28 31 33.00 10.pdf

PDF 55 KB Posted

Attached to
TINKER AFB MAC BOA WWYK190023 Renovate Restrooms B117
Solicitation number
FA813726R0030
Issued by

About this file

This is a technical specification document for a Fire Alarm Reporting System, Radio Type (Section 28 31 33.00 10) for Tinker Air Force Base, Oklahoma, dated April 2019.

The specification establishes comprehensive requirements for a completely supervised radio-type fire alarm reporting system compliant with NFPA 72. Key products and services required include: radio fire alarm transmitters/transceivers operating on 142.850 MHz with minimum 1-watt RF power output, memory capability for multiple simultaneous alarms, and distinct identity codes with message designations (fire, trouble, battery, test, tamper, and master zone); radio fire alarm monitoring base station console with receiver/transceiver, signal decoder, audible and visual alarms, memory buffer for 500+ transmitter codes, and supervision capabilities; interface devices for signal conversion; repeaters where required; antenna systems with vertical polarization capable of withstanding 125 mph winds and 1/2 inch radial ice; and peripheral equipment including location lights, conduit, ground rods, power supply with 48-hour battery backup, and surge protection. The transmitter must include nickel-cadmium batteries with 60-hour standby capacity and 6-month battery-only operation capability, with automatic switchover to battery upon AC power loss and transmission of trouble message within 20 seconds.

The contractor must provide a Registered Professional Engineer with 4+ years of fire protection systems design experience, submit detailed shop drawings, product data, test procedures, operating and maintenance instructions, and conduct field training for operating staff consisting of 8 hours. System installation must comply with NFPA 70, NFPA 72, IEEE standards for surge protection, and include grounding with maximum 25-ohm resistance. Performance and acceptance testing per NFPA 72 must be completed and documented, with test procedures submitted 30 days prior to testing and conducted under contractor supervision in presence of the Contracting Officer.

View the file

Other files

File Type Posted
000_TABLE OF CONTENTS Technical.pdf PDF
05 05 23.16.pdf PDF
05 12 00.pdf PDF
05 30 00.pdf PDF
05 40 00.pdf PDF
05 50 13.pdf PDF
06 41 16.00 10.pdf PDF
07 24 00.pdf PDF
07 41 13.pdf PDF
07 51 13.pdf PDF
08 11 13.pdf PDF
08 14 00.pdf PDF
08 33 23.pdf PDF
08 56 53.pdf PDF
08 81 00.pdf PDF
09 22 00.pdf PDF
09 30 10.pdf PDF
09 72 00.pdf PDF
09 90 00.pdf PDF
10 14 00.10.pdf PDF
10 22 39.pdf PDF
10 26 00.pdf PDF
10 44 16.pdf PDF
23 05 15.pdf PDF
23 08 01.00 20.pdf PDF
23 23 00.pdf PDF
23 25 00.pdf PDF
23 31 13.00 40.pdf PDF
23 64 10.pdf PDF
23 81 23.pdf PDF
23 82 01.pdf PDF
26 05 00.00 40.pdf PDF
26 08 00.pdf PDF
26 20 00.pdf PDF
26 23 00.pdf PDF
26 28 01.00 10.pdf PDF
26 36 00.00 10.pdf PDF
26 41 00.pdf PDF
28 31 00.00 10.pdf PDF
28 31 64.00 10.pdf PDF
32 01 16.pdf PDF
32 01 17.62.pdf PDF
32 01 19.pdf PDF
00 70 00.pdf PDF
00 80 05.pdf PDF
01 33 00.pdf PDF
01 45 00.00 10.pdf PDF
01 50 00.pdf PDF
WWYK20190023_REV02_19MAY2026.pdf PDF
Section M - Evaluation Factors for Award.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Ti nker AFB, OK TAFB Techni cal Spr ci f i cat i ons 2019

SECTI ON 28 31 33. 00 10

FI RE ALARM REPORTI NG SYSTEM, RADI O TYPE

04/17

PART 1 GENERAL

1. 1 REFERENCES

The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.

I NSTI TUTE OF ELECTRI CAL AND ELECTRONI CS ENGI NEERS ( I EEE)

I EEE C135. 30 ( 1988) St andar d f or Zi nc- Coat ed Fer r ous Gr ound Rods f or Over head or Under gr ound Li ne Const r uct i on

I EEE C62. 41. 1 ( 2002; R 2008) Gui de on t he Sur ges Envi r onment i n Low- Vol t age ( 1000 V and Less) AC Power Ci r cui t s

I EEE C62. 41. 2 ( 2002) Recommended Pr act i ce on Char act er i zat i on of Sur ges i n Low- Vol t age ( 1000 V and Less) AC Power Ci r cui t s

NATI ONAL ELECTRI CAL MANUFACTURERS ASSOCI ATI ON ( NEMA)

NEMA I CS 1 ( 2000; R 2015) St andar d f or I ndust r i al Cont r ol and Syst ems: Gener al Requi r ement s

NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)

NFPA 70 ( 2014; AMD 1 2013; Er r at a 1 2013; AMD 2 2013; Er r at a 2 2013; AMD 3 2014; Er r at a 3- 4 2014; AMD 4- 6 2014) Nat i onal El ect r i cal Code

NFPA 72 ( 2013) Nat i onal Fi r e Al ar m and Si gnal i ng Code

NFPA 780 ( 2014) St andar d f or t he I nst al l at i on of Li ght ni ng Pr ot ect i on Syst ems

TELECOMMUNI CATI ONS I NDUSTRY ASSOCI ATI ON ( TI A)

