9b. A1 2 UST Equipment Data_Amend 0001.pdf
PDF 161 KB Posted
- Solicitation number
- FA520920Q017A
About this file
This solicitation is for inspection, maintenance, and repair services for underground storage tanks and auxiliary equipment located at Camp Zama, Sagamihara Family Housing Area, and Akasaka Press Center in Japan. The contractor shall provide all necessary personnel, tools, equipment, materials, and services to perform work on underground tanks storing gasoline, waste oil, JP8 fuel, and FJ1 fuel. Key requirements include inspection and maintenance of tanks, pipes, spill containment, leak detection systems, gauges, pumps, and vapor recovery devices. The work must be performed by an offeror licensed and registered to work in Japan. The pricing schedule and labor rates are in separate Excel attachments. This is a local set-aside opportunity for the Department of the Air Force Pacific Air Forces.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A.1.2. List of USTs and Auxiliary Equipments
<<Camp Zama and SFHA Areas>>
Tank No. Installation Type of
Stored Oil Tank Cap.
Gallon
Installed Date Tank Pipe
Spill Containment
Box Automatic Shut‐
Off Device High Level Alarm Tank Pipe Fuel Truck Grounding
Automatic Tank Gauge Automatic Control System for Transfer Pump Transfer Pump Manual Valve
Check Valve
Fuel Strainer
Water Separator
380‐1N Camp Zama Gasoline 8,000 Jul 2017
Polyuretha ne Tank Coating
Polyethylene Pipe UL971
SUMP
BOX
708‐590 Series
Overfill
Prevention Valve
(Franklin Fueling
Systems)
Magnetostrictive Probe TSP‐LL2 Display TS‐550
EVO
(Franklin Fueling
Systems)
Active Sensor TSP‐ULS
Monitor TS‐550 EVO (Franklin Fueling Systems)
Active Sensor TSP‐ULS
Monitor TS‐550 EVO (Franklin Fueling Systems)
O Magnetostrictive Probe TSP‐LL2
Display TS‐550 EVO (Franklin Fueling
Systems)
/ / 80Ax1 40Ax1 / /
380‐2N Camp Zama Gasoline 8,000 Jul 2017
Coating
Polyethylene Pipe UL971
SUMP
BOX
708‐590 Series
Overfill
Prevention Valve
(Franklin Fueling
Systems)
Magnetostrictive Probe TSP‐LL2 Display TS‐550
EVO
(Franklin Fueling
Systems)
Active Sensor TSP‐ULS
Monitor TS‐550 EVO (Franklin Fueling Systems)
Active Sensor TSP‐ULS
Monitor TS‐550 EVO (Franklin Fueling Systems)
O Magnetostrictive Probe TSP‐LL2
Display TS‐550 EVO (Franklin Fueling
Systems)
/ / 80Ax1 40Ax1 / /
381‐N Camp Zama Waste Oil 822 Oct 2018
Coating
Polyethylene Pipe UL971
SUMP
BOX
Magnetostrictive Probe TSP‐LL2 Display TS‐550
EVO
(Franklin Fueling
Systems)
Active Sensor TSP‐ULS
Monitor TS‐550 EVO (Franklin Fueling Systems)
Active Sensor TSP‐ULS
Monitor TS‐550 EVO (Franklin Fueling Systems)
O Magnetostrictive Probe TSP‐LL2
Display TS‐550 EVO (Franklin Fueling
Systems)
/ / 50Ax1 / / /
534‐N Camp Zama FJ‐1 1,585 Jan 2011
FRP
Outside Wall
Exposed Pipe in Trench O Unknown
Gage: ELM‐201 Display DL‐915 Display DL‐535 (Koh‐Giken Co.)
Active Sensor LKT‐NS211‐10L
Monitor LK‐111 (Koh‐Giken Co.)
N/A O Sensor: ELM‐201 Display DL‐535 (Koh‐Giken Co.)
An earthquake detection device (V‐725) , Controller(SL42, KOHGIKEN), Float Switch (FS‐SS442N,KOHGIKEN), Model: TOP‐2MY400‐HBMVB,CAP:
6l/min, 0.4kw,200V, Size: 15Ax15A, Nippon Oil Pump Co. x 1
25A x 4 25Ax1 Type‐T 25A
OS‐25W‐N
2520 x 940 x 1550 H
1021‐N Camp Zama JP‐8 14,250 May 1987 Sacrificial Anode
Unknown O Unknown
Active Sensor LKL
Monitor LKM‐512‐12 (Koh‐Giken Co.)
