FORMATION THERMAL CONDUCTIVITY TEST
AND DATA ANALYSIS
Sound Geothermal Corporation 3962 East Alpine Valley Circle Sandy, UT 84092 Phone: 801-942-6100
Analysis for:
Fax: 801-942-6127
Building 518 Test location:
Hill AFB, UT
Report Date: May 13, 2010
Sound Geothermal Corporation Test Performed by:
MAIN OFFICE: REGIONAL OFFICES: WEB SITE:
P.O. Box 150 ELKTON, SD ASHEVILLE, NC www.GRTI.com
BOWIE, TX 76230 (605) 692-9069 (828) 225-9166
(940) 872-2222 Fax: (605) 692-2604 Fax: (828) 281-4139 Fax: (940) 872-3678
GRTI
May 13, 2010 FTC Test and Data Analysis
Executive Summary
A formation thermal conductivity test was performed at Building 518 in Hill AFB at a GPS location of N 41° 6' 29.71" (latitude), W 111° 58' 46.64" (longitude). The vertical bore was completed on
April 29, 2010 by Bertram Drilling, Inc. GRTI’s test unit was attached to the vertical bore on the afternoon of May 5, 2010. Geothermal Resource Technologies, Inc. analyzed the collected data using the “line source” method.
This report provides a general overview of the test and procedures that were used to perform the thermal conductivity test along with a plot of the data in real time and in a form used to calculate the formation thermal conductivity. The following average formation thermal conductivity was found from the data analysis.
⇒ Formation Thermal Conductivity = 1.22 Btu/hr-ft-°F
Due to the necessity of a thermal diffusivity value in the design calculation process, an estimate of the average thermal diffusivity was made for the encountered formation.
⇒ Formation Thermal Diffusivity ≈ 0.80 ft2/day
An estimate of the undisturbed formation temperature was determined from the initial temperature data at startup.
⇒ Undisturbed Formation Temperature ≈ 54.9-58.5°F
A copy of the original collected data is available either in a hard copy or an electronic format upon request.
Test Procedures
The American Society of Heating, Refrigeration, and Air-Conditioning Engineers (ASHRAE) has published a set of recommended procedures for performing formation thermal conductivity tests for geothermal applications. GRTI is committed to adhering to ASHRAE recommendations.
Some of these recommended procedures are listed below:
(1) Required Test Duration – A minimum test duration of 36 hours is recommended, with a preference toward 48 hours.
(2) Power Quality – The standard deviation of the power should be less than or equal to 1.5% of the average power, with maximum power variation of less than or equal to 10% of the average power. The heat flux rate should be 51 Btu/hr (15 W) to 85 Btu/hr (25 W) per foot of borehole depth to best simulate the expected peak loads on the u-bend.
(3) Undisturbed Formation Temperature Measurement – The undisturbed formation temperature should be determined by recording the minimum loop temperature as the water returns from the u-bend at test startup.
(4) Installation Procedures for Test Loops – The bore diameter is to be no larger than 6 inches, with 4.5 inches being the target diameter. To ensure against bridging and voids, the bore annulus is to be uniformly grouted from the bottom to the top using a tremie pipe.
(5) Time Between Loop Installation and Testing – A minimum delay of five days between loop installation and test startup is recommended if the formation is expected to have a low thermal conductivity or if low conductivity grouts (< 0.75 Btu/hr·ft·ºF) are used. A minimum delay of three days is recommended for all other conditions.
GRTI’s testing procedures deviate slightly from those above with regard to item (5). While item
(5) bases the delay between installation and testing on the expected formation conductivity, GRTI bases its delay on the type of drilling used in the installation. When air drilling is required, a five-day delay is recommended to allow the bore to return to its undisturbed temperature. For mud rotary drilling, a minimum waiting period of two days is sufficient.
For a complete list of recommended procedures, refer to the ASHRAE 2007 HVAC Applications handbook, pages 32.12-32.13.
Data Analysis
Geothermal Resource Technologies, Inc. uses the "line source" method of data analysis. The line source equation used is not valid for early test times. Also, the line source method assumes an infinitely thin line source of heat in a continuous medium. If a u-bend grouted in a borehole is used to inject heat into the ground at a constant rate in order to determine the average formation thermal conductivity, the test must be run long enough to allow the finite dimensions of the u-bend pipes and the grout to become insignificant. Experience has shown that the amount of time required to allow early test time error and finite borehole dimension effects to become insignificant is approximately ten hours.
In order to analyze real data from a formation thermal conductivity test, the average temperature of the water entering and exiting the u-bend heat exchanger is plotted versus the natural log of time. Using the Method of Least Squares, the linear equation coefficients are then calculated that produce a line that fits the data. This procedure is normally repeated for various time intervals to ensure that variations in the power or other effects are not producing erroneous results.
