Fire Protection Set.pdf
PDF 670 KB Posted
- Solicitation number
- Amity 2025-4
- Issued by
- Connecticut
About this file
Fire Protection Set Summary
This is a fire protection design and demolition document prepared for the Amity Regional School District No. 5 in Bethany, Connecticut, involving the fire pump replacement project at Amity Middle School. The scope of work encompasses the complete removal of existing fire protection infrastructure, including the fire pump, jockey pump, associated piping, valves, supports, and concrete pad, followed by installation of new equipment and systems. The project requires coordination with multiple trades, including electrical and HVAC contractors, and mandates adherence to NFPA standards for sprinkler spacing, density, and placement. The drawings indicate diagrammatic layouts for upper and lower level vault floor plans with detailed schematics showing new inline electric fire pump installation, jockey pump with control panel configuration, new 6-inch fire service connections to the existing storage tank, new 4-inch fire pump test header piping, new sump pumps, and all associated supervised valves and controls. A mandatory pre-bid walkthrough appointment is required, with no appointments scheduled after 2:00 PM on Friday, November 7, 2025, and sealed proposals are due no later than Friday, November 14, 2025 at 1:00 P.M.
The document specifies that all removed equipment shall not be reused and that new installations only are permitted. Critical requirements include coordination with the Authority Having Jurisdiction (AHJ) before draining and refilling the fire protection water storage tank, implementation of fire watch procedures per local fire codes, controlled tank drainage to prevent infrastructure damage, thorough tank cleaning and inspection before refilling to NFPA 22 standards, and complete system testing and commissioning before return to service. The jockey pump controller must be listed for fire service (UL 508A) with pressure switch, motor protection, and hand-off-auto control capabilities, manufactured by Firetrol or equivalent. The fire pump shall be mounted on a new concrete pad with a Stancor Model SV-50 oil maintenance system, and all piping materials must match existing specifications. The contractor assumes responsibility for site familiarization with existing systems, coordination of service interruptions with the owner, and notification of the AHJ and building owner upon work completion.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FIRE PROTECTION ABBREVIATIONS
DESCRIPTIONSYMBOLDESCRIPTIONSYMBOL
LEGEND NOTE
THESE ARE THE GENERAL LEGENDS OF SYMBOLS AND ABBREVIATIONS, AND SHALL
BE USED AS A DICTIONARY TO DEFINE ITEMS INDICATED ON DRAWINGS. NOT ALL
SYMBOLS OR ABBREVIATIONS DEFINED ARE NECESSARILY USED ON THIS PROJECT.
THE FIRE PROTECTION CONTRACTOR IS RESPONSIBLE FOR THE FOLLOWING:
A. THESE GENERAL NOTES ARE APPLICABLE TO ALL FIRE PROTECTION DRAWINGS.
B. DRAWINGS ARE DIAGRAMMATIC AND SHOW THE GENERAL INTENT OF WORK. SEE DETAILS,
RISERS, AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.
C. THE FIRE PROTECTION DRAWINGS INDICATE A SUGGESTED SPRINKLER LAYOUT. SPRINKLERS MAY NOT BE SHOWN IN ALL AREAS. SPRINKLER QUANTITIES SHALL NOT BE COUNTED AS A TAKE OFF OR AS EXACT LOCATIONS. REFER TO NFPA STANDARDS FOR EXACT SPACING, DENSITY, AND LOCATION REQUIREMENTS. ADDITIONAL SPRINKLERS MAY BE REQUIRED IN SOME AREAS DUE TO
OBSTRUCTIONS, SUCH AS DUCTWORK, PIPING, STRUCTURAL ELEMENTS, ETC.
D. SPRINKLERS IN FINISHED CEILING AREAS SHALL ALWAYS BE LOCATED IN THE CENTER OF
CEILING TILES IN BOTH DIRECTIONS UNLESS INDICATED OTHERWISE.
E. REVIEW THE ARCHITECTURAL REFLECTED CEILING PLANS AS PART OF THIS CONTRACT FOR
ADDITIONAL INFORMATION SUCH AS CEILING HEIGHTS, TYPES, SOFFITS AND OR OTHER DEVICE
LOCATIONS.
F. REVIEW THE ELECTRICAL DIVISION DOCUMENTS AND COORDINATE THE FIRE PROTECTION WORK
WITH LOCATIONS OF LIGHTS AND CEILING MOUNTED DEVICES WHICH MAY INTERFERE WITH
SPRINKLER LOCATIONS OR SPRAY PATTERNS.
