213400 - PRESSURE-MAINTENANCE PUMPS.pdf

PDF 44 KB Posted

Attached to
Amity Middle School Bethany Fire Pump Replacement
Solicitation number
Amity 2025-4
Issued by
Connecticut

About this file

This is a technical specification document for pressure-maintenance pumps prepared by Bethany Middle School in Connecticut as part of a fire pump replacement project under Amity Regional School District No. 5's Request for Proposal Amity 2025-4. The specification details the requirements for multistage pressure-maintenance pumps, jockey pumps, and associated controllers to be installed at the school. The primary product specified is a Pentair Pump Group jockey pump, Model PVM1-10, with a rated capacity of 5.00 gallons per minute, total dynamic head of 110.0 psi, 1.50 horsepower motor operating at 3500 rpm, and 460V three-phase 60Hz electrical characteristics. The specification also requires an Eaton Lite Model XTJL-1.5D jockey pump controller rated for 1.5 horsepower at 460V, three phase, 50/60 Hz operation with a main circuit breaker. Sealed proposals are due no later than Friday, November 14, 2025 at 1:00 P.M., with a mandatory pre-bid walkthrough required by appointment only, with no appointments scheduled after 2:00 PM on Friday, November 7, 2025.

The specification establishes comprehensive performance and quality requirements including minimum pressure ratings of 175 psig, compliance with NFPA 20 and FM Global standards for installation, and field quality control procedures requiring manufacturer's factory-authorized service representatives to inspect, test, and adjust all components. Installation requirements include concrete base mounting with dowel rods on 18-inch centers and epoxy-coated anchor bolts, operational testing to confirm proper motor rotation, and control and safety adjustments. All electrical components must be listed and labeled as defined in NFPA 70 by qualified testing agencies. Contractors must submit product data, shop drawings with detailed equipment assemblies and wiring diagrams, field quality control reports, and operation and maintenance data as part of closeout submittals.

View the file

Other files

Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TABLE OF CONTENTS

SECTION 213400 – PRESSURE MAINTENANCE PUMPS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

1.2 SUMMARY

1.3 PERFORMANCE REQUIREMENTS

1.4 ACTION SUBMITTALS

1.5 INFORMATIONAL SUBMITTALS

1.6 CLOSEOUT SUBMITTALS

1.7 QUALITY ASSURANCE

1.8 COORDINATION

PART 2 - PRODUCTS

2.1 MULTISTAGE, PRESSURE-MAINTENANCE PUMPS

2.2 JOCKEY PUMP

2.3 JOCKEY PUMP CONTROLLER

2.4 MOTORS

PART 3 - EXECUTION

3.1 EQUIPMENT INSTALLATION

3.2 FIELD QUALITY CONTROL

3.3 ADJUSTING

BETHANY MIDDLE SCHOOL JUNE 6, 2025

FIRE PUMP REPLACEMENT VAN ZELM #2024090.00

PRESSURE-MAINTENANCE PUMPS 213400 - 1

SECTION 213400 - PRESSURE-MAINTENANCE PUMPS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Multistage, pressure-maintenance pumps.

2. Jockey Pump Controller.

1.3 PERFORMANCE REQUIREMENTS

A. Pump Equipment, Accessory, and Specialty Pressure Rating: 175 psig minimum unless higher pressure rating is indicated.

1.4 ACTION SUBMITTALS

A. Product Data: For each type of product indicated. Include rated capacities, operating characteristics, performance curves, electrical characteristics, and furnished specialties and accessories.

B. Shop Drawings: For pumps, accessories, and specialties. Include plans, elevations, sections, details, and attachments to other work.

1. Detail equipment assemblies and indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection.

2. Wiring Diagrams: For power, signal, and control wiring.

1.5 INFORMATIONAL SUBMITTALS

A. Field quality-control reports.

1.6 CLOSEOUT SUBMITTALS

A. Operation and Maintenance Data: For pumps to include in operation and maintenance manuals.

PRESSURE-MAINTENANCE PUMPS 213400 - 2

1.7 QUALITY ASSURANCE

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

1.8 COORDINATION

A. Coordinate sizes and locations of concrete bases with actual equipment provided.

PART 2 - PRODUCTS

2.1 MULTISTAGE, PRESSURE-MAINTENANCE PUMPS

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. Pentair Pump Group.

