Electrical Legends and General Notes for Fire Pump Replacement Project

This electrical design document pertains to the Amity Regional School District No. 5's Fire Pump Replacement project at Amity Middle School in Bethany, Connecticut. The project involves comprehensive electrical demolition and new installation work associated with replacing the fire pump system and related infrastructure. Key electrical work includes disconnecting and removing existing power feeds to the current fire pump, jockey pump, and sump pump systems; installing new electrical service to two new sump pump panels; furnishing and installing a new FTA200-A remote alarm panel in the main school building corridor; and establishing new conduit and conductor runs from the fire alarm controller panel to the remote alarm panel. The document specifies that a 120V, single-phase, 20-ampere circuit with 2#12, 1#12G conductors in 3/4" conduit must be provided to power the remote alarm panel from the nearest panelboard in electrical room D119. Additionally, 16#12 plus 1#12G conductors in 3/4" conduit must be installed to connect the fire pump controller to the remote alarm panel. The mandatory pre-bid walkthrough is scheduled by appointment only with no appointments after 2:00 PM on Friday, November 7, 2025, and sealed proposals are due by Friday, November 14, 2025, at 1:00 P.M.

The project requires extensive coordination between the electrical contractor, fire protection contractor, and the client regarding equipment placement, signal wiring specifications, and installation procedures. The fire pump controller with automatic transfer switch (ATS), jockey pump controller panel, new inline electric fire pump on a new concrete pad, and new sump pumps are detailed in the scope, with existing equipment to be removed including the existing fire pump, concrete pad, existing jockey pump, and two existing sump pumps. The electrical contractor is responsible for determining actual routing of raceways and wiring while adhering to specifications for concealed wiring in finished areas, plenum-rated wiring in plenum spaces, and coordination of all electrical penetrations with architectural and mechanical systems. The contract documents reference Fire Protection drawings FP-101 and FP-200-DETAIL for coordination of supervisory switches, flow switches, and pressure switches that must be connected to the existing fire alarm system.

View the file

Other files

Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

POWER DEVICES

ELECTRICAL PANEL 480 / 277 VOLT

ELECTRICAL POWER TRANSFORMER

MAGNETIC STARTER

FUSED DISCONNECT SWITCH

COMBINATION MAGNETIC STARTER AND DISCONNECT SWITCH

ELECTRIC MOTOR

VARIABLE FREQUENCY DRIVE

JUNCTION BOX

HARD-WIRED EQUIPMENT CONNECTION

DESCRIPTIONSYMBOL

RELAY

ELECTRICAL PANEL 208 / 120 VOLT

SPECIAL-PURPOSE ELECTRICAL PANEL OR EQUIPMENT CABINET

ELECTRONIC FAUCET / FLUSH VALVE CONTROL TRANSFORMER

TRAP PRIMER SOLENOID TRANSFORMER

MOTORIZED PROJECTION SCREEN POWER CONNECTION BOX

MOTORIZED SHADE POWER CONNECTION BOX

ELECTRIC HAND DRYER POWER CONNECTION BOX

AUDIO / VISUAL SYSTEM JUNCTION BOX - REFER TO

SPECIFICATIONS AND / OR DETAILS FOR ADDITIONAL INFORMATION

PULL BOX, (FEEDERS)

FAN COIL UNIT POWER CONNECTION BOX

SPLICE BOX, (FEEDERS)

COMBINATION POWER / DATA SERVICES POLE

RECESSED MULTI-SERVICE FLOOR BOX

MULTI-SERVICE POKE-THRU ASSEMBLY

ACTIVE HARMONIC FILTER

FLUSH POWER OUTLET WITH LFMC WHIP CONNECTION

TO FURNITURE PARTITION SYSTEM (WALL OR FLOOR)

