This is a technical specification document for electric-drive centrifugal fire pumps for the Amity Regional School District No. 5's fire pump replacement project at Amity Middle School in Bethany, Connecticut. The specification details the requirements for a split-case vertical inline centrifugal fire pump system with associated accessories, including an Aurora inline model 4-383-9B pump with a rated capacity of 500 gallons per minute and total rated head of 231 feet. The pump must be driven by a 50 horsepower motor operating at 3,560 rpm with three-phase electrical characteristics at 460 volts and 60 hertz. The project requires sealed proposals due no later than Friday, November 14, 2025 at 1:00 p.m., with a mandatory pre-bid walkthrough available by appointment only prior to 2:00 p.m. on Friday, November 7, 2025. The specification mandates compliance with NFPA 20 standards for fire pump installation and seismic performance requirements per ASCE/SEI 7, with all equipment to be factory-assembled and tested before shipping with red paint finish applied.
The specification requires manufacturers to be approved from a limited list, with Pentair Pump Group and Aurora Pump identified as acceptable suppliers. All components, including automatic air-release valves, circulation relief valves, and relief valves from manufacturers such as CLA-VAL or Kunkle Valve, must meet UL and FM Global requirements. The flowmeter system must be UL-listed and FM-approved with a capacity indication of at least 175 percent of the pump's rated capacity, with Global Vision model 6-500-GLF designated as the basis of design. Installation requirements include concrete base mounting with dowel rods on 18-inch centers, epoxy-coated anchor bolts, and comprehensive field quality control testing including leak tests and operational tests. A factory-authorized service representative must be engaged for inspection, testing, startup service, and training of the owner's maintenance personnel, with all costs and responsibilities falling to the contractor performing the work.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TABLE OF CONTENTS
SECTION 213113 – ELECTRIC-DRIVE, CENTRIFUGAL FIRE PUMPS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
1.2 SUMMARY
1.3 PERFORMANCE REQUIREMENTS
1.4 ACTION SUBMITTALS
1.5 INFORMATIONAL SUBMITTALS
1.6 CLOSEOUT SUBMITTALS
1.7 QUALITY ASSURANCE
1.8 COORDINATION
PART 2 - PRODUCTS
2.1 GENERAL REQUIREMENTS FOR CENTRIFUGAL FIRE PUMPS
2.2 INLINE FIRE PUMP VERTICAL INLINE CENTRIFUGAL FIRE PUMPS
2.3 FIRE-PUMP ACCESSORIES AND SPECIALTIES
2.4 FLOWMETER SYSTEMS
2.5 GROUT
2.6 SOURCE QUALITY CONTROL
PART 3 - EXECUTION
3.1 EXAMINATION
3.2 INSTALLATION
3.3 ALIGNMENT
3.4 CONNECTIONS
3.5 IDENTIFICATION
3.6 FIELD QUALITY CONTROL
3.7 STARTUP SERVICE
3.8 DEMONSTRATION
BETHANY MIDDLE SCHOOL JUNE 6, 2025
FIRE PUMP REPLACEMENT VAN ZELM #2024090.00
ELECTRIC-DRIVE, CENTRIFUGAL FIRE PUMPS 213113 - 1
SECTION 213113 - ELECTRIC-DRIVE, CENTRIFUGAL FIRE PUMPS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Split-case fire pumps.
2. Fire-pump accessories and specialties.
3. Flowmeter systems.
1.3 PERFORMANCE REQUIREMENTS
A. Seismic Performance: Fire pumps shall withstand the effects of earthquake motions determined according to ASCE/SEI 7.
1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces specified and the unit will be fully operational after the seismic event.
B. Pump Equipment, Accessory, and Specialty Pressure Rating: 175 psig minimum unless higher pressure rating is indicated.
1.4 ACTION SUBMITTALS
A. Product Data: For each type of product indicated. Include rated capacities, operating characteristics, performance curves, electrical characteristics, and furnished specialties and accessories.
