,
WIRING, ETC.
SMOKE SEAL ALL PENETRATIONS,
TYP. BOTH SIDES
FIRESTOP ALL VOIDS & PROVIDE
PREMOLDED NEOPRENE FLUTE
INSERTS; EXTEND GWB TIGHT TO DECK
CONTINUOUS FIRE CAULK,
SMOKE SEAL, TYP.,
INCLUDE INTERIOR SIDE
WHERE ACCESSIBLE
3 5/8" METAL STUDS @ 16"
O.C.
CONSTRUCTION SIDE
CONTINUOUS PERIMETER CAULKING
WHERE NEW CONSTRUCTION
OVERLAPS EXISTING WALL
EXISTING WALL TO REMAIN
CAREFULLY PATCH & REPAIR
EXISTING SPRAY ON FIREPROOFING
FOR FULL COVERAGE & CODE
COMPLIANT CONDITION, TYP.
EXISTING FLOOR OR ROOF DECK
CORRIDOR
C2-30
ELEVATOR ELEVATOR ELEVATOR
STAIR
NO 4
STAIR
NO 5
COMM
2C100
EC
2C101
LACK
2C103
STORAGE
2C106B
WHEEL CHAIR STORAGE
2C106A
STORAGE
2C106
PHYSICAL THERAPY
2C110
TOILET
2C-08
CORRIDOR
C2-27
STORAGE
2C110A
OFFICE
2C110B
COMM
2C117
EC
2C118
CORRIDOR
C2-29
CORRIDOR
C2-28
STORAGE
2C121
R.T. CLINIC
2C120DRIVER CLINIC
2C115
MEN TOILET
2C113
WOMEN TOILET
2C114
TOILET
2C116
JAN.
CLOSET
2C119
STORAGE /
BREAK ROOM
2C112A
MED REHAB
2C112
STORAGE
2C111B
O.T. CLINIC
2C111
2C111C
OFFICE
2C111A
PRIVATE TREATMENT
2C109
K.T. CLINIC
2C107
OFFICE
2C107A TOILET
2C104
JAN. CLOSET
2C102
OPEN COURTYARD
OPEN COURTYARD
PROVIDE
CONSTRUCTION
SIGNAGE ON
DOOR AND
STAIR
FOR EXTERIOR
TEMPORARY
CONSTRUCTION BARRIER
ASSEMBLY, PROVIDE
EXTERIOR GYPSUM
SHEATHING.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592Revisions: Date:
ORIGINAL DRAWING SIZE (30"X42")
B
IM
/1
V A
B ld g
S p in a l C o rd
I n ju ry
R e h a b A re a /1
V
A B ld g
A rc h
V
.r v t
/1
/2
:2
:1
P
M
G-002
INFECTION CONTROL PLAN AND
RISK ASSESSMENT NOTES
RENOVATE BUILDING 7 SPINAL
CORD INJURY (SCI) REHAB AREA
VA MEDICAL CENTER, MEMPHIS, TN
614-19-102
BLDG 7
4/22/2020 MWD QVL
1. G.C. IS TO FOLLOW ALL VA/ ICRA REGULATIONS IN PERFORMING ALL WORK.
2. G.C. IS TO COORDINATE WITH THE VA FOR OFF-HOURS ACCESS TO THE FLOORS ABOVE AND BELOW THE WORK NEEDED FOR
MECHANICAL TIE-INS. TEMPORARY ICRA BARRIERS ARE TO BE INSTALLED AROUND ALL WORK AREAS PRIOR TO CONSTRUCTION.
3. G.C. IS RESPONSIBLE FOR PERFORMING ALL WORK SHOWN IN THE CONTRACT DOCUMENTS IN THE WORK AREA DESIGNATED, AND
FOR PROVIDING ICRA AT EVERY WORK LOCATION.
4. FOLLOW ALL FIRE SAFETY CODES DURING CONSTRUCTION.
5. PAINT ALL HARDWALL ICRA BARRIERS ON THE PUBLIC SIDE OF BARRIERS.
6. G.C. TO PROVIDE THE VA 15 CALENDAR DAYS NOTICE OF ANY WORK TO BE PERFORMED OFF HOURS.
7. G.C. TO COORDINATE CONSTRUCTION WITH THE OWNER AND PROVIDE CRITICAL PATH TIMELINE/GANTT CHART FOR ENTRY OF
PROJECT WITH OWNER APPROVED MILESTONES.
