Fire-Plumbing Drawings.pdf
PDF 2 MB Posted
- Solicitation number
- 36C24920B0003
About this file
This solicitation is for a construction project to renovate the spinal cord injury rehabilitation area in Building 7 at the VA Medical Center in Memphis, Tennessee. The scope of work includes demolishing existing fire detection, fire alarm, and occupant notification systems; installing new sprinklers, plumbing, and fire alarm devices; and modifying walls to meet fire rating requirements. The estimated value is over $2 million. The solicitation number is 36C24920B0003 and was issued by the Department of Veterans Affairs Veterans Health Administration VISN 9. The pre-solicitation notice states that solicitation 36C24919B0001_1 will be posted to fulfill this requirement. Construction is to be completed by qualified firms with experience in medical facility renovations and compliance with VA construction standards.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24920B0003 0007.docx | DOCX document | |
| 36C24920B0003 0006.docx | DOCX document | |
| 36C24920B0003 0005.docx | DOCX document | |
| 36C24920B0003 0004.docx | DOCX document | |
| Amendent_SPECS.pdf | ||
| Amend Rpt 0001.pdf | ||
| Amendment_DRAWINGS.pdf | ||
| 36C24920B0003 0003.docx | DOCX document | |
| RFI Form - Renovate Bldg. 7 SCI Rehab Area.docx | DOCX document | |
| Contractor EMR Certification Form 2020.docx | DOCX document | |
| 36C24920B0003 0002.docx | DOCX document | |
| 36C24920B0003 0001.docx | DOCX document | |
| Drawings 614-19-102.pdf | ||
| Electric-Telecom Drawings.pdf | ||
| 36C24920B0003_1.docx | DOCX document | |
| Addendum G-101.pdf | ||
| Architectural Drawings 2.pdf | ||
| Wage Determination - Shelby County.pdf | ||
| Specifications.pdf | ||
| Architectural Drawings 1.pdf | ||
| Mechanical Drawings.pdf | ||
| General Drawings.pdf |
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DESIGN AND INSTALLATION SHALL BE IN ACCORDANCE WITH NFPA 13, "STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS", 2019 EDITION; NFPA 70, "NATIONAL ELECTRICAL CODE", 2017 EDITION; NFPA 72, "NATIONAL FIRE ALARM AND SIGNALING CODE", 2019 EDITION; NFPA 241, "SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS" 2019 EDITION; AND VA FIRE PROTECTION DESIGN MANUAL (VAFPDM), SEVENTH EDITION, DECEMBER 2015.
THE INTENT, AND EXTENT OF THE FIRE PROTECTION SYSTEM DESIGN IS PERFORMANCE-BASED IN NATURE, AND IS DIAGRAMMATIC ONLY. IT IS NOT INTENDED TO SHOW EVERY PIPE, FITTING, DEVICE, APPLIANCE, COMPONENT, ETC. FIRE ALARM FLOOR PLANS AND RISER DIAGRAM ARE DIAGRAMMATIC AND NOT INTENDED TO SHOW EACH AND EVERY COMPONENT, DEVICE, APPLIANCE, ETC. CONDUIT PATHWAYS AND INTERCONNECTIONS SHALL BE DETERMINED BY THE BUILDING FEATURES, NFPA 70, NFPA 72, SYSTEM MANUFACTURER REQUIREMENTS AND RECOMMENDATIONS.
CONTRACTOR SHALL VISIT JOB SITE PRIOR TO BID WITH THE PROJECT DOCUMENTS AND SPECIFICATIONS TO BECOME FAMILIAR WITH THE SITE AND SCOPE OF WORK. NOTIFY ENGINEER OF RECORD WITH ANY DISCREPANCIES OUTSIDE THIS DESIGN INTENT. ANY CHANGE ORDER REQUEST AS A RESULT OF COORDINATION BETWEEN TRADES SHALL BE DENIED.
ADHERE TO AND OBTAIN ALL PERMITS, LICENSES, FOR BOTH LOCAL AND FEDERAL GOVERNMENT REQUIREMENTS.
DO NOT SCALE PLANS FOR THE PURPOSE OF ESTABLISHING DIMENSIONS. FIELD DIMENSION GOVERN.
FIRE STOP ALL PENETRATIONS OF SMOKE/FIRE PARTITIONS. FIRE STOPPING SHALL BE OF UL LISTED ASSEMBLY.
1.
2.
3.
4.
5.
6.
GENERAL NOTES
CONTRACTOR SHALL SUBMIT COMPLETE SHOP DRAWINGS WITH HYDRAULIC CALCULATIONS, MATERIAL SPECIFICATION BROCHURE TO CONTRACTING OFFICER'S TECHNICAL REPRESENTATIVE FOR REVIEW PRIOR TO
COMMENCING FABRICATION AND INSTALLATION.
FIRE SPRINKLER CONTRACTOR SHALL INSTALL SYSTEM PIPING AND COMPONENTS IN A WORKMANSHIP LIKE MANNER. CHANGES IN INSTALLATION AS A RESULT OF POOR CRAFTSMANSHIP SHALL BE AS DIRECTED BY CONTRACTING OFFICER'S TECHNICAL REPRESENTATIVE AND SHALL BE AT NO ADDITIONAL COST TO THE OWNER.
ANY ADDITIONAL OFFSETS OR FITTINGS REQUIRED FOR PROPER INSTALLATION, COORDINATION WITH OTHER TRADES, AND/OR TO MAINTAIN PROPER CLEARANCES SHALL BE PROVIDED FOR A COMPLETE AND WORKING
SYSTEM.
ALL CONTROL VALVES ON THE FIRE PROTECTION SYSTEM SHALL BE ELECTRICALLY SUPERVISED. COORDINATE THE TYPE AND EXACT LOCATION OF FLOW AND SUPERVISORY SWITCHES BETWEEN FIRE SPRINKLER AND FIRE ALARM CONTRACTORS. FIRE ALARM SYSTEM, SUPERVISION AND WIRING SHALL BE PROVIDED UNDER THE FIRE
ALARM DIVISION.
SPRINKLER SYSTEM(S) SHALL BE DESIGNED FOR A MAXIMUM WORKING PRESSURE OF 175 PSI IN ACCORDANCE
WITH NFPA 13.
SPRINKLER SYSTEM(S) SHALL BE HYDROSTATICALLY TESTED IN ACCORDANCE WITH NFPA 13 (BEFORE AND AFTER
SCOPE OF WORK IS PERFORMED).
ALL VALVES SHALL HAVE A PERMANENTLY AFFIXED SIGN PER NFPA 13 INDICATING ITS FUNCTION AND SECURED
TO THE VALVE WITH SUITABLE CHAIN.
HANGER MATERIAL, SPACING AND METHOD OF ATTACHMENT SHALL BE IN ACCORDANCE WITH NFPA 13 AND
MANUFACTURER'S REQUIREMENTS.
MAINTAIN A MINIMUM OF 18" CLEARANCE BELOW SPRINKLER DEFLECTOR(S) AND ANY PERMANENT OR
TEMPORARY OBSTRUCTION(S) PER NFPA 13.
ONLY LISTED OR APPROVED DEVICES AND MATERIALS AS SPECIFIED IN NFPA 13 SHALL BE INSTALLED
THROUGHOUT THE SYSTEM.
ALL SPRINKLERS SHALL BE INSTALLED ACCORDING TO THEIR LISTED SPACING AND OBSTRUCTION
REQUIREMENTS.
CONTRACTOR SHALL COORDINATE INSTALLATION OF ALL FIRE PROTECTION DEVICES WITH OTHER TRADES AND
EXISTING CONDITIONS.
PROVIDE SYSTEM(S) WITH FLUSHING CONNECTIONS PER NFPA 13.
SPRINKLER SYSTEM PIPING IS REQUIRED TO BE PROVIDED WITH SEISMIC BRACING AS THE SITE IS A CRITICAL FACILITY RISK CATEGORY IV WITH A SEISMIC DESIGN CATEGORY C. PROVIDE EARTHQUAKE PROTECTION IN
ACCORDANCE WITH NFPA 13 REQUIREMENTS.