G. REVIEW THE HVAC DIVISION DOCUMENTS AND COORDINATE THE FIRE PROTECTION WORK WITH
LOCATIONS OF CEILING MOUNTED DEVICES SUCH AS DIFFUSERS, GRILLS, REGISTERS,
LOCATIONS OF HEAT PRODUCING EQUIPMENT AND DUCTWORK REQUIRING SPRINKLER
PROTECTION BELOW THEM.
H. PROVIDE PIPE EXPANSION JOINTS AT ALL BUILDING EXPANSION JOINT LOCATIONS AND
APPROVED SEISMIC EXPANSION LOOPS AT ALL BUILDING SEISMIC JOINT LOCATIONS AS
REQUIRED PER NFPA STANDARDS AND BUILDING CODES. REVIEW ARCHITECTURAL AND
STRUCTURAL DRAWINGS FOR EXACT LOCATIONS OF EXPANSION AND SEISMIC JOINTS.
I. REFER TO SITE PLAN AND CIVIL ENGINEER'S DOCUMENTS FOR ADDITIONAL INFORMATION
PERTAINING TO COORDINATION OF SITE UTILITIES, BOTH EXISTING AND NEW.
J. IN RENOVATION WORK, COORDINATE SYSTEMS SHUTDOWN WITH OWNER IN ORDER TO MAKE
NEW PIPING CONNECTIONS. ALLOW MINIMUM OF TEN (10) DAYS ADVANCE NOTICE FOR OWNER
APPROVAL TO PROCEED WITH CONTRACT WORK.
THE FIRE PROTECTION CONTRACTOR IS RESPONSIBLE FOR THE FOLLOWING:
A. VISIT THE SITE AND BECOME FAMILIAR WITH THE EXISTING SYSTEMS AND CONDITIONS IN AREAS
OF RENOVATION.
B. ALL EXISTING PIPING AND EQUIPMENT SHOWN HAS BEEN TAKEN FROM THE BEST AVAILABLE EXISTING INFORMATION. THE DRAWINGS ARE DIAGRAMMATIC AND ALL PIPING AND DEVICES MAY
NOT BE SHOWN. THE INTENT OF THE DOCUMENTS IS THAT SYSTEM EQUIPMENT AND PIPING IS
TO BE REMOVED IN ALL RENOVATED AREAS AS NOTED AND MAY NOT ALL BE SHOWN.
C. REMOVE ALL FIRE PROTECTION PIPING SYSTEMS INCLUDING BUT NOT LIMITED TO
SPRINKLER/STANDPIPE, SPRINKLERS HANGERS, VALVES, SWITCHES, AND DEVICES AS SHOWN
OR NOTED ON THE DRAWINGS. COORDINATE ALL WIRING WORK RELATED TO DEVICES BEING
REMOVED WITH ELECTRICAL CONTRACTOR.
D. ALL PIPING TO BE REMOVED SHALL BE REMOVED COMPLETELY AND CAPPED AS SHOWN
WITHOUT LEAVING ANY DEAD ENDED PIPING OR ABANDONED PIPING. SECURE IN PLACE.
E. NO FIRE PROTECTION EQUIPMENT OR DEVICES THAT HAVE BEEN DISCONNECTED OR
ABANDONED SHALL REMAIN.
F. IT IS THE INTENT OF THESE DOCUMENTS THAT ANY AND ALL DEVICES REMOVED SHALL NOT BE
REUSED, BUT ONLY NEW SHALL BE INSTALLED.
G. ANY SYSTEM OR EQUIPMENT TO REMAIN ACTIVE DURING RENOVATION SHALL BE KEPT IN
OPERATION BY PROVIDING TEMPORARY CONNECTIONS AS REQUIRED UNTIL NEW SYSTEMS ARE
INSTALLED AND OPERATIONAL.
H. ALL SERVICE INTERRUPTIONS SHALL BE COORDINATED WITH THE OWNER PRIOR TO
COMMENCEMENT OF ANY WORK.
I. THE FIRE MARSHAL AND/OR THE INSURANCE UNDERWRITER SHALL BE CONTACTED TO REVIEW
AND APPROVE THE EXTENT OR PHASING OF THE FIRE PROTECTION DEMOLITION IN ORDER TO
PROTECT THE OCCUPANTS AND PROPERTY. THESE DOCUMENTS DO NOT ADDRESS THE
PHASING OF THE SYSTEM REMOVAL, ONLY THE EXTENT.