B. Shop Drawings: For fire pumps, motor drivers, and fire-pump accessories and specialties.
Include plans, elevations, sections, details, and attachments to other work.
1. Detail equipment assemblies and indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection.
2. Wiring Diagrams: For power, signal, and control wiring.
ELECTRIC-DRIVE, CENTRIFUGAL FIRE PUMPS 213113 - 2
1.5 INFORMATIONAL SUBMITTALS
A. Product Certificates: For each fire pump, from manufacturer.
B. Source quality-control reports.
C. Field quality-control reports.
1.6 CLOSEOUT SUBMITTALS
A. Operation and Maintenance Data: For fire pumps to include in operation and maintenance manuals.
1.7 QUALITY ASSURANCE
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
B. NFPA Compliance: Comply with NFPA 20, "Installation of Stationary Pumps for Fire Protection."
1.8 COORDINATION
A. Coordinate sizes and locations of concrete bases with actual equipment provided.
PART 2 - PRODUCTS
2.1 GENERAL REQUIREMENTS FOR CENTRIFUGAL FIRE PUMPS
A. Description: Factory-assembled and -tested fire-pump and driver unit.
B. Base: Fabricated and attached to fire-pump and driver unit with reinforcement to resist movement of pump during seismic events when base is anchored to building substrate.
C. Finish: Red paint applied to factory-assembled and -tested unit before shipping.
2.2 INLINE FIRE PUMP VERTICAL INLINE CENTRIFUGAL FIRE PUMPS
A. Manufacturers: Subject to compliance with requirements, provide products by the following:
1. Pentair Pump Group; Aurora Pump.
B. Pump:
1. Aurora inline: 4-383-9B, Bronze fitted with cast iron casing.
http://www.specagent.com/LookUp/?uid=123456817686&mf=04&src=wd
ELECTRIC-DRIVE, CENTRIFUGAL FIRE PUMPS 213113 - 3
a. Bronze impeller, bronze case wear ring, packing gland and shaft sleeve Bronze casing rings.
b. Flange rating (Suction/Discharge): (Suction5/Discharge4) 125/125 lb
c. Suction pressure : 8 psi
d. Casing relief valve: UL listed and FM approved. Cia-Val
C. Automatic Air-Release Valves: Comply with NFPA 20 for installation in fire-pump casing.
D. Circulation Relief Valves: UL 1478, brass, spring loaded; for installation in pump discharge piping.
E. Capacities and Characteristics:
1. Rated Capacity: 500 gpm
2. Total Rated Head: 231 FT
3. Inlet Flange: Class 125
4. Outlet Flange: Class 125
5. Suction Head Available at Pump: 8 PSI
6. Motor Horsepower: 50 hp
7. Motor Speed: 3560 rpm.
8. Electrical Characteristics:
a. Volts: 460 V.
b. Phase: Three.
c. Hertz: 60.
2.3 FIRE-PUMP ACCESSORIES AND SPECIALTIES
A. Automatic Air-Release Valves: Comply with NFPA 20 and FM Global requirements for installation in fire-pump casing.
B. Circulation Relief Valves: UL 1478, brass, spring loaded; for installation in pump discharge piping.
C. Relief Valves:
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. CLA-VAL Automatic Control Valves.
b. Kunkle Valve; a part of Tyco International Ltd.
