Electrical Set.pdf
PDF 802 KB Posted
- Solicitation number
- Amity 2025-4
- Issued by
- Connecticut
About this file
Electrical Legends and General Notes for Fire Pump Replacement Project
This electrical design document pertains to the Amity Regional School District No. 5's Fire Pump Replacement project at Amity Middle School in Bethany, Connecticut. The project involves comprehensive electrical demolition and new installation work associated with replacing the fire pump system and related infrastructure. Key electrical work includes disconnecting and removing existing power feeds to the current fire pump, jockey pump, and sump pump systems; installing new electrical service to two new sump pump panels; furnishing and installing a new FTA200-A remote alarm panel in the main school building corridor; and establishing new conduit and conductor runs from the fire alarm controller panel to the remote alarm panel. The document specifies that a 120V, single-phase, 20-ampere circuit with 2#12, 1#12G conductors in 3/4" conduit must be provided to power the remote alarm panel from the nearest panelboard in electrical room D119. Additionally, 16#12 plus 1#12G conductors in 3/4" conduit must be installed to connect the fire pump controller to the remote alarm panel. The mandatory pre-bid walkthrough is scheduled by appointment only with no appointments after 2:00 PM on Friday, November 7, 2025, and sealed proposals are due by Friday, November 14, 2025, at 1:00 P.M.
The project requires extensive coordination between the electrical contractor, fire protection contractor, and the client regarding equipment placement, signal wiring specifications, and installation procedures. The fire pump controller with automatic transfer switch (ATS), jockey pump controller panel, new inline electric fire pump on a new concrete pad, and new sump pumps are detailed in the scope, with existing equipment to be removed including the existing fire pump, concrete pad, existing jockey pump, and two existing sump pumps. The electrical contractor is responsible for determining actual routing of raceways and wiring while adhering to specifications for concealed wiring in finished areas, plenum-rated wiring in plenum spaces, and coordination of all electrical penetrations with architectural and mechanical systems. The contract documents reference Fire Protection drawings FP-101 and FP-200-DETAIL for coordination of supervisory switches, flow switches, and pressure switches that must be connected to the existing fire alarm system.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
POWER DEVICES
ELECTRICAL PANEL 480 / 277 VOLT
ELECTRICAL POWER TRANSFORMER
MAGNETIC STARTER
FUSED DISCONNECT SWITCH
COMBINATION MAGNETIC STARTER AND DISCONNECT SWITCH
ELECTRIC MOTOR
VARIABLE FREQUENCY DRIVE
JUNCTION BOX
HARD-WIRED EQUIPMENT CONNECTION
DESCRIPTIONSYMBOL
RELAY
ELECTRICAL PANEL 208 / 120 VOLT
SPECIAL-PURPOSE ELECTRICAL PANEL OR EQUIPMENT CABINET
ELECTRONIC FAUCET / FLUSH VALVE CONTROL TRANSFORMER
TRAP PRIMER SOLENOID TRANSFORMER
MOTORIZED PROJECTION SCREEN POWER CONNECTION BOX
MOTORIZED SHADE POWER CONNECTION BOX