TIA-222 ( 2009g; Add 1 2007; Add 2 2009; R 2012; R 2013; R 2014) St r uct ur al St andar ds f or Ant enna Suppor t i ng St r uct ur es and Ant ennas

U. S. NATI ONAL ARCHI VES AND RECORDS ADMI NI STRATI ON ( NARA)

47 CFR 15 Radi o Fr equency Devi ces

Apr i l 2019 Page 1 SECTI ON 28 31 33. 00 10

UNDERWRI TERS LABORATORI ES ( UL)

UL 1242 ( 2006; Repr i nt Mar 2014) St andar d f or El ect r i cal I nt er medi at e Met al Condui t - - Steel

UL 467 ( 2013) Gr oundi ng and Bondi ng Equi pment

UL 6 ( 2007; Repr i nt Nov 2014) El ect r i cal Ri gi d Met al Condui t - St eel

UL 797 ( 2007; Repr i nt Dec 2012) El ect r i cal Met al l i c Tubi ng - - St eel

1. 2 SUBMITTALS

Gover nment appr oval i s r equi r ed f or al l submi t t al s. The f ol l owi ng shal l be submi t t ed i n accor dance wi t h Sect i on 01 33 00, SUBMI TTAL PROCEDURES:

SD- 02 Shop Dr awi ngs

Fi r e Al ar m Repor t i ng Syst em

Wi r i ng f or Syst ems

SD- 03 Pr oduct Dat a

Spar e Par t s

Qualifications

Training

Test Pr ocedur es

SD- 06 Test Repor t s

Testing

SD- 07 Cer t i f i cat es

Equipment

SD- 10 Oper at i on and Mai nt enance Dat a

Fi r e Al ar m Repor t i ng Syst em;

1. 3 QUALI TY ASSURANCE

Pr ovi de t he ser vi ces of a Regi st er ed Pr of essi onal Engi neer wi t h at l east 4 year s of cur r ent exper i ence i n t he desi gn of f i r e pr ot ect i on and det ect i on syst ems. Submi t t he qual i f i cat i ons, wi t h ver i f i cat i on of exper i ence and l i cense number , f or t hi s engi neer .

1. 4 DELI VERY, STORAGE, AND HANDLI NG

Pr ot ect al l equi pment del i ver ed and pl aced i n st or age f r om t he weat her , humi di t y and t emper at ur e var i at i ons, di r t , dust , and ot her cont ami nant s.

Apr i l 2019 Page 2 SECTI ON 28 31 33. 00 10

1. 5 SPECI AL TOOLS AND SPARE PARTS

Fur ni sh speci al t ool s necessar y f or t he mai nt enance of t he equi pment .

Pr ovi de one spar e set of f uses of each t ype and si ze r equi r ed and 5 spar e l amps of each t ype.

PART 2 PRODUCTS

2. 1 SYSTEM DESCRI PTI ON

Pr ovi de a cent r al r epor t i ng syst em compl yi ng wi t h NFPA 72. The equi pment f ur ni shed shal l be l i s t ed by Under wr i t er s Labor at or i es, or Fact or y Mut ual Engi neer i ng and Resear ch, or be appr oved or l i s t ed by a nat i onal l y r ecogni zed t est i ng l abor at or y.

a. Fur ni sh t ags wi t h st amped i dent i f i cat i on number s f or keys and l ocks.

Locks shal l be keyed al i ke. The r adi o syst em shal l r epor t al ar ms t o t he r adi o f i r e al ar m moni t or i ng base st at i on. The syst em shal l be a compl et el y super vi sed r adi o t ype f i r e al ar m r epor t i ng syst em.

b. Submi t det ai l dr awi ngs, s i gned by t he Regi st er ed Pr of essi onal Engi neer , consi st i ng of a compl et e l i s t of equi pment and mat er i al , i ncl udi ng manuf act ur er ' s descr i pt i ve and t echni cal l i t er at ur e, cat al og cut s, and i nst al l at i on i nst r uct i ons. Not e t hat t he cont r act dr awi ngs show l ayout s based on t ypi cal det ect or s. Check t he l ayout based on t he act ual det ect or s t o be i nst al l ed and make any necessar y r evi s i ons i n t he det ai l dr awi ngs.

c. Det ai l dr awi ngs shal l al so cont ai n compl et e wi r i ng and schemat i c di agr ams f or t he equi pment f ur ni shed, equi pment l ayout , and any ot her det ai l s r equi r ed t o demonst r at e t hat t he syst em has been coor di nat ed and wi l l pr oper l y f unct i on as a uni t . The syst em shal l i ndi cat e t he ar ea of al ar m. The r adi o communi cat i on l i nk shal l be super vi sed and oper at ed i n accor dance wi t h NFPA 72. El ect r i cal super vi s i on shal l be pr ovi ded f or al l c i r cui t s and f or al l posi t i ons of i nt er f ace panel cont r ol swi t ches.

d. Submi t 4 compl et e copi es of oper at i ng i nst r uct i ons out l i ni ng st ep- by- st ep pr ocedur es r equi r ed f or syst em st ar t up, oper at i on, and shut down. The i nst r uct i ons shal l i ncl ude t he manuf act ur er ' s name, model number , ser vi ce manual , par t s l i s t , and br i ef descr i pt i on of al l equi pment and t hei r basi c oper at i ng f eat ur es.

e. Submi t 4 copi es of mai nt enance i nst r uct i ons l i s t i ng r out i ne mai nt enance pr ocedur es, possi bl e br eakdowns and r epai r s, and t r oubl eshoot i ng gui de. The i nst r uct i ons shal l i ncl ude condui t l ayout , equi pment l ayout and si mpl i f i ed wi r i ng, and cont r ol di agr ams of t he syst em as i nst al l ed. I nst r uct i ons shal l be appr oved pr i or t o t r ai ni ng.