AT LEAST SIX (6) SPARE SPRINKLERS OF EACH TYPE, TEMPERATURE, AND ORIFICE SIZE USED IN THE SYSTEM INCLUDING A SPECIAL WRENCH FOR EACH FIRE SPRINKLER SHALL BE KEPT IN A CABINET WHERE AMBIENT
TEMPERATURE WILL AT NO TIME EXCEED 100°F PER NFPA 13.
PIPE, FITTING, SPRINKLERS, HANGERS, AND COMPONENTS INSTALLED IN CORROSIVE ATMOSPHERES (I.E COMPARTMENTS CONTAINING CORROSIVE MATERIALS AND/OR FUMES, OR EXTERIOR WEATHER CONDITIONS, ETC.) SUCH AS DRAIN PIPES, HANGER ALL-THREAD ROD, ETC., SHALL BE AN APPROVED CORROSION RESISTANT
MATERIAL.
SPRINKLER PIPING 2-IN. AND LESS MUST BE A MINIMUM OF SCH. 40 BLACK STEEL PIPE. PIPING LARGER THAN 2-IN.
MUST BE A MINIMUM OF SCH. 10 BLACK STEEL PIPE. ANY EXISTING CPVC PIPE SHALL BE REMOVED AND REPLACED WITH SCH. 40 BLACK STEEL PIPE WITH CAST IRON FITTINGS PER VAFPDM SECTION 6.1, B, 4.
PIPING WITH A WALL THICKNESS LESS THAN SCH. 40 MUST NOT BE THREADED.
SPRINKLER PROTECTION IS NOT REQUIRED IN THE NONCOMBUSTIBLE CONCEALED SPACE ABOVE THE CEILING
PER NFPA 13.
REFER TO WET-PIPE SPRINKLER SYSTEM SPECIFICATION 21 13 13 FOR ADDITIONAL REQUIREMENTS AND
INFORMATION.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
FIRE SUPPRESSION NOTES
CONTRACTOR SHALL SUBMIT COMPLETE BATTERY CALCULATIONS, VOLTAGE DROP CALCULATIONS, MATERIAL DATA SHEETS, AND SHOP DRAWINGS TO OWNER'S TECHNICAL REPRESENTATIVE FOR REVIEW PRIOR TO COMMENCING FABRICATION AND INSTALLATION. FAILURE TO COMPLY IS AT THE RISK OF THE CONTRACTOR.
REFER TO PLAN DRAWINGS AND PROJECT DOCUMENTS FOR APPROXIMATE FIRE ALARM SYSTEM QUANTITIES AND LOCATIONS, NOT ALL SITE CONDITIONS ARE SHOWN. FIRE ALARM CONTRACTOR SHALL VISIT JOB SITE WITH ALL PROJECT DOCUMENTS PRIOR TO BID TO BECOME FAMILIAR WITH PROJECT DESIGN, INSTALLATION, TESTING AND COMMISSIONING REQUIREMENTS, SITE CONDITIONS FOR NEW SYSTEM INSTALLATION, TO PROVIDE A COMPREHENSIVE AND COMPLETE BID, CODE COMPLIANT SYSTEM DESIGN, INSTALLATION, TESTING, COMMISSIONING AND APPROVAL REQUIREMENTS.
FIRE ALARM SIGNALS AND EMERGENCY COMMUNICATIONS SHALL TAKE PRECEDENCE OVER ALL OTHER
SIGNALS, SUCH AS BUT NOT LIMITED TO PUBLIC ADDRESS SYSTEMS.
ALL NOTIFICATION APPLIANCES CIRCUITS (NAC) SHALL WIRING CLASS SHALL MATCH EXISTING.
ALL SIGNALING LINE CIRCUITS (SLC) SHALL WIRING CLASS SHALL MATCH EXISTING.
ALL INDICATING DEVICE CIRCUITS SHALL WIRING CLASS SHALL MATCH EXISTING.
THE INSTALLATION OF WIRING BETWEEN THE FACP AND RELAY MODULES OR APPLIANCES SHALL WIRING
CLASS SHALL MATCH EXISTING.
ALL CONDUCTORS FOR THE FIRE ALARM SYSTEM SHALL BE INSTALLED IN EMT CONDUIT AND IN ACCORDANCE WITH NFPA 70. THE CONDUCTORS SHALL NOT BE INSTALLED WITH CONDUCTORS OF LIGHTING OR POWER SYSTEMS. THE SUM OF THE CROSS-AREA OF INDIVIDUAL CONDUCTORS SHALL NOT EXCEED 40% OF THE INTERIOR CROSS SECTION OF THE CONDUIT. ALL FIRE ALARM SYSTEM CONDUIT SHALL NOT BE LESS THAN 3/4".
WALL MOUNTED FIRE ALARM DEVICES IN UNFINISHED AREAS MAY BE SURFACED MOUNTED, THE CONDUIT MAY
BE INSTALLED EXPOSED ON WALLS AND ON CEILINGS.
IN FINISHED AREAS, WALL MOUNTED DEVICES SHALL BE FLUSH MOUNTED. THE CONDUIT SHALL BE INSTALLED
CONCEALED IN THE WALLS AND CEILINGS UNLESS REFERENCED AS CEILING MOUNTED.
ELECTRICAL CONTRACTORS SHALL COORDINATE WITH FIRE ALARM VENDOR FOR SYSTEM OPERATING
INSTRUCTIONS AND WIRING DIAGRAMS.
CONTRACTOR SHALL PROVIDE PATHWAY SURVIVABILITY OF LEVEL 1 IN ACCORDANCE WITH NFPA 72.
FIRE ALARM FLOOR PLANS AND RISER DIAGRAM ARE DIAGRAMMATIC AND NOT INTENDED TO SHOW EACH AND EVERY COMPONENT, DEVICE, APPLIANCE, ETC. CONDUIT PATHWAYS AND INTERCONNECTIONS SHALL BE DETERMINED BY THE BUILDING FEATURES, NFPA 70, NFPA 72, SYSTEM MANUFACTURER REQUIREMENTS AND
RECOMMENDATIONS.
FIRE ALARM SYSTEM IS TO BE ADDED TO AN EXISTING ADDRESSABLE FIRE ALARM CONTROL UNIT THAT IS PART OF A COMPREHENSIVE BUILDING. NEW FIRE ALARM COMPONENTS ADDED AS PART OF THIS SCOPE OF WORK SHALL SHALL MEET THE REQUIREMENTS OF THE BUILDING SYSTEM, BUT AT A MINIMUM THE FUNCTIONS
IDENTIFIED IN THE MATRIX.
CONTRACTOR SHALL ADD THE INDICATED FIRE ALARM DEVICES TO THE THE EXISTING SYSTEM. THE NEW DEVICES SHALL OPERATE PER THE EXISTING SEQUENCE OF OPERATIONS AND THE SCOPE OF WORK SHALL
NOT MODIFIY THE EXISTING SEQUENCE OF OPERATIONS.
CONTRACTOR SHALL PROVIDE NOTATION ON THE INSTALLATION DRAWINGS OR A SEPARATE LETTER ON COMPANY LETTERHEAD THAT THE SYSTEM SIGNAL TRANSMISSION, FUNCTIONS AND SEQUENCING HAS BEEN
COORDINATED WITH THE BUILDING COMPREHENSIVE FIRE ALARM SYSTEM.
THE FIRE ALARM SYSTEM SHALL NOT BE COMBINED WITH ANY OTHER BUILDING SYSTEM, SUCH AS BUT NOT
LIMITED TO, AUTOMATION, ENERGY, SECURITY, ETC.
