Fire-Plumbing Drawings.pdf

PDF 2 MB Posted

Attached to
Z1DA--Project# 614-19-102 - Reno Bldg. 7 Spinal Cord Injury Rehab Area
Solicitation number
36C24920B0003
Issued by

About this file

This solicitation is for a construction project to renovate the spinal cord injury rehabilitation area in Building 7 at the VA Medical Center in Memphis, Tennessee. The scope of work includes demolishing existing fire detection, fire alarm, and occupant notification systems; installing new sprinklers, plumbing, and fire alarm devices; and modifying walls to meet fire rating requirements. The estimated value is over $2 million. The solicitation number is 36C24920B0003 and was issued by the Department of Veterans Affairs Veterans Health Administration VISN 9. The pre-solicitation notice states that solicitation 36C24919B0001_1 will be posted to fulfill this requirement. Construction is to be completed by qualified firms with experience in medical facility renovations and compliance with VA construction standards.

View the file

Other files

File Type Posted
36C24920B0003 0007.docx DOCX document
36C24920B0003 0006.docx DOCX document
36C24920B0003 0005.docx DOCX document
36C24920B0003 0004.docx DOCX document
Amendent_SPECS.pdf PDF
Amend Rpt 0001.pdf PDF
Amendment_DRAWINGS.pdf PDF
36C24920B0003 0003.docx DOCX document
RFI Form - Renovate Bldg. 7 SCI Rehab Area.docx DOCX document
Contractor EMR Certification Form 2020.docx DOCX document
36C24920B0003 0002.docx DOCX document
36C24920B0003 0001.docx DOCX document
Drawings 614-19-102.pdf PDF
Electric-Telecom Drawings.pdf PDF
36C24920B0003_1.docx DOCX document
Addendum G-101.pdf PDF
Architectural Drawings 2.pdf PDF
Wage Determination - Shelby County.pdf PDF
Specifications.pdf PDF
Architectural Drawings 1.pdf PDF
Mechanical Drawings.pdf PDF
General Drawings.pdf PDF
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DESIGN AND INSTALLATION SHALL BE IN ACCORDANCE WITH NFPA 13, "STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS", 2019 EDITION; NFPA 70, "NATIONAL ELECTRICAL CODE", 2017 EDITION; NFPA 72, "NATIONAL FIRE ALARM AND SIGNALING CODE", 2019 EDITION; NFPA 241, "SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS" 2019 EDITION; AND VA FIRE PROTECTION DESIGN MANUAL (VAFPDM), SEVENTH EDITION, DECEMBER 2015.

THE INTENT, AND EXTENT OF THE FIRE PROTECTION SYSTEM DESIGN IS PERFORMANCE-BASED IN NATURE, AND IS DIAGRAMMATIC ONLY. IT IS NOT INTENDED TO SHOW EVERY PIPE, FITTING, DEVICE, APPLIANCE, COMPONENT, ETC. FIRE ALARM FLOOR PLANS AND RISER DIAGRAM ARE DIAGRAMMATIC AND NOT INTENDED TO SHOW EACH AND EVERY COMPONENT, DEVICE, APPLIANCE, ETC. CONDUIT PATHWAYS AND INTERCONNECTIONS SHALL BE DETERMINED BY THE BUILDING FEATURES, NFPA 70, NFPA 72, SYSTEM MANUFACTURER REQUIREMENTS AND RECOMMENDATIONS.

CONTRACTOR SHALL VISIT JOB SITE PRIOR TO BID WITH THE PROJECT DOCUMENTS AND SPECIFICATIONS TO BECOME FAMILIAR WITH THE SITE AND SCOPE OF WORK. NOTIFY ENGINEER OF RECORD WITH ANY DISCREPANCIES OUTSIDE THIS DESIGN INTENT. ANY CHANGE ORDER REQUEST AS A RESULT OF COORDINATION BETWEEN TRADES SHALL BE DENIED.

ADHERE TO AND OBTAIN ALL PERMITS, LICENSES, FOR BOTH LOCAL AND FEDERAL GOVERNMENT REQUIREMENTS.

DO NOT SCALE PLANS FOR THE PURPOSE OF ESTABLISHING DIMENSIONS. FIELD DIMENSION GOVERN.

FIRE STOP ALL PENETRATIONS OF SMOKE/FIRE PARTITIONS. FIRE STOPPING SHALL BE OF UL LISTED ASSEMBLY.

1.

2.

3.

4.

5.

6.

GENERAL NOTES

CONTRACTOR SHALL SUBMIT COMPLETE SHOP DRAWINGS WITH HYDRAULIC CALCULATIONS, MATERIAL SPECIFICATION BROCHURE TO CONTRACTING OFFICER'S TECHNICAL REPRESENTATIVE FOR REVIEW PRIOR TO

COMMENCING FABRICATION AND INSTALLATION.

FIRE SPRINKLER CONTRACTOR SHALL INSTALL SYSTEM PIPING AND COMPONENTS IN A WORKMANSHIP LIKE MANNER. CHANGES IN INSTALLATION AS A RESULT OF POOR CRAFTSMANSHIP SHALL BE AS DIRECTED BY CONTRACTING OFFICER'S TECHNICAL REPRESENTATIVE AND SHALL BE AT NO ADDITIONAL COST TO THE OWNER.

ANY ADDITIONAL OFFSETS OR FITTINGS REQUIRED FOR PROPER INSTALLATION, COORDINATION WITH OTHER TRADES, AND/OR TO MAINTAIN PROPER CLEARANCES SHALL BE PROVIDED FOR A COMPLETE AND WORKING

SYSTEM.

ALL CONTROL VALVES ON THE FIRE PROTECTION SYSTEM SHALL BE ELECTRICALLY SUPERVISED. COORDINATE THE TYPE AND EXACT LOCATION OF FLOW AND SUPERVISORY SWITCHES BETWEEN FIRE SPRINKLER AND FIRE ALARM CONTRACTORS. FIRE ALARM SYSTEM, SUPERVISION AND WIRING SHALL BE PROVIDED UNDER THE FIRE

ALARM DIVISION.

SPRINKLER SYSTEM(S) SHALL BE DESIGNED FOR A MAXIMUM WORKING PRESSURE OF 175 PSI IN ACCORDANCE

WITH NFPA 13.

SPRINKLER SYSTEM(S) SHALL BE HYDROSTATICALLY TESTED IN ACCORDANCE WITH NFPA 13 (BEFORE AND AFTER

SCOPE OF WORK IS PERFORMED).

ALL VALVES SHALL HAVE A PERMANENTLY AFFIXED SIGN PER NFPA 13 INDICATING ITS FUNCTION AND SECURED

TO THE VALVE WITH SUITABLE CHAIN.

HANGER MATERIAL, SPACING AND METHOD OF ATTACHMENT SHALL BE IN ACCORDANCE WITH NFPA 13 AND

MANUFACTURER'S REQUIREMENTS.

MAINTAIN A MINIMUM OF 18" CLEARANCE BELOW SPRINKLER DEFLECTOR(S) AND ANY PERMANENT OR

TEMPORARY OBSTRUCTION(S) PER NFPA 13.

ONLY LISTED OR APPROVED DEVICES AND MATERIALS AS SPECIFIED IN NFPA 13 SHALL BE INSTALLED

THROUGHOUT THE SYSTEM.

ALL SPRINKLERS SHALL BE INSTALLED ACCORDING TO THEIR LISTED SPACING AND OBSTRUCTION

REQUIREMENTS.

CONTRACTOR SHALL COORDINATE INSTALLATION OF ALL FIRE PROTECTION DEVICES WITH OTHER TRADES AND

EXISTING CONDITIONS.

PROVIDE SYSTEM(S) WITH FLUSHING CONNECTIONS PER NFPA 13.

SPRINKLER SYSTEM PIPING IS REQUIRED TO BE PROVIDED WITH SEISMIC BRACING AS THE SITE IS A CRITICAL FACILITY RISK CATEGORY IV WITH A SEISMIC DESIGN CATEGORY C. PROVIDE EARTHQUAKE PROTECTION IN

ACCORDANCE WITH NFPA 13 REQUIREMENTS.