2. 2 STANDARD PRODUCTS

Pr ovi de mat er i al and equi pment whi ch ar e t he st andar d pr oduct s of a manuf act ur er r egul ar l y engaged i n t he manuf act ur e of t he pr oduct s and t hat essent i al l y dupl i cat e i t ems t hat have been i n sat i sf act or y use f or at l east 2 year s pr i or t o bi d openi ng. Equi pment shal l be suppor t ed by a ser vi ce or gani zat i on t hat can pr ovi de ser vi ce wi t hi n 24 hour s.

Apr i l 2019 Page 3 SECTI ON 28 31 33. 00 10

2. 3 NAMEPLATES

Maj or component s of equi pment shal l have t he manuf act ur er ' s name, addr ess, t ype or st y l e, vol t age and cur r ent r at i ng, and cat al og number on a noncor r osi ve and nonheat - sensi t i ve pl at e whi ch i s secur el y at t ached t o t he equipment.

2. 4 RADI O FI RE ALARM TRANSMI TTER ( TRANSCEI VER)

Radi o Fi r e Al ar m Tr ansmi t t er and Tr anscei ver shal l be compat i bl e wi t h t he Radi o Fi r e Al ar m Moni t or i ng Base St at i on. The t r ansmi t t er shal l be al l sol i d st at e and compl y wi t h appl i cabl e por t i ons of 47 CFR 15 gover ni ng t ype accept ance. Al l t r ansmi t t er s of a common conf i gur at i on shal l be i nt er changeabl e wi t h t he ot her devi ces f ur ni shed by t he manuf act ur er .

Each t r ansmi t t er and i nt er f ace devi ce shal l be t he manuf act ur er ' s cur r ent commer ci al pr oduct compl et el y assembl ed, wi r ed, t est ed at t he f act or y, and del i ver ed r eady f or i nst al l at i on and oper at i on.

2. 4. 1 Fr equency Al l ocat i on

The t r ansmi t t er s shal l oper at e on a f r equency of 142. 850 MHz.

2. 4. 2 Power Requi r ement s

Powe t r ansmi t t er s by a combi nat i on of l ocal l y avai l abl e 120 Vac, and seal ed ni ckel - cadmi um t ype bat t er i es r equi r i ng no addi t i onal wat er .

Tr ansmi t t er s used i n manual st r eet box conf i gur at i on as i ndi cat ed shal l be power ed by bat t er y onl y. I n t he event of l oss of 120 Vac power , t he t r ansmi t t er shal l aut omat i cal l y swi t ch t o bat t er y oper at i on. The swi t chover shal l be accompl i shed wi t h no i nt er r upt i on of pr ot ect i ve ser vi ce, wi t hout adver sel y af f ect i ng t he bat t er y- power ed capabi l i t i es, and shal l cause t he t r ansmi ssi on of a t r oubl e message i n no l ess t han 20 seconds. Upon r est or at i on of ac power , t r ansf er back t o nor mal ac power suppl y shal l be aut omat i c and t he bat t er y shal l be r echar ged. The conver t er / bat t er y char ger shal l be i nst al l ed wi t hi n t he t r ansmi t t er housi ng. Power suppl y t r ansi ent f i l t er i ng shal l be pr ovi ded.

2. 4. 2. 1 Bat t er y Power

The package shal l be capabl e of suppl y i ng al l t he power r equi r ement s f or a gi ven t r ansmi t t er . Submi t subst ant i at i ng bat t er y cal cul at i ons f or super vi sor y and al ar m power r equi r ement s. Amper e- hour r equi r ement s f or each syst em component , each panel component and t he bat t er y r echar gi ng per i od shal l be i ncl uded.

2. 4. 2. 2 Bat t er y Dur at i on

Radi o f i r e al ar m t r ansmi t t er st andby bat t er y capaci t y shal l pr ovi de suf f i c i ent power t o oper at e t he t r ansmi t t er i n a nor mal st andby st at us f or a mi ni mum of 60 hour s and shal l be capabl e of t r ansmi t t i ng al ar ms dur i ng t hat per i od. The capaci t y f or bat t er y- onl y power ed t r ansmi t t er s shal l be 6 mont hs bef or e r echar gi ng i s necessar y.

2. 4. 2. 3 Bat t er y Super vi s i on

Each r adi o f i r e al ar m t r ansmi t t er shal l const ant l y moni t or and super vi se i t s own bat t er y power ed suppl y. A l ow- bat t er y condi t i on shal l be r epor t ed when bat t er y vol t age f al l s bel ow 85 per cent of t he r at ed vol t age.

Apr i l 2019 Page 4 SECTI ON 28 31 33. 00 10

2. 4. 3 Funct i onal Requi r ement s

2. 4. 3. 1 I nt er f aci ng I ndi cat or s and Cont r ol s

Tr ansmi t t er s shal l i ncor por at e t he pr ovi s i ons f or auxi l i ar y i nt er connect i on t o exi st i ng i nt er i or al ar m syst ems.

2. 4. 3. 2 Gener at i on of Si gnal s

Each t r ansmi t t er shal l be a st andar d desi gn whi ch al l ows t he i mmedi at e t r ansmi ssi on of al l i ni t i at ed si gnal s.

2. 4. 3. 3 Power Out put

The r adi o f r equency ( RF) power out put of each t r ansmi t t er shal l be suf f i c i ent f or r el i abl e al ar m r epor t i ng. The mi ni mum RF power out put shal l be 1 wat t .

