28 31 00.00 10.pdf
PDF 102 KB Posted
- Solicitation number
- FA813726R0030
About this file
This is a technical specification document for a fire detection and alarm system with direct current loop configuration at Tinker Air Force Base, Oklahoma, effective April 2019.
The specification requires a complete, supervised fire alarm reporting system configured in accordance with NFPA 72, with equipment that is UL listed, FM approved, or approved by a nationally recognized testing laboratory. The fire alarm control panel (FACP) shall be Fire Control Instruments (FCI) model FCI-7100 or Fire Lite, or equal, installed in a flush, surface, or semi-flush mounted steel cabinet. The system must operate on 24 Volts DC, feature a looped conduit configuration to maintain functionality if severed at any point, and include alarm initiating device circuits (IDC) Style D and notification appliance circuits (NAC) Style Z. Storage batteries must be 24 VDC sealed lead-calcium type with capacity to operate the system for 72 hours in standby mode plus 15 minutes in full alarm mode. Key components include heat detectors (combination fixed-temperature and rate-of-rise rated 135°F), smoke detectors (ionization, photoelectric, projected beam, and duct-mounted types), combination smoke and heat detectors, flame detectors, manual fire alarm stations, alarm horns (minimum 110 dBA at 10 feet), visual notification appliances with strobe flash (75 candela minimum), remote annunciators, electromagnetic door hold-open devices, and radio alarm transmitters compatible with Monaco D21 supervising station equipment using Monaco BT-XM transceiver.
The specification mandates comprehensive submittals including detail drawings signed by a Registered Professional Engineer or NICET Level 4 technician, product data, test reports, equipment certificates, operating and maintenance instructions, and spare parts data submitted three months prior to beneficial occupancy. Installation personnel must include NICET Level 4 supervision, NICET Level 2 or higher for device installation, and factory-trained technicians. Training requirements include three days of system operation instruction, two days of maintenance training, and one day of expansion and modification training. Preliminary and acceptance testing must be performed in accordance with NFPA 72 standards, with test procedures submitted 30 days in advance and test reports submitted upon completion including NFPA 72 Certificates of Completion and Inspection and Testing Forms. All work shall comply with NFPA 70 and NFPA 72, and system wiring must be solid copper installed in metallic conduit with no mixing of voltage levels or use of wire nut connectors.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Ti nker AFB, OK TAFB Techni cal Spr ci f i cat i ons 2019
SECTI ON 28 31 00. 00 10
FI RE DETECTI ON AND ALARM SYSTEM, DI RECT CURRENT LOOP
04/17
PART 1 GENERAL
1. 1 REFERENCES
The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.
ACOUSTI CAL SOCI ETY OF AMERI CA ( ASA)
ASA S3. 41 ( 2015) Audi bl e Emer gency Evacuat i on Si gnal
( ASA 96)
FM GLOBAL ( FM)
FM APP GUI DE ( updat ed on- l i ne) Appr oval Gui de http://www.approvalguide.com/
I NSTI TUTE OF ELECTRI CAL AND ELECTRONI CS ENGI NEERS ( I EEE)
I EEE C62. 41. 1 ( 2002; R 2008) Gui de on t he Sur ges Envi r onment i n Low- Vol t age ( 1000 V and Less) AC Power Ci r cui t s
I EEE C62. 41. 2 ( 2002) Recommended Pr act i ce on Char act er i zat i on of Sur ges i n Low- Vol t age ( 1000 V and Less) AC Power Ci r cui t s
NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)
NFPA 1221 ( 2013) St andar d f or t he I nst al l at i on, Mai nt enance and Use of Emer gency Ser vi ces Communi cat i ons Syst ems
NFPA 70 ( 2014; AMD 1 2013; Er r at a 1 2013; AMD 2 2013; Er r at a 2 2013; AMD 3 2014; Er r at a 3- 4 2014; AMD 4- 6 2014) Nat i onal El ect r i cal Code
NFPA 72 ( 2013) Nat i onal Fi r e Al ar m and Si gnal i ng Code
NFPA 90A ( 2015) St andar d f or t he I nst al l at i on of Ai r Condi t i oni ng and Vent i l at i ng Syst ems
U. S. NATI ONAL ARCHI VES AND RECORDS ADMI NI STRATI ON ( NARA)
47 CFR 15 Radi o Fr equency Devi ces
UNDERWRI TERS LABORATORI ES ( UL)
UL 1242 ( 2006; Repr i nt Mar 2014) St andar d f or
Apr i l 2019 Page 1 SECTI ON 28 31 00. 00 10
El ect r i cal I nt er medi at e Met al Condui t - - Steel
UL 1971 ( 2002; Repr i nt Oct 2008) Si gnal i ng Devi ces f or t he Hear i ng I mpai r ed
UL 228 ( 2006; Repr i nt Nov 2008) Door Cl oser s- Hol der s, Wi t h or Wi t hout I nt egr al Smoke Det ect or s
UL 268 ( 2016) Smoke Det ect or s f or Fi r e Al ar m Systems
UL 268A ( 2008; Repr i nt Oct 2014) Smoke Det ect or s f or Duct Appl i cat i on
UL 38 ( 2008; Repr i nt Nov 2013) Manual Si gnal i ng Boxes f or Fi r e Al ar m Syst ems
UL 464 ( 2016) St andar d f or Audi bl e Si gnal Appliances
UL 521 ( 1999; Repr i nt Apr 2015) Heat Det ect or s f or Fi r e Pr ot ect i ve Si gnal i ng Syst ems
UL 6 ( 2007; Repr i nt Nov 2014) El ect r i cal Ri gi d Met al Condui t - St eel
UL 797 ( 2007; Repr i nt Dec 2012) El ect r i cal Met al l i c Tubi ng - - St eel
UL 864 ( 2014) St andar d f or Cont r ol Uni t s and Accessor i es f or Fi r e Al ar m Syst ems
1. 2 SUBMITTALS
Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL
PROCEDURES:
SD- 02 Shop Dr awi ngs
Det ai l Dr awi ngs
SD- 03 Pr oduct Dat a
St or age Bat t er i es
Low Bat t er y Vol t age
Spar e Par t s
Techni cal Dat a and Comput er Sof t war e
Training
Testing
SD- 06 Test Repor t s
Apr i l 2019 Page 2 SECTI ON 28 31 00. 00 10
Testing
SD- 07 Cer t i f i cat es
Equipment
Qualifications
SD- 10 Oper at i on and Mai nt enance Dat a
Oper at i ng and Mai nt enance I nst r uct i ons
Techni cal Dat a and Comput er Sof t war e
1. 3 OPERATI NG AND MAI NTENANCE I NSTRUCTI ONS
a. The i nst r uct i ons shal l i ncl ude condui t l ayout , equi pment l ayout and si mpl i f i ed wi r i ng, and cont r ol di agr ams of t he syst em as i nst al l ed.
I ncl ude compl et e pr ocedur es f or syst em r evi s i on and expansi on, det ai l i ng bot h equi pment and sof t war e r equi r ement s. Pr ovi de or i gi nal and backup copi es of al l sof t war e del i ver ed f or t hi s pr oj ect , on each t ype of medi a ut i l i zed. Obt ai n appr oval of i nst r uct i ons pr i or t o training.
b. Submi t f our copi es of oper at i ng i nst r uct i ons out l i ni ng st ep- by- st ep pr ocedur es r equi r ed f or syst em st ar t up, oper at i on, and shut down. The i nst r uct i ons shal l i ncl ude t he manuf act ur er ' s name, model number , ser vi ce manual , par t s l i s t , and compl et e descr i pt i on of equi pment and t hei r basi c oper at i ng f eat ur es. Submi t f our copi es of mai nt enance i nst r uct i ons l i s t i ng r out i ne mai nt enance pr ocedur es, possi bl e br eakdowns and r epai r s, and t r oubl eshoot i ng gui de.
c. Or i gi nal and backup copi es of al l sof t war e del i ver ed f or t hi s pr oj ect shal l be pr ovi ded, on each t ype of medi a ut i l i zed.