AT LEAST SIX (6) SPARE SPRINKLERS OF EACH TYPE, TEMPERATURE, AND ORIFICE SIZE USED IN THE SYSTEM INCLUDING A SPECIAL WRENCH FOR EACH FIRE SPRINKLER SHALL BE KEPT IN A CABINET WHERE AMBIENT

TEMPERATURE WILL AT NO TIME EXCEED 100°F PER NFPA 13.

PIPE, FITTING, SPRINKLERS, HANGERS, AND COMPONENTS INSTALLED IN CORROSIVE ATMOSPHERES (I.E COMPARTMENTS CONTAINING CORROSIVE MATERIALS AND/OR FUMES, OR EXTERIOR WEATHER CONDITIONS, ETC.) SUCH AS DRAIN PIPES, HANGER ALL-THREAD ROD, ETC., SHALL BE AN APPROVED CORROSION RESISTANT

MATERIAL.

SPRINKLER PIPING 2-IN. AND LESS MUST BE A MINIMUM OF SCH. 40 BLACK STEEL PIPE. PIPING LARGER THAN 2-IN.

MUST BE A MINIMUM OF SCH. 10 BLACK STEEL PIPE. ANY EXISTING CPVC PIPE SHALL BE REMOVED AND REPLACED WITH SCH. 40 BLACK STEEL PIPE WITH CAST IRON FITTINGS PER VAFPDM SECTION 6.1, B, 4.

PIPING WITH A WALL THICKNESS LESS THAN SCH. 40 MUST NOT BE THREADED.

SPRINKLER PROTECTION IS NOT REQUIRED IN THE NONCOMBUSTIBLE CONCEALED SPACE ABOVE THE CEILING

PER NFPA 13.

REFER TO WET-PIPE SPRINKLER SYSTEM SPECIFICATION 21 13 13 FOR ADDITIONAL REQUIREMENTS AND

INFORMATION.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

FIRE SUPPRESSION NOTES

CONTRACTOR SHALL SUBMIT COMPLETE BATTERY CALCULATIONS, VOLTAGE DROP CALCULATIONS, MATERIAL DATA SHEETS, AND SHOP DRAWINGS TO OWNER'S TECHNICAL REPRESENTATIVE FOR REVIEW PRIOR TO COMMENCING FABRICATION AND INSTALLATION. FAILURE TO COMPLY IS AT THE RISK OF THE CONTRACTOR.

REFER TO PLAN DRAWINGS AND PROJECT DOCUMENTS FOR APPROXIMATE FIRE ALARM SYSTEM QUANTITIES AND LOCATIONS, NOT ALL SITE CONDITIONS ARE SHOWN. FIRE ALARM CONTRACTOR SHALL VISIT JOB SITE WITH ALL PROJECT DOCUMENTS PRIOR TO BID TO BECOME FAMILIAR WITH PROJECT DESIGN, INSTALLATION, TESTING AND COMMISSIONING REQUIREMENTS, SITE CONDITIONS FOR NEW SYSTEM INSTALLATION, TO PROVIDE A COMPREHENSIVE AND COMPLETE BID, CODE COMPLIANT SYSTEM DESIGN, INSTALLATION, TESTING, COMMISSIONING AND APPROVAL REQUIREMENTS.

FIRE ALARM SIGNALS AND EMERGENCY COMMUNICATIONS SHALL TAKE PRECEDENCE OVER ALL OTHER

SIGNALS, SUCH AS BUT NOT LIMITED TO PUBLIC ADDRESS SYSTEMS.

ALL NOTIFICATION APPLIANCES CIRCUITS (NAC) SHALL WIRING CLASS SHALL MATCH EXISTING.

ALL SIGNALING LINE CIRCUITS (SLC) SHALL WIRING CLASS SHALL MATCH EXISTING.

ALL INDICATING DEVICE CIRCUITS SHALL WIRING CLASS SHALL MATCH EXISTING.

THE INSTALLATION OF WIRING BETWEEN THE FACP AND RELAY MODULES OR APPLIANCES SHALL WIRING

CLASS SHALL MATCH EXISTING.

ALL CONDUCTORS FOR THE FIRE ALARM SYSTEM SHALL BE INSTALLED IN EMT CONDUIT AND IN ACCORDANCE WITH NFPA 70. THE CONDUCTORS SHALL NOT BE INSTALLED WITH CONDUCTORS OF LIGHTING OR POWER SYSTEMS. THE SUM OF THE CROSS-AREA OF INDIVIDUAL CONDUCTORS SHALL NOT EXCEED 40% OF THE INTERIOR CROSS SECTION OF THE CONDUIT. ALL FIRE ALARM SYSTEM CONDUIT SHALL NOT BE LESS THAN 3/4".

WALL MOUNTED FIRE ALARM DEVICES IN UNFINISHED AREAS MAY BE SURFACED MOUNTED, THE CONDUIT MAY

BE INSTALLED EXPOSED ON WALLS AND ON CEILINGS.

IN FINISHED AREAS, WALL MOUNTED DEVICES SHALL BE FLUSH MOUNTED. THE CONDUIT SHALL BE INSTALLED

CONCEALED IN THE WALLS AND CEILINGS UNLESS REFERENCED AS CEILING MOUNTED.

ELECTRICAL CONTRACTORS SHALL COORDINATE WITH FIRE ALARM VENDOR FOR SYSTEM OPERATING

INSTRUCTIONS AND WIRING DIAGRAMS.

CONTRACTOR SHALL PROVIDE PATHWAY SURVIVABILITY OF LEVEL 1 IN ACCORDANCE WITH NFPA 72.

FIRE ALARM FLOOR PLANS AND RISER DIAGRAM ARE DIAGRAMMATIC AND NOT INTENDED TO SHOW EACH AND EVERY COMPONENT, DEVICE, APPLIANCE, ETC. CONDUIT PATHWAYS AND INTERCONNECTIONS SHALL BE DETERMINED BY THE BUILDING FEATURES, NFPA 70, NFPA 72, SYSTEM MANUFACTURER REQUIREMENTS AND

RECOMMENDATIONS.

FIRE ALARM SYSTEM IS TO BE ADDED TO AN EXISTING ADDRESSABLE FIRE ALARM CONTROL UNIT THAT IS PART OF A COMPREHENSIVE BUILDING. NEW FIRE ALARM COMPONENTS ADDED AS PART OF THIS SCOPE OF WORK SHALL SHALL MEET THE REQUIREMENTS OF THE BUILDING SYSTEM, BUT AT A MINIMUM THE FUNCTIONS

IDENTIFIED IN THE MATRIX.

CONTRACTOR SHALL ADD THE INDICATED FIRE ALARM DEVICES TO THE THE EXISTING SYSTEM. THE NEW DEVICES SHALL OPERATE PER THE EXISTING SEQUENCE OF OPERATIONS AND THE SCOPE OF WORK SHALL

NOT MODIFIY THE EXISTING SEQUENCE OF OPERATIONS.

CONTRACTOR SHALL PROVIDE NOTATION ON THE INSTALLATION DRAWINGS OR A SEPARATE LETTER ON COMPANY LETTERHEAD THAT THE SYSTEM SIGNAL TRANSMISSION, FUNCTIONS AND SEQUENCING HAS BEEN

COORDINATED WITH THE BUILDING COMPREHENSIVE FIRE ALARM SYSTEM.

THE FIRE ALARM SYSTEM SHALL NOT BE COMBINED WITH ANY OTHER BUILDING SYSTEM, SUCH AS BUT NOT

LIMITED TO, AUTOMATION, ENERGY, SECURITY, ETC.