8. PRIOR TO THE START OF DEMOLITION, ISOLATE ALL HVAC SYSTEMS IN AREAS WHERE WORK IS BEING PERFORMED. REFER TO
MECHANICAL DRAWINGS FOR ISOLATION AND/ OR REMOVAL. INSTALL ALL TEMPORARY PARTITIONS AND COORDINATE NEW CONSTRUCTION NECESSARY TO MEET ICRA STANDARDS. ESTABLISH NEGATIVE PRESSURE AT ICRA BARRIERS EQUIVALENT TO
0.001 WATER GAUGE. NEGATIVE PRESSURE SHALL BE ACCOMPLISHED BY HEPA EXHAUST FILTRATION UNITS MONITORED BY
DIGITAL RECORDING MANOMETER AND BALL IN TUBE INDICATOR VISIBLE IN PUBLIC AREAS.
9. PATCH AND REPAIR ANY EXISTING WALLS, FLOORS AND CEILINGS AFFECTED BY DEMOLITION AND/OR CONSTRUCTION.
10. CONTRACTOR TO UTILIZE HEPA FILTERED FANS TO CONTROL DUST AND ACHIEVE NEGATIVE PRESSURIZATION IN WORK SITE
THROUGHOUT PROJECT.
11. DO NOT REMOVE BARRIERS/ DUST PARTITIONS FROM WORK AREA UNTIL PROJECT PHASE IS COMPLETED AND PROJECT AREA IS
THOROUGHLY CLEANED AND APPROVED BY ENGINEERING SERVICES.
12. VACUUM WORK WITH HEPA FILTERED VACUUMS. WET MOP WITH DISINFECTANT AFTER VACUUMING - DAILY OR MORE FREQUENTLY
AS NEEDED TO MAINTAIN CLEANLINESS SUITABLE TO VAMC PERSONNEL AND MINIMIZE DUST GENERATION.
13. REMOVE BARRIER/ DUST PARTITION MATERIALS CAREFULLY TO MINIMIZE SPREADING OF DIRT AND DEBRIS ASSOCIATED WITH
CONSTRUCTION.
14. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED CONTAINERS. COVER TRANSPORT RECEPTACLES OR
CARTS, TAPE COVERING. ALL WASTE INSIDE CONSTRUCTION AREA TO BE CONTAINED AND TIGHTLY COVERED AT ALL TIMES.
15. CONTRACTOR SHALL MAINTAIN TEMPORARY LIFE SAFETY DEVICES WITHIN THE CONSTRUCTION SITE THROUGHOUT THE DURATION
OF THE PROJECT AS DIRECTED BY THE VA AND VA SAFETY OFFICE.
16. ROUTE DISCHARGE DUCT OF HEPA FILTER TO EXTERIOR OF BUILDING (THROUGH ADJACENT MECHANICAL ROOM) WHERE
NEGATIVE PRESSURE IS MAINTAINED FOR WORK SPACE. VAMC ICRA GROUP TO MONITOR AIR DURING CONSTRUCTION.
CONTRACTOR TO FOLLOW THE VAMC GUIDELINES AND PREVENTATIVE MEASURES PROVIDED BY THE VAMC ICRA GROUP.
CONTRACTOR TO PREPARE A PLAN OF PROTECTION MEASURES, STATUS REPORTS AND SUBMIT FOR REVIEW AND COMPLIANCE TO THE VAMC ICRA GROUP. ALL CONTRACTORS PERSONNEL INVOLVED ARE TO BE TRAINED ON INFECTIONS PREVENTION MEASURES ESTABLISHED BY THE VAMC. CONTRACTOR TO PROVIDE RECORDING MANOMETER THROUGHOUT CONSTRUCTION DURATION.