Through the analysis process, the collected raw data is converted to spreadsheet format
(Microsoft Excel®) for final analysis. A copy of this data can be obtained either in a hard copy or electronic copy format at any time. If desired, please contact Geothermal Resource
Technologies, Inc. and provide a ship-to address or e-mail address at one of the following:
Contact: Galen Streich
Phone: (605) 692-9069
Fax: (605) 692-2604
E-mail: gstreich@grti.com
Formation Thermal Conductivity Test Report
Date ...……………………………………………………………. May 5-7, 2010 Location ..………………………………………………………… Hill AFB, UT Undisturbed Formation Temperature ...……….……………... Approx. 54.9-58.5°F
Borehole Data – As Provided by Sound Geothermal Corporation
Borehole Diameter ...…………………………………………… 5 1/8 inches
Drill Log .................... Topsoil 0'-3' Brown silty/sandy clay 3'-10' Silty sand with trace gravels 10'-30' Silty brown clay 30'-35' Brown clay 35'-40' Brown sandy clay 40'-60' Brown clay 60'-110' Brown clay, trace coarse sand 110'-120' Sandy brown clay with fine gravels 120'-130' Fine gravels with sandy brown clay 130'-140' Sandy brown clay, trace fine gravel 140'-220' Sandy brown clay, trace gravel, trace sand 220'-230' Sandy brown clay, trace fine gravel 230'-240' Sandy brown clay, large gravel 240'-250' Sandy brown clay, large gravel, trace fine gravel 250'-260' Sandy brown clay, trace sand 260'-280' Sandy brown clay, trace sand, trace gravel 280'-315' Sandy brown clay, trace sand, trace large gravel 315'-330' Sandy brown clay, trace sand, trace fine gravel 330'-360' Gray brown clay, trace sand 360'-400'
U-bend Size …………………………………………………….. 1 1/4 inch HDPE U-Bend Length ..……………………………………………….. 400 ft Grout Type ...……………………………………………….…… GeoPro Thermal Grout Select Grout Solids …………………………………………………..… 6:1 sand to bentonite ratio Grouted Portion ………..……………………………………..… Entire bore
Test Data for Analysis Time Period
Test Duration ...……………….………………………………… 42.5 hrs.
Average Voltage …………………………………………..…… 242.1 V Average Power …………………………………………….…… 8,325 W Total Heat Input Rate ……………………………………..…… 28,414 Btu/hr Calculated Circulator Flow Rate …...…………………….…… 6.2 gpm Standard Deviation of Power …………………………………. 0.08% Maximum Variation in Power …………………………………. 0.25%
0 5 10 15 20 25 30 35 40 45
Time (hours)
Te m pe ra tu re
(F
(T ho us an ds
H ea tin g
R at e (B tu /h r)
Building 518, Hill AFB May 5-7, 2010
Loop In Temp
10-42.5 hr Average
Loop Out Temp
Heat Rate
Figure 1: Temperature versus Time Data
Line Source Data Analysis
-1 0 1 2 3 4 ln(Time)
Te m pe ra tu re
(F
(T ho us an ds
H ea tin g
R at e (B tu /h r)
Building 518, Hill AFB May 5-7, 2010
Loop In Temp
10-42.5 hr Average
Loop Out Temp
Heat Rate
Figure 2: Temperature versus Natural Log of Time
Thermal Time Period Slope Average Heat Input Conductivity
(Btu/hr-ft) (W/ft) (Btu/hr-ft-°F)
10 – 42.5 hrs 4.63 71.0 20.8 1.22
The temperature versus time data was analyzed using the line source analysis for the time period shown above. An average linear curve fit was applied to the data between 10 and 42.5 hours.
The slope of the curve was found to be 4.63. The resulting thermal conductivity was found to be
1.22 Btu/hr-ft-°F.
Estimated Thermal Diffusivity
The reported drilling log for this test borehole indicated that the formation consisted of clay, sand and gravel. A weighted average of heat capacity values based on the indicated formation was used to develop an average heat capacity for the formation. A diffusivity value was then found using the calculated formation thermal conductivity and the estimated heat capacity. The thermal diffusivity for this formation was estimated to be 0.80 ft2/day.
Est. Average Heat Capacity
(Btu/ft3-°F)
Thermal Conductivity (Btu/hr-ft-°F)
Est. Thermal Diffusivity (ft2/day)
36.8 1.22 0.80
Frequently Asked Questions (FAQ’s) Regarding FTC Testing
Q: Thermally-enhanced grout is specified for the final loop field design. The test bore was grouted with a low conductivity, 20% solids, bentonite grout. How do I adjust the thermal conductivity value to account for this?
A: While the conductivity of the grout is important for the loop field design, it is not important for determining formation thermal conductivity. We use the “line source” method to analyze data, which assumes an infinitely thin line rejecting heat at a constant rate into an infinite medium. The initial ten hours, which is influenced by the bore dimensions and grout conductivity, is ignored in the analysis. However, once the heat has penetrated into the formation, the temperature rise of the formation approaches steady-state. It is the slope of the temperature rise that is used in the analysis. Hence, no adjustment to the reported formation thermal conductivity is required.
Q: The software I use to design the loop field requires that I input a value for “soil conductivity”. Is this the same as formation thermal conductivity?
A: Absolutely. Formation, soil, and ground are all used interchangeably to describe the conditions in which the u-bends will be installed. The use of the word “formation” simply implies that the installation conditions may be soil, rock, or some combination of the two.
Q: I’ve just received your report. I have a formation conductivity of 1.54 Btu/hr⋅ft⋅°F. How do
I translate that into a loop length requirement, in terms of bore depth (in feet) per ton?
A: The formation thermal conductivity test provides values for three key parameters required for the ground loop design. These are the “Undisturbed Formation Temperature, Formation Thermal Conductivity, and Formation Thermal Diffusivity.“ These parameters, along with many others, are inputs to commercially available loop design software (e.g.
GchpCalc, available at GeoKiss.com/software). The software uses all of the inputs to determine the required loop length in bore depth per ton.
Q: Is the “Undisturbed Formation Temperature” listed in the report the temperature that I enter into my loop design software where it calls for the “Deep-Earth Temperature”?
A: Generally, yes. The “Undisturbed Formation Temperature” is the constant temperature of the formation. We attempt to determine this value by measuring the temperature of the water entering the test unit at the beginning of the test. However, the value we measure and report may be inaccurate if the test is initiated too quickly after the installation of the test bore, or if the testing operator failed to activate the data acquisition unit prior to energizing the heating elements. If you suspect the temperature we are reporting to be too high or too low, we recommend that you investigate further through other sources.