I nst r uct i ons shal l be appr oved pr i or t o t r ai ni ng.
d. The i nst r uct i ons shal l i ncl ude compl et e pr ocedur es f or syst em r evi s i on and expansi on, det ai l i ng bot h equi pment and sof t war e requirements.
e. Copi es of oper at i ng i nst r uct i ons out l i ni ng st ep- by- st ep pr ocedur es r equi r ed f or syst em st ar t up, oper at i on, and shut down shal l be pr ovi ded as r equi r ed by t he Submi t t al Regi st er .
f . The i nst r uct i ons shal l i ncl ude t he manuf act ur er ' s name, model number , ser vi ce manual , par t s l i s t , and compl et e descr i pt i on of equi pment and t hei r basi c oper at i ng f eat ur es.
g. Copi es of mai nt enance i nst r uct i ons l i s t i ng r out i ne mai nt enance pr ocedur es, possi bl e br eakdowns and r epai r s, and t r oubl eshoot i ng gui de shal l be pr ovi ded as r equi r ed by t he Submi t t al Regi st er .
1. 4 SPECI AL TOOLS AND SPARE PARTS
Submi t spar e par t s dat a f or each di f f er ent i t em of mat er i al and equi pment speci f i ed, not l at er t han 3 mont hs pr i or t o t he dat e of benef i c i al occupancy. Dat a shal l i ncl ude a compl et e l i s t of par t s and suppl i es wi t h t he cur r ent uni t pr i ces and sour ce of suppl y and a l i s t of t he par t s
Apr i l 2019 Page 3 SECTI ON 28 31 00. 00 10 r ecommended by t he manuf act ur er t o be r epl aced af t er one year of ser vi ce.
Fur ni sh sof t war e, connect i ng cabl es and pr opr i et ar y equi pment , necessar y f or t he mai nt enance, t est i ng, and r epr ogr ammi ng of t he equi pment t o t he Cont r act i ng Of f i cer . Fur ni sh t wo spar e f uses of each t ype and si ze r equi r ed, t wo per cent of t he t ot al number of each di f f er ent t ype of det ect or , but no l ess t han t wo each. Spar e f uses shal l be mount ed i n t he f i r e al ar m panel .
1. 5 QUALI TY ASSURANCE
1. 5. 1 Qualifications
Submi t pr oof of qual i f i cat i ons f or r equi r ed per sonnel . The i nst al l er shal l submi t pr oof of exper i ence f or t he Pr of essi onal Engi neer , f i r e al ar m t echni c i an, and t he i nst al l i ng company.
1. 5. 2 Engi neer and Techni c i an
a. Regi st er ed Pr of essi onal Engi neer wi t h ver i f i cat i on of exper i ence and at l east 4 year s of cur r ent exper i ence i n t he desi gn of t he f i r e pr ot ect i on and det ect i on syst ems.
b. Nat i onal I nst i t ut e f or Cer t i f i cat i on i n Engi neer i ng Technol ogi es ( NI CET) qual i f i cat i ons as an engi neer i ng t echni c i an i n f i r e al ar m syst ems pr ogr am wi t h ver i f i cat i on of exper i ence and cur r ent NI CET certificate.
c. The Regi st er ed Pr of essi onal Engi neer may per f or m al l r equi r ed i t ems under t hi s speci f i cat i on. The NI CET Fi r e Al ar m Techni c i an shal l per f or m onl y t he i t ems al l owed by t he speci f i c cat egor y of cer t i f i cat i on hel d.
1. 5. 3 Installer
The i nst al l i ng Cont r act or shal l pr ovi de t he f ol l owi ng: NI CET Fi r e Al ar m Techni c i ans t o per f or m t he i nst al l at i on of t he syst em. A NI CET Level 4 Fi r e Al ar m Techni c i an shal l super vi se t he i nst al l at i on of t he f i r e al ar m syst em. NI CET Level 2 or hi gher Fi r e Al ar m Techni c i an shal l i nst al l and t er mi nat e f i r e al ar m devi ces, cabi net s and panel s. An el ect r i c i an or NI CET Level 1 Fi r e Al ar m Techni c i an shal l i nst al l condui t f or t he f i r e al ar m syst em. The Fi r e Al ar m t echni c i ans i nst al l i ng t he equi pment shal l be f act or y t r ai ned i n t he i nst al l at i on, adj ust ment , t est i ng, and oper at i on of t he equi pment speci f i ed her ei n and on t he dr awi ngs.
1. 5. 4 Fi r e Pr ot ect i on Engi neer
I nst al l at i ons needi ng desi gns or modi f i cat i ons of f i r e det ect i on, f i r e al ar m, or f i r e suppr essi on syst ems wi l l r equi r e t he ser vi ces and r evi ew of a qual i f i ed f i r e pr ot ect i on engi neer . For t he pur poses of meet i ng t hi s r equi r ement , a qual i f i ed f i r e pr ot ect i on engi neer i s def i ned as an i ndi v i dual meet i ng one of t he f ol l owi ng condi t i ons:
a. An engi neer havi ng a Bachel or of Sci ence or Mast er s of Sci ence Degr ee i n Fi r e Pr ot ect i on Engi neer i ng f r om an accr edi t ed uni ver si t y engi neer i ng pr ogr am, pl us a mi ni mum of 2 year s ' wor k exper i ence i n f i r e pr ot ect i on engi neer i ng.
b. A r egi st er ed pr of essi onal engi neer ( P. E. ) i n f i r e pr ot ect i on
Apr i l 2019 Page 4 SECTI ON 28 31 00. 00 10 engineering.
c. A r egi st er ed PE i n a r el at ed engi neer i ng di sci pl i ne and member gr ade st at us i n t he Nat i onal Soci et y of Fi r e Pr ot ect i on Engi neer s.
d. An engi neer wi t h a mi ni mum of 10 year s ' exper i ence i n f i r e pr ot ect i on engi neer i ng and member gr ade st at us i n t he Nat i onal Soci et y of Fi r e Pr ot ect i on Engi neer s.
1. 5. 5 Det ai l Dr awi ngs
Submi t det ai l dr awi ngs pr epar ed and si gned by a Regi st er ed Pr of essi onal Engi neer or a NI CET Level 4 Fi r e Al ar m Techni c i an, consi st i ng of a compl et e l i s t of equi pment and mat er i al , i ncl udi ng manuf act ur er ' s descr i pt i ve and t echni cal l i t er at ur e, cat al og cut s, and i nst al l at i on i nst r uct i ons. Not e t hat t he cont r act dr awi ngs show l ayout s based on t ypi cal det ect or s. Check t he l ayout based on t he act ual det ect or s t o be i nst al l ed and make any necessar y r evi s i ons i n t he det ai l dr awi ngs. The det ai l dr awi ngs shal l al so cont ai n compl et e wi r i ng and schemat i c di agr ams f or t he equi pment f ur ni shed, equi pment l ayout , and any ot her det ai l s r equi r ed t o demonst r at e t hat t he syst em has been coor di nat ed and wi l l pr oper l y f unct i on as a uni t . Det ai l ed poi nt - t o- poi nt wi r i ng di agr am shal l be pr epar ed and si gned by a Regi st er ed Pr of essi onal Engi neer or a NI CET Level 4 Fi r e Al ar m Techni c i an showi ng poi nt s of connect i on. Di agr am shal l i ncl ude connect i ons bet ween syst em devi ces, appl i ances, cont r ol panel s, super vi sed devi ces, and equi pment t hat i s act i vat ed or cont r ol l ed by t he panel.