T P

S B

P B

180906

F

EFTx

TPTx

Tx

F,WP

MSJ

FC J

HDJ

a

AVJ

PSJ

J

VFD

AHF

R

FB

PT

ELECTRIFIED BUSDUCT WITH FUSIBLE, PLUG-IN BRANCH

CIRCUIT DEVICE

ABBREVIATIONS

AMPERE

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AIR HANDLING UNIT

CONDUIT

CABLE TELEVISION

CIRCUIT BREAKER

DESCRIPTIONSYMBOL

A

AFF

AFG

AHU

C

CATV

C/B

CIRCUITCIR

CABINET UNIT HEATERCUH

CABLE TRAYCT

EXISTING TO REMAINER

EXHAUST FANEF

EXISTING LIGHTING TO REMAIN (WITHIN SPECIFIED AREA)ELTR

EMERGENCYEM

ELECTRIC METALLIC TUBINGEMT

EXISTING POWER TO REMAIN (WITHIN SPECIFIED AREA)EPTR

ELECTRIC WATER COOLEREWC

ELECTRIC WATER HEATEREWH

FUSEDF

FIRE ALARMFA

FLEXIBLE METALLIC CONDUITFMC

FUTUREFUT

GROUND FAULT INTERRUPTERGFI / GFCI

ISOLATED GROUNDIG

MAKE-UP AIR UNITMAU

MOTORIZED DAMPERMD

NON-FUSEDNF

NEW LOCATION OF EXISTING RELOCATEDNE

NIGHT LIGHTNL

NEW TO REPLACE EXISTINGNR

POLE (SPACE IN PANELBOARD)P

PRIMARY ELECTRIC SERVICEPE

POLYVINYL CHLORIDE CONDUITPVC

REMOVE EXISTINGRE

REFRIGERATORREF

RELOCATE EXISTINGRL

RIGID METALLIC CONDUITRMC

REMOVE AND REPLACE ON NEW SURFACERR

ROOFTOP UNITRTU

SMOKE DAMPERSD

SECONDARY ELECTRIC SERVICESE

SPACE AND PROVISIONS&P

TELEPHONE (VOICE)T

TEMPERATURE CONTROL PANELTCP

TELEVISIONTV

TRANSFORMERTX

WIRE OR WATTSW

WIRE GUARDWG

WEATHERPROOFWP

WIRELESS ACCESS POINTWA OR WAP

UNIVERSALUNV

CLOSED CIRCUIT TELEVISIONCCTV

EXPLOSION PROOF (INTRINSICALLY SAFE)EXP

ARC FAULT INTERRUPTERAFI / AFCI

LEGEND NOTE

THESE LEGENDS AND ABBREVIATIONS DEFINE ITEMS INDICATED ON DRAWINGS.

NOT ALL SYMBOLS OR ABBREVIATIONS DEFINED ARE NECESSARILY USED ON THIS

PROJECT.

ONE-LINE

POTHEAD

STRESSCONE

CURRENT TRANSFORMER

POTENTIAL TRANSFORMER

FUSE

FUSE CUT OUT

FUSE & SWITCH

DESCRIPTIONSYMBOL

CIRCUIT BREAKER

DRAWOUT CIRCUIT BREAKER

MEDIUM VOLTAGE DRAWOUT CIRCUIT BREAKER

BUSPLUG CIRCUIT BREAKER

BUSPLUG FUSE & SWITCH

GROUND

THERMAL OVERLOAD

RELAY / COIL

N/O CONTACT

N.C. CONTACT

PROTECTIVE RELAY

AMMETER

AMMETER SWITCH

VOLTMETER

VOLTMETER SWITCH

UTILITY METER

OWNERS POWER METER

DISTRIBUTED GENERATION METER

TRANSFORMER (WITH GROUNDING ON SECONDARY SIDE)

SHIELDED TRANSFORMER

(WITH GROUNDING ON SECONDARY SIDE)

AUTO TRANSFORMER

LIGHTNING ARRESTOR

GENERATOR

DELTA

WYE

KEY INTERLOCK (NUMBER INDICATES MATCHED PAIRS)

AUTOMATIC TRANSFER SWITCH (A.T.S.)

BYPASS / ISOLATION AUTOMATIC TRANSFER SWITCH

MAIN LUG ONLY PANELBOARD

MAIN CIRCUIT BREAKER PANELBOARD

ISOLATED POWER PANELBOARD

CIRCUIT BREAKER WITH AMP FRAME OVER AMP TRIP

FUSE DISCONNECT SWITCH, WITH SWITCH SIZE OVER FUSE SIZE

SHORT CIRCUIT DATA POINT / FAULT CURRENT VALUE

SWITCH

SURGE PROTECTION DEVICE

WIRING

BRANCH CIRCUIT WIRING

BRANCH CIRCUIT SWITCHED WIRING

BRANCH CIRCUIT AC OR DC CONTROL WIRING

EMERGENCY FEEDER

TELECOMMUNICATION SYSTEM RACEWAY

NIGHTLIGHT CIRCUIT

CABLE TELEVISION SYSTEM RACEWAY

CABLETRAY

INCOMING PRIMARY ELECTRIC SERVICE

INCOMING SECONDARY ELECTRIC SERVICE

CONDUIT UP

CONDUIT DOWN

HOME RUN. 3/4" CONDUIT, 2#12 AND 1#12 GROUND, UNLESS

OTHERWISE NOTED. NOTE: HOME RUN SHALL BE FROM FIRST

ELECTRICAL DEVICE BACKBOX IN CIRCUIT TO ELECTRICAL PANEL

DESCRIPTIONSYMBOL

LV

T

NL

CT

PE

SE

CATV

EM

ACTIVE HARMONIC FILTERAHF

FULL LOAD AMPSFLA

GROUNDG / GND

LIQUID-TIGHT FLEXIBLE METALLIC CONDUITLFMC

MINIMUM CIRCUIT AMPACITYMCA

NORMALLY CLOSEDNC

NORMALLY OPENNO

SHUNT STRIPST

TYPICALTYP

VOLTS ACVAC

SURFACE MOUNTED RACEWAYWM

POINT OF CONNECTION BETWEEN EXISTING AND NEW WORK

TRIP UNIT ADJUSTMENT FEATURE:

L = LONG TIME; LSI = LONG / SHORT / INSTANTANEOUS

LSGI = LONG / SHORT / INSTANTANEOUS / GROUND FAULT

ELECTRIFIED BUS DUCT WITH PLUG-IN, BRANCH CIRCUIT DEVICEBD

PROGRAMMABLE LOGIC CONTROLLER

MAIN FUSED SWITCH PANELBOARD

150918

150918

150918

L N E

E N

L

L / LSI / LSIG

XXXAF

XXXAT

DG

XXXAS

XXXAF

#K

G

M

C

XX

XX

M

A

AS

V

VS

SPD

PLC

WIRE BREAK

POINT OF CONNECTION / WIRE TAP

POINT OF CONNECTION / WIRE TAP

OR

170608

LOAD BREAK ELBOW

DEAD BREAK ELBOW

DEAD-FRONT TERMINAL JUNCTION (TWO, THREE OR FOUR WAY)

GENERAL ELECTRICAL DEMOLITION NOTES

A. REMOVE ALL EXISTING ELECTRICAL EQUIPMENT SHOWN ON THE DEMO PLAN, EXCEPT WHERE

MARKED OTHERWISE, i.e. LIGHTING, SWITCHES, OUTLETS, PANELBOARDS, ASSOCIATED WIRING BACK TO SOURCE OR TO LAST ACTIVE DEVICE, CONDUIT, ETC. IN PREPARATION FOR NEW WORK.

THIS WORK INCLUDES COMPLETE DEMO AND IS NOT LIMITED TO THE EQUIPMENT SHOWN ON DEMO

PLANS.

B. REMOVE EXISTING FIRE ALARM SYSTEM COMPLETELY INCLUDING BUT NOT LIMITED TO, FIRE

ALARM DEVICES, WIRING, CONDUIT, BOXES, PANELS, ETC. COORDINATE REMOVAL WORK WITH

INSTALLATION OF NEW FIRE ALARM SYSTEM SUCH THAT AN OPERATIONAL FIRE ALARM SYSTEM IS

MAINTAINED THROUGHOUT PERIODS OF BUILDING OCCUPATION. COORDINATE ANY SERVICE

SHUT-DOWN WITH LOCAL FIRE OFFICIAL AND OWNER. PROVIDE FIRE WATCH AS REQUIRED.

C. DISCONNECT AND REMOVE EXISTING WIRING, CONDUIT, BOXES, ETC. SERVING ALL EQUIPMENT

BEING REMOVED BY MECHANICAL AND OTHER TRADES. REFER TO PLUMBING, MECHANICAL AND

ARCHITECTURAL DRAWINGS FOR COORDINATION OF REQUIRED WORK. REMOVALS SHALL BE BACK

TO SOURCE PANEL COMPLETE.

D. EXISTING ELECTRICAL ITEMS THAT ARE BEING DISCONNECTED AND REMOVED AND NOT BEING

REUSED SHALL BE DISPOSED OF PROPERLY.

E. ALL ABANDONED ELECTRICAL WIRING AND DEVICES SHALL BE REMOVED.

F. IF CONTINUITY OF WIRING TO EXISTING ELECTRICAL ITEMS IS INTERRUPTED BY REMOVAL OF

DEVICES, CONTRACTOR SHALL INSTALL ALL NECESSARY WIRING AND RACEWAY TO ENSURE THE

CONTINUITY OF CIRCUITRY IN OTHER AREAS.

G. WIRING FOR ITEMS BEING REMOVED SHALL BE REMOVED BACK TO POWER SOURCE OR LAST

DEVICE TO REMAIN ACTIVE UNLESS NOTED OTHERWISE.

H. NOTIFY CONSTRUCTION MANAGER OR GENERAL CONTRACTOR OF OPENINGS CAUSED BY REMOVAL

OF EXISTING EQUIPMENT NOT BEING REPLACED. ENSURE THE PATCHING IS COMPLETE.

I. ALL EXISTING EXPOSED RACEWAY THAT IS SERVING DEVICES IN FINISHED AREAS THAT ARE TO

REMAIN SHALL BE REMOVED AND REPLACED WITH NEW CONCEALED CONDUIT/RACEWAY AND

CONDUCTORS TO SERVE DEVICES.