REFER TO FIRE ALARM SYSTEM SPECIFICATION 28 31 00 FOR ADDITIONAL REQUIREMENTS AND INFORMATION.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
FIRE ALARM NOTES
FIRE ALARM
CONTROL
PANEL
(FACP)
BATTERIES
120 VAC
BREAKER POWER
PANEL
DACT
1ST FLOOR
2ND FLOOR
CIRCUITS
2ND FLOOR
NAC
EXISTING SIGNALING LINE CIRCUIT (SLC)F
NEW NOTIFICATION APPLIANCE CIRCUIT (NAC)
NEW SPEAKER CIRCUIT
EVAC
BREAKER POWER
PANEL
120 VAC
FACP FIRE SAFETY
A C
T U
A T
E A
U D
IO
V
IS
U
A L
S U
P E
R V
IS
O
R Y
I N
D
IC
A T
IO
N
D E
V
IC
E
A C
T U
A T
E A
U D
IO
V
IS
U
A L A
L A
R M
IN
D
IC
A T
O R
D E
V
IC
E S
A C
T U
A T
E A
U D
IO
V
IS
U
C O
M M
O N
T R
O U
B L E
I N
D
IC
A T
O R
R E
L E
A S
E D
O O
R H
O L D
S
U N
L O
C K
E X
IT
S
A B C D E F G H I J K L
F1 MANUAL PULL STATION IN ZONE OF ALARM
FIRE ALARMS
X
SYSTEM INPUTS T
R
A N
S M
IT
A
L A
R M
S
IG
N A
L T
E
C E
IV
IN
G S
T A
T
IO
N
T R
A N
S M
IT
S
U P
E R
V
IS
O R
Y S
IG
N
R E
C E
IV
IN
G S
T A
T
IO
N
T R
A N
S M
IT
T
R O
U B
L E
S
IG
N A
L
C E
IV
IN
G S
T A
T
IO
N
A L E
R T
S T
R O
B E
T H
R O
U G
H O
U T
T H
Z
N E
C
L E
A R
F
IR
E A
L A
R M
E V
A C
U A
T
IO
N M
E S
S A
G
R
O U
G H
O U
T Z
O N
CENTRAL
STATION
EVAC
SIGNALS
SYSTEM OUTPUTS
X X X
R E
C O
R D
E V
E N
T S
I N
S Y
S T
M
IS
T
O R
Y
X X
C L O
S E
D A
M P
E R
S
XX
EXISTING DEVICES AND OPERATIONS TO BE MAINTAINED. NEW DEVICES SHALL OPERATE THE SAME AS THE EXISTING
DEVICES ARE CURRENTLY PROGRAMMED.
F2 SMOKE DETECTOR X X X XX X XX
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592Revisions: Date:
ORIGINAL SHEET SIZE: 30" X 42"
B
IM
/1
V
A B ld g
S p in a l C o rd
I n ju ry
R e h a b A re a
/1
V A
B ld g
M E
P
F P
V
.r v t
/1
/2
:1
:0
P
M
F-001
FIRE PROTECTION GENERAL
NOTES AND SYMBOLS
RENOVATE BUILDING 7 SPINAL
CORD INJURY (SCI) REHAB AREA
VA MEDICAL CENTER, MEMPHIS, TN
614-19-102
BLDG 7
04/22/2020 BTH NDS
SCALE: N.T.S.D7
FIRE ALARM RISER DIAGRAM
SCALE: N.T.S.F7
FIRE ALARM SEQUENCE OF OPERATIONS
4/17/20
F
F
THE DESIGN, LAYOUT, INSTALLATION AND SETTING OF THE
FIRE SPRINKLER SYSTEM SHALL BE IN ACCORDANCE WITH
CONTRACT DOCUMENTS, SPECIFICATIONS, VA FIRE
PROTECTION MANUAL, LATEST EDITIONS OF THE NATIONALLY
RECOGNIZED FIRE AND LIFE SAFETY CODES, SUCH AS BUT
NOT LIMITED TO, NFPA 13, NFPA 70, NFPA 72, NFPA 101 AND
NFPA 241.
FIRE PROTECTION ALTERATIONS SHALL COMPLY WITH THE
VA MASTER CONSTRUCTION SPECIFICATIONS.
THE EXISTING FIRE SPRINKLER LAYOUT SHALL BE REVISED
TO ACCOMMODATE THE REVISED WALL/ROOM LAYOUT
INSIDE THE PROJECT SCOPE AREA. ALL SPRINKLERS SHALL
BE NEW, QUICK RESPONSE, STANDARD COVERAGE, UNLESS
NOTED OTHERWISE. SPRINKLERS SHALL BE FM APPROVED
AS QUICK RESPONSE.
LOCATION OF SPRINKLERS SHALL BE COORDINATED WITH
CEILING FEATURES AND OBSTRUCTIONS, SUCH AS BUT NOT
LIMITED TO ELEVATION, MATERIAL OF CONSTRUCTION,
LIGHTS, GRILLS, DIFFUSERS, CURTAIN TRACK SYSTEM(S),
LIFT SYSTEM AND OTHER FEATURES AND/OR OBSTRUCTION
OF SIMILAR NATURE.
A MINIMUM OF 18-INCHES OF CLEARANCE SHALL BE
MAINTAINED BETWEEN THE SPRINKLER DEFLECTOR AND ANY
STORAGE MATERIALS AND/OR EQUIPMENT IN ACCORDANCE
WITH NFPA 13.
ALL THROUGH PENETRATIONS OF THE FIRE RESISTANCE
RATED (FRR) BUILDING FEATURES (WALLS, FLOORS,
CEILINGS, ETC.) SHALL BE FIRE STOPPED WITH A UL LISTED
FRR MATERIAL/ ASSEMBLY EQUAL TO OR GREATER THAN THE
FRR OF THE PENETRATED BUILDING FEATURE.
THE USE OF CPVC PIPE AND FITTING IS PROHIBITED.
MINIMIZE OR AVOID DISRUPTIONS TO THE FIRE SPRINKLER
SYSTEM. WHEN DISRUPTIONS ARE ANTICIPATED, ENSURE
THAT PROCEDURES ARE INCORPORATED TO MAINTAIN
EQUIVALENT LEVELS OF FIRE PROTECTION AND PROVIDE
FORMAL NOTIFICATION TO THE FACILITY WHILE SYSTEMS
ARE DOWN.
COORDINATE SPRINKLER LOCATIONS WITH SURFACE
MOUNTED LIGHTING.
PROVIDE HIGH TEMPERATURE RATED SPRINKLERS WHERE
REQUIRED PER NFPA 13.
PROVIDE SEISMIC BRACING ON ALL NEW PIPING PER NFPA
13.
PROVIDE EQUIPMENT AND COMPONENTS FOR ALL FIRE
SPRINKLER SYSTEM PIPING, SPRINKLERS, COUPLINGS,
FITTINGS, VALVES, ETC. THAT COMPRISES A COMPLETE FIRE
SPRINKLER SYSTEM THAT IS IN COMPLIANCE WITH VA
REQUIREMENTS.
DEMOLISH EXISTING FIRE DETECTION, FIRE ALARM, AND
OCCUPANT NOTIFICATION SYSTEM IN ITS ENTIRETY INSIDE
THE INDICATED PROJECT SCOPE AREA. CONTRACTOR SHALL
REPAIR IN KIND ANY DAMAGES THE BUILDING SUSTAINS
DURING DEMOLITION.
CONTRACTOR SHALL DISPOSE OF ALL DEMOLISHED
COMPONENTS AND MATERIALS IN ACCORDANCE WITH ALL
LOCAL AND FEDERAL REGULATIONS.
EXISTING FIRE ALARM AND OCCUPANT NOTIFICATION
SYSTEM IS TO REMAIN IN OPERATION AT ALL TIMES TO THE
FULLEST EXTENT POSSIBLE, UNTIL NEW FIRE ALARM
DEVICES ARE INSTALLED AND TESTED. PLANNED SYSTEM
IMPAIRMENTS SHALL COMPLY WITH NFPA 72 REQUIREMENTS.
A FIRE WATCH WILL BE PROVIDED FOR SYSTEM
IMPAIRMENTS AT THE DISCRETION OF THE FIRE MARSHAL.
FIRE ALARM FLOOR PLANS AND RISER DIAGRAM ARE
DIAGRAMMATIC AND NOT INTENDED TO SHOW EACH AND
EVERY COMPONENT, DEVICE, APPLIANCE, ETC. CONDUIT
PATHWAYS AND INTERCONNECTIONS SHALL BE DETERMINED
BY THE BUILDING FEATURES, NFPA 70, NFPA 72, SYSTEM
MANUFACTURER REQUIREMENTS AND RECOMMENDATIONS.
FIRE ALARM NOTIFICATION APPLIANCES SHALL BE 15
CANDELA UNLESS OTHERWISE NOTED.
CONTRACTOR SHALL PROVIDE THE NECESSARY QUANTITY
OF POWER SUPPLY PANELS FOR CONTROL AND OPERATION
OF ALL NOTIFICATION APPLIANCES. COORDINATE PANELS
WITH THE ELECTRICAL CONTRACTOR FOR REQUIRED POWER
REQUIREMENTS.
