The site information sheet provides details on the UPS configuration including the 80kVA single module from Powerware with a 64kW output. It is currently supporting an 18kVA system load. Battery details include two parallel cabinets each with 40 sealed lead acid jars in series from Eaton, totaling 80 jars. Preventative maintenance is due semi-annually for modules and batteries.
The federal contract opportunity is for emergency and preventative maintenance of UPS systems, batteries, and ancillary equipment at various Air Force locations. Line items include maintenance, diagnostics, repairs, and travel. The solicitation number is FA8217-18-R-5007 and is seeking services from April 2019 through April 2024. The Department of the Air Force Materiel Command Lifecycle Management Center at Hill Air Force Base is the contracting agency. The justification for this non-competitive procurement is that the required services are only available from a limited number of sources.
Site Sheet
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AFSPC Uninterruptible Power Supply (UPS) Site Information Sheet
| 4 Jun 2018 |
| Buckley AFB, Colorado |
| Bldg. 1030 |
1. POINTS OF CONTACT
| Primary: SSgt Franklin Cheney |
| Alternate: |
| 24-Hour Work Center |
Financial Analyst
460th Space Wing Command Post
Franklin.cheney@us.af.mil
460.commandpost@us.af.mil
| (720) 847-4011 |
| DSN 847-4011 |
| (720) 847-4600 |
| DSN 847-4600 |
AFSPC POC: Mr. Aller Delarosa; aller.delarosa.1@us.af.mil; (719) 554-2906; DSN 692-2906
Security Management Office (SMO) Code: BU1SFP2N6
Installation/Restricted Area/Facility Access Requirements: Contact POC
3. ORGANIZATION, MISSION, & LOCATION
Command and Organization: AFSPC; 14 AF; 460 SW
UNCLASS Mission Supported by UPS: 460 SW Command Post & Installation Control Center and Comm Rooms
| Street Address Where UPS is Located: 510 S. Aspen St. |
| UPS/Battery Rm #: 012 |
| Installation: Buckley AFB |
| State: CO |
| Zip: 80011 |
| DoDAAC: FA2543 |
4. UPS MODULE
| Configuration: Single Module, Reverse Transfer |
| Configuration/CTO #: PO8005161200115 |
| Manufacturer: Powerware |
| Series: 9315-80 |
| Model: 80 |
| Date Manufactured: Jun 2004 |
| Date Installed: Aug 2004 |
| Caps Upgrade: 28 Oct 16 |
| kVA: 80 |
| kW: 64 |
| Input/output Voltage: 480 / 480 |
| System Load: 18 kVA |
Module Serial #: (1) EW195ZBA05
5. INTEGRAL EQUIPMENT (i.e. Parallel Cabinet, Maintenance Bypass Cabinet, etc.)
| Manufacturer: UNK |
| Type: Maintenance Bypass |
| Serial #: N/A |
| Remote Monitor: No |
| Emergency Power Off: No |
| Spares Kit: No |
6. BATTERIES
Configuration: (2) parallel cabinets; (40) jars in series per cabinet, (80) total jars
| Manufacturer: Eaton |
| Series: Powerware |
| Model: PWHR12280W4FR |
| Watts/Cell: 283 |
| Date Code: 1113 |
| Date Installed: 4 Dec 2013 |
| Warranty: 3 years parts, 1 year labor |
| Type (Flooded/Sealed): Sealed |
| # Volts per Cell/Jar: 2 / 12 |
| DC Float: 540 VDC |
| # Strings / Unit: 2 |
| # Jars / String: 40 |
| # Cells / Jar: 6 |
| # Jars / Unit: 80 |
| Total Jars / System: 80 |
| Battery monitoring System: No |
| Spare Batteries: No |
7. PREVENTIVE MAINTENANCE DUE
Modules, integral equipment, and sealed batteries are semi-annual (every 6 mos.); flooded batteries are quarterly (every 3 mos.)
8. ADDITIONAL DATA
Laptop Computer Permitted in UPS Room: Yes (no special requirements)
Mobile Telephone Permitted in UPS Room: Yes (no special requirements)
| Telephone in UPS Rm: No |
| Telephone in Battery Rm: No |