ELECTRIC HAND DRYER POWER CONNECTION BOX
AUDIO / VISUAL SYSTEM JUNCTION BOX - REFER TO
SPECIFICATIONS AND / OR DETAILS FOR ADDITIONAL INFORMATION
PULL BOX, (FEEDERS)
FAN COIL UNIT POWER CONNECTION BOX
SPLICE BOX, (FEEDERS)
COMBINATION POWER / DATA SERVICES POLE
RECESSED MULTI-SERVICE FLOOR BOX
MULTI-SERVICE POKE-THRU ASSEMBLY
ACTIVE HARMONIC FILTER
FLUSH POWER OUTLET WITH LFMC WHIP CONNECTION
TO FURNITURE PARTITION SYSTEM (WALL OR FLOOR)
T P
S B
P B
180906
F
EFTx
TPTx
Tx
F,WP
MSJ
FC J
HDJ
a
AVJ
PSJ
J
VFD
AHF
R
FB
PT
ELECTRIFIED BUSDUCT WITH FUSIBLE, PLUG-IN BRANCH
CIRCUIT DEVICE
ABBREVIATIONS
AMPERE
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
CONDUIT
CABLE TELEVISION
CIRCUIT BREAKER
DESCRIPTIONSYMBOL
A
AFF
AFG
AHU
C
CATV
C/B
CIRCUITCIR
CABINET UNIT HEATERCUH
CABLE TRAYCT
EXISTING TO REMAINER
EXHAUST FANEF
EXISTING LIGHTING TO REMAIN (WITHIN SPECIFIED AREA)ELTR
EMERGENCYEM
ELECTRIC METALLIC TUBINGEMT
EXISTING POWER TO REMAIN (WITHIN SPECIFIED AREA)EPTR
ELECTRIC WATER COOLEREWC
ELECTRIC WATER HEATEREWH
FUSEDF
FIRE ALARMFA
FLEXIBLE METALLIC CONDUITFMC
FUTUREFUT
GROUND FAULT INTERRUPTERGFI / GFCI
ISOLATED GROUNDIG
MAKE-UP AIR UNITMAU
MOTORIZED DAMPERMD
NON-FUSEDNF
NEW LOCATION OF EXISTING RELOCATEDNE
NIGHT LIGHTNL
NEW TO REPLACE EXISTINGNR
POLE (SPACE IN PANELBOARD)P
PRIMARY ELECTRIC SERVICEPE
POLYVINYL CHLORIDE CONDUITPVC
REMOVE EXISTINGRE
REFRIGERATORREF
RELOCATE EXISTINGRL
RIGID METALLIC CONDUITRMC
REMOVE AND REPLACE ON NEW SURFACERR
ROOFTOP UNITRTU
SMOKE DAMPERSD
SECONDARY ELECTRIC SERVICESE
SPACE AND PROVISIONS&P
TELEPHONE (VOICE)T
TEMPERATURE CONTROL PANELTCP
TELEVISIONTV
TRANSFORMERTX
WIRE OR WATTSW
WIRE GUARDWG
WEATHERPROOFWP
WIRELESS ACCESS POINTWA OR WAP
UNIVERSALUNV
CLOSED CIRCUIT TELEVISIONCCTV
EXPLOSION PROOF (INTRINSICALLY SAFE)EXP
ARC FAULT INTERRUPTERAFI / AFCI
LEGEND NOTE
THESE LEGENDS AND ABBREVIATIONS DEFINE ITEMS INDICATED ON DRAWINGS.
NOT ALL SYMBOLS OR ABBREVIATIONS DEFINED ARE NECESSARILY USED ON THIS
PROJECT.
ONE-LINE
POTHEAD
STRESSCONE
CURRENT TRANSFORMER
POTENTIAL TRANSFORMER
FUSE
FUSE CUT OUT
FUSE & SWITCH
DESCRIPTIONSYMBOL
CIRCUIT BREAKER
DRAWOUT CIRCUIT BREAKER
MEDIUM VOLTAGE DRAWOUT CIRCUIT BREAKER
BUSPLUG CIRCUIT BREAKER
BUSPLUG FUSE & SWITCH
GROUND
THERMAL OVERLOAD
RELAY / COIL
N/O CONTACT
N.C. CONTACT
PROTECTIVE RELAY
AMMETER
AMMETER SWITCH
VOLTMETER
VOLTMETER SWITCH
UTILITY METER
OWNERS POWER METER
DISTRIBUTED GENERATION METER
TRANSFORMER (WITH GROUNDING ON SECONDARY SIDE)
SHIELDED TRANSFORMER
(WITH GROUNDING ON SECONDARY SIDE)
AUTO TRANSFORMER
LIGHTNING ARRESTOR
GENERATOR
DELTA
WYE
KEY INTERLOCK (NUMBER INDICATES MATCHED PAIRS)
AUTOMATIC TRANSFER SWITCH (A.T.S.)
BYPASS / ISOLATION AUTOMATIC TRANSFER SWITCH
MAIN LUG ONLY PANELBOARD
MAIN CIRCUIT BREAKER PANELBOARD
ISOLATED POWER PANELBOARD
CIRCUIT BREAKER WITH AMP FRAME OVER AMP TRIP
FUSE DISCONNECT SWITCH, WITH SWITCH SIZE OVER FUSE SIZE
SHORT CIRCUIT DATA POINT / FAULT CURRENT VALUE
SWITCH
SURGE PROTECTION DEVICE
WIRING
BRANCH CIRCUIT WIRING
BRANCH CIRCUIT SWITCHED WIRING
BRANCH CIRCUIT AC OR DC CONTROL WIRING
EMERGENCY FEEDER