CONTRACTOR SHALL PROVIDE ALL NECESSARY AND
REQUIRED SYSTEM PROGRAMMING TO MEET THE DESIGN
INTENT AND CODE COMPLIANCE.
GENERAL NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
LEGEND
LIGHT HAZARD
0.10 GPM/SQ.FT OVER 1500 SQ.FT
100 GPM HOSE ALLOWANCE
LH
EXISTING SPRINKLER
PROTECTION TO REMAIN
EX
ORDINARY HAZARD
0.20 GPM/SQ.FT OVER 1500 SQ.FT
250 GPM HOSE ALLOWANCE
OH
MANUAL FIRE ALARM PULL STATION, MOUNT
42" - 48" AFF TO TOP OF HANDLE
ETR = EXISTING TO REMAIN
F
NEW FIRE ALARM CLEAR VISUAL STROBE. WALL
MOUNT AT 80" AFF TO BOTTOM OF LENS OR 6"
BELOW CEILING, WHICHEVER IS LOWER AND NOT
GREATER THAN 96".
NEW FIRE ALARM CLEAR VISUAL STROBE AND
HORN. WALL MOUNT AT 80" AFF TO BOTTOM OF
LENS OR 6" BELOW CEILING, WHICHEVER IS
LOWER AND NOT GREATER THAN 96".
ETR
NEW RECESSED SPRINKLER
NEW UPRIGHT SPRINKLER
EXISTING FLOOR CONTROL ZONE VALVE TO
REMAIN
EXISTING EQUIPMENT, PATHWAYS, ETC. TO REMAIN.
NEW EQUIPMENT, PATHWAYS, ETC. TO BE ADDED.
SMOKE DETECTOR-PHOTOELECTRICS
NOTIFICATION APPLIANCE POWER EXTENDER PANEL.
COORDINATE WITH EXISTING EQUIPMENT IN THE ROOM.
NAC
EX
EX EX
EX
EX EX
OHEQUIP. STORAGE
2C110
CORRIDOR
C2-27
OCCUPATIONAL
THERAPY (OT)
2C113
KINESIO-THERAPY
(KT)
2C112
WOMEN (PATIENT)
2C109
MULTI-PURPOSE
ROOM
2C107
MEN (PATIENT)
2C108
DRIVER THERAPY
2C106
STORAGE
2C105
PRIVATE
TREATMENT
2C104
WAITING
2C102
CORRIDOR
C2-27
CHECK-IN DESK
2C103
PHYSICAL THERAPY
(PT)
2C111
COMM
2C117
EL
2C118
CORRIDOR
C2-28
BREAKROOM
2C114
RECREATIONAL
THERAPY
2C120
WOMEN (STAFF)
2C115
MEN (STAFF)
2C116
JAN
2C119
STORAGE
2C121
OH
OH
LH
LH
LH
LH
LH
LH
LH
LH
LH
LH
LH
OH
LH
LH
LH
LH
STORAGE
2C111A
STORAGE
2C114A
OH
OH
LH
LH
LH
EX
EX
EX
EX EX
EQUIP. STORAGE
2C110
CORRIDOR
C2-27
OCCUPATIONAL
THERAPY (OT)
2C113
KINESIO-THERAPY
(KT)
2C112
WOMEN (PATIENT)
2C109
MULTI-PURPOSE
ROOM
2C107
MEN (PATIENT)
2C108
DRIVER THERAPY
2C106
STORAGE
2C105
PRIVATE
TREATMENT
2C104
WAITING
2C102
CORRIDOR
C2-27
CHECK-IN DESK
2C103
PHYSICAL THERAPY
(PT)
2C111
COMM
2C117
EL
2C118
CORRIDOR
C2-28
BREAKROOM
2C114
RECREATIONAL
THERAPY
2C120
WOMEN (STAFF)
2C115
MEN (STAFF)
2C116
JAN
2C119
STORAGE
2C121
ETR
STORAGE
2C114A
STORAGE
2C111A
S
NAC
AREA OF WORK
2ND FLOOR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592Revisions: Date:
ORIGINAL SHEET SIZE: 30" X 42"
B
IM
/1
V
A B ld g
S p in a l C o rd
I n ju ry
R e h a b A re a
/1
V A
B ld g
M E
P
F P
V
.r v t
/1
/2
:1
:0
P
M
F-101
FIRE PROTECTION & FIRE ALARM
PLANS
RENOVATE BUILDING 7 SPINAL
CORD INJURY (SCI) REHAB AREA
VA MEDICAL CENTER, MEMPHIS, TN
614-19-102
BLDG 7
04/22/2020 BTH NDS
SCALE: 1/8" = 1'-0"F1
FIRE PROTECTION PLAN
SCALE: 1/8" = 1'-0"F5
FIRE ALARM PLAN
SCALE: = 1'-0"
0 8 168
1/8"
N
KEYPLAN
4/17/20
PLUMBING LEGEND
KEY NOTES
DIRECTION OF FLOW
PIPE TURNED DOWN
PIPE TURNED UP
RISE OR DROP
BRANCH BOTTOM CONNECTION
TEE OUTLET UP
TEE OUTLET DOWN
CAP ON END OF PIPE
SANITARY WASTE (NEW) - ABOVE FLOOR OR GRADE
SANITARY WASTE (NEW) - BELOW FLOOR OR GRADE
VENT PIPING (NEW)
POTABLE / DOMESTIC COLD WATER PIPING (NEW)
POTABLE / DOMESTIC HOT WATER SUPPLY PIPING (NEW)
THERMOMETER
TEMPERATURE & PRESSURE RELIEF VALVE
FLOW MEASURING / BALANCING / SHUT-OFF VALVE
BALL VALVE
CHECK VALVE
GATE VALVE
STRAINER
UNION
HOSE BIBB
FLOOR DRAIN
PLUMBING ABBREVIATIONSPLUMBING GENERAL NOTES
1. PLUMBING WORK SHALL BE IN ACCORDANCE WITH THE IBC, IPC, AND VA DESIGN STANDARDS.
2. SLOPES AND INVERT ELEVATIONS SHALL BE ESTABLISHED BEFORE ANY PIPE IS INSTALLED IN ORDER
TO MAINTAIN PROPER SLOPES. ANY DISCREPANCIES SHALL BE REPORTED TO CONTRACTING
OFFICER'S REPRESENTATIVE. ALL PIPING SHALL BE LOCATED AND DETERMINED WHEN TO BE
INSTALLED TO AVOID CONFLICT WITH OTHER TRADES.
3. PIPING SHALL BE CONCEALED UNLESS OTHERWISE NOTED.
4. KEEP ALL BURIED PIPING CLEAR OF FOOTINGS. COORDINATE WITH STRUCTURAL.
5. ALL WALL CLEANOUTS SHALL BE PROVIDED WITH WALL COVERS AND MOUNTED IN UNOBTRUSIVE
LOCATIONS WHILE MAINTAINING ACCESSIBILITY. ALL FLOOR CLEANOUTS SHOWN SHALL BE SET FLUSH
WITH FLOOR AREAS OR FINISHED GRADE.
6. COORDINATE LOCATION OF PIPING AND DRAINS WITH ALL MECHANICAL AND ELECTRICAL EQUIPMENT.
NO PIPING SHALL BE INSTALLED ABOVE ELECTRICAL, COMMUNICATIONS, OR DATA EQUIPMENT OR
PANELS. COMPLY WITH ARCHITECTURAL PLANS FOR EXACT LOCATION OF PLUMBING FIXTURES,
COMPLIANCE TO ADA CLEARANCES, AND FINISHES.
7. PROVIDE REQUIRED WATER, WASTE, AND VENT PIPING, FITTINGS, AND INSULATION, AND MAKE FINAL CONNECTIONS TO EQUIPMENT. THESE PLANS ARE SCHEMATIC AND DIAGRAMMATIC ONLY. THEY DO
NOT SHOW ALL REQUIRED BENDS, OFFSETS, VALVES, AND MISCELLANEOUS FITTINGS FOR A
COMPLETE INSTALLATION. ALL PIPING, EQUIPMENT, AND CONNECTIONS SHALL BE INSTALLED IN
ACCORDANCE WITH SPECIFICATIONS, LOCAL CODES AND ORDINANCES, AND MANUFACTURER'S
INSTRUCTIONS.