REFER TO FIRE ALARM SYSTEM SPECIFICATION 28 31 00 FOR ADDITIONAL REQUIREMENTS AND INFORMATION.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

FIRE ALARM NOTES

FIRE ALARM

CONTROL

PANEL

(FACP)

BATTERIES

120 VAC

BREAKER POWER

PANEL

DACT

1ST FLOOR

2ND FLOOR

CIRCUITS

2ND FLOOR

NAC

EXISTING SIGNALING LINE CIRCUIT (SLC)F

NEW NOTIFICATION APPLIANCE CIRCUIT (NAC)

NEW SPEAKER CIRCUIT

EVAC

BREAKER POWER

PANEL

120 VAC

FACP FIRE SAFETY

A C

T U

A T

E A

U D

IO

V

IS

U

A L

S U

P E

R V

IS

O

R Y

I N

D

IC

A T

IO

N

D E

V

IC

E

A C

T U

A T

E A

U D

IO

V

IS

U

A L A

L A

R M

IN

D

IC

A T

O R

D E

V

IC

E S

A C

T U

A T

E A

U D

IO

V

IS

U

C O

M M

O N

T R

O U

B L E

I N

D

IC

A T

O R

R E

L E

A S

E D

O O

R H

O L D

S

U N

L O

C K

E X

IT

S

A B C D E F G H I J K L

F1 MANUAL PULL STATION IN ZONE OF ALARM

FIRE ALARMS

X

SYSTEM INPUTS T

R

A N

S M

IT

A

L A

R M

S

IG

N A

L T

E

C E

IV

IN

G S

T A

T

IO

N

T R

A N

S M

IT

S

U P

E R

V

IS

O R

Y S

IG

N

R E

C E

IV

IN

G S

T A

T

IO

N

T R

A N

S M

IT

T

R O

U B

L E

S

IG

N A

L

C E

IV

IN

G S

T A

T

IO

N

A L E

R T

S T

R O

B E

T H

R O

U G

H O

U T

T H

Z

N E

C

L E

A R

F

IR

E A

L A

R M

E V

A C

U A

T

IO

N M

E S

S A

G

R

O U

G H

O U

T Z

O N

CENTRAL

STATION

EVAC

SIGNALS

SYSTEM OUTPUTS

X X X

R E

C O

R D

E V

E N

T S

I N

S Y

S T

M

IS

T

O R

Y

X X

C L O

S E

D A

M P

E R

S

XX

EXISTING DEVICES AND OPERATIONS TO BE MAINTAINED. NEW DEVICES SHALL OPERATE THE SAME AS THE EXISTING

DEVICES ARE CURRENTLY PROGRAMMED.

F2 SMOKE DETECTOR X X X XX X XX

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592Revisions: Date:

ORIGINAL SHEET SIZE: 30" X 42"

B

IM

/1

V

A B ld g

S p in a l C o rd

I n ju ry

R e h a b A re a

/1

V A

B ld g

M E

P

F P

V

.r v t

/1

/2

:1

:0

P

M

F-001

FIRE PROTECTION GENERAL

NOTES AND SYMBOLS

RENOVATE BUILDING 7 SPINAL

CORD INJURY (SCI) REHAB AREA

VA MEDICAL CENTER, MEMPHIS, TN

614-19-102

BLDG 7

04/22/2020 BTH NDS

SCALE: N.T.S.D7

FIRE ALARM RISER DIAGRAM

SCALE: N.T.S.F7

FIRE ALARM SEQUENCE OF OPERATIONS

4/17/20

F

F

THE DESIGN, LAYOUT, INSTALLATION AND SETTING OF THE

FIRE SPRINKLER SYSTEM SHALL BE IN ACCORDANCE WITH

CONTRACT DOCUMENTS, SPECIFICATIONS, VA FIRE

PROTECTION MANUAL, LATEST EDITIONS OF THE NATIONALLY

RECOGNIZED FIRE AND LIFE SAFETY CODES, SUCH AS BUT

NOT LIMITED TO, NFPA 13, NFPA 70, NFPA 72, NFPA 101 AND

NFPA 241.

FIRE PROTECTION ALTERATIONS SHALL COMPLY WITH THE

VA MASTER CONSTRUCTION SPECIFICATIONS.

THE EXISTING FIRE SPRINKLER LAYOUT SHALL BE REVISED

TO ACCOMMODATE THE REVISED WALL/ROOM LAYOUT

INSIDE THE PROJECT SCOPE AREA. ALL SPRINKLERS SHALL

BE NEW, QUICK RESPONSE, STANDARD COVERAGE, UNLESS

NOTED OTHERWISE. SPRINKLERS SHALL BE FM APPROVED

AS QUICK RESPONSE.

LOCATION OF SPRINKLERS SHALL BE COORDINATED WITH

CEILING FEATURES AND OBSTRUCTIONS, SUCH AS BUT NOT

LIMITED TO ELEVATION, MATERIAL OF CONSTRUCTION,

LIGHTS, GRILLS, DIFFUSERS, CURTAIN TRACK SYSTEM(S),

LIFT SYSTEM AND OTHER FEATURES AND/OR OBSTRUCTION

OF SIMILAR NATURE.

A MINIMUM OF 18-INCHES OF CLEARANCE SHALL BE

MAINTAINED BETWEEN THE SPRINKLER DEFLECTOR AND ANY

STORAGE MATERIALS AND/OR EQUIPMENT IN ACCORDANCE

WITH NFPA 13.

ALL THROUGH PENETRATIONS OF THE FIRE RESISTANCE

RATED (FRR) BUILDING FEATURES (WALLS, FLOORS,

CEILINGS, ETC.) SHALL BE FIRE STOPPED WITH A UL LISTED

FRR MATERIAL/ ASSEMBLY EQUAL TO OR GREATER THAN THE

FRR OF THE PENETRATED BUILDING FEATURE.

THE USE OF CPVC PIPE AND FITTING IS PROHIBITED.

MINIMIZE OR AVOID DISRUPTIONS TO THE FIRE SPRINKLER

SYSTEM. WHEN DISRUPTIONS ARE ANTICIPATED, ENSURE

THAT PROCEDURES ARE INCORPORATED TO MAINTAIN

EQUIVALENT LEVELS OF FIRE PROTECTION AND PROVIDE

FORMAL NOTIFICATION TO THE FACILITY WHILE SYSTEMS

ARE DOWN.

COORDINATE SPRINKLER LOCATIONS WITH SURFACE

MOUNTED LIGHTING.

PROVIDE HIGH TEMPERATURE RATED SPRINKLERS WHERE

REQUIRED PER NFPA 13.

PROVIDE SEISMIC BRACING ON ALL NEW PIPING PER NFPA

13.

PROVIDE EQUIPMENT AND COMPONENTS FOR ALL FIRE

SPRINKLER SYSTEM PIPING, SPRINKLERS, COUPLINGS,

FITTINGS, VALVES, ETC. THAT COMPRISES A COMPLETE FIRE

SPRINKLER SYSTEM THAT IS IN COMPLIANCE WITH VA

REQUIREMENTS.

DEMOLISH EXISTING FIRE DETECTION, FIRE ALARM, AND

OCCUPANT NOTIFICATION SYSTEM IN ITS ENTIRETY INSIDE

THE INDICATED PROJECT SCOPE AREA. CONTRACTOR SHALL

REPAIR IN KIND ANY DAMAGES THE BUILDING SUSTAINS

DURING DEMOLITION.

CONTRACTOR SHALL DISPOSE OF ALL DEMOLISHED

COMPONENTS AND MATERIALS IN ACCORDANCE WITH ALL

LOCAL AND FEDERAL REGULATIONS.

EXISTING FIRE ALARM AND OCCUPANT NOTIFICATION

SYSTEM IS TO REMAIN IN OPERATION AT ALL TIMES TO THE

FULLEST EXTENT POSSIBLE, UNTIL NEW FIRE ALARM

DEVICES ARE INSTALLED AND TESTED. PLANNED SYSTEM

IMPAIRMENTS SHALL COMPLY WITH NFPA 72 REQUIREMENTS.

A FIRE WATCH WILL BE PROVIDED FOR SYSTEM

IMPAIRMENTS AT THE DISCRETION OF THE FIRE MARSHAL.

FIRE ALARM FLOOR PLANS AND RISER DIAGRAM ARE

DIAGRAMMATIC AND NOT INTENDED TO SHOW EACH AND

EVERY COMPONENT, DEVICE, APPLIANCE, ETC. CONDUIT

PATHWAYS AND INTERCONNECTIONS SHALL BE DETERMINED

BY THE BUILDING FEATURES, NFPA 70, NFPA 72, SYSTEM

MANUFACTURER REQUIREMENTS AND RECOMMENDATIONS.

FIRE ALARM NOTIFICATION APPLIANCES SHALL BE 15

CANDELA UNLESS OTHERWISE NOTED.

CONTRACTOR SHALL PROVIDE THE NECESSARY QUANTITY

OF POWER SUPPLY PANELS FOR CONTROL AND OPERATION

OF ALL NOTIFICATION APPLIANCES. COORDINATE PANELS

WITH THE ELECTRICAL CONTRACTOR FOR REQUIRED POWER

REQUIREMENTS.