TELECOMMUNICATION SYSTEM RACEWAY
NIGHTLIGHT CIRCUIT
CABLE TELEVISION SYSTEM RACEWAY
CABLETRAY
INCOMING PRIMARY ELECTRIC SERVICE
INCOMING SECONDARY ELECTRIC SERVICE
CONDUIT UP
CONDUIT DOWN
HOME RUN. 3/4" CONDUIT, 2#12 AND 1#12 GROUND, UNLESS
OTHERWISE NOTED. NOTE: HOME RUN SHALL BE FROM FIRST
ELECTRICAL DEVICE BACKBOX IN CIRCUIT TO ELECTRICAL PANEL
DESCRIPTIONSYMBOL
LV
T
NL
CT
PE
SE
CATV
EM
ACTIVE HARMONIC FILTERAHF
FULL LOAD AMPSFLA
GROUNDG / GND
LIQUID-TIGHT FLEXIBLE METALLIC CONDUITLFMC
MINIMUM CIRCUIT AMPACITYMCA
NORMALLY CLOSEDNC
NORMALLY OPENNO
SHUNT STRIPST
TYPICALTYP
VOLTS ACVAC
SURFACE MOUNTED RACEWAYWM
POINT OF CONNECTION BETWEEN EXISTING AND NEW WORK
TRIP UNIT ADJUSTMENT FEATURE:
L = LONG TIME; LSI = LONG / SHORT / INSTANTANEOUS
LSGI = LONG / SHORT / INSTANTANEOUS / GROUND FAULT
ELECTRIFIED BUS DUCT WITH PLUG-IN, BRANCH CIRCUIT DEVICEBD
PROGRAMMABLE LOGIC CONTROLLER
MAIN FUSED SWITCH PANELBOARD
150918
150918
150918
L N E
E N
L
L / LSI / LSIG
XXXAF
XXXAT
DG
XXXAS
XXXAF
#K
G
M
C
XX
XX
M
A
AS
V
VS
SPD
PLC
WIRE BREAK
POINT OF CONNECTION / WIRE TAP
POINT OF CONNECTION / WIRE TAP
OR
170608
LOAD BREAK ELBOW
DEAD BREAK ELBOW
DEAD-FRONT TERMINAL JUNCTION (TWO, THREE OR FOUR WAY)
GENERAL ELECTRICAL DEMOLITION NOTES
A. REMOVE ALL EXISTING ELECTRICAL EQUIPMENT SHOWN ON THE DEMO PLAN, EXCEPT WHERE
MARKED OTHERWISE, i.e. LIGHTING, SWITCHES, OUTLETS, PANELBOARDS, ASSOCIATED WIRING BACK TO SOURCE OR TO LAST ACTIVE DEVICE, CONDUIT, ETC. IN PREPARATION FOR NEW WORK.
THIS WORK INCLUDES COMPLETE DEMO AND IS NOT LIMITED TO THE EQUIPMENT SHOWN ON DEMO
PLANS.
B. REMOVE EXISTING FIRE ALARM SYSTEM COMPLETELY INCLUDING BUT NOT LIMITED TO, FIRE
ALARM DEVICES, WIRING, CONDUIT, BOXES, PANELS, ETC. COORDINATE REMOVAL WORK WITH
INSTALLATION OF NEW FIRE ALARM SYSTEM SUCH THAT AN OPERATIONAL FIRE ALARM SYSTEM IS
MAINTAINED THROUGHOUT PERIODS OF BUILDING OCCUPATION. COORDINATE ANY SERVICE
SHUT-DOWN WITH LOCAL FIRE OFFICIAL AND OWNER. PROVIDE FIRE WATCH AS REQUIRED.
C. DISCONNECT AND REMOVE EXISTING WIRING, CONDUIT, BOXES, ETC. SERVING ALL EQUIPMENT
BEING REMOVED BY MECHANICAL AND OTHER TRADES. REFER TO PLUMBING, MECHANICAL AND
ARCHITECTURAL DRAWINGS FOR COORDINATION OF REQUIRED WORK. REMOVALS SHALL BE BACK
TO SOURCE PANEL COMPLETE.
D. EXISTING ELECTRICAL ITEMS THAT ARE BEING DISCONNECTED AND REMOVED AND NOT BEING
REUSED SHALL BE DISPOSED OF PROPERLY.
E. ALL ABANDONED ELECTRICAL WIRING AND DEVICES SHALL BE REMOVED.
F. IF CONTINUITY OF WIRING TO EXISTING ELECTRICAL ITEMS IS INTERRUPTED BY REMOVAL OF
DEVICES, CONTRACTOR SHALL INSTALL ALL NECESSARY WIRING AND RACEWAY TO ENSURE THE
CONTINUITY OF CIRCUITRY IN OTHER AREAS.
G. WIRING FOR ITEMS BEING REMOVED SHALL BE REMOVED BACK TO POWER SOURCE OR LAST
DEVICE TO REMAIN ACTIVE UNLESS NOTED OTHERWISE.
H. NOTIFY CONSTRUCTION MANAGER OR GENERAL CONTRACTOR OF OPENINGS CAUSED BY REMOVAL
OF EXISTING EQUIPMENT NOT BEING REPLACED. ENSURE THE PATCHING IS COMPLETE.
I. ALL EXISTING EXPOSED RACEWAY THAT IS SERVING DEVICES IN FINISHED AREAS THAT ARE TO
REMAIN SHALL BE REMOVED AND REPLACED WITH NEW CONCEALED CONDUIT/RACEWAY AND
CONDUCTORS TO SERVE DEVICES.