2. Description: UL 1478, bronze or cast iron, spring loaded; for installation in fire-suppression water-supply piping.
D. Inlet Fitting: Eccentric tapered reducer at pump suction inlet.
E. Outlet Fitting: Concentric tapered reducer at pump discharge outlet.
F. Hose Valve Manifold Assembly:
http://www.specagent.com/LookUp/?uid=123456802746&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456817623&mf=04&src=wd
ELECTRIC-DRIVE, CENTRIFUGAL FIRE PUMPS 213113 - 4
1. Standard: Comply with requirements in NFPA 20 and FM Global requirements.
2. Header Pipe: ASTM A 53/A 53M, Schedule 40, galvanized steel with ends threaded according to ASME B1.20.1.
3. Header Pipe Fittings: ASME B16.4, galvanized cast-iron threaded fittings.
4. Automatic Drain Valve: UL 1726.
5. Manifold:
a. Adapters and Caps with Chain: Brass or bronze, with outlet threaded according to NFPA 1963 and matching local fire-department threads.
b. Hose Valves: UL 668, bronze, with outlet threaded according to NFPA 1963 and matching local fire-department threads.
c. Test Connections: Comply with UL 405 except provide outlets without clappers instead of inlets.
d. Body: Exposed type with number of outlets required by NFPA 20.
e. Escutcheon Plate Marking: Equivalent to "FIRE PUMP TEST."
2.4 FLOWMETER SYSTEMS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: Basis of design is Global Vision, 6-500-GLF.
1. Gerand Engineering Co.
2. Hydro Flow Products, Inc.
3. Victaulic Company.
B. Description: UL-listed and FM-Approved, fire-pump flowmeter system with capability to indicate flow to not less than 175 percent of fire-pump rated capacity.
C. Pressure Rating: 500 psig
D. Sensor: venturi unless otherwise indicated. Sensor size shall match pipe, tubing, flowmeter, and fittings.
E. Permanently Mounted Flowmeter: Compatible with flow sensor; with dial not less than 4-1/2 inches in diameter.
1. Tubing Package: NPS 1/8 or NPS 1/4 soft copper tubing with copper or brass fittings and valves.
2.5 GROUT
A. Standard: ASTM C 1107, Grade B, post-hardening and volume-adjusting, dry, hydraulic-cement grout.
B. Characteristics: Nonshrink and recommended for interior and exterior applications.
C. Design Mix: 5000-psi, 28-day compressive strength.
D. Packaging: Premixed and factory packaged.
http://www.specagent.com/LookUp/?uid=123456802749&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802750&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456802754&mf=04&src=wd
ELECTRIC-DRIVE, CENTRIFUGAL FIRE PUMPS 213113 - 5
2.6 SOURCE QUALITY CONTROL
A. Testing: Test and inspect fire pumps according to UL 448 requirements for "Operation Test" and "Manufacturing and Production Tests."
1. Verification of Performance: Rate fire pumps according to UL 448.
B. Fire pumps will be considered defective if they do not pass tests and inspections.
C. Prepare test and inspection reports.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine equipment bases and anchorage provisions, with Installer present, for compliance with requirements and for conditions affecting performance of fire pumps.
B. Examine roughing-in for fire-suppression piping systems to verify actual locations of piping connections before fire-pump installation.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 INSTALLATION
A. Fire-Pump Installation Standard: Comply with NFPA 20 for installation of fire pumps, relief valves, and related components.
B. Equipment Mounting: Install fire pumps on concrete bases. Comply with requirements for concrete bases.
1. Install dowel rods to connect concrete base to concrete floor. Unless otherwise indicated, install dowel rods on 18-inch centers around the full perimeter of concrete base.
2. For supported equipment, install epoxy-coated anchor bolts that extend through concrete base and anchor into structural concrete floor.
3. Place and secure anchorage devices. Use setting drawings, templates, diagrams, instructions, and directions furnished with items to be embedded.
4. Install anchor bolts to elevations required for proper attachment to supported equipment.
C. Install fire-pump suction and discharge piping equal to or larger than sizes required by NFPA 20 and FM Global.
D. Support piping and pumps separately so weight of piping does not rest on pumps.
E. Install valves that are same size as connecting piping. Comply with requirements for fire-protection valves specified.
F. Install pressure gages on fire-pump suction and discharge flange pressure-gage tappings.
Comply with requirements for pressure gages specified.