1. 6 TECHNI CAL DATA AND COMPUTER SOFTWARE
Del i ver t echni cal dat a and comput er sof t war e ( meani ng t echni cal dat a whi ch r el at es t o comput er sof t war e) whi ch i s speci f i cal l y i dent i f i ed i n t hi s pr oj ect , and whi ch may be def i ned/ r equi r ed i n ot her speci f i cat i ons, i n accor dance wi t h t he CONTRACT CLAUSES, and i n accor dance wi t h t he Cont r act Dat a Requi r ement s Li st , DD For m 1423. I dent i f y t he dat a del i ver ed by r ef er ence t o t he par t i cul ar speci f i cat i on par agr aph agai nst whi ch i t i s f ur ni shed. Dat a t o be submi t t ed shal l i ncl ude compl et e syst em, equi pment , and sof t war e descr i pt i ons. Descr i pt i ons shal l show how t he equi pment wi l l oper at e as a syst em t o meet t he per f or mance r equi r ement s of t hi s cont r act . The dat a package shal l al so i ncl ude t he f ol l owi ng:
a. I dent i f i cat i on of pr ogr ammabl e por t i ons of syst em equi pment and capabilities.
b. Descr i pt i on of syst em r evi s i on and expansi on capabi l i t i es and met hods of i mpl ement at i on det ai l i ng bot h equi pment and sof t war e r equi r ement s.
c. Pr ovi s i on of oper at i onal sof t war e dat a on al l modes of pr ogr ammabl e por t i ons of t he f i r e al ar m and det ect i on syst em.
d. Descr i pt i on of Fi r e Al ar m Cont r ol Panel equi pment oper at i on.
e. Descr i pt i on of auxi l i ar y and r emot e equi pment oper at i ons.
f . Li br ar y of appl i cat i on sof t war e.
g. Oper at i on and mai nt enance manual s descr i bed under SD- 19 i n t he SUBMI TTALS par agr aph.
Apr i l 2019 Page 5 SECTI ON 28 31 00. 00 10
1. 7 DELI VERY, STORAGE, AND HANDLI NG
Pr ot ect equi pment del i ver ed and pl aced i n st or age wi t h pr ot ect i on f r om t he weat her , humi di t y and t emper at ur e var i at i on, di r t , dust , and any ot her contaminants.
PART 2 PRODUCTS
2. 1 SYSTEM DESCRI PTI ON
Conf i gur e t he f i r e det ect i on and al ar m syst em and t he cent r al r epor t i ng syst em i n accor dance wi t h NFPA 72; except i ons ar e accept abl e as di r ect ed by t he Cont r act i ng Of f i cer . The equi pment f ur ni shed shal l be compat i bl e and be UL l i s t ed, FM appr oved, or appr oved or l i s t ed by a nat i onal l y r ecogni zed t est i ng l abor at or y i n accor dance wi t h t he appl i cabl e NFPA st andar ds. Fur ni sh t ags wi t h st amped i dent i f i cat i on number f or keys and l ocks. Locks shal l be keyed al i ke. Pr ovi de f our keys f or t he syst em.
2. 1. 1 Operation
Pr ovi de a f i r e al ar m and det ect i on syst em t hat i s a compl et e, super vi sed f i r e al ar m r epor t i ng syst em. Act i vat e t he syst em i nt o t he al ar m mode by act uat i on of any al ar m i ni t i at i ng devi ce. Remai n i n t he al ar m mode unt i l t he i ni t i at i ng devi ce i s r eset and t he f i r e al ar m cont r ol panel i s r eset and r est or ed t o nor mal . Connect al ar m i ni t i at i ng devi ces t o i ni t i at i ng devi ce c i r cui t s ( I DC) , St y l e D, i n accor dance wi t h NFPA 72. Connect al ar m not i f i cat i on appl i ances t o not i f i cat i on appl i ance ci r cui t s ( NAC) , St y l e Z i n accor dance wi t h NFPA 72. Pr ovi de a l ooped condui t syst em so t hat i f t he condui t and al l conduct or s wi t hi n ar e sever ed at any poi nt , al l I DC, or NAC wi l l r emai n f unct i onal . The condui t l oop r equi r ement i s not appl i cabl e t o t he s i gnal t r ansmi ssi on l i nk f r om t he l ocal panel s ( at t he pr ot ect ed pr emi ses) t o t he Super vi s i ng St at i on ( f i r e st at i on, f i r e al ar m cent r al communi cat i on cent er ) . Text ual , audi bl e, and vi sual appl i ances and syst ems shal l compl y wi t h NFPA 72. Oper at e f i r e al ar m syst em component s r equi r i ng power , except f or t he cont r ol panel power suppl y, on 24 Vol t s dc.
2. 1. 2 Oper at i onal Feat ur es
The syst em shal l have t he f ol l owi ng oper at i ng f eat ur es:
a. Moni t or el ect r i cal super vi s i on of al ar m I DC and NAC. Smoke det ect or s shal l have combi ned al ar m i ni t i at i ng and power c i r cui t s.
b. Moni t or el ect r i cal super vi s i on of t he pr i mar y power ( ac) suppl y, bat t er y vol t age, pl acement of al ar m zone modul e ( car d, PC boar d) wi t hi n t he cont r ol panel , and t r ansmi t t er t r i ppi ng ci r cui t i nt egr i t y.
c. A t r oubl e buzzer and t r oubl e l i ght emi t t i ng di ode ( LED) t o act i vat e upon a s i ngl e br eak, open, or gr ound f aul t condi t i on whi ch pr event s t he r equi r ed nor mal oper at i on of t he syst em. The t r oubl e s i gnal shal l al so oper at e upon l oss of pr i mar y power ( ac) suppl y, l ow bat t er y vol t age, r emoval of al ar m zone modul e ( car d, PC boar d) , and di sconnect i on of t he c i r cui t used f or t r ansmi t t i ng al ar m si gnal s off-premises.
( 1) A t r oubl e al ar m si l ence swi t ch shal l be pr ovi ded whi ch wi l l s i l ence t he t r oubl e buzzer , but wi l l not ext i ngui sh t he t r oubl e i ndi cat or LED. Subsequent t r oubl e and super vi sor y al ar ms shal l
Apr i l 2019 Page 6 SECTI ON 28 31 00. 00 10 sound t he t r oubl e s i gnal unt i l s i l enced. Af t er t he syst em r et ur ns t o nor mal oper at i ng condi t i ons, t he t r oubl e buzzer shal l agai n sound unt i l t he s i l enci ng swi t ch r et ur ns t o nor mal posi t i on, unl ess aut omat i c t r oubl e r eset i s pr ovi ded.
( 2) Submi t vol t age dr op cal cul at i ons f or not i f i cat i on appl i ance ci r cui t s t o i ndi cat e t hat suf f i c i ent vol t age i s avai l abl e f or pr oper appl i ance oper at i on.
d. A one per son t est mode. Act i vat i ng an i ni t i at i ng devi ce i n t hi s mode wi l l act i vat e an al ar m f or a shor t per i od of t i me, t hen aut omat i cal l y r eset t he al ar m, wi t hout act i vat i ng t he t r ansmi t t er dur i ng t he ent i r e process.
e. A t r ansmi t t er di sconnect swi t ch t o al l ow t est i ng and mai nt enance of t he syst em wi t hout act i vat i ng t he t r ansmi t t er but pr ovi di ng a t r oubl e s i gnal when di sconnect ed and a r est or at i on s i gnal when r econnect ed.
f . Evacuat i on al ar m si l enci ng swi t ch whi ch, when act i vat ed, wi l l s i l ence al ar m devi ces, but wi l l not af f ect t he zone i ndi cat i ng LED/ LCD nor t he oper at i on of t he t r ansmi t t er . Thi s swi t ch shal l be over - r i dden upon act i vat i on of a subsequent al ar m f r om an unal ar med zone and t he NAC devi ces wi l l be act i vat ed.