J. INSTALL BLANK COVER PLATES ON RECESSED OUTLET BOXES ABANDONED UNDER THIS CONTRACT
IN WALLS THAT ARE TO REMAIN.
K. WHERE POWER AND TEL/DATA OUTLETS EXIST ON WALLS TO BE FURRED OUT, THE ELECTRICAL
CONTRACTOR SHALL REMOVE AND REINSTALL DEVICES AND PLATES AND PROVIDE BOX
EXTENSIONS AS NECESSARY TO EXTEND THE OUTLETS TO THE NEW SURFACES.
L. REMOVE DEVICE PLATES (AND DEVICES WHERE NECESSARY) TO ACCOMMODATE NEW WALL
FINISHES. REINSTALL COVER PLATES AND DEVICES AFTER NEW FINISHES ARE COMPLETE.
M. THE BUILDING WILL BE OCCUPIED DURING DEMOLITION. COORDINATE PHASING OF DEMO WORK
WITH CONSTRUCTION MANAGER OR GENERAL CONTRACTOR. EXISTING PANELS MAY NEED
TEMPORARY RE- FEED. ENSURE CONTINUITY OF SERVICES.
161102
GENERAL ELECTRICAL NOTES
A. ALL HOMERUNS/CIRCUITS TO BE 2#12, 1#12G., 3/4"C TO A 20A-1P CIRCUIT BREAKER IN DESIGNATED
PANEL, UNLESS NOTED OTHERWISE. NUMBERS SHOWN AT EACH DEVICE/HOMERUN REPRESENT
CIRCUIT NUMBER IN PANELBOARD.
B. WIRE AND RACEWAY SIZES INDICATED ON HOMERUNS/CIRCUITS SHALL BE CONTINUOUS FOR ENTIRE
LENGTH, UNLESS NOTED OTHERWISE.
C. ALL WIRING (CONDUITS, ETC.) TO BE CONCEALED. NO SURFACE WIRING SHALL BE INSTALLED IN
FINISHED AREAS. THIS CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL CHANNELING
REQUIRED OF EXISTING WALLS AND FLOORS TO ACCOMMODATE NEW WIRING. SEE PATCHING
SPECIFICATIONS, FLOOR PLANS AND ELEVATIONS FOR ADDITIONAL INFORMATION ON
ARCHITECTURAL AND WIRING ROUTING.
D. ALL WIRING ABOVE CEILING THAT IS NOT IN CONDUIT AND IS LOCATED IN A PLENUM SPACE SHALL BE
PLENUM RATED. REFER TO MECHANICAL PLANS FOR PLENUM AREAS.
E. ELECTRICAL CONDUITS, WIRING, BOXES, ETC. SHALL NOT PENETRATE STAIR ENCLOSURE, UNLESS
THEY ARE FEEDING DEVICES LOCATED WITHIN THE STAIR ENCLOSURE.
F. PROVIDE ELECTRICAL OUTLET PLATE GASKET SEALS AT RECEPTACLES, SWITCHES AND OTHER ELECTRICAL BOXES ON EXTERIOR WALLS AND INTERIOR WALLS BETWEEN CONDITIONED AND NON-
CONDITIONED SPACES.
G. ALL INDIVIDUAL OR GENERAL PURPOSE BRANCH 120 VOLT CIRCUITS OVER 100'-0" IN CONDUCTOR LENGTH SHALL BE INCREASED ONE WIRE SIZE (i.e. FROM #12AWG TO #10AWG) AND CIRCUITS OVER 170'-0" IN CONDUCTOR LENGTH SHALL BE INCREASED TWO WIRE SIZES (i.e. FROM #12AWG TO #8AWG)
UNLESS NOTED OTHERWISE.
H. ALL INDIVIDUAL OR GENERAL PURPOSE BRANCH 277 VOLT CIRCUITS OVER 230'-0" IN CONDUCTOR LENGTH SHALL BE INCREASED ONE WIRE SIZE (i.e. FROM #12AWG TO #10AWG) AND CIRCUITS OVER 380'-0" IN CONDUCTOR LENGTH SHALL BE INCREASED TWO WIRE SIZES (i.e. FROM #12AWG TO #8AWG,)
UNLESS NOTED OTHERWISE.
I. PROVIDE UNIVERSAL BLANK PLUGS ON ALL SPARE CONDUITS.
J. SEAL ALL CONDUITS AT THE LAST STRUCTURE PRIOR TO CONDUITS ENTERING A BUILDING PER SPECIFICATIONS AND DETAILS. ALL SPARE CONDUITS SHALL HAVE NYLON PULL STRING AND FOOTAGE
TAPE.
