FA875126Q0013 Attachment 4 B3 Lighting Floor Plan.pdf
PDF 268 KB Posted
- Attached to
- Renovate Suite H8, Building 3
- Solicitation number
- FA875126Q0013
About this file
This is an electrical construction drawing for Suite H8 lighting controls at Rome Research Site, Building 3 in Rome, New York, dated June 18, 2026. The drawing provides detailed specifications and installation requirements for a WattStopper lighting control system retrofit project designated ULDF20-0308.
The project requires installation of multiple WattStopper control devices including motion sensors (LMDC-100, LMDX-100), dimming digital switches (LMSW-211), room controllers (LMRC-213), network bridge devices (LMBC-300, LMBC-61), and a motion detector switch (LMDW-101). Devices must be mounted in specified ceiling and wall locations throughout Suite H8 and connected via plenum-rated Cat 5e cable with RJ-45 connectors in a free topology network configuration. Critical installation requirements include mounting motion sensors at exact manufacturer-specified locations, installing dimming switches per manufacturer instructions, connecting room controllers to lighting loads, and properly configuring all devices to the network bridge. The contractor must record all device serial numbers on the WattStopper device schedule provided on the drawing, test all field-fabricated cables before connection, document actual device locations and circuits on as-built documentation, and contact AFRL/RIOCC Civil Engineering at 330-7634 for clarification on device connections. A discontinued motion detector switch will be provided by the government and requires connection to the existing room network on the mezzanine level above Suite H8.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Suite H8
H8-B
LMDC-48.9,10.2 LVP-G8-8
G8-P
(Load A)
LVP-H7-1 #5
LVP-H7-1 #5
LMRC
212RC-34.2,3
LMRC
101MRC-34.4
WS
WS
MDX-34.2.5
MDX-34.2.4
MDX-34.2.3
2,3.2
DM-34.2.1
MDM-34.3.1
HVP-H8-1
LVP-H8-4
LVP-H7-1
UP
H8-D
Corridor 8 H8-D H8-E H8-F H8-H
H8-M
H8-L
H8-K
H8-C
H8-A
E
E
E
E
E
E
WS
LMDM-61.1.1
WS
LMDM-61.5.1
LMDC-61.3.1
LMDC-61.3.2
LMDC-61.3.3
LMDC-61.6.1
LMDX-61.4.4
LMDX-61.4.3
LMDX-61.4.2
LMDC-61.8.3
LMDC-61.8.2
LMDX-61.7.4
LMDX-61.7.2 LMDX-61.7.3
WS
LMDM-61.2.1
LMDC-61.2.2
LMDC-61.2.3
LMRC-61.1,2,3 (Load B)
WS
1 LMDM-61.9.1
WS
LMDM-61.4.1
WS
LMDM-61.7.1
WS
LMDM-61.8.1
LMRC-61.4,5,6 (Load B)
LMRC-61.1,2,3 (Load C)
LMRC-61.7,8 (Load A)
LMRC-61.7,8 (Load B)
LMRC-61.7,8,9 (Load C)
LMRC
LMRC-61.1,2,3
LMBCLMBC-61
HVP-H8-1 #21 LMRC-61.1,2,3 (Load A)
LMRC
LMRC-61.4,5,6 HVP-H8-1 #19
LMRC
LMRC-61.7,8,9 HVP-H8-1 #24
LMRC-61.4,5,6 (Load C)
LMRC-61.4,5,6 (Load A)
U P
UP
LMDW-33.4.1
LMDX-33.4.2
LMRC
101 LMRC-33.4
LMRC-33.4
H8-D
DOWN
LMDW-33.4.3
WattStopper Devices
LABEL PART # LOCATION
LMBC
CONNECTION
SERIAL
NUMBER
LMBC-61 LMBC-300 Corridor G -
LMRC-61.1,2,3 LMRC-213
Corridor 8 (N Closet) LMBC-61
LMDM-61.1.1 LMSW-211 Corridor 8 LMBC-61
LMDM-61.2.1 LMSW-211 H8-B LMBC-61
LMDC-61.2.2 LMDC-100 H8-B LMBC-61
LMDC-61.2.3 LMDC-100 H8-B LMBC-61
LMDC-61.3.1 LMDC-100 Corridor 8 LMBC-61
LMDC-35.3.2 LMDC-100 Corridor 8 LMBC-61
LMDC-61.3.3 LMDC-100 Corridor 8 LMBC-61
LMRC-61.4,5,6 LMRC-213 Corridor 8 LMBC-61
LMDM-61.4.1 LMSW-211 H8-M LMBC-61
LMDX-61.4.2 LMDX-100 H8-M LMBC-61
LMDX-61.4.3 LMDX-100 H8-M LMBC-61
LMDX-61.4.4 LMDX-100 H8-M LMBC-61
LMDM-61.5.1 LMSW-211 Corridor 8 LMBC-61
LMDC-61.6.1 LMDC-100 H8-A LMBC-61
LMRC-61.7,8,9 LMRC-213 H8-C LMBC-61
LMDM-61.7.1 LMSW-211 H8-K LMBC-61
LMDX-61.7.2 LMDX-100 H8-K LMBC-61
LMDX-71.7.3 LMDX-100 H8-K LMBC-61
LMDX-71.7.4 LMDX-100 H8-K LMBC-61
LMDM-61.8.1 LMSW-211 H8-L LMBC-61
LMDC-61.8.2 LMDC-100 H8-L LMBC-61
LMDC-61.8.3 LMDC-100 H8-L LMBC-61
LMDM-61.9.1 LMSW-211 H8-C LMBC-61
LMDW-33.4.3 LMDW-101 Roof Access LMBC-33
LIGHTING CONTROL NOTES:
1. PROVIDE DEVICES AS SHOWN ON NEW LIGHTING CONTROL LAYOUT PLANS AND WATTSTOPPER DEVICE
SCHEDULE ON THIS PAGE. ATTACH SERIAL NUMBER STICKERS PROVIDED WITH NEW DEVICES IN DEVICE
SCHEDULE AS NECESSARY. FOR RELOCATED DEVICES RECORD SERIAL NUMBERS IN SCHEDULE.
