The file's text, extracted by GovTribe without its formatting.
AFSPC Uninterruptible Power Supply (UPS) Site Information Sheet
| 4 Jun 2018 |
| Buckley AFB, Colorado |
| Bldg. 1028 |
1. POINTS OF CONTACT
| Primary: Ryan Davis, DAFC |
| Alternate: James Flammia, DAFC |
| Alternate: Mr. Troy Forbes |
| Ryan.davis.63@us.af.mil |
| James.flammia@us.af.mil |
| Troy.Forbes.2@us.af.mil |
| (773) 710-6708 |
| DSN 847-7927 |
| (303) 598-4411 |
| DSN 847-7322 |
| (720) 847-9929 |
| DSN 847-9929 |
| Additional: Communication Focal Point (CFP) Standby Person |
| AFSPC POC: Mr. Aller Delarosa |
| CFP Non-duty Hours: 1631-0729 |
| Command UPS Program Manager |
| (720) 847-2666, Option 3 |
| (719) 554-2906 DSN 692-2906 |
Security Management Office; 460SCS_SCXS@us.af.mil; david.benn.1@us.af.mil; (720) 847-9948; DSN 847-9948
Installation/Restricted Area/Facility Access Requirements: Contact BDOC
2. ORGANIZATION, MISSION, & LOCATION
Command and Organization: AFSPC; 14 AF; 460 SW; 460 MSG; 460 SFS
UNCLASS Mission Supported by UPS: Base BDOC & Emergency Communications Center
| Street Address Where UPS is Located: 19081 Camp Hale Way |
| UPS/Battery Rm #: 117 |
| Installation: Buckley AFB |
| State: CO |
| Zip: 80011 |
| DoDAAC: 503000 |
3. UPS MODULE
| Configuration: Reverse Transfer |
| Configuration/CTO #: Unknown |
| Manufacturer: Liebert |
| Series: |
| Model: 38SA060A0A00 |
| Date Manufactured: 20 Sep 2012 |
| Date Installed:1 Feb 2013 |
| Caps Date Code: 0112 |
| kVA: 60 |
| kW: 54 |
| Input/output Voltage: 480 / 480 |
| System Load: 14 kVA |
Module Serial #: 2101200662127020000
4. INTEGRAL EQUIPMENT (i.e. Parallel Cabinet, Maintenance Bypass Cabinet, etc.)
| Manufacturer: PowerLogic ION6200 |
| Type: Power and Energy Meter |
| Serial #: HA-120800538-03 |
| Remote Monitor Panel: No |
| Emergency Power Off: No |
| Spares Kit: No |
5. BATTERIES
Configuration: One string of 40 jars
| Manufacturer: Enersys |
| Series: DataSafe |
| Model: 12HX205-FR |
| Watts/Cell: 204 |
| Date Code: 0912 |
| Date Installed: Feb 13 |
| Warranty: 3 years |
| Type (Flooded/Sealed): Sealed |
| # Volts per Cell/Jar: 2 / 12 |
| DC Float: 540VDC |
| # Strings / Unit: 1 |
| # Jars / String: 40 |
| # Cells / Jar:6 |
| # Jars / Unit: 40 |
| Total Jars / System: 40 |
| Battery Monitoring System: No |
| Spare Batteries: No |
6. PREVENTIVE MAINTENANCE
Modules, integral equipment, and sealed batteries are semi-annual (every 6 mos.); flooded batteries are quarterly (every 3 mos.)
7. ADDITIONAL DATA
| Laptop Computer Permitted in UPS Room: Yes |
| Mobile Telephone Permitted in UPS Room: Yes |