CONTRACTOR SHALL PROVIDE ALL NECESSARY AND

REQUIRED SYSTEM PROGRAMMING TO MEET THE DESIGN

INTENT AND CODE COMPLIANCE.

GENERAL NOTES:

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

LEGEND

LIGHT HAZARD

0.10 GPM/SQ.FT OVER 1500 SQ.FT

100 GPM HOSE ALLOWANCE

LH

EXISTING SPRINKLER

PROTECTION TO REMAIN

EX

ORDINARY HAZARD

0.20 GPM/SQ.FT OVER 1500 SQ.FT

250 GPM HOSE ALLOWANCE

OH

MANUAL FIRE ALARM PULL STATION, MOUNT

42" - 48" AFF TO TOP OF HANDLE

ETR = EXISTING TO REMAIN

F

NEW FIRE ALARM CLEAR VISUAL STROBE. WALL

MOUNT AT 80" AFF TO BOTTOM OF LENS OR 6"

BELOW CEILING, WHICHEVER IS LOWER AND NOT

GREATER THAN 96".

NEW FIRE ALARM CLEAR VISUAL STROBE AND

HORN. WALL MOUNT AT 80" AFF TO BOTTOM OF

LENS OR 6" BELOW CEILING, WHICHEVER IS

LOWER AND NOT GREATER THAN 96".

ETR

NEW RECESSED SPRINKLER

NEW UPRIGHT SPRINKLER

EXISTING FLOOR CONTROL ZONE VALVE TO

REMAIN

EXISTING EQUIPMENT, PATHWAYS, ETC. TO REMAIN.

NEW EQUIPMENT, PATHWAYS, ETC. TO BE ADDED.

SMOKE DETECTOR-PHOTOELECTRICS

NOTIFICATION APPLIANCE POWER EXTENDER PANEL.

COORDINATE WITH EXISTING EQUIPMENT IN THE ROOM.

NAC

EX

EX EX

EX

EX EX

OHEQUIP. STORAGE

2C110

CORRIDOR

C2-27

OCCUPATIONAL

THERAPY (OT)

2C113

KINESIO-THERAPY

(KT)

2C112

WOMEN (PATIENT)

2C109

MULTI-PURPOSE

ROOM

2C107

MEN (PATIENT)

2C108

DRIVER THERAPY

2C106

STORAGE

2C105

PRIVATE

TREATMENT

2C104

WAITING

2C102

CORRIDOR

C2-27

CHECK-IN DESK

2C103

PHYSICAL THERAPY

(PT)

2C111

COMM

2C117

EL

2C118

CORRIDOR

C2-28

BREAKROOM

2C114

RECREATIONAL

THERAPY

2C120

WOMEN (STAFF)

2C115

MEN (STAFF)

2C116

JAN

2C119

STORAGE

2C121

OH

OH

LH

LH

LH

LH

LH

LH

LH

LH

LH

LH

LH

OH

LH

LH

LH

LH

STORAGE

2C111A

STORAGE

2C114A

OH

OH

LH

LH

LH

EX

EX

EX

EX EX

EQUIP. STORAGE

2C110

CORRIDOR

C2-27

OCCUPATIONAL

THERAPY (OT)

2C113

KINESIO-THERAPY

(KT)

2C112

WOMEN (PATIENT)

2C109

MULTI-PURPOSE

ROOM

2C107

MEN (PATIENT)

2C108

DRIVER THERAPY

2C106

STORAGE

2C105

PRIVATE

TREATMENT

2C104

WAITING

2C102

CORRIDOR

C2-27

CHECK-IN DESK

2C103

PHYSICAL THERAPY

(PT)

2C111

COMM

2C117

EL

2C118

CORRIDOR

C2-28

BREAKROOM

2C114

RECREATIONAL

THERAPY

2C120

WOMEN (STAFF)

2C115

MEN (STAFF)

2C116

JAN

2C119

STORAGE

2C121

ETR

STORAGE

2C114A

STORAGE

2C111A

S

NAC

AREA OF WORK

2ND FLOOR

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592Revisions: Date:

ORIGINAL SHEET SIZE: 30" X 42"

B

IM

/1

V

A B ld g

S p in a l C o rd

I n ju ry

R e h a b A re a

/1

V A

B ld g

M E

P

F P

V

.r v t

/1

/2

:1

:0

P

M

F-101

FIRE PROTECTION & FIRE ALARM

PLANS

RENOVATE BUILDING 7 SPINAL

CORD INJURY (SCI) REHAB AREA

VA MEDICAL CENTER, MEMPHIS, TN

614-19-102

BLDG 7

04/22/2020 BTH NDS

SCALE: 1/8" = 1'-0"F1

FIRE PROTECTION PLAN

SCALE: 1/8" = 1'-0"F5

FIRE ALARM PLAN

SCALE: = 1'-0"

0 8 168

1/8"

N

KEYPLAN

4/17/20

PLUMBING LEGEND

KEY NOTES

DIRECTION OF FLOW

PIPE TURNED DOWN

PIPE TURNED UP

RISE OR DROP

BRANCH BOTTOM CONNECTION

TEE OUTLET UP

TEE OUTLET DOWN

CAP ON END OF PIPE

SANITARY WASTE (NEW) - ABOVE FLOOR OR GRADE

SANITARY WASTE (NEW) - BELOW FLOOR OR GRADE

VENT PIPING (NEW)

POTABLE / DOMESTIC COLD WATER PIPING (NEW)

POTABLE / DOMESTIC HOT WATER SUPPLY PIPING (NEW)

THERMOMETER

TEMPERATURE & PRESSURE RELIEF VALVE

FLOW MEASURING / BALANCING / SHUT-OFF VALVE

BALL VALVE

CHECK VALVE

GATE VALVE

STRAINER

UNION

HOSE BIBB

FLOOR DRAIN

PLUMBING ABBREVIATIONSPLUMBING GENERAL NOTES

1. PLUMBING WORK SHALL BE IN ACCORDANCE WITH THE IBC, IPC, AND VA DESIGN STANDARDS.

2. SLOPES AND INVERT ELEVATIONS SHALL BE ESTABLISHED BEFORE ANY PIPE IS INSTALLED IN ORDER

TO MAINTAIN PROPER SLOPES. ANY DISCREPANCIES SHALL BE REPORTED TO CONTRACTING

OFFICER'S REPRESENTATIVE. ALL PIPING SHALL BE LOCATED AND DETERMINED WHEN TO BE

INSTALLED TO AVOID CONFLICT WITH OTHER TRADES.

3. PIPING SHALL BE CONCEALED UNLESS OTHERWISE NOTED.

4. KEEP ALL BURIED PIPING CLEAR OF FOOTINGS. COORDINATE WITH STRUCTURAL.

5. ALL WALL CLEANOUTS SHALL BE PROVIDED WITH WALL COVERS AND MOUNTED IN UNOBTRUSIVE

LOCATIONS WHILE MAINTAINING ACCESSIBILITY. ALL FLOOR CLEANOUTS SHOWN SHALL BE SET FLUSH

WITH FLOOR AREAS OR FINISHED GRADE.

6. COORDINATE LOCATION OF PIPING AND DRAINS WITH ALL MECHANICAL AND ELECTRICAL EQUIPMENT.

NO PIPING SHALL BE INSTALLED ABOVE ELECTRICAL, COMMUNICATIONS, OR DATA EQUIPMENT OR

PANELS. COMPLY WITH ARCHITECTURAL PLANS FOR EXACT LOCATION OF PLUMBING FIXTURES,

COMPLIANCE TO ADA CLEARANCES, AND FINISHES.

7. PROVIDE REQUIRED WATER, WASTE, AND VENT PIPING, FITTINGS, AND INSULATION, AND MAKE FINAL CONNECTIONS TO EQUIPMENT. THESE PLANS ARE SCHEMATIC AND DIAGRAMMATIC ONLY. THEY DO

NOT SHOW ALL REQUIRED BENDS, OFFSETS, VALVES, AND MISCELLANEOUS FITTINGS FOR A

COMPLETE INSTALLATION. ALL PIPING, EQUIPMENT, AND CONNECTIONS SHALL BE INSTALLED IN

ACCORDANCE WITH SPECIFICATIONS, LOCAL CODES AND ORDINANCES, AND MANUFACTURER'S

INSTRUCTIONS.