8. SANITARY SEWER PIPING SHALL BE INSTALLED TO PROVIDE A MINIMUM SLOPE OF 1%. WASTE PIPING
3" AND SMALLER SHALL BE INSTALLED TO PROVIDE A MINIMUM SLOPE OF 2%.
9. DO NOT SCALE DRAWINGS. REFER TO ARCHITECTURE DRAWINGS FOR EXACT DIMENSIONS, FIXTURE
LOCATIONS, ROOM NAMES, AND NUMBERS.
10. EXTENSION OF EQUIPMENT DRAINS TO FLOOR DRAINS, FLOOR SINKS, AND OPEN SITE DRAINS SHALL
BE PROVIDED BY EQUIPMENT CONTRACTOR.
11. WHERE POSSIBLE, INSTALL SHUT-OFF VALVES AND EQUIPMENT REQUIRING MAINTENANCE, CLEANING AND ADJUSTMENT ABOVE ACCESSIBLE CEILINGS OR IN SERVICE AREAS SUCH AS JANITOR'S CLOSETS.
IN OTHER LOCATIONS, PROVIDE ACCESS PANELS IN INCONSPICUOUS LOCATIONS WITH FINISH TO
MATCH ARCHITECTURAL.
12. ALL HOSE BIBBS, WALL HYDRANTS, AND VALVES WITH THREADED HOSE CONNECTIONS SHALL BE
EQUIPPED WITH VACUUM BREAKER.
13. WHERE CONNECTING TO A UTILITY OR SERVICE, VERIFY LOCATION, SIZES, MATERIALS, FLUID BEING HANDLED, AND INVERTS OF ALL EXISTING UTILITIES AND CONFIRM THAT NEW PIPES BEING ROUTED TO EXISTING UTILITIES CAN BE INSTALLED CONFORMING TO CODE AND AS SHOWN. NOTIFY CONTRACTING
OFFICER OF ANY CONFLICTS OR DISCREPANCIES PRIOR TO PURCHASING ANY MATERIALS OR
PERFORMING ANY WORK OR EXTENSION OF CONNECTION, WITH THE EXCEPTION OF EXCAVATION OR
OTHER WORK TO PROVIDE ACCESS TO THE CONCEALED UTILITY.
14. PROVIDE INSULATION, PIPE IDENTIFICATION, AND OTHER REQUIREMENTS AS LISTED IN
SPECIFICATIONS.
15. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS AND ELEVATIONS OF ALL PLUMBING
FIXTURES.
16. ALL PIPING ABOVE GRADE SHALL BE PROPERLY SUPPORTED FROM THE BUILDING STRUCTURE AND
SHALL NOT REST ON CEILING TILES OR BE SUPPORTED FROM CEILING TILES.
17. WATER PIPING ROUTED ABOVE CEILINGS AND IN EXTERIOR WALLS SHALL BE ROUTED ON HEATED SIDE
(UNDERSIDE) OF CEILING INSULATION AND HEATED SIDE (INSIDE) OF WALL INSULATION.
18. TOPS OF ALL FLOOR DRAINS AND CLEANOUTS SHALL BE SET FLUSH WITH FINISHED FLOOR, UNLESS
NOTED OTHERWISE.
19. LOCATE ALL SECTIONAL OR MAIN CONTROL VALVES WITHIN 1'-0" FROM ACCESS PANELS, CEILING
TILES, OR OTHER POINT OF ACCESS.
20. PROVIDE WATER HAMMER ARRESTORS SIZED PER PDI SPECIFICATIONS ON ALL DOMESTIC WATER LINES SERVING FLUSH VALVE FIXTURES, WASHING MACHINES SUPPLIES, PRV STATIONS, AND OTHER
INSTALLATIONS WITH QUICK CLOSING VALVES.
21. PROVIDE A MANUFACTURED EXPANSION DEVICE OR FABRICATED EXPANSION LOOP ON ALL PIPING
SYSTEMS CROSSING BUILDING EXPANSION JOINTS.
22. COORDINATE ELECTRICAL CHARACTERISTICS AND REQUIREMENTS OF ALL PLUMBING EQUIPMENT WITH THE ELECTRICAL DRAWINGS AND THE ELECTRICAL CONTRACTOR, AND FURNISH EQUIPMENT
WIRED FOR THE VOLTAGES SHOWN THEREIN.
23. ALL PLUMBING EQUIPMENT AND SYSTEMS SHALL BE GUARANTEED FOR A MINIMUM PERIOD OF ONE
YEAR AFTER OWNER'S FINAL ACCEPTANCE.
24. ALL PIPE PENETRATIONS OF FIRE AND/OR SMOKE-RATED ASSEMBLIES SHALL BE FIRE-STOPPED AS REQUIRED TO RESTORE ASSEMBLY TO ORIGINAL INTEGRITY. FIRE BARRIER PRODUCTS SHALL BE AS MANUFACTURED BY 3M COMPANY, CP25 CAULK, CS195 COMPOSITE PANEL, FS195 WRAP/STRIP, OR PSS 7900 SERIES SYSTEMS AS RECOMMENDED BY MANUFACTURER FOR PARTICULAR APPLICATION, OR
EQUIVALENT SYSTEM AS APPROVED BY LOCAL CODE OFFICIALS.
25. ALL WATER CLOSET FLUSH VALVE LEVERS SHALL BE LOCATED ON THE APPROACH SIDE OF THE
WATER CLOSET.
26. ALL GAS REGULATORS REQUIRING VENTS SHALL BE VENTED TO THE EXTERIOR PER THE
INTERNATIONAL GAS CODE REQUIREMENTS. VENT TERMINALS SHALL BE A MINIMUM OF 10'-0" FROM
ANY AIR INTAKE OR SOURCE OF IGNITION.
27. ALL VENTS THROUGH ROOF SHALL BE LOCATED A MINIMUM OF 10'-0" FROM ANY OUTSIDE AIR INTAKE.
28. ALL COLD WATER, HOT WATER, AND DRAIN PIPING AT HANDICAPPED FIXTURES SHALL BE INSULATED
WITH HANDI-LAV GUARD MODELS 102 AND 105 (OR APPROVED EQUAL) INSULATION KITS.