g. El ect r i cal super vi s i on f or c i r cui t s used f or super vi sor y s i gnal ser vi ces ( i . e. , spr i nkl er syst ems, val ves, et c. ) . Super vi s i on shal l det ect any open, shor t , or gr ound.
h. Conf i r mat i on or ver i f i cat i on modul es f or smoke det ect i on i ni t i at i ng c i r cui t s. The modul es shal l i nt er r upt t he t r ansmi ssi on of an al ar m si gnal t o t he syst em cont r ol panel f or a f act or y pr eset per i od. Thi s i nt er r upt i on per i od shal l be adj ust abl e f r om 1 t o 60 seconds and be f act or y set at 20 seconds. I mmedi at el y f ol l owi ng t he i nt er r upt i on per i od, a conf i r mat i on per i od shal l be i n ef f ect dur i ng whi ch t i me an al ar m si gnal , i f pr esent , wi l l be sent i mmedi at el y t o t he cont r ol panel . Fi r e al ar m devi ces, ot her t han smoke det ect or s, wi l l be pr ohi bi t ed on ci r cui t s cont r ol l ed by conf i r mat i on or ver i f i cat i on modules.
i . The f i r e al ar m cont r ol panel shal l pr ovi de super vi sed r el ays f or HVAC shut down. An over r i de at t he HVAC panel shal l not be pr ovi ded.
j . Pr ovi de one per son t est mode - Act i vat i ng an i ni t i at i ng devi ce i n t hi s mode wi l l act i vat e an al ar m f or a shor t per i od of t i me, t hen aut omat i cal l y r eset t he al ar m, wi t hout act i vat i ng t he t r ansmi t t er dur i ng t he ent i r e pr ocess.
k. The f i r e al ar m cont r ol panel shal l pr ovi de t he r equi r ed moni t or i ng and super vi sed cont r ol out put s needed t o accompl i sh el evat or r ecal l .
l . The f i r e al ar m cont r ol panel shal l pr ovi de t he r equi r ed modul es t o moni t or and cont r ol t he f i r e spr i nkl er syst em, or ot her f i r e pr ot ect i on ext i ngui shi ng syst em.
m. Zones f or al ar m I DC and NAC shal l be ar r anged as i ndi cat ed on t he cont r act dr awi ngs.
n. The f i r e al ar m cont r ol panel shal l be r eadi l y capabl e of f ut ur e expansi on and modi f i cat i on by qual i f i ed t echni c i ans. Exampl es of
Apr i l 2019 Page 7 SECTI ON 28 31 00. 00 10 r equi r ed changes ar e: addi ng or del et i ng devi ces or zones; changi ng syst em r esponses t o par t i cul ar i nput s i gnal s; pr ogr ammi ng cer t ai n i nput s i gnal s t o act i vat e auxi l i ar y devi ces.
2. 1. 3 Al ar m Funct i ons
An al ar m condi t i on on a c i r cui t shal l aut omat i cal l y i ni t i at e t he f ol l owi ng functions:
a. Tr ansmi ssi on of s i gnal s over t he st at i on r adi o f i r e r epor t i ng syst em.
The si gnal shal l be common f or al l zones.
b. Vi sual i ndi cat i ons of t he al ar med zones on t he f i r e al ar m cont r ol panel annunci at or and on t he r emot e annunci at or , as speci f i ed.
c. Cont i nuous soundi ng or oper at i on of al ar m not i f i cat i on appl i ances t hr oughout t he bui l di ng as r equi r ed by ASA S3. 41.
d. Cl osur e of door s hel d open by el ect r omagnet i c devi ces.
e. Oper at i on of t he smoke cont r ol syst em.
f . Deact i vat i on of t he ai r handl i ng uni t s i n t he al ar med zone.
g. Shut down of power t o t he dat a pr ocessi ng equi pment i n t he al ar med zones.
h. Aut omat i c di schar ge of t he desi gnat ed f i r e suppr essi on syst ems. A 15 second maxi mum del ay shal l be pr ovi ded f or t he del uge syst em, a 30 second del ay f or t he wet pi pe syst em.
2. 1. 4 Pr i mar y Power
Pr ovi de oper at i ng power as r equi r ed by par agr aph Power Suppl y f or t he Syst em. Tr ansf er f r om nor mal t o emer gency power or r est or at i on f r om emer gency t o nor mal power shal l be f ul l y aut omat i c and not cause t r ansmi ssi on of a f al se al ar m. Loss of ac power shal l not pr event t r ansmi ssi on of a s i gnal v i a t he f i r e r epor t i ng syst em upon oper at i on of any i ni t i at i ng c i r cui t .
2. 1. 5 Bat t er y Backup Power
Bat t er y backup power shal l be t hr ough use of r echar geabl e, seal ed- t ype st or age bat t er i es and bat t er y char ger .
2. 1. 6 I nt er f ace Wi t h Exi st i ng Fi r e Al ar m Equi pment
The equi pment speci f i ed her ei n shal l oper at e as an ext ensi on t o an exi st i ng conf i gur at i on. The new equi pment shal l be connect ed t o exi st i ng moni t or i ng equi pment at t he Super vi s i ng St at i on ( Bui l di ng 117) . Exi st i ng cont r ol and moni t or i ng equi pment shal l be expanded, modi f i ed, or suppl ement ed as necessar y t o ext end t he exi st i ng cont r ol and moni t or i ng f unct i ons t o t he new poi nt s or zones. New component s shal l be capabl e of mer gi ng wi t h t he exi st i ng conf i gur at i on wi t hout degr adi ng t he per f or mance of ei t her syst em. The scope of t he accept ance t est s of par agr aph Test i ng shal l i ncl ude aspect s of oper at i on t hat i nvol ve combi ned use of bot h new and exi st i ng por t i ons of t he f i nal conf i gur at i on.
Apr i l 2019 Page 8 SECTI ON 28 31 00. 00 10
2. 1. 7 I nt er f ace Wi t h Ot her Equi pment
Fur ni sh i nt er f aci ng component s as r equi r ed t o connect t o subsyst ems or devi ces whi ch i nt er act wi t h t he f i r e al ar m syst em, such as super vi sor y or al ar m cont act s i n suppr essi on syst ems, oper at i ng i nt er f aces f or smoke cont r ol syst ems, door r el eases, et c.
2. 2 STANDARD PRODUCTS
Pr ovi de mat er i al and equi pment whi ch ar e t he st andar d pr oduct s of a manuf act ur er r egul ar l y engaged i n t he manuf act ur e of t he pr oduct s f or at l east 2 year s pr i or t o bi d openi ng. Equi pment shal l be suppor t ed by a ser vi ce or gani zat i on t hat can pr ovi de ser vi ce wi t hi n 24 hour s of notification.
2. 3 NAMEPLATES
Maj or component s of equi pment shal l have t he manuf act ur er ' s name, addr ess, t ype or st y l e, vol t age and cur r ent r at i ng, and cat al og number on a noncor r osi ve and nonheat - sensi t i ve pl at e whi ch i s secur el y at t ached t o t he equipment.
2. 4 CONTROL PANEL
Fi r e Al ar m Cont r ol panel ( FACP) shal l be " Fi r e Cont r ol I nst r ument s" ( FCI ) or equal . The pr ef er r ed FACP and devi ces shal l be FCI - 7100 or Fi r e Li t e.
