AFSPC-Buckley-00730.docx

DOCX document 22 KB Posted

Attached to
PCCIE Emergency Maintenance and Preventative Maintenance (EMPM)
Solicitation number
FA8217-18-R-5007
Issued by

About this file

This document contains a site information sheet for an uninterruptible power supply (UPS) located at Building 730 of Buckley Air Force Base in Colorado, as well as a related federal contract opportunity notice for emergency and preventative maintenance of the UPS and associated systems.

The site information sheet provides details on the UPS configuration including manufacturer, model, installation date, and battery specifications. It identifies contact information for maintenance and facility access. The related federal contract opportunity is a pre-solicitation notice seeking emergency and preventative maintenance services for the UPS, batteries, ancillary equipment, and diagnostic and repair actions. The opportunity includes line items for maintenance of these systems with a period of performance from April 2019 through April 2024. The justification cited is that the required supplies or services are only available from a limited number of responsible sources.

Site Sheet

View the file

Other files

File Type Posted
FA821718R5007_______0003.pdf PDF
Germany.pdf PDF
Japan.pdf PDF
Clarification_on_the_Pricing_Sheet_for_the_Third_Party_Tab_for_Full_Service.docx DOCX document
PricingEMPM-SAMPLE.xlsx XLSX spreadsheet
PricingEMPM-FY19-16Aug18-Protected.xlsx XLSX spreadsheet
PricingEMPM-FY22-16Aug18-Protected.xlsx XLSX spreadsheet
FA821718R5007_______0002.pdf PDF
PricingEMPM-FY20-16Aug18-Protected.xlsx XLSX spreadsheet
PricingEMPM-FY23-16Aug18-Protected.xlsx XLSX spreadsheet
PricingEMPM-FY21-16Aug18-Protected.xlsx XLSX spreadsheet
PricingEMPM-FY24-16Aug18-Protected.xlsx XLSX spreadsheet
SOFA_Contract_Clause.pdf PDF
Cross_Reference_Matrix.xlsx XLSX spreadsheet
PWS_PCCIE_16_Aug_2018_Amend_1.docx DOCX document
RevisedCDRLS_09_10_2018.pdf PDF
FA821718R5007_______0001.pdf PDF
PCCIE_Questions_and_Answers_6_Sep_2018.docx DOCX document
AFSPC-Buckey-01028-ECC.docx DOCX document
PricingEMPM-FY19-16Aug18-Protected.xlsx XLSX spreadsheet
AFSPC-Buckley-00442-SBIRS-Tech.docx DOCX document
CDRLs_A0001_A00026.pdf PDF
FA821718R5007.pdf PDF
AFSPC-Buckley-00442-SBIRS-Utility.docx DOCX document
PricingEMPM-FY20-16Aug18-Protected.xlsx XLSX spreadsheet
AFSPC-Buckley-00433.docx DOCX document
PricingEMPM-FY21-16Aug18-Protected.xlsx XLSX spreadsheet
CDRL-Matrix.xlsx XLSX spreadsheet
PWS_PCCIE_16_Aug_2018.pdf PDF
PricingEMPM-FY24-16Aug18-Protected.xlsx XLSX spreadsheet
AFSPC-Buckley-01030.docx DOCX document
PCCIE-Instruction-and-Evaluation-13-Aug-18.pdf PDF
PricingEMPM-FY23-16Aug18-Protected.xlsx XLSX spreadsheet
AppendixC-PCCIE.pdf PDF
PricingEMPM-FY25-16Aug18-Protected.xlsx XLSX spreadsheet
PricingEMPM-FY22-16Aug18-Protected.xlsx XLSX spreadsheet
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AFSPC Uninterruptible Power Supply (UPS) Site Information Sheet

4 Jun 2018
Buckley AFB, Colorado
Bldg. 730

1. POINTS OF CONTACT

Primary: Adam Sablan
Alternate: SSgt Dillard Colton
Alternate:
Adam.sablan@us.af.mil
Colton.dillard@us.af.mil
(720) 847-5015
DSN 847-5015
(720) 847-0999
DSN 847-0999
Additional: Communication Focal Point (CFP) Standby Person
AFSPC POC: Mr. Aller Delarosa
CFP Non-duty Hours: 1631-0729
Command UPS Program Manager
(720) 847-2666, Option 3
(719) 554-2906 DSN 692-2906

Security Management Office POC: TSgt Emmett Ladd; emmett.ladd@us.af.mil; (720) 847-5850; DSN 847-5850

Installation/Restricted Area/Facility Access Requirements: Contact POC

2. ORGANIZATION, MISSION, & LOCATION

Command and Organization: AFSPC; 14 AF; 460 SW; 460 OG; 460 SCS

UNCLASS Mission Supported by UPS: Network Control Center, AFSPC SharePoint, MHSI, JWICS PoP

Street Address Where UPS is Located: 84 N. Aspen St.
UPS/Battery Rm #: L008
Installation: Buckley AFB
State: CO
Zip: 80011
DoDAAC: 503000

3. UPS MODULE

Configuration: Parallel Redundant
Configuration/CTO #: TC1022201130010
Manufacturer: Powerware
Series: 9390-120
Model: 120
Date Manufactured: Nov 2007
Date Installed: 17 Dec 2007
Caps Upgrade: 9 Nov 16
kVA: 120
kW: 96
Input/output Voltage: 480 / 480
System Load: 58 kVA

Module Serial #: (1) EA463CAA12 (2) EA465CAA07

4. INTEGRAL EQUIPMENT (i.e. Parallel Cabinet, Maintenance Bypass Cabinet, etc.)

Manufacturer:
Type:
Serial #:
Powerware
Integrated Distribution Cabinet (MIS, MBP)
EA442EAA04
Powerware
Parallel Tie Cabinet
No Serial #
Remote Monitor: No
Emergency Power Off: Yes, Rm. L008
Spares Kit: No

5. BATTERIES

Configuration: (2) parallel cabinets per module, (4) total cabinets; (40) jars in series per cabinet, (160) total jars

Manufacturer: Eaton
Series: Powerware
Model: PWHR12280W4FR
Watts/Cell: 283
Date Code: 0314
Date Installed: Jun 14
Warranty: 3 years
Type (Flooded/Sealed): Sealed
# Volts per Cell/Jar: 2 / 12
DC Float: 540 VDC
# Strings / Unit: 2
# Jars / String: 40
# Cells / Jar: 6
# Jars / Unit: 80
Total Jars / System: 160
Battery Monitoring System: No
Spare Batteries: No

6. PREVENTIVE MAINTENANCE

Modules, integral equipment, and sealed batteries are semi-annual (every 6 mos.); flooded batteries are quarterly (every 3 mos.)

7. ADDITIONAL DATA

Telephone in UPS/Battery Room: No

Mobile Telephone Permitted in UPS Room: No

Laptop Computer Permitted in UPS Room: Yes (Submit laptop authorization letter, contact POC)