K. RACEWAY AND WIRING INDICATED ON DRAWINGS ARE RECOMMENDATIONS FOR SPECIFIC ROUTES OR
SPECIAL CONDITIONS. CONTRACTOR IS RESPONSIBLE FOR DETERMINING ACTUAL ROUTING.
L. ALTHOUGH ALL FEEDER AND BRANCH CIRCUIT WIRE AND CONDUIT IS NOT SPECIFICALLY SHOWN, IT IS
THE INTENT OF THESE DOCUMENTS THAT A COMPLETE FEEDER AND BRANCH CIRCUIT WIRING
SYSTEM BE INSTALLED.
M. ENSURE THAT NO PIPING, DUCTWORK, LEAK PROTECTION APPARATUS OR OTHER EQUIPMENT FOREIGN TO THE ELECTRICAL TRADE PASSES THROUGH THE SPACE EQUAL TO THE WIDTH AND DEPTH OF THE
ELECTRICAL DISTRIBUTION EQUIPMENT AND EXTENDING FROM THE FLOOR TO THE STRUCTURAL
CEILING.
161102
GENERAL POWER NOTES
A. COORDINATE EXACT LOCATION OF ELECTRICAL DEVICES SUCH AS RECEPTACLES, SWITCHES, FIRE ALARM DEVICES, ETC. WITH ARCHITECTURAL PLANS, ELEVATIONS AND DETAILS PRIOR TO
START OF WORK, REQUEST CLARIFICATIONS FROM ARCHITECT PRIOR TO INSTALLATION.
B. ANY RECEPTACLE LOCATED WITHIN 6'-0" OF EDGE OF SINK SHALL BE A GFI RECEPTACLE OR
PROTECTED BY A GFI CIRCUIT BREAKER.
C. UNLESS OTHERWISE INDICATED, REFER TO MOTOR CIRCUIT SCHEDULE FOR ELECTRICAL
REQUIREMENTS OF ALL MECHANICAL (HVAC, PLUMBING, FIRE PROTECTION, ETC.) EQUIPMENT.
REFER TO DRAWINGS FOR EACH TRADE FOR EXACT LOCATION OF EQUIPMENT.
D. DO NOT INSTALL OUTLETS BACK TO BACK. PROVIDE MINIMUM 24 INCH HORIZONTAL SPACING IN
FIRE RATED WALLS. MOUNT LOW VOLTAGE AND POWER OUTLETS IN DIFFERENT STUD WALL
CAVITIES.
E. WHEN THE COMBINING OF CIRCUITS OR HOMERUNS IS PERMITTED ELSEWHERE IN THE
CONTRACT DOCUMENTS, RACEWAYS SHALL BE LIMITED TO SIX CURRENT CARRYING
CONDUCTORS (THREE PHASE AND THREE NEUTRALS) PLUS GROUNDING CONDUCTORS UNLESS
OTHERWISE INDICATED. PROVIDE A DEDICATED NEUTRAL FOR EACH SINGLE PHASE CIRCUIT,
UNLESS "OVERSIZED" NEUTRAL IS PROVIDED AS PART OF MANUFACTURED ASSEMBLY. IF
MANUFACTURED ASSEMBLIES ARE PROVIDED WITH "OVERSIZED" NEUTRALS, PROVIDE
MATCHING "OVERSIZED" NEUTRALS FROM SOURCE PANEL TO MANUFACTURED ASSEMBLY.
F. PROVIDE NYLON PULL STRING IN ALL EMPTY CONDUIT SYSTEMS FOR USE IN INSTALLING
SYSTEM WIRING.
G. PROVIDE GFI TYPE CIRCUIT BREAKER TO SERVE RECEPTACLE IF THEY ARE DESIGNATED BOTH
GFI AND IG TYPE.
H. ALL CIRCUITS WIRED TO ELECTRONIC GRADE PANELBOARDS SHALL BE 2#12, 1#12 EQUIP. GND., 1 #12 ISOLATED GND., IN 3/4"C. RECEPTACLES FED BY THESE CIRCUITS SHALL BE ISOLATED
GROUND TYPE. REFER TO PANELBOARD SCHEDULE TO IDENTIFY ELECTRONIC GRADE
PANELBOARDS.
I. COORDINATE CABLETRAY ROUTING ABOVE CORRIDOR CEILINGS WITH MECHANICAL EQUIPMENT
AND PIPING. ADJUST RUNS AS REQUIRED.
J. REFER TO TELECOMMUNICATION, SECURITY AND AUDIO/VISUAL DRAWINGS FOR EXACT
LOCATION OF ALL TELECOMMUNICATION OUTLETS, SECURITY DEVICES, VIDEO OUTLETS,
AMPLIFIER, SPEAKERS, ETC. PROVIDE ALL REQUIRED RACEWAY FOR THESE SYSTEMS FOR A
COMPLETE INSTALLATION. SEE ELECTRICAL, TELECOMMUNICATION, SECURITY AND
AUDIO/VISUAL SPECIFICATIONS AND DRAWINGS FOR ADDITIONAL REQUIREMENTS.