J. REVIEW THE ARCHITECTURAL DEMOLITION DRAWINGS AS PART OF THIS CONTRACT FOR
ADDITIONAL INFORMATION AND REQUIREMENTS.
REMOVE EXISTING PIPING OR EQUIPMENT
FIRE DEPARTMENT CONNECTION PIPING
PIPE DOWN
CAPPED PIPE
PIPE DROP
PIPE UP
FIRE PUMP TEST HEADER PIPING
PREACTION SPRINKLER SYSTEM
EXISTING PIPING OR EQUIPMENT
FDC
FPTH
PA
FIRE LINE
FIRE SERVICE BURIED
WET SPRINKLER SYSTEM
DRY PIPE SPRINKLER SYSTEM
DRAIN PIPING
FLOW DIRECTION
F
SP
DRY
F
D
HD HEAT DETECTOR
TYP TYPICAL
UG
VIF
UNDERGROUND
VERIFY IN FIELD
PREACTION ALARM VALVE CABINET
REDUCED PRESSURE BACKFLOW PREVENTER ASSEMBLY
PAC
RCV
SP
SS
RPD
RR
PSI
PRV
PS
PIV
RISER CONTROL VALVE
SUPERVISORY SWITCH
REMOVE & RELOCATE
SPRINKLER
PRESSURE REGULATING VALVE
POUNDS PER SQUARE INCH
PRESSURE SWITCH
POST INDICATOR VALVE
LPS
PA
NIC
NO
NC
JPC
IT
JP
HT
LOW PRESSURE SWITCH
NOT IN CONTRACT
NORMALLY OPEN
NORMALLY CLOSED
PREACTION
JOCKEY PUMP CONTROLLER
JOCKEY PUMP
INTERMEDIATE TEMPERATURE
HIGH TEMPERATURE
CTE CONNECT TO EXISTING
FLOOR CONTROL VALVE ASSEMBLY
DOUBLE CHECK VALVE ASSEMBLY
FHC FIRE HOSE CABINET
FS
G
GPM
FVC
FSP
FHV
FPTH
FPC
FHR
FLOW SWITCH
GALLONS PER MINUTE
FIRE VALVE CABINET
FIRE STANDPIPE
CAGE GUARD
FIRE HOSE VALVE
FIRE PUMP TEST HEADER
FIRE PUMP CONTROLLER
FIRE HOSE RACK
EL
FCVA
FDC
ETR
EX
DN
EC
DCVA
DPV
ELEVATION
FIRE DEPARTMENT CONNECTION
EXISTING TO REMAIN
EXISTING
EXTENDED COVERAGE
DRY PIPE VALVE
DOWN
AFF
BOP
AFG
ATS
BFP
ACV
ABOVE FINISHED FLOOR
BOTTOM OF PIPE
ABOVE FINISHED GRADE
BACKFLOW PREVENTER
AUTOMATIC TRANSFER SWITCH
ALARM CHECK VALVE
CHECK VALVE
SMOKE DETECTOR
HEAT DETECTOR
BACKFLOW PREVENTER ASSEMBLY (DCVA) WITH SHUTOFF VALVES
PREACTION ALARM ASSEMBLY CABINET
AUTOMATIC TRANSFER SWITCH
FLOOR CONTROL VALVE ASSEMBLY
CONNECT TO EXISTING
JOCKEY PUMP CONTROLLER
FIRE PUMP CONTROLLER
BACKFLOW PREVENTER ASSEMBLY (RPD) WITH SHUTOFF VALVES
ALARM BELL
PRESSURE GAUGE
FIRE PUMP TEST HEADER (REFER TO SPECIFICATIONS FOR TYPE)
POST INDICATOR VALVE (SUPERVISED)
PRESSURE REGULATING VALVE (X = PSI SETTING)
PUMP
EXISTING SPRINKLER TO REMAIN
PRESSURE REGULATING ANGLE HOSE VALVE
ANGLE HOSE VALVE
OS&Y VALVE (SUPERVISED)
BUTTERFLY VALVE (SUPERVISED)
FIRE VALVE CABINET
LOW PRESSURE SWITCH
PRESSURE SWITCH
ALARM CHECK VALVE RISER ASSEMBLY
SPRINKLER FLOW SWITCH
DRY PIPE VALVE RISER ASSEMBLY
PREACTION VALVE RISER ASSEMBLY
EXISTING SIDEWALL SPRINKLER TO REMAIN
EXISTING SPRINKLER TO BE REMOVED
EXISTING SIDEWALL SPRINKLER TO BE REMOVED