29. NOT ALL PLUMBING ABBREVIATIONS SHOWN WILL BE USED FOR THIS PROJECT.
TRAP PRIMER
FLOOR CLEANOUT
WALL CLEANOUT
WATER HAMMER ARRESTOR
PLAN ELEV
TP
FCOFCO
WCO WCO
BRANCH TOP CONNECTION
POTABLE / DOMESTIC HOT WATER RETURN PIPING (NEW)
S
W
SANITARY RISER DIAGRAM DESIGNATION
RISER DIAGRAM NUMBER
DOMESTIC WATER RISER DIAGRAM DESIGNATION
RISER DIAGRAM NUMBER
A/C ABOVE CEILING
ADA AMERICANS WITH DISABILITIES ACT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
ARCH ARCHITECTURE, ARCHITECTURAL
BFP BACKFLOW PREVENTER
B/F BELOW FLOOR
B/G BELOW GRADE
BLDG BUILDING
BV BALL VALVE
CA COMPRESSED AIR
CD CONDENSATE DRAIN
CONT. CONTINUATION
CO CLEANOUT
CV CHECK VALVE
CONTR CONTRACTOR
CW COLD WATER (POTABLE / DOMESTIC)
DEG. DEGREES
DF DRINKING FOUNTAIN
DHWR DOMESTIC HOT WATER RETURN
DN DOWN
DSN DOWNSPOUT NOZZLE
DWGS DRAWINGS
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EMEW EMERGENCY EYEWASH
EMSH EMERGENCY SHOWER
ESEW EMERGENCY SHOWER / EYEWASH
EXST, (E) EXISTING
FCO FLOOR CLEANOUT
FD FLOOR DRAIN
GC GENERAL CONTRACTOR
GPF GALLONS PER FLUSH
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GV GATE VALVE
GWH GAS WATER HEATER
HB HOSE BIBB
H/C HANDICAP
HW HOT WATER (POTABLE / DOMESTIC)
I.E. INVERT ELEVATION
IBC INTERNATIONAL BUILDING CODE
IFGC INTERNATIONAL FUEL GAS CODE
IMB ICE MAKER BOX
IPC INTERNATIONAL PLUMBING CODE
IW INDIRECT WASTE
[kg] KILOGRAMS
KW KILOWATT
L LAUNDRY
LP LIQUID PETROLEUM
LV LAVATORY
[m] METERS [mm] MILLIMETERS
MFG MANUFACTURER
MS MOP SINK
NFWH NON-FREEZE WALL HYDRANT
NG NATURAL GAS
NIC NOT IN CONTRACT
ORD OVERFLOW ROOF DRAIN
P, PLBG PLUMBING
PDI PLUMBING DRAINAGE INSTITUTE
PSI POUNDS PER SQUARE INCH
RD ROOF DRAIN
RL RAIN LEADER
RPZ REDUCED PRESSURE ZONE
SAN, S SANITARY PIPING
SANS SANITARY SEWER
SH SHOWER
SK SINK
SOV SHUT-OFF VALVE
STR STRAINER
SS STAINLESS STEEL
TMV THERMOSTATIC MIXING VALVE
T&P TEMPERATURE AND PRESSURE
RELIEF VALVE
TP TRAP PRIMER
TYP TYPICAL
UR URINAL
U/G UNDERGROUND
U/SAN UNDERGROUND SANITARY
V VENT PIPING
VTR VENT THROUGH ROOF
W WASTE PIPING
WB CLOTHES WASHER OUTLET BOX
WC WATER CLOSET
WCO WALL CLEANOUT
WH WATER HEATER
WHA WATER HAMMER ARRESTOR
W/O WITHOUT
W/ WITH
YCO YARD CLEANOUT
CONNECT TO EXISTING
DISCONNECT FROM EXISTING
PLUMBING FIXTURE SCHEDULES
TAG FIXTURE TYPE COLD WATER PIPE
SIZE (IN)
HOT WATER PIPE
SIZE (IN)
WASTE PIPE SIZE
(IN)
VENT PIPE SIZE
(IN)
FLOW
RESTRICTION
DESCRIPTION
EWC-1 ELECTRIC WATER COOLER 1/2 -- 2 2 -- PROVIDE WITH DUAL HEAD AND BOTTLE FILLING STATION, 8 GPH CHILLING CAPACITY, ADA COMPLIANCE. PROVIDE ACCESSORY APRON.
LAV-1 LAVATORY, WALL MOUNT 1/2 1/2 1-1/4 2 0.5 GPM PROVIDE WITH DRAIN COVER AND MANUAL OPERATED FAUCET.
MS-1 MOP SINK 3/4 3/4 2 2 -- PROVIDE FAUCET WITH PAIL HOOK. PROVIDE 24"x24" STAINLESS STEEL PANELS ON ADJACENT CORNER.
SK-1 SINK, COUNTER MOUNT 3/4 3/4 1-1/2 2 1.5 GPM PROVIDE WITH DRAIN COVER AND MANUAL OPERATED FAUCET.
SK-2 TWO COMPARTMENT SINK 3/4 3/4 1-1/2 2 1.5 GPM PROVIDE WITH HAND SPRAY FAUCET.
WC-1 WATER CLOSET, WALL MOUNT,
ACCESSIBLE
1 -- 3 2 1.28 GPF PROVIDE ELONGATED BOWL AND MANUAL OPERATED FLUSHOMETER.
CB-1 COLD WATER CONNECTION BOX 1/2 -- -- -- -- PROVIDE WITH FIRE-RATED RECESSED CABINET. STEEL BRAIDED HOSE CONNECTION TO WATER / ICE DISPENSER.
MANUFACTURER MODEL NO.
BASIS OF DESIGN
SK-3 SINK, COUNTER MOUNT 3/4 3/4 1-1/2 2 1.5 GPM PROVIDE WITH DRAIN COVER AND MANUAL OPERATED FAUCET.
OATEY
ELKAY
KOHLER
FIAT
ELKAY
ELKAY
ELKAY
KOHLER
38490
LZSTL8WSSK
K-2007
SB3624
PSR2521
GECR3321
BPSH15C
K-4325
NEW RATED WALL LEGEND
1-HR RATED FIRE BARRIER
2-HR RATED FIRE BARRIER
1-HR FIRE RATED SMOKE BARRIER
SMOKE PARTITION
GC TO MODIFY EXISTING REMAIN WALLS/PARTITIONS
AS REQUIRED TO MEET FIRE RATED REQUIREMENT AS
SHOWN ON NEW FLOOR PLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592Revisions: Date:
ORIGINAL SHEET SIZE: 30" X 42"
B
IM
/1
V
A B ld g
S p in a l C o rd
I n ju ry
R e h a b A re a
/1
V A
B ld g
M E
P
F P
V
.r v t
/1
/2
:1
:1
A
M
P-001
PLUMBING LEGEND, SYMBOLS,
AND GENERAL NOTES
RENOVATE BUILDING 7 SPINAL
CORD INJURY (SCI) REHAB AREA
VA MEDICAL CENTER, MEMPHIS, TN
614-19-102
BLDG 7
04/22/2020 DKH MTR
NOTES:
1. EXISTING EQUIPMENT IS SHOWN WITH THIN, HALFTONE LINEWORK.
2. DEMOLISHED EQUIPMENT IS SHOWN WITH BOLD LINEWORK,
DASHED, AND HATCHED.
3. NEW OR RELOCATED EQUIPMENT IS SHOWN WITH BOLD LINEWORK.
4. BELOW IS AN EXAMPLE OF EACH:
EXISTING EQUIPMENT
EQUIPMENT TO BE DEMOLISHED
NEW OR RELOCATED EQUIPMENT
R.T. CLINIC
2C120
STORAGE
2C121
JAN. CLOSET
2C119TOILET
2C116
DRIVER CLINIC
2C115
CORRIDOR
C2-29
COMM
2C117
EC
2C118
STORAGE
2C110A
OFFICE
2C110B
PHYSICAL THERAPY
2C110
TOILET
2C-08
MED REHAB
2C112
STORAGE/BREAK ROOM
2C112A
STORAGE
2C111B
O.T. CLINIC
2C111
OFFICE
2C111A
PRIVATE TREATMENT
2C109
K.T. CLINIC
2C107 CORRIDOR
C2-27
WHEEL CHAIR STORAGE
2C106A
OFFICE
2C107A
JAN. CLOSET
2C102TOILET
2C104
LACK
2C103
STORAGE
2C106B
MEN TOILET
2C113
WOMEN TOILET
2C114
STORAGE
2C106
(E) 3/4" DHWR
(E) 1 1/2" HW
(E) 2 1/2" CW
(E) 2" CW
(E) 2" HW
2" VTR, ETR
2" VTR, ETR
2" VTR, ETR
4" VTR, ETR
4" VTR, ETR
4" VTR, ETR
2" VTR, ETR
2" VTR, ETR
2" VTR, ETR
(E) 3" CW
(E) 3/4" DHWR
(E) 2" HW(E) 1/2" DHWR
(E) 1" HW
(E) 2" CW
(E) 3/4" HW
(E) 2"
(E) 1" HW
(E) 2 1/2" CW
(E) 1/2" HW
(E) 1/2" CW
(E) 2 1/2" CW
(E) 1" HW
(E) 3" CW
(E) 2" HW
(E) 3/4" DHWR
(E) 1/2" DHWR
(E) 2 1/2" CW
(E) 2" HW
(E) 3/4" DHWR
(E) 2" CW
(E) 1" HW
(E) 2 1/2" CW
(E) 2" HW
(E) 2 1/2" CW
(E) 1 1/2" HW
(E) 2" CW
(E) 1" HW
(E) 1/2"
(E) 1/2"
ELEVATOR ELEVATOR ELEVATOR
STAIR
NO 4
STAIR
NO 5
COMM
2C100
EC
2C101
CORRIDOR
C2-30
CORRIDOR
C2-27
SINK, ETR
2" VTR, ETR
KEYNOTES:
AREA OF WORK
2ND FLOOR
R.T. CLINIC
2C120
STORAGE
2C121
JAN. CLOSET
2C119
TOILET
2C116
DRIVER CLINIC
2C115
CORRIDOR
C2-29
COMM
2C117
EC
2C118
STORAGE
2C110A
OFFICE
2C110B
PHYSICAL THERAPY
2C110
TOILET
2C-08
MED REHAB
2C112
STORAGE/BREAK ROOM
2C112A
STORAGE
2C111B
O.T. CLINIC
2C111
OFFICE
2C111A
PRIVATE TREATMENT
2C109
K.T. CLINIC
2C107 CORRIDOR
C2-28
WHEEL CHAIR STORAGE
2C106A
OFFICE
2C107A
JAN. CLOSET
2C102
TOILET
2C104
LACK
2C103
STORAGE
2C106B
MEN TOILET
2C113
WOMEN TOILET
2C114
STORAGE
2C106
ELEVATOR ELEVATOR ELEVATOR
STAIR
NO 4
STAIR
NO 5
COMM
2C100
EC
2C101
CORRIDOR
C2-30
SINK, ETR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592Revisions: Date:
ORIGINAL SHEET SIZE: 30" X 42"
B
IM
/1
V
A B ld g
S p in a l C o rd
I n ju ry
R e h a b A re a
/1
V A
B ld g
M E
P
F P
V
.r v t
/1
/2
:1
:3
A
M
PD101
PLUMBING SUPPLY DEMOLITION
PLANS
RENOVATE BUILDING 7 SPINAL
CORD INJURY (SCI) REHAB AREA
VA MEDICAL CENTER, MEMPHIS, TN
614-19-102
BLDG 7
04/22/2020 DKH MTR
GENERAL NOTES:
1. REFER TO P-001 FOR PLUMBING GENERAL NOTES,
ABBREVIATIONS, AND LEGENDS.