J. COORDINATE EXACT LOCATION OF JUNCTION BOX FOR EQUIPMENT WHICH IS FURNISHED BY
OWNER OR OTHERS WITH EQUIPMENT SUPPLIER PRIOR TO CONSTRUCTION. PROVIDE WIRING
FROM JUNCTION BOX TO EQUIPMENT CONNECTION AS REQUIRED.
K. COORDINATE EXACT LOCATION OF MODULAR SYSTEMS FURNITURE POWER AND
DATA/TELEPHONE ENTRANCE LOCATIONS WITH FURNITURE SUPPLIER PRIOR TO
CONSTRUCTION.
L. WIRING INDICATED BY CIRCUIT NUMBER SYMBOL SHALL INCLUDE A NEUTRAL WHEN THE LOAD
SERVED HAS PROVISIONS FOR, OR REQUIRES A NEUTRAL. TYPICALLY, ALL FEEDERS AND
BRANCH CIRCUITS WILL REQUIRE A NEUTRAL, EXCEPT MOST MOTOR CIRCUITS.
160220
DATE
REV.
NO.
DRAWING TITLE:
FI
R
E P
U M
P R
E
PL
A C
E M
E N
T B
E T
H A
N Y
M
ID
D L
E S
C H
O O
L
A M
IT
Y
R
EG
IO
N
LU
K
E H
IL
L
R O
A D
B
ET
H A
N Y
, C T
DESCRIPTION
REVISIONS
PR
O
JE
C
T N
A M
E:
KEYPLAN
DRAWING NUMBER:
PROJ #: 2024090.00
DATE: 06/06/2025
CHECK BY:
DRAWN BY:
SCALE:
U se r I D
Fi le N am e:
Fi le
P at h:
E0
-L
G N
D .d w g
U :\2
4\
0.
\B
IM
\C
AD
\E le ct ric al
6/ 9/
1:
:4
PM
R iv er a- Pe na , K ris tia n G
N
AV N E MLZ
E N G I N E E R S
VAN ZELM HEYWOOD & SHADFORD, INC.
10 TALCOTT NOTCH, FARMINGTON, CT 06032 - 1800
Connecticut | Massachusetts | North Carolina
CT: 860.284.5064 MA: 617.218.9976 NC: 704.799.7275
AMITY
ISSUED FOR BID
JUNE 06,2025
E001
BGS
EDA/AJD
NONE
ELECTRICAL LEGENDS
AND GENERAL NOTES
A B
C D
E
3 4
6 7 8
K
9 10
A6
C106
ART ROOM
B117
CLASSROOM
OPEN
B118
TEAM ROOM
B137
COMPUTER LAB
C101
CORRIDOR
C116
CORRIDOR
C100
TELE DATA
IDF
C105
HEALTH
C104
BOOK STORAGE
C102
TOILET
FACULTY
C103
TOILET
FACULTY
C111
CORRIDOR
D121
TESTING
SPECIAL ED.
D119
ELEC. ROOM
D124
SPECIAL ED.
C109
CORRIDOR
C107
KILN ROOM
C115
PASSAGE
C112
SHOP
TECH. ED.
C113
CLASSROOM
TECH. ED.
D101
ENGLISH
D102
SOCIAL STUDIESC108
TOOL STORAGE
C114
DUST COLLECTOR
LPD1
CPD2
CPD1
PPD1
PPD2
PPD3
ELECTRICAL GENERAL NOTES:
1. REMOTE ALARM PANEL FTA200-A IS SUPPLIED BY FIRE PROTECTION
CONTRACTOR.COORDINATE WITH FIRE PROTECTION CONTRACTOR FOR ITS
INSTALLATION.
2. PROVIDE 120V 1P 20A TO POWER THE REMOTE ALARM PANEL FROM ONE OF THE
NEAREST PANELBOARD LOCATED IN ELECTRICAL ROOM 410. PROVIDE 2 #
12,1#12G, 3 /4 " C.
3. FURNISH AND INSTALL 16 #12 + 1 #12G 3 / 4 " C. COORDINATE WITH CLIENT AND
FIRE PUMP CONTRACTOR ON THE SIGNAL / ALARM TO WIRE FROM FIRE PUMP
CONTROLLER TO REMOTE ALARM PANEL.
FIRE PUMP HOUSE
REMOTE ALARM PANEL
ER
FIRE PUMP
CONTROLLER W/ATS
DATE
REV.
NO.