NEW UPRIGHT SPRINKLER
NEW DRY SIDEWALL SPRINKLER
NEW PENDENT SPRINKLER
NEW CONCEALED SPRINKLER
NEW DRY PENDENT OR CONCEALED SPRINKLER
NEW WET SIDEWALL SPRINKLER
REMOTE ALARM PANEL
PRESSURE RELIEF VALVE
SUPERVISORY SWITCH (TAMPER SWITCH)
FIRE PROTECTION SYMBOLS
POST MOUNTED FIRE DEPARTMENT CONNECTION
(REFER TO SPECIFICATIONS FOR TYPE)
WALL MOUNTED FIRE DEPARTMENT CONNECTION
(REFER TO SPECIFICATIONS FOR TYPE)
E
R
A
D
PA
FS
PS
LPS
SS
PRV
NEW PENDENT SPRINKLER WITH SPRING UPRIGHT
X
FDC
FDC
ATS
FPC
JPC
PAC
RAP
FCVA
FVC
S
H
FIRE PROTECTION PIPING LEGENDFIRE PROTECTION GENERAL NOTES
FIRE PROTECTION DEMOLITION NOTES
E
R
GATE VALVE (SUPERVISED)
DATE
REV.
NO.
DRAWING TITLE:
FI
R
E P
U M
P R
E
PL
A C
E M
E N
T B
E T
H A
N Y
M
ID
D L
E S
C H
O O
L
A M
IT
Y
R
EG
IO
N
LU
K
E H
IL
L
R O
A D
B
ET
H A
N Y
, C T
DESCRIPTION
REVISIONS
PR
O
JE
C
T N
A M
E:
KEYPLAN
DRAWING NUMBER:
PROJ #: 2024090.00
DATE: 06/06/2025
CHECK BY:
DRAWN BY:
SCALE:
U se r I D
Fi le N am e:
Fi le
P at h:
FP
-0
-L G
N D
.d w g U
:\2
4\
0.
\B
IM
\C
AD
\F ire
-P ro te ct io n
6/ 5/
2:
:5
PM
R iv er a- Pe na , K ris tia n G
N
AV N E MLZ
E N G I N E E R S
VAN ZELM HEYWOOD & SHADFORD, INC.
10 TALCOTT NOTCH, FARMINGTON, CT 06032 - 1800
Connecticut | Massachusetts | North Carolina
CT: 860.284.5064 MA: 617.218.9976 NC: 704.799.7275
AMITY
ISSUED FOR BID
JUNE 06,2025
FP001
YRP
SSK/AJD
NONE
FIRE PROTECTION
LEGENDS, DETAILS
AND GENERAL NOTES
REMOVE EXISTING JOCKEY
PUMP CONTROLLER AND
ASSOCIATED CONDUIT/WIRING
BACK TO SOURCE AS REQUIRED
TO ALLOW NEW CONNECTIONS
EXISTING 4" FIRE PUMP TEST
HEAD PIPING UP TO REMAIN
EXISTING BURIED FIRE
SERVICE TO SCHOOL
TO REMAIN
SCALE:1 1/2" = 1'-0"
FIRE PROTECTION DEMOLITION UPPER LEVEL VAULT
SCALE:2 1/2" = 1'-0"
FIRE PROTECTION DEMOLITION LOWER LEVEL VAULT
SCALE:3 1/2" = 1'-0"
FIRE PROTECTION NEW WORK UPPER LEVEL VAULT
EXISTING JOCKEY PUMP
TO BE REMOVED
EXISTING BURIED FIRE
SERVICE TO SCHOOL
TO REMAIN
EXISTING FIRE SUPPLY
FROM BURIED TANK TO REMAIN
EXISTING FIRE PUMP
AND CONCRETE PAD TO
BE REMOVED
REMOVE ALL EXISTING FIRE
PROTECTION PIPING, VALVES
SUPPORTS, FIRE PUMP, JOCKEY
PUMP, CONCRETE PAD
EXISTING FIRE PUMP
TEST HEADER TO
REMAIN.
FIRE PUMP
CONTROLLER / AUTO.
TRANSFER SWITCH TO
REMAIN
(2)EXISTING SUMP PUMP
TO BE REMOVED. CUT-BACK
DISCHARGE PIPING TO ALLOW
RECONNECTION TO NEW PIPING
EXISTING FIRE PUMP
TEST HEADER TO
REMAIN
FIRE PUMP
CONTROLLER / AUTO.