2. 4. 3. 4 Memory

Tr ansmi t t er s shal l have memor y capabi l i t y . Mul t i pl e, s i mul t aneous al ar ms shal l not r esul t i n t he l oss of any messages. Messages shal l be st or ed unt i l t hey ar e t r ansmi t t ed.

2. 4. 3. 5 Tr ansmi ssi on Conf i r mat i on

When a s i gnal i s i ni t i at ed at a publ i c box ( push but t on or pul l l ever ) , t he t r ansmi t t er shal l pr oduce an audi bl e or v i sual i ndi cat i on t hat t he t r ansmi t t er i s oper at i ng and t hat a s i gnal i s bei ng sent .

2. 4. 3. 6 Tr ansmi t t er I dent i t y Code

Each t r ansmi t t er shal l t r ansmi t a di st i nct i dent i t y code number as par t of al l s i gnal s emanat i ng f r om t he t r ansmi t t er . The i dent i t y code shal l al l ow f or no l ess t han a 4 di gi t code sel ect i on and be t r ansmi t t ed not l ess t han t hr ee compl et e r ounds ( cycl es) .

2. 4. 3. 7 Message Desi gnat i ons

Each t r ansmi t t er shal l al l ow as a mi ni mum no l ess t han 10 di st i nct and i ndi v i dual l y i dent i f i abl e message desi gnat i ons as t o t he t ypes or causes of t r ansmi t t er act uat i on.

2. 4. 3. 7. 1 Mast er Message

Mast er messages shal l be t r ansmi t t ed upon aut omat i c act uat i on of t he t r ansmi t t er . The bui l di ng and zone causi ng act uat i on shal l be i ndi v i dual l y i dent i f i ed as par t of t hi s t r ansmi ssi on. The t r ansmi t t er shal l be capabl e of i dent i f y i ng and t r ansmi t t i ng a mi ni mum of 4 mast er ( zone) messages.

2. 4. 3. 7. 2 Test Message

Test message shal l be capabl e of bot h manual and aut omat i c act uat i on.

When a t r anscei ver met hod i s empl oyed, i t shal l pr ovi de f or aut omat i c i nt er r ogat i on at pr esel ect ed per i ods or cont i nuous aut omat i c i nt er r ogat i on i n accor dance wi t h t he gover ni ng st andar d. Addi t i onal l y, t r anscei ver syst ems shal l pr ovi de f or sel ect i ve i nt er r ogat i on at t i mes det er mi ned by t he user . Test i ng t he aut omat i c t est act uat i on shal l occur a mi ni mum of

Apr i l 2019 Page 5 SECTI ON 28 31 33. 00 10 once i n each 24- hour per i od, at an opt i onal l y pr esel ect ed t i me. St abi l i t y of t he el ect r oni c act uat i ng devi ce shal l be pl us or mi nus 1 mi nut e per mont h wi t hi n t he t emper at ur e r ange st i pul at ed f or syst em oper at i on.

Act uat i on of t he " Test " message desi gnat i on, r egar dl ess of i ni t i at i ng means, shal l cause no l ess t han 1 compl et e message t o be sent .

2. 4. 3. 7. 3 Tamper Message Desi gnat i on

The t amper message shal l be aut omat i cal l y t r ansmi t t ed when a t amper swi t ch i s t r i pped i n t he t r ansmi t t er housi ng.

2. 4. 3. 7. 4 Tr oubl e Message Desi gnat i on

Tr oubl e message shal l be aut omat i cal l y t r ansmi t t ed i n t he event of a f ai l ur e i n excess of 1 mi nut e of t he mai n oper at i ng power sour ce of t he transmitter.

2. 4. 4 Tr ansmi t t er Housi ngs

The housi ngs on t r ansmi t t er s shal l be f abr i cat ed f r om cor r osi on- r esi st ant cast met al or sui t abl e subst i t ut e whi ch has t he physi cal st r engt h suf f i c i ent t o war d of f physi cal damage nor mal l y expect ed t o be r ecei ved by vandal i sm. The housi ng shal l be seal ed agai nst t he ent r y of moi st ur e, dust , di r t , i nsect s, and ot her f or ei gn obj ect s. Ext er i or housi ngs shal l be NEMA 4X.

2. 4. 4. 1 Lock

I nt er nal component s shal l be pr ot ect ed f r om vandal i sm by a t amper - pr oof l ock on t he t r ansmi t t er housi ng. The housi ng shal l al l ow access t o al l i nt er nal component s f or t est i ng, ser vi c i ng, and r epl acement at t he i nst al l at i on s i t e.

2. 4. 4. 2 Mounting

Tr ansmi t t er housi ngs shal l be desi gned f or uni ver sal mount i ng on wal l s, pol es, or pedest al s. Mount i ng shal l ut i l i ze ei t her l ag bol t s, anchor bol t s, st ai nl ess st eel bandi ng, mount i ng br acket s, or a shackl e/ bol t combi nat i on, as appl i cabl e t o t he speci f i c i nst al l at i on.

2. 4. 4. 3 Oper at i ng Panel

Each publ i c l y accessi bl e t r ansmi t t er shal l have an oper at i ng panel t hat i ncor por at es a dedi cat ed si gnal i ni t i at i ng devi ce ( pul l hook or push but t on) c l ear l y i dent i f i ed f or t he i ni t i at i on of " FI RE" s i gnal s. The devi ce shal l be pr ot ect ed wi t h a convent i onal spr i ng- l oaded, " f ast - act i on" br eak- gl ass, or s i mi l ar pul l - t ype door t hat al l ows obser vat i on of t he act uat i on devi ce when i n t he c l osed posi t i on. The door shal l be f abr i cat ed and f i ni shed i n a manner consi st ent wi t h t hat r equi r ed of t he mai n housi ng.