FACPs shal l compl y wi t h t he appl i cabl e r equi r ement s of UL 864. Panel shal l be modul ar , i nst al l ed i n a f l ush, sur f ace, or semi - f l ush mount ed st eel cabi net wi t h hi nged door and cyl i nder l ock as speci f i ed. Cont r ol panel shal l be a c l ean, uncl ut t er ed, and or der l y assembl ed panel cont ai ni ng component s and equi pment r equi r ed t o pr ovi de t he speci f i ed oper at i ng and super vi sor y f unct i ons of t he syst em. The panel shal l have pr omi nent r i gi d pl ast i c, phenol i c or met al i dent i f i cat i on pl at es f or LEDs, zones, cont r ol s, met er s, f uses, and swi t ches.
a. Namepl at es f or f uses shal l al so i ncl ude amper e r at i ng. Separ at e al ar m and t r oubl e LEDs shal l be pr ovi ded f or each zone al ar m. These LEDs shal l be l ocat ed on t he ext er i or of t he cabi net door or be vi s i bl e t hr ough t he cabi net door . Cont r ol panel swi t ches shal l be wi t hi n t he l ocked cabi net .
b. A sui t abl e means ( s i ngl e oper at i on) shal l be pr ovi ded f or t est i ng t he cont r ol panel v i sual i ndi cat i ng devi ces ( met er s or LEDs) . Met er s and LEDs shal l be pl ai nl y v i s i bl e when t he cabi net door i s c l osed.
Si gnal s and LEDs shal l be pr ovi ded t o i ndi cat e by zone any al ar m, super vi sor y or t r oubl e condi t i on on t he syst em. Each I DC shal l be power ed and super vi sed so t hat a s i gnal on one zone does not pr event t he r ecei pt of s i gnal s f r om ot her zones.
c. Loss of power , i ncl udi ng bat t er i es, shal l not r equi r e t he r el oadi ng of a pr ogr am. Upon r est or at i on of power , st ar t up shal l be aut omat i c, and shal l not r equi r e any manual oper at i on. The l oss of pr i mar y power or t he sequence of appl y i ng pr i mar y or emer gency power shal l not af f ect t he t r ansmi ssi on of al ar m, super vi sor y or t r oubl e s i gnal s. Vi sual annunci at or s shal l be pr ovi ded f or each act i ve zone and spar e zone.
20% spar e zones shal l be pr ovi ded. Each LED shal l pr ovi de speci f i c i dent i f i cat i on of t he zone by means of a per manent l y at t ached r i gi d pl ast i c, phenol i c, or met al s i gn wi t h ei t her r ai sed or engr aved letters.
Apr i l 2019 Page 9 SECTI ON 28 31 00. 00 10
d. Zone i dent i f i cat i on shal l consi st of a wor d descr i pt i on of t he zone.
Cabi net s shal l be pr ovi ded wi t h ampl e gut t er space t o al l ow pr oper c l ear ance bet ween t he cabi net and l i ve par t s of t he panel equi pment .
I f mor e t han one modul ar uni t i s r equi r ed t o f or m a cont r ol panel , t he uni t s shal l be i nst al l ed i n a s i ngl e cabi net l ar ge enough t o accommodat e uni t s. Cabi net s shal l be pai nt ed r ed.
2. 4. 1 Remot e Syst em Tr oubl e Audi bl e/ Vi sual Appl i ance
Audi bl e appl i ance shal l have a mi ni mum sound l evel out put r at i ng of 85 dBA at 10 f eet and oper at e i n conj unct i on wi t h t he panel ' s i nt egr al t r oubl e s i gnal . The audi bl e devi ce shal l be s i l enced by t he syst em t r oubl e s i l ence swi t ch l ocat ed at t he r emot e l ocat i on, but shal l not ext i ngui sh t he vi sual i ndi cat or . Pr ovi de a r i gi d pl ast i c, phenol i c or met al i dent i f i cat i on s i gn whi ch r eads " Fi r e Al ar m Syst em Tr oubl e" at t he audi bl e appl i ance. The vi sual appl i ance l ocat ed wi t h t he audi bl e appl i ance shal l not be ext i ngui shed unt i l t he t r oubl e has been cl ear ed.
2. 4. 2 Ci r cui t Connect i ons
Connect c i r cui t conduct or s ent er i ng or l eavi ng t he panel t o scr ew- t ype t er mi nal s wi t h each conduct or and t er mi nal mar ked f or i dent i f i cat i on.
2. 4. 3 Syst em Expansi on and Modi f i cat i on Capabi l i t i es
Pr ovi de any equi pment and sof t war e needed by qual i f i ed t echni c i ans t o i mpl ement f ut ur e changes t o t he f i r e al ar m syst em as par t of t hi s cont r act .
2. 5 STORAGE BATTERI ES
2. 5. 1 Capacity
Pr ovi de st or age bat t er i es t hat ar e 24 Vdc seal ed, l ead- cal c i um t ype r equi r i ng no addi t i onal wat er wi t h ampl e capaci t y, wi t h pr i mar y power di sconnect ed, t o oper at e t he f i r e al ar m syst em f or a per i od of 72 hour s.
Fol l owi ng t hi s per i od of bat t er y oper at i on, t he bat t er i es shal l have ampl e capaci t y t o oper at e al l component s of t he syst em, i ncl udi ng al l al ar m si gnal i ng devi ces i n t he t ot al al ar m mode f or a mi ni mum per i od of 15 mi nut es. Bat t er i es shal l be pr ovi ded wi t h over - cur r ent pr ot ect i on i n accor dance wi t h NFPA 72. Submi t subst ant i at i ng bat t er y cal cul at i ons f or super vi sor y and al ar m power r equi r ement s. I ncl ude amper e- hour r equi r ement s f or each syst em component and each panel component , and t he bat t er y r echar gi ng per i od.
2. 5. 2 Placement
Locat e bat t er i es at t he bot t om of t he panel or i n a separ at e bat t er y cabi net as speci f i ed. Pr ovi de bat t er i es wi t h over cur r ent pr ot ect i on i n accor dance wi t h NFPA 72. Separ at e bat t er y cabi net s shal l have a l ockabl e, hi nged cover s i mi l ar t o t he f i r e al ar m panel . Key t he l ock t he same as t he f i r e al ar m cont r ol panel . Pai nt cabi net s t o mat ch t he f i r e al ar m cont r ol panel .
2. 6 BATTERY CHARGER
Bat t er y char ger shal l be compl et el y aut omat i c, 24 Vdc wi t h hi gh/ l ow char gi ng r at e, capabl e of r est or i ng t he bat t er i es f r om f ul l di schar ge ( 18 Vol t s dc) t o f ul l char ge wi t hi n 48 hour s. A separ at e ammet er shal l be
Apr i l 2019 Page 10 SECTI ON 28 31 00. 00 10 pr ovi ded f or i ndi cat i ng r at e of char ge. A separ at e vol t met er shal l be pr ovi ded t o i ndi cat e t he st at e of t he bat t er y char ge. A pi l ot l i ght i ndi cat i ng when bat t er i es ar e manual l y pl aced on a hi gh r at e of char ge shal l be pr ovi ded as par t of t he uni t assembl y, i f a hi gh r at e swi t ch i s pr ovi ded. Locat e char ger i n cont r ol panel cabi net or i n a separ at e bat t er y cabi net .
2. 7 MANUAL FI RE ALARM STATI ONS
Manual f i r e al ar m st at i ons shal l conf or m t o t he appl i cabl e r equi r ement s of UL 38. Connect manual st at i ons i nt o s i gnal l i ne c i r cui t s. St at i ons shal l be i nst al l ed on sur f ace, or semi - f l ush mount ed out l et boxes at 48 i nches.
St at i ons shal l be s i ngl eor doubl e act i on t ype, as speci f i ed. St at i ons shal l be f i ni shed i n r ed, wi t h r ai sed l et t er oper at i ng i nst r uct i ons of cont r ast i ng col or . St at i ons r equi r i ng t he br eaki ng of gl ass or pl ast i c panel s f or oper at i on ar e not accept abl e. St at i ons empl oyi ng gl ass r ods ar e not accept abl e. The use of a key or wr ench shal l be r equi r ed t o r eset t he st at i on. Gr avi t y or mer cur y swi t ches ar e not accept abl e. Swi t ches and cont act s shal l be r at ed f or t he vol t age and cur r ent upon whi ch t hey oper at e. St at i ons shal l have a separ at e scr ew t er mi nal f or each conduct or . Sur f ace mount ed boxes shal l be mat ched and pai nt ed t he same col or as t he f i r e al ar m manual st at i ons.