TRANSFER SWITCH TO
REMAIN
*EXISTING FREESTANDING FIRE
DEPARTMENT CONNECTION LOCATED
ON SITE TO REMAIN
SCALE:4 1/2" = 1'-0"
FIRE PROTECTION NEW WORK LOWER LEVEL VAULT
FPTH PIPING UP
CONNECT NEW 6" FIRE
SERVICE TO EXISTING
FROM STORAGE TANKCOPY
FLOW METER
& FLOW
SWITCH
CONNECT NEW 6" FIRE
SERVICE TO EXISTING
NEW INLINE
ELECTRIC FIRE PUMP
NEW JOCKEY PUMP
CONNECT NEW 4" FPTH
PIPING TO EXISTING
NEW SUMP PUMPS. CONNECT NEW
DISCHARGE TO EXISTING. PIPES &
FITTINGS MATERIAL TO MATCH
EXISTING, PROVIDE STANCOR, INC.
MODEL # SV-50 PUMP
"OIL-MINDER" SYSTEM WITH
CONFIGURATION "C".
NEW SUPERVISED OS&Y
VALVE. TYPICAL
FIRE PROTECTION
CONTRACTOR TO PROVIDE
NEW CONCRETE PAD
PROVIDE ALL NEW FIRE
PROTECTION PIPING, VALVES
SUPPORTS, FIRE PUMP, JOCKEY
PUMP, CONCRETE PAD
NOTES:
1. CONTRACTOR SHALL COORDINATE WITH THE AUTHORITY HAVING JURISDICTION
(AHJ) BEFORE DRAINING AND REFILLING THE FIRE PROTECTION WATER
STORAGE TANK.
2. PRIOR TO DRAINING THE TANK, ENSURE THAT FIRE WATCH PROCEDURES ARE IN
PLACE AS REQUIRED BY LOCAL FIRE CODES.
3. TANK SHALL BE COMPLETELY DRAINED IN A CONTROLLED MANNER TO PREVENT
DAMAGE TO THE TANK AND SURROUNDING INFRASTRUCTURE.
4. AFTER INSTALLATION OF THE NEW FIRE PUMP, THE CONTRACTOR SHALL
THOROUGHLY CLEAN AND INSPECT THE TANK BEFORE REFILLING.
5. TANK SHALL BE REFILLED TO THE REQUIRED CAPACITY PER NFPA 22
STANDARDS, ENSURING PROPER WATER QUALITY.
6. PERFORM NECESSARY TESTING AND COMMISSIONING OF THE FIRE PUMP AND
VERIFY PROPER OPERATION OF ASSOCIATED PIPING AND VALVES.
7. NOTIFY THE AHJ AND BUILDING OWNER UPON COMPLETION OF WORK AND
BEFORE RETURNING THE SYSTEM TO SERVICE.
8. FURNISHED AND INSTALL JOCKEY PUMP WITH CONTROL PANEL AS
MANUFACTURED BY FIRETROL OR EQUAL.
9. FURNISH AND INSTALL JOCKEY PUMP WITH CONTROL PANEL AS MANUFACTURED
BY FIRETROL OR EQUAL; WITH DISCONNECT H-O-A SWITCH WITH PILOT LIGHT,
AND RUN TIMER
NEW JOCKEY PUMP CONTROLLER
LISTED FOR FIRE SERVICE (UL 508A),
WITH PRESSURE SWITCH, MOTOR
PROTECTION, AND HAND-OFF-AUTO
CONTROL. COORDINATE WITH FIRE
PUMP CONTROLLER AND FIRE ALARM
SYSTEM AS REQUIRED. TEST AND
COMMISSION COMPLETE SYSTEM.
DATE
REV.
NO.
DRAWING TITLE:
FI
R
E P
U M
P R
E
PL
A C
E M
E N
T B
E T
H A
N Y
M
ID
D L
E S
C H
O O
L
A M
IT
Y
R
EG
IO
N
LU
K
E H
IL
L
R O
A D
B
ET
H A
N Y
, C T
DESCRIPTION
REVISIONS
PR
O
JE
C
T N
A M
E:
KEYPLAN
DRAWING NUMBER:
PROJ #: 2024090.00
DATE: 06/06/2025
CHECK BY:
DRAWN BY:
SCALE:
U se r I D
Fi le N am e:
Fi le
P at h:
FP
-1
-F L0
1.
dw g U
:\2
4\
0.