17. PROVIDE TEMPORARY 1 HR. RATED CONSTRUCTION BARRIER (ul465) PRIOR TO THE START OF DEMOLITION. CONSTRUCTION DUST PARTITIONS OF 3-5/8" METAL STUDS W/ 5/8" GWB. ON BOTH SIDES AND CONTINUOUS FIRESTOP SEALANT AS REQUIRED. PAINT BARRIER EXPOSED TO THE PUBLIC. ERECT PARTITION TIGHT TO THE FLOOR, SIDE WALLS AND THE UNDERSIDE OF THE
STRUCTURE. SEAL HOLES, PIPES, CONDUITS AND PENETRATIONS APPROPRIATELY.
18. PROVIDE STICKY MATS AND HEPA VACUUM FOR WORKERS CLOTHING. REMOVE AT COMPLETION OF WORK. MATS TO BE CHANGED
AS SOON AS VISIBLY SOILED.
19. ALL CONSTRUCTION ENTRANCES SHALL HAVE CYPHER LOCK WITH KEY OVERRIDE. COORDINATE WITH VA FOR LOCK CORE
INSTALLATION.
20. ADJACENT SPACES SHALL REMAIN OCCUPIED AND OPERATIONAL. MAINTAIN USER ACCESS AND MEANS OF EGRESS THROUGH THE EXISTING CORRIDORS. MAINTAIN NEGATIVE PRESSURE AND POSITIVE PRESSURE AS REQUIRED.
21. TEMPORARY SERVICE SHUT-OFFS AND HOURS OF OPERATION ARE TO BE COORDINATED WITH THE VA.
22. COORDINATE MOVEMENT OF CONSTRUCTION EQUIPMENT INTO AND WITHIN THE AREA OF WORK. COORDINATION SHALL BE
REVIEWED ON A DAILY BASIS WITH THE VA.
23. CONTRACTOR TO MEET WITH THE VA SECURITY PRIOR TO CONSTRUCTION.
24. CONTRACTOR SHALL FIELD VERIFY THE LOCATION OF EXISTING UTILITIES WITHIN THE LIMITS OF CONSTRUCTION. THE
CONTRACTOR SHALL EXERCISE CAUTION TO AVOID DAMAGE OF EXISTING UTILITIES.
25. GC TO VERIFY AND CONFIRM THAT ALL NEW AND EXISTING PENETRATIONS IN THE EXISTING RATED WALLS ARE FIRESTOPPED TO
MEET CODE.
ICRA GENERAL CONSTRUCTION NOTES:
1. G.C. TO PROVIDE TEMPORARY EXIT SIGNS & LIGHTS INSIDE OF CONSTRUCTION BARRIERS.
2. G.C. TO PROVIDE CONTINUOUS CAULKING & SMOKE SEALS AS REQ'D FOR COMPLETELY SEALED CONDITION SEPARATING
OPERATIONAL AREAS FROM CONSTRUCTION AREAS.
3. G.C. TO PROVIDE CONSTRUCTION SIGNAGE PER THE GENERAL REQUIREMENTS.
4. ALL SMOKE DETECTORS SHALL BE HEAT DETECTORS.
5. G.C. TO CONSTRUCT ALL CONSTRUCTION BARRIERS AT NIGHT AND PROVIDE PLASTIC IN PLACE FOR DUST CONTROL DURING
FABRICATION. PROVIDE FOR NEGATIVE AIR WITH HEPA FILTER TO OUTSIDE.
6. G.C. TO PROVIDE SELF CLOSING FIRE-RATED DOORS AND METAL FRAMES COMMENSURATE WITH PARTITION. IN ROOMS REQUIRING
ACCESS, G.C. TO COORDINATE EXACT QUANTITY REQUIRED. DOORS SHALL BE ABLE TO ACCEPT A VA SCSR LOCK BY KABA FOR KEY CARD ACCESS. G.C. TO PROVIDE LOCK AND KEY CARD ACCESS. PAINT DOOR AND FRAME TO MATCH ADJACENT WALL.
7. G.C. TO PROVIDE TEAR-OFF WALK OFF MATS IMMEDIATELY INSIDE OF EVERY CONSTRUCTION ENTRANCE DOOR. G.C. TO CHANGE WALK OFF MATS ON AVERAGE OF 8 TIMES PER DAY. G.C. TO COORDINATE EXACT QUANTITY REQUIRED.