/ O 918 DP Clock Gauge 918 AC Interface
(MORRISON BROS.
Co.)
Model: 80x65FSS2G55.5, CAP: 700l/min, 5.5kw,200V, Size: 80Ax65A, EBARA
(S) 100Ax4 20Ax3 15Ax3 10Ax2
OCV CAPITAL VALVE
100Ax1 Safety Valve (SL‐
10ED VENN)
100Ax1 Type‐Y 20Ax1 100Ax2
Wako Industrial
VFCS‐12N15‐
658FJ
112‐1N SFHA Gasoline 6,000 Sep 1992 Sacrificial Anode
Unknown O Unknown Active
TTA‐SIM
(Tyco Thermal Controls Co.)
Active
TTA‐SIM
(Tyco Thermal Controls Co.)
O C89‐LCT‐M85
(Safety Gauge Co.) / / / 1 / /
112‐2N SFHA Gasoline 6,000 May 1990 Sacrificial Anode
Unknown O Unknown Active
TTA‐SIM
(Tyco Thermal Controls Co.)
Active
TTA‐SIM
(Tyco Thermal Controls Co.)
O C89‐LCT‐M85
(Safety Gauge Co.) / / / 1 / /
130‐01‐1N SFHA FJ‐1 1,058 Mar 2013
FRP
Outside Wall
Exposed Pipe in Trench O OPW61S03
(Koh‐Giken Co.)
Gage: ELM Display DL‐915 Display DL‐535 (Koh‐Giken Co.)
Active Sensor LKT‐NS211‐10L
Monitor LK‐111 (Koh‐Giken Co.)
N/A O Gage: ELM Display DL‐915 Display DL‐535 (Koh‐Giken Co.)
An earthquake detection device (V‐725) , Level Controller (Safety Elcon, SL‐401), Float Switch (FS‐SS444N)
Model: GPLII‐10V,CAP: 3l/min, Head:
3M, 0.2kw,200V, TERAL
(S) 25Ax2 32A x 1
(R) 25Ax1 25Ax1
Type‐T
KW‐1
25A
VENN
3 Tanks 630 mm□ x 750 mmH x 3 tanks
A1.2‐1
Corrosion Protection Spill/Overfill Protection Leak Detection System Other Auxiliary Systems
Symbol Legend: O = Equipped and/or Installed, /= Not Equipped and/or Not Installed, Empty cell = Unknown
A.1.2‐1
<<Akasaka Press Center Areas>>
Tank No. Installation Type of
Stored Oil Tank Cap.
Gallon
Installed Date Tank Pipe
Spill Containment
Box Automatic Shut‐
Off Device High Level Alarm Tank Pipe Fuel Truck Grounding
Automatic Tank Gauge Vapor Recovery Device Transfer Pump Manual Valve
Check Valve
Fuel Strainer
Water Separator
8‐H4‐1N APC Gasoline 1,980 Apr 2010
Not Required FRP Tank
Polyethylene Coating Pipe
O
Unknown
MS‐RD
(Showa‐Kiki
Kogyo)
Active Sensor OLM‐S Monitor OLM‐
MT2
(Showa‐Kiki
Kogyo)
/ O MS‐RD
(Showa‐Kiki Kogyo)
Device VR‐ST (50A) Hose VR‐HCNS (50A x 10m)
(Showa‐Kiki Kogyo) / / 1 / /
8‐H4‐2N APC Gasoline 1,980 Apr 2010
Not Required FRP Tank
Polyethylene Coating Pipe
O
Unknown
MS‐RD
(Showa‐Kiki
Kogyo)
Active Sensor OLM‐S Monitor OLM‐
MT2
(Showa‐Kiki
Kogyo)
/ O MS‐RD
(Showa‐Kiki Kogyo)
Device VR‐ST (50A) Hose VR‐HCNS (50A x 10m)
(Showa‐Kiki Kogyo) / / 1 / /
A1.2‐2
Corrosion Protection Spill/Overfill Protection Leak Detection System Other Auxiliary Systems
Symbol Legend: O = Equipped and/or Installed, /= Not Equipped and/or Not Installed, Empty cell = Unknown
File details come from the government source that posted it. Updated .