\B
IM
\C
AD
\F ire
-P ro te ct io n
6/ 5/
2:
:0
PM
R iv er a- Pe na , K ris tia n G
N
AV N E MLZ
E N G I N E E R S
VAN ZELM HEYWOOD & SHADFORD, INC.
10 TALCOTT NOTCH, FARMINGTON, CT 06032 - 1800
Connecticut | Massachusetts | North Carolina
CT: 860.284.5064 MA: 617.218.9976 NC: 704.799.7275
AMITY
ISSUED FOR BID
JUNE 06,2025
FP101
YRP
SSK/AJD
1/2"=1'-0"
FIRE PROTECTION
UPPER AND LOWER
LEVEL VAULT
FLOOR PLANS
SS
SS
SS
SS
SS
SS
SS
SS
JPC
SCALE:1 1/2" = 1'-0"
FIRE PROTECTION SYSTEM SCHEMATIC DETAIL
PS
SS
FS
SS
SS
SS
SS
SS
SS
FLOW
METER
N.O.
DRAIN
N.O.
N.C.
2"
6"
6"
6"
N.C.
AUTO AIR
RELEASE
IF REQ'D
J.P.
N.O.
N.O.N.O.
EXISTING WALL MOUNTED FIRE
PUMP TEST HEADER ASSEMBLY
SERVICE VALVE
BURIED FIRE SERVICE
FINISHED GRADE
JOCKEY PUMP BOLTED
TO CONCRETE PAD
AUTOMATIC AIR RELIEF VALVE
ECCENTRIC REDUCER
PRESSURE GAUGE
TO MAIN RELIEF
VALVE IF REQ'D.
REFER TO
SPECIFICATIONS
CONCENTRIC REDUCER
TYPICAL HOUSEKEEPING PAD
FIRE PUMP BOLTED TO
CONCRETE PAD.
REFER TO SPECIFICATIONS
CORROSION RESISTANT
SENSING TUBING TO FIRE
PUMP CONTROLLER
CORROSION RESISTANT
SENSING TUBING TO
JOCKEY PUMP CONTROLLER
PIPE STAND WITH
SADDLE, BOLTED TO
FLOOR (TYPICAL)
LOW WATER PRESSURE
SUPERVISORY SWITCH
WHEN REQUIRED BY
AUTHORITY HAVING
JURISDICTION
TEST LOOP FOR
TESTING FIRE PUMP
WET PIPE SUPPLY TO FIRE
PROTECTION SYSTEM. TIE
INTO EXISTING
FLOW
SWITCH
SS
N.C.
FINISHED FLOOR
2"
METER THROTTLE
VALVE (MUST BE
OS&Y TYPE)
6"
6" 4"
6"
TIE INTO EXISTING
TIE INTO EXISTING
DATE
REV.
NO.
DRAWING TITLE:
FI
R
E P
U M
P R
E
PL
A C
E M
E N
T B
E T
H A
N Y
M
ID
D L
E S
C H
O O
L
A M
IT
Y
R
EG
IO
N
LU
K
E H
IL
L
R O
A D
B
ET
H A
N Y
, C T
DESCRIPTION
REVISIONS
PR
O
JE
C
T N
A M
E:
KEYPLAN
DRAWING NUMBER:
PROJ #: 2024090.00
DATE: 06/06/2025
CHECK BY:
DRAWN BY:
SCALE:
U se r I D
Fi le N am e:
Fi le
P at h:
FP
-2
-D et ai l.d w g
U :\2
4\
0.
\B
IM
\C
AD
\F ire -P ro te ct io n 6/
5/
2:
:0
PM
R iv er a-
Pe na
, K ris tia n
G
N
AV N E MLZ
E N G I N E E R S
VAN ZELM HEYWOOD & SHADFORD, INC.
10 TALCOTT NOTCH, FARMINGTON, CT 06032 - 1800
Connecticut | Massachusetts | North Carolina
CT: 860.284.5064 MA: 617.218.9976 NC: 704.799.7275
AMITY
ISSUED FOR BID
JUNE 06,2025
FP200
YRP
SSK/AJD
1/2"=1'-0"
FIRE PROTECTION
DETAIL
| Sheets and Views |
| FP-001-LGND-FP-001 |
| FP-101-FL01-FP-101 |
| FP-200-Detail-FP-200 |
File details come from the government source that posted it. Updated .