2.2 JOCKEY PUMP

A. Nameplate: Permanently attached to pump and indicating capacity and characteristics. If Project has more than one type or configuration of multistage, pressure-maintenance pump, delete paragraph below and schedule pressure-maintenance pumps on Drawings

B. Model: PVM1-10, Stackable cast iron, NPT threaded /flanged

C. Capacities and Characteristics:

1. Rated Capacity: 5.00 gpm

2. Total Dynamic Head: 110.0 psi

3. Inlet and Outlet Size: NPS 1-1/4

4. Discharge and Suction Flanges: Class 250.

5. Motor Horsepower: 1.50 hp

6. Motor Speed: 3500 rpm

7. Electrical Characteristics:

a. Volts: 460 V

b. Phases: Three.

c. Hertz: 60.

2.3 JOCKEY PUMP CONTROLLER

A. Description: Eaton Lite Model XTJL-1.5D, Across- the- line, 460v, 3 phase, 50/60 Hz, 1.5 Hp, manufacturer model number XTJL-1.5D-L1. Provide main circuit breaker.

http://www.specagent.com/LookUp/?uid=123456817686&mf=04&src=wd

PRESSURE-MAINTENANCE PUMPS 213400 - 3

2.4 MOTORS

A. Comply with NEMA designation, temperature rating, service factor, enclosure type, and efficiency requirements for motors specified in Section 210513 "Common Motor Requirements for Fire Suppression Equipment."

1. Motor Sizes: Minimum size as indicated; if not indicated, large enough so driven load will not require motor to operate in service factor range above 1.0.

PART 3 - EXECUTION

3.1 EQUIPMENT INSTALLATION

A. NFPA Standard: Comply with NFPA 20 and FM Global for installation of pressure-maintenance pumps.

B. Base-Mounted Pump Mounting: Install pumps on concrete bases. Comply with requirements for concrete bases specified.

1. Install dowel rods to connect concrete base to concrete floor. Unless otherwise indicated, install dowel rods on 18-inch centers around the full perimeter of concrete base.

2. For supported equipment, install epoxy-coated anchor bolts that extend through concrete base and anchor into structural concrete floor.

3. Place and secure anchorage devices. Use setting drawings, templates, diagrams, instructions, and directions furnished with items to be embedded.

4. Install anchor bolts to elevations required for proper attachment to supported equipment.

5. Attach pumps to equipment base using anchor bolts.

C. Install multistage, pressure-maintenance pumps according to HI 1.4.

3.2 FIELD QUALITY CONTROL

A. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect, test, and adjust components, assemblies, and equipment installations, including connections.

B. Perform tests and inspections.

1. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect components, assemblies, and equipment installations, including connections, and to assist in testing.

C. Tests and Inspections:

1. Operational Test: After electrical circuitry has been energized, start units to confirm proper motor rotation and unit operation.

2. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment.