2. 4. 4. 4 Labeling

Each publ i c l y accessi bl e t r ansmi t t er shal l be l abel ed on bot h s i des and on t he f r ont sur f ace wi t h t he wor d " FI RE. " The l abel shal l be whi t e wi t h r ed lettering.

Apr i l 2019 Page 6 SECTI ON 28 31 33. 00 10

2. 4. 5 Envi r onment al Oper at i ng Requi r ement s

The t r ansmi t t er shal l be desi gned f or r el i abl e out si de oper at i on i n an ambi ent t emper at ur e r ange of - 22 t o 140 degr ees F. Tr ansmi t t er s shal l be cor r osi on- r esi st ant and desi gned f or r el i abl e oper at i on under adver se cl i mat i c condi t i ons i ncl udi ng 100 mph wi nds, i ce, r ai n, and snow st or ms.

2. 4. 6 Painting

Radi o f i r e al ar m t r ansmi t t er and i nt er f ace housi ngs shal l be f act or y pai nt ed. The f i ni sh col or shal l be f i r e engi ne r ed. Pai nt ed sur f aces damaged dur i ng i nst al l at i on shal l be r epai nt ed t o mat ch exi st i ng pai nt .

2. 5 RADI O TRANSMI TTER I NTERFACE DEVI CE

The i nt er f ace devi ce shal l pr ovi de a means of conver t i ng t he s i gnal s t hat ar e avai l abl e f r om t he l ocal cont r ol equi pment i nt o a f or m t hat i s compat i bl e wi t h t he t r ansmi t t er i nput s, whi l e st i l l mai nt ai ni ng el ect r i cal super vi s i on of t he ent i r e syst em. I nt er f ace devi ces shal l be ut i l i zed when di r ect connect i on bet ween l ocal cont r ol equi pment and t he t r ansmi t t er i s not possi bl e. I nt er f ace devi ces shal l be compl et el y assembl ed, wi r ed, t est ed at t he f act or y, and del i ver ed r eady f or i nst al l at i on and oper at i on.

2. 5. 1 Enclosure

When f ur ni shed as an i ndependent sel f - cont ai ned devi ce, t he i nt er f ace devi ce shal l be i ncor por at ed i nt o an encl osur e conf or mi ng t o NEMA I CS 1or ot her nat i onal st andar d as r equi r ed by i t s l ocat i on.

2. 5. 2 Indicators

I ndi cat or s shal l be pr ovi ded t o i ndi cat e al ar m and t r oubl e condi t i ons and shal l consi st of a r ed f i r e al ar m and an amber t r oubl e l i ght . The i ndi cat or s shal l be desi gned t o ensur e v i s i bi l i t y dur i ng dayl i ght hour s and t o i ndi cat e t he r epor t i ng zone.

2. 5. 3 Access

Swi t ches and ot her cont r ol s shal l not be accessi bl e wi t hout t he use of a key. Access t o cont r ol s shal l be by unl ocki ng and openi ng a panel or door .

2. 5. 4 Mounting

I nt er f ace housi ngs shal l be desi gned f or uni ver sal mount i ng on wal l s, pol es, or pedest al s. Mount i ng shal l ut i l i ze ei t her l ag bol t s, anchor bol t s, st ai nl ess st eel bandi ng, mount i ng br acket s, or a shackl e/ bol t combi nat i on, as appl i cabl e t o t he speci f i c i nst al l at i on.

2. 5. 5 Inputs/Outputs

Each i nt er f ace panel shal l pr ovi de, as a mi ni mum, t he number of al ar m ci r cui t i nput s and out put s i ndi cat ed. Each i nput c i r cui t shal l be ar r anged so t hat t he al ar m si gnal s shal l over r i de t he t r oubl e s i gnal s.

2. 6 RADI O FI RE ALARM MONI TORI NG BASE STATI ON

2. 6. 1 Recei ver ( Tr anscei ver ) Syst em

One mast er r adi o f i r e al ar m r ecei v i ng ( t r anscei ver ) syst em compat i bl e wi t h

Apr i l 2019 Page 7 SECTI ON 28 31 33. 00 10 t r ansmi t t er f r equency shal l be pr ovi ded. The syst em shal l be compl et el y assembl ed, wi r ed, t est ed at t he f act or y, and del i ver ed r eady f or i nst al l at i on and oper at i on. Tr anscei ver s shal l be sol i d- st at e desi gn and shal l use f r equency modul at i on. The t r anscei ver can be a s i ngl e i nt egr at ed uni t , or i t may consi st of separ at e t r ansmi t t er and r ecei ver modul es wi t h a common power suppl y, ampl i f i er , and cont r ol uni t .

2. 6. 1. 1 Tr ansmi t t er Sect i on

Tr ansmi t t er shal l oper at e on a f r equency of 142. 850 MHz. Fr equency st abi l i t y shal l be wi t hi n 0. 00025 per cent over t he oper at i ng t emper at ur e r ange. Tr ansmi t t er shal l be desi gned t o wor k i nt o a 50- ohm l oad.

Fr equency devi at i on shal l be l ess t han or equal t o 5 kHz. Audi o r esponse shal l be wi t hi n pl us 1 dB and mi nus 3 dB over t he 300 Hz t o 3, 000 Hz r ange.