J. INSTALL BLANK COVER PLATES ON RECESSED OUTLET BOXES ABANDONED UNDER THIS CONTRACT

IN WALLS THAT ARE TO REMAIN.

K. WHERE POWER AND TEL/DATA OUTLETS EXIST ON WALLS TO BE FURRED OUT, THE ELECTRICAL

CONTRACTOR SHALL REMOVE AND REINSTALL DEVICES AND PLATES AND PROVIDE BOX

EXTENSIONS AS NECESSARY TO EXTEND THE OUTLETS TO THE NEW SURFACES.

L. REMOVE DEVICE PLATES (AND DEVICES WHERE NECESSARY) TO ACCOMMODATE NEW WALL

FINISHES. REINSTALL COVER PLATES AND DEVICES AFTER NEW FINISHES ARE COMPLETE.

M. THE BUILDING WILL BE OCCUPIED DURING DEMOLITION. COORDINATE PHASING OF DEMO WORK

WITH CONSTRUCTION MANAGER OR GENERAL CONTRACTOR. EXISTING PANELS MAY NEED

TEMPORARY RE- FEED. ENSURE CONTINUITY OF SERVICES.

161102

GENERAL ELECTRICAL NOTES

A. ALL HOMERUNS/CIRCUITS TO BE 2#12, 1#12G., 3/4"C TO A 20A-1P CIRCUIT BREAKER IN DESIGNATED

PANEL, UNLESS NOTED OTHERWISE. NUMBERS SHOWN AT EACH DEVICE/HOMERUN REPRESENT

CIRCUIT NUMBER IN PANELBOARD.

B. WIRE AND RACEWAY SIZES INDICATED ON HOMERUNS/CIRCUITS SHALL BE CONTINUOUS FOR ENTIRE

LENGTH, UNLESS NOTED OTHERWISE.

C. ALL WIRING (CONDUITS, ETC.) TO BE CONCEALED. NO SURFACE WIRING SHALL BE INSTALLED IN

FINISHED AREAS. THIS CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL CHANNELING

REQUIRED OF EXISTING WALLS AND FLOORS TO ACCOMMODATE NEW WIRING. SEE PATCHING

SPECIFICATIONS, FLOOR PLANS AND ELEVATIONS FOR ADDITIONAL INFORMATION ON

ARCHITECTURAL AND WIRING ROUTING.

D. ALL WIRING ABOVE CEILING THAT IS NOT IN CONDUIT AND IS LOCATED IN A PLENUM SPACE SHALL BE

PLENUM RATED. REFER TO MECHANICAL PLANS FOR PLENUM AREAS.

E. ELECTRICAL CONDUITS, WIRING, BOXES, ETC. SHALL NOT PENETRATE STAIR ENCLOSURE, UNLESS

THEY ARE FEEDING DEVICES LOCATED WITHIN THE STAIR ENCLOSURE.

F. PROVIDE ELECTRICAL OUTLET PLATE GASKET SEALS AT RECEPTACLES, SWITCHES AND OTHER ELECTRICAL BOXES ON EXTERIOR WALLS AND INTERIOR WALLS BETWEEN CONDITIONED AND NON-

CONDITIONED SPACES.

G. ALL INDIVIDUAL OR GENERAL PURPOSE BRANCH 120 VOLT CIRCUITS OVER 100'-0" IN CONDUCTOR LENGTH SHALL BE INCREASED ONE WIRE SIZE (i.e. FROM #12AWG TO #10AWG) AND CIRCUITS OVER 170'-0" IN CONDUCTOR LENGTH SHALL BE INCREASED TWO WIRE SIZES (i.e. FROM #12AWG TO #8AWG)

UNLESS NOTED OTHERWISE.

H. ALL INDIVIDUAL OR GENERAL PURPOSE BRANCH 277 VOLT CIRCUITS OVER 230'-0" IN CONDUCTOR LENGTH SHALL BE INCREASED ONE WIRE SIZE (i.e. FROM #12AWG TO #10AWG) AND CIRCUITS OVER 380'-0" IN CONDUCTOR LENGTH SHALL BE INCREASED TWO WIRE SIZES (i.e. FROM #12AWG TO #8AWG,)

UNLESS NOTED OTHERWISE.

I. PROVIDE UNIVERSAL BLANK PLUGS ON ALL SPARE CONDUITS.

J. SEAL ALL CONDUITS AT THE LAST STRUCTURE PRIOR TO CONDUITS ENTERING A BUILDING PER SPECIFICATIONS AND DETAILS. ALL SPARE CONDUITS SHALL HAVE NYLON PULL STRING AND FOOTAGE

TAPE.

K. RACEWAY AND WIRING INDICATED ON DRAWINGS ARE RECOMMENDATIONS FOR SPECIFIC ROUTES OR

SPECIAL CONDITIONS. CONTRACTOR IS RESPONSIBLE FOR DETERMINING ACTUAL ROUTING.