8. SANITARY SEWER PIPING SHALL BE INSTALLED TO PROVIDE A MINIMUM SLOPE OF 1%. WASTE PIPING

3" AND SMALLER SHALL BE INSTALLED TO PROVIDE A MINIMUM SLOPE OF 2%.

9. DO NOT SCALE DRAWINGS. REFER TO ARCHITECTURE DRAWINGS FOR EXACT DIMENSIONS, FIXTURE

LOCATIONS, ROOM NAMES, AND NUMBERS.

10. EXTENSION OF EQUIPMENT DRAINS TO FLOOR DRAINS, FLOOR SINKS, AND OPEN SITE DRAINS SHALL

BE PROVIDED BY EQUIPMENT CONTRACTOR.

11. WHERE POSSIBLE, INSTALL SHUT-OFF VALVES AND EQUIPMENT REQUIRING MAINTENANCE, CLEANING AND ADJUSTMENT ABOVE ACCESSIBLE CEILINGS OR IN SERVICE AREAS SUCH AS JANITOR'S CLOSETS.

IN OTHER LOCATIONS, PROVIDE ACCESS PANELS IN INCONSPICUOUS LOCATIONS WITH FINISH TO

MATCH ARCHITECTURAL.

12. ALL HOSE BIBBS, WALL HYDRANTS, AND VALVES WITH THREADED HOSE CONNECTIONS SHALL BE

EQUIPPED WITH VACUUM BREAKER.

13. WHERE CONNECTING TO A UTILITY OR SERVICE, VERIFY LOCATION, SIZES, MATERIALS, FLUID BEING HANDLED, AND INVERTS OF ALL EXISTING UTILITIES AND CONFIRM THAT NEW PIPES BEING ROUTED TO EXISTING UTILITIES CAN BE INSTALLED CONFORMING TO CODE AND AS SHOWN. NOTIFY CONTRACTING

OFFICER OF ANY CONFLICTS OR DISCREPANCIES PRIOR TO PURCHASING ANY MATERIALS OR

PERFORMING ANY WORK OR EXTENSION OF CONNECTION, WITH THE EXCEPTION OF EXCAVATION OR

OTHER WORK TO PROVIDE ACCESS TO THE CONCEALED UTILITY.

14. PROVIDE INSULATION, PIPE IDENTIFICATION, AND OTHER REQUIREMENTS AS LISTED IN

SPECIFICATIONS.

15. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS AND ELEVATIONS OF ALL PLUMBING

FIXTURES.

16. ALL PIPING ABOVE GRADE SHALL BE PROPERLY SUPPORTED FROM THE BUILDING STRUCTURE AND

SHALL NOT REST ON CEILING TILES OR BE SUPPORTED FROM CEILING TILES.

17. WATER PIPING ROUTED ABOVE CEILINGS AND IN EXTERIOR WALLS SHALL BE ROUTED ON HEATED SIDE

(UNDERSIDE) OF CEILING INSULATION AND HEATED SIDE (INSIDE) OF WALL INSULATION.

18. TOPS OF ALL FLOOR DRAINS AND CLEANOUTS SHALL BE SET FLUSH WITH FINISHED FLOOR, UNLESS

NOTED OTHERWISE.

19. LOCATE ALL SECTIONAL OR MAIN CONTROL VALVES WITHIN 1'-0" FROM ACCESS PANELS, CEILING

TILES, OR OTHER POINT OF ACCESS.

20. PROVIDE WATER HAMMER ARRESTORS SIZED PER PDI SPECIFICATIONS ON ALL DOMESTIC WATER LINES SERVING FLUSH VALVE FIXTURES, WASHING MACHINES SUPPLIES, PRV STATIONS, AND OTHER

INSTALLATIONS WITH QUICK CLOSING VALVES.

21. PROVIDE A MANUFACTURED EXPANSION DEVICE OR FABRICATED EXPANSION LOOP ON ALL PIPING

SYSTEMS CROSSING BUILDING EXPANSION JOINTS.

22. COORDINATE ELECTRICAL CHARACTERISTICS AND REQUIREMENTS OF ALL PLUMBING EQUIPMENT WITH THE ELECTRICAL DRAWINGS AND THE ELECTRICAL CONTRACTOR, AND FURNISH EQUIPMENT

WIRED FOR THE VOLTAGES SHOWN THEREIN.

23. ALL PLUMBING EQUIPMENT AND SYSTEMS SHALL BE GUARANTEED FOR A MINIMUM PERIOD OF ONE

YEAR AFTER OWNER'S FINAL ACCEPTANCE.

24. ALL PIPE PENETRATIONS OF FIRE AND/OR SMOKE-RATED ASSEMBLIES SHALL BE FIRE-STOPPED AS REQUIRED TO RESTORE ASSEMBLY TO ORIGINAL INTEGRITY. FIRE BARRIER PRODUCTS SHALL BE AS MANUFACTURED BY 3M COMPANY, CP25 CAULK, CS195 COMPOSITE PANEL, FS195 WRAP/STRIP, OR PSS 7900 SERIES SYSTEMS AS RECOMMENDED BY MANUFACTURER FOR PARTICULAR APPLICATION, OR

EQUIVALENT SYSTEM AS APPROVED BY LOCAL CODE OFFICIALS.

25. ALL WATER CLOSET FLUSH VALVE LEVERS SHALL BE LOCATED ON THE APPROACH SIDE OF THE

WATER CLOSET.

26. ALL GAS REGULATORS REQUIRING VENTS SHALL BE VENTED TO THE EXTERIOR PER THE

INTERNATIONAL GAS CODE REQUIREMENTS. VENT TERMINALS SHALL BE A MINIMUM OF 10'-0" FROM

ANY AIR INTAKE OR SOURCE OF IGNITION.

27. ALL VENTS THROUGH ROOF SHALL BE LOCATED A MINIMUM OF 10'-0" FROM ANY OUTSIDE AIR INTAKE.

28. ALL COLD WATER, HOT WATER, AND DRAIN PIPING AT HANDICAPPED FIXTURES SHALL BE INSULATED

WITH HANDI-LAV GUARD MODELS 102 AND 105 (OR APPROVED EQUAL) INSULATION KITS.

29. NOT ALL PLUMBING ABBREVIATIONS SHOWN WILL BE USED FOR THIS PROJECT.

TRAP PRIMER

FLOOR CLEANOUT

WALL CLEANOUT

WATER HAMMER ARRESTOR

PLAN ELEV

TP

FCOFCO

WCO WCO

BRANCH TOP CONNECTION

POTABLE / DOMESTIC HOT WATER RETURN PIPING (NEW)

S

W

SANITARY RISER DIAGRAM DESIGNATION

RISER DIAGRAM NUMBER

DOMESTIC WATER RISER DIAGRAM DESIGNATION

RISER DIAGRAM NUMBER

A/C ABOVE CEILING

ADA AMERICANS WITH DISABILITIES ACT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

ARCH ARCHITECTURE, ARCHITECTURAL

BFP BACKFLOW PREVENTER

B/F BELOW FLOOR

B/G BELOW GRADE

BLDG BUILDING

BV BALL VALVE

CA COMPRESSED AIR

CD CONDENSATE DRAIN

CONT. CONTINUATION

CO CLEANOUT

CV CHECK VALVE

CONTR CONTRACTOR

CW COLD WATER (POTABLE / DOMESTIC)

DEG. DEGREES

DF DRINKING FOUNTAIN

DHWR DOMESTIC HOT WATER RETURN

DN DOWN

DSN DOWNSPOUT NOZZLE

DWGS DRAWINGS

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EMEW EMERGENCY EYEWASH

EMSH EMERGENCY SHOWER

ESEW EMERGENCY SHOWER / EYEWASH

EXST, (E) EXISTING

FCO FLOOR CLEANOUT

FD FLOOR DRAIN

GC GENERAL CONTRACTOR

GPF GALLONS PER FLUSH

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GV GATE VALVE

GWH GAS WATER HEATER

HB HOSE BIBB

H/C HANDICAP

HW HOT WATER (POTABLE / DOMESTIC)