2. 6. 1. 2 Recei ver Sect i on

Recei ver ant enna i nput i mpedance shal l be 50 ohms. Recei ver shal l be t uned t o a f r equency assi gnment as speci f i ed. Recei ver shal l have no mor e t han 5 per cent audi o di st or t i on measur ed at 1, 000 Hz. Recei ver shal l have a noi se l evel not gr eat er t han mi nus 50 dB bel ow t he si gnal l evel .

Recei ver out put shal l be compat i bl e wi t h t he associ at ed devi ce.

2. 6. 2 Fi r e Al ar m Consol e

Consol e shal l cont ai n a compl et e and i ndependent f i r e al ar m r ecei v i ng syst em, consi st i ng of , as a mi ni mum, a r adi o r ecei ver / t r ansmi t t er , s i gnal t o message decoder , audi o al ar m si gnal i ng devi ces, audi o al ar m si l ence swi t ch, v i sual di spl ay, al ar m r eset swi t ch( es) , al ar m r ecor di ng pr i nt er , pr i mar y and emer gency power suppl i es, power suppl y moni t or s, memor y devi ces, and al l necessar y i nt er connect i ng cabl es.

2. 6. 2. 1 Audi bl e Fi r e Al ar m

The audi bl e al ar m si gnal i ng devi ces used t o i ndi cat e t he r ecei pt of f i r e al ar m messages shal l pr oduce a uni que sound. The devi ce shal l be i nt er nal l y mount ed i n t he consol e and shal l be act i vat ed upon r ecei pt of al l f i r e al ar m si gnal s. The audi bl e devi ces used t o i ndi cat e t he r ecei pt of t r ansmi t t er / i nt er f ace t r oubl e messages, i ncl udi ng t amper and l ow- bat t er y vol t age, shal l be separ at e and di st i nct f r om t he devi ce used t o denot e r ecei pt of f i r e al ar m messages.

2. 6. 2. 2 Vi sual Di spl ay

Consol e di spl ay shal l i ndi cat e, as a mi ni mum, t he or i gi nat i ng t r ansmi t t er i dent i t y code number and shal l i ncl ude t he f ol l owi ng message desi gnat i ons:

a. Fi r e

b. Tr oubl e

c. Bat t er y

d. Test

e. Tamper f . Mast er Zone, as speci f i ed

2. 6. 2. 3 Consol e Memor y

Consol e shal l have a memor y buf f er capabl e of r et ai ni ng a mi ni mum of 500 t r ansmi t t er codes, t oget her wi t h t he speci f i c message desi gnat i ons associ at ed wi t h each t r ansmi t t er . The syst em shal l r ej ect any r ecei ved

Apr i l 2019 Page 8 SECTI ON 28 31 33. 00 10 message not mat chi ng t he pr ogr ammed t r ansmi t t er codes wher e such message i dent i f i cat i on code i s not st or ed i n t he syst em. Upon command, t he consol e shal l di spl ay and pr i nt a summar y of t r ansmi t t er s whi ch have t r ansmi t t ed a l ow- bat t er y or t r oubl e message, or f ai l ed t o t r ansmi t a message dur i ng t he pr evi ous 24- hour t est per i od. Any i ncomi ng t r ansmi t t er s i gnal shal l pr e- empt t he command di spl ay and pr i nt out f unct i on, and be pr ocessed, di spl ayed, and pr i nt ed. The 24- hour memor y shal l not be pur ged and shal l al ways be cur r ent and avai l abl e. Tr ansmi t t er memor y dat a shal l not be l ost i n t he event of a t ot al l oss of oper at i ng or emer gency power supplies.

2. 6. 2. 4 Consol e Super vi s i on

The super vi sor y syst em shal l pr ovi de const ant super vi s i on of t he oper at i ng condi t i ons of t he consol e. I ndi cat or s shal l be pr ovi ded f or each maj or component , and an audi bl e s i gnal shal l be pr oduced i n t he event of f ai l ur e of any maj or component . A swi t ch shal l be pr ovi ded t o s i l ence t he audi bl e t r oubl e s i gnal .

2. 6. 2. 5 Recei ver Super vi s i on

The super vi sor y syst em shal l pr ovi de const ant super vi s i on and di spl ay of t he oper at i ng condi t i on of t he r adi o r ecei ver s, and shal l i ndi cat e an abnor mal condi t i on when a r adi o f i r e al ar m t r ansmi t t er car r i er l ast i ng mor e t han 15 seconds i s det ect ed. The r ecei ver ' s abi l i t y t o pr oper l y r ecei ve and decode an i ncomi ng si gnal shal l be t est ed at l east once ever y 10 mi nut es.

2. 6. 2. 6 Manual Bat t er y Test

Consol e shal l have a swi t ch t o manual l y pl ace t he consol e on emer gency bat t er y power f or t est pur poses.

2. 6. 2. 7 El ect r i cal Connect i ons

Consol e shal l be desi gned wi t h modul ar component s t o al l ow i nt er change of component s f or mai nt enance pur poses. Pr i mar y power cabl es shal l i ncor por at e posi t i ve t wi st - l ock connect i ons. I nt er connect i ng cabl es and connect or s shal l be compat i bl e wi t h comput er qual i t y s i gnal dat a transmission.

2. 6. 3 Ant enna Syst em

The ant enna syst em shal l ut i l i ze ver t i cal pol ar i zat i on ant ennas, communi cat i on l i nks bet ween t r ansmi t t er s/ r ecei ver s and ant ennas, and mat chi ng net wor ks as needed f or t he pr oper cover age. The ant enna syst em shal l be ei t her omni - di r ect i onal or shaped- cover aged as sel ect ed by t he Cont r act or based on t he t opogr aphy. The ant enna syst em and cabl i ng shal l be f ur ni shed t o pr ovi de adequat e syst em gai n. The ant ennas shal l be capabl e of wi t hst andi ng t he envi r onment al condi t i ons of 125 mph wi nd and 1/ 2 i nch r adi al i ce wi t hout f ai l ur e. Li ght ni ng pr ot ect i on shal l compl y with NFPA 780. Ant enna suppor t i ng st r uct ur es shal l compl y wi t h TIA-222 .

