This document provides details on an upcoming federal contract opportunity for uninterruptible power supply (UPS) maintenance services at Buckley Air Force Base in Colorado. The solicitation will require emergency and preventative maintenance of UPS modules and batteries, preventative maintenance of ancillary equipment, UPS system diagnostic and repair services, and overseas travel. Delivery orders will have a period of performance from April 2019 through April 2024. Responses are due by April 14, 2019. The solicitation will be conducted electronically under authority of the Federal Acquisition Regulation for supplies or services available from only one or a limited number of responsible sources to satisfy agency requirements. The contracting agency is the Department of the Air Force Materiel Command Lifecycle Management Center at Hill Air Force Base.
Site Sheet
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AFSPC Uninterruptible Power Supply (UPS) Site Information Sheet
| 4 Jun 2018 |
| Buckley AFB, Colorado |
| Bldg. 442 |
1. POINTS OF CONTACT
| Primary: Mr. Jacob Livingston |
| Alternate: Mr. Duane Bartley |
| Additional: Mr. Patrick Holder |
| Utilities Plant Supervisor |
| Electrical Engineer |
| Facilities Superintendent |
| anthony.flick.2@us.af.mil |
| duane.bartley.1@us.af.mil |
| Patrick.holder.1@us.af.mil |
| (720) 847-5794 |
| (720) 847-9893 |
| (720) 847-9982 |
| DSN 847-9982 |
| (720) 847-9916 |
| DSN 847-9916 |
24-Hour Work Center: Power Plant Control Room, (720) 847-5794/5, DSN 847-5794/5
AFSPC POC: Mr. Aller Delarosa; aller.delarosa.1@us.af.mil; (719) 554-2906; DSN 692-2906
Security Management Office (SMO) Code: SSO BUCKLEY; willard.viar.ctr@us.af.mil; (720) 847-7350;
DSN 847-7350
Installation/Restricted Area/Facility Access Requirements: Contact POC for instructions and necessary forms
2. ORGANIZATION, MISSION, & LOCATION
Command and Organization: AFSPC; 14 AF; 460 SW; 460 OG; 2 SWS
| UNCLASS Mission Supported by UPS: SBIRS (Utility Bus) |
| UPS Room #: 191 |
| Street Address Where UPS is Located: 18079 E. Buttermilk Ave. |
| Battery Rm #: 193 |
| Installation: Buckley AFB |
| State: CO |
| Zip: 80011 |
| DoDAAC: F03000 |
3. UPS MODULE
| Configuration: Parallel capacity frames; Two parallel redundant systems |
| Configuration/CTO #: 9PL13C0009C00R2 |
| Manufacturer: Eaton |
| Series: 93PM |
| Model: 110-150 |
| Date Manufactured: Nov 2016 |
| Date Installed: 26 Jan 17 |
| Caps Date Code: |
| kVA: 130 (ea.) |
| kW: 130 (ea.) |
| Input/output Voltage: 480 / 480 |
| System Load: ____ kVA |
Module Serial #: 1. EK481UXX03 (3A) 2. EK481UXX02 (3B) 3. EK481UXX01 (4A) 4. EK474UXX01 (4B)
4. INTEGRAL EQUIPMENT (i.e. Parallel Cabinet, Maintenance Bypass Cabinet, etc.)
| Manufacturer: |
| Type: |
| Serial #: |
| Type: |
| Serial # |
| Eaton |
| Parallel Cabinet (3AB) |
| No Serial Number |
| Maintenance Bypass 3 |
| No Serial Number |
| Eaton |
| Parallel Cabinet (4AB) |
| No Serial Number |
| Maintenance Bypass 4 |
| No Serial Number |
| Square D |
| Manual Hot Tie (3,4) |
| No Serial Number |
| Remote Monitor: Yes, Ctrl. Rm; Sense a Phone |
| Emergency Power Off: No |
| Spares Kit: Yes |
5. BATTERIES
Configuration: (2) strings per S/N, (8) strings total; (40) jars in series per string; (320) total jars
| Manufacturer: Enersys |
| Series: DataSafe |
| Model: 12HX300FR |
| Watts/Cell: 284 |
| Date Code: 1116 |
| Date Installed: 26 Jan 17 |
| Warranty: 3 years |
| Type (Flooded/Sealed): Sealed |
| # Volts per Cell/Jar: 2 / 12 |
| DC Float: 540 VDC |
| # Strings / Unit: 2 |
| # Jars / String: 40 |
| # Cells / Jar: 6 |
| # Jars / Unit: 80 |
| Total Jars / System: 320 |
6. PREVENTIVE MAINTENANCE DUE
Modules, integral equipment, and sealed batteries are semi-annual (every 6 mos.); flooded batteries are quarterly (every 3 mos.)
7. ADDITIONAL DATA
Laptop Computer Permitted in UPS Room: Yes (Submit attached Laptop Authorization Letter, Wi-Fi deactivated)
Mobile Telephones Permitted in UPS Room: No (Not permitted in Restricted Area)