DRAWING TITLE:
FI
R
E P
U M
P R
E
PL
A C
E M
E N
T B
E T
H A
N Y
M
ID
D L
E S
C H
O O
L
A M
IT
Y
R
EG
IO
N
LU
K
E H
IL
L
R O
A D
B
ET
H A
N Y
, C T
DESCRIPTION
REVISIONS
PR
O
JE
C
T N
A M
E:
KEYPLAN
DRAWING NUMBER:
PROJ #: 2024090.00
DATE: 06/06/2025
CHECK BY:
DRAWN BY:
SCALE:
U se r I D
Fi le N am e:
Fi le
P at h:
E1
-F
L0 1.
dw g
U :\2
4\
0.
\B
IM
\C
AD
\E le ct ric al
6/ 9/
1:
:4
PM
R iv er a- Pe na , K ris tia n G
N
AV N E MLZ
E N G I N E E R S
VAN ZELM HEYWOOD & SHADFORD, INC.
10 TALCOTT NOTCH, FARMINGTON, CT 06032 - 1800
Connecticut | Massachusetts | North Carolina
CT: 860.284.5064 MA: 617.218.9976 NC: 704.799.7275
AMITY
ISSUED FOR BID
JUNE 06,2025
E101
BGS
EDA/AJD
1/2"=1'-0"
ELECTRICAL MAIN
BUILDING PARTIAL
FLOOR PLANS
SCALE:1 1/8" = 1'-0"
ELECTRICAL ROOM D119
AutoCAD SHX Text
FEL
SCALE:1 1/2" = 1'-0"
ELECTRICAL DEMOLITION UPPER LEVEL VAULT
SCALE:2 1/2" = 1'-0"
ELECTRICAL DEMOLITION LOWER LEVEL VAULT
SCALE:3 1/2" = 1'-0"
ELECTRICAL NEW WORK UPPER LEVEL VAULT
SCALE:4 1/2" = 1'-0"
ELECTRICAL NEW WORK LOWER LEVEL VAULT
FIRE PUMP
CONTROLLER W/ATS
JOCKEY PUMP
CONTROLLER
NEW SUMP PUMPS.
SAME MODEL AS
EXISTING PUMPS.
NEW INLINE ELECTRIC
FIRE PUMP ON NEW
CONCRETE PAD.
NEW JOCKEY PUMP
EXISTING JOCKEY PUMP
TO BE REMOVED
EXISTING FIRE PUMP
AND CONCRETE PAD TO
BE REMOVED
(2)EXISTING SUMP PUMP
TO BE REMOVED.
RR
ER
RR RR
RR
ER
PANELBOARD
"FPV"
ELECTRICAL POWER UPPER LEVEL DEMO WORK NOTES :
ER - EXISTING TO REMAIN.
RR - REMOVE AND REPLACE
DISCONNECT MAIN FEED POWER TO PANELBOARD "FPV",
JOCKEY PUMP CONTROLLER PANEL AND FIRE PUMP
CONTROLLER W/ATS.
ELECTRICAL POWER UPPER LEVEL NEW WORK NOTES :
RECONNECT MAIN FEED POWER TO PANELBOARD "FPV" , JOCKEY
PUMP CONTROLLER PANEL AND FIRE PUMP CONTROLLER W/ATS..
FURNISH AND INSTALL NEW CONDUCTOR AND CONDUIT FROM
PANELBOARD "FPV" TO TWO NEW SUMP PUMP PANELS.
FURNISH AND INSTALL NEW CONDUIT AND CONDUCTORS FROM FIRE
ALARM CONTROLLER PANEL TO THE REMOTE ALARM PANEL
LOCATED IN THE CORRIDOR IN THE MAIN SCHOOL BUILDING. REFER
DRAWING E-102 FOR ADDITIONAL INFORMATION.
FURNISH AND INSTALL NEW FTA200-A REMOTE ALARM PANEL.
COORDINATE WITH FIRE PROTECTION CONTRACTOR AND CLIENT
FOR ITS LOCATION AND COMPLY WITH MANUFACTURER
INSTRUCTION FOR ITS INSTALLATION. REFER DRAWING E-101 FOR
ADDITIONAL INFORMATION.
ELECTRICAL POWER LOWER LEVEL DEMO WORK NOTES :
DISCONNECT AND REMOVE POWER TO JOCKEY PUMP.
EVALUATE THE EXISTING CONDITION OF THE CONDUIT,
CONDUCTORS AND IF THE RESULT OF EVALUATION IS THAT
THE CONDUITS AND CONDUCTORS CANNOT BE REUSED FOR
NEW WORK, THEN DEMO THE CONDUIT AND CONDUCTORS
OF JOCKEY PUMP. IF NOT, PRESERVE THE CONDUIT AND
CONDUCTORS FOR NEW WORK.
DISCONNECT AND REMOVE POWER TO FIRE PUMP.
