This is a specification document for Section 05 40 00 Cold-Formed Metal Framing for the AFRL Renovate H8 Laboratory project (Contract No. ULDF200308AE), revised August 18, 2018. The specification establishes comprehensive requirements for the design, manufacture, delivery, and installation of load-bearing cold-formed steel framing components, including studs, joists, tracks, bracing, bridging, and accessories. All framing components must comply with ASTM C955 and be manufactured from steel sheet meeting ASTM A1003/A1003M Structural Grade ST50H with metallic coating (G60, A60, AZ50, or GF30). Steel studs must be C-shaped with minimum 0.0428-inch base-metal thickness and 1-5/8-inch flange width, while steel tracks must be U-shaped with matching thickness. Studs and joists of 54 mils or heavier must use galvanized steel per ASTM A653/A653M and ASTM A1003/A1003M (SS Grade 50, G60), whereas lighter gauge members (43 mils or lighter) must meet SS Grade 33 (33,000 psi) specifications. Products must contain minimum 25 percent average recycled content of steel.
The specification mandates strict quality assurance requirements including mill certificates or independent testing agency reports demonstrating compliance with minimum yield strengths and uncoated steel thickness per ASTM A370 coupon testing. Framing design must follow AISI S100, with shop drawings and design calculations prepared by registered professional engineers requiring government approval. Installation must comply with ASTM C1007 and AISI S200. Fastening methods include welding per AWS D1.3/D1.3M (qualified procedures and personnel required, no field welding of materials lighter than 43 mils) or self-drilling, self-tapping screws per ASTM C1513 with hot-dip galvanizing per ASTM A123/A123M or electroplated coating per ASTM F1941. Steel-to-concrete connections utilize ASTM F1554 Grade 55 anchor rods, post-installed adhesive or expansion anchors, or power-actuated fasteners. Installation tolerances vary by finish type: framing covered with wallboard or mortar-set tile allows 1/4-inch deviation in 8 feet, while ceramic tile set in dry-set or organic adhesive requires tighter 1/8-inch tolerances. Erection includes horizontal bracing requirements based on load type and wall height, with specific spacing limits for wind and axial loads.
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AFRL, RENOVATE H8 LABORATORY, B3 ULDF200308AE
SECTION 05 40 00
COLD-FORMED METAL FRAMING
05/15, CHG 1: 08/18
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN CONCRETE INSTITUTE (ACI)
ACI 318 (2019; R 2022) Building Code Requirements for Structural Concrete (ACI 318-19) and Commentary (ACI 318R-19)
AMERICAN IRON AND STEEL INSTITUTE (AISI)
AISI S100 (2012) North American Specification for the Design of Cold-Formed Steel Structural Members
AISI S110 (2007; Suppl 1; Reaffirmed 2012) Standard for Seismic Design of Cold-Formed Steel Structural Systems - Special Bolted Moment Frames
AISI S200 (2007) North American Standard for Cold-Formed Steel Framing - General Provision
AISI S201 (2007) North American Standard for Cold-Formed Steel Framing - Product Data
AISI S202 (2011) Code of Standard Practice for Cold-formed Steel Structural Framing
AISI S211 (2007) North American Standard for Cold-Formed Steel Framing - Wall Stud Design
AISI S212 (2007) North American Standard for Cold-Formed Steel Framing - Header Design
AISI S213 (2007; Suppl 1 2009) North American Standard for Cold-Formed Steel Framing - Lateral Design
AISI S214 (2012) North American Standard for Cold-Formed Steel Framing – Truss Design
AMERICAN WELDING SOCIETY (AWS)
AWS D1.1/D1.1M (2020; Errata 1 2021) Structural Welding Code - Steel
SECTION 05 40 00 PAGE 1
AWS D1.3/D1.3M (2018) Structural Welding Code - Sheet Steel
ASTM INTERNATIONAL (ASTM)
ASTM A123/A123M (2024) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products
ASTM A153/A153M (2023) Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware
ASTM A307 (2021) Standard Specification for Carbon Steel Bolts, Studs, and Threaded Rod 60 000 PSI Tensile Strength
ASTM A370 (2024) Standard Test Methods and Definitions for Mechanical Testing of Steel Products
ASTM A653/A653M (2023) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A1003/A1003M (2023; E 2024) Standard Specification for Steel Sheet, Carbon, Metallic- and Nonmetallic-Coated for Cold-Formed Framing Members
ASTM C955 (2024) Standard Specification for Cold-Formed Steel Structural Framing Members