8. G.C. TO PROVIDE FOOT PRE-WASH PRIOR TO WALKING OUT OF THE CONSTRUCTION AREA. G.C. TO COORDINATE EXACT QUANTITY
REQUIRED.
9. ALL EXTERIOR AREAS TO BE KEPT CLEAN FOR ANY DEBRIS BEING CARRIED OUT.
10. SEE TEMPORARY CONSTRUCTION BARRIER DETAIL F7/G-002.
TEMPORARY CONSTRUCTION BARRIER GENERAL NOTES:
SCALE: = 1'-0"
0 8 168
1/8"
N
KEYPLAN
SCALE: N.T.S.F7
TEMPORARY CONSTRUCTION BARRIER DETAIL
SCALE: 1/8" = 1'-0"F1
PARTIAL 2ND LEVEL - INFECTION CONTROL PLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592Revisions: Date:
ORIGINAL DRAWING SIZE (30"X42")
G-101
BUILDING CODE SUMMARY &
DEDUCTIVE ALTERNATES
RENOVATE BUILDING 7 SPINAL
CORD INJURY (SCI) REHAB AREA
VA MEDICAL CENTER, MEMPHIS, TN
614-19-102
BLDG 7
4/22/2020 MWD QVL
VHAMEMFONGL
Polygon
VHAMEMFONGL
Typewritten Text Revision 1 - Remove Schedule of Deductive Alternates
VHAMEMFONGL
Typewritten Text 11/9/2020
VHAMEMFONGL
Typewritten Text Revision 1
UP
2B119
C2-23
C2-24
2C122 2C123
C2-26
NO 4
C2-30
2C1012C100
C2-25
2D100B
2D100A
2D100 2D101
2B118
HOPTEL
CORRIDOR
MENS TOILET WOMENS TOILET
STAIR
CORRIDOR
ECCOMM
CORRIDOR
ELEVATOR ELEVATOR OFFICEELEVATOR
KITCHEN
PVA OFFICE MECH RM
REF.
1. DEVICES HAVE BEEN SHOWN; BUT THE CONTRACTOR SHALL ENSURE
THE INSTALLATION OF ALL LIFE SAFETY DEVICES INDICATED ON THE
ENGINEERING DRAWINGS.
2. CONTRACTOR SHALL FIELD VERIFY THE LOCATION OF ANY EXISTING
FIRE RATED WALLS. ANY WORK DONE AROUND EXISTING FIRE RATED
WALLS SHALL BE DONE WITH CARE SO AS NOT TO COMPROMISE THE
RATING'S INTEGRITY. ANY DAMAGE SHALL BE REPAIRED IMMEDIATELY.
3. CONTRACTORS SHALL FOLLOW EM-385-1-1 AND NFPA 241, ALONG WITH
THE INSTALLATION’S FIRE REGULATIONS.
4. FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS AND
SMOKE PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE
PROTECTED OPENINGS OR PENETRATIONS SHALL BE EFFECTIVELY AND
PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING. SUCH
IDENTIFICATION SHALL:
a. BE LOCATED WITHIN 15 FEET OF THE END OF EACH WALL AND
AT INTERVALS NOT EXCEEDING 30 FEET MEASURED
HORIZONTALLY ALONG WITH WALL OR PARTITION.
b. INCLUDE LETTERING NOT LESS THAN 3 INCHES IN HEIGHT WITH
A MINIMUM 3/8-INCH STROKE IN A CONTRASTING COLOR
INCORPORATING THE SUGGESTED WORDING, “FIRE AND/OR
SMOKE BARRIER – PROTECT ALL OPENINGS,” OR OTHER
WORDING
GENERAL LIFE SAFETY NOTES:
LIFE SAFETY PLAN LEGEND
45'-0" TRAVEL DISTANCE
FEC
SEMI- RECESSED FIRE EXTINGUISHER CABINET -
EXISTING TO REMAIN.
WALL MOUNTED FIRE EXTINGUISHER -
EXISTING TO REMAIN.
FIRE EXTINGUISHER NOTE:
1. GC TO COORDINATE WITH HANDRAIL &
CRASH RAIL. PROVIDE STICK - ON
LETTERING AND DIRECTIONAL ARROWS TO
IDENTIFY THE CABINET OR EXTINGUISHERS
LOCATION.