2. 8 FI RE DETECTI NG DEVI CES
Fi r e det ect i ng devi ces shal l compl y wi t h t he appl i cabl e r equi r ement s of NFPA 72, NFPA 90A, UL 268, UL 268A, and UL 521. The det ect or s shal l be pr ovi ded as i ndi cat ed. Det ect or base shal l have scr ew t er mi nal s f or maki ng connect i ons. No sol der connect i ons wi l l be al l owed. Det ect or s l ocat ed i n conceal ed l ocat i ons ( above cei l i ng, r ai sed f l oor s, et c. ) shal l have a r emot e v i s i bl e i ndi cat or LED/ LCD. I nst al l ed devi ces shal l conf or m t o t he NFPA 70 hazar d c l assi f i cat i on of t he ar ea wher e devi ces ar e t o be i nst al l ed. I f appl i cabl e, addr essabl e f i r e det ect i ng devi ces, except f l ame det ect or s, shal l be dynami cal l y super vi sed and uni quel y i dent i f i ed i n t he cont r ol panel .
2. 8. 1 Heat Det ect or s
Heat det ect or s shal l be desi gned f or det ect i on of f i r e by combi nat i on f i xed t emper at ur e and r at e- of - r i se pr i nci pl e. Heat det ect or spaci ng shal l be r at ed i n accor dance wi t h UL 521. Det ect or s l ocat ed i n ar eas subj ect t o moi st ur e, ext er i or at mospher i c condi t i ons, or hazar dous l ocat i ons as shown on dr awi ngs, shal l be t ypes appr oved f or such l ocat i ons. Heat det ect or s l ocat ed i n at t i c spaces or s i mi l ar conceal ed spaces bel ow t he r oof shal l be i nt er medi at e t emper at ur e r at ed.
2. 8. 1. 1 Combi nat i on Fi xed- Temper at ur e and Rat e- of - Ri se Det ect or s
Det ect or s shal l be desi gned f or sur f aceor semi - f l ush out l et box mount i ng and suppor t ed i ndependent l y of wi r i ng connect i ons. Cont act s shal l be sel f - r eset t i ng af t er r esponse t o r at e- of - r i se pr i nci pl e. Under f i xed t emper at ur e act uat i on, t he det ect or shal l have a per manent ext er nal i ndi cat i on whi ch i s r eadi l y v i s i bl e. Det ect or uni t s l ocat ed i n boi l er r ooms, shower s, or ot her ar eas subj ect t o abnor mal t emper at ur e changes shal l oper at e on f i xed t emper at ur e pr i nci pl e onl y. The UL 521 t est r at i ng f or t he f i xed t emper at ur e por t i on shal l be 135 degr ees F. The UL 521 t est r at i ng f or t he Rat e- of - Ri se det ect or s shal l be r at ed f or 50 by 50 f t .
Apr i l 2019 Page 11 SECTI ON 28 31 00. 00 10
2. 8. 1. 2 Rat e Compensat i ng Det ect or s
Det ect or s shal l be sur f ace or f l ush mount ed ver t i cal or hor i zont al t ype, as speci f i ed, wi t h out l et box suppor t ed i ndependent l y of wi r i ng connect i ons. Det ect or s shal l be her met i cal l y seal ed and aut omat i cal l y r eset t i ng. Rat e Compensat ed det ect or s shal l be r at ed f or 50 by 50 f t .
2. 8. 1. 3 Fi xed Temper at ur e Det ect or s
Det ect or s shal l be desi gned f or sur f ace or semi - f l ush out l et box mount i ng and suppor t ed i ndependent l y of wi r i ng connect i ons. Det ect or s shal l be desi gned t o det ect hi gh heat . The det ect or s shal l have a speci f i c t emper at ur e set t i ng of 135 degr ees F. The UL 521 t est r at i ng f or t he f i xed t emper at ur e det ect or s shal l be r at ed f or 15 by 15 f t .
2. 8. 2 Smoke Det ect or s
Smoke det ect or s shal l be desi gned f or det ect i on of abnor mal smoke densi t i es. Smoke det ect or s shal l be as speci f i ed. Det ect or s shal l cont ai n a v i s i bl e i ndi cat or LED t hat shows when t he uni t i s i n al ar m condi t i on. Det ect or s shal l not be adver sel y af f ect ed by v i br at i on or pr essur e. Det ect or s shal l be t he pl ug- i n t ype i n whi ch t he det ect or base cont ai ns t er mi nal s f or maki ng wi r i ng connect i ons. Det ect or s t hat ar e t o be i nst al l ed i n conceal ed ( above f al se cei l i ngs, et c. ) l ocat i ons shal l be pr ovi ded wi t h a r emot e i ndi cat or LED sui t abl e f or mount i ng i n a f i ni shed, v i s i bl e l ocat i on.
2. 8. 2. 1 I oni zat i on Det ect or s
I oni zat i on det ect or s wi t h a dual chamber shal l be r esponsi ve t o bot h i nvi s i bl e and vi s i bl e par t i c l es of combust i on. One chamber shal l be a r ef er ence chamber and t he second a sampl i ng chamber . Det ect or s cont ai ni ng r adi um shal l not be pr ovi ded. Det ect or s shal l not cause an al ar m condi t i on due t o ant i c i pat ed f l uct uat i ons i n r el at i ve humi di t y. The sensi t i v i t y of t he det ect or shal l be f i el d adj ust abl e t o compensat e f or oper at i ng condi t i ons. Det ect or shal l r equi r e no r epl acement or r eadj ust ment t o r est or e i t t o nor mal oper at i on af t er an al ar m condi t i on.
Each det ect or shal l be capabl e of wi t hst andi ng ambi ent ai r vel oci t y up t o 300 f pm i n accor dance wi t h UL 268. Det ect or s shal l have at l east a t wo- st age sensi t i v i t y set t i ng, wi t h det ect or s i ni t i al l y set f or nor mal sensi t i v i t y. A l ower sensi t i v i t y shal l be avai l abl e f or each det ect or .
The l ower sensi t i v i t y shal l be wi t hi n t he l i mi t s est abl i shed f or t hat det ect or by UL or FM.
2. 8. 2. 2 Phot oel ect r i c Det ect or s
Det ect or s shal l oper at e on a l i ght scat t er i ng concept usi ng an LED l i ght sour ce. Fai l ur e of t he LED shal l not cause an al ar m condi t i on. Det ect or s shal l be f act or y set f or sensi t i v i t y and shal l r equi r e no f i el d adj ust ment s of any k i nd. Det ect or s shal l have an obscur at i on r at i ng i n accor dance wi t h UL 268.
2. 8. 2. 3 Pr oj ect ed Beam Smoke Det ect or s
Det ect or s shal l be desi gned f or det ect i on of abnor mal smoke densi t i es.
Det ect or s shal l consi st of separ at e t r ansmi t t er and r ecei ver uni t s. The t r ansmi t t er uni t shal l emi t an i nf r ar ed beam t o t he r ecei ver uni t . When t he si gnal at t he r ecei ver f al l s bel ow a pr eset sensi t i v i t y, t he det ect or shal l i ni t i at e an al ar m. The r ecei ver shal l cont ai n an LED whi ch i s
Apr i l 2019 Page 12 SECTI ON 28 31 00. 00 10 power ed upon an al ar m condi t i on. Long- t er m changes t o t he r ecei ved si gnal caused by envi r onment al var i at i ons shal l be aut omat i cal l y compensat ed.