ELECTRIC-DRIVE, CENTRIFUGAL FIRE PUMPS 213113 - 6
G. Install piping hangers and supports, anchors, valves, gages, and equipment supports according to NFPA 20 and FM Global requirements.
H. Install flowmeters and sensors. Install flowmeter-system components and make connections according to NFPA 20, FM Global and manufacturer's written instructions.
I. Electrical Wiring: Install electrical devices furnished by equipment manufacturers but not factory mounted. Furnish copies of manufacturers' wiring diagram submittals to electrical Installer.
J. Wiring Method: Conceal conductors and cables in accessible ceilings, walls, and floors where possible.
3.3 ALIGNMENT
A. Align split-case pump and driver shafts after complete unit has been leveled on concrete base, grout has set, and anchor bolts have been tightened.
B. After alignment is correct, tighten anchor bolts evenly. Fill baseplate completely with grout, with metal blocks and shims or wedges in place. Tighten anchor bolts after grout has hardened.
Check alignment and make required corrections.
C. Align piping connections.
D. Align pump and driver shafts for angular and parallel alignment and to tolerances specified by manufacturer.
3.4 CONNECTIONS
A. Comply with requirements for piping and valves specified. Drawings indicate general arrangement of piping, fittings, and specialties.
B. Install piping adjacent to pumps and equipment to allow service and maintenance.
C. Connect relief-valve discharge to drainage piping or point of discharge.
D. Connect flowmeter-system meters, sensors, and valves to tubing.
E. Connect fire pumps to their controllers.
3.5 IDENTIFICATION
A. Identify system components. Comply with requirements for fire-pump marking according to NFPA 20 and FM Global.
ELECTRIC-DRIVE, CENTRIFUGAL FIRE PUMPS 213113 - 7
3.6 FIELD QUALITY CONTROL
A. Test each fire pump with its controller as a unit. Comply with requirements for electric-motor-driver fire-pump controllers specified in Section 213900 "Controllers for Fire-Pump Drivers."
B. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect, test, and adjust components, assemblies, and equipment installations, including connections.
C. Perform tests and inspections.
1. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect components, assemblies, and equipment installations, including connections, and to assist in testing.
D. Tests and Inspections:
1. After installing components, assemblies, and equipment including controller, test for compliance with requirements.
2. Test according to NFPA 20 and FM Global for acceptance and performance testing.
3. Leak Test: After installation, charge system and test for leaks. Repair leaks and retest until no leaks exist.
4. Operational Test: After electrical circuitry has been energized, start units to confirm proper motor rotation and unit operation.
5. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment.
E. Components, assemblies, and equipment will be considered defective if they do not pass tests and inspections.
F. Prepare test and inspection reports.
G. Furnish fire hoses in number, size, and length required to reach storm drain or other acceptable location to dispose of fire-pump test water. Hoses are for tests only and do not convey to Owner.
3.7 STARTUP SERVICE
A. Engage a factory-authorized service representative to perform startup service.
1. Complete installation and startup checks according to manufacturer's written instructions.
3.8 DEMONSTRATION
A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain fire pumps.
END OF SECTION
| PART 1 - GENERAL |
| 1.1 RELATED DOCUMENTS |
| A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. |
| 1.2 SUMMARY |
| A. Section Includes: |
| 1. Split-case fire pumps. |
| 2. Fire-pump accessories and specialties. |
| 3. Flowmeter systems. |
| 1.3 PERFORMANCE REQUIREMENTS |
| A. Seismic Performance: Fire pumps shall withstand the effects of earthquake motions determined according to ASCE/SEI 7. |
| 1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces specified and the unit will be fully operational after the seismic event. |
B. Pump Equipment, Accessory, and Specialty Pressure Rating: 175 psig minimum unless higher pressure rating is indicated.