ASTM C1007 (2020) Standard Specification for Installation of Load Bearing (Transverse and Axial) Steel Studs and Related Accessories
ASTM C1513 (2024) Standard Specification for Steel Tapping Screws for Cold-Formed Steel Framing Connections
ASTM E119 (2024) Standard Test Methods for Fire Tests of Building Construction and Materials
ASTM E329 (2023) Standard Specification for Agencies Engaged in Construction Inspection, Testing, or Special Inspection
ASTM E488/E488M (2022) Standard Test Methods for Strength of Anchors in Concrete Elements
ASTM F1554 (2020) Standard Specification for Anchor Bolts, Steel, 36, 55, and 105-ksi Yield Strength
SECTION 05 40 00 PAGE 2
ASTM F1941 (2010) Standard Specification for Electrodeposited Coatings on Threaded Fasteners (Unified Inch Screw Threads
(UN/UNR))
ASTM F2329/F2329M (2015; R 2023) Standard Specification for Zinc Coating, Hot-Dip, Requirements for Application to Carbon and Alloy Steel Bolts, Screws, Washers, Nuts, and Special Threaded Fasteners
INTERNATIONAL CODE COUNCIL (ICC)
ICC IBC (2024) International Building Code
U.S. DEPARTMENT OF DEFENSE (DOD)
UFC 3-301-01 (2023; with Change 2, 2024) Structural Engineering
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Framing Components ; G
SD-03 Product Data
Steel Studs, Joists , Tracks, Bracing, Bridging and Accessories
Recycled Content of Steel Products ; S
SD-07 Certificates
Load-Bearing Cold-Formed Metal Framing
Welds
1.3 DELIVERY, STORAGE, AND HANDLING
Steel framing and related accessories shall be stored and handled in accordance with the AISI S202 , "Code of Standard Practice for Cold-Formed Steel Structural Framing".
1.4 LOAD-BEARING COLD-FORMED METAL FRAMING
Include top and bottom tracks, bracing, fastenings, and other accessories necessary for complete installation. Framing members shall have the structural properties indicated. Where physical structural properties are not indicated, they shall be as necessary to withstand all imposed loads.
Design framing in accordance with AISI S100 .
Submit mill certificates or test reports from independent testing agency, SECTION 05 40 00 PAGE 3 qualified in accordance with ASTM E329, showing that the steel sheet used in the manufacture of each cold-formed component complies with the minimum yield strengths and uncoated steel thickness specified. Test reports shall be based on the results of three coupon tests in accordance with
ASTM A370.
1.5 MAXIMUM DEFLECTION
Deflections of structural members shall not exceed the more restrictive of the limitations of ICC IBC and UFC 3-301-01 .
1.6 QUALITY ASSURANCE
a. Engineering Responsibility: Preparation of Shop Drawings, design calculations, and other structural data by a registered professional engineer.
b. Testing Agency Qualifications: An independent testing agency, acceptable to authorities having jurisdiction, qualified according to ASTM E329 for testing indicated.
c. Product Tests: Mill certificates or data from a qualified independent testing agency indicating steel sheet complies with requirements, including base-metal thickness, yield strength, tensile strength, total elongation, chemical requirements, and metallic-coating thickness.
d. Welding Qualifications: Qualify procedures and personnel according to the following:
(1) AWS D1.1/D1.1M , "Structural Welding Code - Steel".
(2) AWS D1.3/D1.3M , "Structural Welding Code - Sheet Steel".
e. Fire-Test-Response Characteristics: Where indicated, provide cold-formed metal framing identical to that of assemblies tested for fire resistance per ASTM E119 by, and displaying a classification label from, a testing and inspecting agency acceptable to authorities having jurisdiction.
f. AISI Specifications and Standards: Comply with:
(1) AISI S100 , "North American Specification for the Design of Cold-Formed Steel Structural Members".
(2) AISI S110 , "Standard for Seismic Design of Cold-Formed Steel Structural Systems - Special Bolted Moment Frames".
(3) AISI S200 , "North American Standard for Cold-Formed Steel Framing
- General Provision".
(4) AISI S201 , "North American Standard for Cold-Formed Steel Framing
- Product Data".
(5) AISI S202 , "Code of Standard Practice for Cold-Formed Steel Structural Framing".
(6) AISI S211 , "North American Standard for Cold-Formed Steel Framing
- Wall Stud Design".
SECTION 05 40 00 PAGE 4
(7) AISI S212 , "North American Standard for Cold-Formed Steel Framing
- Header Design".