L. ALTHOUGH ALL FEEDER AND BRANCH CIRCUIT WIRE AND CONDUIT IS NOT SPECIFICALLY SHOWN, IT IS

THE INTENT OF THESE DOCUMENTS THAT A COMPLETE FEEDER AND BRANCH CIRCUIT WIRING

SYSTEM BE INSTALLED.

M. ENSURE THAT NO PIPING, DUCTWORK, LEAK PROTECTION APPARATUS OR OTHER EQUIPMENT FOREIGN TO THE ELECTRICAL TRADE PASSES THROUGH THE SPACE EQUAL TO THE WIDTH AND DEPTH OF THE

ELECTRICAL DISTRIBUTION EQUIPMENT AND EXTENDING FROM THE FLOOR TO THE STRUCTURAL

CEILING.

161102

GENERAL POWER NOTES

A. COORDINATE EXACT LOCATION OF ELECTRICAL DEVICES SUCH AS RECEPTACLES, SWITCHES, FIRE ALARM DEVICES, ETC. WITH ARCHITECTURAL PLANS, ELEVATIONS AND DETAILS PRIOR TO

START OF WORK, REQUEST CLARIFICATIONS FROM ARCHITECT PRIOR TO INSTALLATION.

B. ANY RECEPTACLE LOCATED WITHIN 6'-0" OF EDGE OF SINK SHALL BE A GFI RECEPTACLE OR

PROTECTED BY A GFI CIRCUIT BREAKER.

C. UNLESS OTHERWISE INDICATED, REFER TO MOTOR CIRCUIT SCHEDULE FOR ELECTRICAL

REQUIREMENTS OF ALL MECHANICAL (HVAC, PLUMBING, FIRE PROTECTION, ETC.) EQUIPMENT.

REFER TO DRAWINGS FOR EACH TRADE FOR EXACT LOCATION OF EQUIPMENT.

D. DO NOT INSTALL OUTLETS BACK TO BACK. PROVIDE MINIMUM 24 INCH HORIZONTAL SPACING IN

FIRE RATED WALLS. MOUNT LOW VOLTAGE AND POWER OUTLETS IN DIFFERENT STUD WALL

CAVITIES.

E. WHEN THE COMBINING OF CIRCUITS OR HOMERUNS IS PERMITTED ELSEWHERE IN THE

CONTRACT DOCUMENTS, RACEWAYS SHALL BE LIMITED TO SIX CURRENT CARRYING

CONDUCTORS (THREE PHASE AND THREE NEUTRALS) PLUS GROUNDING CONDUCTORS UNLESS

OTHERWISE INDICATED. PROVIDE A DEDICATED NEUTRAL FOR EACH SINGLE PHASE CIRCUIT,

UNLESS "OVERSIZED" NEUTRAL IS PROVIDED AS PART OF MANUFACTURED ASSEMBLY. IF

MANUFACTURED ASSEMBLIES ARE PROVIDED WITH "OVERSIZED" NEUTRALS, PROVIDE

MATCHING "OVERSIZED" NEUTRALS FROM SOURCE PANEL TO MANUFACTURED ASSEMBLY.

F. PROVIDE NYLON PULL STRING IN ALL EMPTY CONDUIT SYSTEMS FOR USE IN INSTALLING

SYSTEM WIRING.

G. PROVIDE GFI TYPE CIRCUIT BREAKER TO SERVE RECEPTACLE IF THEY ARE DESIGNATED BOTH

GFI AND IG TYPE.

H. ALL CIRCUITS WIRED TO ELECTRONIC GRADE PANELBOARDS SHALL BE 2#12, 1#12 EQUIP. GND., 1 #12 ISOLATED GND., IN 3/4"C. RECEPTACLES FED BY THESE CIRCUITS SHALL BE ISOLATED

GROUND TYPE. REFER TO PANELBOARD SCHEDULE TO IDENTIFY ELECTRONIC GRADE

PANELBOARDS.

I. COORDINATE CABLETRAY ROUTING ABOVE CORRIDOR CEILINGS WITH MECHANICAL EQUIPMENT

AND PIPING. ADJUST RUNS AS REQUIRED.

J. REFER TO TELECOMMUNICATION, SECURITY AND AUDIO/VISUAL DRAWINGS FOR EXACT

LOCATION OF ALL TELECOMMUNICATION OUTLETS, SECURITY DEVICES, VIDEO OUTLETS,

AMPLIFIER, SPEAKERS, ETC. PROVIDE ALL REQUIRED RACEWAY FOR THESE SYSTEMS FOR A

COMPLETE INSTALLATION. SEE ELECTRICAL, TELECOMMUNICATION, SECURITY AND

AUDIO/VISUAL SPECIFICATIONS AND DRAWINGS FOR ADDITIONAL REQUIREMENTS.