| 1.4 ACTION SUBMITTALS |
| A. Product Data: For each type of product indicated. Include rated capacities, operating characteristics, performance curves, electrical characteristics, and furnished specialties and accessories. |
| B. Shop Drawings: For fire pumps, motor drivers, and fire-pump accessories and specialties. Include plans, elevations, sections, details, and attachments to other work. |
| 1. Detail equipment assemblies and indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection. |
| 2. Wiring Diagrams: For power, signal, and control wiring. |
| 1.5 INFORMATIONAL SUBMITTALS |
| A. |
| A. |
| A. |
| A. |
| A. |
| A. |
| A. Product Certificates: For each fire pump, from manufacturer. |
| B. Source quality-control reports. |
| C. Field quality-control reports. |
| 1.6 CLOSEOUT SUBMITTALS |
| A. Operation and Maintenance Data: For fire pumps to include in operation and maintenance manuals. |
| 1.7 QUALITY ASSURANCE |
| A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. |
| B. NFPA Compliance: Comply with NFPA 20, "Installation of Stationary Pumps for Fire Protection." |
| 1.8 COORDINATION |
| A. Coordinate sizes and locations of concrete bases with actual equipment provided. |
| PART 2 - PRODUCTS |
| 2.1 GENERAL REQUIREMENTS FOR CENTRIFUGAL FIRE PUMPS |
| A. Description: Factory-assembled and -tested fire-pump and driver unit. |
| B. Base: Fabricated and attached to fire-pump and driver unit with reinforcement to resist movement of pump during seismic events when base is anchored to building substrate. |
| C. Finish: Red paint applied to factory-assembled and -tested unit before shipping. |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 2.2 INLINE FIRE PUMP VERTICAL INLINE CENTRIFUGAL FIRE PUMPS |
| A. Manufacturers: Subject to compliance with requirements, provide products by the following: |
| 1. |
| 1. Pentair Pump Group; Aurora Pump. |
| A. |
| A. |
| A. |
| A. |
| A. |
| A. |
| A. |
| A. |
| A. |
| A. |
| B. Pump: |
| 1. Aurora inline: 4-383-9B, Bronze fitted with cast iron casing. |
| a. Bronze impeller, bronze case wear ring, packing gland and shaft sleeve Bronze casing rings. |
| b. Flange rating (Suction/Discharge): (Suction5/Discharge4) 125/125 lb |
| c. Suction pressure : 8 psi |
| d. Casing relief valve: UL listed and FM approved. Cia-Val |
| C. Automatic Air-Release Valves: Comply with NFPA 20 for installation in fire-pump casing. |
| D. Circulation Relief Valves: UL 1478, brass, spring loaded; for installation in pump discharge piping. |
| E. Capacities and Characteristics: |
| 1. Rated Capacity: 500 gpm |
| 2. Total Rated Head: 231 FT |
| 3. Inlet Flange: Class 125 |
| 4. Outlet Flange: Class 125 |
| 5. Suction Head Available at Pump: 8 PSI |
| 6. Motor Horsepower: 50 hp |
| 7. Motor Speed: 3560 rpm. |
| 8. Electrical Characteristics: |
| a. Volts: 460 V. |
| b. Phase: Three. |
| a. Hertz: 60. |
| a. |
| a. |
| a. |
| a. |
| c. |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 1.1 |
| 2.3 FIRE-PUMP ACCESSORIES AND SPECIALTIES |
| A. Automatic Air-Release Valves: Comply with NFPA 20 and FM Global requirements for installation in fire-pump casing. |
| B. Circulation Relief Valves: UL 1478, brass, spring loaded; for installation in pump discharge piping. |
| C. Relief Valves: |
| 1. Manufacturers: Subject to compliance with requirements, provide products by one of the following: |
| a. |
| a. |
| a. CLA-VAL Automatic Control Valves. |
| a. Kunkle Valve; a part of Tyco International Ltd. |
| b. |
| 1. |
| 1. |
| 1. |
| 2. Description: UL 1478, bronze or cast iron, spring loaded; for installation in fire-suppression water-supply piping. |
| D. Inlet Fitting: Eccentric tapered reducer at pump suction inlet. |
| E. Outlet Fitting: Concentric tapered reducer at pump discharge outlet. |
| F. Hose Valve Manifold Assembly: |
| 1. Standard: Comply with requirements in NFPA 20 and FM Global requirements. |