(8) AISI S213 , "North American Standard for Cold-Formed Steel Framing
- Lateral Design".
(9) AISI S214 , "North American Standard for Cold-Formed Steel Framing
- Truss Design".
1.6.1 Drawing Requirements
Submit framing components to show sizes, thicknesses, layout, material designations, methods of installation, and accessories including the following:
a. Cross sections, plans, and/or elevations showing component types and locations for each framing application; including shop coatings and material thicknesses for each framing component.
b. Connection details showing fastener type, quantity, location, and other information to assure proper installation.
c. Drawings depicting panel configuration, dimensions, components, locations, and construction sequence if the Contractor elects to install prefabricated/prefinished frames.
PART 2 PRODUCTS
2.1 STEEL STUDS, JOISTS , TRACKS, BRACING, BRIDGING AND ACCESSORIES
Framing components shall comply with ASTM C955 and the following.
a. Provide products with an average recycled content of steel products so postconsumer recycled content plus one half of preconsumer recycled content not less than 25 percent.
b. Steel Sheet: ASTM A1003/A1003M , Structural Grade, Type H, metallic coated, of grade and coating weight as follows:
(1) Grade: ST50H (ST340H).
(2) Coating: G60 (Z180), A60 (ZF180), AZ50 (AZ150), or GF30 (ZGF90).
c. Steel Studs: Manufacturer's standard C-shaped steel studs, of web depths indicated, punched, with stiffened flanges, and as follows:
(1) Minimum Base-Metal Thickness: 0.0428 inch .
(2) Flange Width: 1-5/8 inches .
d. Steel Track: Manufacturer's standard U-shaped steel track, of web depths indicated, unpunched, with straight flanges, and as follows:
(1) Minimum Base-Metal Thickness: Matching steel studs.
(2) Flange Width: 1- 5/8 inches .
SECTION 05 40 00 PAGE 5
2.1.1 Studs and Joists of 54 mils (0.054 Inch) and Heavier
Galvanized steel, ASTM A653/A653M and ASTM A1003/A1003M , SS Grade 50, G60 .
2.1.2 Studs and Joists of 43 mils (0.043 Inch) and Lighter
Studs and Joists of 43 mils (0.043 Inch) and Lighter, Track, and Accessories (All thicknesses): Galvanized steel, ASTM A653/A653M and ASTM A1003/A1003M , SS, Grade 33 33,000 psi G60 .
2.1.3 Sizes, Thickness, Section Modulus, and Other Structural Properties
Size and thickness as indicated and/or as required.
2.2 MARKINGS
Studs and track shall have product markings stamped on the web of the section. The markings shall be repeated throughout the length of the member at a maximum spacing of 4 feet on center and shall be legible and easily read. The product marking shall include the following:
a. An ICC number.
b. Manufacturer's identification.
c. Minimum delivered uncoated steel thickness.
d. Protective coating designator.
e. Minimum yield strength.
2.3 CONNECTIONS
2.3.1 Steel-To-Concrete Connections
a. Anchor Rods: ASTM F1554, Grade 55; galvanized per ASTM A153/A153M .
b. Post-Installed Concrete Anchors: Adhesive or expansion anchors fabricated from corrosion-resistant materials with allowable load capacities in accordance with ICC-ES AC193 and ACI 318 greater than or equal to the design load as determined by testing per ASTM E488/E488M conducted by a qualified testing agency.
c. Power-Actuated Fasteners: Fabricated from corrosion-resistant materials with allowable load capacities in accordance with ICC-ES AC 70 greater than or equal to the design load as determined by testing per ASTM E1190 conducted by a qualified testing agency.
2.3.2 Steel-To-Steel Connections
a. Screws: ASTM C1513, corrosion-resistant-coated, self-drilling, self-tapping steel screws of the type and size indicated. Provide low-profile head beneath sheathing and manufacturer's standard elsewhere. Electroplated to a minimum of 5 micron zinc coating per ASTM F1941 or hot-dipped galvanized per ASTM A123/A123M or
ASTM A153/A153M .
b. Bolts: ASTM A307 coated by hot-dip process per ASTM F2329/F2329M or zinc-coated by mechanical-deposition process per ASTM B695, Class 55.
SECTION 05 40 00 PAGE 6
c. Welding Electrodes: Comply with AWS standards.
2.4 PLASTIC GROMMETS
Supply plastic grommets for stud webs as recommended by stud manufacturer, to protect electrical wires and plumbing piping. Prevent metal-to-metal contact between wiring/piping and studs.