Det ect or s shal l i ncor por at e f eat ur es t o assur e t hat t hey ar e oper at i onal ;
a t r oubl e s i gnal shal l be i ni t i at ed i f t he beam i s obst r uct ed, t he l i mi t s of t he compensat i on c i r cui t ar e r eached, or t he housi ng cover i s r emoved.
Det ect or s shal l have mul t i pl e sensi t i v i t y set t i ngs i n or der t o meet UL l i s t i ngs f or t he di f f er ent di st ances cover ed by t he beam. I n t he event of beam i nt er f er ence f or mor e t han t hr ee seconds a t r oubl e al ar m shal l be transmitted.
2. 8. 2. 4 Duct Det ect or s
Duct - mount ed phot oel ect r i c smoke det ect or s shal l be f ur ni shed and i nst al l ed wher e i ndi cat ed and i n accor dance wi t h NFPA 90A. Uni t s shal l consi st of a smoke det ect or as speci f i ed i n par agr aph Phot oel ect r i c Det ect or s, mount ed i n a speci al housi ng f i t t ed wi t h duct sampl i ng t ubes.
Det ect or c i r cui t r y shal l be mount ed i n a met al l i c encl osur e ext er i or t o t he duct . Det ect or s shal l have a manual r eset . Det ect or s shal l be r at ed f or ai r vel oci t i es t hat i ncl ude ai r f l ows bet ween 500 and 4000 f pm.
Det ect or s shal l be power ed f r om t he f i r e al ar m panel . Sampl i ng t ubes shal l r un t he f ul l wi dt h of t he duct . The duct det ect or package shal l conf or m t o t he r equi r ement s of NFPA 90A, UL 268A, and shal l be UL l i s t ed f or use i n ai r - handl i ng syst ems. The cont r ol f unct i ons, oper at i on, r eset , and bypass shal l be cont r ol l ed f r om t he f i r e al ar m cont r ol panel . Li ght s t o i ndi cat e t he oper at i on and al ar m condi t i on; and t he t est and r eset but t ons shal l be v i s i bl e and accessi bl e wi t h t he uni t i nst al l ed and t he cover i n pl ace. Det ect or s mount ed above 6 f eet and t hose mount ed bel ow 6 f eet t hat cannot be easi l y accessed whi l e st andi ng on t he f l oor , shal l be pr ovi ded wi t h a r emot e det ect or i ndi cat or panel cont ai ni ng t est and r eset swi t ches. Remot e l amps and swi t ches as wel l as t he af f ect ed f an uni t s shal l be pr oper l y i dent i f i ed i n et ched pl ast i c pl acar ds. Det ect or s shal l have auxi l i ar y cont act s t o pr ovi de cont r ol , i nt er l ock, and shut down f unct i ons speci f i ed i n Sect i on 23 09 23. 01 LONWORKS DI RECT DI GI TAL CONTROL FOR HVAC AND OTHER BUI LDI NG CONTROL SYSTEMS. The det ect or s shal l be suppl i ed by t he f i r e al ar m syst em manuf act ur er t o ensur e compl et e syst em compatibility.
2. 8. 3 Combi nat i on Smoke and Heat Det ect or s
Combi nat i on smoke and heat det ect or s shal l have an audi bl e devi ce ( sel f - cont ai ned) and be desi gned f or det ect i on of abnor mal smoke densi t i es by t he phot oel ect r i c pr i nci pl e and abnor mal heat by a f i xed t emper at ur e sensor . Smoke det ect or s shal l be pr ovi ded wi t h an LED l i ght sour ce.
Fai l ur e of t he LED shal l not cause an al ar m condi t i on and t he sensi t i v i t y shal l be f act or y set at a nomi nal 3 per cent and r equi r e no f i el d adj ust ment s of any k i nd. Heat det ect or por t i on shal l be f i xed t emper at ur e sensor r at ed at 135 degr ees F. The audi bl e appl i ances shal l have a mi ni mum sound out put of at l east 85 dBA at 10 f eet . Det ect or s shal l cont ai n a v i s i bl e i ndi cat or LED t hat shows when t he uni t i s i n al ar m condi t i on. Det ect or s shal l not be adver sel y af f ect ed by v i br at i on or pr essur e. Heat det ect or s shal l connect t o a cont r ol panel I DC and shal l be non- r est or abl e or sel f r est or abl e, as speci f i ed.
2. 8. 4 Fl ame Det ect or s
The det ect or s shal l compl y wi t h FM APP GUI DE. The det ect or s shal l be sensi t i ve t o t he mi cr on r ange best sui t ed f or t hei r i nt ended use. The det ect or s shal l oper at e over el ect r i cal l y super vi sed wi r i ng c i r cui t s and t he l oss of power t o t he det ect or shal l r esul t i n a t r oubl e s i gnal . A
Apr i l 2019 Page 13 SECTI ON 28 31 00. 00 10 sel f - t est f eat ur e shal l be pr ovi ded f or each det ect or t o be i ndi v i dual l y tested.
2. 8. 4. 1 Ul t r avi ol et ( UV) Fl ame Det ect or s N/A
2. 8. 4. 2 Combi nat i on UV/ I R Fl ame Det ect or
The UV/ I R det ect or shal l pr ovi de di scr i mi nat i on agai nst f al se al ar ms by r equi r i ng bot h UV and I R f l ame det ect i on bef or e an al ar m i s sent . The UV sensor shal l be sensi t i ve i n t he r ange of 0. 185 t o 0. 265 mi cr omet er s onl y. The I R sensor shal l be sensi t i ve i n t he mi cr omet er s r ange best sui t ed f or t he i nt ended ser vi ce and must be cr oss zoned. Det ect or s shal l be compl et el y i nsensi t i ve t o l i ght sour ces i n t he v i s i bl e f r equency r ange.
2. 9 NOTI FI CATI ON APPLI ANCES
Audi bl e appl i ances shal l conf or m t o t he appl i cabl e r equi r ement s of UL 464.
Devi ces shal l be connect ed i nt o not i f i cat i on appl i ance ci r cui t s. Devi ces shal l have a separ at e scr ew t er mi nal f or each conduct or . Audi bl e appl i ances shal l gener at e a uni que audi bl e sound f r om ot her devi ces pr ovi ded i n t he bui l di ng and sur r oundi ng ar ea. Sur f ace mount ed audi bl e appl i ances shal l be pai nt ed r ed. Recessed audi bl e appl i ances shal l be i nst al l ed wi t h a gr i l l t hat i s pai nt ed r ed.
2. 9. 1 Al ar m Bel l s N/A
2. 9. 2 Al ar m Hor ns
Hor ns shal l be sur f ace mount ed, wi t h t he mat chi ng mount i ng back box as i ndi cat ed on t he cont r act dr awi ngs and vi br at i ng t ype sui t abl e f or use i n an el ect r i cal l y super vi sed ci r cui t . Hor ns shal l pr oduce a sound r at i ng of at l east 110 dBA at 10 f eet . Hor ns used i n ext er i or l ocat i ons shal l be speci f i cal l y l i s t ed or appr oved f or out door use and be pr ovi ded wi t h met al housi ng and pr ot ect i ve gr i l l es.
2. 9. 3 Chimes
Chi mes shal l be el ect r i cal l y oper at ed, super vi sed, el ect r oni c t ype, wi t h an adj ust abl e f r equency of 800 t o 1200 Her t z. Chi mes shal l have a mi ni mum sound r at i ng of 80 dBA at 10 f eet .
2. 9. 4 Vi sual Not i f i cat i on Appl i ances
Vi sual not i f i cat i on appl i ances shal l conf or m t o t he appl i cabl e r equi r ement s of UL 1971. Appl i ances shal l have cl ear hi gh i nt ensi t y opt i c l ens, xenon f l ash t ubes, and out put whi t e l i ght . St r obe f l ash r at e shal l be bet ween 1 t o 3 f l ashes per second and a mi ni mum of 75 candel a. St r obe shal l be sur f ace or semi - f l ush mount ed as speci f i ed. I n hi gh noi se ar eas, such as war ehouses or ar eas i dent i f i ed i n t he pr oj ect dr awi ngs or St at ement of Wor k, r ed r ot at i on beacons shal l be used. The candl e power out put shal l be as speci f i ed, but no l ess t han 1, 000, 000 candl e power .