2. 6. 3. 1 Gr oundi ng Conduct or s

Ant enna gr oundi ng conduct or s shal l be mi ni mum 32- st r and, No. 17 AWG copper .

Apr i l 2019 Page 9 SECTI ON 28 31 33. 00 10

2. 6. 3. 2 Communi cat i on Li nks

Tr ansmi ssi on l i ne bet ween t he t r ansmi t t er / r ecei ver and t he ant enna shal l be 50- ohm i mpedance r at ed f or t he t r ansmi t t er out put power . As a mi ni mum, cabl e shal l exhi bi t an at t enuat i on not exceedi ng 1. 1 dB per 100 f eet at 200 mHz.

2. 7 FI RE ALARM SYSTEM PERI PHERAL EQUI PMENT

2. 7. 1 Repeaters

Repeat er s shal l be pr ovi ded wher e i ndi cat ed or r equi r ed t o meet syst em r equi r ement s. The r epeat er shal l r ecei ve and t r ansmi t on on t he f r equency speci f i ed by t he Base Fi r e Mar shal . The r ecei ver and t r ansmi t t er sect i ons shal l conf or m t o t he r equi r ement s speci f i ed f or t r anscei ver s. Two- way dat a t r ansmi ssi on shal l be r el ayed bet ween t he base st at i on and r emot e st at i ons. Repeat er shal l ut i l i ze a bandpass- t ype dupl exer and one ant enna, or mul t i pl e- bandpass cavi t y f i l t er s and mul t i pl e ant ennas. The dupl exer or f i l t er cavi t i es shal l i sol at e t he r ecei ver f r om t r ansmi t t er spur i ous noi se and pr event r ecei ver desensi t i zat i on. The dupl exer or f i l t er cavi t i es shal l be r at ed t o handl e t he out put power of t he t r ansmi t t er . Repeat er shal l be keyed wi t h t one- encoded cont r ol c i r cui t .

A t r ansmi t t er t i me- out c i r cui t shal l be pr ovi ded t o pr event syst em l ockup.

2. 7. 2 Radi o Fi r e Al ar m Tr ansmi t t er Box Locat i on Li ght

Each i ndi cat ed t r ansmi t t er pr ovi di ng publ i c l y accessi bl e act uat i ng f unct i ons shal l be pr ovi ded wi t h a vapor - t i ght , i ncandescent t ype l i ght f i x t ur e const r uct ed of a f l ame r et ar dant , nonpl ast i c, pol ycar bonat e mat er i al wi t h a t hr eaded r uby gl obe. The l i ght shal l be suppor t ed wi t h 1/ 2 i nch gal vani zed st eel condui t and l ocat ed appr oxi mat el y 1 f oot above t he box. The l i ght shal l be pr ovi ded wi t h an i ncandescent , 50- wat t , 120- vol t ext ended ser vi ce l amp. Tr ansmi t t er s whi ch ar e power ed by bat t er y onl y shal l not be equi pped wi t h l ocat i on l i ght s.

2. 7. 3 Conduit

Condui t and f i t t i ngs shal l compl y wi t h UL 6, UL 1242, and UL 797.

2. 7. 4 Gr ound Rods

Gr ound r ods shal l be of copper - c l ad st eel conf or mi ng t o UL 467 3/ 4 i nch i n di amet er by 10 f eet i n l engt h.

2. 7. 5 Power Suppl y

The oper at i ng power f or t he syst em shal l be s i ngl e phase t aken f r om t he bui l di ng el ect r i c ser vi ce as speci f i ed i n par agr aph Power Suppl y f or t he Syst em. Emer gency backup power shal l be pr ovi ded by seal ed ni ckel - cal c i um t ype bat t er i es r equi r i ng no addi t i onal wat er . The char gi ng syst em shal l r echar ge f ul l y di schar ged bat t er i es wi t hi n 12 hour s and mai nt ai n t he bat t er i es i n t he f ul l y char ged st at e. The bat t er y shal l have t he capaci t y t o oper at e t he syst em f or not l ess t han 48 hour s under maxi mum nor mal l oad wi t h t he power suppl y t o t he char ger di sconnect ed.

2. 7. 6 Wiring

Wi r i ng shal l be i n accor dance wi t h NFPA 70 and as i ndi cat ed. St at i on wi r i ng shal l be col or coded.

Apr i l 2019 Page 10 SECTI ON 28 31 33. 00 10

PART 3 EXECUTI ON

3. 1 EXAMINATION

Af t er becomi ng f ami l i ar wi t h al l det ai l s of t he wor k, ver i f y al l di mensi ons i n t he f i el d, and advi se t he Cont r act i ng Of f i cer of any di scr epancy bef or e per f or mi ng t he wor k.

3. 2 INSTALLATION

Per f or m i nst al l at i on as shown and i n accor dance wi t h t he manuf act ur er ' s r ecommendat i ons, unl ess ot her wi se speci f i ed. Pr ovi de al l necessar y i nt er connect i ons, ser vi ces, and adj ust ment s r equi r ed f or a compl et e and oper at i onal syst em. El ect r i cal wor k shal l be i n accor dance wi t h NFPA 70.