I.E. INVERT ELEVATION

IBC INTERNATIONAL BUILDING CODE

IFGC INTERNATIONAL FUEL GAS CODE

IMB ICE MAKER BOX

IPC INTERNATIONAL PLUMBING CODE

IW INDIRECT WASTE

[kg] KILOGRAMS

KW KILOWATT

L LAUNDRY

LP LIQUID PETROLEUM

LV LAVATORY

[m] METERS [mm] MILLIMETERS

MFG MANUFACTURER

MS MOP SINK

NFWH NON-FREEZE WALL HYDRANT

NG NATURAL GAS

NIC NOT IN CONTRACT

ORD OVERFLOW ROOF DRAIN

P, PLBG PLUMBING

PDI PLUMBING DRAINAGE INSTITUTE

PSI POUNDS PER SQUARE INCH

RD ROOF DRAIN

RL RAIN LEADER

RPZ REDUCED PRESSURE ZONE

SAN, S SANITARY PIPING

SANS SANITARY SEWER

SH SHOWER

SK SINK

SOV SHUT-OFF VALVE

STR STRAINER

SS STAINLESS STEEL

TMV THERMOSTATIC MIXING VALVE

T&P TEMPERATURE AND PRESSURE

RELIEF VALVE

TP TRAP PRIMER

TYP TYPICAL

UR URINAL

U/G UNDERGROUND

U/SAN UNDERGROUND SANITARY

V VENT PIPING

VTR VENT THROUGH ROOF

W WASTE PIPING

WB CLOTHES WASHER OUTLET BOX

WC WATER CLOSET

WCO WALL CLEANOUT

WH WATER HEATER

WHA WATER HAMMER ARRESTOR

W/O WITHOUT

W/ WITH

YCO YARD CLEANOUT

CONNECT TO EXISTING

DISCONNECT FROM EXISTING

PLUMBING FIXTURE SCHEDULES

TAG FIXTURE TYPE COLD WATER PIPE

SIZE (IN)

HOT WATER PIPE

SIZE (IN)

WASTE PIPE SIZE

(IN)

VENT PIPE SIZE

(IN)

FLOW

RESTRICTION

DESCRIPTION

EWC-1 ELECTRIC WATER COOLER 1/2 -- 2 2 -- PROVIDE WITH DUAL HEAD AND BOTTLE FILLING STATION, 8 GPH CHILLING CAPACITY, ADA COMPLIANCE. PROVIDE ACCESSORY APRON.

LAV-1 LAVATORY, WALL MOUNT 1/2 1/2 1-1/4 2 0.5 GPM PROVIDE WITH DRAIN COVER AND MANUAL OPERATED FAUCET.

MS-1 MOP SINK 3/4 3/4 2 2 -- PROVIDE FAUCET WITH PAIL HOOK. PROVIDE 24"x24" STAINLESS STEEL PANELS ON ADJACENT CORNER.

SK-1 SINK, COUNTER MOUNT 3/4 3/4 1-1/2 2 1.5 GPM PROVIDE WITH DRAIN COVER AND MANUAL OPERATED FAUCET.

SK-2 TWO COMPARTMENT SINK 3/4 3/4 1-1/2 2 1.5 GPM PROVIDE WITH HAND SPRAY FAUCET.

WC-1 WATER CLOSET, WALL MOUNT,

ACCESSIBLE

1 -- 3 2 1.28 GPF PROVIDE ELONGATED BOWL AND MANUAL OPERATED FLUSHOMETER.

CB-1 COLD WATER CONNECTION BOX 1/2 -- -- -- -- PROVIDE WITH FIRE-RATED RECESSED CABINET. STEEL BRAIDED HOSE CONNECTION TO WATER / ICE DISPENSER.

MANUFACTURER MODEL NO.

BASIS OF DESIGN

SK-3 SINK, COUNTER MOUNT 3/4 3/4 1-1/2 2 1.5 GPM PROVIDE WITH DRAIN COVER AND MANUAL OPERATED FAUCET.

OATEY

ELKAY

KOHLER

FIAT

ELKAY

ELKAY

ELKAY

KOHLER

38490

LZSTL8WSSK

K-2007

SB3624

PSR2521

GECR3321

BPSH15C

K-4325

NEW RATED WALL LEGEND

1-HR RATED FIRE BARRIER

2-HR RATED FIRE BARRIER

1-HR FIRE RATED SMOKE BARRIER

SMOKE PARTITION

GC TO MODIFY EXISTING REMAIN WALLS/PARTITIONS

AS REQUIRED TO MEET FIRE RATED REQUIREMENT AS

SHOWN ON NEW FLOOR PLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592Revisions: Date:

ORIGINAL SHEET SIZE: 30" X 42"

B

IM

/1

V

A B ld g

S p in a l C o rd

I n ju ry

R e h a b A re a

/1

V A

B ld g

M E

P

F P

V

.r v t

/1

/2

:1

:1

A

M

P-001

PLUMBING LEGEND, SYMBOLS,

AND GENERAL NOTES

RENOVATE BUILDING 7 SPINAL

CORD INJURY (SCI) REHAB AREA

VA MEDICAL CENTER, MEMPHIS, TN

614-19-102

BLDG 7

04/22/2020 DKH MTR

NOTES:

1. EXISTING EQUIPMENT IS SHOWN WITH THIN, HALFTONE LINEWORK.

2. DEMOLISHED EQUIPMENT IS SHOWN WITH BOLD LINEWORK,

DASHED, AND HATCHED.

3. NEW OR RELOCATED EQUIPMENT IS SHOWN WITH BOLD LINEWORK.

4. BELOW IS AN EXAMPLE OF EACH:

EXISTING EQUIPMENT

EQUIPMENT TO BE DEMOLISHED

NEW OR RELOCATED EQUIPMENT

R.T. CLINIC

2C120

STORAGE

2C121

JAN. CLOSET

2C119TOILET

2C116

DRIVER CLINIC

2C115

CORRIDOR

C2-29

COMM

2C117

EC

2C118

STORAGE

2C110A

OFFICE

2C110B

PHYSICAL THERAPY

2C110

TOILET

2C-08

MED REHAB

2C112

STORAGE/BREAK ROOM

2C112A

STORAGE

2C111B

O.T. CLINIC

2C111

OFFICE

2C111A

PRIVATE TREATMENT

2C109

K.T. CLINIC

2C107 CORRIDOR

C2-27

WHEEL CHAIR STORAGE

2C106A

OFFICE

2C107A

JAN. CLOSET

2C102TOILET

2C104

LACK

2C103

STORAGE

2C106B

MEN TOILET

2C113

WOMEN TOILET

2C114

STORAGE

2C106

(E) 3/4" DHWR

(E) 1 1/2" HW

(E) 2 1/2" CW

(E) 2" CW

(E) 2" HW

2" VTR, ETR

2" VTR, ETR

2" VTR, ETR

4" VTR, ETR

4" VTR, ETR

4" VTR, ETR

2" VTR, ETR

2" VTR, ETR

2" VTR, ETR

(E) 3" CW

(E) 3/4" DHWR

(E) 2" HW(E) 1/2" DHWR

(E) 1" HW

(E) 2" CW

(E) 3/4" HW

(E) 2"

(E) 1" HW

(E) 2 1/2" CW

(E) 1/2" HW

(E) 1/2" CW

(E) 2 1/2" CW

(E) 1" HW

(E) 3" CW

(E) 2" HW

(E) 3/4" DHWR

(E) 1/2" DHWR

(E) 2 1/2" CW

(E) 2" HW

(E) 3/4" DHWR

(E) 2" CW

(E) 1" HW

(E) 2 1/2" CW

(E) 2" HW

(E) 2 1/2" CW

(E) 1 1/2" HW

(E) 2" CW

(E) 1" HW

(E) 1/2"

(E) 1/2"

ELEVATOR ELEVATOR ELEVATOR

STAIR

NO 4

STAIR

NO 5

COMM

2C100

EC

2C101

CORRIDOR

C2-30

CORRIDOR

C2-27

SINK, ETR

2" VTR, ETR

KEYNOTES:

AREA OF WORK

2ND FLOOR

R.T. CLINIC

2C120

STORAGE

2C121

JAN. CLOSET

2C119

TOILET

2C116

DRIVER CLINIC

2C115

CORRIDOR

C2-29

COMM

2C117

EC

2C118

STORAGE

2C110A

OFFICE

2C110B

PHYSICAL THERAPY

2C110

TOILET

2C-08

MED REHAB

2C112

STORAGE/BREAK ROOM

2C112A

STORAGE

2C111B

O.T. CLINIC

2C111

OFFICE

2C111A

PRIVATE TREATMENT

2C109

K.T. CLINIC

2C107 CORRIDOR

C2-28

WHEEL CHAIR STORAGE

2C106A

OFFICE

2C107A

JAN. CLOSET

2C102

TOILET

2C104

LACK

2C103

STORAGE

2C106B

MEN TOILET

2C113

WOMEN TOILET

2C114

STORAGE

2C106

ELEVATOR ELEVATOR ELEVATOR

STAIR

NO 4

STAIR

NO 5

COMM

2C100

EC

2C101

CORRIDOR

C2-30

SINK, ETR

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592Revisions: Date:

ORIGINAL SHEET SIZE: 30" X 42"

B

IM

/1

V

A B ld g

S p in a l C o rd

I n ju ry

R e h a b A re a

/1

V A

B ld g

M E

P

F P

V

.r v t

/1

/2

:1

:3

A

M

PD101

PLUMBING SUPPLY DEMOLITION

PLANS

RENOVATE BUILDING 7 SPINAL

CORD INJURY (SCI) REHAB AREA

VA MEDICAL CENTER, MEMPHIS, TN

614-19-102

BLDG 7

04/22/2020 DKH MTR

GENERAL NOTES:

1. REFER TO P-001 FOR PLUMBING GENERAL NOTES,

ABBREVIATIONS, AND LEGENDS.

SCALE: 1/8" = 1'-0"F1

PLUMBING DEMOLITION - UNDER SECOND FLOOR

N

SCALE: = 1'-0"

0 8 168

1/8"

KEYPLAN

SCALE: 1/8" = 1'-0"F5

PLUMBING SUPPLY DEMOLITION - ABOVE SECOND FLOOR

1. DOMESTIC WATER PIPING TO EQUIPMENT ON FIRST FLOOR.

2. 2" VENT UP TO SECOND FLOOR. SEE F1/PD102 FOR

CONTINUATION.

3. DEMOLISH PIPING BACK TO TEE AND CAP.

4. DEMOLISH PLUMBING FIXTURE AND ASSOCIATED

APPURTENANCES. DEMOLISH AND CAP SANITARY PIPING AT

NEAREST MAIN.

5. DEMOLISH PLUMBING FIXTURE AND CAP PIPING FOR FUTURE

WORK.

6. DEMOLISH DOMESTIC PIPING FROM BELOW.

7. PIPING CONTINUES INTO AREA NOT IN PROJECT SCOPE.

NOTE:

PLUMBING PIPING SHOWN ON THIS VIEW IS BELOW SECOND FLOOR AND ABOVE

FIRST FLOOR CEILING. SECOND FLOOR WALLS ARE OVERLAYED FOR CLARITY.

PHYSICAL

THERAPY

(PT)

2C111

KINESIO-THERAPY

(KT)

2C112

OCCUPATIONAL

THERAPY

(OT)

2C113

MULTI-PURPOSE

ROOM

2C107

EQUIP.

STORAGE

2C110

CORRIDOR

C2-28

BREAKROOM

2C114

RECREATIONAL

THERAPY

2C120

STORAGE

2C114A

WOMEN

(STAFF)

2C115

MEN

(STAFF)

2C116

JAN

2C119

STORAGE

2C121

COMM

2C117

EL

2C118

CHARTING

2C113A

CHARTING

2C112A

WOMEN

(PATIENT)

2C109

MEN

(PATIENT)

2C108

DRIVER

THERAPY

2C106

STORAGE

2C105

PRIVATE

TREATMENT

2C104

CHECK-IN

DESK

2C103

WAITING

2C102

STORAGE

2C111A

CORRIDOR

C2-27

SK-2

MS-1

WC-1

SK-1

SK-3

SK-3

WC-1

LAV-1

LAV-1

WC-1

WC-1

LAV-1

LAV-1

ELEVATOR ELEVATOR ELEVATOR

STAIR

NO 4

STAIR

NO 5

COMM

2C100

EC

2C101

CORRIDOR

C2-30

SINK, ETR

EWC-1

CB-1

SK-1

KEYNOTES:

AREA OF WORK

2ND FLOOR

RECREATIONAL

THERAPY

2C120

STORAGE

2C121

JAN

2C119

MEN

(STAFF)

2C116

STORAGE

2C114A

WOMEN

(STAFF)

2C115

BREAKROOM

2C114

CORRIDOR

C2-28

COMM

2C117

EL

2C118

EQUIP.

STORAGE

2C110

OCCUPATIONAL

THERAPY

(OT)

2C113

KINESIO-THERAPY

(KT)

2C112

CHARTING

2C113A

CHARTING

2C112A

MULTI-PURPOSE

ROOM

2C107

WOMEN

(PATIENT)

2C109

MEN

(PATIENT)

2C108

PHYSICAL

THERAPY

(PT)

2C111

CORRIDOR

C2-27

CHECK-IN

DESK

2C103

WAITING

2C102

PRIVATE

TREATMENT

2C104

STORAGE

2C105

DRIVER

THERAPY

2C106

STORAGE

2C111A

SK-2

MS-1

WC-1

SK-1

SK-1

SK-3

SK-3

WC-1

LAV-1

LAV-1

WC-1

WC-1

LAV-1

LAV-1

(E) 1" HW

(E) 1 1/2" CW

(E) 3/4" DHWR

(E) 1 1/2" HW

(E) 2 1/2" CW

(E) 2" HW

(E) 2" CW

(E) 2 1/2" CW

(E) 2" HW

(E) 3/4" DHWR

(E) 2" HW

(E) 2 1/2" CW

(E) 2" CW

(E) 1" HW

(E) 3" CW

(E) 2" HW

(E) 3/4" DHWR

(E) 1" HW

(E) 2" CW

ELEVATOR ELEVATOR ELEVATOR

STAIR

NO 4

STAIR

NO 5

COMM

2C100

EC

2C101

CORRIDOR

C2-30

SINK, ETR

EWC-1

CB-1

2" CW

3/4" HW

3/4" HW

3/4" CW

3/4" HW

3/4" CW

3/4" CW 3/4" HW

3/4" CW

3/4" HW

1/2" HW

1 1/2" CW

3/4" CW

3/4" HW

3/4" CW

3/4" HW

NEW RATED WALL LEGEND

1-HR RATED FIRE BARRIER

2-HR RATED FIRE BARRIER

1-HR FIRE RATED SMOKE BARRIER

SMOKE PARTITION

GC TO MODIFY EXISTING REMAIN WALLS/PARTITIONS

AS REQUIRED TO MEET FIRE RATED REQUIREMENT AS

SHOWN ON NEW FLOOR PLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592Revisions: Date:

ORIGINAL SHEET SIZE: 30" X 42"

B

IM

/1

V

A B ld g

S p in a l C o rd

I n ju ry

R e h a b A re a

/1

V A

B ld g

M E

P

F P

V

.r v t

/1

/2

:1

:2

A

M

P-101

PLUMBING SUPPLY NEW WORK

PLANS

RENOVATE BUILDING 7 SPINAL

CORD INJURY (SCI) REHAB AREA

VA MEDICAL CENTER, MEMPHIS, TN

614-19-102

BLDG 7

04/22/2020 DKH MTR

SCALE: 1/8" = 1'-0"F5

PLUMBING SUPPLY NEW WORK

GENERAL NOTES:

1. REFER TO P-001 FOR PLUMBING GENERAL NOTES,

ABBREVIATIONS, AND LEGENDS.

2. REFER G-101 FOR DEDUCTIVE ALTERNATE SCHEDULE.

N

SCALE: = 1'-0"

0 8 168

1/8"

KEYPLAN

SCALE: 1/8" = 1'-0"F1

PLUMBING NEW WORK - UNDER SECOND FLOOR

NOTE:

PLUMBING PIPING SHOWN ON THIS VIEW IS BELOW SECOND FLOOR AND ABOVE

FIRST FLOOR CEILING. SECOND FLOOR WALLS ARE OVERLAYED FOR CLARITY.