J. COORDINATE EXACT LOCATION OF JUNCTION BOX FOR EQUIPMENT WHICH IS FURNISHED BY

OWNER OR OTHERS WITH EQUIPMENT SUPPLIER PRIOR TO CONSTRUCTION. PROVIDE WIRING

FROM JUNCTION BOX TO EQUIPMENT CONNECTION AS REQUIRED.

K. COORDINATE EXACT LOCATION OF MODULAR SYSTEMS FURNITURE POWER AND

DATA/TELEPHONE ENTRANCE LOCATIONS WITH FURNITURE SUPPLIER PRIOR TO

CONSTRUCTION.

L. WIRING INDICATED BY CIRCUIT NUMBER SYMBOL SHALL INCLUDE A NEUTRAL WHEN THE LOAD

SERVED HAS PROVISIONS FOR, OR REQUIRES A NEUTRAL. TYPICALLY, ALL FEEDERS AND

BRANCH CIRCUITS WILL REQUIRE A NEUTRAL, EXCEPT MOST MOTOR CIRCUITS.

160220

DATE

REV.

NO.

DRAWING TITLE:

FI

R

E P

U M

P R

E

PL

A C

E M

E N

T B

E T

H A

N Y

M

ID

D L

E S

C H

O O

L

A M

IT

Y

R

EG

IO

N

LU

K

E H

IL

L

R O

A D

B

ET

H A

N Y

, C T

DESCRIPTION

REVISIONS

PR

O

JE

C

T N

A M

E:

KEYPLAN

DRAWING NUMBER:

PROJ #: 2024090.00

DATE: 06/06/2025

CHECK BY:

DRAWN BY:

SCALE:

U se r I D

Fi le N am e:

Fi le

P at h:

E0

-L

G N

D .d w g

U :\2

4\

0.

\B

IM

\C

AD

\E le ct ric al

6/ 9/

1:

:4

PM

R iv er a- Pe na , K ris tia n G

N

AV N E MLZ

E N G I N E E R S

VAN ZELM HEYWOOD & SHADFORD, INC.

10 TALCOTT NOTCH, FARMINGTON, CT 06032 - 1800

Connecticut | Massachusetts | North Carolina

CT: 860.284.5064 MA: 617.218.9976 NC: 704.799.7275

AMITY

ISSUED FOR BID

JUNE 06,2025

E001

BGS

EDA/AJD

NONE

ELECTRICAL LEGENDS

AND GENERAL NOTES

A B

C D

E

3 4

6 7 8

K

9 10

A6

C106

ART ROOM

B117

CLASSROOM

OPEN

B118

TEAM ROOM

B137

COMPUTER LAB

C101

CORRIDOR

C116

CORRIDOR

C100

TELE DATA

IDF

C105

HEALTH

C104

BOOK STORAGE

C102

TOILET

FACULTY

C103

TOILET

FACULTY

C111

CORRIDOR

D121

TESTING

SPECIAL ED.

D119

ELEC. ROOM

D124

SPECIAL ED.

C109

CORRIDOR

C107

KILN ROOM

C115

PASSAGE

C112

SHOP

TECH. ED.

C113

CLASSROOM

TECH. ED.

D101

ENGLISH

D102

SOCIAL STUDIESC108

TOOL STORAGE

C114

DUST COLLECTOR

LPD1

CPD2

CPD1

PPD1

PPD2

PPD3

ELECTRICAL GENERAL NOTES:

1. REMOTE ALARM PANEL FTA200-A IS SUPPLIED BY FIRE PROTECTION

CONTRACTOR.COORDINATE WITH FIRE PROTECTION CONTRACTOR FOR ITS

INSTALLATION.

2. PROVIDE 120V 1P 20A TO POWER THE REMOTE ALARM PANEL FROM ONE OF THE

NEAREST PANELBOARD LOCATED IN ELECTRICAL ROOM 410. PROVIDE 2 #

12,1#12G, 3 /4 " C.

3. FURNISH AND INSTALL 16 #12 + 1 #12G 3 / 4 " C. COORDINATE WITH CLIENT AND

FIRE PUMP CONTRACTOR ON THE SIGNAL / ALARM TO WIRE FROM FIRE PUMP

CONTROLLER TO REMOTE ALARM PANEL.

FIRE PUMP HOUSE

REMOTE ALARM PANEL

ER

FIRE PUMP

CONTROLLER W/ATS

DATE

REV.

NO.