3. 2. 1 Power Suppl y f or t he Syst em

Pr ovi de a s i ngl e dedi cat ed br anch- ci r cui t connect i on f or suppl y i ng power t o t he f i r e al ar m syst em. The backup power suppl y shal l be aut omat i cal l y ener gi zed upon f ai l ur e of t he nor mal power suppl y.

3. 2. 2 Wi r i ng f or Syst ems

Wi r i ng f or syst ems shal l be i nst al l ed i n r i gi d condui t , i nt er medi at e met al l i c condui t , or el ect r i c met al l i c t ubi ng. The conduct or s f or t he f i r e al ar m syst em shal l not be i nst al l ed i n condui t s, j unct i on boxes, or out l et boxes wi t h conduct or s of l i ght i ng and power syst ems. The sum of t he cr oss- sect i onal ar eas of i ndi v i dual conduct or s shal l not exceed 40 per cent of t he i nt er i or cr oss- sect i onal ar ea of t he condui t . Condui t shal l compl y wi t h NFPA 70. Pr ovi de ampl e gut t er space t o accommodat e necessar y wi r i ng. Submi t det ai l poi nt - t o- poi nt wi r i ng di agr am, s i gned by t he Regi st er ed Pr of essi onal Engi neer , showi ng al l poi nt s of connect i on.

Di agr am shal l i ncl ude connect i ons bet ween syst em devi ces, appl i ances, cont r ol panel s, super vi sed devi ces, an al l equi pment t hat i s act i vat ed or cont r ol l ed by t he panel .

3. 3 OVERVOLTAGE AND SURGE PROTECTI ON

Equi pment connect ed t o al t er nat i ng cur r ent c i r cui t s shal l be pr ot ect ed f r om sur ges i n accor dance wi t h I EEE C62. 41. 1, I EEE C62. 41. 2 and NFPA 70.

Cabl es and conduct or s whi ch ser ve as communi cat i ons l i nks, except f i ber opt i cs, shal l have sur ge pr ot ect i on c i r cui t s i nst al l ed at each end. Fuses shal l not be used f or sur ge pr ot ect i on.

3. 4 GROUNDING

Gr ound r ods shal l not pr ot r ude mor e t han 6 i nches above gr ade.

Noncur r ent - car r y i ng met al l i c par t s associ at ed wi t h r adi o f i r e al ar m equi pment shal l have a maxi mum r esi st ance t o sol i d " ear t h" gr ound not t o exceed 25 ohms.

3. 5 TRAINING

Conduct a t r ai ni ng cour se f or oper at i ng st af f i n t he bui l di ng wher e t he syst em i s i nst al l ed as desi gnat ed by t he Cont r act i ng Of f i cer . The t r ai ni ng per i od shal l consi st of 1 t r ai ni ng day, 8 hour s per day and shal l st ar t af t er t he syst em i s f unct i onal l y compl et ed but pr i or t o t he f i nal accept ance t est s. The f i el d i nst r uct i ons shal l cover al l of t he i t ems

Apr i l 2019 Page 11 SECTI ON 28 31 33. 00 10 cont ai ned i n t he appr oved oper at i ng and mai nt enance i nst r uct i ons.

3. 6 TESTING

Submi t t est r epor t s i n bookl et f or m showi ng f i el d t est s per f or med t o pr ove compl i ance wi t h t he speci f i ed per f or mance cr i t er i a, upon compl et i on and t est i ng of t he i nst al l ed syst em. Each t est r epor t shal l document al l r eadi ngs, t est r esul t s, and i ndi cat e t he f i nal posi t i on of cont r ol s.

Not i f y t he Cont r act i ng Of f i cer 30 days bef or e t he per f or mance and accept ance t est s ar e t o be conduct ed and submi t t he t est pr ocedur es t o be used. Submi t det ai l ed t est pr ocedur es f or t he f i r e al ar m r epor t i ng syst em 30 days pr i or t o per f or mi ng syst em t est s. The t est pr ocedur es shal l be s i gned by t he Regi st er ed Pr of essi onal Engi neer . Per f or m t he t est s i n t he pr esence of t he Cont r act i ng Of f i cer under t he super vi s i on of t he f i r e al ar m syst em manuf act ur er ' s qual i f i ed r epr esent at i ve. Fur ni sh al l i nst r ument s and per sonnel r equi r ed f or t he t est s.

3. 6. 1 Per f or mance Test i ng

Upon compl et i on of t he i nst al l at i on, t he syst em shal l be subj ect ed t o a compl et e f unct i onal and oper at i onal per f or mance t est . Test shal l det er mi ne t hat t he syst em i s f r ee f r om gr ounded, shor t ed, or open ci r cui t s. When al l cor r ect i ons have been made, t he syst em shal l be r et est ed t o assur e t hat i t i s f unct i onal . Copi es of per f or mance t est r epor t s shal l be submi t t ed i n accor dance wi t h par agr aph SUBMI TTALS.

3. 6. 2 Accept ance Test

The t est i ng shal l be i n accor dance wi t h NFPA 72. The r ecommended t est s i n NFPA 72 shal l be consi der ed mandat or y and shal l ver i f y t hat al l pr evi ous def i c i enci es have been cor r ect ed. The t est s shal l i ncl ude t he f ol l owi ng:

a. Test s t o i ndi cat e t her e ar e no gr ounded, shor t ed, or open ci r cui t s.

b. Test s of each r adi o f i r e al ar m t r ansmi t t er / r ecei ver / t r anscei ver / repeater.

c. Test s of r adi o f i r e al ar m moni t or i ng base st at i on f or al l r equi r ed functions.

d. Test s of nor mal and emer gency power suppl i es.

- - End of Sect i on - -