EVALUATE THE EXISTING CONDITION OF THE CONDUIT,
CONDUCTORS AND IF THE RESULT OF EVALUATION IS THAT
THE CONDUITS AND CONDUCTORS CANNOT BE REUSED FOR
NEW WORK, THEN DEMO THE CONDUIT AND CONDUCTORS
OF JOCKEY PUMP. IF NOT, PRESERVE THE CONDUIT AND
CONDUCTORS FOR NEW WORK.
DISCONNECT AND REMOVE FEED TO SOURCE FOR SUMP
PUMP PANEL AND SUMP PUMPS WHICH ARE BEING
DEMOLISHED.
ELECTRICAL POWER LOWER LEVEL NEW WORK NOTES :
NEW CONDUITS / CONDUCTORS OR EXTEND THE
PRESERVED EXISTING FEED AS PER THE DEMOLITION
NOTES OF JOCKEY PUMP TO RECONNECT POWER TO
JOCKEY PUMP FROM THE JOCKEY PUMP CONTROLLER
PANEL. REFER TO FP-101 DRAWINGS AND COORDINATE
WITH FIRE PROTECTION CONTRACTOR FOR ITS
SPECIFICATIONS AND INSTALLATION.
NEW CONDUITS / CONDUCTORS OR EXTEND THE
PRESERVED EXISTING FEED AS PER THE DEMOLITION
NOTES OF FIRE PUMP TO RECONNECT POWER TO INLINE
FIRE PUMP FROM FIRE PUMP CONTROLLER PANEL.REFER
TO FP-101 DRAWINGS AND COORDINATE WITH FIRE
PROTECTION CONTRACTOR FOR ITS SPECIFICATIONS
AND INSTALLATION.
SUMP PUMP PANELS, JUNCTION BOX FOR SUMP PUMPS,
SUMP PUMPS, CABLES AND ACCESSORIES ARE SUPPLIED
BY FIRE PROTECTION CONTRACTOR. COORDINATE WITH
FIRE PROTECTION CONTRACTOR FOR THE INSTALLATION,
WIRING AS NEEDED FOR THE SUMP PUMPS, SUMP PUMP
PANELS AND JUNCTION BOX. REFER TO FP-101 DRAWING
FOR FURTHER INFORMATION.
REFER TO FP-101 AND FP-200-DETAIL FIRE PROTECTION
DRAWING TO COORDINATE WITH THE WIRING OF
SUPERVISORY SWITCH, FLOW SWITCH AND PRESSURE
SWITCH. ALL THE SWITCHES TO BE TIED TO THE EXISTING
FIRE ALARM SYSTEM. ELECTRICAL CONTRACTOR TO
COORDINATE WITH FIRE PROTECTION CONTRACTOR FOR
THE SCOPE OF THIS WORK.
FIRE PUMP
CONTROLLER W/ATS
NEW JOCKEY PUMP
CONTROLLER
PANELBOARD
"FPV"
NEW SUMP PUMP
PANEL
NEW SUMP PUMP
PANEL NEW JUNCTION BOX
FOR SUMP PUMP
PANEL
NEW JUNCTION BOX
FOR SUMP PUMP
PANEL
GFCI
GFCI
DATE
REV.
NO.
DRAWING TITLE:
FI
R
E P
U M
P R
E
PL
A C
E M
E N
T B
E T
H A
N Y
M
ID
D L
E S
C H
O O
L
A M
IT
Y
R
EG
IO
N
LU
K
E H
IL
L
R O
A D
B
ET
H A
N Y
, C T
DESCRIPTION
REVISIONS
PR
O
JE
C
T N
A M
E:
KEYPLAN
DRAWING NUMBER:
PROJ #: 2024090.00
DATE: 06/06/2025
CHECK BY:
DRAWN BY:
SCALE:
U se r I D
Fi le N am e:
Fi le
P at h:
E1
-F
L0 1.
dw g
U :\2
4\
0.
\B
IM
\C
AD
\E le ct ric al
6/ 9/
1:
:4
PM
R iv er a- Pe na , K ris tia n G
N
AV N E MLZ
E N G I N E E R S
VAN ZELM HEYWOOD & SHADFORD, INC.
10 TALCOTT NOTCH, FARMINGTON, CT 06032 - 1800
Connecticut | Massachusetts | North Carolina
CT: 860.284.5064 MA: 617.218.9976 NC: 704.799.7275
AMITY
ISSUED FOR BID
JUNE 06,2025
E102
BGS
EJF
1/2"=1'-0"
ELECTRICAL UPPER AND
LOWER LEVEL VAULT
FLOOR PLANS
| Sheets and Views |
| E001-LGND-E-001 |
| SEU101-SITE-E-101 |
| E101-FL01-E-101 |
| E101-FL01-E-102 |
| E600-SPEC-E-600 |
| E600-SPEC-E-601 |
File details come from the government source that posted it. Updated .