2.5 SEALER GASKET
Closed-cell neoprene foam, 1/4-inch thick, selected from manufacturer's standard widths to match width of bottom track on concrete slab or foundation.
PART 3 EXECUTION
3.1 FASTENING
Fasten framing members together by welding or by using self-drilling, self-tapping screws. Electrodes and screw connections shall be as required and indicated in the design calculations.
3.1.1 Welds
All welding shall be performed in accordance with AWS D1.3/D1.3M , as modified by AISI S100 . All welders, welding operations, and welding procedures shall be qualified according to AWS D1.3/D1.3M . Submit certified copies of welder qualifications test records showing qualification in accordance with AWS D1.3/D1.3M . All welds shall be cleaned and coated with rust inhibitive galvanizing paint. Do not field weld materials lighter than 43 mils .
3.1.2 Screws
Screws shall be of the self-drilling self-tapping type, size, and location as required. Screw penetration through joined materials shall not be less than three exposed threads. Minimum spacings and edge distances for screws shall be as specified in AISI S100 . Screws covered by sheathing materials shall have low profile heads.
3.1.3 Anchors
Anchors shall be of the type, size, and location as indicated and/or as required.
3.1.4 Powder-Actuated Fasteners
Powder-actuated fasteners shall be of the type, size, and location as required.
3.2 INSTALLATION
Install cold-formed framing in accordance with ASTM C1007 and AISI S200 .
Install cold-formed steel framing according to AISI S202 and to manufacturer's written instructions unless more stringent requirements are indicated.
SECTION 05 40 00 PAGE 7
3.2.1 Tracks
Provide accurately aligned runners at top and bottom of studs. Install sealer gasket under bottom of track on concrete slab or foundation.
Anchor tracks as indicated in design calculations. Butt weld joints in tracks or splice with stud inserts. Fasteners shall be at least 3 inches from the edge of concrete slabs.
3.2.2 Studs
Cut studs square and set with firm bearing against webs of top and bottom tracks. Position studs vertically in tracks and space as indicated in design. Do not splice studs. Provide at least two studs at jambs of doors and other openings 2 feet wide or larger. Provide jack studs over openings, as necessary, to maintain indicated stud spacing. Provide tripled studs at corners, positioned to receive interior and exterior finishes. Fasten studs to top and bottom tracks by welding or screwing both flanges to the tracks. Framed wall openings shall include headers and supporting components as shown on the drawings. Headers shall be installed in all openings that are larger than the stud spacing in a wall. In curtain wall construction, provide for vertical movement where studs connect to the structural frame. Provide horizontal bracing in accordance with the design calculations and AISI S100 . Bracing shall be not less than the following:
LOAD HEIGHT BRACING
Wind load only Up to 10 feet One row at mid-height
Over 10 feet Rows 5'-0" o.c. maximum
Axial load Up to 10 feet Two rows at 1/3 points
Over 10 feet Rows 3'-4" o.c. maximum
3.2.3 Joists and Trusses
a. Provide a stud directly under each joist or truss. The maximum spacing of studs as indicated shall be maintained.
b. Install, bridge, and brace cold-formed steel trusses according to AISI S200 , AISI S214 , AISI's "Code of Standard Practice for Cold-Formed Steel Structural Framing," and manufacturer's written instructions unless more stringent requirements are indicated.
c. Install temporary bracing and supports. Maintain braces and supports in place, undisturbed, until entire integrated supporting structure has been completed and permanent connections to framing are secured.
d. Do not alter, cut, or remove framing members or connections of trusses.
3.2.4 Erection Tolerances
a. Framing members which will be covered by finishes such as wallboard, SECTION 05 40 00 PAGE 8 plaster, or ceramic tile set in a mortar setting bed, shall be within the following limits:
(a) 1) Layout of walls and partitions: 1/4 inch from intended position;
(b) 2) Plates and runners: 1/4 inch in 8 feet from a straight line;
(c) 3) Studs: 1/4 inch in 8 feet out of plumb, not cumulative;
and
(d) 4) Face of framing members: 1/4 inch in 8 feet from a true plane.
b. Framing members which will be covered by ceramic tile set in dry-set mortar, latex-portland cement mortar, or organic adhesive shall be within the following limits:
(a) 1) Layout of walls and partitions: 1/4 inch from intended position;
(b) 2) Plates and runners: 1/8 inch in 8 feet from a straight line;
(c) 3) Studs: 1/8 inch in 8 feet out of plumb, not cumulative;
and
(d) 4) Face of framing members: 1/8 inch in 8 feet from a true plane.
-- End of Section --