SCALE: 1/8" = 1'-0"F1
PLUMBING DEMOLITION - UNDER SECOND FLOOR
N
SCALE: = 1'-0"
0 8 168
1/8"
KEYPLAN
SCALE: 1/8" = 1'-0"F5
PLUMBING SUPPLY DEMOLITION - ABOVE SECOND FLOOR
1. DOMESTIC WATER PIPING TO EQUIPMENT ON FIRST FLOOR.
2. 2" VENT UP TO SECOND FLOOR. SEE F1/PD102 FOR
CONTINUATION.
3. DEMOLISH PIPING BACK TO TEE AND CAP.
4. DEMOLISH PLUMBING FIXTURE AND ASSOCIATED
APPURTENANCES. DEMOLISH AND CAP SANITARY PIPING AT
NEAREST MAIN.
5. DEMOLISH PLUMBING FIXTURE AND CAP PIPING FOR FUTURE
WORK.
6. DEMOLISH DOMESTIC PIPING FROM BELOW.
7. PIPING CONTINUES INTO AREA NOT IN PROJECT SCOPE.
NOTE:
PLUMBING PIPING SHOWN ON THIS VIEW IS BELOW SECOND FLOOR AND ABOVE
FIRST FLOOR CEILING. SECOND FLOOR WALLS ARE OVERLAYED FOR CLARITY.
PHYSICAL
THERAPY
(PT)
2C111
KINESIO-THERAPY
(KT)
2C112
OCCUPATIONAL
THERAPY
(OT)
2C113
MULTI-PURPOSE
ROOM
2C107
EQUIP.
STORAGE
2C110
CORRIDOR
C2-28
BREAKROOM
2C114
RECREATIONAL
THERAPY
2C120
STORAGE
2C114A
WOMEN
(STAFF)
2C115
MEN
(STAFF)
2C116
JAN
2C119
STORAGE
2C121
COMM
2C117
EL
2C118
CHARTING
2C113A
CHARTING
2C112A
WOMEN
(PATIENT)
2C109
MEN
(PATIENT)
2C108
DRIVER
THERAPY
2C106
STORAGE
2C105
PRIVATE
TREATMENT
2C104
CHECK-IN
DESK
2C103
WAITING
2C102
STORAGE
2C111A
CORRIDOR
C2-27
SK-2
MS-1
WC-1
SK-1
SK-3
SK-3
WC-1
LAV-1
LAV-1
WC-1
WC-1
LAV-1
LAV-1
ELEVATOR ELEVATOR ELEVATOR
STAIR
NO 4
STAIR
NO 5
COMM
2C100
EC
2C101
CORRIDOR
C2-30
SINK, ETR
EWC-1
CB-1
SK-1
KEYNOTES:
AREA OF WORK
2ND FLOOR
RECREATIONAL
THERAPY
2C120
STORAGE
2C121
JAN
2C119
MEN
(STAFF)
2C116
STORAGE
2C114A
WOMEN
(STAFF)
2C115
BREAKROOM
2C114
CORRIDOR
C2-28
COMM
2C117
EL
2C118
EQUIP.
STORAGE
2C110
OCCUPATIONAL
THERAPY
(OT)
2C113
KINESIO-THERAPY
(KT)
2C112
CHARTING
2C113A
CHARTING
2C112A
MULTI-PURPOSE
ROOM
2C107
WOMEN
(PATIENT)
2C109
MEN
(PATIENT)
2C108
PHYSICAL
THERAPY
(PT)
2C111
CORRIDOR
C2-27
CHECK-IN
DESK
2C103
WAITING
2C102
PRIVATE
TREATMENT
2C104
STORAGE
2C105
DRIVER
THERAPY
2C106
STORAGE
2C111A
SK-2
MS-1
WC-1
SK-1
SK-1
SK-3
SK-3
WC-1
LAV-1
LAV-1
WC-1
WC-1
LAV-1
LAV-1
(E) 1" HW
(E) 1 1/2" CW
(E) 3/4" DHWR
(E) 1 1/2" HW
(E) 2 1/2" CW
(E) 2" HW
(E) 2" CW
(E) 2 1/2" CW
(E) 2" HW
(E) 3/4" DHWR
(E) 2" HW
(E) 2 1/2" CW
(E) 2" CW
(E) 1" HW
(E) 3" CW
(E) 2" HW
(E) 3/4" DHWR
(E) 1" HW
(E) 2" CW
ELEVATOR ELEVATOR ELEVATOR
STAIR
NO 4
STAIR
NO 5
COMM
2C100
EC
2C101
CORRIDOR
C2-30
SINK, ETR
EWC-1
CB-1
2" CW
3/4" HW
3/4" HW
3/4" CW
3/4" HW
3/4" CW
3/4" CW 3/4" HW
3/4" CW
3/4" HW
1/2" HW
1 1/2" CW
3/4" CW
3/4" HW
3/4" CW
3/4" HW
NEW RATED WALL LEGEND
1-HR RATED FIRE BARRIER
2-HR RATED FIRE BARRIER
1-HR FIRE RATED SMOKE BARRIER
SMOKE PARTITION
GC TO MODIFY EXISTING REMAIN WALLS/PARTITIONS
AS REQUIRED TO MEET FIRE RATED REQUIREMENT AS
SHOWN ON NEW FLOOR PLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592Revisions: Date:
ORIGINAL SHEET SIZE: 30" X 42"
B
IM
/1
V
A B ld g
S p in a l C o rd
I n ju ry
R e h a b A re a
/1
V A
B ld g
M E
P
F P
V
.r v t
/1
/2
:1
:2
A
M
P-101
PLUMBING SUPPLY NEW WORK
PLANS
RENOVATE BUILDING 7 SPINAL
CORD INJURY (SCI) REHAB AREA
VA MEDICAL CENTER, MEMPHIS, TN
614-19-102
BLDG 7
04/22/2020 DKH MTR
SCALE: 1/8" = 1'-0"F5
PLUMBING SUPPLY NEW WORK
GENERAL NOTES:
1. REFER TO P-001 FOR PLUMBING GENERAL NOTES,
ABBREVIATIONS, AND LEGENDS.
2. REFER G-101 FOR DEDUCTIVE ALTERNATE SCHEDULE.
N
SCALE: = 1'-0"
0 8 168
1/8"
KEYPLAN
SCALE: 1/8" = 1'-0"F1
PLUMBING NEW WORK - UNDER SECOND FLOOR
NOTE:
PLUMBING PIPING SHOWN ON THIS VIEW IS BELOW SECOND FLOOR AND ABOVE
FIRST FLOOR CEILING. SECOND FLOOR WALLS ARE OVERLAYED FOR CLARITY.