PRESSURE-MAINTENANCE PUMPS 213400 - 4

D. Pressure-maintenance pumps will be considered defective if they do not pass tests and inspections.

E. Prepare test and inspection reports.

3.3 ADJUSTING

A. Lubricate pumps as recommended by manufacturer.

B. Set field-adjustable pressure-switch ranges as indicated.

END OF SECTION

PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Multistage, pressure-maintenance pumps.
2. Jockey Pump Controller.
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.3 PERFORMANCE REQUIREMENTS
A. Pump Equipment, Accessory, and Specialty Pressure Rating: 175 psig minimum unless higher pressure rating is indicated.
1.4 ACTION SUBMITTALS
A. Product Data: For each type of product indicated. Include rated capacities, operating characteristics, performance curves, electrical characteristics, and furnished specialties and accessories.
B. Shop Drawings: For pumps, accessories, and specialties. Include plans, elevations, sections, details, and attachments to other work.
1. Detail equipment assemblies and indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection.
2. Wiring Diagrams: For power, signal, and control wiring.
1.5 INFORMATIONAL SUBMITTALS
A. Field quality-control reports.
1.6 CLOSEOUT SUBMITTALS
A. Operation and Maintenance Data: For pumps to include in operation and maintenance manuals.
1.7 QUALITY ASSURANCE
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
1.8 COORDINATION
A. Coordinate sizes and locations of concrete bases with actual equipment provided.
PART 1 - PRODUCTS
PART 2 -
2.1 MULTISTAGE, PRESSURE-MAINTENANCE PUMPS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1.
1. Pentair Pump Group
1.
1.
1. .
1.1
1.1
1.1
2.2 JOCKEY PUMP
A. Nameplate: Permanently attached to pump and indicating capacity and characteristics. If Project has more than one type or configuration of multistage, pressure-maintenance pump, delete paragraph below and schedule pressure-maintenance pumps on Dra...
A.
A.
A.
A.
A.
A.
A.
A.
A.
A.
A.
A.
B. Model: PVM1-10, Stackable cast iron, NPT threaded /flanged
C. Capacities and Characteristics:
1. Rated Capacity: 5.00 gpm
2. Total Dynamic Head: 110.0 psi
1.
3. Inlet and Outlet Size: NPS 1-1/4
4. Discharge and Suction Flanges: Class 250.
1.
5. Motor Horsepower: 1.50 hp
6. Motor Speed: 3500 rpm
7. Electrical Characteristics:
a. Volts: 460 V
b. Phases: Three.
c. Hertz: 60.
2.3 JOCKEY PUMP CONTROLLER
A. Description: Eaton Lite Model XTJL-1.5D, Across- the- line, 460v, 3 phase, 50/60 Hz, 1.5 Hp, manufacturer model number XTJL-1.5D-L1. Provide main circuit breaker.
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
2.4 MOTORS
A. Comply with NEMA designation, temperature rating, service factor, enclosure type, and efficiency requirements for motors specified in Section 210513 "Common Motor Requirements for Fire Suppression Equipment."
1. Motor Sizes: Minimum size as indicated; if not indicated, large enough so driven load will not require motor to operate in service factor range above 1.0.
PART 3 - EXECUTION
3.1 EQUIPMENT INSTALLATION
A.
A.
A. NFPA Standard: Comply with NFPA 20 and FM Global for installation of pressure-maintenance pumps.
B. Base-Mounted Pump Mounting: Install pumps on concrete bases. Comply with requirements for concrete bases specified.
1. Install dowel rods to connect concrete base to concrete floor. Unless otherwise indicated, install dowel rods on 18-inch centers around the full perimeter of concrete base.
2. For supported equipment, install epoxy-coated anchor bolts that extend through concrete base and anchor into structural concrete floor.
3. Place and secure anchorage devices. Use setting drawings, templates, diagrams, instructions, and directions furnished with items to be embedded.
4. Install anchor bolts to elevations required for proper attachment to supported equipment.
5. Attach pumps to equipment base using anchor bolts.

C. Install multistage, pressure-maintenance pumps according to HI 1.4.

1.1
3.2 FIELD QUALITY CONTROL
A. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect, test, and adjust components, assemblies, and equipment installations, including connections.
B. Perform tests and inspections.
1. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect components, assemblies, and equipment installations, including connections, and to assist in testing.
C. Tests and Inspections:
1. Operational Test: After electrical circuitry has been energized, start units to confirm proper motor rotation and unit operation.
2. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment.
D. Pressure-maintenance pumps will be considered defective if they do not pass tests and inspections.
E. Prepare test and inspection reports.
3.3 ADJUSTING
A. Lubricate pumps as recommended by manufacturer.
B. Set field-adjustable pressure-switch ranges as indicated.

Blank Page