2. MOUNT MOTION SENSORS (LMDC-100, LMDX-100) IN CEILING AT EXACT LOCATIONS SHOWN ACCORDING TO
MANUFACTURER'S INSTRUCTIONS.
3. MOTION DETECTOR SWITCH (LMDW-101) LOCATED AT ROOF ACCESS IS A DISCONTINUES DEVICE WHICH WILL BE PROVIDED BY THE GOVERNMENT. CONNECT TO EXISTING ROOM NETWORK ON MEZZANINE LEVEL
ABOVE SUITE H8.
4. INSTALL DIMMING DIGITAL SWITCHES (LMSW-211) IN LOCATIONS SHOWN ACCORDING TO MANUFACTURER'S
INSTRUCTIONS.
5. CONNECT ROOM CONTROLLERS (LMRC-213) TO LIGHTING LOADS AS INDICTED ACCORDING TO
MANUFACTURER'S INSTRUCTIONS. NOTE LOCATION OF ROOM CONTROLLERS ON AS-BUILT
DOCUMENTATION.
6. CONNECT MOTION SENSORS, SWITCHES AND ROOM CONTROLLERS TOGETHER USING PLENUM RATED CAT 5e CABLE WITH RJ-45 ENDS. IT IS RECOMMENDED THAT FIELD FABRICATED CABLES BE TESTED FOR PROPER OPERATION BEFORE BEING CONNECTED. IT IS CRITICAL THAT "LOCAL NETWORK" DEVICES ARE CONNECTED CORRECTLY TO EACH NETWORK BRIDGE DEVICE (LMBC-300). "LOCAL NETWORKS" ARE FREE TOPOLOGY NETWORKS AND DEVICES CAN BE CONNECTED TO EACH OTHER THROUGH ANY OPEN RJ-45
PORT.
7. IT IS CRITICAL THAT SERIAL NUMBERS FOR ALL DEVICES ARE NOTED UPON INSTALLATION. SPACE HAS BEEN PROVIDED IN THE WATTSTOPPER DEVICE SCHEDULE ON THIS PAGE TO AFFIX SERIAL NUMBER STICKERS INCLUDED WITH ALL NEW DEVICES. ALSO NOTE ON AS-BUILT DOCUMENTATION ACTUAL LOCATIONS OF ALL DEVICES AND CIRCUITS FEEDING ROOM CONTROLLERS. IF THERE ARE QUESTIONS ABOUT CONNECTING DEVICES, PLEASE CONTACT AFRL/RIOCC CIVIL ENGINEERING AT 330-7634.
LIGHTING LOAD A
LIGHTING LOAD B
LIGHTING LOAD C
ZONE LIGHTING
FEED CIRCUIT
N BUILDING 3 FLOOR PLAN
SUITE H8 LIGHTING 1/8"=1'-0"
Rome Research Site, New York
ROME RESEARCH SITE
PROJECT MANAGER:
DESIGNER:
DRAFTER:
SHEET TITLE:
PROJECT TITLE:
DATE:SHEET:DRAWING NO: FACILITY NO:
PROJECT NO:
OF
RENOVATE SUITE H8
1 18 JUN 2026
MWF
ULDF20-0308
BLDG. 3
ELECTRICAL
SUITE H8 LIGHTING
CONTROLS
LC-101 1
MWF
MWF
N BUILDING 3 MEZZ./ROOF PLAN
AREA ABOVE SUITE H8 1/8"=1'-0"
LIGHTING CONTROL WIRING DETAIL
NO SCALE
File details come from the government source that posted it. Updated .