| 2. Header Pipe: ASTM A 53/A 53M, Schedule 40, galvanized steel with ends threaded according to ASME B1.20.1. |
| 3. Header Pipe Fittings: ASME B16.4, galvanized cast-iron threaded fittings. |
| 4. Automatic Drain Valve: UL 1726. |
| 5. Manifold: |
| a. |
| a. |
| a. |
| a. Adapters and Caps with Chain: Brass or bronze, with outlet threaded according to NFPA 1963 and matching local fire-department threads. |
| a. Hose Valves: UL 668, bronze, with outlet threaded according to NFPA 1963 and matching local fire-department threads. |
| b. |
| a. |
| a. |
| a. |
| c. Test Connections: Comply with UL 405 except provide outlets without clappers instead of inlets. |
| d. Body: Exposed type with number of outlets required by NFPA 20. |
| a. |
| a. |
| e. Escutcheon Plate Marking: Equivalent to "FIRE PUMP TEST." |
| 2.4 FLOWMETER SYSTEMS |
| A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: Basis of design is Global Vision, 6-500-GLF. |
| 1. |
| 1. |
| 1. |
| 1. Gerand Engineering Co. |
| 2. Hydro Flow Products, Inc. |
| 1. |
| 1. |
| 1. |
| 1. |
| 3. Victaulic Company. |
| A. |
| B. Description: UL-listed and FM-Approved, fire-pump flowmeter system with capability to indicate flow to not less than 175 percent of fire-pump rated capacity. |
| C. Pressure Rating: 500 psig |
| D. Sensor: venturi unless otherwise indicated. Sensor size shall match pipe, tubing, flowmeter, and fittings. |
| E. Permanently Mounted Flowmeter: Compatible with flow sensor; with dial not less than 4-1/2 inches in diameter. |
| 1. Tubing Package: NPS 1/8 or NPS 1/4 soft copper tubing with copper or brass fittings and valves. |
| 1.1 |
| 2.5 GROUT |
| A. Standard: ASTM C 1107, Grade B, post-hardening and volume-adjusting, dry, hydraulic-cement grout. |
| B. Characteristics: Nonshrink and recommended for interior and exterior applications. |
| C. Design Mix: 5000-psi, 28-day compressive strength. |
| D. Packaging: Premixed and factory packaged. |
| 2.6 SOURCE QUALITY CONTROL |
| A. Testing: Test and inspect fire pumps according to UL 448 requirements for "Operation Test" and "Manufacturing and Production Tests." |
| 1. Verification of Performance: Rate fire pumps according to UL 448. |
| B. Fire pumps will be considered defective if they do not pass tests and inspections. |
| C. Prepare test and inspection reports. |
| PART 3 - EXECUTION |
| 3.1 EXAMINATION |
| A. Examine equipment bases and anchorage provisions, with Installer present, for compliance with requirements and for conditions affecting performance of fire pumps. |
| B. Examine roughing-in for fire-suppression piping systems to verify actual locations of piping connections before fire-pump installation. |
| C. Proceed with installation only after unsatisfactory conditions have been corrected. |
| 3.2 INSTALLATION |
| A. Fire-Pump Installation Standard: Comply with NFPA 20 for installation of fire pumps, relief valves, and related components. |
| B. Equipment Mounting: Install fire pumps on concrete bases. Comply with requirements for concrete bases. |
| 1. Install dowel rods to connect concrete base to concrete floor. Unless otherwise indicated, install dowel rods on 18-inch centers around the full perimeter of concrete base. |
| 2. For supported equipment, install epoxy-coated anchor bolts that extend through concrete base and anchor into structural concrete floor. |
| 3. Place and secure anchorage devices. Use setting drawings, templates, diagrams, instructions, and directions furnished with items to be embedded. |
| 4. Install anchor bolts to elevations required for proper attachment to supported equipment. |
| C. Install fire-pump suction and discharge piping equal to or larger than sizes required by NFPA 20 and FM Global. |
| D. Support piping and pumps separately so weight of piping does not rest on pumps. |