DRAWING TITLE:

FI

R

E P

U M

P R

E

PL

A C

E M

E N

T B

E T

H A

N Y

M

ID

D L

E S

C H

O O

L

A M

IT

Y

R

EG

IO

N

LU

K

E H

IL

L

R O

A D

B

ET

H A

N Y

, C T

DESCRIPTION

REVISIONS

PR

O

JE

C

T N

A M

E:

KEYPLAN

DRAWING NUMBER:

PROJ #: 2024090.00

DATE: 06/06/2025

CHECK BY:

DRAWN BY:

SCALE:

U se r I D

Fi le N am e:

Fi le

P at h:

E1

-F

L0 1.

dw g

U :\2

4\

0.

\B

IM

\C

AD

\E le ct ric al

6/ 9/

1:

:4

PM

R iv er a- Pe na , K ris tia n G

N

AV N E MLZ

E N G I N E E R S

VAN ZELM HEYWOOD & SHADFORD, INC.

10 TALCOTT NOTCH, FARMINGTON, CT 06032 - 1800

Connecticut | Massachusetts | North Carolina

CT: 860.284.5064 MA: 617.218.9976 NC: 704.799.7275

AMITY

ISSUED FOR BID

JUNE 06,2025

E101

BGS

EDA/AJD

1/2"=1'-0"

ELECTRICAL MAIN

BUILDING PARTIAL

FLOOR PLANS

SCALE:1 1/8" = 1'-0"

ELECTRICAL ROOM D119

AutoCAD SHX Text

FEL

SCALE:1 1/2" = 1'-0"

ELECTRICAL DEMOLITION UPPER LEVEL VAULT

SCALE:2 1/2" = 1'-0"

ELECTRICAL DEMOLITION LOWER LEVEL VAULT

SCALE:3 1/2" = 1'-0"

ELECTRICAL NEW WORK UPPER LEVEL VAULT

SCALE:4 1/2" = 1'-0"

ELECTRICAL NEW WORK LOWER LEVEL VAULT

FIRE PUMP

CONTROLLER W/ATS

JOCKEY PUMP

CONTROLLER

NEW SUMP PUMPS.

SAME MODEL AS

EXISTING PUMPS.

NEW INLINE ELECTRIC

FIRE PUMP ON NEW

CONCRETE PAD.

NEW JOCKEY PUMP

EXISTING JOCKEY PUMP

TO BE REMOVED

EXISTING FIRE PUMP

AND CONCRETE PAD TO

BE REMOVED

(2)EXISTING SUMP PUMP

TO BE REMOVED.

RR

ER

RR RR

RR

ER

PANELBOARD

"FPV"

ELECTRICAL POWER UPPER LEVEL DEMO WORK NOTES :

ER - EXISTING TO REMAIN.

RR - REMOVE AND REPLACE

DISCONNECT MAIN FEED POWER TO PANELBOARD "FPV",

JOCKEY PUMP CONTROLLER PANEL AND FIRE PUMP

CONTROLLER W/ATS.

ELECTRICAL POWER UPPER LEVEL NEW WORK NOTES :

RECONNECT MAIN FEED POWER TO PANELBOARD "FPV" , JOCKEY

PUMP CONTROLLER PANEL AND FIRE PUMP CONTROLLER W/ATS..

FURNISH AND INSTALL NEW CONDUCTOR AND CONDUIT FROM

PANELBOARD "FPV" TO TWO NEW SUMP PUMP PANELS.

FURNISH AND INSTALL NEW CONDUIT AND CONDUCTORS FROM FIRE

ALARM CONTROLLER PANEL TO THE REMOTE ALARM PANEL

LOCATED IN THE CORRIDOR IN THE MAIN SCHOOL BUILDING. REFER

DRAWING E-102 FOR ADDITIONAL INFORMATION.

FURNISH AND INSTALL NEW FTA200-A REMOTE ALARM PANEL.

COORDINATE WITH FIRE PROTECTION CONTRACTOR AND CLIENT

FOR ITS LOCATION AND COMPLY WITH MANUFACTURER

INSTRUCTION FOR ITS INSTALLATION. REFER DRAWING E-101 FOR

ADDITIONAL INFORMATION.

ELECTRICAL POWER LOWER LEVEL DEMO WORK NOTES :

DISCONNECT AND REMOVE POWER TO JOCKEY PUMP.

EVALUATE THE EXISTING CONDITION OF THE CONDUIT,

CONDUCTORS AND IF THE RESULT OF EVALUATION IS THAT

THE CONDUITS AND CONDUCTORS CANNOT BE REUSED FOR

NEW WORK, THEN DEMO THE CONDUIT AND CONDUCTORS

OF JOCKEY PUMP. IF NOT, PRESERVE THE CONDUIT AND

CONDUCTORS FOR NEW WORK.

DISCONNECT AND REMOVE POWER TO FIRE PUMP.