EXIT SIGN-
SEE ELECT. DWGS.
EGRESS CLEAR WIDTH
CAPACITY/NO. OF OCCUPANTS
36" 100/100
FE
NEW RATED WALL LEGEND
1-HR RATED FIRE BARRIER
2-HR RATED FIRE BARRIER
1-HR FIRE RATED SMOKE BARRIER
SMOKE PARTITION
GC TO MODIFY EXISTING REMAIN WALLS/PARTITIONS
AS REQUIRED TO MEET FIRE RATED REQUIREMENT AS
SHOWN ON NEW FLOOR PLAN
OCCUPANT LOAD CALCULATION
MARK
69 PPL
OCCUPANT (USE) TYPE OCCUPANT LOAD
INSTITUTIONAL
(AMBULATORY)
52 PPLASSEMBLY
(ACCESSORY <10%)
TOTAL OCCUPANT LOAD 121 PPL
HORIZONTAL (EXIT WIDTH)
INCHES OF EGRESS REQUIRED (121 X 0.2)
INCHES OF EGRESS PROVIDED
VERTICAL (STAIR WIDTH)
INCHES OF EGRESS REQUIRED (121 X 0.3)
INCHES OF EGRESS PROVIDED
24"
165"
36"
86"
ELEVATOR ELEVATOR ELEVATOR
STAIR
NO 4
STAIR
NO 5
COMM
2C100
EC
2C101
CORRIDOR
C2-30
WAITING
2C102
PRIVATE
TREATMENT
2C104
CHECK-IN
DESK
2C103
CORRIDOR
C2-27
PHYSICAL
THERAPY
(PT)
2C111
STORAGE
2C105
DRIVER
THERAPY
2C106
KINESIO-THERAPY
(KT)
2C112
OCCUPATIONAL
THERAPY
(OT)
2C113
BREAKROOM
2C114 RECREATIONAL
THERAPY
2C120
STORAGE
2C121
JAN
2C119
MEN
(STAFF)
2C116
WOMEN
(STAFF)
2C115
COMM
2C117
EL
2C118
EQUIP.
STORAGE
2C110
MULTI-PURPOSE
ROOM
2C107
WOMEN
(PATIENT)
2C109
MEN
(PATIENT)
2C108
SCI CLINIC SUITE
NON SLEEPING PATIENT CARE
I-2 NEW AMBULATORY (NFPA CHAPTER 20)
AREA: 7,655 SF
121'
AREA: 6, 878 SF
OCC. CLASSIFICATION INSTITUTIONAL
(AMBULATORY)
OCC. LOAD FACTOR: 100 GROSS
TOTAL OCC. LOAD: 69
FEC
AREA: 343 SF
OCC. CLASSIFICATION ASSEMBLY
OCC. LOAD FACTOR: 15 NET
TOTAL OCC. LOAD: 23
AREA: 428 SF
OCC. CLASSIFICATION ASSEMBLY
OCC. LOAD FACTOR: 15 NET
TOTAL OCC. LOAD: 29
33" 165/61
STORAGE
2C111A
CHARTING
2C112A
CHARTING
2C113A
STORAGE
2C114A
OPEN COURTYARD
OPEN COURTYARD
FE
68" 340/61
AREA OF WORK
2ND FLOOR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592Revisions: Date:
ORIGINAL DRAWING SIZE (30"X42")
B
IM
/1
V A
B ld g
S p in a l C o rd
I n ju ry
R e h a b A re a /1
V
A B ld g
A rc h
V
.r v t
/1
/2
:2
:2
P
M
G-102
LIFE SAFETY PLAN RENOVATE BUILDING 7 SPINAL
CORD INJURY (SCI) REHAB AREA
VA MEDICAL CENTER, MEMPHIS, TN
614-19-102
BLDG 7
4/22/2020 MWD QVL
SCALE: = 1'-0"
0 8 168
1/8"
N
SCALE: 1/8" = 1'-0"F1
PARTIAL 2ND LEVEL - LIFE SAFETY PLAN
KEYPLAN