1. DOMESTIC PIPE UP FROM FLOOR BELOW. EXTEND PIPING AND
CONNECT TO ASSOCIATED PLUMBING FIXTURE(S).
2. COORDINATE COLD WATER CONNECTION BOX, CB-1, LOCATION
WITH FINAL WATER / ICE DISPENSER LOCATION. 1/2" COLD
WATER SUPPLY TO WATER / ICE DISPENSER. MAKE FINAL
CONNECTION WITH STEEL BRAIDED HOSE.
3. PIPING CONTINUES INTO AREA NOT IN PROJECT SCOPE.
4. CONNECT NEW PLUMBING FIXTURE TO EXISTING DOMESTIC
COLD WATER SUPPLY.
5. CONNECT NEW PLUMBING FIXTURE TO EXISTING DOMESTIC
COLD AND HOT WATER SUPPLY.
KEYNOTES:
PHYSICAL
THERAPY
(PT)
2C111
STORAGE
2C111A
CORRIDOR
C2-27
CHECK-IN
DESK
2C103
WAITING
2C102 PRIVATE
TREATMENT
2C104
STORAGE
2C105
DRIVER
THERAPY
2C106
MULTI-PURPOSE
ROOM
2C107
WOMEN
(PATIENT)
2C109
MEN
(PATIENT)
2C108
KINESIO-THERAPY
(KT)
2C112
OCCUPATIONAL
THERAPY
(OT)
2C113
CHARTING
2C112A
CHARTING
2C113A
EQUIP.
STORAGE
2C110
CORRIDOR
C2-28
BREAKROOM
2C114 WOMEN
(STAFF)
2C115
STORAGE
2C114A
MEN
(STAFF)
2C116
JAN
2C119
STORAGE
2C121
RECREATIONAL
THERAPY
2C120
EL
2C118
COMM
2C117
(E) 6" ST
(E) 10" ST
(E) 4" ST
(E) 6" ST
(E) 4" ST
2" S
2" S
(E) 4" S
(E) 2" S
(E) 4" S
(E) 4" S
(E) 4" S
(E) 2" S
3" S
3" S
1 1/4" S
3" S
(E) 4" S
(E) 2" S
1 1/4" S
4" S
1 1/4" S
1 1/2" S
1 1/2" S
SK-2
MS-1WC-1
SK-1
SK-1
SK-3
SK-3
WC-1
LAV-1
LAV-1
WC-1
WC-1
LAV-1
LAV-1
ELEVATOR ELEVATOR ELEVATOR
STAIR
NO 4
STAIR
NO 5
COMM
2C100
EC
2C101
CORRIDOR
C2-30
SINK, ETR
2" V
2" V
2" V
2" V
2" V
2" V
2" VTR
2" V
3" S
2" V
3" V
3" VTR
2" V
3" S
EWC-1
2" S
CB-1
AREA OF WORK
2ND FLOOR
NEW RATED WALL LEGEND
1-HR RATED FIRE BARRIER
2-HR RATED FIRE BARRIER
1-HR FIRE RATED SMOKE BARRIER
SMOKE PARTITION
GC TO MODIFY EXISTING REMAIN WALLS/PARTITIONS
AS REQUIRED TO MEET FIRE RATED REQUIREMENT AS
SHOWN ON NEW FLOOR PLAN
(E) 4" ST
(E) 8" ST
(E) 10" ST
(E) 10" ST
(E) 6" ST
(E) 4" ST
(E) 6" ST
(E) 6" ST
(E) 10" ST
(E) 6" ST
(E) 2" V
(E) 2" V
(AND CAP)
R.T. CLINIC
2C120
STORAGE
2C121
JAN. CLOSET
2C119
TOILET
2C116
DRIVER CLINIC
2C115
CORRIDOR
C2-29
COMM
2C117
EC
2C118
STORAGE
2C110A
OFFICE
2C110B
PHYSICAL THERAPY
2C110
TOILET
2C-08
MED REHAB
2C112
STORAGE/BREAK ROOM
2C112A
STORAGE
2C111B
O.T. CLINIC
2C111
OFFICE
2C111A
PRIVATE TREATMENT
2C109
K.T. CLINIC
2C107
CORRIDOR
C2-27
WHEEL CHAIR STORAGE
2C106A
OFFICE
2C107A
JAN. CLOSET
2C102
TOILET
2C104
LACK
2C103
STORAGE
2C106B
MEN TOILET
2C113
WOMEN TOILET
2C114
STORAGE
2C106
(TYP)
(TYP 3)
ELEVATOR ELEVATOR ELEVATOR
STAIR
NO 4
STAIR
NO 5
COMM
2C100
EC
2C101
CORRIDOR
C2-30
CORRIDOR
C2-28
SINK, ETR
4" VTR, ETR
2" V UP
13 13
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Designed
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592
POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740
Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592Revisions: Date:
ORIGINAL SHEET SIZE: 30" X 42"
B
IM
/1
V
A B ld g
S p in a l C o rd
I n ju ry
R e h a b A re a
/1
V A
B ld g
M E
P
F P
V
.r v t
/1
/2
:1
:2
A
M
P-102
PLUMBING SANITARY DEMOLITION
AND NEW WORK PLANS
RENOVATE BUILDING 7 SPINAL
CORD INJURY (SCI) REHAB AREA
VA MEDICAL CENTER, MEMPHIS, TN
614-19-102
BLDG 7
04/22/2020 DKH MTR
GENERAL NOTES:
1. REFER TO P-001 FOR PLUMBING GENERAL NOTES,
ABBREVIATIONS, AND LEGENDS.
2. REFER G-101 FOR DEDUCTIVE ALTERNATE SCHEDULE.
3. DEMOLISH ALL SANITARY AND VENT PIPING UP TO INDICATED
PENETRATIONS DOWN TO FIRST FLOOR UNLESS NOTED.
SCALE: 1/8" = 1'-0"F5
PLUMBING SANITARY NEW WORK - BELOW SECOND FLOOR
N
SCALE: = 1'-0"
0 8 168
1/8"
KEYPLAN
1. EXISTING TO REMAIN 6" STORM DRAINAGE DOWN FROM ROOF
DRAIN ABOVE TO FIRST FLOOR.
2. EXISTING TO REMAIN 8" STORM DRAINAGE DOWN FROM ROOF
DRAIN ABOVE TO FIRST FLOOR.
3. EXISTING TO REMAIN 10" STORM DRAINAGE DOWN TO FLOOR
BELOW TO FIRST FLOOR.
4. EXISTING TO REMAIN 4" SANITARY DOWN TO FLOOR BELOW.
5. 2" VTR TO BE DEMOLISHED. CAP AND SEAL PIPE ABOVE
CEILING AT NEAREST MAIN.
6. 2" VTR EXISTING TO REMAIN.
7. PIPING CONTINUES INTO AREA NOT IN PROJECT SCOPE.
8. DEMOLISH PLUMBING FIXTURE AND ASSOCIATED
APPURTENANCES.
9. DEMOLISH EXISTING FLOOR DRAIN.
10. 2" VTR TO BE DEMOLISHED. CAP AND SEAL PIPE
PENETRATIONS FOR 2 HOUR FIRE-RATING IN ASSOCIATED
FIRE-RATED BARRIER.
11. 4" VTR EXISTING TO REMAIN.
12. PROVIDE SANITARY DRAIN TO WATER / ICE DISPENSER,
MINIMUM SIZE OF EQUIPMENT DRAIN CONNECTION. ROUTE
DOWN THROUGH WALL AND CONNECT TO NEAREST SANITARY
BRANCH. PROVIDE FIRE SEALANT FOR WALL PENETRATION.
13. DEMOLISH EXISTING DRAIN CONNECTION TO MEDICAL
EQUIPMENT. PATCH AND SEAL FLOOR TO MATCH EXISTING AT
FLOOR PENETRATION.
SCALE: 1/8" = 1'-0"F1
PLUMBING SANITARY DEMOLITION - BELOW SECOND FLOOR
(E) 6" ST DN BELOW FLOOR
(E) 4" ST
BELOW FLOOR
File details come from the government source that posted it. Updated .