EVALUATE THE EXISTING CONDITION OF THE CONDUIT,

CONDUCTORS AND IF THE RESULT OF EVALUATION IS THAT

THE CONDUITS AND CONDUCTORS CANNOT BE REUSED FOR

NEW WORK, THEN DEMO THE CONDUIT AND CONDUCTORS

OF JOCKEY PUMP. IF NOT, PRESERVE THE CONDUIT AND

CONDUCTORS FOR NEW WORK.

DISCONNECT AND REMOVE FEED TO SOURCE FOR SUMP

PUMP PANEL AND SUMP PUMPS WHICH ARE BEING

DEMOLISHED.

ELECTRICAL POWER LOWER LEVEL NEW WORK NOTES :

NEW CONDUITS / CONDUCTORS OR EXTEND THE

PRESERVED EXISTING FEED AS PER THE DEMOLITION

NOTES OF JOCKEY PUMP TO RECONNECT POWER TO

JOCKEY PUMP FROM THE JOCKEY PUMP CONTROLLER

PANEL. REFER TO FP-101 DRAWINGS AND COORDINATE

WITH FIRE PROTECTION CONTRACTOR FOR ITS

SPECIFICATIONS AND INSTALLATION.

NEW CONDUITS / CONDUCTORS OR EXTEND THE

PRESERVED EXISTING FEED AS PER THE DEMOLITION

NOTES OF FIRE PUMP TO RECONNECT POWER TO INLINE

FIRE PUMP FROM FIRE PUMP CONTROLLER PANEL.REFER

TO FP-101 DRAWINGS AND COORDINATE WITH FIRE

PROTECTION CONTRACTOR FOR ITS SPECIFICATIONS

AND INSTALLATION.

SUMP PUMP PANELS, JUNCTION BOX FOR SUMP PUMPS,

SUMP PUMPS, CABLES AND ACCESSORIES ARE SUPPLIED

BY FIRE PROTECTION CONTRACTOR. COORDINATE WITH

FIRE PROTECTION CONTRACTOR FOR THE INSTALLATION,

WIRING AS NEEDED FOR THE SUMP PUMPS, SUMP PUMP

PANELS AND JUNCTION BOX. REFER TO FP-101 DRAWING

FOR FURTHER INFORMATION.

REFER TO FP-101 AND FP-200-DETAIL FIRE PROTECTION

DRAWING TO COORDINATE WITH THE WIRING OF

SUPERVISORY SWITCH, FLOW SWITCH AND PRESSURE

SWITCH. ALL THE SWITCHES TO BE TIED TO THE EXISTING

FIRE ALARM SYSTEM. ELECTRICAL CONTRACTOR TO

COORDINATE WITH FIRE PROTECTION CONTRACTOR FOR

THE SCOPE OF THIS WORK.

FIRE PUMP

CONTROLLER W/ATS

NEW JOCKEY PUMP

CONTROLLER

PANELBOARD

"FPV"

NEW SUMP PUMP

PANEL

NEW SUMP PUMP

PANEL NEW JUNCTION BOX

FOR SUMP PUMP

PANEL

NEW JUNCTION BOX

FOR SUMP PUMP

PANEL

GFCI

GFCI

DATE

REV.

NO.

DRAWING TITLE:

FI

R

E P

U M

P R

E

PL

A C

E M

E N

T B

E T

H A

N Y

M

ID

D L

E S

C H

O O

L

A M

IT

Y

R

EG

IO

N

LU

K

E H

IL

L

R O

A D

B

ET

H A

N Y

, C T

DESCRIPTION

REVISIONS

PR

O

JE

C

T N

A M

E:

KEYPLAN

DRAWING NUMBER:

PROJ #: 2024090.00

DATE: 06/06/2025

CHECK BY:

DRAWN BY:

SCALE:

U se r I D

Fi le N am e:

Fi le

P at h:

E1

-F

L0 1.

dw g

U :\2

4\

0.

\B

IM

\C

AD

\E le ct ric al

6/ 9/

1:

:4

PM

R iv er a- Pe na , K ris tia n G

N

AV N E MLZ

E N G I N E E R S

VAN ZELM HEYWOOD & SHADFORD, INC.

10 TALCOTT NOTCH, FARMINGTON, CT 06032 - 1800

Connecticut | Massachusetts | North Carolina

CT: 860.284.5064 MA: 617.218.9976 NC: 704.799.7275

AMITY

ISSUED FOR BID

JUNE 06,2025

E102

BGS

EJF

1/2"=1'-0"

ELECTRICAL UPPER AND

LOWER LEVEL VAULT

FLOOR PLANS

Sheets and Views
E001-LGND-E-001
SEU101-SITE-E-101
E101-FL01-E-101
E101-FL01-E-102
E600-SPEC-E-600
E600-SPEC-E-601

File details come from the government source that posted it. Updated .