| E. Install valves that are same size as connecting piping. Comply with requirements for fire-protection valves specified. |
| F. Install pressure gages on fire-pump suction and discharge flange pressure-gage tappings. Comply with requirements for pressure gages specified. |
| G. Install piping hangers and supports, anchors, valves, gages, and equipment supports according to NFPA 20 and FM Global requirements. |
| H. Install flowmeters and sensors. Install flowmeter-system components and make connections according to NFPA 20, FM Global and manufacturer's written instructions. |
| I. Electrical Wiring: Install electrical devices furnished by equipment manufacturers but not factory mounted. Furnish copies of manufacturers' wiring diagram submittals to electrical Installer. |
| J. Wiring Method: Conceal conductors and cables in accessible ceilings, walls, and floors where possible. |
| 3.3 ALIGNMENT |
| A. Align split-case pump and driver shafts after complete unit has been leveled on concrete base, grout has set, and anchor bolts have been tightened. |
| B. After alignment is correct, tighten anchor bolts evenly. Fill baseplate completely with grout, with metal blocks and shims or wedges in place. Tighten anchor bolts after grout has hardened. Check alignment and make required corrections. |
| C. Align piping connections. |
| D. Align pump and driver shafts for angular and parallel alignment and to tolerances specified by manufacturer. |
| 3.4 CONNECTIONS |
| A. Comply with requirements for piping and valves specified. Drawings indicate general arrangement of piping, fittings, and specialties. |
| B. Install piping adjacent to pumps and equipment to allow service and maintenance. |
| C. Connect relief-valve discharge to drainage piping or point of discharge. |
| D. Connect flowmeter-system meters, sensors, and valves to tubing. |
| E. Connect fire pumps to their controllers. |
| 3.5 IDENTIFICATION |
| A. Identify system components. Comply with requirements for fire-pump marking according to NFPA 20 and FM Global. |
| 3.6 FIELD QUALITY CONTROL |
| A. Test each fire pump with its controller as a unit. Comply with requirements for electric-motor-driver fire-pump controllers specified in Section 213900 "Controllers for Fire-Pump Drivers." |
| B. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect, test, and adjust components, assemblies, and equipment installations, including connections. |
| C. Perform tests and inspections. |
| 1. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect components, assemblies, and equipment installations, including connections, and to assist in testing. |
| D. Tests and Inspections: |
| 1. After installing components, assemblies, and equipment including controller, test for compliance with requirements. |
| 2. Test according to NFPA 20 and FM Global for acceptance and performance testing. |
| 3. Leak Test: After installation, charge system and test for leaks. Repair leaks and retest until no leaks exist. |
| 4. Operational Test: After electrical circuitry has been energized, start units to confirm proper motor rotation and unit operation. |
| 5. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment. |
| E. Components, assemblies, and equipment will be considered defective if they do not pass tests and inspections. |
| F. Prepare test and inspection reports. |
| G. Furnish fire hoses in number, size, and length required to reach storm drain or other acceptable location to dispose of fire-pump test water. Hoses are for tests only and do not convey to Owner. |
| 3.7 STARTUP SERVICE |
| A. Engage a factory-authorized service representative to perform startup service. |
| 1. Complete installation and startup checks according to manufacturer's written instructions. |
| 1.1 |
| 3.8 DEMONSTRATION |
| A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain fire pumps. |
| Blank Page |