1. DOMESTIC PIPE UP FROM FLOOR BELOW. EXTEND PIPING AND

CONNECT TO ASSOCIATED PLUMBING FIXTURE(S).

2. COORDINATE COLD WATER CONNECTION BOX, CB-1, LOCATION

WITH FINAL WATER / ICE DISPENSER LOCATION. 1/2" COLD

WATER SUPPLY TO WATER / ICE DISPENSER. MAKE FINAL

CONNECTION WITH STEEL BRAIDED HOSE.

3. PIPING CONTINUES INTO AREA NOT IN PROJECT SCOPE.

4. CONNECT NEW PLUMBING FIXTURE TO EXISTING DOMESTIC

COLD WATER SUPPLY.

5. CONNECT NEW PLUMBING FIXTURE TO EXISTING DOMESTIC

COLD AND HOT WATER SUPPLY.

KEYNOTES:

PHYSICAL

THERAPY

(PT)

2C111

STORAGE

2C111A

CORRIDOR

C2-27

CHECK-IN

DESK

2C103

WAITING

2C102 PRIVATE

TREATMENT

2C104

STORAGE

2C105

DRIVER

THERAPY

2C106

MULTI-PURPOSE

ROOM

2C107

WOMEN

(PATIENT)

2C109

MEN

(PATIENT)

2C108

KINESIO-THERAPY

(KT)

2C112

OCCUPATIONAL

THERAPY

(OT)

2C113

CHARTING

2C112A

CHARTING

2C113A

EQUIP.

STORAGE

2C110

CORRIDOR

C2-28

BREAKROOM

2C114 WOMEN

(STAFF)

2C115

STORAGE

2C114A

MEN

(STAFF)

2C116

JAN

2C119

STORAGE

2C121

RECREATIONAL

THERAPY

2C120

EL

2C118

COMM

2C117

(E) 6" ST

(E) 10" ST

(E) 4" ST

(E) 6" ST

(E) 4" ST

2" S

2" S

(E) 4" S

(E) 2" S

(E) 4" S

(E) 4" S

(E) 4" S

(E) 2" S

3" S

3" S

1 1/4" S

3" S

(E) 4" S

(E) 2" S

1 1/4" S

4" S

1 1/4" S

1 1/2" S

1 1/2" S

SK-2

MS-1WC-1

SK-1

SK-1

SK-3

SK-3

WC-1

LAV-1

LAV-1

WC-1

WC-1

LAV-1

LAV-1

ELEVATOR ELEVATOR ELEVATOR

STAIR

NO 4

STAIR

NO 5

COMM

2C100

EC

2C101

CORRIDOR

C2-30

SINK, ETR

2" V

2" V

2" V

2" V

2" V

2" V

2" VTR

2" V

3" S

2" V

3" V

3" VTR

2" V

3" S

EWC-1

2" S

CB-1

AREA OF WORK

2ND FLOOR

NEW RATED WALL LEGEND

1-HR RATED FIRE BARRIER

2-HR RATED FIRE BARRIER

1-HR FIRE RATED SMOKE BARRIER

SMOKE PARTITION

GC TO MODIFY EXISTING REMAIN WALLS/PARTITIONS

AS REQUIRED TO MEET FIRE RATED REQUIREMENT AS

SHOWN ON NEW FLOOR PLAN

(E) 4" ST

(E) 8" ST

(E) 10" ST

(E) 10" ST

(E) 6" ST

(E) 4" ST

(E) 6" ST

(E) 6" ST

(E) 10" ST

(E) 6" ST

(E) 2" V

(E) 2" V

(AND CAP)

R.T. CLINIC

2C120

STORAGE

2C121

JAN. CLOSET

2C119

TOILET

2C116

DRIVER CLINIC

2C115

CORRIDOR

C2-29

COMM

2C117

EC

2C118

STORAGE

2C110A

OFFICE

2C110B

PHYSICAL THERAPY

2C110

TOILET

2C-08

MED REHAB

2C112

STORAGE/BREAK ROOM

2C112A

STORAGE

2C111B

O.T. CLINIC

2C111

OFFICE

2C111A

PRIVATE TREATMENT

2C109

K.T. CLINIC

2C107

CORRIDOR

C2-27

WHEEL CHAIR STORAGE

2C106A

OFFICE

2C107A

JAN. CLOSET

2C102

TOILET

2C104

LACK

2C103

STORAGE

2C106B

MEN TOILET

2C113

WOMEN TOILET

2C114

STORAGE

2C106

(TYP)

(TYP 3)

ELEVATOR ELEVATOR ELEVATOR

STAIR

NO 4

STAIR

NO 5

COMM

2C100

EC

2C101

CORRIDOR

C2-30

CORRIDOR

C2-28

SINK, ETR

4" VTR, ETR

2" V UP

13 13

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Designed

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Raymond-Pond SDVOSB JV, LLC 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592

POND & Company 3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092 678-336-7740

Raymond Engineering 1224 Royal Drive, Suite 100 Conyers, GA 30094 770-483-9592Revisions: Date:

ORIGINAL SHEET SIZE: 30" X 42"

B

IM

/1

V

A B ld g

S p in a l C o rd

I n ju ry

R e h a b A re a

/1

V A

B ld g

M E

P

F P

V

.r v t

/1

/2

:1

:2

A

M

P-102

PLUMBING SANITARY DEMOLITION

AND NEW WORK PLANS

RENOVATE BUILDING 7 SPINAL

CORD INJURY (SCI) REHAB AREA

VA MEDICAL CENTER, MEMPHIS, TN

614-19-102

BLDG 7

04/22/2020 DKH MTR

GENERAL NOTES:

1. REFER TO P-001 FOR PLUMBING GENERAL NOTES,

ABBREVIATIONS, AND LEGENDS.

2. REFER G-101 FOR DEDUCTIVE ALTERNATE SCHEDULE.

3. DEMOLISH ALL SANITARY AND VENT PIPING UP TO INDICATED

PENETRATIONS DOWN TO FIRST FLOOR UNLESS NOTED.

SCALE: 1/8" = 1'-0"F5

PLUMBING SANITARY NEW WORK - BELOW SECOND FLOOR

N

SCALE: = 1'-0"

0 8 168

1/8"

KEYPLAN

1. EXISTING TO REMAIN 6" STORM DRAINAGE DOWN FROM ROOF

DRAIN ABOVE TO FIRST FLOOR.

2. EXISTING TO REMAIN 8" STORM DRAINAGE DOWN FROM ROOF

DRAIN ABOVE TO FIRST FLOOR.

3. EXISTING TO REMAIN 10" STORM DRAINAGE DOWN TO FLOOR

BELOW TO FIRST FLOOR.

4. EXISTING TO REMAIN 4" SANITARY DOWN TO FLOOR BELOW.

5. 2" VTR TO BE DEMOLISHED. CAP AND SEAL PIPE ABOVE

CEILING AT NEAREST MAIN.

6. 2" VTR EXISTING TO REMAIN.

7. PIPING CONTINUES INTO AREA NOT IN PROJECT SCOPE.

8. DEMOLISH PLUMBING FIXTURE AND ASSOCIATED

APPURTENANCES.

9. DEMOLISH EXISTING FLOOR DRAIN.

10. 2" VTR TO BE DEMOLISHED. CAP AND SEAL PIPE

PENETRATIONS FOR 2 HOUR FIRE-RATING IN ASSOCIATED

FIRE-RATED BARRIER.

11. 4" VTR EXISTING TO REMAIN.

12. PROVIDE SANITARY DRAIN TO WATER / ICE DISPENSER,

MINIMUM SIZE OF EQUIPMENT DRAIN CONNECTION. ROUTE

DOWN THROUGH WALL AND CONNECT TO NEAREST SANITARY

BRANCH. PROVIDE FIRE SEALANT FOR WALL PENETRATION.

13. DEMOLISH EXISTING DRAIN CONNECTION TO MEDICAL

EQUIPMENT. PATCH AND SEAL FLOOR TO MATCH EXISTING AT

FLOOR PENETRATION.

SCALE: 1/8" = 1'-0"F1

PLUMBING SANITARY DEMOLITION - BELOW SECOND FLOOR

(E) 6" ST DN BELOW FLOOR

(E) 4" ST

BELOW FLOOR

File details come from the government source that posted it. Updated .