2. 9. 5 Combi nat i on Audi bl e/ Vi sual Not i f i cat i on Appl i ances
Combi nat i on audi bl e/ v i sual not i f i cat i on appl i ances shal l pr ovi de t he same r equi r ement s as i ndi v i dual uni t s, except t hat t hey shal l mount as a uni t i n st andar d backboxes. Uni t s shal l be f act or y assembl ed. Any ot her
Apr i l 2019 Page 14 SECTI ON 28 31 00. 00 10 audi bl e not i f i cat i on appl i ance empl oyed i n t he f i r e al ar m syst ems shal l be appr oved by t he Cont r act i ng Of f i cer .
2. 10 REMOTE ANNUNCI ATI ON EQUI PMENT
2. 10. 1 Remot e Annunci at or
Annunci at or shal l have i ndi cat or LEDs. The LED f or t he pr oper zone shal l l i ght upon any al ar m. Pr ovi de a super vi sor y LED t o i ndi cat e a super vi sor y mal f unct i on. A syst em t r oubl e LED shal l be pr ovi ded t o i ndi cat e a syst em f ai l ur e. Annunci at or LEDs shal l be ext i ngui shed onl y by oper at i ng t he al ar m r eset swi t ch on t he cont r ol panel . Annunci at or shal l cont ai n a LED t est swi t ch, an audi bl e t r oubl e s i gnal , and a t r oubl e s i l ence swi t ch t o s i l ence t he audi bl e al ar m, but not ext i ngui sh t he t r oubl e LED. Swi t ches shal l be l ocat ed wi t hi n a l ocked panel and easi l y v i s i bl e t hr ough a gl ass or pl ast i c v i ewi ng pl at e. Panel door shal l have a keyed l ock i dent i cal t o t he l ock on t he cont r ol panel . Zone i dent i f i cat i on shal l be by s i l k- scr eened or engr aved l abel s and shal l consi st of wor d descr i pt i on of t he zone. Annunci at or shal l be sur f ace, semi - f l ush or f l ush mount ed as specified.
2. 10. 2 Remot e Gr aphi c Annunci at or
Gr aphi c annunci at or shal l have a pl an vi ew of t he bui l di ng. Each i ni t i at i ng devi ce ( i dent i cal devi ces i n t he same r oom may be combi ned, as appr oved) shal l be i ndi cat ed by an LED shown i n i t s r el at i ve posi t i on i n t he bui l di ng and shal l i l l umi nat e f or abnor mal condi t i on i n t hat ar ea.
LEDs shal l be r ed f or al ar m condi t i on, as speci f i ed f or super vi sor y mal f unct i on condi t i on, and amber f or t r oubl e condi t i on. Pl an vi ews shal l be appr oxi mat el y t o scal e and i n no case smal l er t han 12 i nches i n l engt h or wi dt h. Annunci at or shal l have a door wi t h pi ano hi nge and t wo poi nt cyl i nder l ock or t wo cyl i nder l ocks. Lock shal l be oper abl e usi ng t he same key as t he cont r ol panel . Annunci at or shal l cont ai n a LED t est swi t ch, audi bl e t r oubl e s i gnal and a t r oubl e swi t ch t o s i l ence t he audi bl e al ar m, but not ext i ngui sh t he t r oubl e LED. Annunci at or shal l be sur f ace, semi - f l ush or f l ush mount ed, as speci f i ed.
2. 11 FI RE DETECTI ON AND ALARM SYSTEM PERI PHERAL EQUI PMENT
2. 11. 1 El ect r omagnet i c Door Hol d- Open Devi ces
At t ach devi ces t o t he wal l s unl ess ot her wi se i ndi cat ed. Devi ces shal l compl y wi t h t he appr opr i at e r equi r ement s of UL 228. Devi ces shal l oper at e on 24 Vol t dc power . Compat i bl e magnet i c component shal l be at t ached t o t he door . Under nor mal condi t i ons, t he magnet s wi l l at t r act and hol d t he door s open. When magnet s ar e de- ener gi zed, t hey shal l r el ease t he door s.
Magnet s shal l have a hol di ng f or ce of 25 pounds. Devi ces shal l be UL or FM appr oved. Housi ng f or devi ces shal l be br ushed al umi num or st ai nl ess st eel . Oper at i on shal l be f ai l saf e wi t h no movi ng par t s.
El ect r omagnet i c door hol d- open devi ces shal l not be r equi r ed t o be hel d open dur i ng bui l di ng power f ai l ur e.
2. 11. 2 Conduit
Condui t and f i t t i ngs shal l compl y wi t h UL 6, UL 1242 and UL 797.
2. 11. 3 Wiring
Wi r i ng shal l conf or m t o NFPA 70. Wi r i ng f or 120 Vac power shal l be No. 12
Apr i l 2019 Page 15 SECTI ON 28 31 00. 00 10
AWG mi ni mum. Wi r i ng f or Fi r e Al ar m ci r cui t s shal l be No. 16 AWG mi ni mum.
Vol t ages shal l not be mi xed i n any j unct i on box, housi ng, or devi ce, except t hose cont ai ni ng power suppl i es and cont r ol r el ays. Wi r i ng shal l conf or m t o NFPA 70. Syst em f i el d wi r i ng shal l be sol i d copper and i nst al l ed i n met al l i c condui t or el ect r i cal met al l i c t ubi ng, except r i gi d pl ast i c condui t may be used under s l ab- on- gr ade. Conduct or s shal l be col or coded. Conduct or s used f or t he same f unct i ons shal l be s i mi l ar l y col or coded. Wi r i ng code col or shal l r emai n uni f or m t hr oughout t he c i r cui t . Pi gt ai l or T- t ap connect i ons t o i ni t i at i ng devi ce c i r cui t s, super vi sor y al ar m ci r cui t s, and not i f i cat i on appl i ance ci r cui t s ar e prohibited.
2. 12 TRANSMITTERS
2. 12. 1 Radi o Al ar m Tr ansmi t t er s
Tr ansmi t t er s shal l be compat i bl e wi t h pr opr i et ar y super vi s i ng st at i on r ecei v i ng equi pment . Each r adi o al ar m t r ansmi t t er shal l be t he manuf act ur er ' s r ecogni zed commer ci al pr oduct , compl et el y assembl ed, wi r ed, f act or y t est ed, and del i ver ed r eady f or i nst al l at i on and oper at i on.
Tr ansmi t t er s shal l be pr ovi ded i n accor dance wi t h appl i cabl e por t i ons of NFPA 72, NFPA 1221, and 47 CFR 15. Tr ansmi t t er el ect r oni cs modul e shal l be cont ai ned wi t hi n t he physi cal housi ng as an i nt egr al , r emovabl e assembl y. The pr opr i et ar y super vi s i ng st at i on r ecei v i ng equi pment i s Monanco D21 and t he t r anscei ver shal l be Monaco BT- XM. At t he Cont r act or ' s opt i on, and i f UL l i s t ed, t he t r ansmi t t er may be housed i n t he same panel as t he f i r e al ar m cont r ol panel .
2. 12. 1. 1 Tr ansmi t t er Power Suppl y
Each r adi o al ar m t r ansmi t t er shal l be power ed by a combi nat i on of l ocal l y avai l abl e 120- vol t ac power and a seal ed, l ead- cal c i um bat t er y.
2. 12. 1. 1. 1 Operation
Oper at e each t r ansmi t t er f r om 120- vol t ac power . I n t he event of 120- vol t ac power l oss, t he t r ansmi t t er shal l…